AIR TO WATER HEAT PUMP OPERATION MANUAL (ALH-split type )

AIR TO WATER HEAT PUMP OPERATION MANUAL (ALH-split type ) Please read this manual carefully for installation and keep it well, pls contact your local...
Author: Conrad Walters
5 downloads 0 Views 2MB Size
AIR TO WATER HEAT PUMP OPERATION MANUAL (ALH-split type )

Please read this manual carefully for installation and keep it well, pls contact your local dealer for any question

CONTENT GENERAL ----------------------------------------------- 1 INSTALLATION INSTRUCTION ------------------- 3 PIPE CONNECTION --------------------------------- 4 ELECTRICAL CONNECTIONS ------------------- 6 CONTROL ---------------------------------------------- 7 TECHNICAL DATA ----------------------------------- 13

OPERATION PRINCIPLE ALTO split ALTO split

Sensor buffle tank

Fan coil 1

buffle tank

Water tank 2

Outdoor unit Indoor unit Refrigeration outlet

Fan coil 2 Refrigeration inlet DOMESTIC USE

Fresh water inlet Hot water outlet Water tank 1

Fan coil 3 Sensor Controller

1

PRODUCTS DESCRIPTION There are 7 models for Alto ALH/S series(EVI-Enhanced vapour injection technology) heat pump range. They are AHH-R075/ALH, AHH-R100/ALH, AHH-R120/ALH,AHH-R140/ALH, AHH-R160/ALH, AHH-R220/ALH, AHH-R280/ALH. Heat is distributed throughout the house over a hydronic heating system with outlet water temperature of 65℃. Most of the heating demand is taken care of by the heat pump. ALTO 1.Outdoor unit Evaporator Fan and fan motor Handle valve 2.Indoor unit EVI scroll compressor EVI plate heat exchanger Expansion valve Water pump Pressure balance valve Handle valve Auxiliary electric heater Safety equipment for refrigerant system Electric components (If the electric heating element is turned on)

until If the water temperature is not acchieved after heat pump heating for 30 minutes, electric heater is turned on to assist the heating till the targeted temperature is reached

and valves).

2

INSTALLATION AND SITING

Outdoor unit

3

to room

Safety valve

to water tank

Water Input/Output connection : Dn25 Refrigeration Input connection: Copper pipe 3/4" Refrigeration Output connection: Copper pipe 1"

There are two sets 5 metre copper pipes in the accessary kits to connect the outdoor and indoor unit. 4

Venting venting valve

Open the pump electric cover by screwing, fix the terminals according to the schematic symbols.

5

Y/Gn

C1 Rly C2

Wh Re Bk

COMP

L

C

L

N

S R C

N

FAN MOTOR Y/Gn

AHH-R100/ALH/S Electrical diagram

6

EVI

FM

N L

EVI

FM

N L

From up to down is the 3 sets data for timer OR electric heater

Heating function Room heating Tank heating

7

BUTTON EXPLANATION Before switching on the unit press this button for 5 seconds to turn on the user’s setting function. Press this button for 10 seconds to turn on the manufacture parameter setting function. After switching on the unit. Press this button for 5 seconds to set heater manually or heater automatically just press transienctly to select heater consumption. Press shortly to switch water tank temperature setting and room temperature setting. The room symbol will appear on the screen when enter room temperature setting. Press for 5 seconds to get into manually protection against legionella flashes on the screen function

it can get into the consulting for current running status checking press for 5 seconds to enter manual defrosting function

8

(For installer only)

Ambient temperature offset Defrosting temperature offset Tank temperature offset Compressor exhaust temperature offset Room temperature offset Water in temperature offset Water out temperature offset Hot water differential

5

Room temperature differential

1

---

---

Ambient temperature of heat pump stop running Room anti-freezing setting

30 0

15

Compressor exhaust temperature overheat

4

Water temperature of anti-freezing

2 3 -5

Temperature of entering to defrost

8

Temperature of exit to defrost Defrosting interval time

45 minutes 8 minutes

Defrosting setting time

10 minutes

Anti-freezing interval time Buzzer for malfunction

1

Restart function Clock adjusting time

F-25

Cycle of protection against legionella

F-26

Summer/Winter option

0 30 days 18℃

9

20

110

Ambient temperature of anti-freezing

Temperature differential of 4-way valve protection

---

3

20

Before the running of heat pump ,

TEMPERATURE SETTING

Press

and

can set target tank temperature/Room temperature tank tank tank

10

CONSULT FUNCTION (For installer only)

TH6 Water in temperature

TH7 Water out temperature

L-08 L-09

ELECTRIC HEATER SETTING After the heat pump is turned on Press for 3 seconds can lead to manual electric heating OR automatic electric heating. Automatic electric heating is set in default.When manual electric heating is activated, it buzzs twice. Press again to cancel electric heating setting(you must press three times until the three sliver at the up-left corner disappear.)

Manual electric heating setting

button

Automatic electric heating setting

11

FAILURE DISPLAY

Error code Er00

Error phenomenon Communication problem

Troubleshooting 1.Check and adjust the quick connection fiting of wire control. 2.Check the digital wire of wire control

Er01

Ambient temperature sensor problem

The ambient temperature sensor is not working well, please change a good one

Er02

Defrosting temperature sensor problem

The defrosting temperature sensor is not working well, please change a good one

Er03

Water tank temperature The water tank temperature sensor is not working well, please sensor problem change a good one

Er04

Compressor exhaust temperature sensor problem

The discharge pipe temperature sensor is not working well, please change a good one

Er05

Room temperature sensor problem

The room temperature sensor is not working well, please change a good one

Er06

Water in temperature sensor problem

The water in temperature sensor is not working well, please change a good one

Er07

Water out temperature sensor problem

The water out temperature sensor is not working well, please change a good one

Er08

Phase protection

1.Change the locating of any two phase 2.Check the voltage between phase wire

Er09

System malfunction protection

Check the refrigerant system

Er10

Whole system Flow lack or flow switch problem

1.Make sure there is no air in water circulation system 2.Check the venting valve and venting valve seal ring 3.Check the main circulation pump 4.Open the venting valve to exhaust air 5.Check the main circulation pump be sure the pump is operating well

Er11

Tank Flow lack or flow switch problem

Er12

High pressure protection

Er13

Low pressure protection

1.Check the water tank to make sure it’s full of water 2.Make sure the venting valve is sealed and no air in the water tank 1.Check the temperature difference between inlet and outlet of heat pump 2.See that the thermostats are open in the radiators or the floor heating. More than the half of them must be open to the whole position. 3.Check the filter(water) and clean it if it some dust in it. 4. Check if it is air in the water system. remove from the vessels. 1.Check whether there is any ice around the heat pump 2.Check whether the fan of heat pump is working

12

EXPLODED VIEW OUTDOOR UNIT(HEAT PUMP)

18

17

13

EXPLODED VIEW INDOOR UNIT

1 2

33

13 15

32

3

14

4

16 17

11

12

19 18

1.Back cover 2.Gantry shelf 3.Copper tube 4.Expansion valve1 5.Accumulator 6.Water pump 2 7.Heat exchanger 2 supporter 8.Heat exchanger 2 9.Three way valve 10.Water pipe 11.Water pump 1 12.Electric heater 13.Compressor 14.Heat exchanger 1 supporter 15.Heat exchanger 1 16.Front plate 17.Front door 18.Bottom supporter 19.Supporter plate 20.Electrical box cover

14

5

6

7 8 1.Back cover 2. Gantry shelf 10 3.Copper tube 23 24 9 4.Expansion valve1 5.Accumulator 22 6.Water pump 2 25 26 7.Heat exchanger 2 supporter 8.Heat exchanger 2 31 29 9.Three way valve 10.Water pipe 28 30 11.Water pump 1 21 27 12.Electric heater 20 13.Compressor 14.Heat exchanger 1 supporter 15.Heat exchanger 1 16.Front plate 17.Front door 18.Bottom supporter 19.Supporter plate 20.Electrical box cover 21.Electrical box panel 22.Electrical box 23.Expansion valve2 24.Solenoid valve 25.Plate heat exchanger3 26.Plate heat exchanger3 supporter 27.PCB 28.Breaker 29.Drying filter 30.Contactor 31.Liquid sight 32.Shut-off valve 1 33.Shut-off valve 2

TECHNICAL DATA AHH-R075/ALH

AHH-R100/ALH

AHH-R120/ALH

AHH-R140/ALH

AHH-R160/ALH

AHH-R220/ALH

AHH-R280/ALH

w

10350/2315

13500/3015

15500/3452

17080/3838

18580/4125

27500/6100

34800/7720

w/w

4.47

4.48

4.49

4.45

4.5

4.51

4.51

w

8010/2102

10700/2810

12100/3168

14200/3717

16000/4175

22800/5950

28300/7370

MODEL Delivered/supplied power at 7/35℃ * COP at air 7/35℃ ** Delivered/supplied power at 2/35℃ COP at air 2/35℃ Delivered/supplied power at -7/35℃ COP at air -7/35℃ Delivered/supplied power at 7/50℃ COP at air 7/50℃ Delivered/supplied power at 2/50℃ COP at air 2/50℃ Delivered/supplied power at -7/50℃ COP at air -7/50℃

w/w

3.81

3.81

3.82

3.82

3.83

3.83

3.84

w

5070/1892

6750/2510

7680/2855

8520/3167

9480/3525

14750/5445

18200/6715

w/w

2.68

2.69

2.69

2.69

2.69

2.71

2.71

w

9800/2580

12980/3410

14680/3850

16180/4280

18050/4750

26050/6800

32960/8610

w/w

3.8

3.81

3.81

3.78

3.8

3.83

3.83

w

7820/2270

10410/3015

11810/3420

13860/4010

15650/4510

22250/6430

27620/7950

w/w

3.44

3.45

3.45

3.46

3.47

3.46

3.47

w

4970/2075

6600/2810

7370/3130

8175/3475

9020/3835

14150/5975

17460/7370

w/w

2.4

2.35

2.35

2.35

2.35

2.37

2.37

Power supply

V/P/Hz

Compressor

Type

220~240V/50Hz/1P

380~415V/50Hz/3P

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Max water temperature

o

60

60

60

60

60

60

60

Water tempe(with electric heater)

o

C

70

70

70

70

70

70

70

Water connection

inch/mm

1.2/30.5

1.2/30.5

1.2/30.5

1.2/30.5

1.2/30.5

1.2/30.5

1.2/30.5

Water-proof grade

Type

Guaranteed operating range

C

o

C

IP X 4

IP X 4

IP X 4

IP X 4

IP X 4

IP X 4

IP X 4

-25 ~ 42

-25 ~ 35

-25 ~ 42

-25 ~ 42

-25 ~ 42

-25 ~ 42

-25 ~ 42

54

58

62

Nominal Sound leve

dBA

52

54

54

54

Outdoor Unit (L/W/H)

mm

910/360/880

940/390/1010

940/390/1280

940/360/1280

60

75

75

90

Indoor Unit

Weight

kg

(H/L/W)

mm

Weight

kg

940/360/1280 1450/820/1050 1450/860/1050 105

125

125

600/440/870 600/440/870 600/440/870 600/440/870 600/440/870 1150/620/950 1150/620/950 80

92

105

15

132

165

205

295