Use of PCM Enhanced Insulation in the Building Envelope
Use of PCM Enhanced Insulation in
the Building Envelope David W. Yarbrough, PhD, PE Jan Kosny, PhD William A. Miller, PhD, PE Building Technology Ce...
the Building Envelope David W. Yarbrough, PhD, PE Jan Kosny, PhD William A. Miller, PhD, PE Building Technology Center
Oak Ridge National Laboratory
Oak Ridge, Tennessee, USA
Limitations
• Standard method to reduce heat flow is to add R-value. • Limits have been reached. • Adding more R-Value is not practical when space is limited.
Basic Concepts A thin layer of Phase Change Material (PCM)
that maintains a constant temperature is used
to control the ∆T across a layer of insulation.
The PCM stores and releases heat as the surrounding temperatures change.
PCM CAN BE CONFIGURED TWO WAYS
PCMs can be localized or distributed in an insulation or some other building material. Exterior temperatures must cycle across the phase change temperature for the PCM to be useful. Materials for use in a building envelope are selected with a phase change material near the occupied space temperature. PCMs include organic materials that melt in the temperature range 60 to 90 °F. Inorganic salt solutions exhibiting large heats of solution or dilution can also be used.
Without PCM Layer Thermocouples Typ.
Attic
R 24
+ + + + + +
Ceiling
120.0 F 112.3 F 106.6 F 100.0 F 93.30 F 86.60 F 80.00 F
Temperature distribution is linear. Heat flow into ceiling is 1.666 BTU/ ft2·h under these conditions.
With PCM Layer PCM layer Attic
Thermocouples
120.0 F 100.5 F 81.00 F 80.75 F 80.50 F 80.25 F 80.00 F
R8 R16
Ceiling
PCM layer is 0.125 inch thick and maintains 81 °F throughout the diurnal cycle. Heat flow into ceiling is 0.0625 BTU/ft 2 · h. (1.666 without PCM)
Low Space Requirements
• A 0.125 in. thick layer of PCM (0.5 lb) with thermal resistance on both sides will last a complete diurnal cycle.
Test Box 1/8 inch PCM Layer
Diurnal Cycle T3 T2
R=6 foam board
T1
Room Temp
R=16 foam board
One Cycle Demonstration
No PCM Heating 2.29
No PCM
13.30
115
110
105
100
95
90
85
80
75
70
PCM Heating 0.15
PCM Cooling
Heating Saved 93%
4.36
Cooling Reduction 67.2%
0.25 lb of Octadecane per sq. ft.
Heating Cooling
63.64%
65.04%
2.63 5.37
Temperature (F)
110 90 70 50
1
49
97
145
193
One 24 Hour Cycle
241
289
337
Peak Load is Shifted
Temperature (F)
Normal Peak
120 100 4 hrs.
80 PCM Peak
60 1
49
97
145
193
241
Time (10 min. increments)
289
337
Lower Heat Flow into
Building.
• Reduction in heat flow into the conditioned space is demonstrated. • These examples demonstrate the potential
for heating and cooling load reductions.
Observations 1. A thin layer of phase change material can control the T difference across an inner layer of insulation for several hours. 2. The amount of Phase Change Material needed can be minimized by thermally protecting it with a second layer of insulation 3. Optimum amount and position is provided by simulation for a given site and location in the building envelope.
HFM CAN BE OPERATED IN TRANSIENT
MODE TO TEST PCMs
Test specimen is initially isothermal at a temperature below the phase change temperature. One plate is ramped quickly to a temperature above the phase change temperature. The heat fluxes in and out of the test specimen are monitored with time. A comparison of heat flux data for specimens with and without PCM is used to evaluate performance.
Test Configuration • • • • • •
Top Plate – cold Top layer of insulation R = 9 ft2·h·°F/Btu
Layer of PCM Bottom layer of insulation R=5 ft2·h·°F/Btu
Bottom Plate – cold ramps to hot hot ramps to cold
TEMPERATURES ABOVE AND BELOW THE PHASE CHANGE
TEMPERATURE ARE UTILIZED
Test specimen is initially isothermal. bottom plate 69.8 °F top plate 70 °F Bottom plate temperature changed rapidly to a temperature above the phase change temperature. bottom plate 69.8 °F to 120.2 °F Result is a positive flux (into specimen) on the hot side and negative flux (out of specimen) on the cold side. (charging) Bottom plate temperature is returned to initial temperature when steady state is achieved. (discharging) This procedure can be carried out for specimens with and without PCM.
Hot-Side Flux During the Charge and Discharge Portions of the Cycle Cellulose with 0% PCM
Flux (Btu/ft^2.h)
20 10 hot side/flux in/out
0
cold side/flux out
-10 -20 0
50 100 150 200 250 300 350 Time (minutes)
Hot-Side Flux During the Charge and Discharge Portions of the Cycle for Cellulose with 30 wt% PCM
Comparison of the “Charging” of Cellulose Insulation Materials with and without PCM
Comparison of the Flux out of the Cellulose Insulation Materials with and without PCM
Total Heat into Cold Plate as a Function of PCM Content
Heat Flux Data for Inorganic PCM Heat Flow into Conditioned Space 4
F lu x
3
No PCM Chloride 1
2
Chloride 2
1 0 0
100
200 Time (minutes)
300
400
A COMPARISON OF FLUX DATA FOR SPECIMENS WITH AND WITHOUT PCM ALLOWS AN EVALUATION OF PERFORMANCE Heat Flow into Conditioned Space 4
Flux
3 No PCM
2
PCM
1 0 0
100
200 Time (minutes)
300
400
HFM CAN BE USED TO MONITOR HEAT FLUX FOR INSULATION WITHOUT PCM
Transient Heat Flow Meter Test flux into spe cime n is positiv e 10
Heat Flux
5 Hot Side
0
Cold Side
-5
-10 0
36
72
108 144 180 216
Time (minute s)
Total Heat Discharged to Hot Plate as a Function of PCM Content
Wall Containing Cellulose-PCM Blend have been Tested in a Hot-Box (C 1363)
PCM–Enhanced Cellulose Insulation has been Tested in Field Conditions In Two Full-Scale Demonstration Projects 2x6 Wood-Framed Walls were Used
North-Western Wall
South - Facing Wall
In Both Experiments, Walls Containing ~ 20% PCM were Instated Next to the Walls without PCM
Charging and Discharging PCM 90.0
Discharging time about 6 hours
Temp. inside the wall F
PCM is absorbing heat and melting
PCM is releasing heat and solidifying
80.0
Temperatures inside the wall cavity: Thick line – PCM Thin line – No PCM
Charging time about 6 hours 70.0 1
13
25
37
49
61
73
85
Cellulose W all East No PCM (oF) CELL_E_TC5
97
109
121
133
145
157
169
181
Cellulose W all W est W / PCM (oF) CELL_W _TC5
193
Significant Difference in Energy
Performance was Observed
Example of Heat Flux Measurements 2
Heating Load
•
1.5 1
0.5
•
Btu/hft2
0 1
49
97
145
193
241
289
337
385
433
481
529
577
625
673
-0.5
PCM wall -1
•
-1.5 -2
No PCM wall -2.5 -3
Cooling Load
time [h/4]
One week of data Sunny days Cool nights
•
PCM wall is significantly more thermally stable than the other wall Peak-hour heat flux reduction by at least 1/3 in PCM wall Significantly lower heat flux amplitude in PCM wall ~2 hours shifting of the peak-hour load by PCM wall
Potential 40% Cooling Load Savings for 40 oF Temperature Excitation 2006 ORNL Dynamic Hot-box testing of 2x6 Wall with PCM-Enhanced Cellulose Insulation (22% PCM) Cluster of PCM pellets
Reduction [%]
Cellulose fiber
Surface Load
0.5 0.4
42.00% 27.00%
0.3
19.00%
0.2 0.1 0 First 5 hours
First 10 hours
All 15 hours
Long-Term Energy Performance Monitoring
Spring, Summer, Fall, Winter 2006
and Spring 2007
130
Example of Results from ORNL 2006 Measurements 120 Exterior
surfaces
Temperatures [F]
110
100 Interior
surfaces
90
80
70
One week data Sunny days Cool nights
60 Exterior air
50
1
49
97
145
193
241
289
337
Cellulose Wall East No PCM (oF) CELL_E_TC1 Cellulose Wall West W/ PCM (oF) CELL_W_TC1 ESRA OUTSIDE T/C (oF) AMB_AIR
385
433
481
529
577
Cellulose Wall East No PCM (oF) CELL_E_TC8 Cellulose Wall West W/ PCM (oF) CELL_W_TC8
625
673
PCM-Enhanced Cellulose in Test Walls
100.0
•
Temp. inside the wall F
90.0
85 oF
•
PC action
78 oF
80.0
•
• Temperatures inside the wall cavities: Thick lines – PCM Thin lines – No PCM
70.0
PCM stabilizes the core of the wall by its heat storage capacity Warming and cooling down of the core in the PCM wall is significantly slower Peak-hour temperature excitation is shifted in PCM wall Significantly lower temperature amplitudes can be observed in PCM wall cavities
60.0 1
13
25
37
49
61
73
85
97
Cellulose Wall East No PCM (oF) CELL_E_TC3 Cellulose Wall East No PCM (oF) CELL_E_TC5 Cellulose Wall West W/ PCM (oF) CELL_W_TC4
109
121
133
145
157
169
181
193
Cellulose Wall East No PCM (oF) CELL_E_TC4 Cellulose Wall West W/ PCM (oF) CELL_W_TC3 Cellulose Wall West W/ PCM (oF) CELL_W_TC5
% Cooling Load Reductions 100
90
Cooling-dominated loads
80
70
60
50
Average ~42% 40
30
20
April
May
June
July
August
Sept.
Oct.
Nov.
Dec.
Jan.
10
0 0
5
10
15
20 Weeks
25
30
35
40
Summary
• Several applications of microencapsulated organic PCMs were tested. • Applications with localized PCM have been tested. • Laboratory and field work demonstrated good
performance of PCM-enhanced insulation
– Thermal conductivity of the PCM-enhanced cellulose was not increased by the addition of PCM microcapsules – Cellulose wall with dispersed PCM demonstrated potential for over 40% reduction of the peak thermal load during 5 hour thermal ramp
• Field tests confirmed hot-box test data on cooling load reduction potential of PCM-enhanced cellulose • Field tests demonstrated potential for application of PCMs in mixed and heating-dominated climates for reduction of heating loads