INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

TECHNICAL MANUAL & PARTS LIST DRAFT INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK63ZE-S, SRK71ZE-S ...
Author: Katrina Bishop
63 downloads 2 Views 1MB Size
TECHNICAL MANUAL & PARTS LIST DRAFT

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK63ZE-S, SRK71ZE-S

INDOOR UNIT Models SRK63ZE-S, SRK71ZE-S

OUTDOOR UNIT Models SRC63ZE-S, SRC71ZE-S

REMOTE CONTROLLER

1

GENERAL INFORMATION

1.1 Specific features The “Mitsubishi Daiya” room air-conditioner: SRK series are of split and wall mounted type and the unit consists of indoor unit and outdoor unit with refrigerant precharged in factory. The indoor unit is composed of room air cooling or heating equipment with operation control switch and the outdoor unit is composed of condensing unit with compressor. (1) Inverter (Frequency converter) for multi-steps power control ¡ Heating/Cooling The rotational speed of a compressor is changed in step in relation to varying load, to interlock with the indoor and outdoor unit fans controlled to changes in frequency, thus controlling the power. ¡ Allowing quick heating/cooling operation during start-up period. Constant room temperature by fine-tuned control after the unit has stabilized. (2) Fuzzy control ¡ Fuzzy control calculates the amount of variation in the difference between the return air temperature and the setting temperature in compliance with the fuzzy rules in order to control the air capacity and the inverter frequency. (3) Remote control flap & louver The Flap & louver can be automatically controlled by operating wireless remote control. ¡ Flap swing : The flaps swing up and down successively. ¡ Louver swing : The louvers swing left and right successively. ¡ Multi-directional Air Flow : Activating both up/down air swing and left/right air swing at the same time results in a multidirectional air flow. ¡ Memory flap : Once the Flap & louver position is set, the unit memorizes the position and continues to operate at the same position from the next time. (4) Self diagnosis function ¡ We are constantly trying to do better service to our customers by installing such judges that show abnormality of operation as follows.

RUN light

1 time flash TIMER light ON

2 time flash 6 time flash

TIMER light

Heat exchanger sensor error RUN light keeps flashing

Room temperature sensor error Indoor fan motor error

RUN light ON

RUN light 2 time flash

1 time flash

Outdoor temperature sensor error

2 time flash

Outdoor heat exchanger sensor error

4 time flash

Discharge pipe temp. sensor error

1 time flash

Current cut

2 time flash

Trouble of outdoor unit

3 time flash

Over current

5 time flash

Over heat of compressor

6 time flash

Error of signal transmission

7 time flash

Outdoor fan motor error

2 time flash

Rotor lock

1.2 How to read the model name Example :

SR K 63

Z E-S

R410A models Series No. Inverter type Product capacity Wall mounted type Split type room air-conditioner

-

1-

2

SELECTION DATA

2.1 Specifications Model SRK63ZE-S (Indoor unit) SRC63ZE-S (Outdoor unit)

(220/230/240V)

Model

SRK63ZE-S

Item

Refrigerant piping

Operation data(1)(2)

Cooling capacity(1) Heating capacity(1) Power source Cooling input Running current (Cooling) Heating input Running current (Heating) Inrush current COP Sound level Cooling Power level Noise level Sound level Heating Power level Exterior dimensions Height × Width × Depth Color Net weight Refrigerant equipment Compressor type & Q’ty Motor Starting method Heat exchanger Refrigerant control Refrigerant(3) Refrigerant oil Deice control Air handling equipment Fan type & Q’ty Motor (Cooling) Air flow (at High) (Heating) Air filter, Q’ty Shock & vibration absorber Electric heater Operation control Operation switch Room temperature control Pilot lamp Safety equipment O.D Connecting method Attached length of piping

Insulation Drain hose Power source supply Size × Core number Connecting method Accessories (included) Optional parts Connection wiring

W W

SRC63ZE-S 6300 (900~7100) 7100 (900~9000) 1 Phase, 220-240V, 50Hz 1.84 8.4/8.1/7.7 1.86 8.5/8.2/7.8

kW A kW A A

Cooling: 3.42 Heating: 3.82 Hi 43, Me 39, Lo 33, ULo 26

47

dB

58 Hi 44, Me 38, Lo 32, ULo 27

62 48

59

63

mm

318 × 1098 × 248

750 × 880 × 340

kg

Yellowish white 18

Stucco white 65



TNB220FLBM1 (Twin rotary type) × 1

kW

– 1.3 – Line starting Slit fins & inner grooved tubing Straight fin & inner grooved tubing Capillary tubes + Electronic expansion valve R410A 1.9 (Pre-Charged up to the piping length of 15m) 0.67 (MEL56) Microcomputer control

kg R

W CMM

Tangential fan × 1

Propeller fan × 1

46 18.5 21 Polypropylene net (washable) × 2 – –

86 46 46 – Cushion rubber (for compressor) –

Wireless-Remote controller



Microcomputer thermostat – RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange) Compressor overheat protection, Heating overload protection (High pressure control), Overcurrent protection, Frost protection, Serial signal error protection, Indoor fan motor error protection, Cooling overload protection mm (in)

Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″) Flare connecting Liquid line: 0.70m – Gas line : 0.63m Necessary (Both sides) Connectable Terminal block (Screw fixing type) 1.5 mm2 × 4 cores (Including earth cable) Terminal block (Screw fixing type) Mounting kit, Clean filter (Allergen clear filter × 1, Photocatalytic washable deodorizig filter × 1) –

Notes (1) The data are measured at the following conditions. Item Operation Cooling Heating

Indoor air temperature DB WB 27ºC 19ºC 20ºC –

Outdoor air temperature DB WB 35ºC 24ºC 7ºC 6ºC

The piping length is 7.5m. (2) The operation data are applied to the 220/230/240V districts respectively. (3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping. (Purging is not required even for the short piping.) If the piping length is longer, when it is 15 to 30 m, add 25g refrigerant per meter.

-

2-

Standards ISO-T1, JIS C9612 ISO-T1, JIS C9612

Model SRK71ZE-S (Indoor unit) SRC71ZE-S (Outdoor unit)

(220/230/240V)

Model

SRK71ZE-S

Item

Operation data(1)(2)

Cooling capacity(1) Heating capacity(1) Power source Cooling input Running current (Cooling) Heating input Running current (Heating) Inrush current COP Cooling

Sound level Power level

Heating

Sound level Power level

Noise level

Exterior dimensions Height × Width × Depth Color Net weight Refrigerant equipment Compressor type & Q’ty Motor Starting method Heat exchanger Refrigerant control Refrigerant(3) Refrigerant oil Deice control Air handling equipment Fan type & Q’ty Motor Air flow (at High)

W W kW A kW A A

Hi 45, Me 40, Lo 34, ULo 26 60

52 67

Hi 46, Me 40, Lo 34, ULo 27 60

49 64

mm

318 × 1098 × 248

750 × 880 × 340

kg

Yellowish white 18

Stucco white 65



TNB220FLBM1 [Twin rotary type] × 1

dB

– 1.3 – Line starting Slit fins & inner grooved tubing Straight fin & inner grooved turbing Capillary tubes + Electronic expansion valve R410A 1.9 (Pre-Charged up to the piping length of 15m) 0.67 (MEL56) Microcomputer control

kg R

W CMM

Air filter, Q’ty Shock & vibration absorber Electric heater Operation control Operation switch Room temperature control Pilot lamp Safety equipment

Refrigerant piping

7100 (900~8000) 8000 (900~10500) 1 Phase, 220-240V, 50Hz 2.21 10.1/9.7/9.3 2.21 10.1/9.7/9.3 10.1/9.7/9.3 Cooling: 3.21 Heating: 3.62

kW

(Cooling) (Heating)

SRC71ZE-S

Tangential fan × 1

Propeller fan × 1

46 20 22.5 Polypropylene net (washable) × 2 – –

86 56 49 – Cushion rubber (for compressor) –

Wireless-Remote controller



Microcomputer thermostat – RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange) Compressor overheat protection, Heating overload protection (High pressure control), Overcurrent protection, Frost protection, Serial signal error protection, Indoor fan motor error protection, Cooling overload protection

O.D Connecting method Attached length of piping

Insulation Drain hose Power source supply Size × Core number Connecting method Accessories (included) Optional parts Connection wiring

mm (in)

Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″) Flare connecting Liquid line: 0.70m – Gas line : 0.63m Necessary (Both sides) Connectable Terminal block (Screw fixing type) 1.5 mm2 × 4 cores (Including earth cable) Terminal block (Screw fixing type) Mounting kit, Clean filter (Allergen clear filter × 1, Photocatalytic washable deodorizig filter × 1) –

Notes (1) The data are measured at the following conditions. Item Operation Cooling Heating

Indoor air temperature DB WB 27ºC 19ºC 20ºC –

Outdoor air temperature DB WB 35ºC 24ºC 7ºC 6ºC

The piping length is 7.5m. (2) The operation data are applied to the 220/230/240V districts respectively. (3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping. (Purging is not required even for the short piping.) If the piping length is longer, when it is 15 to 30 m, add 25g refrigerant per meter.

-

3-

Standards ISO-T1, JIS C9612 ISO-T1, JIS C9612

2.2 Range of usage & limitations Models SRK63ZE-S, 71ZE-S

Item Indoor return air temperature (Upper, lower limits)

Cooling operation: Approximately 18 to 32°C Heating operation: Approximately 15 to 30°C

Outdoor air temperature (Upper, lower limits)

Cooling operation: Approximately -15 to 46°C Heating operation: Approximately -15 to 21°C

Refrigerant line (one way) length

Max. 30m

Vertical height difference between outdoor unit and indoor unit

Max. 20m (Outdoor unit is higher) Max. 20m (Outdoor unit is lower) Rating ± 10%

Power source voltage Voltage at starting

Min. 85% of rating

Frequency of ON-OFF cycle

Max. 10 times/h

ON and OFF interval

Max. 3 minutes

2.3 Exterior dimensions (1) Indoor unit Models SRK63ZE-S, 71ZE-S Unit: mm

A 1098

248

3

9 48

318

Piping hole right (left)

Terminal block 55

Indoor unit 886 450

49.5

50

Installation board

106 299 50

150

349

8.5

106

221.5

4 19

17.3 1098

51.2

64

4 43.5

77 Piping for Gas (ø15.88) 633.5 Piping for Liquid (ø6.35) 703.5 Drain hose 772 (ø16) Piping hole (ø65) Piping hole (ø65)

55

53.5

55

7.7

44.5

47

25

44.5 301.8

60 25

VIEW A

-

4-

(2) Outdoor unit Models SRC63ZE-S, 71ZE-S 532

223 60

Drain Holes

380 418

Unit: mm

2-ø15

61 150

580 880

25.8 29.8

150

19

61

340

47.5

19

15

87.9 Terminal block

742.2

165.5

Service valve (Liquid) Flare fitting ø6.35 (1/4")

25.1

103.3

24.1

30°

48.5

30°

Service valve (Gas) Flare fitting ø15.88 (5/8")

2.4 Piping system Models SRK63ZE-S, 71ZE-S Indoor unit

Outdoor unit

Cooling cycle Heating cycle

Flare connection

Piping (Gas) ø15.88 Humidity sensor

Service valve (Gas)

Outdoor air temp. sensor

Check joint

4 way valve Accumulator

Room temp. sensor

Heat exchanger sensor

Discharge pipe temp. sensor

Heat exchanger

Heat exchanger

Compressor

Piping (Liquid) ø6.35

Service valve (Liquid) Capillary tube

Flare connection

Electronic expansion valve

Strainer

-

5-

Capillary tube

Heat exchanger sensor

2.5 Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification ✕ Correction factors as follows. (1) Coefficient of cooling and heating capacity in relation to temperatures

(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor units.

Piping length [m]

7

10

15

20

25

30

Cooling

1.0

0.99

0.975

0.965

0.95

Heating

1.0

1.0

1.0

1.0

1.0

(3) Correction relative to frosting on outdoor heat exchanger during heating In additions to the foregoing corrections (1), (2) the heating capacity needs to be adjusted also with respect to the frosting on the outdoor heat exchanger. Air inlet temperature of outdoor unit in ˚CWB

-10

-9

-7

-5

-3

-1

1

3

5

Adjustment coefficient

0.95

0.94

0.93

0.91

0.88

0.86

0.87

0.92

1.00

How to obtain the cooling and heating capacity Example : The net cooling capacity of the model SRK63ZE-S with the piping length of 15m, indoor wet-bulb temperature at 19.0˚C and outdoor dry-bulb temperature 35˚C is Net cooling capacity =

6300

SRK63ZE-S

-

6-



0.975

Length 15m



1.0

=

Factor by air temperatures

6143 W

2/N

1

1

Th6

CNB

EEV

Wireless R-AMP

Th1 Th2 Th3

Terminal block To wired remote controller (option)

C1 Symbol Th3 Th4 Th5 Th6 ZNR 20S EEV DS

Parts name Humidity sensor Heat exch.sensor(Outdoor unit) Outdoor air temp.sensor Discharge pipe temp.sensor Varistor 4 way valve(coil) Electronic expansion valve Diode stack

Symbol L RL XR1 XR2 XR3 XR4 XR5

Parts name Inductor Inspection lamp Operation indication (DC12) Heating indication (DC12) ON indication for CM(DC12) Check indication (DC12) Distant operation

AF-L2 OR L

PWB2

N1 L IC2 N2 P2

C1

F 250V 20A

N_1

+

Parts name Compressor motor Fuse Fan motor(Indoor) Fan motor(Outdoor) Flap motor Louver motor Room temp.sensor Heat exch.sensor(Indoor unit)

CNH

AF-L1 OR

P_1

RD

P_1 N

+

CM F FMI FMO SM LM1,2 Th1 Th2

~ DS1

N_1 BK

+

Symbol

~

1 CNG 2

C1

Meaning of marks

BL GR AC.L

AC.N CNG -

XYZ

Display SM

AC.N AC.L BL GR

+

XYZ

Color symbol Black BK Blue BL Orange OR Red RD Y Yellow WH White Y/G Yellow/Green GR Green

F 250V 2A

PWB3

P Q1 WV U

CM

Power transistor

CNF

RD WH BK

7-

CNG

G3 N-1 L-1

BK WH RD

-

CNE

F 250V 20A

PWB1

CNG

Th5

CNO

CNH

CNX CNM

CNT

RD DC-P

LM1

Th4

CNJ

CNY

G2 6 4

F1 250V 2A

20S

XR5

LM2

N L

CNC CNB CND Switching power circuit

Y/G Printed circuit board

CNT

Power Source 1 Phase 220-240V 50Hz

Y/G WH BK

J

HEATER

Option

ZNR XR1 XR2 XR3 XR4

G

F 250V 3.15A

2/N

Y/GN RD WH BK

CNI BK DC-N

R/L

RD

S/N

3

FMo

Y/GN

BK

JEM-A

WH

HA

3

ELECTRICAL DATA

FMI

6 5 4 3 1 CNU

3

BL Y WH BK RD

3.1 Electrical wiring

Y/GN RD WH BK

Heat exchanger

Outdoor unit TB TB

Models SRK63ZE-S, 71ZE-S

Indoor unit

4

OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER

4.1 Operation control function by remote control switch Remote controller Models All models S Operation section FAN SPEED button Each time the button is pushed, the cator is switched over in turn.

OPERATION MODE select button indi-

Each time the button is pushed, the cator is switched over in turn.

indi-

ON/OFF button

HI POWER/ECONO button

Press for starting operation, press again for stopping.

This button changes the HI POWER/ ECONOMY mode.

AIR FLOW (UP/DOWN) button This button changes the flow (up/down) mode.

ALLERGEN button This button selects ALLERGEN CLEAR operation.

AIR FLOW (LEFT/RIGHT) button This button changes the air flow (left/right) mode.

TEMPERATURE button This button sets the room temperature. (This button changes the present time and TIMER time.)

CANCEL button This button cancels the ON timer,OFF timer, and SLEEP operation.

SLEEP button

OFF TIMER button

This button changes to SLEEP operation.

This button selects OFF TIMER operation.

CLEAN switch

RESET switch

This switch changes the CLEAN mode.

ON TIMER button This button selects ON TIMER operation.

Switch for resetting microcomputer.

• The above illustration shows all controls, but in practice only the relevant parts are shown.

TIME SET UP switch Switch for setting the time.

S Indication section ON/OFF TIMER indicator

SLEEP indicator

Indicates during ON/OFF TIMER operation.

Indicates during SLEEP operation.

OPERATION MODE Indicator TEMPERATURE Indicator

Indicates selected operation with [

Indicates set temperature. (Does not indicate temperature when operation mode is on AUTO)

(Auto) •

(Cool) •

lamp.

(Heat) •

(Dry)]

TIME Indicator Indicates present time or timer setting time.

FAN SPEED Indicator Indicates set air flow rate with

AIR FLOW Indicator

lamp.

Shows selected flap and louver mode.

ALLERGEN CLEAR Indicator Indicates during ALLERGEN CLEAR operation.

HI POWER/ECONO MODE Indicator

CLEAN Indicator

Indicates during High power/economy mode operation.

Indicates during CLEAN operation.

-

8-

Unit indication section Models All models RUN (HOT KEEP) light (green) • Illuminates during operation. • Blinks at air flow stop due to the ‘HOT KEEP’.

TIMER light (yellow) Illuminates during TIMER operation.

HI POWER light (green) Illuminates during HI POWER operation.

ECONOMY light (orange) Illuminates during ECONOMY operation.

-

9-

5

INSTALLATION

R410A refrigerant is used for this air-conditioner. Execute the installation work while taking care of the following points in addition to the general caution items.

5.1 Installation tools Prepare the following special tools for R410A in addition to the general-purpose tools. ¡Flare tool

¡Vacuum pump adaptor

¡Gauge manifold

¡Leak detector

¡Charge hose

5.2 Refrigerant piping ¡Use the copper pipe that has less than 40 mg/10 m of oil adhesion and 0.8 mm of wall thickness. Never use the thin walled pipe the thickness of which is less than 0.8 mm. ¡Use the flare nut attached to the air-conditioner.

5.3 Pipe connection (1) Pipe working Dimension "B" Copper pipe dia.

Dimension "A" (mm)

Liquid side ø6.35

9.1

ø9.52

13.2

ø12.7 ø15.88

Gas side

Dimension "B" (mm)

Copper pipe dia.

Clutch type flare tool for R410A ø6.35

0.0 ~ 0.5

ø9.52

0.0 ~ 0.5

16.6

ø12.7

0.0 ~ 0.5

19.7

ø15.88

0.0 ~ 0.5

Flare tool bar

Copper pipe

(2) Tightening torque ¡The tightening torque is shown below. Copper pipe dia. Liquid side Gas side

Across flats of flare nut Tightening torque N·m (kgf·m) (mm)

ø6.35

17

14 ~ 18 (1.4 ~ 1.8)

ø9.52

22

33 ~ 42 (3.3 ~ 4.2)

ø12.7

24

50 ~ 62 (5.0 ~ 6.2)

ø15.88

27

63 ~ 77 (6.3 ~ 7.7)

(3) Vacuuming ¡

The charge hose for R22 cannot be connected because the service port diameter is different from the conventional one. Use the special charge hose for R410A.

¡

Use the vacuum pump adapter for reverse flow prevention to check the reverse flow of vacuum pump oil. If oil flows back to the air-conditioner, it causes failure of refrigerant cycle. Service valve (Two-way)

Compound Pressure pressure gauge gauge -101kPa (-76cmHg)

Handle Lo Service valve (3-way) Charge Hose Service Port (Special for R410A)

Vacuum pump adaptor (For reverse flow prevention) (Special for R410A)

-

10 -

Gauge manifold (Special for R410A)

Handle Hi Charge hose (Special for R410A) Vacuum Pump

PARTS LIST (Main parts) (1) Indoor unit Parts No. Parts Name

No.

SRK71ZE-S

SRK63ZE-S 1

PANEL ASSY, FRONT

RKW102A200

2

PANEL, FRONT

RKW122A200

3

PANEL, AIR INLET

RKW435A201

4

GRILLE ASSY, AIR OUTLET

RKW435A202

5

MOTOR, DC

SSA512T072

6

IMPELLER

SSA431G043A

7

HEAT EXCH ASSY(AIR)

RKW301A200A

8

PWB ASSY

9

CONTROL ASSY, REMOTE

RKW505A200A

RKW505A200 RKW502A200

(2) Outdoor unit Parts No. No.

Parts Name SRC71ZE-S

SRC63ZE-S 1

PANEL ASSY, FRONT

RCR122A001

2

PANEL, TOP

RCR124A001

3

GRILLE, AIR OUTLET

RCR435A001

4

BRACKET, MOTOR

RCR116A001

5

MOTOR, DC

SSA512T076

6

FAN, PROPELLER

SSA431B247

7

BASE ASSY

RCR111A001

8

HEAT EXCH(AIR)

RCR311A001

9

VALVE, S(4WAY)

SSA382C078

10

COIL, SOLENOID

SSA382F027B

11

COMPRESSOR ASSY

PCA201A048A

12

PWB ASSY(MAIN)

RCR505A001

13

PWB ASSY(POWER)

RCR505A002

14

PWB ASSY(CAPACITOR)

15

VALVE, BODY(EXP)

SSA387F035

16

COIL, SOLENOID

SSA382F210L

RPC505A852B

-

11 -

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER

Air-Conditioning & Refrigeration Systems Headquarters 16-5, 2-chome, Kounan, Minato-ku, Tokyo, 108-8215, Japan Fax : (03) 6716-5926