EFLAME 1202
STOKVIS Energy Systems maintenance and after sales service You can be sure that your new Stokvis product is the very best of its type in design, materials and construction. However to obtain the maximum benefits from your quality product, it is essential that it is maintained at maximum efficiency throughout its long working life. For this reason, STOKVIS Energy Systems provides full UK cover with factory trained engineers to offer you a total service opportunity throughout the year. This ensures that your equipment can be checked, serviced and, if
ENERGY PRODUCTS
necessary, adjusted to ensure maximum energy saving performance. Also, in the unlikely event of a breakdown, repairs can be tackled
High Efficiency
speedily and cost effectively – wherever you are in the UK. Just phone,
and Condensing
fax or e-mail STOKVIS Energy Systems for prompt professional attention
Gas Fired Boilers
to your needs.
• Hot Water Plate Heat Exchanger Packages
The company
•
Since the early 1980’s , STOKVIS Energy Systems has been acknowledged as the vanguard in it’s field for both quality of products and customer service.
High Efficiency Sanitary Hot Water Packages • Dual Fuel Boilers
It is our dedicated objective to continue
•
to excel at providing you our customers
Pressurisation and Booster Sets
and partners with both the products
•
and services you need in these most
Direct Gas Fired
demanding and dynamic times both now
Air Heating and
and into the future.
Ventilating Systems •
Ivan Thompson Managing Director
Steel Panel and Low Temperature Radiators • Packaged Plant Rooms •
ECONOFLAME STOKVIS INDUSTRIAL BOILERS (INTERNATIONAL) LIMITED 96R Walton Road East Molesey Surrey KT8 0DL TELEPHONE 08707 707747 • FACSIMILE 08707 707767 Email:
[email protected] • Website: http://www.stokvisboilers.com
EconoFlame A3 03.indd 1
COMMERCIAL & INDUSTRIAL BOILERS
09/12/2002, 16:03:08
ECONOFLAME BOILERS R3400
ECONOFLAME SERIES
R3600
Since 1985 Stokvis have been offering a range of fully modulating, high efficiency gas fired boilers. Researched and developed over the years, evolving through and culminating in the most comprehensive ‘state of the art’ premix, ultra low NOx and condensing range of products :- all exceeding part L Building Regulations; the full range of premix models are ECA listed, as is the R18 atmospheric range.
R2000 & R18 Series Features And Benefits ECONOFLAME FEATURES • Modulated gas valve and secondary air damper operated by servomotor. • Matching of part load conditions from 100%down to 20%. More efficient at part loads than conventional boilers, obviating need for many modules. • Gas and secondary air ratios controlled from one source. No possibility of error in control. • Servomotor signals indicate load conditions. Allows boilers to be sequenced for optimum efficiency. • Damper insulated, preventing downward heat radiation. Obviating requirement for heat absorbent base and helps maintain high efficiency.
• Atmospheric stainless steel, gas burner.
A B C D E F G H I J K L M N
— — — — — — — — — — — — — —
Integral Draught Diverter Servomotor Modulated Gas valve Gas supply Primary air Operating mechanism Secondary air Flue deflector Casing Heat exchanger Insulation Burner bars Air diffuser Secondary air damper
H I
J A
K
B
ECONOFLAME BOILER RANGE TECHNICAL DATA
C L
D E
M
F G
R3400 Type
R3600
R3401 R3402 R3403 R3404 R3405 R3406
R3601 R3602 R3603 R3604 R3605
N
• Efficiency Curves Efficiency curves for different types of boilers
• Quiet in operation. Can be installed in areas where noise restrictions are paramount. • Complete burner including all gas and air controls can be removed on wheels. Easy to maintain, labour costs kept to a minimum. • Primary air controlled by inducement from modulated gas. No need for sophisticated controls and complicated maintenance. • Even secondary air distribution across burner. Ensuring even flame and high efficiency.
Nominal heat output
kW
657
729
853
965
1078 1189
kW
631
739
836
934
1031
Nominal heat input (nett. CV)
kW
702
784
917
1038 1159 1279
kW
653
764
865
966
1066
kW
176
196
229
260
kW
187
218
247
276
305
1
Minimum heat output
290
320
2
Gross thermal efficiency in %
Gas consumption
Gas consumption
Gas consumption
m³/h 64.5
71.9
84.1
95.2 106.3 117.3
m³/h
59.9
70.1
79.4
88.6
97.8
m³/h
24.6
27.4
32.1
36.3
40.6
44.8
m³/h
22.8
26.7
30.3
33.8
37.3
Water volume
ltr
50
53
70
75
80
85
ltr
61
78
83
92
97
Max. working pressure
bar
6
6
6
6
6
6
bar
6
6
6
6
6
DN65 PN6 DN80 PN6
DN65 PN6 DN80 PN6
natural gas H (10,9 kWh/m3) 3
Propane 4
5
1 Econoflame boiler 2 Power boiler 2-stage firing 3 Power boiler on-off 4 Atmospheric boiler 2-stage 5 Atmospheric boiler on-off
Gas connection
Rp2" Rp2" Rp2" Rp2"
Water connections
DN65 PN6
DN65 PN6
DN80 PN6
DN80 PN6
DN65 PN6 DN80 PN6
DN65 PN6
DN80 PN6
DN80 PN6
DN65 PN6 DN80 PN6
Rp2" Rp2" Rp2"
Flue connection
mm
300
350
350
400
400
400
mm
300
350
350
400
400
Electrical supply
Phase
3
3
3
3
3
3
Phase
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Hz
50
50
50
50
50
Fuse
A
16
16
20
20
20
20
A
16
16
20
20
20
Boiler output in %
with stainless steel baffles. • High conductivity of copper. Meaning minimum size of heat exchanger, maximum output. • Copper resistant to thermal shock. Giving longer lifetime expectancy of heat exchanger (5 year guarantee) • Baffles give maximum turbulence of flue gases. Maximum heat extraction from flue gases giving high efficiency. • Substantially lighter than Cast Iron / Welded Steel boilers. Structural limitations are overcome when boilers are located in roof top plantrooms.
The R2200
is a fan assisted model with a two stage burner and is similar in design to the R2000 series.
• Smaller flue diameter than the atmospheric boilers. Ideally suited for replacement of cast iron/steel shell pressure jet boilers.
100
width
mm
1330 1330 1130 1130 1330 1330
mm
1330 1130 1130 1330 1330
height
mm
1355 1355 1355 1355 1355 1355
mm
1355 1355 1355 1355 1355
length
mm
2265 2265 2653 2653 2658 2658
mm
2265 2653 2653 2658 2658
99 98
Weight, empty, ± 5 %
97
kg
675
740
840
950
1070 1200
kg
800
900
1010 1160 1290
96 95
Table Technical Data
94 93 92 91 90 50 55 60 65 70 75 80 85 90 95 100 Capacity %
EconoFlame A3 03.indd 4
Dimensions
R2200 Efficiency Figures (weather compensated)
Efficiency (nett cv) %
• Nine/eighteen tube extruded fin, copper heat exchanger
- Heat output measured with :
60 - 80 °C
60 - 80 °C
- Gas consumption at
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
- Gas specification
II 2H3P
II 2H3P
- Appliance category
B23 C53 C33 C63
B23 C53 C33 C63
- Protection degree
IP20
IP20
09/12/2002, 16:07:27
The R2700, R3400 Models
ECONOFLAME BOILERS R2700
• • • • • • • • •
R2900
Premix Fully Modulating boiler Ultra low NOx Higher efficiency than atmospheric models Smaller footprint than atmospheric models Smaller flue diameter than atmospheric models Stainless steel construction, high build quality Integral primary boiler pump BMS compatible Semi condensing capability NO MINIMUM return temperature requirements
R300,R2900 & R3600 MODELS • All the features listed above PLUS FULLY CONDENSING EFFICIENCY ALL EXCEED PART ‘L’ BUILDING REGULATION REQUIREMENTS ALL INCLUDED ON THE ENHANCED CAPITAL ALLOWANCE (ECA) SCHEME ENERGY TECHNOLOGY PRODUCT LIST. ECONOFLAME R2700 / R2900
ECONOFLAME BOILER RANGE TECHNICAL DATA R2900
R2700 R2701 R2702 R2703 R2704 R2705 R2706 R2707 R2708 R2709
R2900 R2901 R2902 R2903 R2904 R2905 R2906 R2907 R2908 R2909
Nominal heat output
kW
95
119
141
178
218
299
374
445
521
597
kW
96
122
153
188
257
322
383
449
514
566
Nominal heat input (nett. CV)
kW
101
126
151
190
233
319
400
475
557
638
kW
99
126
158
194
266
333
396
464
532
585
kW
25
33
38
48
58
80
100
119
139
160
kW
25
33
40
48.5
66
83
100
112
133
146
Gas consumption
Gas consumption
natural gas H (10,9 kWh/m3)
m³/h
9.3
11.6
13.9
17.4
21.4
29.3
36.7
43.6
51.1
58.5
m³/h
9.1
11.6
14.5
17.8
24.4
30.5
36.3
42.6
48.8
53.7
Propane
m³/h
3.5
4.4
5.3
6.6
8.2
11.2
14.0
16.6
19.5
22.3
m³/h
3.5
4.4
5.5
6.8
9.3
11.6
13.8
16.2
18.6
20.5
Water volume
ltr
18
18
18
19
20
35
38
41
44
47
ltr
20
20
21
22
39
42
45
48
55
58
Max. working pressure
bar
6
6
6
6
6
6
6
6
6
6
bar
6
6
6
6
6
6
6
6
6
6
Gas connection
Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" Rp2"
Water connections
R2"
R2"
R2"
R2"
R2"
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" R2"
R2"
R2"
R2"
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
Flue connection
mm
150
150
150
180
200
200
250
250
300
300
mm
150
150
180
200
200
250
250
250
300
300
Electrical supply
Phase
3
3
3
3
3
3
3
3
3
3
Phase
3
3
3
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
50
50
50
Hz
50
50
50
50
50
50
50
50
50
50
Fuse
A
10
10
10
10
10
10
10
10
10
16
A
10
10
10
10
10
10
10
10
10
10
Dimensions
width
mm
830
1130 1130
mm
830
height
mm
1355 1355 1355 1355 1355 1355 1355 1355 1355 1355
mm
1355 1355 1355 1355 1355 1355 1355 1355 1355 1355
length
mm
1535 1535 1535 1535 1535 1918 1918 1908 1908 1908
mm
1535 1535 1535 1535 1918 1918 1908 1908 1908 1958
Weight, empty, ± 5 %
kg
325
830
325
830
325
830
340
930
360
830
500
830
525
930
560
615
645
kg
340
830
340
830
355
Table Technical Data - Heat output measured with :
60 - 80 °C
60 - 80 °C
- Gas consumption at
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
- Gas specification
II 2H3P
II 2H3P
- Appliance category
B23 C53 C33 C63
B23 C53 C33 C63
- Protection degree
IP20
IP20
EconoFlame A3 03.indd 3
Additional Condensing Heat Exchanger (R2900)
Gas consumption
930
375
830
530
830
555
930
590
Efficiency Figures
1130 1130 1230
645
705
735
Efficiency (nett cv) %
Minimum heat output
Efficiency Figures @ 60° C Flow, 40° C Return.
Efficiency Figures @ 80° C Flow, 60° C Return.
107 106 105 104 103 102 101 100 99 98 97 96 95 94 93
107 106 105 104 103 102 101 100 99 98 97 96 95 94 93
Efficiency (nett cv) %
R2700 Type
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %
09/12/2002, 16:07:09
ECONOFLAME BOILERS
ECONOFLAME BOILERS
R2000
R18
R2200
ECONOFLAME BOILER RANGE TECHNICAL DATA
ECONOFLAME BOILER RANGE TECHNICAL DATA
R2200
R18
R2000 Type
R300
R2017 R2022 R2028 R2034 R2041 R2048 R2056 R2066 R2077 R2090 R2105 R2122
132
154
180
210
244
280
Type
R300
2207 2210 2213 2216 2220 2224 2228
R301 R302 R303 R304 R305 R306 R307
Nominal heat output
kW
57.7
74.6
95.8 116.7 139.1 162.7 190.7 222.1 261.1 309.0 361.0 425.0
kW
481
558
649
756
875
1002
Nominal heat output
kW
81.3 116.4 151.5 186.7 233.9 280.9 328.5
kW
70
86
114
139
185
230
274
Nominal heat input (nett. CV)
kW
65.5
84.8 107.7 131.6 158.6 185.5 217.4 253.3 296.2 348.0 403.9 470.7
kW
538
625
727
846
980
1122
Nominal heat input (nett. CV)
kW
88.2 126.0 163.8 201.6 252.0 302.4 352.8
kW
74
91
121
147
194
243
289
Minimum heat output
kW
-
kW
-
-
-
-
-
-
kW
16
20
27
33
44
55
65
-
-
-
-
-
-
-
-
-
-
-
Gas consumption
Gas consumption
Minimum heat output
kW
Gas consumption
natural gas H (10,9 kWh/m3)
m³/h
6.0
7.9
9.9
12.2
14.7
17.2
20.2
23.5
27.5
32.3
37.4
43.6
m³/h 49.3
57.9
67.4
78.4
90.8 104.0
Propane
m³/h
2.3
2.9
3.8
4.7
5.6
6.6
7.7
8.9
10.5
12.3
14.3
16.6
m³/h 19.0
22.1
25.7
29.9
34.7
39.7
Water volume
ltr
5.6
5.9
6.2
6.5
6.9
7.3
7.7
8.3
8.9
9.6
10.5
11.4
ltr
22.0
23.2
24.6
26.3
28.1
30.1
Max. working pressure
bar
11
11
11
11
11
11
11
11
11
11
11
11
bar
11
11
11
11
11
11 DN65 PN16 DN80 PN16
Gas connection
¾"
¾"
1"
1"
1"
1"
1½"
1½"
1½"
1½"
1½"
1½"
2"
2"
2"
2"
Water connections
2"
2"
2"
2"
2"
2"
DN65 PN16
DN65 PN16
DN65 PN16
DN65 PN16
DN65 PN16
DN65 PN16
DN80 PN16
DN80 PN16
DN80 PN16
DN80 PN16
DN65 PN16 DN80 PN16
-
-
-
-
-
-
-
Gas consumption
Gas consumption
natural gas H (10,9 kWh/m3)
m³/h
9.3
13.3
17.3
21.3
26.7
32.0
37.3
m³/h
6.79
8.35 11.10 13.49 17.80 22.29 26.51
Propane
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
m³/h
2.6
3.2
4.2
5.15
6.8
8.5
10.1
Water volume
ltr
6.2
6.9
7.7
8.5
9.6
10.5
11.4
ltr
13
15
17
19
36
39
42
Max. working pressure
bar
6
6
6
6
6
6
6
bar
6
6
6
6
6
6
6
Gas connection Water connections
1"
1¼"
1¼"
1¼"
1¼"
1½"
1½"
Rp¾" Rp¾" Rp¾" Rp¾"
R1"
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
R1½" R1½" R1½" R1½"
R2"
R1½" R1½" R2"
R2"
Flue connection
mm
200
225
250
250
300
300
350
350
400
400
450
450
mm
450
500
550
600
650
700
Flue connection
mm
150
180
200
200
250
250
300
mm
100
100
100
150
180
200
200
Electrical supply
Phase
1
1
1
1
1
1
1
1
1
1
1
1
Phase
1
1
1
1
1
1
Electrical supply
Phase
1
1
1
1
1
1
1
Phase
1
1
1
1
1
1
1
Frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
Hz
50
50
50
50
50
50
Frequency
Hz
50
50
50
50
50
50
50
Hz
50
50
50
50
50
50
50
Fuse
A
6
6
6
6
6
6
6
6
6
6
6
6
A
6
6
6
6
6
6
Fuse
A
6
6
6
6
6
6
6
A
10
10
10
10
10
10
10
width
mm
786
786
786
786
786
786
786
mm
500
600
700
800
600
700
800
Dimensions
Dimensions
depth
mm
1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017
mm 1633 1633 1633 1633 1618 1618
height
mm
1612 1612 1612 1612 1612 1612 1612 1612 1632 1632 1652 1652
mm 1795 1795 1795 1795 1895 1895
height
mm
1440 1440 1440 1440 1440 1440 1440
mm
1205 1240 1240 1240 1240 1240 1240
length
mm
820
898
994
1090 1200 1312 1438 1598 1772 1978 2216 2486
mm 1461 1636 1842 2080 2350 2636
length
mm
1016 1226 1436 1646 1926 2206 2486
mm
635
635
635
635
890
890
890
kg
195
210
225
240
kg
120
140
160
180
250
270
290
Weight, empty, ± 5 %
260
280
305
330
365
400
440
490
kg
620
660
705
760
820
885
Weight, empty, ± 5 %
kg
165
200
245
285
340
375
440
Table Technical Data
Table Technical Data 60 - 80 °C
- Heat output measured with :
60 - 80 °C
60 - 80 °C
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
- Gas consumption at
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
II 2H3P
II 2H3P
- Gas specification
I 2H
II 2H3P
- Appliance category
B11
B11
- Appliance category
B14
B23 C53 C33 C63
- Protection degree
IP30
IP30
- Protection degree
IP20
IP20
- Heat output measured with :
60 - 80 °C
- Gas consumption at - Gas specification
EconoFlame A3 03.indd 2
09/12/2002, 16:06:54
ECONOFLAME BOILERS
ECONOFLAME BOILERS
R2000
R18
R2200
ECONOFLAME BOILER RANGE TECHNICAL DATA
ECONOFLAME BOILER RANGE TECHNICAL DATA
R2200
R18
R2000 Type
R300
R2017 R2022 R2028 R2034 R2041 R2048 R2056 R2066 R2077 R2090 R2105 R2122
132
154
180
210
244
280
Type
R300
2207 2210 2213 2216 2220 2224 2228
R301 R302 R303 R304 R305 R306 R307
Nominal heat output
kW
57.7
74.6
95.8 116.7 139.1 162.7 190.7 222.1 261.1 309.0 361.0 425.0
kW
481
558
649
756
875
1002
Nominal heat output
kW
81.3 116.4 151.5 186.7 233.9 280.9 328.5
kW
70
86
114
139
185
230
274
Nominal heat input (nett. CV)
kW
65.5
84.8 107.7 131.6 158.6 185.5 217.4 253.3 296.2 348.0 403.9 470.7
kW
538
625
727
846
980
1122
Nominal heat input (nett. CV)
kW
88.2 126.0 163.8 201.6 252.0 302.4 352.8
kW
74
91
121
147
194
243
289
Minimum heat output
kW
-
kW
-
-
-
-
-
-
kW
16
20
27
33
44
55
65
-
-
-
-
-
-
-
-
-
-
-
Gas consumption
Gas consumption
Minimum heat output
kW
Gas consumption
natural gas H (10,9 kWh/m3)
m³/h
6.0
7.9
9.9
12.2
14.7
17.2
20.2
23.5
27.5
32.3
37.4
43.6
m³/h 49.3
57.9
67.4
78.4
90.8 104.0
Propane
m³/h
2.3
2.9
3.8
4.7
5.6
6.6
7.7
8.9
10.5
12.3
14.3
16.6
m³/h 19.0
22.1
25.7
29.9
34.7
39.7
Water volume
ltr
5.6
5.9
6.2
6.5
6.9
7.3
7.7
8.3
8.9
9.6
10.5
11.4
ltr
22.0
23.2
24.6
26.3
28.1
30.1
Max. working pressure
bar
11
11
11
11
11
11
11
11
11
11
11
11
bar
11
11
11
11
11
11 DN65 PN16 DN80 PN16
Gas connection
¾"
¾"
1"
1"
1"
1"
1½"
1½"
1½"
1½"
1½"
1½"
2"
2"
2"
2"
Water connections
2"
2"
2"
2"
2"
2"
DN65 PN16
DN65 PN16
DN65 PN16
DN65 PN16
DN65 PN16
DN65 PN16
DN80 PN16
DN80 PN16
DN80 PN16
DN80 PN16
DN65 PN16 DN80 PN16
-
-
-
-
-
-
-
Gas consumption
Gas consumption
natural gas H (10,9 kWh/m3)
m³/h
9.3
13.3
17.3
21.3
26.7
32.0
37.3
m³/h
6.79
8.35 11.10 13.49 17.80 22.29 26.51
Propane
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
m³/h
2.6
3.2
4.2
5.15
6.8
8.5
10.1
Water volume
ltr
6.2
6.9
7.7
8.5
9.6
10.5
11.4
ltr
13
15
17
19
36
39
42
Max. working pressure
bar
6
6
6
6
6
6
6
bar
6
6
6
6
6
6
6
Gas connection Water connections
1"
1¼"
1¼"
1¼"
1¼"
1½"
1½"
Rp¾" Rp¾" Rp¾" Rp¾"
R1"
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
DN50 PN6
R1½" R1½" R1½" R1½"
R2"
R1½" R1½" R2"
R2"
Flue connection
mm
200
225
250
250
300
300
350
350
400
400
450
450
mm
450
500
550
600
650
700
Flue connection
mm
150
180
200
200
250
250
300
mm
100
100
100
150
180
200
200
Electrical supply
Phase
1
1
1
1
1
1
1
1
1
1
1
1
Phase
1
1
1
1
1
1
Electrical supply
Phase
1
1
1
1
1
1
1
Phase
1
1
1
1
1
1
1
Frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
Hz
50
50
50
50
50
50
Frequency
Hz
50
50
50
50
50
50
50
Hz
50
50
50
50
50
50
50
Fuse
A
6
6
6
6
6
6
6
6
6
6
6
6
A
6
6
6
6
6
6
Fuse
A
6
6
6
6
6
6
6
A
10
10
10
10
10
10
10
width
mm
786
786
786
786
786
786
786
mm
500
600
700
800
600
700
800
Dimensions
Dimensions
depth
mm
1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017
mm 1633 1633 1633 1633 1618 1618
height
mm
1612 1612 1612 1612 1612 1612 1612 1612 1632 1632 1652 1652
mm 1795 1795 1795 1795 1895 1895
height
mm
1440 1440 1440 1440 1440 1440 1440
mm
1205 1240 1240 1240 1240 1240 1240
length
mm
820
898
994
1090 1200 1312 1438 1598 1772 1978 2216 2486
mm 1461 1636 1842 2080 2350 2636
length
mm
1016 1226 1436 1646 1926 2206 2486
mm
635
635
635
635
890
890
890
kg
195
210
225
240
kg
120
140
160
180
250
270
290
Weight, empty, ± 5 %
260
280
305
330
365
400
440
490
kg
620
660
705
760
820
885
Weight, empty, ± 5 %
kg
165
200
245
285
340
375
440
Table Technical Data
Table Technical Data 60 - 80 °C
- Heat output measured with :
60 - 80 °C
60 - 80 °C
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
- Gas consumption at
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
II 2H3P
II 2H3P
- Gas specification
I 2H
II 2H3P
- Appliance category
B11
B11
- Appliance category
B14
B23 C53 C33 C63
- Protection degree
IP30
IP30
- Protection degree
IP20
IP20
- Heat output measured with :
60 - 80 °C
- Gas consumption at - Gas specification
EconoFlame A3 03.indd 2
09/12/2002, 16:06:54
The R2700, R3400 Models
ECONOFLAME BOILERS R2700
• • • • • • • • •
R2900
Premix Fully Modulating boiler Ultra low NOx Higher efficiency than atmospheric models Smaller footprint than atmospheric models Smaller flue diameter than atmospheric models Stainless steel construction, high build quality Integral primary boiler pump BMS compatible Semi condensing capability NO MINIMUM return temperature requirements
R300,R2900 & R3600 MODELS • All the features listed above PLUS FULLY CONDENSING EFFICIENCY ALL EXCEED PART ‘L’ BUILDING REGULATION REQUIREMENTS ALL INCLUDED ON THE ENHANCED CAPITAL ALLOWANCE (ECA) SCHEME ENERGY TECHNOLOGY PRODUCT LIST. ECONOFLAME R2700 / R2900
ECONOFLAME BOILER RANGE TECHNICAL DATA R2900
R2700 R2701 R2702 R2703 R2704 R2705 R2706 R2707 R2708 R2709
R2900 R2901 R2902 R2903 R2904 R2905 R2906 R2907 R2908 R2909
Nominal heat output
kW
95
119
141
178
218
299
374
445
521
597
kW
96
122
153
188
257
322
383
449
514
566
Nominal heat input (nett. CV)
kW
101
126
151
190
233
319
400
475
557
638
kW
99
126
158
194
266
333
396
464
532
585
kW
25
33
38
48
58
80
100
119
139
160
kW
25
33
40
48.5
66
83
100
112
133
146
Gas consumption
Gas consumption
natural gas H (10,9 kWh/m3)
m³/h
9.3
11.6
13.9
17.4
21.4
29.3
36.7
43.6
51.1
58.5
m³/h
9.1
11.6
14.5
17.8
24.4
30.5
36.3
42.6
48.8
53.7
Propane
m³/h
3.5
4.4
5.3
6.6
8.2
11.2
14.0
16.6
19.5
22.3
m³/h
3.5
4.4
5.5
6.8
9.3
11.6
13.8
16.2
18.6
20.5
Water volume
ltr
18
18
18
19
20
35
38
41
44
47
ltr
20
20
21
22
39
42
45
48
55
58
Max. working pressure
bar
6
6
6
6
6
6
6
6
6
6
bar
6
6
6
6
6
6
6
6
6
6
Gas connection
Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" Rp2"
Water connections
R2"
R2"
R2"
R2"
R2"
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" R2"
R2"
R2"
R2"
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
DN65 PN6
Flue connection
mm
150
150
150
180
200
200
250
250
300
300
mm
150
150
180
200
200
250
250
250
300
300
Electrical supply
Phase
3
3
3
3
3
3
3
3
3
3
Phase
3
3
3
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
50
50
50
Hz
50
50
50
50
50
50
50
50
50
50
Fuse
A
10
10
10
10
10
10
10
10
10
16
A
10
10
10
10
10
10
10
10
10
10
Dimensions
width
mm
830
1130 1130
mm
830
height
mm
1355 1355 1355 1355 1355 1355 1355 1355 1355 1355
mm
1355 1355 1355 1355 1355 1355 1355 1355 1355 1355
length
mm
1535 1535 1535 1535 1535 1918 1918 1908 1908 1908
mm
1535 1535 1535 1535 1918 1918 1908 1908 1908 1958
Weight, empty, ± 5 %
kg
325
830
325
830
325
830
340
930
360
830
500
830
525
930
560
615
645
kg
340
830
340
830
355
Table Technical Data - Heat output measured with :
60 - 80 °C
60 - 80 °C
- Gas consumption at
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
- Gas specification
II 2H3P
II 2H3P
- Appliance category
B23 C53 C33 C63
B23 C53 C33 C63
- Protection degree
IP20
IP20
EconoFlame A3 03.indd 3
Additional Condensing Heat Exchanger (R2900)
Gas consumption
930
375
830
530
830
555
930
590
Efficiency Figures
1130 1130 1230
645
705
735
Efficiency (nett cv) %
Minimum heat output
Efficiency Figures @ 60° C Flow, 40° C Return.
Efficiency Figures @ 80° C Flow, 60° C Return.
107 106 105 104 103 102 101 100 99 98 97 96 95 94 93
107 106 105 104 103 102 101 100 99 98 97 96 95 94 93
Efficiency (nett cv) %
R2700 Type
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %
09/12/2002, 16:07:09
ECONOFLAME BOILERS R3400
ECONOFLAME SERIES
R3600
Since 1985 Stokvis have been offering a range of fully modulating, high efficiency gas fired boilers. Researched and developed over the years, evolving through and culminating in the most comprehensive ‘state of the art’ premix, ultra low NOx and condensing range of products :- all exceeding part L Building Regulations; the full range of premix models are ECA listed, as is the R18 atmospheric range.
R2000 & R18 Series Features And Benefits ECONOFLAME FEATURES • Modulated gas valve and secondary air damper operated by servomotor. • Matching of part load conditions from 100%down to 20%. More efficient at part loads than conventional boilers, obviating need for many modules. • Gas and secondary air ratios controlled from one source. No possibility of error in control. • Servomotor signals indicate load conditions. Allows boilers to be sequenced for optimum efficiency. • Damper insulated, preventing downward heat radiation. Obviating requirement for heat absorbent base and helps maintain high efficiency.
• Atmospheric stainless steel, gas burner.
A B C D E F G H I J K L M N
— — — — — — — — — — — — — —
Integral Draught Diverter Servomotor Modulated Gas valve Gas supply Primary air Operating mechanism Secondary air Flue deflector Casing Heat exchanger Insulation Burner bars Air diffuser Secondary air damper
H I
J A
K
B
ECONOFLAME BOILER RANGE TECHNICAL DATA
C L
D E
M
F G
R3400 Type
R3600
R3401 R3402 R3403 R3404 R3405 R3406
R3601 R3602 R3603 R3604 R3605
N
• Efficiency Curves Efficiency curves for different types of boilers
• Quiet in operation. Can be installed in areas where noise restrictions are paramount. • Complete burner including all gas and air controls can be removed on wheels. Easy to maintain, labour costs kept to a minimum. • Primary air controlled by inducement from modulated gas. No need for sophisticated controls and complicated maintenance. • Even secondary air distribution across burner. Ensuring even flame and high efficiency.
Nominal heat output
kW
657
729
853
965
1078 1189
kW
631
739
836
934
1031
Nominal heat input (nett. CV)
kW
702
784
917
1038 1159 1279
kW
653
764
865
966
1066
kW
176
196
229
260
kW
187
218
247
276
305
1
Minimum heat output
290
320
2
Gross thermal efficiency in %
Gas consumption
Gas consumption
Gas consumption
m³/h 64.5
71.9
84.1
95.2 106.3 117.3
m³/h
59.9
70.1
79.4
88.6
97.8
m³/h
24.6
27.4
32.1
36.3
40.6
44.8
m³/h
22.8
26.7
30.3
33.8
37.3
Water volume
ltr
50
53
70
75
80
85
ltr
61
78
83
92
97
Max. working pressure
bar
6
6
6
6
6
6
bar
6
6
6
6
6
DN65 PN6 DN80 PN6
DN65 PN6 DN80 PN6
natural gas H (10,9 kWh/m3) 3
Propane 4
5
1 Econoflame boiler 2 Power boiler 2-stage firing 3 Power boiler on-off 4 Atmospheric boiler 2-stage 5 Atmospheric boiler on-off
Gas connection
Rp2" Rp2" Rp2" Rp2"
Water connections
DN65 PN6
DN65 PN6
DN80 PN6
DN80 PN6
DN65 PN6 DN80 PN6
DN65 PN6
DN80 PN6
DN80 PN6
DN65 PN6 DN80 PN6
Rp2" Rp2" Rp2"
Flue connection
mm
300
350
350
400
400
400
mm
300
350
350
400
400
Electrical supply
Phase
3
3
3
3
3
3
Phase
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Hz
50
50
50
50
50
Fuse
A
16
16
20
20
20
20
A
16
16
20
20
20
Boiler output in %
with stainless steel baffles. • High conductivity of copper. Meaning minimum size of heat exchanger, maximum output. • Copper resistant to thermal shock. Giving longer lifetime expectancy of heat exchanger (5 year guarantee) • Baffles give maximum turbulence of flue gases. Maximum heat extraction from flue gases giving high efficiency. • Substantially lighter than Cast Iron / Welded Steel boilers. Structural limitations are overcome when boilers are located in roof top plantrooms.
The R2200
is a fan assisted model with a two stage burner and is similar in design to the R2000 series.
• Smaller flue diameter than the atmospheric boilers. Ideally suited for replacement of cast iron/steel shell pressure jet boilers.
100
width
mm
1330 1330 1130 1130 1330 1330
mm
1330 1130 1130 1330 1330
height
mm
1355 1355 1355 1355 1355 1355
mm
1355 1355 1355 1355 1355
length
mm
2265 2265 2653 2653 2658 2658
mm
2265 2653 2653 2658 2658
99 98
Weight, empty, ± 5 %
97
kg
675
740
840
950
1070 1200
kg
800
900
1010 1160 1290
96 95
Table Technical Data
94 93 92 91 90 50 55 60 65 70 75 80 85 90 95 100 Capacity %
EconoFlame A3 03.indd 4
Dimensions
R2200 Efficiency Figures (weather compensated)
Efficiency (nett cv) %
• Nine/eighteen tube extruded fin, copper heat exchanger
- Heat output measured with :
60 - 80 °C
60 - 80 °C
- Gas consumption at
1013 mbar. 15 °C, dry
1013 mbar. 15 °C, dry
- Gas specification
II 2H3P
II 2H3P
- Appliance category
B23 C53 C33 C63
B23 C53 C33 C63
- Protection degree
IP20
IP20
09/12/2002, 16:07:27
EFLAME 1202
STOKVIS Energy Systems maintenance and after sales service You can be sure that your new Stokvis product is the very best of its type in design, materials and construction. However to obtain the maximum benefits from your quality product, it is essential that it is maintained at maximum efficiency throughout its long working life. For this reason, STOKVIS Energy Systems provides full UK cover with factory trained engineers to offer you a total service opportunity throughout the year. This ensures that your equipment can be checked, serviced and, if
ENERGY PRODUCTS
necessary, adjusted to ensure maximum energy saving performance. Also, in the unlikely event of a breakdown, repairs can be tackled
High Efficiency
speedily and cost effectively – wherever you are in the UK. Just phone,
and Condensing
fax or e-mail STOKVIS Energy Systems for prompt professional attention
Gas Fired Boilers
to your needs.
• Hot Water Plate Heat Exchanger Packages
The company
•
Since the early 1980’s , STOKVIS Energy Systems has been acknowledged as the vanguard in it’s field for both quality of products and customer service.
High Efficiency Sanitary Hot Water Packages • Dual Fuel Boilers
It is our dedicated objective to continue
•
to excel at providing you our customers
Pressurisation and Booster Sets
and partners with both the products
•
and services you need in these most
Direct Gas Fired
demanding and dynamic times both now
Air Heating and
and into the future.
Ventilating Systems •
Ivan Thompson Managing Director
Steel Panel and Low Temperature Radiators • Packaged Plant Rooms •
ECONOFLAME STOKVIS INDUSTRIAL BOILERS (INTERNATIONAL) LIMITED 96R Walton Road East Molesey Surrey KT8 0DL TELEPHONE 08707 707747 • FACSIMILE 08707 707767 Email:
[email protected] • Website: http://www.stokvisboilers.com
EconoFlame A3 03.indd 1
COMMERCIAL & INDUSTRIAL BOILERS
09/12/2002, 16:03:08