ECONOFLAME COMMERCIAL & INDUSTRIAL BOILERS

EFLAME 1202 STOKVIS Energy Systems maintenance and after sales service You can be sure that your new Stokvis product is the very best of its type in ...
Author: Karen Young
0 downloads 2 Views 2MB Size
EFLAME 1202

STOKVIS Energy Systems maintenance and after sales service You can be sure that your new Stokvis product is the very best of its type in design, materials and construction. However to obtain the maximum benefits from your quality product, it is essential that it is maintained at maximum efficiency throughout its long working life. For this reason, STOKVIS Energy Systems provides full UK cover with factory trained engineers to offer you a total service opportunity throughout the year. This ensures that your equipment can be checked, serviced and, if

ENERGY PRODUCTS

necessary, adjusted to ensure maximum energy saving performance. Also, in the unlikely event of a breakdown, repairs can be tackled

High Efficiency

speedily and cost effectively – wherever you are in the UK. Just phone,

and Condensing

fax or e-mail STOKVIS Energy Systems for prompt professional attention

Gas Fired Boilers

to your needs.

• Hot Water Plate Heat Exchanger Packages

The company



Since the early 1980’s , STOKVIS Energy Systems has been acknowledged as the vanguard in it’s field for both quality of products and customer service.

High Efficiency Sanitary Hot Water Packages • Dual Fuel Boilers

It is our dedicated objective to continue



to excel at providing you our customers

Pressurisation and Booster Sets

and partners with both the products



and services you need in these most

Direct Gas Fired

demanding and dynamic times both now

Air Heating and

and into the future.

Ventilating Systems •

Ivan Thompson Managing Director

Steel Panel and Low Temperature Radiators • Packaged Plant Rooms •

ECONOFLAME STOKVIS INDUSTRIAL BOILERS (INTERNATIONAL) LIMITED 96R Walton Road East Molesey Surrey KT8 0DL TELEPHONE 08707 707747 • FACSIMILE 08707 707767 Email: [email protected] • Website: http://www.stokvisboilers.com

EconoFlame A3 03.indd 1

COMMERCIAL & INDUSTRIAL BOILERS

09/12/2002, 16:03:08

ECONOFLAME BOILERS R3400

ECONOFLAME SERIES

R3600

Since 1985 Stokvis have been offering a range of fully modulating, high efficiency gas fired boilers. Researched and developed over the years, evolving through and culminating in the most comprehensive ‘state of the art’ premix, ultra low NOx and condensing range of products :- all exceeding part L Building Regulations; the full range of premix models are ECA listed, as is the R18 atmospheric range.

R2000 & R18 Series Features And Benefits ECONOFLAME FEATURES • Modulated gas valve and secondary air damper operated by servomotor. • Matching of part load conditions from 100%down to 20%. More efficient at part loads than conventional boilers, obviating need for many modules. • Gas and secondary air ratios controlled from one source. No possibility of error in control. • Servomotor signals indicate load conditions. Allows boilers to be sequenced for optimum efficiency. • Damper insulated, preventing downward heat radiation. Obviating requirement for heat absorbent base and helps maintain high efficiency.

• Atmospheric stainless steel, gas burner.

A B C D E F G H I J K L M N

— — — — — — — — — — — — — —

Integral Draught Diverter Servomotor Modulated Gas valve Gas supply Primary air Operating mechanism Secondary air Flue deflector Casing Heat exchanger Insulation Burner bars Air diffuser Secondary air damper

H I

J A

K

B

ECONOFLAME BOILER RANGE TECHNICAL DATA

C L

D E

M

F G

R3400 Type

R3600

R3401 R3402 R3403 R3404 R3405 R3406

R3601 R3602 R3603 R3604 R3605

N

• Efficiency Curves Efficiency curves for different types of boilers

• Quiet in operation. Can be installed in areas where noise restrictions are paramount. • Complete burner including all gas and air controls can be removed on wheels. Easy to maintain, labour costs kept to a minimum. • Primary air controlled by inducement from modulated gas. No need for sophisticated controls and complicated maintenance. • Even secondary air distribution across burner. Ensuring even flame and high efficiency.

Nominal heat output

kW

657

729

853

965

1078 1189

kW

631

739

836

934

1031

Nominal heat input (nett. CV)

kW

702

784

917

1038 1159 1279

kW

653

764

865

966

1066

kW

176

196

229

260

kW

187

218

247

276

305

1

Minimum heat output

290

320

2

Gross thermal efficiency in %

Gas consumption

Gas consumption

Gas consumption

m³/h 64.5

71.9

84.1

95.2 106.3 117.3

m³/h

59.9

70.1

79.4

88.6

97.8

m³/h

24.6

27.4

32.1

36.3

40.6

44.8

m³/h

22.8

26.7

30.3

33.8

37.3

Water volume

ltr

50

53

70

75

80

85

ltr

61

78

83

92

97

Max. working pressure

bar

6

6

6

6

6

6

bar

6

6

6

6

6

DN65 PN6 DN80 PN6

DN65 PN6 DN80 PN6

natural gas H (10,9 kWh/m3) 3

Propane 4

5

1 Econoflame boiler 2 Power boiler 2-stage firing 3 Power boiler on-off 4 Atmospheric boiler 2-stage 5 Atmospheric boiler on-off

Gas connection

Rp2" Rp2" Rp2" Rp2"

Water connections

DN65 PN6

DN65 PN6

DN80 PN6

DN80 PN6

DN65 PN6 DN80 PN6

DN65 PN6

DN80 PN6

DN80 PN6

DN65 PN6 DN80 PN6

Rp2" Rp2" Rp2"

Flue connection

mm

300

350

350

400

400

400

mm

300

350

350

400

400

Electrical supply

Phase

3

3

3

3

3

3

Phase

3

3

3

3

3

Frequency

Hz

50

50

50

50

50

50

Hz

50

50

50

50

50

Fuse

A

16

16

20

20

20

20

A

16

16

20

20

20

Boiler output in %

with stainless steel baffles. • High conductivity of copper. Meaning minimum size of heat exchanger, maximum output. • Copper resistant to thermal shock. Giving longer lifetime expectancy of heat exchanger (5 year guarantee) • Baffles give maximum turbulence of flue gases. Maximum heat extraction from flue gases giving high efficiency. • Substantially lighter than Cast Iron / Welded Steel boilers. Structural limitations are overcome when boilers are located in roof top plantrooms.

The R2200

is a fan assisted model with a two stage burner and is similar in design to the R2000 series.

• Smaller flue diameter than the atmospheric boilers. Ideally suited for replacement of cast iron/steel shell pressure jet boilers.

100

width

mm

1330 1330 1130 1130 1330 1330

mm

1330 1130 1130 1330 1330

height

mm

1355 1355 1355 1355 1355 1355

mm

1355 1355 1355 1355 1355

length

mm

2265 2265 2653 2653 2658 2658

mm

2265 2653 2653 2658 2658

99 98

Weight, empty, ± 5 %

97

kg

675

740

840

950

1070 1200

kg

800

900

1010 1160 1290

96 95

Table Technical Data

94 93 92 91 90 50 55 60 65 70 75 80 85 90 95 100 Capacity %

EconoFlame A3 03.indd 4

Dimensions

R2200 Efficiency Figures (weather compensated)

Efficiency (nett cv) %

• Nine/eighteen tube extruded fin, copper heat exchanger

- Heat output measured with :

60 - 80 °C

60 - 80 °C

- Gas consumption at

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

- Gas specification

II 2H3P

II 2H3P

- Appliance category

B23 C53 C33 C63

B23 C53 C33 C63

- Protection degree

IP20

IP20

09/12/2002, 16:07:27

The R2700, R3400 Models

ECONOFLAME BOILERS R2700

• • • • • • • • •

R2900

Premix Fully Modulating boiler Ultra low NOx Higher efficiency than atmospheric models Smaller footprint than atmospheric models Smaller flue diameter than atmospheric models Stainless steel construction, high build quality Integral primary boiler pump BMS compatible Semi condensing capability NO MINIMUM return temperature requirements

R300,R2900 & R3600 MODELS • All the features listed above PLUS FULLY CONDENSING EFFICIENCY ALL EXCEED PART ‘L’ BUILDING REGULATION REQUIREMENTS ALL INCLUDED ON THE ENHANCED CAPITAL ALLOWANCE (ECA) SCHEME ENERGY TECHNOLOGY PRODUCT LIST. ECONOFLAME R2700 / R2900

ECONOFLAME BOILER RANGE TECHNICAL DATA R2900

R2700 R2701 R2702 R2703 R2704 R2705 R2706 R2707 R2708 R2709

R2900 R2901 R2902 R2903 R2904 R2905 R2906 R2907 R2908 R2909

Nominal heat output

kW

95

119

141

178

218

299

374

445

521

597

kW

96

122

153

188

257

322

383

449

514

566

Nominal heat input (nett. CV)

kW

101

126

151

190

233

319

400

475

557

638

kW

99

126

158

194

266

333

396

464

532

585

kW

25

33

38

48

58

80

100

119

139

160

kW

25

33

40

48.5

66

83

100

112

133

146

Gas consumption

Gas consumption

natural gas H (10,9 kWh/m3)

m³/h

9.3

11.6

13.9

17.4

21.4

29.3

36.7

43.6

51.1

58.5

m³/h

9.1

11.6

14.5

17.8

24.4

30.5

36.3

42.6

48.8

53.7

Propane

m³/h

3.5

4.4

5.3

6.6

8.2

11.2

14.0

16.6

19.5

22.3

m³/h

3.5

4.4

5.5

6.8

9.3

11.6

13.8

16.2

18.6

20.5

Water volume

ltr

18

18

18

19

20

35

38

41

44

47

ltr

20

20

21

22

39

42

45

48

55

58

Max. working pressure

bar

6

6

6

6

6

6

6

6

6

6

bar

6

6

6

6

6

6

6

6

6

6

Gas connection

Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" Rp2"

Water connections

R2"

R2"

R2"

R2"

R2"

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" R2"

R2"

R2"

R2"

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

Flue connection

mm

150

150

150

180

200

200

250

250

300

300

mm

150

150

180

200

200

250

250

250

300

300

Electrical supply

Phase

3

3

3

3

3

3

3

3

3

3

Phase

3

3

3

3

3

3

3

3

3

3

Frequency

Hz

50

50

50

50

50

50

50

50

50

50

Hz

50

50

50

50

50

50

50

50

50

50

Fuse

A

10

10

10

10

10

10

10

10

10

16

A

10

10

10

10

10

10

10

10

10

10

Dimensions

width

mm

830

1130 1130

mm

830

height

mm

1355 1355 1355 1355 1355 1355 1355 1355 1355 1355

mm

1355 1355 1355 1355 1355 1355 1355 1355 1355 1355

length

mm

1535 1535 1535 1535 1535 1918 1918 1908 1908 1908

mm

1535 1535 1535 1535 1918 1918 1908 1908 1908 1958

Weight, empty, ± 5 %

kg

325

830

325

830

325

830

340

930

360

830

500

830

525

930

560

615

645

kg

340

830

340

830

355

Table Technical Data - Heat output measured with :

60 - 80 °C

60 - 80 °C

- Gas consumption at

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

- Gas specification

II 2H3P

II 2H3P

- Appliance category

B23 C53 C33 C63

B23 C53 C33 C63

- Protection degree

IP20

IP20

EconoFlame A3 03.indd 3

Additional Condensing Heat Exchanger (R2900)

Gas consumption

930

375

830

530

830

555

930

590

Efficiency Figures

1130 1130 1230

645

705

735

Efficiency (nett cv) %

Minimum heat output

Efficiency Figures @ 60° C Flow, 40° C Return.

Efficiency Figures @ 80° C Flow, 60° C Return.

107 106 105 104 103 102 101 100 99 98 97 96 95 94 93

107 106 105 104 103 102 101 100 99 98 97 96 95 94 93

Efficiency (nett cv) %

R2700 Type

25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %

25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %

09/12/2002, 16:07:09

ECONOFLAME BOILERS

ECONOFLAME BOILERS

R2000

R18

R2200

ECONOFLAME BOILER RANGE TECHNICAL DATA

ECONOFLAME BOILER RANGE TECHNICAL DATA

R2200

R18

R2000 Type

R300

R2017 R2022 R2028 R2034 R2041 R2048 R2056 R2066 R2077 R2090 R2105 R2122

132

154

180

210

244

280

Type

R300

2207 2210 2213 2216 2220 2224 2228

R301 R302 R303 R304 R305 R306 R307

Nominal heat output

kW

57.7

74.6

95.8 116.7 139.1 162.7 190.7 222.1 261.1 309.0 361.0 425.0

kW

481

558

649

756

875

1002

Nominal heat output

kW

81.3 116.4 151.5 186.7 233.9 280.9 328.5

kW

70

86

114

139

185

230

274

Nominal heat input (nett. CV)

kW

65.5

84.8 107.7 131.6 158.6 185.5 217.4 253.3 296.2 348.0 403.9 470.7

kW

538

625

727

846

980

1122

Nominal heat input (nett. CV)

kW

88.2 126.0 163.8 201.6 252.0 302.4 352.8

kW

74

91

121

147

194

243

289

Minimum heat output

kW

-

kW

-

-

-

-

-

-

kW

16

20

27

33

44

55

65

-

-

-

-

-

-

-

-

-

-

-

Gas consumption

Gas consumption

Minimum heat output

kW

Gas consumption

natural gas H (10,9 kWh/m3)

m³/h

6.0

7.9

9.9

12.2

14.7

17.2

20.2

23.5

27.5

32.3

37.4

43.6

m³/h 49.3

57.9

67.4

78.4

90.8 104.0

Propane

m³/h

2.3

2.9

3.8

4.7

5.6

6.6

7.7

8.9

10.5

12.3

14.3

16.6

m³/h 19.0

22.1

25.7

29.9

34.7

39.7

Water volume

ltr

5.6

5.9

6.2

6.5

6.9

7.3

7.7

8.3

8.9

9.6

10.5

11.4

ltr

22.0

23.2

24.6

26.3

28.1

30.1

Max. working pressure

bar

11

11

11

11

11

11

11

11

11

11

11

11

bar

11

11

11

11

11

11 DN65 PN16 DN80 PN16

Gas connection

¾"

¾"

1"

1"

1"

1"

1½"

1½"

1½"

1½"

1½"

1½"

2"

2"

2"

2"

Water connections

2"

2"

2"

2"

2"

2"

DN65 PN16

DN65 PN16

DN65 PN16

DN65 PN16

DN65 PN16

DN65 PN16

DN80 PN16

DN80 PN16

DN80 PN16

DN80 PN16

DN65 PN16 DN80 PN16

-

-

-

-

-

-

-

Gas consumption

Gas consumption

natural gas H (10,9 kWh/m3)

m³/h

9.3

13.3

17.3

21.3

26.7

32.0

37.3

m³/h

6.79

8.35 11.10 13.49 17.80 22.29 26.51

Propane

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

m³/h

2.6

3.2

4.2

5.15

6.8

8.5

10.1

Water volume

ltr

6.2

6.9

7.7

8.5

9.6

10.5

11.4

ltr

13

15

17

19

36

39

42

Max. working pressure

bar

6

6

6

6

6

6

6

bar

6

6

6

6

6

6

6

Gas connection Water connections

1"

1¼"

1¼"

1¼"

1¼"

1½"

1½"

Rp¾" Rp¾" Rp¾" Rp¾"

R1"

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

R1½" R1½" R1½" R1½"

R2"

R1½" R1½" R2"

R2"

Flue connection

mm

200

225

250

250

300

300

350

350

400

400

450

450

mm

450

500

550

600

650

700

Flue connection

mm

150

180

200

200

250

250

300

mm

100

100

100

150

180

200

200

Electrical supply

Phase

1

1

1

1

1

1

1

1

1

1

1

1

Phase

1

1

1

1

1

1

Electrical supply

Phase

1

1

1

1

1

1

1

Phase

1

1

1

1

1

1

1

Frequency

Hz

50

50

50

50

50

50

50

50

50

50

50

50

Hz

50

50

50

50

50

50

Frequency

Hz

50

50

50

50

50

50

50

Hz

50

50

50

50

50

50

50

Fuse

A

6

6

6

6

6

6

6

6

6

6

6

6

A

6

6

6

6

6

6

Fuse

A

6

6

6

6

6

6

6

A

10

10

10

10

10

10

10

width

mm

786

786

786

786

786

786

786

mm

500

600

700

800

600

700

800

Dimensions

Dimensions

depth

mm

1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017

mm 1633 1633 1633 1633 1618 1618

height

mm

1612 1612 1612 1612 1612 1612 1612 1612 1632 1632 1652 1652

mm 1795 1795 1795 1795 1895 1895

height

mm

1440 1440 1440 1440 1440 1440 1440

mm

1205 1240 1240 1240 1240 1240 1240

length

mm

820

898

994

1090 1200 1312 1438 1598 1772 1978 2216 2486

mm 1461 1636 1842 2080 2350 2636

length

mm

1016 1226 1436 1646 1926 2206 2486

mm

635

635

635

635

890

890

890

kg

195

210

225

240

kg

120

140

160

180

250

270

290

Weight, empty, ± 5 %

260

280

305

330

365

400

440

490

kg

620

660

705

760

820

885

Weight, empty, ± 5 %

kg

165

200

245

285

340

375

440

Table Technical Data

Table Technical Data 60 - 80 °C

- Heat output measured with :

60 - 80 °C

60 - 80 °C

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

- Gas consumption at

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

II 2H3P

II 2H3P

- Gas specification

I 2H

II 2H3P

- Appliance category

B11

B11

- Appliance category

B14

B23 C53 C33 C63

- Protection degree

IP30

IP30

- Protection degree

IP20

IP20

- Heat output measured with :

60 - 80 °C

- Gas consumption at - Gas specification

EconoFlame A3 03.indd 2

09/12/2002, 16:06:54

ECONOFLAME BOILERS

ECONOFLAME BOILERS

R2000

R18

R2200

ECONOFLAME BOILER RANGE TECHNICAL DATA

ECONOFLAME BOILER RANGE TECHNICAL DATA

R2200

R18

R2000 Type

R300

R2017 R2022 R2028 R2034 R2041 R2048 R2056 R2066 R2077 R2090 R2105 R2122

132

154

180

210

244

280

Type

R300

2207 2210 2213 2216 2220 2224 2228

R301 R302 R303 R304 R305 R306 R307

Nominal heat output

kW

57.7

74.6

95.8 116.7 139.1 162.7 190.7 222.1 261.1 309.0 361.0 425.0

kW

481

558

649

756

875

1002

Nominal heat output

kW

81.3 116.4 151.5 186.7 233.9 280.9 328.5

kW

70

86

114

139

185

230

274

Nominal heat input (nett. CV)

kW

65.5

84.8 107.7 131.6 158.6 185.5 217.4 253.3 296.2 348.0 403.9 470.7

kW

538

625

727

846

980

1122

Nominal heat input (nett. CV)

kW

88.2 126.0 163.8 201.6 252.0 302.4 352.8

kW

74

91

121

147

194

243

289

Minimum heat output

kW

-

kW

-

-

-

-

-

-

kW

16

20

27

33

44

55

65

-

-

-

-

-

-

-

-

-

-

-

Gas consumption

Gas consumption

Minimum heat output

kW

Gas consumption

natural gas H (10,9 kWh/m3)

m³/h

6.0

7.9

9.9

12.2

14.7

17.2

20.2

23.5

27.5

32.3

37.4

43.6

m³/h 49.3

57.9

67.4

78.4

90.8 104.0

Propane

m³/h

2.3

2.9

3.8

4.7

5.6

6.6

7.7

8.9

10.5

12.3

14.3

16.6

m³/h 19.0

22.1

25.7

29.9

34.7

39.7

Water volume

ltr

5.6

5.9

6.2

6.5

6.9

7.3

7.7

8.3

8.9

9.6

10.5

11.4

ltr

22.0

23.2

24.6

26.3

28.1

30.1

Max. working pressure

bar

11

11

11

11

11

11

11

11

11

11

11

11

bar

11

11

11

11

11

11 DN65 PN16 DN80 PN16

Gas connection

¾"

¾"

1"

1"

1"

1"

1½"

1½"

1½"

1½"

1½"

1½"

2"

2"

2"

2"

Water connections

2"

2"

2"

2"

2"

2"

DN65 PN16

DN65 PN16

DN65 PN16

DN65 PN16

DN65 PN16

DN65 PN16

DN80 PN16

DN80 PN16

DN80 PN16

DN80 PN16

DN65 PN16 DN80 PN16

-

-

-

-

-

-

-

Gas consumption

Gas consumption

natural gas H (10,9 kWh/m3)

m³/h

9.3

13.3

17.3

21.3

26.7

32.0

37.3

m³/h

6.79

8.35 11.10 13.49 17.80 22.29 26.51

Propane

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

m³/h

2.6

3.2

4.2

5.15

6.8

8.5

10.1

Water volume

ltr

6.2

6.9

7.7

8.5

9.6

10.5

11.4

ltr

13

15

17

19

36

39

42

Max. working pressure

bar

6

6

6

6

6

6

6

bar

6

6

6

6

6

6

6

Gas connection Water connections

1"

1¼"

1¼"

1¼"

1¼"

1½"

1½"

Rp¾" Rp¾" Rp¾" Rp¾"

R1"

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

DN50 PN6

R1½" R1½" R1½" R1½"

R2"

R1½" R1½" R2"

R2"

Flue connection

mm

200

225

250

250

300

300

350

350

400

400

450

450

mm

450

500

550

600

650

700

Flue connection

mm

150

180

200

200

250

250

300

mm

100

100

100

150

180

200

200

Electrical supply

Phase

1

1

1

1

1

1

1

1

1

1

1

1

Phase

1

1

1

1

1

1

Electrical supply

Phase

1

1

1

1

1

1

1

Phase

1

1

1

1

1

1

1

Frequency

Hz

50

50

50

50

50

50

50

50

50

50

50

50

Hz

50

50

50

50

50

50

Frequency

Hz

50

50

50

50

50

50

50

Hz

50

50

50

50

50

50

50

Fuse

A

6

6

6

6

6

6

6

6

6

6

6

6

A

6

6

6

6

6

6

Fuse

A

6

6

6

6

6

6

6

A

10

10

10

10

10

10

10

width

mm

786

786

786

786

786

786

786

mm

500

600

700

800

600

700

800

Dimensions

Dimensions

depth

mm

1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017 1017

mm 1633 1633 1633 1633 1618 1618

height

mm

1612 1612 1612 1612 1612 1612 1612 1612 1632 1632 1652 1652

mm 1795 1795 1795 1795 1895 1895

height

mm

1440 1440 1440 1440 1440 1440 1440

mm

1205 1240 1240 1240 1240 1240 1240

length

mm

820

898

994

1090 1200 1312 1438 1598 1772 1978 2216 2486

mm 1461 1636 1842 2080 2350 2636

length

mm

1016 1226 1436 1646 1926 2206 2486

mm

635

635

635

635

890

890

890

kg

195

210

225

240

kg

120

140

160

180

250

270

290

Weight, empty, ± 5 %

260

280

305

330

365

400

440

490

kg

620

660

705

760

820

885

Weight, empty, ± 5 %

kg

165

200

245

285

340

375

440

Table Technical Data

Table Technical Data 60 - 80 °C

- Heat output measured with :

60 - 80 °C

60 - 80 °C

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

- Gas consumption at

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

II 2H3P

II 2H3P

- Gas specification

I 2H

II 2H3P

- Appliance category

B11

B11

- Appliance category

B14

B23 C53 C33 C63

- Protection degree

IP30

IP30

- Protection degree

IP20

IP20

- Heat output measured with :

60 - 80 °C

- Gas consumption at - Gas specification

EconoFlame A3 03.indd 2

09/12/2002, 16:06:54

The R2700, R3400 Models

ECONOFLAME BOILERS R2700

• • • • • • • • •

R2900

Premix Fully Modulating boiler Ultra low NOx Higher efficiency than atmospheric models Smaller footprint than atmospheric models Smaller flue diameter than atmospheric models Stainless steel construction, high build quality Integral primary boiler pump BMS compatible Semi condensing capability NO MINIMUM return temperature requirements

R300,R2900 & R3600 MODELS • All the features listed above PLUS FULLY CONDENSING EFFICIENCY ALL EXCEED PART ‘L’ BUILDING REGULATION REQUIREMENTS ALL INCLUDED ON THE ENHANCED CAPITAL ALLOWANCE (ECA) SCHEME ENERGY TECHNOLOGY PRODUCT LIST. ECONOFLAME R2700 / R2900

ECONOFLAME BOILER RANGE TECHNICAL DATA R2900

R2700 R2701 R2702 R2703 R2704 R2705 R2706 R2707 R2708 R2709

R2900 R2901 R2902 R2903 R2904 R2905 R2906 R2907 R2908 R2909

Nominal heat output

kW

95

119

141

178

218

299

374

445

521

597

kW

96

122

153

188

257

322

383

449

514

566

Nominal heat input (nett. CV)

kW

101

126

151

190

233

319

400

475

557

638

kW

99

126

158

194

266

333

396

464

532

585

kW

25

33

38

48

58

80

100

119

139

160

kW

25

33

40

48.5

66

83

100

112

133

146

Gas consumption

Gas consumption

natural gas H (10,9 kWh/m3)

m³/h

9.3

11.6

13.9

17.4

21.4

29.3

36.7

43.6

51.1

58.5

m³/h

9.1

11.6

14.5

17.8

24.4

30.5

36.3

42.6

48.8

53.7

Propane

m³/h

3.5

4.4

5.3

6.6

8.2

11.2

14.0

16.6

19.5

22.3

m³/h

3.5

4.4

5.5

6.8

9.3

11.6

13.8

16.2

18.6

20.5

Water volume

ltr

18

18

18

19

20

35

38

41

44

47

ltr

20

20

21

22

39

42

45

48

55

58

Max. working pressure

bar

6

6

6

6

6

6

6

6

6

6

bar

6

6

6

6

6

6

6

6

6

6

Gas connection

Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" Rp2"

Water connections

R2"

R2"

R2"

R2"

R2"

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp1½" Rp2" Rp2" Rp2" R2"

R2"

R2"

R2"

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

Flue connection

mm

150

150

150

180

200

200

250

250

300

300

mm

150

150

180

200

200

250

250

250

300

300

Electrical supply

Phase

3

3

3

3

3

3

3

3

3

3

Phase

3

3

3

3

3

3

3

3

3

3

Frequency

Hz

50

50

50

50

50

50

50

50

50

50

Hz

50

50

50

50

50

50

50

50

50

50

Fuse

A

10

10

10

10

10

10

10

10

10

16

A

10

10

10

10

10

10

10

10

10

10

Dimensions

width

mm

830

1130 1130

mm

830

height

mm

1355 1355 1355 1355 1355 1355 1355 1355 1355 1355

mm

1355 1355 1355 1355 1355 1355 1355 1355 1355 1355

length

mm

1535 1535 1535 1535 1535 1918 1918 1908 1908 1908

mm

1535 1535 1535 1535 1918 1918 1908 1908 1908 1958

Weight, empty, ± 5 %

kg

325

830

325

830

325

830

340

930

360

830

500

830

525

930

560

615

645

kg

340

830

340

830

355

Table Technical Data - Heat output measured with :

60 - 80 °C

60 - 80 °C

- Gas consumption at

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

- Gas specification

II 2H3P

II 2H3P

- Appliance category

B23 C53 C33 C63

B23 C53 C33 C63

- Protection degree

IP20

IP20

EconoFlame A3 03.indd 3

Additional Condensing Heat Exchanger (R2900)

Gas consumption

930

375

830

530

830

555

930

590

Efficiency Figures

1130 1130 1230

645

705

735

Efficiency (nett cv) %

Minimum heat output

Efficiency Figures @ 60° C Flow, 40° C Return.

Efficiency Figures @ 80° C Flow, 60° C Return.

107 106 105 104 103 102 101 100 99 98 97 96 95 94 93

107 106 105 104 103 102 101 100 99 98 97 96 95 94 93

Efficiency (nett cv) %

R2700 Type

25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %

25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Capacity %

09/12/2002, 16:07:09

ECONOFLAME BOILERS R3400

ECONOFLAME SERIES

R3600

Since 1985 Stokvis have been offering a range of fully modulating, high efficiency gas fired boilers. Researched and developed over the years, evolving through and culminating in the most comprehensive ‘state of the art’ premix, ultra low NOx and condensing range of products :- all exceeding part L Building Regulations; the full range of premix models are ECA listed, as is the R18 atmospheric range.

R2000 & R18 Series Features And Benefits ECONOFLAME FEATURES • Modulated gas valve and secondary air damper operated by servomotor. • Matching of part load conditions from 100%down to 20%. More efficient at part loads than conventional boilers, obviating need for many modules. • Gas and secondary air ratios controlled from one source. No possibility of error in control. • Servomotor signals indicate load conditions. Allows boilers to be sequenced for optimum efficiency. • Damper insulated, preventing downward heat radiation. Obviating requirement for heat absorbent base and helps maintain high efficiency.

• Atmospheric stainless steel, gas burner.

A B C D E F G H I J K L M N

— — — — — — — — — — — — — —

Integral Draught Diverter Servomotor Modulated Gas valve Gas supply Primary air Operating mechanism Secondary air Flue deflector Casing Heat exchanger Insulation Burner bars Air diffuser Secondary air damper

H I

J A

K

B

ECONOFLAME BOILER RANGE TECHNICAL DATA

C L

D E

M

F G

R3400 Type

R3600

R3401 R3402 R3403 R3404 R3405 R3406

R3601 R3602 R3603 R3604 R3605

N

• Efficiency Curves Efficiency curves for different types of boilers

• Quiet in operation. Can be installed in areas where noise restrictions are paramount. • Complete burner including all gas and air controls can be removed on wheels. Easy to maintain, labour costs kept to a minimum. • Primary air controlled by inducement from modulated gas. No need for sophisticated controls and complicated maintenance. • Even secondary air distribution across burner. Ensuring even flame and high efficiency.

Nominal heat output

kW

657

729

853

965

1078 1189

kW

631

739

836

934

1031

Nominal heat input (nett. CV)

kW

702

784

917

1038 1159 1279

kW

653

764

865

966

1066

kW

176

196

229

260

kW

187

218

247

276

305

1

Minimum heat output

290

320

2

Gross thermal efficiency in %

Gas consumption

Gas consumption

Gas consumption

m³/h 64.5

71.9

84.1

95.2 106.3 117.3

m³/h

59.9

70.1

79.4

88.6

97.8

m³/h

24.6

27.4

32.1

36.3

40.6

44.8

m³/h

22.8

26.7

30.3

33.8

37.3

Water volume

ltr

50

53

70

75

80

85

ltr

61

78

83

92

97

Max. working pressure

bar

6

6

6

6

6

6

bar

6

6

6

6

6

DN65 PN6 DN80 PN6

DN65 PN6 DN80 PN6

natural gas H (10,9 kWh/m3) 3

Propane 4

5

1 Econoflame boiler 2 Power boiler 2-stage firing 3 Power boiler on-off 4 Atmospheric boiler 2-stage 5 Atmospheric boiler on-off

Gas connection

Rp2" Rp2" Rp2" Rp2"

Water connections

DN65 PN6

DN65 PN6

DN80 PN6

DN80 PN6

DN65 PN6 DN80 PN6

DN65 PN6

DN80 PN6

DN80 PN6

DN65 PN6 DN80 PN6

Rp2" Rp2" Rp2"

Flue connection

mm

300

350

350

400

400

400

mm

300

350

350

400

400

Electrical supply

Phase

3

3

3

3

3

3

Phase

3

3

3

3

3

Frequency

Hz

50

50

50

50

50

50

Hz

50

50

50

50

50

Fuse

A

16

16

20

20

20

20

A

16

16

20

20

20

Boiler output in %

with stainless steel baffles. • High conductivity of copper. Meaning minimum size of heat exchanger, maximum output. • Copper resistant to thermal shock. Giving longer lifetime expectancy of heat exchanger (5 year guarantee) • Baffles give maximum turbulence of flue gases. Maximum heat extraction from flue gases giving high efficiency. • Substantially lighter than Cast Iron / Welded Steel boilers. Structural limitations are overcome when boilers are located in roof top plantrooms.

The R2200

is a fan assisted model with a two stage burner and is similar in design to the R2000 series.

• Smaller flue diameter than the atmospheric boilers. Ideally suited for replacement of cast iron/steel shell pressure jet boilers.

100

width

mm

1330 1330 1130 1130 1330 1330

mm

1330 1130 1130 1330 1330

height

mm

1355 1355 1355 1355 1355 1355

mm

1355 1355 1355 1355 1355

length

mm

2265 2265 2653 2653 2658 2658

mm

2265 2653 2653 2658 2658

99 98

Weight, empty, ± 5 %

97

kg

675

740

840

950

1070 1200

kg

800

900

1010 1160 1290

96 95

Table Technical Data

94 93 92 91 90 50 55 60 65 70 75 80 85 90 95 100 Capacity %

EconoFlame A3 03.indd 4

Dimensions

R2200 Efficiency Figures (weather compensated)

Efficiency (nett cv) %

• Nine/eighteen tube extruded fin, copper heat exchanger

- Heat output measured with :

60 - 80 °C

60 - 80 °C

- Gas consumption at

1013 mbar. 15 °C, dry

1013 mbar. 15 °C, dry

- Gas specification

II 2H3P

II 2H3P

- Appliance category

B23 C53 C33 C63

B23 C53 C33 C63

- Protection degree

IP20

IP20

09/12/2002, 16:07:27

EFLAME 1202

STOKVIS Energy Systems maintenance and after sales service You can be sure that your new Stokvis product is the very best of its type in design, materials and construction. However to obtain the maximum benefits from your quality product, it is essential that it is maintained at maximum efficiency throughout its long working life. For this reason, STOKVIS Energy Systems provides full UK cover with factory trained engineers to offer you a total service opportunity throughout the year. This ensures that your equipment can be checked, serviced and, if

ENERGY PRODUCTS

necessary, adjusted to ensure maximum energy saving performance. Also, in the unlikely event of a breakdown, repairs can be tackled

High Efficiency

speedily and cost effectively – wherever you are in the UK. Just phone,

and Condensing

fax or e-mail STOKVIS Energy Systems for prompt professional attention

Gas Fired Boilers

to your needs.

• Hot Water Plate Heat Exchanger Packages

The company



Since the early 1980’s , STOKVIS Energy Systems has been acknowledged as the vanguard in it’s field for both quality of products and customer service.

High Efficiency Sanitary Hot Water Packages • Dual Fuel Boilers

It is our dedicated objective to continue



to excel at providing you our customers

Pressurisation and Booster Sets

and partners with both the products



and services you need in these most

Direct Gas Fired

demanding and dynamic times both now

Air Heating and

and into the future.

Ventilating Systems •

Ivan Thompson Managing Director

Steel Panel and Low Temperature Radiators • Packaged Plant Rooms •

ECONOFLAME STOKVIS INDUSTRIAL BOILERS (INTERNATIONAL) LIMITED 96R Walton Road East Molesey Surrey KT8 0DL TELEPHONE 08707 707747 • FACSIMILE 08707 707767 Email: [email protected] • Website: http://www.stokvisboilers.com

EconoFlame A3 03.indd 1

COMMERCIAL & INDUSTRIAL BOILERS

09/12/2002, 16:03:08