AIR TO WATER HEAT PUMP OPERATION MANUAL (ALH-split type )
AIR TO WATER HEAT PUMP OPERATION MANUAL (ALH-split type )
Please read this manual carefully for installation and keep it well, pls contact your local...
AIR TO WATER HEAT PUMP OPERATION MANUAL (ALH-split type )
Please read this manual carefully for installation and keep it well, pls contact your local dealer for any question
CONTENT GENERAL ----------------------------------------------- 1 INSTALLATION INSTRUCTION ------------------- 3 PIPE CONNECTION --------------------------------- 4 ELECTRICAL CONNECTIONS ------------------- 6 CONTROL ---------------------------------------------- 7 TECHNICAL DATA ----------------------------------- 13
OPERATION PRINCIPLE ALTO split ALTO split
Sensor buffle tank
Fan coil 1
buffle tank
Water tank 2
Outdoor unit Indoor unit Refrigeration outlet
Fan coil 2 Refrigeration inlet DOMESTIC USE
Fresh water inlet Hot water outlet Water tank 1
Fan coil 3 Sensor Controller
1
PRODUCTS DESCRIPTION There are 7 models for Alto ALH/S series(EVI-Enhanced vapour injection technology) heat pump range. They are AHH-R075/ALH, AHH-R100/ALH, AHH-R120/ALH,AHH-R140/ALH, AHH-R160/ALH, AHH-R220/ALH, AHH-R280/ALH. Heat is distributed throughout the house over a hydronic heating system with outlet water temperature of 65℃. Most of the heating demand is taken care of by the heat pump. ALTO 1.Outdoor unit Evaporator Fan and fan motor Handle valve 2.Indoor unit EVI scroll compressor EVI plate heat exchanger Expansion valve Water pump Pressure balance valve Handle valve Auxiliary electric heater Safety equipment for refrigerant system Electric components (If the electric heating element is turned on)
until If the water temperature is not acchieved after heat pump heating for 30 minutes, electric heater is turned on to assist the heating till the targeted temperature is reached
There are two sets 5 metre copper pipes in the accessary kits to connect the outdoor and indoor unit. 4
Venting venting valve
Open the pump electric cover by screwing, fix the terminals according to the schematic symbols.
5
Y/Gn
C1 Rly C2
Wh Re Bk
COMP
L
C
L
N
S R C
N
FAN MOTOR Y/Gn
AHH-R100/ALH/S Electrical diagram
6
EVI
FM
N L
EVI
FM
N L
From up to down is the 3 sets data for timer OR electric heater
Heating function Room heating Tank heating
7
BUTTON EXPLANATION Before switching on the unit press this button for 5 seconds to turn on the user’s setting function. Press this button for 10 seconds to turn on the manufacture parameter setting function. After switching on the unit. Press this button for 5 seconds to set heater manually or heater automatically just press transienctly to select heater consumption. Press shortly to switch water tank temperature setting and room temperature setting. The room symbol will appear on the screen when enter room temperature setting. Press for 5 seconds to get into manually protection against legionella flashes on the screen function
it can get into the consulting for current running status checking press for 5 seconds to enter manual defrosting function
8
(For installer only)
Ambient temperature offset Defrosting temperature offset Tank temperature offset Compressor exhaust temperature offset Room temperature offset Water in temperature offset Water out temperature offset Hot water differential
5
Room temperature differential
1
---
---
Ambient temperature of heat pump stop running Room anti-freezing setting
30 0
15
Compressor exhaust temperature overheat
4
Water temperature of anti-freezing
2 3 -5
Temperature of entering to defrost
8
Temperature of exit to defrost Defrosting interval time
45 minutes 8 minutes
Defrosting setting time
10 minutes
Anti-freezing interval time Buzzer for malfunction
1
Restart function Clock adjusting time
F-25
Cycle of protection against legionella
F-26
Summer/Winter option
0 30 days 18℃
9
20
110
Ambient temperature of anti-freezing
Temperature differential of 4-way valve protection
---
3
20
Before the running of heat pump ,
TEMPERATURE SETTING
Press
and
can set target tank temperature/Room temperature tank tank tank
10
CONSULT FUNCTION (For installer only)
TH6 Water in temperature
TH7 Water out temperature
L-08 L-09
ELECTRIC HEATER SETTING After the heat pump is turned on Press for 3 seconds can lead to manual electric heating OR automatic electric heating. Automatic electric heating is set in default.When manual electric heating is activated, it buzzs twice. Press again to cancel electric heating setting(you must press three times until the three sliver at the up-left corner disappear.)
Manual electric heating setting
button
Automatic electric heating setting
11
FAILURE DISPLAY
Error code Er00
Error phenomenon Communication problem
Troubleshooting 1.Check and adjust the quick connection fiting of wire control. 2.Check the digital wire of wire control
Er01
Ambient temperature sensor problem
The ambient temperature sensor is not working well, please change a good one
Er02
Defrosting temperature sensor problem
The defrosting temperature sensor is not working well, please change a good one
Er03
Water tank temperature The water tank temperature sensor is not working well, please sensor problem change a good one
Er04
Compressor exhaust temperature sensor problem
The discharge pipe temperature sensor is not working well, please change a good one
Er05
Room temperature sensor problem
The room temperature sensor is not working well, please change a good one
Er06
Water in temperature sensor problem
The water in temperature sensor is not working well, please change a good one
Er07
Water out temperature sensor problem
The water out temperature sensor is not working well, please change a good one
Er08
Phase protection
1.Change the locating of any two phase 2.Check the voltage between phase wire
Er09
System malfunction protection
Check the refrigerant system
Er10
Whole system Flow lack or flow switch problem
1.Make sure there is no air in water circulation system 2.Check the venting valve and venting valve seal ring 3.Check the main circulation pump 4.Open the venting valve to exhaust air 5.Check the main circulation pump be sure the pump is operating well
Er11
Tank Flow lack or flow switch problem
Er12
High pressure protection
Er13
Low pressure protection
1.Check the water tank to make sure it’s full of water 2.Make sure the venting valve is sealed and no air in the water tank 1.Check the temperature difference between inlet and outlet of heat pump 2.See that the thermostats are open in the radiators or the floor heating. More than the half of them must be open to the whole position. 3.Check the filter(water) and clean it if it some dust in it. 4. Check if it is air in the water system. remove from the vessels. 1.Check whether there is any ice around the heat pump 2.Check whether the fan of heat pump is working
MODEL Delivered/supplied power at 7/35℃ * COP at air 7/35℃ ** Delivered/supplied power at 2/35℃ COP at air 2/35℃ Delivered/supplied power at -7/35℃ COP at air -7/35℃ Delivered/supplied power at 7/50℃ COP at air 7/50℃ Delivered/supplied power at 2/50℃ COP at air 2/50℃ Delivered/supplied power at -7/50℃ COP at air -7/50℃