E N T R A N C E S P E C B O O K

OUR OUR MISSION MISSION

through professionally trained employees providing

SERVICE ENTRANCE SPECIFICATION BOOK TABLE OF CONTENTS MISSION STATEMENT............................................................................................3 BOARD OF DIRECTORS..........................................................................................3 OFFICE HOURS .....................................................................................................4 SERVICE ENTRANCE SPECIFICATIONS—GENERAL NOTES....................................5 PERMANENT OVERHEAD SERVICE - METER POLE............................................. 6-7 TEMPORARY OVERHEAD SERVICE - METER POLE............................................. 8-9 TEMPORARY UNDERGROUND SERVICE - METER POLE.................................. 10-11 PERMANENT OVERHEAD SERVICE - THRU ROOF (ROOF JACK)...................... 12-13 PERMANENT OVERHEAD SERVICE - WALL MOUNTED.................................... 14-15 PERMANENT UNDERGROUND SERVICE - WALL MOUNTED............................ 16-17 PERMANENT UNDERGROUND SERVICE TO MOBILE HOME METER POLE....... 18-19 UNDERGROUND SERVICE............................................................................... 20-21 PARISH PERMITS........................................................................................... 22-23

safe, reliable and affordable electricity as well as other high quality products and services. As a good corporate citizen, DEMCO is committed to stimulating the economic growth and prosperity of our area through ethical conduct and sound business principles.

www.demco.org

BOARD OF DIRECTORS Richard W. Sitman President DISTRICT 10 St. Helena Parish

Steve Irving

Vice-President DISTRICT 4 East Baton Rouge Parish

Dennis Lott

Secretary/Treasurer DISTRICT 8 Livingston Parish 24-Hour Outage & Emergency Service

(225) 261-1160 / 1-800-262-1160 2

DEMCO exists to serve the members/customers

Clarence Brock DISTRICT 1 Ascension Parish

Ann Samuel

Daniel P. Berthelot

Randy Lorio

Joseph Self, Sr.

Alice Faye Morris

Eugene O. Traylor

Glenn DeLee

Freddy Metz

DISTRICT 2 East Baton Rouge Parish DISTRICT 3 East Baton Rouge Parish DISTRICT 5 East Feliciana Parish DISTRICT 6 East Feliciana Parish

Leslie Falks

DISTRICT 7 Livingston Parish 3

DISTRICT 9 Livingston Parish

DISTRICT 11 St. Helena Parish

DISTRICT 12 Tangipahoa Parish

DISTRICT 13 West Feliciana Parish

SERVICE ENTRANCE SPECIFICATIONS

OFFICE HOURS

GENERAL NOTES

Monday through Friday

1. All service entrances must meet the minimum requirements before being connected by DEMCO.

LOCATION

ADDRESS

PHONE

HOURS

2. In Parishes, Cities and Towns where an electrical inspection is required, please contact the proper officials for their minimum requirements.

Billing/Service

16262 Wax Road Greenwell Springs LA 70739

(225) 261-1177 1-800-262-1170

8:00 a.m. - 4:30 p.m

3. Items not specifically covered here shall be bound by the requirements set in the National Electrical Code (NEC), latest edition.

Outage/Emergency 16262 Wax Road Greenwell Springs LA 70739

(225) 261-1160 1-800-262-1160

24/7

Headquarters

16262 Wax Road Greenwell Springs LA 70739

(225) 261-1221 1-800-262-0221

8:00 a.m. - 4:30 p.m

Ascension

15095 Highway 931 (225) 261-1177 8:00 a.m. - 4:30 p.m. Gonzales 1-800-262-1170 Lobby closed 12:30 - 1:30 p.m. LA 70737

Central

16262 Wax Road Greenwell Springs LA 70739

(225) 261-1177 1-800-262-1170

8:00 a.m. - 4:30 p.m.

Denham Springs

1810 S. Range Ave Denham Springs LA 70726

(225) 261-1177 1-800-262-1170

8:00 a.m. - 4:30 p.m.

Greensburg

6823 Highway 10 Greensburg LA 70441

(225) 261-1177 1-800-262-1170

8:00 a.m. - 12:00 p.m. 12:30 p.m. - 4:30 p.m.

Livingston

29444 Frost Rd. Livingston LA 70754

(225) 261-1177 1-800-262-1170

8:00 a.m. - 4:30 p.m.

St. Francisville

6843 US Hwy. 61 St. Francisville LA 70775

(225) 261-1177 1-800-262-1170

8:00 a.m. - 12:00 p.m. 12:30 p.m. - 4:00 p.m.

Zachary

20110 Plank Road Zachary LA 70791

(225) 261-1177 1-800-262-1170

8:00 a.m. - 4:30 p.m.

Mailing Address: DEMCO, P.O. Box 15659, Baton Rouge, LA 70895

4. In East Baton Rouge Parish, the ground wire is to be connected to the system neutral in the first disconnect enclosure (panel box or disconnect box). 5. All meter loop material, except meter, to be furnished, installed and maintained by member. The meter pan is to be installed and maintained by member.

Lobby closed 1:00 - 2:00 p.m.

6. Mobile home installations are to remain if mobile home is moved. 7. For underground service, Member/Builder is responsible for furnishing and installing conduit (36” below grade) from the meter pan to a point 24” beyond any surface obstruction (present or planned). This includes patios, driveways, sidewalks, etc. 8. Where overhead service crosses and area subject to vehicle traffic, the pole must be tall enough to ensure that the clearance from the service to the ground is at least 15’ – 6”. 9. The temporary pole shall be located no more than 15’ nor less than 5’ from the edge of the utility servitude and as close to the DEMCO pole, transformer, or pedestal as possible. 10. No Member-owned equipment (including lights, meter loops, etc.) shall be allowed on DEMCO facilities. METER PAN INFORMATION The member/contractor will be responsible for supplying and installing a DEMCO approved meter pan. DEMCO has meter pans available for purchase. General Guidelines for approved meter pans. • UL listed. • NEMA 3R rating (outdoor use) • Constructed of galvanized steel. • The connectors shall be rated for both copper and aluminum. • The ringless type. • Match the service requirements. (i.e., 200 A service requires a 200 A meter pan) • A 320 meter pan shall have a by-pass lever. • An underground service must have a meter pan approved for underground (Minimum dimensions for 200 A underground pan 11”W x 15.5”H x 4.5”D) Milbank, Anchor, Square D, Landis, and Gyr are the only approved manufacturers. For questions regarding meter pans, contact DEMCO at 225-261-1177.

4

5

PERMANENT OVERHEAD SERVICE - METER POLE SINGLE PHASE — 120/240V - 200 AMP OR LESS

2’ Max.

6”

WEATHERHEAD

CONDUIT STRAPS MINIMUM OF 3 FOR RIGID METAL CONDUIT AND MINIMUM OF 4 FOR RIGID NONMETALLIC CONDUIT.

CONDUIT CONDUIT TO BE INSTALLED FROM THE WEATHERHEAD TO METER PAN TO DISCONNECT SWITCH. CONDUIT MAY BE RIGID METAL OR RIGID NONMETALLIC (SCHEDULE 80 PVC). CONDUIT SIZES MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. CONDUIT SIZES SMALLER THAN 2” ARE NOT ACCEPTABLE. USE SUITABLE COUPLINGS TO CONNECT CONDUIT TO METER PAN AND CONDUIT NIPPLE TO THE METER PAN AND DISCONNECT SWITCH. METER PAN DEMCO APPROVED METER PAN INSTALLED BY MEMBER. CONDUIT NIPPLE ATTACHED TO METER PAN MUST HAVE BUSHING. BOND NEUTRAL TO METER ENCLOSURE. SEE DETAIL “A”. DISCONNECT SWITCH (WEATHER PROOF) FUSE OR BREAKER TYPE SUITABLE FOR SERVICE ENTRANCE. DISCONNECT SWITCH MUST BE SIZED BY A QUALIFIED ELECTRICIAN. BOND NEUTRAL TO DISCONNECT ENCLOSURE.

GROUND ROD CLAMP USE CLAMP APPROVED FOR DIRECT BURIAL.

DETAIL “A”

5’ 6”

GROUND ROD COPPER WELD OR GALVANIZED GROUND ROD NOT LESS THAN 8 FEET LONG AND NOT SMALLER THAN 5/8 INCH IN DIAMETER. BURY TOP OF GROUND ROD TO A DEPTH OF 1 FOOT.

3’ Min.

GROUND LEVEL

4’ Burial Depth

MEMBER’S WIRES WIRES MUST BE INSULATED COPPER AND MUST EXTEND OUT OF THE WEATHERHEAD 18”. WIRE SIZE MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. WIRE SIZES SMALLER THAN NO. 2 AWG NOT ACCEPTABLE.

GROUND WIRE #6 COPPER MINIMUM. PUT STAPLES EVERY 6 INCHES. GROUND WIRE MUST BE BONDED TO NEUTRAL LUG.

2’ Max.

15’ 6” Min.

WOOD POLE TREATED, MINIMUM 20’ LONG, MINIMUM 6” DIAMETER ROUND OR 6” X 6” SQUARE.

DEMCO ELECTRIC SERVICE WIRES

CONDUIT FOR TRAILER (36” BELOW GROUND) 6

METER BASE

WHITE NEUTRAL

NOTES: 1. ALL ITEMS SHOWN ARE MEMBER FURNISHED AND INSTALLED EXCEPT WHERE NOTED. 2. NO MEMBER FACILITIES WILL BE ALLOWED ON DEMCO FACILITIES. 3. WHERE LOCAL ORDINANCE PERMITS FACTORY INSTALLED POWER SUPPLY CORD WILL BE ALLOWED.

MINIMUM #6 COPPER GROUND WIRE

BUSHING 7

1’

TEMPORARY OVERHEAD SERVICE - METER POLE SINGLE PHASE — 120/240V — 200 AMP OR LESS

2’ Max.

MEMBER’S WIRES WIRES MUST BE INSULATED COPPER AND MUST EXTEND OUT OF THE WEATHERHEAD 18”. WIRE SIZE MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN.

NOTES: 1. TEMPORARY SERVICE STRUCTURES SHALL WITHSTAND THE STRESSES OF SERVICE WIRES AND ATTACHED EQUIPMENT.

WEATHERHEAD 12’ MINIMUM HEIGHT WHEN SERVICE WILL CROSS AN AREA SUBJECT TO VEHICLE TRAFFIC, THE MINIMUM HEIGHT SHALL BE 15’ - 6”.

2. ANY TEMPORARY SERVICE THAT IS NOT CONSIDERED ADEQUATE SHALL NOT BE CONNECTED.

CONDUIT CONDUIT TO BE INSTALLED FROM THE WEATHERHEAD TO METER PAN TO DISCONNECT SWITCH. CONDUIT MAY BE RIGID METAL OR RIGID NONMETALLIC (SCHEDULE 80 PVC). CONDUIT SIZES MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. CONDUIT SIZES SMALLER THAN 1 ¼” ARE NOT ACCEPTABLE. USE SUITABLE COUPLINGS TO CONNECT CONDUIT TO METER PAN AND CONDUIT NIPPLE TO THE DISCONNECT SWITCH.

3. ALL SINGLE PHASE RECEPTACLE OUTLETS THAT ARE NOT A PART OF THE PERMANENT WIRING OF THE BUILDING OR STRUCTURE MUST HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION. (NEC 305-6)

BRACING

(3) 2” X 4” X 16’

POLE

CONDUIT STRAPS MINIMUM OF 3.

4. MINIMUM OF 4’ x 4’ x 20’ – 0” TREATED SERVICE POLE.

4” x 4” x 20’ (TREATED)

DISCONNECT SWITCH (WEATHER PROOF) FUSE OR BREAKER TYPE SUITABLE FOR SERVICE ENTRANCE. DISCONNECT SWITCH MUST BE SIZED BY A QUALIFIED ELECTRICIAN. BOND NEUTRAL TO DISCONNECT ENCLOSURE.

2’ Max.

5. BRACING SHALL BE SET BACK A MINIMUM OF 6’ FROM POLE. 6. ADDITIONAL BRACING WILL BE REQUIRED FOR DISTANCES FURTHER THAN 30’ FROM UTILITY POLE. 7. ALL ITEMS SHOWN ARE MEMBER FURNISHED AND INSTALLED EXCEPT WHERE NOTED.

5’ 6”

METER PAN DEMCO APPROVED METER PAN INSTALLED BY MEMBER. CONDUIT NIPPLE INSIDE METER PAN MUST HAVE BUSHING. BOND NEUTRAL TO METER ENCLOSURE. SEE DETAIL “A”.

GROUND WIRE #6 COPPER MINIMUM. PUT STAPLES EVERY 6 INCHES. GROUND WIRE MUST BE BONDED TO NEUTRAL LUG.

8. NO MEMBER FACILITIES WILL BE ALLOWED ON DEMCO FACILITIES.

GROUND ROD CLAMP USE CLAMP APPROVED FOR DIRECT BURIAL.

DETAIL “A” METER BASE

4’ Min.

GROUND ROD COPPER WELD OR GALVANIZED GROUND ROD NOT LESS THAN 8 FEET LONG AND NOT SMALLER THAN 5/8 INCH IN DIAMETER. GROUND ROD CAN BE EXTENDED 12” ABOVE FINISH GRADE FOR TEMPORARY INSTALLATION.

WHITE NEUTRAL MINIMUM #6 COPPER GROUND WIRE BUSHING

8

9

TEMPORARY UNDERGROUND SERVICE - METER POLE SINGLE PHASE — 120/240V — 200 AMP OR LESS POLE

4” x 4” (TREATED)

METER PAN DEMCO APPROVED METER PAN INSTALLED BY MEMBER. CONDUIT NIPPLE INSIDE METER PAN MUST HAVE BUSHING. BOND NEUTRAL TO METER ENCLOSURE. SEE DETAIL “A”.

DISCONNECT SWITCH (WEATHER PROOF) FUSE OR BREAKER TYPE SUITABLE FOR SERVICE ENTRANCE. DISCONNECT SWITCH MUST BE SIZED BY A QUALIFIED ELECTRICIAN. BOND NEUTRAL TO DISCONNECT ENCLOSURE. GROUND WIRE #6 COPPER MINIMUM. PUT STAPLES EVERY 6 INCHES. GROUND WIRE MUST BE BONDED TO NEUTRAL LUG.

METER BASE CONDUIT STRAP

GROUND ROD COPPER WELD OR GALVANIZED GROUND ROD NOT LESS THAN 8 FEET LONG AND NOT SMALLER THAN 5/8 INCH IN DIAMETER. GROUND ROD CAN BE EXTENDED 12” ABOVE FINISH GRADE FOR TEMPORARY INSTALLATION. NOTES: 1. TEMPORARY SERVICE STRUCTURES SHALL WITHSTAND THE STRESSES OF SERVICE WIRES AND ATTACHED EQUIPMENT. 2. ANY TEMPORARY SERVICE THAT IS NOT CONSIDERED ADEQUATE SHALL NOT BE CONNECTED. 3. ALL SINGLE PHASE RECEPTACLE OUTLETS THAT ARE NOT A PART OF THE PERMANENT WIRING OF THE BUILDING OR STRUCTURE MUST HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION. (NEC 305-6) 4. THE TEMPORARY POLE SHALL BE LOCATED NO MORE THAN 15’ NOR LESS THAN 5’ FROM THE EDGE OF THE UTILITY SERVITUDE AND AS CLOSE TO THE DEMCO POLE, TRANSFORMER OR PEDESTAL AS POSSIBLE. 5. ALL ITEMS SHOWN ARE MEMBER FURNISHED AND INSTALLED EXCEPT WHERE NOTED. 6. NO MEMBER FACILITIES WILL BE ALLOWED ON DEMCO FACILITIES.

10

WHITE NEUTRAL MINIMUM #6 COPPER GROUND WIRE

ALLOW FOR SUFFICIENT WIRE TO REACH SOURCE

BUSHING

3’ Min. Pole Depth

GROUND ROD CLAMP USE CLAMP APPROVED FOR DIRECT BURIAL.

DETAIL “A”

5’ to 6’

CONDUIT CONDUIT TO BE INSTALLED FROM THE WEATHERHEAD TO METER PAN TO DISCONNECT SWITCH. CONDUIT MUST BE RIGID NONMETALLIC (SCHEDULE 80 PVC). CONDUIT SIZES MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. CONDUIT SIZES SMALLER THAN 1 ¼” ARE NOT ACCEPTABLE. USE SUITABLE COUPLINGS TO CONNECT CONDUIT TO METER PAN AND CONDUIT NIPPLE TO THE DISCONNECT SWITCH.

11

PERMANENT OVERHEAD SERVICE - THRU-ROOF (ROOF JACK) SINGLE PHASE — 120/240V — 200 AMP OR LESS WEATHERHEAD

3’ 6” Max. 2’ 6” Min.

DEMCO ELECTRIC SERVICE WIRES

PROPER BLOCKING BETWEEN RAFTERS TO SUPPORT CONDUIT. (2 X 6 BLOCKING)

MEMBER’S WIRES WIRES MUST BE INSULATED COPPER AND MUST EXTEND OUT OF THE WEATHERHEAD 18”. WIRE SIZE MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. WIRE SIZES SMALLER THAN NO. 2 AWG NOT ACCEPTABLE. CONDUIT CONDUIT TO BE INSTALLED FROM THE WEATHERHEAD TO THE METER PAN. CONDUIT SHALL BE RIGID METAL. CONDUIT SIZES MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. CONDUIT SIZES SMALLER THAN 2” ARE NOT ACCEPTABLE. USE SUITABLE COUPLINGS TO CONNECT CONDUIT TO METER PAN.

2’ Max.

METER PAN DEMCO APPROVED METER PAN INSTALLED BY MEMBER. CONDUIT NIPPLE ATTACHED TO METER PAN MUST HAVE BUSHING. BOND NEUTRAL TO METER ENCLOSURE. SEE DETAIL “A”. GROUND WIRE #6 COPPER MINIMUM INSTALLED IN ½” CONDUIT SECURELY FASTENED TO WALL. CONDUIT MAY BE RIGID METAL OR RIGID NONMETALLIC (SCHEDULE 80 PVC). GROUND CLAMP USE CLAMP APPROVED FOR DIRECT BURIAL.

DETAIL “A”

GROUND ROD COPPER WELD OR GALVANIZED GROUND ROD NOT LESS THAN 8 FEET LONG AND NOT SMALLER THAN 5/8 INCH IN DIAMETER. BURY TOP OF GROUND ROD TO A DEPTH OF 1 FOOT.

5’ 6”

13’ Min.

CONDUIT STRAPS STRAPS MUST BE INSTALLED NO MORE THAN 5 FEET APART.

NOTES: 1. ALL ITEMS SHOWN ARE MEMBER FURNISHED AND INSTALLED EXCEPT WHERE NOTED. 2. NO MEMBER FACILITIES WILL BE ALLOWED ON DEMCO FACILITIES.

GRADE

METER BASE

WHITE NEUTRAL

MINIMUM #6 COPPER GROUND WIRE

BUSHING 12

13

PERMANENT OVERHEAD SERVICE - WALL MOUNTED SINGLE PHASE — 120/240V — 200 AMP OR LESS WEATHERHEAD

MEMBER’S WIRES WIRES MUST BE INSULATED COPPER AND MUST EXTEND OUT OF THE WEATHERHEAD 18”. WIRE SIZE MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. WIRE SIZES SMALLER THAN NO. 2 AWG NOT ACCEPTABLE. CONDUIT CONDUIT TO BE INSTALLED FROM THE WEATHERHEAD TO THE METER PAN. CONDUIT SHALL BE RIGID METAL. CONDUIT SIZES MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. CONDUIT SIZES SMALLER THAN 2” ARE NOT ACCEPTABLE. USE SUITABLE COUPLINGS TO CONNECT CONDUIT TO METER PAN.

THIS HEIGHT MAY BE REDUCED TO 12’ WHEN HEIGHT OF THE BUILDING WILL NOT ALLOW 13’ VALUE.

CONDUIT STRAPS STRAPS MUST BE INSTALLED NO MORE THAN 5 FEET APART.

2’ Max.

METER PAN DEMCO APPROVED METER PAN INSTALLED BY MEMBER. CONDUIT NIPPLE ATTACHED TO METER PAN MUST HAVE BUSHING. BOND NEUTRAL TO METER ENCLOSURE. SEE DETAIL “A”. GROUND WIRE #6 COPPER MINIMUM INSTALLED IN ½” CONDUIT SECURELY FASTENED TO WALL. CONDUIT MAY BE RIGID METAL OR RIGID NONMETALLIC (SCHEDULE 80 PVC). GROUND CLAMP USE CLAMP APPROVED FOR DIRECT BURIAL.

DETAIL “A”

GROUND ROD COPPER WELD OR GALVANIZED GROUND ROD NOT LESS THAN 8 FEET LONG AND NOT SMALLER THAN 5/8 INCH IN DIAMETER. BURY TOP OF GROUND ROD TO A DEPTH OF 1 FOOT.

5’ 6”

13’ Min.

2’ Max.

DEMCO ELECTRIC SERVICE WIRES

NOTES: 1. ALL ITEMS SHOWN ARE MEMBER FURNISHED AND INSTALLED EXCEPT WHERE NOTED. 2. NO MEMBER FACILITIES WILL BE ALLOWED ON DEMCO FACILITIES.

GRADE

METER BASE

WHITE NEUTRAL

MINIMUM #6 COPPER GROUND WIRE

BUSHING 14

15

PERMANENT UNDERGROUND SERVICE - WALL MOUNTED SINGLE PHASE — 120/240V — 200 AMP OR LESS

METER PAN DEMCO APPROVED METER PAN INSTALLED BY MEMBER. CONDUIT NIPPLE ATTACHED TO METER PAN MUST HAVE BUSHING. BOND NEUTRAL TO METER ENCLOSURE. SEE DETAIL “A”. CONDUIT CONDUIT MUST BE RIGID METAL OR RIGID NONMETALLIC (SCHEDULE 80 PVC). CONDUIT SIZES MUST BE DETERMINED BY A QUALIFIED ELECTRICIAN. CONDUIT SIZES SMALLER THAN 2” ARE NOT ACCEPTABLE. USE SUITABLE COUPLINGS TO CONNECT CONDUIT TO METER PAN. SEE NOTE 3. CONDUIT STRAPS MINIMUM 2. GROUND WIRE #6 COPPER MINIMUM INSTALLED IN ½” CONDUIT SECURELY FASTENED TO WALL. CONDUIT MAY BE RIGID METAL OR RIGID NONMETALLIC (SCHEDULE 80 PVC). GROUND CLAMP USE CLAMP APPROVED FOR DIRECT BURIAL. 6’

GROUND ROD COPPER WELD OR GALVANIZED GROUND ROD NOT LESS THAN 8 FEET LONG AND NOT SMALLER THAN 5/8 INCH IN DIAMETER. BURY TOP OF GROUND ROD TO A DEPTH OF 1 FOOT.

3’

GRADE

TOP OF CONDUIT

DETAIL “A” METER PAN

NOTES: 1. ALL ITEMS SHOWN ARE MEMBER FURNISHED AND INSTALLED EXCEPT WHERE NOTED. 2. 2” SCHEDULE 80 PVC CONDUIT SHALL BE PROVIDED BY MEMBER. CONDUIT FROM METER PAN SHALL EXTEND 24” (PATIOS, SIDEWALKS, DRIVEWAYS, ETC…) 3. CONDUIT TO BE INSTALLED FROM THE METER PAN TO 3’ – 0” BELOW GRADE, UTILIZING (1) ONE 90° SWEEP, 24” RADIUS MINIMUM. 4. NO MEMBER FACILITIES WILL BE ALLOWED ON DEMCO FACILITIES.

WHITE NEUTRAL

MINIMUM #6 COPPER GROUND WIRE

2” BUSHING 16

17

PERMANENT UNDERGROUND SERVICE TO MOBILE HOME METER POLE — UNDERGROUND SUBDIVISION SINGLE PHASE — 120/240V — 200 AMP OR LESS OPTION 1 SINGLE POLE MOUNT STRUCTURE

M

OPTION 2 TWO POLE MOUNT STRUCTURE

M

M

WOODEN POLE 8’ ABOVE, 3’ BELOW GROUND MINIMUM

NOTE: ALL MATERIAL, EXCEPT METER, TO BE FURNISHED, INSTALLED AND MAINTAINED BY MEMBER.

MOBILE HOME PANEL

COMBINATION METER/SERVICE DISCONNECT/BREAKER ENCLOSURE OR SEPARATE METER ENCLOSURE AND SERVICE DISCONNECT/BREAKER ENCLOSURE

CONDUIT 2” CONDUIT PIPE FOR MOBILE HOME (36” MIN. BELOW GROUND) GROUND WIRE #6 CU MINIMUM (GROUNDING ELECTRODE CONDUCTOR GROUND ROD 5/8” X 8’ COPPER WELD OR GALV. GROUND ROD BURY TOP OF GROUND ROD TO A DEPTH OF 1 FOOT

CONDUIT FOR SERVICE (36” MIN. BELOW GROUND)

GRADE

M

INSULATED NEUTRAL BUS PANEL GROUNDING BUS GROUND TO MOBILE HOME

SERVICE ENTRANCE EQUIPMENT

GROUNDING ELECTRODE CONDUCTOR #6 CU MINIMUM WHITE (NEUTRAL) GREEN (GROUNDING)

TO GROUND ROD

GROUNDING THE WHITE (NEUTRAL) CONDUCTOR SHALL BE RUN FROM THE “INSULATED BUSBAR” IN THE MOBILE HOME PANEL TO THE SERVICE-ENTRANCE EQUIPMENT, WHERE IT IS CONNECTED TO THE TERMINAL AT THE POINT OF CONNECTION TO THE GROUNDING ELECTRODE CONDUCTOR. THE GREEN-COLORED (GROUNDING) CONDUCTOR SHALL BE RUN FROM THE “PANEL GROUNDING BUS” IN THE MOBILE HOME TO THE SERVICE-ENTRANCE EQUIPMENT, WHERE IT IS CONNECTED TO THE WHITE CONDUCTOR (NEUTRAL) AT THE POINT OF CONNECTION TO THE GROUNDING ELECTRODE CONDUCTOR. THE GROUNDED (WHITE) CONDUCTOR AND THE GROUNDING (GREEN) CONDUCTOR MUST BE KEPT SEPARATE WITHIN THE MOBILE HOME STRUCTURE IN ORDER TO SECURE THE MAXIMUM PROTECTION AGAINST ELECTRIC-SHOCK HAZARD SHOULD THE SUPPLY NEUTRAL CONDUCTOR BECOME OPEN. (NEC 550.16)

18

19

UNDERGROUND SERVICE SINGLE RESIDENCE PULL BOX FOR SECONDARY SYSTEM Plastic or fiberglass for grass areas or polymer concrete for light duty areas (see notes 2, 3, and 4)

STANDARD SERVICE INSTALLATION WITH PULL BOX PULL BOX (See pull box detail and notes 2, 3, 4)

Conduit run as specified

Pentahead bolts

DEMCO facility. Transformer or Pedestal

Typical Grade

STANDARD SERVICE INSTALLATION See note 2

Conduit run as specified

DEMCO facility. Transformer or Pedestal

20

NOTES 1. MEMBER FACILITIES SHALL COMPLY WITH THE NEC AND AUTHORITIES HAVING JURISDICTION. 2. MEMBER SHALL CONSULT WITH COMPANY FOR LOCATION OF PULL BOX FOR ANY LENGTH OVER 200’. 3. IF MORE THAN THREE 90° BENDS (INCLUDING RISER BENDS AND REGARDLESS OF LENGTH) ARE REQUIRED IN ANY RUN, CONSULT THE COMPANY. 4. PULL BOX SHALL BE INSTALLED AT A 90° BEND OR THE CENTER OF RUN AND BE OF SUFFICIENT STRENGTH TO SUPPORT PROBABLE LOCAL TRAFFIC (CONSULT COMPANY FOR BOX IN AREAS WITH TRAFFIC OR TRUCKS DRIVING OVER BOXES). RECOMMENDED SIZE: 17”W X 30”L X 18”D. 5. THE MEMBER SHALL BEAR THE COST OF CONDUIT AND ITS INSTALLATION. 6. CONDUIT SHALL BE 2” OR 2.5” AND SHALL BEAR THE U.L. LABEL, RIGID NONMETALLIC (SCHEDULE 80 PVC ABOVE THE GROUND, SCHEDULE 40 BELOW GRADE, GRAY ONLY.) 7. THE MEMBER SHALL INSTALL 80 lb. TEST NON-METALLIC (NYLON, ETC.) PULL LINE IN MEMBER’S CONDUIT. 8. UNDERGROUND SERVICE CONDUIT SHALL BE SEPARATED FROM TELEPHONE, CABLE, OR WATER FACILITIES BY NOT LESS THAN 3” OF CONCRETE, 4” OF BRICK MASONRY, OR 12” OF WELL TAMPED EARTH AND 18” OF WELL TAMPED EARTH FOR GAS FACILITIES. 9. CONDUIT TO BE INSTALLED TO THE SERVITUDE EDGE AT THE CLOSEST POINT TO DEMCO’S TRANSFORMER OR PEDESTAL. 10. CONDUIT SHALL BE INSTALLED AT A MINIMUM DEPTH OF 36” AND MUST BE INSPECTED BY A DEMCO REPRESENTATIVE BEFORE BACKFILLING. 11. MEMBER WILL BE REQUIRED TO CORRECT ANY PROBLEMS WITH CONDUIT PRIOR TO DEMCO INSTALLING WIRE. DEMCO WILL CORRECT PROBLEMS AT MEMBER’S REQUEST FOR AN ADDITIONAL FEE. 21

CITY/PARISH PERMIT REQUIREMENTS These are the general requirements for permitting in parishes and cities in our area. DEMCO will adhere to these and any requirements imposed by governing authorities.

POWER THEFTS AND METER TAMPER – A permit to reconnect service will be required on all locations where power theft has occurred and on any location where meter tamper has caused damage to the meter pan.

The following permits and inspections are required by local government agencies prior to connection of electrical service.

SECOND OR ADDITIONAL SERVICES AT AN EXISTING RESIDENTIAL ADDRESS – As before, any new service requires a permit. However, EBR in some cases will no longer allow additional meters at an existing address. This is a zoning decision unrelated to DEMCO. If this type of application is made by a Member, we will not be able to assign or build a job for the order until a cleared permit has been received.

ASCENSION PARISH Any new construction, rebuilt service or connection of an inactive residential or commercial building needs permits from the following: Environmental Services (225) 644-5916 1024 SE Ascension Complex Gonzales, LA 70737

CITY OF BAKER

All connects need permits from the following: City of Baker (225) 778-0850 3325 Groom Road, Baker, LA 70714

CITY OF CENTRAL

Building, Planning & Zoning (225) 621-5700 42077 Churchpoint Road Gonzales, LA 70737

Any new construction, new mobile home, commercial building, or rebuilt service needs a permit from the following:

TRANSFER OF SERVICE FOR HOUSE, MOBILE HOME OR COMMERCIAL BUILDING THAT WAS NOT DISCONNECTED - NO PERMIT IS NEEDED.

EAST BATON ROUGE PARISH Any new construction, mobile home, commercial building, or rebuilt service needs permits from the following:

City of Central (225) 262-5000 6703 Sullivan Rd, Central, LA 70818 RECONNECTION OF SERVICE FOR EXISTING RESIDENCE, MOBILE HOME OR APARTMENT ONLY — NO PERMIT IS NEEDED UNLESS NO SERVICE FOR SIX MONTHS OR LONGER.

CITY OF ZACHARY

Any house, mobile home, or commercial building needs permits from the following: City of Zachary (225) 654-6873 4650 Main Street, Zachary, LA 70791

City Parish Permit Office – (225) 389-3226 300 N. 10th Street, Baton Rouge, LA 70802

TRANSFER OF SERVICE FOR HOUSES ONLY DOES NOT REQUIRE A PERMIT UNLESS NO SERVICE FOR OVER 6 MONTHS.

EBR Record Room – (225) 389-3233 RECONNECTION OF SERVICE FOR HOUSES OR APARTMENTS ONLY - NO PERMIT IS NEEDED UNLESS NO SERVICE FOR SIX MONTHS OR LONGER. NON-PAY RECONNECTS ON MOBILE HOMES – Any Member living in a mobile home that was disconnected for non-payment has 6 months to pay and reconnect their service without permits. After 6 months a permit will be required to reconnect. 22

23

CITY/PARISH PERMIT REQUIREMENTS (CONT.)

EAST FELICIANA PARISH

TOWN OF LIVINGSTON

Any house, mobile home, or commercial building needs permits from the following: Police Jury (225) 683-8577 12064 Marston Street, Clinton, LA 70722

Any new construction within the City limits of the Town of Livingston needs permits from the following: Town of Livingston (225) 686-7153 20550 Circle Drive, Livingston, LA 70754

The Health Unit (225) 683-8551 12080 Marston Street, Clinton, LA 70722

TRANSFER OF SERVICE NEEDS PERMITS FROM LIVINGSTON PARISH (SEE ABOVE)

COMMERCIAL BUILDING – A SCHOOL BOARD TAX PERMIT IS ALSO NEEDED.

TOWN OF SLAUGHTER

Same as East Feliciana Parish requirements.

LIVINGSTON PARISH Any house, mobile home, commercial building, or rebuilt service needs permits from the following:

TOWN OF WALKER

Any new or existing house, mobile home, or commercial building within the city limits of Walker needs permits from the following: Town of Walker (225) 664-3123 Municipal Building 10136 Florida Boulevard, Walker, LA 70785

VILLAGE OF FRENCH SETTLEMENT

Any house, mobile home, or commercial building needs permits from the following:

Parish Permit Office (225) 686-3021 29261 Frost Road, Livingston, LA 70754

Village of French Settlement (225) 698-6100 16015 Hwy. 16, French Settlement, LA 70733

Environmental Health Unit (225) 686-9364 / (225) 686-1786 29261 Frost Road, Livingston, LA 70754

ST. HELENA PARISH

Any house, mobile home, or commercial building needs permits from the following:

CITY OF DENHAM SPRINGS

Only mobile homes & commercial buildings need permits from the following: City of Denham Springs (225) 667-8326 941 Government Street, Denham Springs, LA 70726

TOWN OF KILLIAN

Any existing house, mobile home, or commercial building needs permits from the following: Town of Killian (225) 695-6785 28284 La Hwy. 22, Springfield, LA 70462

Police Jury (225) 222-3266 17911 Hwy. 43 N, Greensburg, LA 70441 Health Unit (225) 222-6176 53 N 2nd Street, Greensburg, LA 70441 IF DISCONNECTED OVER 30 DAYS PERMITS ARE NEEDED.

Any new construction needs a building permit from both the town of Killian and Livingston Parish. 24

25

CITY/PARISH PERMIT REQUIREMENTS (CONT.)

TANGIPAHOA PARISH

Any house, mobile home, or commercial building needs permits from the following: Environmental Office (985) 748-2024 63103 Commercial St., Roseland, LA 70456 Hammond Permit Office (985) 748-3246 15481 Club Deluxe Rd, Hammond, LA 70403

WEST FELICIANA PARISH

Any house, mobile home, or commercial building needs permits from the following: Health Unit (225) 635-3644 5154 Burnett Road, St. Francisville, LA 70775 Police Jury (225) 635-3864 5934 Commerce, St. Francisville, LA 70775 School Board (225) 635-3891 4727 Fidelity Street, St. Francisville, LA 70775 COMMERCIAL BUILDING – SCHOOL BOARD PERMIT ALSO NEEDED.