SECTION C DOMESTIC WATER PIPING SPECIALTIES

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park NB Coronado, CA SECTION C-2 22 1145 - DOMESTIC WATER PIPING SPECIALTIES PART 1 1.1 GENER...
Author: Lauren McGee
0 downloads 0 Views 115KB Size
NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

NB Coronado, CA

SECTION C-2 22 1145 - DOMESTIC WATER PIPING SPECIALTIES PART 1 1.1

GENERAL

DESCRIPTION A.

Provide all labor, materials, and equipment necessary for the installation of domestic water piping specialties where shown on the Drawings and specified in this Request for Proposal (RFP). This work includes (but is not limited to): 1.

Vacuum breakers

2.

Backflow preventers

3.

Water pressure-reducing valves

4.

Balancing valves

5.

Temperature-actuated water mixing valves

6.

Strainers

7.

Hose bibbs

8.

Wall hydrants

9.

Drain valves

10. Water hammer arresters 11. Trap-seal primer valves B.

1.2

PERFORMANCE REQUIREMENTS A.

1.3

See "Domestic Water Piping Specialties" of Section 22 1145 of “Technical Specifications” of Section C-2 of this RFP for water meters.

Minimum Working Pressure for Domestic Water Piping Specialties: 125 pound force per square inch gauge (psig) unless otherwise indicated.

SUBMITTALS A.

See Part E.2, “Submittals” of “Construction Requirements” of Section C-1 of this RFP.

Section C-2 (22 1145)

Page 181

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

1.4

QUALITY ASSURANCE A.

B.

PART 2 2.1

NB Coronado, CA

Comply with the requirements of “The Public Health and Safety Company” of the National Sanitation Foundation (NSF): 1.

Comply with NSF 14, "Plastics Piping Components and Related Materials" for plastic domestic water piping components.

2.

Comply with NSF 61, "Drinking Water System Components - Health Effects; Sections One through Nine."

See “Contract Quality Control and Quality Assurance” of Section H-26 of this RFP.

PRODUCTS

VACUUM BREAKERS A.

Pipe-Applied, Atmospheric-Type Vacuum Breakers: 1.

Manufacturers: Subject to compliance with requirements, provide Watts 288 Series or equivalent products by one of the following: a. Ames Company b. Conbraco Industries, Incorporated c. FEBCO; SPX Valves & Controls d. Watts Industries, Incorporated; Water Products Division e. Zurn Plumbing Products Group; Wilkins Division

2.

Standard: American Society of Safety Engineers (ASSE) 1001

3.

Size: Nominal pipe size (NPS) 1/4 to NPS Three, as required to match connected piping

4.

Body: Bronze

5.

Inlet and Outlet Connections: Threaded

6.

Finish: Chrome plated

Section C-2 (22 1145)

Page 182

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

B.

NB Coronado, CA

Hose-Connection Vacuum Breakers: 1.

Manufacturers: Subject to compliance with requirements, provide Watts Series 8 or equivalent products by one of the following: a. Arrowhead Brass Products, Incorporated b. Conbraco Industries, Incorporated c. Watts Industries, Incorporated; Water Products Division d. Woodford Manufacturing Company e. Zurn Plumbing Products Group

2.2

2.

Standard: ASSE 1001

3.

Body: Bronze, nonremovable, with manual drain

4.

Outlet Connection: Garden-hose threaded complying with American Society of Mechanical Engineers (ASME) B1.20.7

5.

Finish: Chrome or nickel plated

BACKFLOW PREVENTERS A.

Intermediate Atmospheric-Vent Backflow Preventers: 1.

Manufacturers: Subject to compliance with requirements, provide Watts Series 009D or equivalent products by one of the following: a. Conbraco Industries, Incorporated b. FEBCO; SPX Valves & Controls c. Watts Industries, Incorporated; Water Products Division d. Zurn Plumbing Products Group; Wilkins Division

2.

Standard: ASSE 1012

3.

Operation: Continuous-pressure applications

4.

Body: Bronze

5.

End Connections: Solder joint

Section C-2 (22 1145)

Page 183

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

6. B.

NB Coronado, CA

Finish: Chrome plated

Reduced-Pressure-Principle Backflow Preventers: 1.

Manufacturers: Subject to compliance with requirements, provide Watts Series 009 or equivalent products by one of the following: a. Ames Company b. Conbraco Industries, Incorporated c. FEBCO; SPX Valves & Controls d. Watts Industries, Incorporated; Water Products Division e. Zurn Plumbing Products Group; Wilkins Division

2.

Standard: ASSE 1013

3.

Operation: Continuous-pressure applications

4.

Pressure Loss: 12 psig maximum, through middle 1/3 of flow range

5.

Body: Bronze for NPS Two and smaller; cast iron with interior lining complying with American Water Works Association C550 (AWWA) or that is Food and Drug Administration (FDA) approved for NPS 2-1/2 and larger

6.

End Connections: Threaded for NPS Two and smaller; flanged for NPS 2-1/2 and larger

7.

Configuration: Verify with Drawings of this RFP and available layout space

8.

Accessories: a. Valves: Ball type with threaded ends on inlet and outlet of NPS Two and smaller; outside screw and yoke gate-type with flanged ends on inlet and outlet of NPS 2-1/2 and larger b. Air-Gap Fitting: ASME A112.1.2, matching backflow-preventer connection

2.3

WATER PRESSURE-REDUCING VALVES A.

Water Regulators:

Section C-2 (22 1145)

Page 184

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

1.

NB Coronado, CA

Manufacturers: Subject to compliance with requirements, provide Watts Series 223 or equivalent products by one of the following: a. Conbraco Industries, Incorporated b. Watts Industries, Incorporated; Water Products Division c. Zurn Plumbing Products Group; Wilkins Division

2.4

2.

Standard: ASSE 1003

3.

Pressure Rating: Initial working pressure of 150 psig

4.

Body: Bronze with chrome-plated finish for NPS Two and smaller; cast iron with interior lining complying with AWWA C550 or that is FDA approved for NPS 2-1/2 and NPS Three

5.

End Connections: Threaded for NPS Two and smaller; flanged for NPS 2-1/2 and NPS Three

BALANCING VALVES A.

Memory-Stop Balancing Valves 1.

Manufacturers: Subject to compliance with requirements, provide Apollo 64 Series with balancing stop or equivalent products by one of the following: a. Conbraco Industries, Incorporated b. Crane Company; Hammond Valve c. Milwaukee Valve Company d. NIBCO Incorporated e. Red-White Valve Corporation

2.

Standard: MSS SP-110 for two piece, copper-alloy ball valves

3.

Pressure Rating: 400 psig minimum Center for Watershed Protection (CWP)

4.

Size: NPS Two or smaller

5.

Body: Copper alloy

6.

Port: Standard or full port

Section C-2 (22 1145)

Page 185

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

NB Coronado, CA

7.

Ball: Chrome-plated brass

8.

Seats and Seals: Replaceable

9.

End Connections: Solder joint or threaded

10. Handle: Vinyl-covered steel with memory-setting device 2.5

TEMPERATURE-ACTUATED WATER MIXING VALVES A.

Water-Temperature Limiting Devices: 1.

Manufacturers: Subject to compliance with requirements, provide CashAcme Series 160 or equivalent products by one of the following: a. Conbraco Industries, Incorporated b. Powers; a Watts Industries Company c. Symmons Industries, Incorporated d. Watts Industries, Incorporated.; Water Products Division e. Zurn Plumbing Products Group; Wilkins Division

2.6

2.

Standard: ASSE 1017

3.

Pressure Rating: 125 psig

4.

Type: Thermostatically controlled water mixing valve

5.

Material: Bronze body with corrosion-resistant interior components

6.

Connections: Threaded inlets and outlet

7.

Accessories: Check stops on hot- and cold-water supplies, and adjustable, temperature-control handle

HOSE BIBBS A.

Non Freeze Hose Bibbs: 1.

Manufacturers: Subject to compliance with requirements, provide Woodford Model 24 or equivalent products by one of the following:

Section C-2 (22 1145)

Page 186

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

NB Coronado, CA

a. Josam Company b. MIFAB, Incorporated c. Smith, Jay R. Manufacturing Company.; Division of Smith Industries, Incorporated d. Watts Drainage Products Incorporated e. Woodford Manufacturing Company f. Zurn Plumbing Products Group; Light Commercial Operation g. Champion-Arrowhead 2.

Standard: ASME A112.21.3M

3.

Body Material: Bronze

4.

Seat: Bronze, replaceable

5.

Supply Connections: NPS 3/4 threaded

6.

Outlet Connection: Garden-hose thread complying with ASME B1.20.7

7.

Pressure Rating: 125 psig

8.

Vacuum Breaker: Integral nonremovable, drainable, hose-connection vacuum breaker complying with ASSE 1011

9.

Finish: Chrome or nickel plated

10. Operation: Wheel handle 11. Coordinate equipment and connections for Recreational Vehicle (RV) Sites to facilitate two NPS 3/4 hose bibbs placed in shroud of utility pedestal. 2.7

WALL HYDRANTS A.

Nonfreeze Wall Hydrants: 1.

Manufacturers: Subject to compliance with requirements, provide Woodford Model B65 or equivalent products by one of the following: a. Josam Company

Section C-2 (22 1145)

Page 187

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

NB Coronado, CA

b. MIFAB, Incorporated c. Smith, Jay R. Manufacturing Company; Division of Smith Industries, Incorporated d. Watts Drainage Products Incorporated e. Woodford Manufacturing Company f. Zurn Plumbing Products Group; Light Commercial Operation 2.

Standard: ASME A112.21.3M for concealed exposed-outlet, self-draining wall hydrants

3.

Pressure Rating: 125 psig

4.

Operation: Loose key

5.

Casing and Operating Rod: Of length required to match wall thickness. Include wall clamp

6.

Inlet: NPS 3/4 or NPS One

7.

Outlet: Concealed, with integral vacuum breaker and garden-hose thread complying with ASME B1.20.7

8.

Box: Deep, flush mounting with cover

9.

Box and Cover Finish: Bronze

10. Operating Keys(s): Two with each wall hydrant 2.8

WATER HAMMER ARRESTERS A.

Water Hammer Arresters: 1.

Manufacturers: Subject to compliance with requirements, provide Watts Series 15 or equivalent products by one of the following: a. AMTROL, Incorporated b. Josam Company c. MIFAB, Incorporated d. PPP Incorporated

Section C-2 (22 1145)

Page 188

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

NB Coronado, CA

e. Smith, Jay R. Manufacturing Company; Division of Smith Industries, Incorporated f. Watts Drainage Products Incorporated g. Zurn Plumbing Products Group; Specification Drainage Operation

2.9

2.

Standard: ASSE 1010 or Plumbing and Drainage Institute - Water Hammer (PDI-WH) 201

3.

Type: Brass Piston

4.

Size: ASSE 1010, Sizes AA and A through F or PDI-WH 201, Sizes A through F

TRAP-SEAL PRIMER VALVES A.

Supply-Type, Trap-Seal Primer Valves: 1.

Manufacturers: Subject to compliance with requirements, provide Watts Series A200 or equivalent products by one of the following: a. MIFAB, Incorporated b. PPP Incorporated c. Sioux Chief Manufacturing Company, Incorporated d. Smith, Jay R. Manufacturing Company; Division of Smith Industries, Incorporated e. Watts Industries, Incorporated.; Water Products Division

2.

Standard: ASSE 1018

3.

Pressure Rating: 125 psig minimum

4.

Body: Bronze

5.

Inlet and Outlet Connections: NPS 1/2 threaded, union, or solder joint

6.

Gravity Drain Outlet Connection: NPS 1/2 threaded or solder joint

7.

Finish: Chrome plated, or rough bronze for units used with pipe or tube that is not chrome finished

Section C-2 (22 1145)

Page 189

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

PART 3 3.1

NB Coronado, CA

EXECUTION

INSTALLATION A.

Refer to "Common Work Results for Plumbing” of Section 22 0523 of “Technical Specifications” of Section C-2 of this RFP for piping joining materials, joint construction, and basic installation requirements.

B.

Install backflow preventers in each water supply to mechanical equipment and systems at each RV Site and to other equipment and water systems that may be sources of contamination. Comply with Base Public Works Department (PWD). 1.

Locate backflow preventers in same room as connected equipment or system.

2.

Install drain for backflow preventers with atmospheric-vent drain connection with air-gap fitting, fixed air-gap fitting, or equivalent positive pipe separation of at least two pipe diameters in drain piping and pipe to floor drain. Locate air-gap device attached to or under backflow preventer. Simple air breaks are not acceptable for this application.

3.

Do not install bypass piping around backflow preventers.

4.

Piping in finished areas to be concealed to the greatest extent possible.

C.

Where static water pressure exceeds 80 psig, install water regulators with inlet and outlet shutoff valves.

D.

Install balancing valves in locations where they can easily be adjusted. Provide tags for easy location. 1.

Install temperature-actuated water mixing valves with check stops or shutoff valves on inlets.

E.

Install Y-pattern strainers for water on supply side of each control valve, water pressure-reducing valve, and pump.

F.

Install water hammer arresters in water piping per Plumbing and Drainage Institute Water Hammer 201 (PDI-WH 201).

G.

Install supply-type, trap-seal primer valves with outlet piping pitched down toward drain trap a minimum of one percent, and connect to floor-drain body, trap, or inlet fitting. Adjust valve for proper flow.

Section C-2 (22 1145)

Page 190

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

H.

3.2

3.3

NB Coronado, CA

The Drawings of this RFP indicate the general arrangement of piping and specialties. Some field change may be required. Secure written approval from Contracting Officer’s Representative (COR) of proposed modification solution.

ADJUSTING (WHEN APPLICABLE) A.

Set field-adjustable pressure set points of water pressure-reducing valves to pressure setpoint shown on Drawings of this RFP.

B.

Set field-adjustable flow of balancing valves to gallons per minute (gpm) shown on Drawings of this RFP.

C.

Set field-adjustable temperature set points of temperature-actuated water mixing valves to temperature setpoint shown on the Drawings of this RFP.

FIELD QUALITY CONTROL A.

Perform tests and inspections required by the Base PWD and the State of California.

B.

Specialties Inspections: 1.

Do not enclose, cover, or put piping or specialties into operation until it has been inspected and approved by Base PWD.

2.

During installation, notify Base PWD at least 15 days before desired date for inspection. Perform tests specified below in presence of Base PWD: a. Roughing-in Inspection: Arrange for inspection of specialties before concealing or closing-in after roughing-in and before setting fixtures. b. Final Inspection: Arrange final inspection for Base PWD to observe tests specified below and to ensure compliance with requirements.

3.

Reinspection: If Base PWD find that specialties will not pass tests or inspections, the Contractor shall make required corrections and arrange for reinspection.

4.

Reports: Prepare inspection reports and distribute as required by Base PWD and the NAFI.

Section C-2 (22 1145)

Page 191

NAVMWR-12-R-0010 Upgrade and Expand Fiddler’s Cove RV Park

C.

NB Coronado, CA

Piping Tests: To be performed per the requirements of the Base PWD. 1.

Fill domestic water specialties. Check components to determine specialties are functioning as required.

2.

Test for leaks and defects in specializes and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit a separate report for each test, complete with diagram of specialty tested.

3.

Leave new specialty uncovered and unconcealed until it has been tested and approved. Expose work that was covered or concealed before it was tested.

4.

Prepare reports for tests as required by Base PWD and for corrective action required and provide copies to COR.

D.

Specialties will be considered defective if equipment/devices do not pass tests and inspections.

E.

All work shall be constructed in accordance with the requirements of this RFP. All work is subject to inspection and/or correction if deemed appropriate, which is described in “Inspection and Acceptance” of Section E of this RFP.

END OF SECTION 22 1145