Intelligent Building Series

C-Touch Training Manual

C-Touch Training Manual V1.2 Prepared By Clipsal Integrated Systems ACN 089 444 931

For Technical Enquiries Please Ring

1300 722 247

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 1

Intelligent Building Series

C-Touch Training Manual

CONTENTS TOPIC

1.0 1.1 1.2 1.2 1.3 2.0 2.1 3.0 3.1 3.1.1 3.1.2 3.1.3 3.1.4 4.0 4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.2 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 6.0 6.1 6.2 6.3 7.0 7.1 7.2 7.5 7.6 8.0 8.1 9.0 10.0 11.0 12.0 13.0 14.0 14. 1 14.2

PAGE NO.

PRODUCT RANGE............................................................................................. 3 DESCRIPTION.................................................................................................... 4 CAPABILITIES ................................................................................................... 4 CAPABILITIES ................................................................................................... 5 DEFINITIONS...................................................................................................... 6 ADDING ITEMS TO THE DISPLAY ................................................................... 7 FUNCTIONS OF THE TOOL BAR OPTIONS .................................................... 7 GETTING STARTED ........................................................................................ 10 TOUCH SCREEN PROJECT DETAILS ........................................................... 11 SCREEN TYPE.............................................................................................. 11 PROJECT TAB.............................................................................................. 12 INSTALLER TAB .......................................................................................... 13 OPTIONS TAB .............................................................................................. 14 C-TOUCH COMPONENTS ............................................................................... 17 COMPONENT PROPERTIES........................................................................... 18 VISUAL PROPERTIES.................................................................................. 18 PAGE LINK ................................................................................................... 26 SPECIAL FUNCTION .................................................................................... 27 REMOTE CONTROL ..................................................................................... 28 TOOLS .............................................................................................................. 32 SCHEDULES .................................................................................................... 33 EDIT SCHEDULE ............................................................................................. 33 SCHEDULE ITEM ............................................................................................. 34 ENABLE TAB ................................................................................................... 35 TIME TAB ......................................................................................................... 36 DAY TAB .......................................................................................................... 37 EVENT .............................................................................................................. 39 SCHEDULE MONITOR..................................................................................... 42 SCENES............................................................................................................ 43 SCENE NAME .................................................................................................. 45 TRIGGERING.................................................................................................... 45 ACTIONS .......................................................................................................... 46 PROGRAM OPTIONS ...................................................................................... 47 AUTO SAVE ..................................................................................................... 47 SHOW ............................................................................................................... 48 CONNECTIONS................................................................................................ 49 OTHER.............................................................................................................. 50 CONNECT TO C-BUS ...................................................................................... 51 USING C-TOUCH AS A PC INTERFACE ........................................................ 52 DEFAULT FONT............................................................................................... 53 SHOW RESOURCES .................................................................................... 54 SHOW REMOTE ........................................................................................... 56 SIMULATION MODE ..................................................................................... 57 EVENT LOG .................................................................................................. 58 DOWNLOADING TO C-TOUCH.................................................................... 60 DOWNLOADING VIA THE SERIAL CABLE ................................................ 60 DOWNLOADING VIA C-BUS........................................................................ 62

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 2

Intelligent Building Series 1.0

C-Touch Training Manual

PRODUCT RANGE

The products included in this range are: SC5000CTA

C-Touch, slim line style (includes one 5035TX)

BS5000CTA

C-Touch, stainless steel (includes one 5035TX)

BB5000CTA

C-Touch, brass (includes one 5035TX)

BG5000CTA

C-Touch, gold (includes one 5035TX)

BC5000CTA

C-Touch, chrome (includes one 5035TX)

BP5000CTA

C-Touch, powder coated (includes one 5035TX)

5035TX

C-Touch (or Scene Master) hand held infrared remote control.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 3

Intelligent Building Series 1.1

C-Touch Training Manual

DESCRIPTION

The C-Touch unit is a flexible and powerful controller and schedular for C-Bus systems which has infrared remote control capabilities. C-Touch is a touch screen with a black and white liquid crystal (LCD) display, which can be mounted in the wall of your home or building and can be connected to the CBus home automation system. It can provide a central point of control and scheduling of services throughout the home. The C-Touch unit can display a series of “pages” which contain touch sensitive controls associated with various loads throughout the C-Bus Network. These pages may be re-configured by means of a personal computer running the C-Touch configuration software. Through the C-Touch unit the user may set up “scenes” with multiple loads coming on together to set a particular mood at the press of a soft button. The C-Touch unit can also control loads according to a schedule.

The appearance of every C-Touch setup will be unique, so your C-Touch display may not look like the examples in this guide.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 4

Intelligent Building Series 1.2

C-Touch Training Manual

CAPABILITIES

The C-Touch unit can provide the following functions: Switching of loads. Dimming. User presets. User timers. Screen care and maintenance facility. Inbuilt self-diagnostic utility. Page based display of information from a C-Bus Network. Pages can contain drawings, pictures and text in multiple languages. Control of up to 100 different loads in different areas. Provision of Scenes to control multiple loads. Provision of Scheduling, loads can be turned on or off on a regular basis. Variable fade rates for each load or lighting zone. Infra-red remote control. Backlit display for ease of use in low light situations. User-Friendly naming of controls. Display of time and date. Adjustable Confirmation beep. Adjustable Backlight Control.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 5

Intelligent Building Series 1.3

C-Touch Training Manual

DEFINITIONS

The following definitions are useful in discussing the C-Touch unit: TERM

DEFENITION

Load

A load is an electrical device connected to mains voltage via a C-Bus Output Unit. Most loads are lights, but may be any device such as sprinklers, AC Power points, heaters, projection screens, motors etc.

Scene

A scene is defined as the combination of loads distributed in various control zones with different levels. The scene can be set up with the configuration software and assigned to soft keys on the C-Touch unit.

Fade Rate

The fade rate indicates the length of time it takes for a load to ramp to a desired level.

Zone

Refers to an illuminated area. In C-Touch a zone is a C-Bus Group address representing one or many loads connected to a C-Bus output unit. All the lights in your dining room might be in one zone.

Schedule

A schedule is a sequence of events that are to occur at particular times or dates in the future.

Soft Key

An area on the surface of C-Touch which can be pressed to cause something to happen.

Page

A page is an assortment of soft keys and graphics that represents something understandable to the user.

Component

A graphical object displayed on a C-Touch screen. Components include soft keys, images, text, clocks, temperature sensors and other items.

Backlight

The back of the screen is illuminated to make it visible when it is dark. This illumination is called backlight.

Input Unit

An input unit is a C-Bus unit which the user interacts with to make things happen on a C-Bus Network (C-Touch itself, a key input unit or passive infrared sensor are examples)

Output Unit

An output unit delivers power to loads; a relay and dimmer are examples.

Control

A component that can be used to turn loads on or off or change their level.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 6

Intelligent Building Series 2.0

C-Touch Training Manual

ADDING ITEMS TO THE DISPLAY

Components can be added to the touch screen by clicking once on the chosen speed button, which are located on the tool bar. Move the cursor down to the touch screen and click once again where you want the component to be. The desired item should now appear on the touch screen.

Figure 2.0 2.1 ICON

FUNCTIONS OF THE TOOL BAR OPTIONS DESCRIPTION This icon will allow the user to edit the current project’s details.

This button creates a new page in the current project.

This icon opens a Touch Screen project.

This button saves the project. If the project is new, this button will open a ‘Save As’ window. This option allows shapes to be drawn on the screen. It will place whatever shape is selected in the drop down list, which is situated to the left of it. This allows you to place a button, like the one on the speed button, onto the screen. It also has an indicator to show the C-Bus state. This is a button with no action associated with it. It is usually used to select other pages to display. If a heading for a page or text is required on the screen, click this button and a box will pop up allowing you to type. Once the text is entered press ‘OK’ and click on the display. A picture can be inserted onto your display by pressing this button.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 7

Intelligent Building Series ICON

C-Touch Training Manual

DESCRIPTION Allows the date and time to be placed on the display. The date and time display can be altered to personal preference. If you want a slider on your display press this button. A slider can be used to control or monitor load levels. Displays what load level is being used for that particular group address. It can be used below a slider to display exactly what the load level is. Monitor function allows user to monitor the temperature, voltage and light level. A basic indicator that can be associated with a group address. The indicator will become illuminated when that group address is turned on. This is the tools button. It allows you to place tools on your page which allow you to change such things as date, time, brightness of display, contrast etc. Cuts the selected component(s).

Copies the selected component(s).

Pastes the cut or copied component(s) onto the touch screen display. NOTE: A pasted component will be placed on top of the cut/copied component, so it may look as if nothing has happened. The paint format button allows you to copy the style of a component and paste it onto another so it looks the same. To do this, highlight the component you want to copy, press the copy button, highlight the component(s) you want to change and press the paint format button. NOTE: This function only changes the look of the component, all it’s previous functions will remain the same. Undo tool. Allows the user to undo the previous action performed.

Selects all the components on the page. This is useful when all components need to be moved together, copied or deleted.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 8

Intelligent Building Series ICON

C-Touch Training Manual

DESCRIPTION When components are selected it allows the secondary component(s) to be aligned with the primary component. Components must be selected first and when the button is clicked an option menu will pop up displaying alignment options. Changes the height of the secondary component(s) to match the height of the primary component. Components must first be selected. Changes the width of the secondary component(s) to match the width of the primary component. Components must first be selected. Used when components on the screen are placed overlapping each other. Selecting a component and pressing this button will move it to the back of the order, it will place the component behind all others. This has basically the same function as the previous button except the selected component will only move 1 position back rather than behind all other components. Moves the selected component 1 position forward.

Moves the selected component to the front of the order. It places it in front of all other components This button allows you to schedule loads to come on at specific times, on certain days etc. This is explained in more detail later on. This button is a shortcut button to the edit scene menu. It brings up the menu allowing you to create a scene or edit an existing scene When text on your display is highlighted you can press this button to change the default font, size etc. This font will be used next time you place a component with text on it.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 9

Intelligent Building Series 3.0

C-Touch Training Manual

GETTING STARTED

Open up the program C-Touch. A touch screen unit should now appear on the screen with a blank display, as below. Once the program has loaded drop down the ‘FILE’ menu and select ‘NEW PROJECT’.

Figure 3.1

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 10

Intelligent Building Series 3.1

C-Touch Training Manual

TOUCH SCREEN PROJECT DETAILS

Once the New Project option is selected, a window titled ‘Touch Screen Project Details’ will open. Clicking on ‘Edit’ and ‘Project Detail’ can also access the project details window. This will allow the programmer to perform various functions to the touch screen. There are four selectable tabs: Screen Type Project Installer Options 3.1.1

SCREEN TYPE

Figure 3.2 There are two options to choose from on the Screen Type Tab: Model Type

Selects type of touch screen.

Orientation

Selects what whether the IR receiver is on the top or bottom.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 11

Intelligent Building Series 3.1.2

C-Touch Training Manual

PROJECT TAB

Figure 3.3 The Project Tab allows the programmer to enter in various details about the installation such as: Project Name

Location

Consultant

Architect

Owner

Notes

There are also three other drop down menus on this tab: C-Bus Project

Allows the programmer to make an association to a CBus project. This allows the C-Touch software to use the same Tag Descriptions as used in the C-Bus Software.

Touch Screen is on

Allows the programmer to specify what network the touch screen is on, in the case of a multi-network installation.

Unit Address

Allows the programmer to specify what the unit address of the touch screen is.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 12

Intelligent Building Series 3.1.3

C-Touch Training Manual

INSTALLER TAB

Figure 3.4 The Installer Tab provides a facility for the programmer to enter in his or her own details. This is important for the customer as it provides them with contact details if reprogramming is required. These details include: Name

Country

Company

Phone

Address

Mobile

City

Fax

State

E-mail

Postcode

Web Site

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 13

Intelligent Building Series 3.1.4

C-Touch Training Manual

OPTIONS TAB

Figure 3.5 The Options Tab allows the programmer to once again program the touch screen with various setting. These setting are: Time-Out Details

Key Press Sounds

Start-Up Details

Miscellaneous

The Time-Out Details allows the programmer to: Time-Out Page

Determine which page to revert to after a specified period.

Dark Time-Out Page

Determine which page to revert to after a specified period if the room is dark.

Time-Out After

A Period of time before the touch screen reverts to a Time-Out Page. This timer is re-triggered each time the touch screen is pressed.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 14

Intelligent Building Series

C-Touch Training Manual

The Start-Up Details allows the programmer to: Start-Up Page

The page the touch screen will revert to directly after downloading a project, or C-Bus Power is reinstated.

Installer Details

Name of Installer.

Installer Contact Details

The installers company contact details.

The Key Press Sounds allows the programmer to: Volume

Specify the volume of each press of the touch screen.

Pitch

Determines the pitch of the beep each time the touch screen is pressed.

Duration

Determines how long the beep will last each time the touch screen is pressed.

The Misc function allows the programmer to: Show Night Light

Enables and disables the backlight.

Once all of the information in the Project Details has been entered, press the ‘OK’ button. The C-Touch software will then revert back to the main programming page.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 15

Intelligent Building Series 3.2

C-Touch Training Manual

PAGE FUNCTIONS

There are various page properties that may be needed when programming a touch screen. They can be accessed by clicking on ‘Edit’ and then ‘Page.’ There the programmer will notice the various options: Delete Page

Deletes the current page shown in the page drop down menu.

New Page

Adds a new black page to the project. Following this a window will appear asking the programmer to give the new page a unique name.

Add Pages

Adds an existing project to the current project (Scenes and Scheduled included).

Duplicate Page

Creates an exact duplicate of the selected page. Following this a window will appear asking the programmer to give the duplicated page a unique name.

Page Properties

Allows the programmer to change the name of an existing page and password protect the page. This function can also be acceded by double left clicking on a blank section of the touch screen.

When the Page Properties button is selected a window below will appear. To change the page name simply type in the new name in the designated section of the window. To add or change a password on the page, click on the ‘Set Password’ button. This will prompt another window where the password can be entered. The password must consist of a combination of numbers (0 to 9), and be a maximum of 6 numbers long.

Figure 3.6

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 16

Intelligent Building Series 4.0

C-Touch Training Manual

C-TOUCH COMPONENTS

Various Components can be placed on the touch screen. These components can be placed on the screen by clicking on ‘EDIT’ and then ‘PLACE COMPONENTS’ or selecting the desired button on the tool bar. The C-Touch components consist of: Shape

Places the selected shape on a Touch Screen.

C-Bus Button

A button specifically used to turn group addresses to dim, of switch on or off.

Text Button

A button used to navigate between pages.

Text

Places text onto the screen of all different fonts and sizes.

Image

Places a black and white bitmap onto the screen.

Clock

Places a programmable clock onto the screen.

Slider

Places an indicator in slider form used for monitoring C-Bus output levels.

Percentage

Places an indicator in a numeric percentage form used for monitoring C-Bus output levels.

Indicator

Places an indicator on the screen to monitor output levels.

Tools

Places special preset text buttons on the screen to access special functions.

Note: - All of these listed components share the same GUI. This means that most of these components can be programmed in a similar way.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 17

Intelligent Building Series 4.1

C-Touch Training Manual

COMPONENT PROPERTIES

The component properties GUI consists of various tabs which allow the installer to program the components to achieve the desired result. These fundamental functions are: Visual Properties

Allows the programmer to change the physical appearance and location of the component.

Page Link

Allows the programmer to make a component jump to a designated page.

Special Functions

Allows the programmer to make a component link to one of the touch screens special functions.

Remote Control

Allows the component to be infrared enabled.

C-Bus

Allows the component to control C-Bus.

4.1.1

VISUAL PROPERTIES

The options on the Visible Properties tab depend upon the type of component. POSITION TAB This allows you to manually enter the size and position of the component.

Figure 4.1

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 18

Intelligent Building Series

C-Touch Training Manual

BORDER TAB This tab allows you to enter the appearance of the border of the component.

Figure 4.2 Border Style

Allows the border type and shape to be changed.

Line Style

Allows the line style to be changed, i.e. dashed, solid transparent etc.

Border Width

Modifies the physical thickness of the border.

Colour Status Indication

Allows the border colour to change to show the status of the associated C-Bus group. Select the Active Border Colour and Inactive Border Colour to designate what colour the borders will change to.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 19

Intelligent Building Series

C-Touch Training Manual

BACKGROUND TAB This tab allows you to enter the appearance of the background of the component. You can select the style and colour. Note that the background can be set to none to make it transparent.

Figure 4.3 Background Style

Selects the type of background used on the component.

Colour Status Indication

Allows the border colour to change to show the status of the associated C-Bus group. Select the Active Background Colour and Inactive Background Colour to designate what colour the borders will change to.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 20

Intelligent Building Series

C-Touch Training Manual

TEXT TAB This tab allows you to set the text, the text alignment (top, left centre etc) and the text font.

Figure 4.4 Text Font Status Indication

Allows the set text to change to show the status of the associated C-Bus group.

Set Font

Allows the programmer to use a variety of different fonts and sizes on various components. Each font added will be made available to all other components.

Text Alignment

Copyright 2002

Allows the text to be aligned in various positions within a button.

Clipsal Integrated Systems Pty Ltd

Page 21

Intelligent Building Series

C-Touch Training Manual

IMAGES TAB This tab allows you to select which image(s) are displayed on a button component and the image alignment (top, left, centre etc).

Figure 4.5 Show Image

Displays an image on a C-Bus Button. Either selects one of the standard images, or click on the Custom button and select your own active and inactive images.

Transparent Image

An image can be made transparent by selecting the Transparent Image check box. The colour of the bottom left pixel will be used as the transparent colour. Any pixels in the image matching this colour will not be displayed (i.e. will be transparent).

Image Alignment

Copyright 2002

Allows the text to be aligned in various positions within a button.

Clipsal Integrated Systems Pty Ltd

Page 22

Intelligent Building Series

C-Touch Training Manual

CLOCK TAB The clock tab allows you to set the properties of a clock component. It also has a timer function.

Figure 4.6 Time

Allows programmer to display and format the time details if required.

Day

Allows programmer to display and format the day details if required.

Date

Allows programmer to display and format the date details if required.

C-Bus Timer

Allows the programmer to a timer mode. The time displayed will not be the current time, but the remaining time left on the timer for the associated C-Bus Group Address.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 23

Intelligent Building Series

C-Touch Training Manual

SLIDER TAB This tab allows the programmer to edit the appearance of a slider component.

Figure 4.7 Slot

This edits the slot’s properties of the slider.

Tick Marks

This edits the markings of the slider.

Thumb

This edits the properties of the slider.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 24

Intelligent Building Series

C-Touch Training Manual

MONITOR TAB This allows you to set the properties of a Monitor Component. You must select the unit address of the C-Bus device that is having its data read. The type of data displayed, its precision and the update rate can all be set. Avoid updating the value more often than is absolutely necessary to avoid excessive C-Bus network traffic.

Figure 4.8 Monitor Type

Allows the monitoring of: • Temperature • Voltage • Light Level

Unit Address

Selects the unit address of each sensor or output unit

Refresh Rate

Determines how often the monitored reading is updated.

Accuracy

Determines how many decimal places are used on the reading (0-2).

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 25

Intelligent Building Series 4.1.2

C-Touch Training Manual

PAGE LINK

This tab allows the user to make links between pages. Every page which has been created in the project will appear in the page drop down menu.

Figure 4.9 User Page

Links to a page designed by the user.

Special Page

Links to a special tools page.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 26

Intelligent Building Series 4.1.3

C-Touch Training Manual

SPECIAL FUNCTION

When a component is activated, it can cause some “Special Functions” to be executed. To do this, a special function needs to be added to the component. Special Functions include: Setting the Time Setting the Date Setting the Contrast Controlling the backlight Setting the Backlight Threshold All of these things are normally done with the special pages which are included with C-Touch. There may be occasions where it is necessary to control these features from other pages (for example, having a time setting page in another language).

Figure 4.10

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 27

Intelligent Building Series 4.1.4

C-Touch Training Manual

REMOTE CONTROL

The C-Touch unit can be controlled from a remote control. You can either use the one that comes with the unit, or any remote control which uses NEC codes. A remote control key can be associated with a Component on the C-Touch unit. When the remote control key is pressed, the C-Touch unit will act as if you pressed the screen in the centre of that component. To set up the association between a component and a remote control key : Select the Remote Control tab from the Component Properties dialogue box Select the IR Remote Control Enabled check box. If you are using the remote control that came with the C-Touch unit, you can just select the desired key from the drop-down list. If you are using another remote control unit, you will need to enter the Manufacturer and Key codes. Remote control codes can be found on various web sites, or can be read via the C-Touch unit. To do this, you need to have a C-Touch unit and select the Diagnostics page. Select the Unit Data page, and there will be information about the last received IR code. Point your remote control at the C-Touch unit and press the key. You will see the Manufacturer Code and Key Code appear on the C-Touch screen. These values can then be entered in the Component Properties dialogue box. You can test that the remote control codes have been set up correctly (if using the remote control that came with C-Touch) by selecting the Show Remote item from the Options menu. A dialogue box will appear with an image of the remote control unit on it. Clicking on one of the keys will execute the action set up for that key.

Figure 4.11

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 28

Intelligent Building Series 4.1.5

C-Touch Training Manual

C-BUS

The C-Bus tab acts like a key input unit GUI except: There are more presets. There are no custom functions using key commands. The component will behave differently depending on which type is selected. The CBus component can be set to any of the following types: ICON

FUNCTION

DESCRIPTION

ON

This switches the load on.

OFF

This switches the load off.

ON/OFF

This toggles the load on and off. If the load level is greater than 0%, it is regarded as being on.

DIMMER

A short press will toggle the load on and off. A longer press will dim the load up and down.

ON/UP

A short press will switch the load on. A longer press will dim the load up.

OFF/DOWN

A short press will switch the load off. A longer press will dim the load down.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 29

Intelligent Building Series ICON

C-Touch Training Manual

FUNCTION

DESCRIPTION

TIMER

This will switch a load to a particular level for a particular time. When the time expires, the load will return to a specified level.

PRESET

This will set the load to a preset level (0-100%).

PRESS

This will set the load to a particular level while the component is being pressed. When the component is released, the load will return to a specified level.

SCENE

This will set a scene.

STATUS

This will show the C-Bus status, but pressing the component will have no effect.

UNUSED

This will not show C-Bus status or perform and C-Bus action when pressed.

To set the C-Bus properties : Select the C-Bus type. Enter the network. Enter the Application Number. Enter the Group Address. Then select any other properties required for the C-Bus type. If the component is to be a preset, press or timer, you will need to select the following properties: Level

You can either select a particular level in percent or a tag. If you are connected to C-Bus, you can also use the current level of the Group Address.

Ramp Rate

Select a rate at which the Group Address level is to change.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 30

Intelligent Building Series

C-Touch Training Manual

If the component is a timer, you will need to select the timer duration and type. A toggle timer will start when it is pressed, then stop after the time-out period, or if the timer is pressed again before it has timed out. A re-settable timer will start the timer again if pressed before the timer has expired. Note that a clock component can be used to display the amount of time left on a timer. If the component is a press button or a timer, you need to select the level to which the Group Address is to return to when the press button is released or the timer expires.

Figure 4.12

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 31

Intelligent Building Series 4.2

C-Touch Training Manual

TOOLS

When a component is activated, it can cause another page to be displayed. To do this, a link to the user defined page needs to be added to the component. It is also possible to create links to special Tool buttons. These tools are unable to be accessed on the C-Touch software, as they can only be accessed once the project has been downloaded into the touch screen. Buttons with links to the special tool pages can be created quickly by clicking on the “tools” button on the tool bar, then selecting the required one. Otherwise they can be programmed on the ‘Page Link’ settings in the C-Touch software. The special functions are: BACK

If the user clicks on the component, the previous page will be displayed.

CALIBRATION

This allows the C-Touch unit touch panel to be calibrated.

DIAGNOSTICS

This shows some diagnostics information.

STARTUP PAGE

This displays the start-up page.

CLEANING MODE

This puts the unit in cleaning mode.

TIME SET

This allows the user to set the time.

DATE SET

This allows the user to set the date.

CONTRAST SET

This allows the user to set the C-Touch unit contrast.

BACKLIGHT SET

This allows the user to control the backlight.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 32

Intelligent Building Series 5.0

C-Touch Training Manual

SCHEDULES

A Schedule is an event that is set to occur at a particular time on particular days. The C-Touch scheduler allows the programmer to include up to 250 schedules. 5.1

EDIT SCHEDULE

Schedule Editor allows the user to add or edit a schedule in a project. The Schedule Editor is accessed via a number of methods: By clicking on the Schedules button on the tool bar. By clicking on ‘Edit’, then ‘Schedule’ and ‘Edit Schedule.’ By clicking on ‘Edit’, then ‘Schedule’ and ‘Schedule Monitor.’ This will bring up another window which has an Edit Schedule button on the tool bar.

Figure 5.1 There are four options that may be used when programming a schedule: To create a new schedule click on the add button. To delete a schedule select a schedule in the list and click the delete button. To edit a schedule select a schedule in the list and click the edit button. To make a duplicate of a schedule, select a schedule in the list and click the duplicate button. If the Add or Edit button is selected, then a window called ‘Schedule Item’ will appear. This will allow the programmer to program the Schedule.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 33

Intelligent Building Series 5.2

C-Touch Training Manual

SCHEDULE ITEM

Each Schedule has several main properties: A name/description An enabling Group Address A time A day An event Once the Schedule Item opens there is a area called description that needs to be filled in (see Figure 5.2). Description

Copyright 2002

The description for the Schedule is set in a box above all the tabs. The description should be something meaningful to you so that it makes sense when you see it in a list. This name will appear in the Schedule Manager’s Schedule List (Figure 5.1).

Clipsal Integrated Systems Pty Ltd

Page 34

Intelligent Building Series 5.3

C-Touch Training Manual

ENABLE TAB

The Enable Tab acts as on override control for the C-Touch Scheduler. If the Schedule does not need to be turned on and off, leave this as “unused”. Typically, a particular Group Address on the Control Application (number CA hex) will enable the Schedule when it is at 100%.

Figure 5.2 Application

Selects the Application that the enable Group Address will be on.

Group

Selects the Group Address that will enable or disable the Schedule.

Level

Selects a level for the Enable Group Address to reach before the Schedule is enabled. The ‘100%’ and ‘0%’ button are shortcut levels. Same function as Level, but the Group Address and Level are included in the same ‘Tag’ description. This tag can be created in both the C-Bus and C-Touch Software.

Tag

There are also two buttons to the left of the Group drop down box. They are: Add Group

Adds a new group to the project. This function can only be accessed if a project has been selected in the project details.

Edit Group

Edits an existing Group Address’ Tag Description. This function can only be accessed if a project has been selected in the project details.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 35

Intelligent Building Series 5.4

C-Touch Training Manual

TIME TAB

The Time Tab (shown below) has the function to set the time that the schedule will be triggered on (assuming that the schedule is enabled). The time is set in a 24 hour clock format in hh:mm:ss.

Figure 5.3

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 36

Intelligent Building Series 5.5

C-Touch Training Manual

DAY TAB

The day(s) that the Schedule is to occur is set on the Day tab as shown below. By default, the Schedule is set to occur every day.

Figure 5.4 There are two ways of selecting the day: By clicking in the drop down box. This has 6 preset calendar periods to choose from. By clicking the ‘More’ button. This allows for specific programming on any combinations of days in a year (see Figure 5.5). Once Only

You will need to enter the date, or select it from the dropdown calendar.

Every Day

Runs the schedule every single day.

Every Week Day

Runs the schedule from Monday to Friday.

Every Weekend

Runs the schedule from Saturday and Sunday.

Every Week

Runs the schedule on a specific day of the week.

Every Month

Runs the schedule on a specific day of the month.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 37

Intelligent Building Series

C-Touch Training Manual

For more complicated day selections, the programmer must select the ‘More’ button. This will change the GUI as shown below. There are 4 levels of programming: Day Of Week

Day Of Month

Month

Year

Figure 5.5 Day Of Week

Selects specific days of the week. The buttons below the days are shortcut buttons, allowing you to quickly select all days, clear all days, set week days or weekends.

Day Of Month

Selects a specific date within a month. The buttons below the dates are shortcut buttons, allowing you to quickly select all days, clear all days, or select the 1st, 2nd, 3rd or 4th quarter of a month.

Month

Selects a specific combination of months. The buttons below the months are shortcut buttons, allowing you to quickly select all months or clear all months.

Year

Has the option of selecting any year or a specific year.

The Days, Months and Years can be combined in any way you wish. So for example, if you want the Schedule to occur on the first Tuesday of every month, select Tuesday and the first 7 days of the month.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 38

Intelligent Building Series 5.6

C-Touch Training Manual

EVENT

The event is the action that will occur at the scheduled time and day. There are three choices: Ramp Group. Pulse Group. Set Scene. The Ramp Group Function allows a schedule to turn a single Group Address on or off.

Figure 5.6 Network

Selects a network to issue a C-Bus command to.

Application

Selects an Application for a C-Bus command to be issued to.

Group Address

Selects the Group Address that will be actioned upon when the schedule is activated.

Level

Sets the Group Address to a specific level. The ‘100%’ and ‘0%’ button are shortcut levels.

Ramp Rate

Copyright 2002

Provides a selectable ramp rate or an instant on or off command.

Clipsal Integrated Systems Pty Ltd

Page 39

Intelligent Building Series

C-Touch Training Manual

The Pulse Group works the same as the Ramp Group function, however the Pulse Group is a timer. The schedule will turn a Group Address on for a period of time, and the turn off after the timer has timed out.

Figure 5.7 Network

Selects a network to issue a C-Bus command to.

Application

Selects an Application for a C-Bus command to be issued to.

Group Address

Selects the Group Address that will be actioned upon when the schedule is activated.

Level

Sets the Group Address to a specific level. The ‘100%’ and ‘0%’ button are shortcut levels.

Ramp Rate

Provides a selectable ramp rate or an instant on or off command.

Duration

Set the amount of time that the schedule will run for.

Return To Original Level

Will return the Group Address to its original level (before the schedule started) once the schedule has ended.

Return To Level

Will return the Group Address to a specified level once the schedule has ended.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 40

Intelligent Building Series

C-Touch Training Manual

The Set Scene function allows a schedule to trigger a scene at a specified time.

Figure 5.8 Scene

The Scene Drop Down menu will contain any scenes compiled by the programmer.

Edit / Add

Allows the user to add and edit the scenes to be triggered by the scheduler.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 41

Intelligent Building Series 5.7

C-Touch Training Manual

SCHEDULE MONITOR

The Schedule Monitor allows the user to see all schedules in a project, and to see which are active. To open the Schedule Monitor dialogue box, click on ‘Edit’ then ‘Schedule’ and then ‘Schedule Monitor.’ Note that Schedules will not be executed unless the Scheduler is running. It can also be set running by clicking on the Run Scheduler item in the Schedule menu.

Figure 5.9

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 42

Intelligent Building Series 6.0

C-Touch Training Manual

SCENES

A Scene is a pre-determined set of levels for particular Group Addresses. A scene can be used to set a series of lights to particular levels rather than setting them individually. Unlike other C-Bus Scene devices, the touch screen can accommodate: 100 Scenes. 100 Group Addresses per Scene. To access or create a new scene click on ‘EDIT’ and ‘SCENE,’ then click on ‘EDIT SCENES.’ It can also be accessed by clicking on the shortcut button in the tool bar. This will open the Scene Manager.

Figure 6.1 There are four options that may be used when programming a scene: To create a new scene click on the add button. To delete a scene select a scene in the list and click the delete button. To edit a scene select a scene in the list and click the edit button. To make a duplicate of a scene, select a scene in the list and click the duplicate button.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 43

Intelligent Building Series

C-Touch Training Manual

If the Add or Edit button is selected, then a window called ‘Scene Item Edit’ will appear. This will allow the programmer to program the Scene. The Scene Editor allows the user to edit a scenes in a project. The Scene Editor is accessed via the Scene Manager. Each Scene has several main properties: A name/description. A triggering Group Address. A series of actions.

Figure 6.2

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 44

Intelligent Building Series 6.1

C-Touch Training Manual

SCENE NAME

The name should be something meaningful to you so that it makes sense when you see it in a list. This name will appear in the Scene Manager. Once a scene has been created, it is possible to quickly make the scene settings correspond to the current C-Bus levels by clicking on the Reset All Levels button. This is only available if the software is connected to C-Bus. 6.2

TRIGGERING

The triggering Group Address is the Group Address and Level that trigger the Scene to be executed. If the Scene does not need to be triggered from a remote unit, leave this as “unused”. Typically, a particular Group Address on the Control Application (number CA hex) will trigger the Scene when it is at 100%. Note: - To trigger a scene, the group address needs to be set to the trigger level, not merely ramp through it. Note: - On and Off commands should not be used to trigger scenes on the Control Application because they are not supported by the Control Application in any C-Bus devices. Only use ramp to level commands to trigger devices using the Control Application. Application

Selects the Application that the enable Group Address will be on.

Group

Selects the Group Address that will trigger the Scene.

Level

Selects a level for the Remote Group Address to reach before the Scene is triggered. The ‘100%’ and ‘0%’ button are shortcut levels. Same function as Level, but the Group Address and Level are included in the same ‘Tag’ description. This tag can be created in both the C-Bus and C-Touch Software.

Tag

There are also two buttons to the left of the Group drop down box. They are: Add Group

Adds a new group to the project. This function can only be accessed if a project has been selected in the project details.

Edit Group

Edits an existing Group Address’ Tag Description. This function can only be accessed if a project has been selected in the project details.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 45

Intelligent Building Series 6.3

C-Touch Training Manual

ACTIONS

The actions are the C-Bus events that the Scene will execute. There are a number of buttons that are used when making new actions, they are: Add

Includes a new action into a scene.

Delete

Removes an existing action from a scene.

Edit

Allows actions to be modified within a scene.

Up

Shifts an existing action up the list.

Down

Shifts an existing action down the list.

To create a new action simply click the add button. This will allow the programmer to access the various parameters needed to create a scene. Network

Selects the Network that the Group Address is on.

Application

Selects the Application that the Group Address will be on.

Group

Selects the Group Address that will be included in the Scene.

To Tag

Selects a level for the Remote Group Address to reach before the Scene is triggered. The ‘100%’ and ‘0%’ button are shortcut levels.

To Level

Same function as Level, but the Group Address and Level are included in the same ‘Tag’ description. This tag can be created in both the CBus and C-Touch Software.

Ramp Rate

Selects the amount of time needed for a group address to turn on or off.

Once all this information is entered, click ‘OK’ and the action will be added to the scene list. Continue to do this until the scene is completed.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 46

Intelligent Building Series 7.0

C-Touch Training Manual

PROGRAM OPTIONS

The Software can have various options configured by selecting the Program Options item from the Options menu. 7.1

AUTO SAVE

When Auto Save is enabled, the project will be saved at regular intervals. The interval can be set to between 5 and 60 minutes.

Figure 7.1

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 47

Intelligent Building Series 7.2

C-Touch Training Manual

SHOW

The Show tab allows the programmer to set up the software for easy use.

Figure 7.2 Show Background

Adds and Removes the touch screen face plate from the main display.

Show Component Toolbar

Adds and Removes all of the shortcut buttons for the components.

Show Edit Toolbar

Adds and Removes all of the shortcut buttons for the editing functions.

Show Status Bar

Adds and Removes the status bar.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 48

Intelligent Building Series 7.5

C-Touch Training Manual

CONNECTIONS

This tab allows you to select how you wish to connect to C-Bus and to C-Touch.

Figure 7.3 With connecting to C-Bus, you can either connect directly via a serial port, or via CGate. If you are connecting via serial, you also have the following options : Which COM port you want to use. The PC Interface Version. Note that the software works best with PC Interfaces of version 3.12 or later. If your PC Interface is earlier than Version 3 (you can find out the version using the C-Bus Installation Software), you will need to select Version 1 or 2 PC Interface. Whether you want to do a full network scan on start-up. The network scan is time consuming, but is necessary if you want to be sure of establishing all of the Group Address Levels. If you are connecting via C-Gate, you can select which IP Address C-Gate will be at. When connecting to C-Touch, you have two options: Connecting directly via a serial port. If you are connecting directly, just select the COM port number. Connecting via C-Bus, you will also need to have set the Unit Address of the touch screen in the Project Details dialogue box. Note that when connecting via C-Bus, you can not use C-Gate.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 49

Intelligent Building Series 7.6

C-Touch Training Manual

OTHER

By default, when the right mouse button is clicked on a component, the action for that component is executed. You can alternatively have a pop-up menu appear when the right mouse button is clicked.

Figure 7.3

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 50

Intelligent Building Series 8.0

C-Touch Training Manual

CONNECT TO C-BUS

The C-Touch Configuration Software can control C-Bus if it is connected. This is used mainly for testing purposes, but can also be used for establishing the current group address levels when setting scenes. To connect to C-Bus, select the Connect to C-Bus sub menu from the Options menu. This will connect you to C-Bus using the method set-up in the Program Options. The software will take several seconds to read the current state of the C-Bus network.

Figure 8.1 Once connected, a message will be returned saying that the touch screen software has connected to C-Bus. All C-Bus buttons on the software will show and control the state of C-Bus Group Addresses.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 51

Intelligent Building Series 8.1

C-Touch Training Manual

USING C-TOUCH AS A PC INTERFACE

You can also use the C-Touch unit as a PC Interface. Connect your PC to the CTouch serial connector using the cable supplied and to connect to C-Bus. C-Touch will display a message that it is in PC Interface Mode. When you have finished, remove the cable, and C-Touch will reset itself. Note: - The C-Touch will not operate in its normal manner while it is being used as a PC Interface. A simple method to enable the C-Touch to be used as a PC Interface is: Start the C-Touch Configuration Software. Select Connect to C-Bus from the Options menu. Select the required COM port. Disconnect again, repeating steps 2 and 3. The above steps have now set the Handshaking lines and any software may use CTouch as a PC Interface (provided the software does not reset the handshaking lines).

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 52

Intelligent Building Series 9.0

C-Touch Training Manual

DEFAULT FONT

To edit a font in the C-Touch project, simply click on ‘OPTIONS’ and then ‘FONTS.’ Fonts can also be accessed from the fonts button the toolbar. This will open the font selection window. There you will see a list of fonts currently in use and an example of what the text looks like.

Figure 9.1 To add a new font, select the ‘Select Other Fonts’ button. This will open another window that will allow the programmer to select: Font Size Font Style (Bold, Italics etc) Effects (Strikeout, Underline and Colour) Script (Greek, Arabic Text etc)

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 53

Intelligent Building Series 10.0

C-Touch Training Manual

SHOW RESOURCES

The C-Touch Configuration Software generates a file which is downloaded to a CTouch unit. The C-Touch units have limited amounts of memory, so you are limited in the size of the configuration file that you can download. The 5000CTA has 256K of non-volatile memory, of which 64K is used by the software, leaving 192K for the user configuration data. If you select the Show Resources item from the Options menu, a dialogue box will be displayed.

Figure 10.1

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 54

Intelligent Building Series

C-Touch Training Manual

This graphical display shows the amount of memory that you have used, and where it is being used. The memory is broken down into the following sections : Program

This cannot be controlled by the user.

Bitmaps

This is the memory used by image components.

Fonts

This is the memory used by the fonts.

Components

This is the memory used by the other components.

Other

This is the memory used by scenes, schedules and other items.

Spare

This is the amount of memory left

The purpose of this is to enable you to see where the memory is being used to help you to make a more efficient project. In order to minimise the size of the download file, follow these hints: Minimise the number and size of bitmaps. A full-screen bitmap will use 10k Bytes of C-Touch memory. Minimise the size of Buttons. Minimise the number of fonts used (only the fonts for clocks, percentage indicators and monitors are downloaded). Make the appearance of buttons that do the same thing (eg sliders or a “back” button) identical. Identical buttons are only saved once (if optimisation is on). Anything that you can’t see (eg. the group address or page link details) will not affect this.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 55

Intelligent Building Series 11.0

C-Touch Training Manual

SHOW REMOTE

The show remote function can be accessed by clicking on ‘OPTIONS’ and then ‘SHOW REMOTE.’ This will open up a photo of the 8 Key Remote Control.

Figure 11.1 By clicking on the buttons on the remote control, the user can test and control CTouch components that have been programmed for remote operation.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 56

Intelligent Building Series 12.0

C-Touch Training Manual

SIMULATION MODE

The touch screen software can be put into simulation mode by clicking on ‘OPTIONS’ and then on ‘SIMULATION MODE.’ It can also be access by pressing ‘Ctrl’ and ‘S.’ Simulation mode does the following things: Components are activated by a left or right mouse click. Passwords operate. The menus and tool bars are hidden. Note: - The software is always in a partial simulation mode. To make a Component do its programmed function, right click on the component. If the component has a link, the new page will be selected. If the component is a button, the state of the button will change (if C-Bus is connected, the command will be executed).

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 57

Intelligent Building Series 13.0

C-Touch Training Manual

EVENT LOG

An event log can be used to monitor the C-Bus events which have occurred. To show the event log, select the ‘SHOW LOG’ item from the ‘OPTIONS’ menu.

Figure 13.1 There are four radio buttons which determine the state of the logging: Disable Log

This disables the logging.

Enable Log

This enables the logging.

Save to File

This saves all logged events into the selected file.

Append to File

This appends all logged events to the end of the selected file.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 58

Intelligent Building Series

C-Touch Training Manual

There are also checkboxes at the bottom of the dialogue box that enable various options: Show Data as CSV

This logs all data as Comma Separated Values to allow the log file to be imported into a spreadsheet, database or other program.

Show Sent Commands

This enables the logging of commands sent from the software.

Show Received Commands

This enables the logging of commands received from C-Bus.

Show Event Time

When selected, this appends the date and time of each event.

There are four buttons that provide additional functions: Clear

This clears all entries in the log (but not in the file).

Select File

This allows the desired file name to be selected.

Close

This hides the log (but does not disable logging). Note that events will continue to be logged, even if the log is hidden, as long as the Enable Log, Save to File or Append to File options are selected.

Help

Shows the help file

All sent commands in the log will be prefixed by “Tx” which is short for transmit. All received commands in the log will be prefixed by “Rx” which is short for receive.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 59

Intelligent Building Series 14.0

C-Touch Training Manual

DOWNLOADING TO C-TOUCH

There are two types of information that you may want to download to the C-Touch Unit. The more common requirement is to download the user configuration data that you have created. Occasionally, you may wish to download new firmware into the unit to add new features. There are two alternative means of downloading data to the C-Touch unit: Directly via a serial cable. Via C-Bus. You can select which option you wish to use in the Program Options dialogue box. 14. 1

DOWNLOADING VIA THE SERIAL CABLE

To download, first connect your PC to the touch screen via the supplied serial cable. In the Transfer menu, select the Download menu item. The C-Touch software will attempt to connect to the touch screen.

Figure 14.1

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 60

Intelligent Building Series

C-Touch Training Manual

Once connected to the touch screen the download Dialogue Box will appear.

Figure 14.2 Do Not Download Configuration Data

Allows user not to download the project to the touch screen. This is selected when new firmware is being downloaded to the touch screen.

Prepare Current File, But Do Not Download

Compiles the file ready for download, but does not physically download it to the screen.

Download Current File

If you want to download the configuration data for the project that is already open, you just need to click on OK, and the downloading process will start. It may take up to five minutes, depending on the size of your file.

Download Other Configuration File

If you want to download a different file, click the Download Other Configuration File radio button, enter the desired file and click OK.

Download Firmware

Allows user to download new firmware. Select the Download Firmware check box, enter the desired file (*.mot) and click on OK.

Set C-Touch Time To PC Time

Automatically synchronised the C-Touch clock with the PC clock.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 61

Intelligent Building Series 14.2

C-Touch Training Manual

DOWNLOADING VIA C-BUS

There may be occasions where it is inconvenient to remove the C-Touch unit from the wall and connect to the serial connector. In this case, you may wish to download via C-Bus. There are several limitations to using this approach: It is much slower. Using the serial cable is approximately 20 times faster. You cannot download across C-Bus bridges. You can only download new configuration data, not firmware. The process to download via C-Bus is as follows: In the Project Details dialogue box, enter the Unit Address of the C-Touch unit. Connect your PC to a PC Interface on the same network as the C-Touch unit. Connect to C-Bus by selecting the Connect to C-Bus menu item from the Options Menu. In the Transfer menu, select the Download menu item, and the download Dialogue Box will appear (as shown previously). If you want to download the configuration data for the project that is already open, you just need to click on OK, and the downloading process will start. It may take up to an hour or two, depending on the size of your file and the amount of C-Bus traffic. If you want to download a different file, click the Download Other Configuration File radio button, enter the desired file and click OK. Note: - The 5000CTA units have a limit of 100 reprogramming cycles. If this limit is exceeded, re-programming may no longer be possible.

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 62

Intelligent Building Series

C-Touch Training Manual

Further Information For further information about C-Bus, please read the documentation that comes with each C-Bus Device. Further assistance can be obtained as follows:C-Bus Manuals • The 5000M/2 C-Bus Technical Manual provides a comprehensive and definitive guide to Clipsal C-Bus. Includes hardware and software specifications, product datasheets, system design and installation guides, and software overview with fully worked programming examples. C-Bus Installation Software • The 5000S/2 C-Bus Installation Software (includes 5000M/2 C-Bus Technical Manual)may be used to unlock the power and flexibility of Clipsal C-Bus. Unit operation may be completely customised to suit user requirements. Advanced control functions may be programmed. C-Bus Installer Training Courses • Contact your nearest Clipsal Integrated Systems Sales or Technical Support Officer and enquire about Clipsal C-Bus Installer Training and Certification programs today!! Technical Support and Trouble Shooting • For further assistance, please consult your nearest Clipsal Integrated Systems Sales Representative or Technical Support Officer. Technical Support Hotline Technical Support E-Mail Sales Support E-Mail Clipsal Integrated Systems Website

1 300 722 247 (Cost 25¢ per call, Australia Only) [email protected] [email protected] www.clipsal.com/cis

Products of Clipsal Integrated Systems Pty Ltd ABN 15 089 444 931 Head Office 12 Park Terrace, Bowden South Australia 5007 International Phone +61 8 8269 0560 International Fax +61 8 8346 0845 Internet www.clipsal.com/cis E-Mail [email protected]

Copyright 2002

Clipsal Integrated Systems Pty Ltd

Page 63