Fans | Air Handling Units | Air Distribution Products | Air Conditioning | Fire Safety | Air Curtains and Heating Products | Tunnel Fans
SYSTHERM Air-to-Water Heat Pump The most efficient solution for space heating
|
SYSTHERM
Air-to-Water Heat Pump SYSTHERM The most efficient solution for space heating SYSTHERM AIR EVO offers the highest level of performance in the market, reaching COP up to 5,0 (SYSTHERM 06) thus assuring the best solution for space heating and domestic hot water installation. Flexible use for renovation and new buldings. The built-in electronic control integrates all the parameters for a fast and easy setting of the type of space heating system. Advanced DC inverter control for the compressor, fan motor and water pump. Twin-rotary compressors assure excellent capacity performance and very low noise level. Optimized for medium-low temperature installations, like floor-heating and low temperature radiators. Very wide operation, from down to -20 °C up to +35 °C, can guarantee the production of domestic hot water all year round. The factory fitted electric heater in the base plate prevents the accumulation of defrosted water and ice. The low noise function limits the frequency of compressor and fan motor thus reducing the noise level by 4dB(A). Thanks to the Inverter control, the capacity range can rank from 30% to 130%. Two-stage electric heater supports maintaining the heating output at the desired value. 21
XA
SYSTHERM CONTROL UNIT and OUTDOOR SENSOR (included)
Hydrophylic aluminium fins of the indoor units improve the heat exchange efficiency in cooling and heating mode. Built-in electric heater assures a costant outlet temperature even during defrost cycle. Environmentally friendly R410A refrigerant.
K60D071Z
Accessories SYSTHERM TANK 35/70
SYSTHERM BOILER CONTROL
SYSTHERM AMBIENT SENSOR
Insulated buffer/mixing tank of 35 liters capacity (art. 39474) or 70liters (art. 39475). It has to be used when the water content in the piping system is below the minimum volume required by the heat pump unit or when it is necessary to create a secondary circuit indipendent from the heat pump operation.
Control system kit for boiler back-up (art. 39476). The control kit allows to set a secondary heating source like a gas boler as back-up for the heat pump. The control kit includes a dedicated Control unit with back-up functions K60D071Z and the control box for the connection to the gas boiler or other heating source.
Remote ambient sensor (art. 39473). It is used to control the temperature in the second zone (optional) connected to the standard Control unit.
XA
21
2
60D071Z
SYSTHERM |
SYSTHERM components Heat Pump unit SYSTHERM is equipped with all components to make the installation easy and reliable. Strong steel galvanized cabinet for long-lasting DC Inverter Twin-rotary compressor assures high efficiency, low vibration and low noise Generous sized heat exchanger guarantees high performance in any outdoor condition DC brushless fan motors, indipendent control of each fan High capacity Twin-rotary compressor assures excellent heating/cooling output even in harsh outdoor conditions Full DC Inverter control, only 3A start-up current Water pump driven by Inverter with manual adjustment of the available static pressure. The anti-sticking function and defrost protection prevents the water circuit to be blocked Two stage electric heater support in a stainless steel material equipped with water pressure switch and manual and automatic safety thermostat Built-in electric heater with the heating belt fitted on the base of the outdoor unit, the rain, snow or accumulation of defrosted water is avoided Electronic expansion valve regulates precisely the refrigerant flow to the heat exchange
Control unit
21
XA
Control unit designed to control heating installations with heat pump and electric support heater for residential purposes Suitable for standard applications of floor system, radiators and fancoils Four heating mode available: Comfort, Hourly Program, Economy, Vacation Easy to use with a large display Communication to heat pump unit via a two-wire bus line
3
4
|
SYSTHERM
SYSTHERM applications SYSTHERM can supply a variety of heating and cooling applications, from low temperature system to medium temperature, keeping the efficiency always at the highest level.
Floor heating application Radiant heating has a number of advantages. It is more efficient than baseboard heating and usually more efficient than forced-air heating because it eliminates duct losses. People with allergies often prefer radiant heat because it doesn‘t distribute allergens like forced air systems can. SYSTHERM has built-in functions which can SYSTHERM control kit directly control the floor-heating system. The (included) heat pump and the supplementary electric Outdoor Sensor Communication line heater are controlled in relation to a setpoint resulting from the water temperature calculated according to a water rule (according to the outside temperature) thus matching exactly UNDE R F L O O R the heating demand of the building.
HE ATING SYSTEM BOARD O.U PCB
Water Outlet Sensor
(Board A2) CWC 2
IPM S
Vibration damping hose (as accessory)
C O O L ING
Electric Heater
S
S
Pump
Vibration damping hose (as accessory)
Water Inlet Sensors
SYSTHERM Unit Buffer Tank (if insufficient volume of water) DATE
REV
TION(S) MODIFICA TION
29/11/2010
Creation
CP
02/04/2012
Buffer tank if water volume too small
CP
02
04/03/2013
Precision V ersion “FA”
CP
Low temperature radiators Radiators can be used in a wide range of water temperature and they are cost-effective way to reach and maintain ideal room temperature quickly and comfortably. Radiators react quickly and precisely to changing temperature needs, which can differ from room to room, reaching high levels of thermal comfort throughout any building.
O.U PCB
1097070G
DRG by
00 01
INVE RTE R AWHP MONOB L OC K AQUAS E T - ‘’PHIE ’’ + ‘’PHR IE ’’ WITH INTE G R ATE D E L E C TR IC S UPPORT HE ATE R APPL IC ATION 1 ZONE UNDE R F L OOR (HE ATING - C OOL ING )
04/03/2013 DATE
PB
SYSTHERM Control Kit
Comunication line
Flow Regular (accessory)
Water Pump (permanent operation) not supplied Decoupling Tank (accessory)
SYSTEM BOARD
R ADIATO R S
Discharge Valve (not supplied)
S
DATE
CP
Outdoor Sensor
(Board A2) CWC 2
IPM
DRG by
CKD by
Water Outlet Sensor
R ADIATO R S
Flexible (accessory) In Line Strainer (supplied with AWHP)
Electric Heater S
PUMP
S
Water Inlet Sensors
Flexible (accessory) Dirt Separator (accessory)
SYSTHERM Unit
REV
DATE
MODIFICA TION(S)
DRG by
00
29/11/2010
Creation
CP
01
04/04/2012
Modification message mixing tank
CP
02
04/03/2013
Precision V ersion “FA”
CP
1097072G
R ADIATO R S
INVE RTE R AWHP MONOB L OC K AQUAS E T - ‘’PHIE ’’ + ‘’PHR IE ’’ WITH INTE G R ATE D E L E C TR IC S UPPORT HE ATE R APPL IC ATION 1 ZONE R ADIATOR S L OW TE MPE R ATUR E (HE ATING ONLY)
DRG by
DATE
CP
04/03/2013
CKD by
DATE
PB
5
SYSTHERM |
Fan coils application Fan coil units may be installed in a variety of positions and require small bulding space for the installation. Outdoor Sensor Each fan coil can be controlled individually and can provide quick heat up in the room. The room temperature is adjusted by the thermostat provided with the fancoils. SYSTHERM can be directly connected to the fan coils. In case the water content is not sufficient, it is recommended to install a buffer tank in the water circuit.
Room 1
SYSTHERM Control Kit
Communication line
Thermostat Eco
Eco
Terminal unit
Room 2
Thermostat
SYSTEM BOARD O.U PCB
(BOARD A2) CWC 2
IPM S
Terminal unit
Water Outlet Sensor Flexible (accessory)
Room 3 Thermostat
Electric Heater
Eco
S
S
Water Inlet
PUMP Sensors
Flexible (accessory)
In Line Strainer (supplied with AWHP)
SYSTHERM Unit
Buffer Tank (if water volume needed)
Terminal unit
Floor heating or radiators with boiler back-up 1097071G RTE R AWHP MONOB L OC K AQUAS E T - ‘’PHIE ’’ + ‘’PHR IE ’’ The Control kit SYSTHERMO BOILER CONTROL (art. 39476) is designed INVE to control WITH INTEheating G R ATE D E L E C TRinstallations IC S UPPORT HE ATE R with a heat pump APPL IC ATION 1 ZONE TE R MINAL UNITS (HE ATING or - C OOL ING ) in boiler back-up in residential applications. It can be used for one zone with radiators floor system. The priority of heating is always given to the heat pump unit. REV
DATE
MODIFICA TION(S)
DRG by
00
29/11/2010
Creation
CP
01
04/04/2012
Modification message buffer tank
CP
02
04/03/2013
Precision V ersion “FA”
CP
DRG by
DATE
CP
04/03/2013
CKD by
DATE
PB
SYSTHERM Control Kit
Communication line
Supply 230 V/1/50 Hz
Boiler with DHW or without DHW
Mixing Valve proportional (accessory)
SA
System Control Kit K 60D071Z (accessory) Zone Board
Communication line
Heating Board
Water Pump existing (not supplied)
S
Ambiant Sensor (if control box is not in the room) (accessory)
Water Outlet Sensor
Flow Regulator
R ADIATOR S Decoupling bottle kit (accessory)
Installation to be done according directives, laws and standard trade practices
S
Water Inlet Sensor
Decoupling Bottle
or
Flow Regulator Isolation Isolation Valve Valve
UNDE R F L O O R
Outdoor Sensor
Communication line O.U PCB IPM
(Board A2) CWC 2
Outlet water sensor
Buffer Tank (if water volume in the installation is too small)
S
Flexible (accessory)
Pump
Flexible (accessory)
In Line Strainer (supplied with AWHP)
SYSTHERM Unit
MODIFICA TIONS
Dirt separator (accessory)
REV
DATE
00
23/11/2010
01
10/02/2011 Expansion vessel in AWHP
02
07/03/2013 PHIRE precision F A version
CP
03
10/04/2013 PHIE / PHRIE - F A or FB
CP
Creation
DRG by CP CP
1097061G
INVE R T E R AWHP - MO NO B L O C K AQ UAS E T “P HIE ” / “P HR IE ” B O IL E R B AC K -UP 1 Z O NE R ADIATO R S or U NDE R F L O O R “P R O P O R T IO NNAL AC T IO N” WIT H MIX ING VALVE
DRG by
DATE
CP
10/04/2013
CKD by
DATE
PB
6
|
SYSTHERM
SYSTHERM Technical features Model
SYSTHERM
Art. no. Refrigerant / Charged quantity Power supply Heating A7/W35
Heating A2/W35
Heating A7/W45
Heating A2/W45
Heating A7/W55
Heating A2/W55
Cooling A35/W18
Cooling A35/W7
kg
06 AIR EVO PH Q
14 AIR EVO PH Q
24 AIR EVO PH R
39470
39471
39472
R410A / 1,8
V/Ph/Hz Nominal capacity
kW
COP Nominal capacity
kW
COP Nominal capacity
kW
COP Nominal capacity
kW
COP Heating capacity
kW
COP Heating capacity
kW
COP Nominal capacity
kW
EER Nominal capacity
kW
EER
Electric heater support 1st + 2nd stage Nominal water flow A7/W35 Max. available water pressure
kW m³/h kPa
R410A / 3,8 220-240/1/50
R410A / 6,5 380-415/3/50
5,30
13,60
23,50
5,0
4,67
4,43
4,70
10,20
14,15
3,67
3,40
3,29
4,90
12,45
22,65
3,68
3,47
3,62
4,06
9,75
13,67
2,78
2,64
2,62
5,80
12,18
22,66
2,71
2,80
2,89
4,03
9,15
14,40
2,24
2,20
2,25
4,32
10,60
23,15
3,76
3,94
3,20
4,14
10,20
18,33
2,56
2,55
2,29
1,5 or 3 + 1,5
2 or 4 + 2
3 or 6 + 3
0,92
2,32
4,09
59
52
81
Sound pressure level Max/Quiet mode
dB(A)
39/37
44/40
44/40
Sound power level Max/Quiet mode
dB(A)
67/65
72/68
72/68
90
145
180
Net weight
kg
Compressor start-up current
A
3
3
3
Max. input current
A
11,7
22
16,5
Outdoor temperature limits
°C
Heating -20…+35 / Cooling +10…+43
Water temperature limits
°C
Heating +25…+55 / Cooling +5…+25
Sound power level according to EN 12102. Sound pressure level at a distance of 10 m on a reflective surface. In quiet operating mode the capacity output is limited to the nominal capacity.
SYSTHERM |
Dimensions SYSTHERM 06 AIR EVO PH Q
SYSTHERM 14 AIR EVO PH Q
SYSTHERM 24 AIR EVO PH R
7
8
| Systemair
Systemair Worldwide
Systemair production facilities worldwide: Skinnskatteberg, Sweden:
Langenfeld, Germany:
Hasselager, Denmark:
Head office of the Systemair group, distribution center and largest production facility with one of Europe’s most advanced R&D-centers. Frico’s central warehouse is also located here.
Production of air curtains.
Production of modular air handling units.
Hässleholm, Sweden:
Dal, Eidsvoll, Norway:
VEAB is the leading European manufacturer of electric duct heaters. Production of heating and cooling coils, electric and water based.
Production of air handling units for the Norwegian market.
Ukmerge, Lithuania: Production of smaller air handling units with energy recovery systems.
The factory in Bratislava manufactures air distribution products and EN certified fire and smoke dampers.
Maribor, Slovenia:
Madrid, Spain:
Specialized in centrifugal smoke extract fans, EN certified.
Production of air handling units for the southern European market.
Windischbuch, Germany: Production facility for fans and modular air handling units, specialized on engineered products (e.g. tunnel and jet fans). Distribution center.
Mülheim an der Ruhr, Germany: Menerga is a leading European producer of air handling units for swimming pool halls and comfort ventilation with extra high efficiency.
Bratislava, Slovakia:
Systemair |
Quality: Systemair is certified in accordance with ISO 9001; ISO 14001 and ATEX. Our research and development laboratories are one of the most modern in Europe; measurements are made in accordance with international standards like AMCA and ISO.
Bouctouche, Canada Tillsonburg, Canada Kansas City, USA
Save energy, lower running cost! Our label "Green Ventilation" features products with a high energy saving potential.All products labelled with "Green Ventilation" combine energy economy with energy efficiency.
Skinnskatteberg, Sweden Dal, Eidsvoll, Norway Hässleholm, Sweden Hasselager, Denmark Ukmerge, Lithuania Waalwijk, Niederlande Langenfeld, Germany Mülheim an der Ruhr, Germany Bratislava, Slovakia Tillières-sur-Avre, France Maribor, Slovenia Windischbuch, Germany Milano, Italy Istanbul, Turkey Madrid, Spain
Wujiang, China New Delhi, India
Hyderabad, India
Kuala Lumpur, Malaysia
Milan, Italy:
Bouctouche, Canada:
Kuala Lumpur, Malaysia:
Our factory in Italy, Systemair AC, develops and manufactures a wide range of air conditioner.
Our main North American production facility of air handling units and inline fans for commercial and residential applications is located in Bouctouche.
Production and marketing of products for Tunnel and garage ventilation.
Waalwijk, Netherlands: Holland Heating is Netherlands leading manufacturer of air handling units.
Tillsonburg, Canada:
Hyderabad, India: Production if air distribution products.
New Delhi, India:
Production of air conditioning products.
In Tillsonburg we develop, engineer, service and manufacture school classroom ventilation equipment for the American market.
Istanbul, Turkey:
Kansas City, USA:
Wujiang, China:
Tillières-sur-Avre, France:
Systemair-HSK is Turkey‘s leading manufacturer of air handling units.
Production of fans for the US market.
The factories in New Delhi and Noida manufacture grilles and diffusers.
Production of air handling units for the Asian market.
9
www.systemair.com
Systemair · July 2015