Air cooled liquid chillers and heat pumps with scroll compressors fon indoor installation from 37 to 325 kW
DHigh energy efficiency at partial loads
DIntegrated pump kit
DHigh performance centrifugal fans
The NECS-C units NECS-C is the new range of chillers and heat pumps with scroll compressors and R-410A refrigerant. Available in two versions both with two compressors in one circuit and four compressors in two circuits, the key drivers of NECS-C are maximum energy efficiency and minimum noise emissions.
R-410A, why? Although R-410A is a blend, it behaves just like a pure gas and features a negligible temperature glide. Thanks to its outstanding heat conductivity, R-410A contributes towards achieving elevated system efficiency. R-410A is also an ecological gas because its elevated efficiency reduces electricity consumption and consequently CO2 emissions and because it does not damage the ozone layer (ODP = 0). The scroll compressor has been redesigned for use with the new gas and is now even more compact and silent than before.
Complete versatility NECS-C and NECS-CN units are designed to fully satisfy any application need thanks to a complete range of models, versions and configurations. NECS-C is available in partial (D) and total (R) recovery and in B (base) HT (high temperature / high efficiency). Moreover, a low temperature accessory that permits heating down to -10°C outdoor temperature is available.
High efficiency at part loads NECS-C units have been designed with the goal of guaranteeing high efficiency at part load. The result achieved in the single-circuit dual-compressor is an ESEER > 4.1, equivalent to a 38% saving in seasonal energy consumption compared to the previous R-407C version.
Advantages The technological choices aimed to provide the maximum overall quality and the use of the most innovative technologies make NECS-C a unit able to ensure maximum energy efficiency, easy installation thanks to its compact size, versatility and settings for integration in the Idrorelax centralized hydronic system.
Heat pumps with SMART DEFROST All NECS-C units are available as NECS-CN heat pump model. Innovating the control of traditional heat pump units, NECS-C and NECS-CN feature the innovative SMART DEFROST function: a defrost control logic that reduces both unit downtime and defrost energy consumption.
High performance centrifugal fans The NECS-C units are equipped with dual suction fans, statically and dynamically balanced and coupled by belts and pulleys adjustable to their relevant three-phase motors assembled on turnbuckle runners. Working static head up to 180Pa is available, upon request, at nominal capacity.
Integrated pump unit NECS-C was designed to minimize installation work. The integrated pump unit is an option that incorporates all the hydraulic components, thus optimizing installation space, time and costs. The choice of either a single or dual high or low head pump makes NECS-C units plug & play.
Technological choices Consistent with corporate culture, the NECS-C series has been designed to offer extremely high quality products with cutting-edge technology focusing on maximum energy efficiency, versatility and flexibility.
The new NECS-C units can be equipped with the hydronic kit that incorporates the main hydraulic components thus optimizing hydraulic and electrical installation space, time and costs. The innovative QuickMind regulation featured on NECS-C units was designed to operate in low water content systems thus providing highly professional alternatives to the installation of units with accumulation groups.
Pump and buffer tank configuration (NECS-C 2 compressors)
The hydronic kit can be requested with the following configurations for all versions: 2-pole single low static head single pump hydronic kit 2-pole single high static head single pump hydronic kit 2-pole dual low static head pump hydronic kit 2-pole dual high static head pump hydronic kit 2-pole low static head pump Monobloc centrifugal horizontal electrical pump with axial suction and radial exhaust, fit for continual service.
2 Pumps configuration (NECS-C 4 compressors)
2-pole high static head pump Available for all versions. Second pump Stand-by low or high static pump with programmed hourly rotation; automatic start in the event of working pump fault.
Horizontal or vertical air supply The design for the 4 compressor unit includes the possibility of selecting the unit with air supply best suited to specific installation needs (vertical / horizontal), thus reducing time and costs. The horizontal air supply kit is available for 2 compressor versions. The horizontal supply solution is especially efficient in installations that do not permit traditional vertical supply.
Precision and reliability NECS-C units have been designed to ensure the highest efficiency and reliability in all the working conditions. All the components have been carefully selected and the algorithms have been specifically developed for these units.
Advanced control system The W3000 Compact control with LCD display is available for all the units (optional for some models). The controller features an easy-to-use interface with seven selectable languages: Italian, English, French, German, Spanish, Swedish and Russian. This ensures to have a dedicated version for each country or a general and independent English version for all the countries.
Remote keypad The controller is available with remote keypad that can be connected to the unit at a distance of 200m thanks to the remote connection without power supply (in this case it is supplied by the unit) or up to 500m with local dedicated power supply.
Compatibility with BMS systems The compatibility with BMW systems thanks to the protocols BACnet, OverIP, ModBUS and LonWorks. The Black Box saves up to 200 alarm events that can be easily printed.
Internal Clock The Internal Clock manages a weekly schedule organized into time bands in order to optimise unit performance by minimising power consumption during periods of inactivity, such as during the night. Up to 10 daily time bands can be associated with different operating set points. Energy production is therefore optimized during daily peaks, reducing the consumption when the unit is off. If there isn’t request of hot and cold water, it is possible to manage the switching off of the unit, planning the following operation.
Technical data The NECS-C series includes a wide range of models and versions to fully meet any application need always ensuring the highest reliability, and design flexibility. NECS-C / B Power supply V/ph/Hz PERFORMANCE COOLING ONLY (GROSS VALUE) Cooling capacity (1) kW Total power input (1) kW EER (1) ESEER (1) COOLING ONLY (EN14511 VALUE) Cooling capacity (1)(2) kW EER (1)(2) ESEER (1)(2) Cooling energy class COMPRESSORS Compressors nr. N No. Circuits N FANS Air flow m3/s Available static pressure Pa NOISE LEVEL Noise Power (4) dB(A) SIZE AND WEIGHT A (5) mm B (5) mm H (5) mm Operating weight (5) kg
NECS-C / HT Power supply V/ph/Hz PERFORMANCE COOLING ONLY (GROSS VALUE) Cooling capacity (1) kW Total power input (1) kW EER (1) ESEER (1) COOLING ONLY (EN14511 VALUE) Cooling capacity (1)(2) kW EER (1)(2) ESEER (1)(2) Cooling energy class COMPRESSORS Compressors nr. N No. Circuits N FANS Air flow m3/s Available static pressure Pa NOISE LEVEL Noise Power (4) dB(A) SIZE AND WEIGHT A (5) mm B (5) mm H (5) mm Operating weight (5) kg
0152
0182
0202
0252
0302
0352
0412
0452
0512 0552
0612
0604
0704
0804
0904
1004
1104
1204
400/3/50
37,1 15,7 2,36 4,70
43,0 18,3 2,35 4,30
50,5 20,6 2,45 4,46
57,0 23,2 2,46 4,35
74,8 30,4 2,46 4,18
86,4 36,8 2,35 3,86
97,9 40,7 2,41 3,88
109 46,8 2,32 3,73
121 51,5 2,35 3,74
138 58,3 2,36 4,17
159 67,2 2,36 3,94
152 62,5 2,43 3,70
172 73,1 2,35 3,58
195 83,5 2,33 3,53
222 89,6 2,47 3,90
244 102 2,40 3,77
281 115 2,45 3,84
312 133 2,34 3,63
36,8 2,60 4,39 B
42,6 2,56 3,96 B
50,1 2,64 4,20 B
56,6 2,62 4,12 B
74,3 2,59 3,97 B
86,0 2,56 3,74 B
97,4 2,59 3,71 B
108 2,49 3,63 C
120 2,49 3,61 C
137 2,48 3,80 C
158 2,54 3,61 B
151 2,61 3,68 B
171 2,51 3,56 B
194 2,52 3,47 B
221 2,64 3,80 B
243 2,55 3,62 B
280 2,58 3,73 B
311 2,49 3,60 C
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
4 2
4 2
4 2
4 2
4 2
4 2
4 2
4,44 120
5,00 120
5,00 120
5,00 120
5,56 120
8,89 120
8,89 120
9,44 120
9,44 120
9,44 120
14,2 120
13,3 120
14,2 120
18,9 120
17,8 120
18,9 120
18,9 120
23,6 120
85
88
88
88
90
95
95
96
96
96
98
97
98
99
98
99
99
100
2200 920 1642 670
2200 920 1642 670
2200 920 1642 700
2200 920 1642 720
2200 920 1642 880
2602 1104 1927 1120
2602 1104 1927 1170
2602 1104 1927 1210
2602 1104 1927 1260
3602 1104 1927 1450
3602 1104 1927 1550
3602 1277 1900 1845
3602 1277 1900 1940
4602 1277 2235 2310
4602 1277 2235 2445
4602 1277 2235 2515
4602 1277 2235 2695
5602 1277 2235 2885
0152
0182
0202
0252
0302
0352
0412
0452
0512 0552
0612
0604
0704
0804
0904
1004
1104
1204
400/3/50
39,0 14,9 2,62 4,83
45,5 17,4 2,61 4,48
52,7 20,0 2,64 4,51
59,4 22,4 2,65 4,42
80,0 30,6 2,61 3,93
91,5 34,6 2,64 4,01
103 39,8 2,58 3,81
114 44,1 2,58 4,03
130 50,8 2,56 3,78
148 57,8 2,55 3,97
165 64,6 2,56 3,94
158 61,2 2,58 3,54
183 69,0 2,65 3,94
203 79,9 2,54 3,67
228 89,1 2,55 3,77
257 99,3 2,59 3,71
296 112 2,64 3,84
325 128 2,53 3,75
38,7 2,89 4,50 A
45,1 2,87 4,11 A
52,3 2,86 4,24 A
59,0 2,85 4,18 A
79,4 2,87 3,71 A
91,0 2,89 3,84 A
102 2,79 3,67 A
113 2,77 3,84 A
129 2,82 3,63 A
147 2,77 3,68 A
164 2,75 3,70 A
157 2,80 3,54 A
182 2,89 3,78 A
202 2,75 3,58 A
227 2,74 3,65 A
256 2,81 3,62 A
294 2,83 3,70 A
323 2,69 3,67 B
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
4 2
4 2
4 2
4 2
4 2
4 2
4 2
4,44 120
5,28 120
5,28 120
5,28 120
8,89 120
8,89 120
9,44 120
9,44 120
14,2 120
14,2 120
14,2 120
14,2 120
17,8 120
18,9 120
18,9 120
23,6 120
23,6 120
23,6 120
85
89
89
89
95
95
96
96
98
98
98
98
98
99
99
100
100
100
2200 920 1642 690
2200 920 1642 710
2200 920 1642 730
2200 920 1642 760
2602 1104 1927 1090
2602 1104 1927 1120
2602 1104 1927 1230
3602 1104 1927 1400
3602 1104 1927 1490
3602 1104 1927 1560
3602 1104 1927 1630
3602 1277 1900 1920
4602 1277 2235 2320
4602 1277 2235 2380
4602 1277 2235 2580
5602 1277 2235 2845
5602 1277 2235 3055
5602 1277 2235 3115
NECS-CN / B Power supply V/ph/Hz PERFORMANCE COOLING ONLY (GROSS VALUE) Cooling capacity (1) Total power input (1) EER (1) ESEER (1) COOLING ONLY (EN14511 VALUE) Cooling capacity (1)(2) kW EER (1)(2) ESEER (1)(2) Cooling energy class HEATING ONLY (GROSS VALUE) Total heating capacity (3) kW Total power input (3) kW COP (3) HEATING ONLY (EN14511 VALUE) Total heating capacity (3)(2) kW COP (3)(2) Cooling energy class COMPRESSORS Compressors nr. N No. Circuits N FANS Air flow m3/s Available static pressure Pa NOISE LEVEL Noise Power (4) dB(A) SIZE AND WEIGHT A (5) mm B (5) mm H (5) mm Operating weight (5) kg
0152
0182
0202
0252
0302
0352
0412
0452
0512 0552
0612
0604
0704
0804
0904
1004
1104
1204
400/3/50
36,4 14,9 2,44 4,65
42,3 17,1 2,47 4,48
49,0 19,7 2,49 4,48
55,3 22,4 2,47 4,36
73,0 31,2 2,34 3,85
84,1 35,0 2,40 3,95
94,9 39,0 2,43 3,92
107 43,8 2,45 3,98
119 49,5 2,41 3,74
137 57,9 2,36 3,81
154 64,4 2,39 3,76
146 60,3 2,42 3,74
164 71,6 2,29 3,58
187 79,0 2,37 3,80
213 87,2 2,44 3,93
237 99,8 2,37 3,55
274 113 2,43 3,61
303 131 2,32 3,52
36,1 2,68 4,44 B
42,0 2,70 4,17 A
48,7 2,68 4,29 B
54,9 2,63 4,07 B
72,5 2,55 3,66 B
83,7 2,61 3,79 B
94,4 2,61 3,75 B
107 2,62 3,81 B
119 2,57 3,62 B
136 2,56 3,65 B
154 2,57 3,61 B
146 2,60 3,75 B
163 2,43 3,55 C
186 2,55 3,71 B
212 2,60 3,83 B
236 2,53 3,49 B
273 2,60 3,57 B
302 2,47 3,47 C
42,4 14,8 2,86
48,0 16,8 2,86
56,1 19,4 2,89
63,7 22,1 2,88
81,6 29,8 2,74
94,6 33,7 2,81
107 37,6 2,84
122 42,2 2,90
135 47,4 2,85
153 55,3 2,76
173 61,8 2,80
165 57,8 2,85
185 66,3 2,78
208 74,4 2,79
235 82,6 2,84
261 94,3 2,77
302 108 2,80
336 122 2,74
42,8 3,17 A
48,5 3,15 A
56,6 3,15 A
64,2 3,10 A
82,3 3,03 A
95,1 3,08 A
107 3,08 A
123 3,13 A
136 3,07 A
154 3,02 A
174 3,03 A
166 3,09 A
185 3,00 A
209 3,03 A
236 3,06 A
262 2,98 B
304 3,03 A
337 2,94 B
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
2 1
4 2
4 2
4 2
4 2
4 2
4 2
4 2
4,17 120
4,72 120
4,72 120
4,72 120
8,33 120
8,33 120
8,33 120
8,89 120
9,72 120
13,3 120
13,3 120
12,5 120
13,3 120
16,7 120
16,7 120
18,9 120
22,2 120
23,6 120
84
86
86
86
93
93
93
95
97
97
97
95
97
97
97
99
99
100
2200 920 1642 720
2200 920 1642 730
2200 920 1642 750
2200 920 1642 790
2602 1104 1927 1080
2602 1104 1927 1170
2602 1104 1927 1230
3602 1104 1927 1470
3602 1104 1927 1490
3602 1104 1927 1600
3602 1104 1927 1660
3602 1277 1900 1980
3602 1277 1900 2055
4602 1277 2235 2475
4602 1277 2235 2630
4602 1277 2235 2725
5602 1277 2235 3145
5602 1277 2235 3205
Notes: 1) Plant (side) cooling exchanger water (in/out) 12°C/7°C; Source (side) heat exchanger air (in) 35°C 2) Values in compliance with EN14511-3:2011 3) Plant (side) heat exchanger water (in/out) 40°C/45°C; Source (side) heat exchanger air (in) 7°C - 87% R.H. 4) Total sound power of fans, as declared by the maker, at the rated speed of rotation and a useful static head of 120 Pa on the delivery side. 5) Unit in standard configuration/execution, without optional accessories. The units highlighted in this publication contain HFC R410A [GWP100 2088] fluorinated greenhouse gases.
Versions
Configurations
NECS-C/B, NECS-CN/B Standard unit version
NECS-C, NECS-CN
NECS-C/HT (High Temperature or High Efficiency)
NECS-CD, NECS-CND
Version suited for operations in high air temperature climates. This version includes the use of an increased condensation section to guarantee operations even in severe weather conditions.
cooling only or heat pump unit complete with partial heat recovery section
cooling only or heat pump standard unit H
NECS-CR Thus, the benefit of increased cooling power is obtained at nominal air temperature with a reduction in absorbed power and therefore improved cooling efficiency (EER).
cooling only unit complete with full heat recovery section (model available for 4-compressor units only)
A B
NECS-C / NECS-CN_ENG_01-2017