GENERAL PIPING NOTES 1.

MINIMUM SIZE OF STEAM CONDENSATE RETURN PIPING SHALL BE 1" UNLESS OTHERWISE NOTED.

THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) CONTRACTOR SHALL VISIT THE SITE TO DETERMINE ALL PRE-EXISTING CONDITIONS AND WORK NECESSARY PRIOR TO SUBMISSION OF BID PRICE.

2.

PROVIDE ISOLATION VALVES IN SUPPLY AND RETURN PIPING ON EACH FLOOR, AND IN BRANCH PIPING SERVING MORE THAN ONE PIECE OF EQUIPMENT.

THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) CONTRACTOR SHALL BE FAMILIAR WITH ALL CONTRACT DOCUMENTS FOR ALL TRADES AND COORDINATE WITH OTHER CONTRACTORS.

3.

DRAWINGS ARE DIAGRAMMATIC ONLY: FINAL ROUTING OF DUCTWORK, PIPING AND EQUIPMENT LOCATIONS SHALL BE DETERMINED IN THE FIELD. ADDITIONAL OFFSETS, ELBOWS, ETC., SHALL BE PROVIDED AND INSTALLED WITHOUT ADDITIONAL COST TO THE OWNER.

1.

ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF SMACNA STANDARDS.

1.

MINIMUM SIZE OF HOT WATER SUPPLY, HOT WATER RETURN AND CONDENSATE DRAIN PIPING SHALL BE 3/4" UNLESS OTHERWISE NOTED.

2.

PROVIDE VOLUME DAMPERS AT ALL LOW PRESSURE SUPPLY, RETURN AND EXHAUST DUCTWORK BRANCH TAKE-OFFS.

2.

SUPPLY AND RETURN DUCT MAINS FROM AIR HANDLING EQUIPMENT SHALL BE INTERNALLY LINED WITH 1" ACCOUSTICAL LINING A MINIMUM OF 10'-0" FROM THE UNIT UNLESS OTHERWISE NOTED. ALL DUCTWORK DIMENSIONS INDICATED ARE CLEAR INSIDE DIMENSIONS. ALL INTERNAL ACCOUSTICAL DUCT LINING SHALL HAVE AIR SURFACE COATED WITH ACRYLIC COATING FORMULATED WITH IMMOBILIZED EPA REGISTERED ANTI-MICROBIAL AGENT PROVEN TO RESIST MICROBIAL GROWTH AS DETERMINED BY ASTM G21 AND G22.

3.

3.

4. 5.

REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATIONS OF DIFFUSERS, REGISTERS AND GRILLES. FIRE DAMPERS AND ACCESS PANELS SHALL BE INSTALLED AT ALL FIRE RATED ASSEMBLIES AND FLOOR PENETRATIONS. REFER TO ARCHITECTURAL DRAWINGS FOR ASSEMBLY LOCATIONS. WHERE DUCTS PENETRATE WALLS THAT CARRY BOTH FIRE AND SMOKE RATINGS, THE DAMPER SHALL BE COMBINATION FIRE/ SMOKE DAMPERS. COMBINATION FIRE/ SMOKE DAMPERS SHALL BE PROVIDED WITH POWER IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS. THE MECHANICAL SUBCONTRACTOR SHALL COORDINATE COMBINATION FIRE/ SMOKE DAMPER POWER REQUIREMENTS WITH THE ELECTRICAL SUBCONTRACTOR.

6.

PROVIDE FIRE DAMPERS AT ALL TRANSFER DUCTS IN FIRE RATED PARTITIONS.

7.

EACH SUPPLY DIFFUSER/REGISTER RUNOUT SHALL BE PROVIDED WITH A VOLUME DAMPER. REFER TO CEILING DIFFUSER BRANCH TAKE-OFF DETAIL FOR ADDITIONAL INFORMATION.

8.

9.

4.

5.

6.

7.

8.

RUNOUT SIZES TO DIFFUSERS/REGISTERS SHALL MATCH INLET SIZE NOTED IN THE DIFFUSER REGISTER/ GRILLE SCHEDULE OR TAG UNLESS SHOWN OTHERWISE ON THE FLOOR PLANS.

11. ALL FANS SUPPLYING MORE THAN 2,000 CFM OF AIR TO ANY SPACE SHALL BE INSTALLED WITH A SMOKE DETECTOR IN THE RETURN DUCTWORK. DUCT SMOKE DETECTORS SHALL BE INSTALLED IN THE RETURN AIR PATH OF AIR DISTRIBUTION SYSTEMS UTILIZING A COMMON SUPPLY AND/OR RETURN AIR PLENUM WITH A COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM. THE SMOKE DETECTOR SHALL BE WIRED TO STOP THE FAN UPON DETECTION OF SMOKE, AND SIGNAL THE BUILDING FIRE ALARM CONTROL PANEL. THE SMOKE DETECTOR SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, MOUNTED IN THE DUCT BY MECHANICAL CONTRACTOR AND WIRED BY THE ELECTRICAL CONTRACTOR 12. LOCATIONS OF LOUVERS SHOWN ON THE PLANS ARE APPROXIMATE. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION. 13. FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 6'-0" IN LENGTH. FLEXIBLE DUCTWORK SHALL BE INSTALLED AS STRAIGHT AS POSSIBLE AND SHALL BE ROUTED AND SUPPORTED WITHOUT FORMING CRIMPS OR OTHER AIR FLOW RESTRICTIONS. PROVIDE SQUARE TO ROUND ADAPTERS OR BOOTS TO CONNECT TO AIR DEVICES NECK WHEN REQUIRED.

4.

PIPING AT PUMPS AND EQUIPMENT SHALL BE SUPPORTED SO THAT NO PIPING OR ACCESSORY LOAD IS CARRIED BY THE PUMP OR EQUIPMENT. 5.

ALL VOLUME DAMPERS LOCATED ABOVE HARD NON-ACCESSIBLE CEILINGS SHALL BE PROVIDED WITH A YOUNG REGULATOR VOLUME DAMPER FOR REMOTE BALANCING.

10. RUNOUT SIZES TO TERMINAL UNITS SHALL MATCH INLET SIZE UNLESS OTHERWISE NOTED OR SHOWN ON THE FLOOR PLANS.

PROVIDE SHUTOFF VALVES IN THE SUPPLY AND RETURN PIPING TO ALL EQUIPMENT TO ALLOW FOR SERVICING. UNIONS AND FLANGES SHALL BE ARRANGED SUCH THAT EQUIPMENT CAN BE SERVICED WITHOUT CUTTING AND MINIMAL DISRUPTION OF PIPING SERVING THE EQUIPMENT.

9.

ALL PIPING ABOVE GRADE SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR CEILING STRUCTURE. PIPING HUNG FROM JOISTS SHALL BE HUNG FROM THE TOP CHORDS OF THE JOISTS. INSULATE ALL CHILLED WATER PIPING. ALL EXPOSED INSULATED PIPING BELOW 10'-0" AFF SHALL BE JACKETED. ALL EXTERIOR COOLING WATER PIPING SHALL BE INSULATED & JACKETED OVER ELECTRIC HEAT TRACING. REFER TO SPECIFICATIONS FOR INSULATION & JACKETING REQUIREMENTS. WHERE MAXIMUM OPERATING PRESSURE IS GREATER THAN 150 PSIG IN ANY SYSTEM, THE HVAC CONTRACTOR SHALL FURNISH AND INSTALL PRODUCTS, PIPING, VALVES, FITTINGS AND ACCESSORIES WITH PRESSURE CLASSIFICATIONS THAT ARE SUITABLE FOR SERVICE. IN GENERAL, ALL PRODUCTS, PIPING, VALVES, FITTINGS AND ACCESSORIES BELOW 350 FEET OF THE HIGHEST PIPING POINT MUST HAVE PRESSURE RATINGS OF 300 PSI W.O.G. OR GREATER. ALL PRODUCTS, PIPING, VALVES, FITTINGS, AND ACCESSORIES BELOW 575 FEET OF THE HIGHEST PIPING POINT MUST HAVE PRESSURE RATINGS OF 500 PSI W.O.G. OR GREATER. EXPANSION IN PIPING SYSTEMS SHALL BE COMPENSATED FOR BY THE USE OF U-BENDS, Z-BENDS OR EXPANSION JOINTS AS INDICATED. U-BENDS (LOOPS) AND Z-BENDS SHALL BE COMPLETE WITH PIPE GUIDES AND ANCHORS.

10. PROVIDE AUTOMATIC AIR VENT (WITH DRAIN) AT HIGH POINTS OF ALL RECIRCULATING WATER PIPING SYSTEMS. 11. CONDENSATE FROM ALL EVAPORATOR COILS SHALL BE TRAPPED AND ROUTED TO THE NEAREST HUB/FLOOR DRAIN, STORM OR EXTERIOR DRY WELLS. CONDENSATE PIPING SHALL BE INSULATED COPPER IN HVAC PLENUMS, SCHEDULE 40 PVC ACCEPTABLE ELSEWHERE. CONDENSATE SHALL BE PUMPED AS REQUIRED. 12. REFRIGERANT PIPING SHALL BE TYPE L OR REFRIGERATION SERVICE COPPER TUBING WITH BRAZED JOINTS. SUCTION PIPING SHALL BE INSULATED WITH 3/4" MANVILLE AEROTUBE II PIPE INSULATION OVER TUBING WITHOUT CUTTING. ALL JOINTS AND SEAMS SHALL BE SEALED WITH ADHESIVE. 13. REFRIGERANT PIPING CARRYING OTHER THAN GROUP A1 OR B1 REFRIGERANTS AND INTERCONNECTING SEPARATE PIECES OF EQUIPMENT AND PASSING VERTICALLY THROUGH FLOORS FROM ONE STORY TO ANOTHER SHALL BE ENCLOSED IN A CODE APPROVED RIGID AND TIGHT CONTINUOUS FIRE RESISTING PIPE DUCT OR SHAFT HAVING NO OPENINGS INTO FLOORS NOT SERVED BY THE REFRIGERATING SYSTEM, AS REQUIRED BY LOCAL CODE AUTHORITIES. THE PIPE DUCT OR SHAFT SHALL BE VENTED TO OUTDOORS.

HVAC LEGEND

GENERAL HVAC NOTES

6.

THE HVAC CONTRACTOR SHALL COORDINATE ALL ELECTRICAL AND PLUMBING REQUIREMENTS WITH THE ELECTRICAL AND PLUMBING CONTRACTORS. THE AUTOMATIC TEMPERATURE CONTROL (ATC) CONTRACTOR SHALL COORDINATE THERMOSTAT LOCATIONS WITH THE ARCHITECTURAL FURNITURE PLANS. THERMOSTATS SHALL BE INSTALLED 54" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. THE HVAC CONTRACTOR SHALL FURNISH AND INSTALL ALL INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE HVAC WORK COMPLETE AND READY FOR OPERATION.

7.

ALL HVAC WORK SHALL BE IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES.

8.

ALL HVAC EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

9.

FURNISH TO THE GENERAL CONTRACTOR ALL INFORMATION REQUIRED FOR SETTING OF WALL, ROOF AND PARTITION OPENINGS FOR HVAC WORK. THIS INFORMATION SHALL BE FURNISHED IN A TIMELY MANNER SUCH THAT CONSTRUCTION SCHEDULE IS NOT JEOPARDIZED.

PIPING SYSTEMS

PIPING SPECIALTIES

BOILER FEED WATER

GATE VALVE

BS

BRINE SUPPLY

CHECK VALVE

BR

BRINE RETURN

BFW

CHWS

DUCTWORK SPECIALTIES

CWR

TRIPLE DUTY VALVE

CD

CONDENSATION DRAIN

CWS

CONDENSER WATER SUPPLY

CWR

CONDENSER WATER RETURN

BALANCING VALVE PRESSURE REDUCING VALVE

DIRECTION OF FLOW

3 WAY CONTROL VALVE

VOLUME EXTRACTOR

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

RELIEF VALVE

FILL

SPLITTER DAMPER

FUEL OIL GAUGE

AIR VENT

UP

G

GLYCOL SUPPLY

GR

GLYCOL RETURN

CD

HIGH PRESSURE STEAM SUPPLY

14. HEATING DESIGN CONDITIONS ARE AND 70ºF INDOOR AT 3ºF OUTDOOR.

HSS

HIGH PRESSURE STEAM CONDENSATE

15. THE HVAC CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL MECHANICAL EQUIPMENT,DUCTWORK, PIPING, ETC. TO FIT WITHIN THE SPACE ALLOWED BY THE ARCHITECTURAL AND STRUCTURAL CONDITIONS. CUTTING OR OTHERWISE ALTERING ANY STRUCTURAL MEMBERS SHALL NOT BE PERMITTED WITHOUT WRITTEN PERMISSION FROM THE ARCHITECT.

HWS

HOT WATER SUPPLY

24. UNLESS NOTED OTHERWISE, TRANSFORMERS, CONTROLS AND CONTROL WIRING REQUIRED FOR ALL MECHANICAL SYSTEMS SHALL BE FURNISHED WITH THE EQUIPMENT IT SERVES AND INSTALLED BY THE MECHANICAL CONTRACTOR. MOTOR STARTERS FOR HVAC EQUIPMENT SHALL BE FURNISHED WITH THE MOTOR OR APPARATUS WHICH IT OPERATES. MOTOR STARTER INSTALLATION SHALL BE BY THE ELECTRICAL CONTRACTOR. 25. ALL EVAPORATORS AND COOLING COILS LOCATED ABOVE THE LOWEST LEVEL FINISHED FLOOR SHALL BE INSTALLED WITH AN AUXILIARY CONDENSATE DRAIN PAN UNDER THE UNIT. PROVIDE AN ELECTRONIC WATER LEVEL DETECTOR WIRED TO SHUTDOWN THE UNIT UPON DETECTION OF WATER IN THE AUXILIARY DRAIN PAN. 26. AS AN ALTERNATE TO THE AUXILIARY CONDENSATE DRAIN PAN, AN ELECTRONIC WATER LEVEL DETECTOR WIRED TO SHUTDOWN THE UNIT UPON DETECTION OF WATER MAY BE INSTALLED IN THE PRIMARY DRAIN LINE, THE OVERFLOW DRAIN LINE OR THE EQUIPMENT-SUPPLIED DRAIN PAN. THE WATER LEVEL DETECTOR SHALL BE LOCATED AT A POINT HIGHER THAN THE PRIMARY DRAIN LINE CONNECTION AND BELOW THE OVERFLOW RIM OF SUCH PAN.

DUCT DROP IN RESPECT TO AIR FLOW

HWR

HOT WATER RETURN

LSS

LOW PRESSURE STEAM SUPPLY

LSC

LOW PRESSURE STEAM CONDENSATE

MSS

MEDIUM PRESSURE STEAM SUPPLY

MSC

MEDIUM PRESSURE STEAM CONDENSATE

BT

DUCT RISE IN RESPECT TO AIR FLOW

STAE COLLEGE, PA 16801

STRAINER

FLEXIBLE DUCT CONNECTION

STRUCTURAL ENGINEER

FLOAT & THERMOSTATIC TRAP

DIFFUSER

WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

INVERTED BUCKET TRAP RETURN/EXHAUST OUTLET TEE-TURNED DOWN

A G

ELBOW-TURNED DOWN

DIFFUSER WITH FLEX DUCT

ELBOW-TURNED UP

RETURN/EXHAUST OUTLET

PIPE ANCHOR

RETURN GRILLE RG-1

PIPE GUIDE

ACOUSTICAL DUCT LINING

FLEXIBLE PIPE CONNECTION

PC

PUMPED CONDENSATE

RL

REFRIGERANT LIQUID

RS

REFRIGERANT SUCTION

RHG

REFRIGERANT HOT GAS

UNION

VENT

COMPANION FLANGE

SOUND ATTENUATOR

REDUCER

V

NEW DUCTWORK

PIPE CAP

FUTURE DUCTWORK EXISTING DUCT TO REMAIN EXISTING DUCT TO BE REMOVED

BLIND FLANGE FIRE DAMPER (VERTICAL) FLOW MEASURING STATION

MISCELLANEOUS

FIRE DAMPER (HORIZONTAL)

FLOW VENTURI T

THERMOSTAT (TEMPERATURE SENSOR)

T

E

T

R

T

N

THERMOSTAT-RELOCATED (TEMPERATURE SENSOR)

GAUGES (PRESSURE)

THERMOSTAT-NEW (TEMPERATURE SENSOR)

2 WAY CONTROL VALVE

HUMIDISTAT (HUMIDITY SENSOR)

CO2

CARBON DIOXIDE (CO2) SENSOR CARBON MONOXIDE (CO) SENSOR

CO

THERMOMETER

THERMOSTAT-EXISTING (TEMPERATURE SENSOR)

H

FIRE SMOKE DAMPER (VERTICAL)

FIRE SMOKE DAMPER (HORIZONTAL)

H

MD HUMIDIFIER

MOTORIZED DAMPER

TAGS

TRANSFER DUCT

CONNECT NEW TO EXISTING LIMIT OF REMOVAL

SD

EQP #

MOTORIZED EQUIPMENT (EF, B) UPPER - EQUIPMENT DESIGNATION LOWER - EQUIPMENT NUMBER

EQP #

NON-MOTORIZED EQUIPMENT (ET, AS, CV) UPPER - EQUIPMENT DESIGNATION LOWER - EQUIPMENT NUMBER

SMOKE DETECTOR

U

UNDERCUT DOOR

L

LOUVERED DOOR

CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

A

F&TT

LITITZ, PA 17543

GEOTECHNICAL ENGINEER

GAS

GS

AHA CONSULTING ENGINEERS ROSWELL, GA 30076

FOG

23. ALL REQUIRED CONTROL WIRING (INCLUDING POWER WIRING REQUIRED FOR CONTROL PANELS, DEVICES, ETC. ) NOT SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE INCLUDED AS PART OF THE MECHANICAL WORK.

MEP ENGINEER

DUCT TURNING DOWN

11. FIELD MEASURE THE EXACT SIZES AND VERIFY ALL OPENINGS FOR SHAFTS AND LOUVERS PRIOR TO SUBMISSION OF SHOP DRAWINGS AND INSTALLATION.

22. ALL MECHANICAL EQUIPMENT REQUIRING ELECTRICAL POWER SHALL BE INSTALLED WITH DISCONNECT SWITCHES AT EACH PIECE OF EQUIPMENT. COORDINATE SWITCH TYPE WITH EQUIPMENT CHARACTERISTICS, MANUFACTURER'S RECOMMENDATIONS AND THE ELECTRICAL DRAWINGS.

FLAT OVAL DUCT WITH SIZE

ANGLE VALVE

DN

21. THE HVAC CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH ELECTRICAL DRAWINGS PRIOR TO SUBMITTING SHOP DRAWINGS OR ORDERING EQUIPMENT. EQUIPMENT SHALL BE FURNISHED WIRED FOR THE VOLTAGES SHOWN ON THE ELECTRICAL PLANS.

12

DIRECTION OF PITCH

F

1600 NORTH SECOND STREET

1801 OLD ALABAMA RD, SUITE 125

DRAIN/HOSE BIBB

20. WHERE ABOVE CEILING VOLUMES AND MECHANICAL CLOSETS ARE UTILIZED AS A RETURN AIR PLENUM, ALL MATERIALS EXPOSED WITHIN THE PLENUMS SHALL BE NON-COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 AS DETERMINED IN ACCORDANCE WITH ASTM E84.

12Ø

ROUND DUCT WITH SIZE

DUCT TURNING UP

FUEL OIL RETURN

19. ALL PIPE AND DUCT PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE THE ASSEMBLY TO ITS ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY TREMCO, HILTI, 3M OR APPROVED EQUAL.

ASSOCIATE ARCHITECT

BUTTERFLY VALVE

FOR

18. PORTIONS OF DUCTWORK AND PIPE INSULATION VISIBLE THROUGH AIR DISTRIBUTION DEVICES IN FINISHED AREAS SHALL BE PAINTED FLAT BLACK.

DUCT SECTION - RETURN

48

10. COORDINATE PHASING REQUIREMENTS FOR THE PROJECT WITH THE GENERAL CONTRACTOR.

17. PROVIDE ACCESS PANELS IN NON-ACCESSIBLE CEILINGS AND IN WALL STRUCTURE OF ADEQUATE SIZE TO ALLOW FOR MAINTENANCE, BALANCING AND COMPLETE REPLACEMENT OF EQUIPMENT WITHOUT DISTURBING PERMANENT CONSTRUCTION. ACCESS PANELS IN CEILINGS AND WALLS SHALL BE PROVIDED WHERE SHOWN ON THE PLANS OR NECESSARY TO ACCESS DAMPERS, VALVES, ETC. COORDINATE EXACT LOCATION & SIZES OF ALL ACCESS PANELS WITH THE ARCHITECT DURING THE SHOP DRAWING PROCESS.

12

HARRISBURG, PA 17102-2499

WEIGHTED LEVER VALVE

16. ANY EXISTING WALL, FLOOR, OR CEILING SURFACE THAT IS DISTURBED DURING THE COURSE OF THE HVAC WORK SHALL BE REPAIRED TO MATCH NEW AND/OR EXISTING CONDITIONS.

ATLANTA, GA 30326

MURRAY AND ASSOCIATES ARCHITECTS

FUEL OIL SUPPLY

13. COOLING DESIGN CONDITIONS ARE 75 F, 50% RH, INDOOR AT 89ºF DB/72ºF WB OUTDOOR.

DUCT SECTION - SUPPLY

24

FOS

12. MINIMAL CONTROL POWER HAS BEEN IDENTIFIED ON THE DRAWINGS. IF ANY ADDITIONAL POWER IS REQUIRED BASED ON SYSTEMS DESIGN BY THE CONTROLS CONTRACTOR THE ATC/BAS CONTRACTOR SHALL BE RESPONSIBLE TO SUPPLY THAT POWER.

12

BALL VALVE

CITY WATER MAKEUP

TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675

24

CHILLED WATER RETURN

COMPRESSED AIR

ARCHITECT HKS, INC.

ROUND DUCT

12Ø

CHILLED WATER SUPPLY

CA

FLAT OVAL DUCT

24 x 12

GLOBE VALVE CHWR

RECTANGULAR DUCT

14 x 6

H-1 A P 1

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

GENERAL DUCTWORK NOTES

UPPER - SECTION DESIGNATION LOWER - DRAWING NUMBER

UPPER - RISER DESIGNATION LOWER - RISER NUMBER

KEY PLAN

A

HVAC ABBREVIATIONS FPM

FEET PER MINUTE

AD

ACCESS DOOR

FPT

FAN POWERED TERMINAL

PRV

PRESSURE REDUCING VALVE

AFF

ABOVE FINISHED FLOOR

GPH

GALLONS PER HOUR

PSIG

POUNDS PER SQUARE INCH GAUGE

AP

ACCESS PANEL

GPM

GALLONS PER MINUTE

AS

AIR SEPARATOR

HP

TEMPLATE VERSION: 2.6.8.20141012

REQ'D

RETURN AIR

HPR

HIGH PRESSURE STEAM CONDENSATE RETURN

CFM

CUBIC FEET PER MINUTE

HPS

HIGH PRESSURE STEAM SUPPLY

RPM

REVOLUTIONS PER MINUTE

CHWR

CHILLED WATER RETURN

HWR

HEATING WATER RETURN

SMD

SMOKE DAMPER

CHWS

CHILLED WATER SUPPLY

HWS

HEATING WATER SUPPLY

SD

SMOKE DETECTOR

CO

CLEAN OUT

LAT

LEAVING AIR TEMPERATURE

SP

STATIC PRESSURE (INCHES OF WATER)

CW

COLD WATER (PLUMBING)

LBS/HR

RH

SPD

SPLITTER DAMPER

CWR

CONDENSER WATER RETURN

LPR

LOW PRESSURE STEAM CONDENSATE RETURN

T&P

TEMPERATURE AND PRESSURE

CWS

CONDENSER WATER SUPPLY

LPS

LOW PRESSURE STEAM SUPPLY

TYP

TYPICAL

DRAIN

LRA

LOCK ROTOR AMPS

DB

DRY BULB

LWT

LEAVING WATER TEMPERATURE

DIM

DIMENSION

MAX

MAXIMUM

DRAWING

MBH

THOUSAND BTU PER HOUR

VAC VD VDC

DX

DIRECT EXPANSION

MD

MOTORIZED DAMPER

EAT

ENTERING AIR TEMPERATURE

MIN

MINIMUM

ETR

EXISTING TO REMAIN

MPR

MEDIUM PRESSURE STEAM RETURN

WB

ELECTRIC PNEUMATIC RELAY

MPS

MEDIUM PRESSURE STEAM SUPPLY

WMS

EP

W/ W/OUT

DATE

RELATIVE HUMIDITY

POUNDS PER HOUR

V

REVISION NO. DESCRIPTION

REQUIRED

AUTOMATIC TEMPERATURE CONTROL

DWG

12/14/2015 11:03:10 PM

RA

PLUMBING

ATC

D

PLOT DATE:

HORSEPOWER

PLBG

B

AUTOMATIC CONTROL DAMPER

ACD

VOLTS VOLTS A/C VOLUME DAMPER AHA PROJECT NUMBER

VOLTS D/C

G1215-004.00

WITH

DATE

WITHOUT WET BULB TEMPERATURE °F

03 DECEMBER 2015

1/2" x 1/2" GALVANIZED WIRE MESH SCREEN

ISSUE

WET SPRINKLER

ENTERING WATER TEMPERATURE

NC

NORMALLY CLOSED

EXH

EXHAUST

NIC

NOT IN CONTRACT

CONSTRUCTION DOCUMENTS

F&T

FLOAT AND THERMOSTATIC

NO

NORMALLY OPEN

SHEET TITLE

FACP

FIRE ALARM CONTROL PANNEL

OA

OUTSIDE AIR

HVAC GENERAL NOTES AND LEGEND

EWT

FCU

FAN COIL UNIT

OBD

OPPOSED BLADE DAMPER

FLA

FULL LOAD AMPS

OED

OPEN END DRAIN

FD

FIRE DAMPER OR FLOOR DRAIN

PD

PRESSURE DROP

COMBINATION FIRE DAMPER/SMOKE DAMPER

PE

PNEUMATIC ELECTRIC SWITCH

FD/SMD

WS

REVISED 15 DECEMBER 2015

SHEET NO.

M-001

19

18

17.4

17

1514.8

16

13

14.1 14

12

11

10

9 ARCHITECT HKS, INC.

19.9

x.2

20

x.4.1

TWO LIVE OAK CENTER

x.6

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

2 M-201

20.8

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

21

UTILITY TUNNEL T.R 028.1

WL G-2

22

SITE/CIVIL ENGINEER

23

DERCK & EDSON ASSOCIATES

ER-3 125

ER-2 75

027 GEOTECHNICAL ENGINEER

TRANSFORMER RM T

IDF

013

A-1

ER-1 50

CUST FAMILY 014 TOILET

6"x8"

SD-2 125

SD-2 120

010

011

WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

015.1

SERVERY #2

STO.

025

SD-4 485

SD-1 40

STRUCTURAL ENGINEER

CENTRAL PLANT

012

8"x14"

CIRC

STAE COLLEGE, PA 16801

1 M-404

024

PUBLIC TLT RM ER-4 M 300

G-1

2701 CAROLEAN INDUSTRIAL DRIVE

y.6.5 y.6

OFFICE

018

UH

CMT LABORATORIES, INC.

015.2

FOOD SERVICE PREP

DSS

029 SD-2 115

ER-2 75

LITITZ, PA 17543

18"x12"

PUBLIC TLT RM F

MOD T

33 SOUTH BROAD STREET

ICE/SODA

6"x10"

G-1

WL G-1

1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

EF

24

AHA CONSULTING ENGINEERS

028

18"x12"

23.6

MEP ENGINEER

026

SD-4 485

FIRE PUMP

ELEC.

GENERATOR RM

015.5

015.4

015.3

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

21.5

015

LOCKER RM

1 M-406

CUST SD-4 485

FTR

SD-5 630

A

(TYP. 4)

RG-1 --(TYP 12)

16"x14"

16"x16"

VESTIBULE

SD-5 545

Y.5 Y X.5 X.3

023

POT WASH

SD-5 630

008

SERVERY #2

020

70"x20"

SD-5 545

SD-4 485

SD-4 485

60"x20"

CIRC

88"x30"

Z

022

016

STAIR 04 LD-4 340

24"x20"

24"x18"

S-004

SD-4 485

X LD-4 340

SR 255

FD

SD-4 485

SD-5 630

50"x20"

W

SR 485

T.R. 017

V.8

U.3

SD-5 630

V.7

LD-4 340

23.6

32"x20"

SD-5 630

24

12"x18"

SD-4 485

SD-4 485

T.5

SERVERY #1

FTR

LD-4 340

U

FD

019

A

T

V 32"x16"

LD-4 340

14"ø

DINING HALL

SD-4 485

SD-5 630

KEF

009

MAU G-1

SD-5 630

LD-4 340

MATCHLINE: 3/ M-102

SD-3 245 KEF

I.6

LD-4 340

SD-3 245

Q

18"ø

WL G-3

T DSS

LD-4 340

SD-5 630

R

007

SD-3 245

SD-3 245

22"x16"

RECEIVING/ INVENTORY STORAGE

SR 255

G-2

SD-5 630

S 48"x16"

SR 255

K LD-4 340

SR 255

G-1

40"x16"

B-2

SD-3 245

P ELEC 007.1

SD-3 245

O N

KEY PLAN

MATCHLINE: 3/ M-102

24"x18"

1 M-101

HVAC PLAN - GROUND FLOOR - AREA A

J

K

L

M

A

M.2

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

AHA PROJECT NUMBER

12/14/2015 11:03:15 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - GROUND FLOOR - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-101

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

15

14

M.2

13

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

M

2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM

JK

LD-4 340

KEF

SD-5 630

I.6

LD-4 340

SD-3 245

MECHANICSBURG, PA 17050

18"ø

WL G-3

SD-3 245

SD-3 245

22"x16"

100 STERLING PARKWAY, SUITE 108

SR 255

G-2

T

ELEC

DSS

I

SD-5 630

LD-4 340

H.2 H G

SD-3 245

DSS

SD-3 245

24"x18"

B-1

SD-3 245

SD-3 245

030

MATCHLINE: 1/ M-101

SD-3 245 SD-3 245

ELEC

007.1

B-2

SD-3 245

WL G-10

UP SD-4 465

ATM

SD-3 245

SD-3 245

031

SD-3 245

SALES FLOOR

OFFICE

002

006

30"x18"

F.3

SD-3 205

SD-3 210

EUH

E D

MOD T

G-1

VESTIBULE SD-4 460

SD-3 245

001 14"x18"

FTR A

SD-3 245

SD-4 460

SD-3 245

SD-3 245

SD-3 245

40"x18"

005

C.2

OFFICE

18"x18"

004

SD-3 245 LD-3 245

WL G-8

OFFICE 64"x20"

F

SD-3 245

FTR

25

(TYP. 7)

SD-3 150

SD-3 245

A

B.5 EWH

B

G-4

SD-3 245

LD-3 245

C

84"x21"

MECH RM

STORAGE

033

SD-3 245

032

84"x21"

A.5

72"x18"

LD-3 245

WL G-9

EF

A.3

G-6 FTR

LD-3 245

LD-3 245

LD-3 245

8

LD-3 245

LD-3 245

LD-3 245

A

AHU

(TYP. 14)

G-3

A WL G-11

LD-3 245

7

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

MATCHLINE: 1/ M-101

6

5.3

5

4

2

1 KEY PLAN

3 M-102

HVAC PLAN - GROUND FLOOR - AREA B

A

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

AHA PROJECT NUMBER

12/14/2015 11:03:17 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - GROUND FLOOR - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-102

9

11 19

18

17.4

17

1514.8

16

1312.8

14.1 14

10

12

ARCHITECT HKS, INC.

x.1

x.2

x.4 x.4.1 x.5

x.6

x.7

x.8

TWO LIVE OAK CENTER

x.9x.10

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER

MECH

AHA CONSULTING ENGINEERS

WL 1-3

101

1801 OLD ALABAMA RD, SUITE 125

LD-1 145

AHU

ROSWELL, GA 30076

LD-1 145

1-1

50"x20"

PUBLIC TLT1-1RM -M

72"x15"

COMMONS 100

1-1

12"x10" FPT

INTEGRATIVE LEARNING

LD-1 170

24"x14"

102

SD-1 70

LD-1 170

SD-2 150

1-4

12"x10"108

-

SD-2 160

FPT

SD-2 150

22"x10"

28"x10"

18"ø

T TO FPT-1-2

Y.5

32"x10"

Y X.5 X.3 X

FTR

40"x10"

SD-2 165

A

LD-1 145 LD-1 145

LD-1 170

LD-1 145 LD-1 170

W V.8

LD-1 170

FTR

LD-1 170

LD-1 170

LD-1 145

LD-1 145

21

LD-1 170

LD-3 240

T TO FPT-1-5

18"x10"

20.8 LD-3 240

22

LD-3 240

22"x12"

M.2 M

RD-5 ---

SD-3 235

FTR

SD-3 275

110.2

RD-5 ---

1-3

RF 1-1

SD-3 250

18"x14"

32"x14"

WL 1-5 32"x14"

EWH

1-5

10"x10"

1-4

MAIL LOBBY

STAIR 02

110.1

S-102

SD-2 150

14"ø

RECP. SD-1 90

14"ø

107

SD-1 25

EF 1-2

6"x6" LD-3 240

24

16"x12"

(TYPICAL)

LD-3 240

23.6

TO AHU-1-2 10"x12"

FPT

RG-1 ---

LD-3 240

A

V.7

MAIL RECEIVING

SD-3 250

SD-2 150

A

21.5

23

32"x14"

RD-5 ---

RD-5 ---

20"x10"

106

S-104

1-2

SD-3 240

10"x10"

LOUNGE

MECHANICSBURG, PA 17050

EWH

T

(TYP. 2)

STRUCTURAL ENGINEER

111

TO FPT-1-3

STAIR 04 LD-1 170

SD-3 235

A

SD-2 185

1-3

FPT

FTR

STAE COLLEGE, PA 16801

MECH

30"x12"

16"x12"

CONFERENCE RM

2701 CAROLEAN INDUSTRIAL DRIVE

y.6.5 y.6

100 STERLING PARKWAY, SUITE 108

22"x12"

RD-4 ---

LD-1 180

T

SD-2 145

SD-2 145

ELEV.

24"x10" LD-1 170

SD-2 185

14"ø

105

Z

T

22"x10" FPT

16"ø

LD-1 180

32"x14"

WBCM

20"x14"

TO FPT-1-4

16"x10"

32"x14"

110

(TYP. 6)

22"x10"

PUBLIC TLT RM 28"x14" -F

50"x16"

LD-1 180

1-2

CMT LABORATORIES, INC.

SD-3 330

A

T

110.3

110.4

MAIL VEST.

FTR

SD-2 145

TO FPT-1-1

ER-3 225

1-1

FTR

SD-2 160

A

WL 1-4

AHU

OFFICE

LD-2 185

LD-1 180

FTR

RD-3 ---

SD-3 250

LD-2 185

A

16"x10" 100"x30"

EWH

14"x10"

FTR

LD-1 150

103

S-101

WKSTATIONS

LD-1 150

SD-2 145

75"x15"

GEOTECHNICAL ENGINEER

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

50"x24" ER-3 225

LD-1 150

12"x10"

1-2

LD-1 170 A

LITITZ, PA 17543

EF

STAIR 01 LD-1 170

33 SOUTH BROAD STREET

EWH

WL 1-1 SD-1 100

DERCK & EDSON ASSOCIATES

LD-1 145

WL 1-2

12"x10"

SITE/CIVIL ENGINEER

T LD-3 220

DSS A-2

SD-2 145

ELEV. LD-5 500

TLT

1-6

112

-

20"x10"

6"ø

STO.

U.3

14"x10"

SD-1 90

IDF 104

FPT

102"x26"

SD-3 220

113

107.1 40"x16"

JC

V

U

OFFICE

EF

T.5

OFFICE

1-3

115

T

114

1

L

SD-3 220

2

F

S

4

CORRIDOR TRPL SUITE

JK

MATCHLINE: 1/ M-104

C-101

117

WL 1-6

SD-3 235 WL 1-7

CD-1 160

I.6

Q

SD-3 240

STAFF BK RM 1

R

116

P 1

O N

TRPL SUITE (MIR) 118

KEY PLAN

A

1 M-103

HVAC PLAN - 1ST FLOOR - AREA A SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

2/M-401

C

RA SUITE (AREA A) - REFER TO .....

3/M-401

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

E

DOUBLE SUITE - REFER TO ......

5/M-401

DATE

KEYED NOTES

12/14/2015 11:03:21 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 1ST FLOOR - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-103

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M 15

14

M.2

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM

JK

WL 1-7

P O N

TRPL SUITE (MIR)

I

118 F

H.2 H

QUAD SUITE B I

G

121

2 20"x10" FCU

F.3

4 10"x10" 10"x8"

LAUNDRY

122

E

RG-A --3

RD-3 --(TYP. 2)

8"x8"

B-4

24"x10"

1

119

RA SUITE 127

T

EF

A

IDF T

123

CD-1 160

ELEC

FCU

DSS

E

1-4

T

30"x10"

T

12"x10"

E D

10"x8"

10"x10" RG-A ---

1

F

2

ER-1 200

SD-3 350 SD-2 150

6"x4" 1

BDBL SUITE - CW 129

MECH 12"x12" FTR

LOUNGE

A

(TYP. 10)

MATCHLINE: 1/ M-103

20"x10"

T

120 CD-1 160

124

1

DSS

D 2

B-3

22"x10"

20"x10"

10"x10"

SD-2 225 (TYP. 2)

2

QUAD SUITE A

131 1

2

G

133

2

1

2

C.2

5

C

2 14"x10"

QUAD SUITE C 14"x10" LD-2 225 (TYP. 4)

1

1

TRPL SUITE (MIR) - CW F

125 J

10"x10"

14"x10"

25

1

10"x10"

1

TRPL SUITE (MIR) F 126

CORRIDOR

2 CD-1 160

1

2

1

2 M-106

STAIR 05

C-102

B.5

S-105 1

2

DBL SUITE

DBL SUITE

128

130

B

B

1

2

CD-1 160

B

AREA COORD. SUITE (AC)

A

A.5

132

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1 D 3

MECHANICSBURG, PA 17050

CD-1 160

1

I.6

100 STERLING PARKWAY, SUITE 108

Q

EWH

STAIR 03

1-5

A.3

S-103

A

8

7

6

5.3

5

4

2

1

4.4 1 M-104

KEY PLAN

HVAC PLAN - 1ST FLOOR - AREA B

A

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:24 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 1ST FLOOR - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-104

19

18

17.4

17

1514.8

16

13 12.8

14.1 14

10

12 11

9 ARCHITECT HKS, INC.

x.1

x.2

x.4 x.4.1 x.5

x.6

x.7

x.8

TWO LIVE OAK CENTER

x.9x.10

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER

QUAD SUITE D

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

238

LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

1

236

A-3

T

K

G CD-1 170 QUAD

STAIR 01

D 4

S-201

FCU

2701 CAROLEAN INDUSTRIAL DRIVE

y.6.5 y.6

IDF

DSS

STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM

SUITE (MIR)

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

234

2

F

CD-1 170

3

FTR A

JC 242

LD-2 230

SD-2 230

(TYP. 3)

ELEC.

2

D

239

LOUNGE

RA SUITE 237

1 2

243

1

C

1

10"x10"

B

6"x4"

T

CORRIDOR

DBL SUITE

1

T

235

10"x10"

ER-1 50

232

A-4

2

1

1

(TYP. 8)

2

DSS

SR-1 1170

20"x10"

Z

GRAD SUITE

1

2

146

16"x10"

1

2

F TRPL SUITE (MIR)

1

1

CD-1 170

233 2 2

Y.5 Y X.5 X.3

1

LD-1 170

G

1

16"x10" LD-1 180

QUAD SUITE 230

20.8

F

21.5

CT

2

3

(FUTURE)

(FUTURE)

CRCU

CRCU

G-1

G-2

SR-1 1170

1

TRPL SUITE

CT

1

S-202

F

241

CT

STAIR 02

14"x10"

21

TRPL SUITE

X

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

RG-A ---

1

231

22"x10"

22 W

D 4

1

ELEV.

23

V.8

-

V.7

QUAD SUITE (MIR)

-

M

23.6

U.3

D 1ELEV. 18"x10"

U

201

T.5

24 G

10"x10" 10"x10"

V

T 2

1

L

2

S

1

F

R

TRPL SUITE

JK

MATCHLINE: 1/ M-106

CD-1 170

CORRIDOR

202

Q

147

1

I.6

P 1

TRPL SUITE (MIR)

O N

203

KEY PLAN

MATCHLINE: 1/ M-106

F

A

1 M-105

HVAC PLAN - 2ND FLOOR - AREA A SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:28 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 2ND FLOOR - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-105

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M 15

14

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

F

STRUCTURAL ENGINEER MATCHLINE: 1/ M-105

WBCM

TRPL SUITE

JK

202

MECHANICSBURG, PA 17050

147

1

P O N

TRPL SUITE (MIR)

I

203

D 3

F

H.2 H

QUAD SUITE B

206

I

G 2

FCU E

SD-3 350

ER-1 200

SD-2 150

RD-3 --(TYP 2)

1

3 RG-A ---

RG-A ---

1

10"x10"

DSS

IDF T

8"ø

208

14"x4" 12"x8" FTR

(TYP. 10)

2 1

204

QUAD SUITE B

DSS B-5

E

T

14"x4"

LOUNGE 209

4 F TRPL SUITE (MIR) - CW

4

DBL SUITE - CW 213 2

1

1

215

2

1

2

1

1

4 G QUAD SUITE - CW

4 B DBL SUITE - CW

217

219 1

2

2

1

2

I

C.2

2

C

10"x10" 34"x10"

12"x10" LD-2 225 (TYP. 4)

B

6"x4" 6"x4" 6"x4" 8"ø

1 SD-2 225 (TYP. 2) 14"x4"

211

D 2

12"x12"

T 14"x4"

221

RA SUITE

A

T

CD-1 190

E D

2

ELEC

FCU

B-6

A

CD-1 190

LAUNDRY

207

F.3

MATCHLINE: 1/ M-105

20"x10"

16"x10"

22"x10"

22"x10"

25 J

1

CORRIDOR

1

2

1

1

1

2

1

2

1

TRPL SUITE (MIR)

QUAD SUITE C

212

210

CD-1 190

2 M-106

F

B

B.5

14"x4"

10"x10"

148

14"x10"

DBL SUITE 214

2

QUAD SUITE G

216

1

B

1

DBL SUITE (MIR)

CD-1 190

DBL SUITE B

2

8"ø

220

218

B

1 4

A.5

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1

I.6

F

100 STERLING PARKWAY, SUITE 108

Q

CORRIDOR

SR-1 1170

STAIR 03 D 5

S-203

A

LD-2 190

8

7

6

5.3

5

4

3

2

1

4.4 1 M-106

KEY PLAN

HVAC PLAN - 2ND FLOOR - AREA B

A

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND 25 BBBB

CC C C

PLUMBING PIPING. SEE PLUMBING PLANS FOR TYPES AND SIZES.

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401 AHA PROJECT NUMBER

F

TEMPLATE VERSION: 2.6.8.20141012

12/14/2015 11:03:32 PM

A

4X6 OA DUCT

FIRE PROTECTION PIPING.

PLOT DATE:

KEYED NOTES

C.2 C.2

14X10 EA DUCT 20X10 OA DUCT

4X6 EA DUCT

SHEET NOTES

DATE

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

B.5

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS

2ND FLOOR 129' - 3"

2 M-106

TYPICAL CORRIDOR SECTION SCALE: 1/4" = 1'-0"

SHEET TITLE

HVAC DUCTWORK PLAN - 2ND FLOOR - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-106

9

11 19

18

17.4

17

1514.8

16

1312.8

14.1 14

10

12

ARCHITECT HKS, INC.

x.4

x.5

x.6

x.7

x.8

TWO LIVE OAK CENTER

x.9x.10

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

IDF

DSS A-5

QUAD SUITE D D 4

FCU

K

STAIR 01

336

334

T

CD-1 170

338

S-301

STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM

G

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

2

F

RG-A ---

1 2

1

ER-1 50

A

(TYP. 8)

JC

EWH

342

LD-2 230

SD-2 230

(TYP. 3)

2

3-1

DBL SUITE

1

T

16"x10"

3-1

10"x10"

D

1

DOUBLE SUITE

1

332

B

10"x10"

339

RA SUITE

B

337

2

16"x10"

2

333

343

1

2

F TRPL SUITE (MIR)

1

LOUNGE

2

C-300 EF

1

CORRIDOR

335

3

FTR

2

T

1

1

CD-1 170

1

LD-1 180

1

G

QUAD SUITE

20.8

F

14"x10"

EWH 3-2 STAIR 02

330

S-302

21

TRPL SUITE

Y X.5 X.3 X

LD-1 170

2

2

Y.5

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

ELEC.

CD-1 170

20"x10"

Z

QUAD SUITE (MIR)

1

2701 CAROLEAN INDUSTRIAL DRIVE

y.6.5 y.6

F

341

1

TRPL SUITE

21.5

1

331

22"x10"

8"ø

22 W

D 4

1 14"x4"

23

V.8

U.3

D 1

V.7

M

23.6

U

18"x10"

24

T.5

QUAD SUITE (MIR) 301

10"x10" 10"x10"

V

T

G 2

1

L

2

S

1 CD-1 170

F

TRPL SUITE

JK

MATCHLINE: 1/ M-108

R

CORRIDOR C-301

302

Q

1

I.6

P 1

TRPL SUITE (MIR)

O N

303

KEY PLAN

MATCHLINE: 1/ M-108

F

A

1 M-107

HVAC PLAN - 3RD FLOOR - AREA A SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:36 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 3RD FLOOR - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-107

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M 15

14

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

1

2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

F MATCHLINE: 1/ M-107

TRPL SUITE

JK

STRUCTURAL ENGINEER

CORRIDOR

WBCM

C-301

302

MECHANICSBURG, PA 17050

1

P O N

TRPL SUITE (MIR)

I

303

D 3

CD-1 190

F

H.2 H

MATCHLINE: 1/ M-107

QUAD SUITE B LAUNDRY

307

306

G

I

2

FCU E

RG-A ---

SD-3 350

ER-1 200

SD-2 150

RD-3 --(TYP 2)

8"x8"

1

3

T

1

ELEC

FCU A

DSS B-7

IDFT

T

FTR

14"x4"

T

14"x4"

321

B

6"x4" 6"x4" 6"x4" 8"ø

2

1

1

DBL SUITE - CW

TRPL SUITE 4(MIR) F - CW

4 G QUAD SUITE - CW

313

315

317

4

2

2

1

1

1

34"x10"

20"x10"

22"x10"

22"x10"

25 J

1

2

1

1

16"x10"

CORRIDOR

14"x10"

C-302

TRPL SUITE (MIR)

QUAD SUITE C 310

312

CD-1 190

F

B

4

2

C.2

DBL SUITE - CW 1

1

I

319

2

C

10"x10" 14"x4"

10"x10"

1 1

2

1

B

2

2

12"x10" LD-2 225 (TYP. 4)

311

E

D 2

12"x12"

1 SD-2 225 (TYP. 2)

QUAD SUITE B

EF

LOUNGE 309

RA SUITE

3-2

CD-1 190

16"x10" 14"x4"

A

(TYP. 10)

304

8"ø

308

14"x4" 12"x8"

E D

1

RG-A --10"x10"

F

2

2

2

1

DBL SUITE

DBL SUITE

314

316

CD-1 190

G

B

1

2

QUAD SUITE

DBL SUITE (MIR)

318

320

B

1 8"ø 1

B

4

A.5

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1

I.6

F.3

100 STERLING PARKWAY, SUITE 108

Q

EWH 3-3

STAIR 03 D 5

S-303

A

LD-2 190

8

7

6

5.3

5

4

3

2

1

4.4 1 M-108

KEY PLAN

HVAC PLAN - 3RD FLOOR - AREA B

A

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:39 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 3RD FLOOR - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-108

9

11 19

18

17.4

17

1514.8

16

1312.8

14.1 14

10

12

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

IDF

DSS A-6

QUAD SUITE D S-401

1 CD-1 170

SR-1 1170

FTR

1

JC SD-2 230

16"x10"

ELEC.

10"x10"

ER-1 50

442

(TYP. 3)

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

2

DBL SUITE

1

T

C-400

T

1

1

DOUBLE SUITE 432

D

B

10"x10"

439

RA SUITE

B

437

2

16"x10"

2

433

443

1

2

F TRPL SUITE (MIR)

1

LOUNGE

2

CORRIDOR

A-7

435

(TYP. 8)

LD-2 230

G

DSS

2

1

3

A

WBCM

2

RG-A --20"x10"

STRUCTURAL ENGINEER

CD-1 170

438

F

Z

434

T

1

CD-1 170

1 1

LD-1 170

2

G

2 LD-1 180

Y.5

1

14"x10"

STAIR 02

430

S-402

21

TRPL SUITE

Y X.5 X.3 X

QUAD SUITE

20.8

F

F

441

21.5

SR-1 1170

1

TRPL SUITE

1

431

22"x10" 8"ø

22 W

D 4

1

23

V.8

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

D 4

FCU

K

STAIR 01

436

STAE COLLEGE, PA 16801

QUAD SUITE (MIR)

1

U.3

D 1

V.7

M

23.6

U

18"x10"

24

T.5

QUAD SUITE (MIR) 401

10"x10" 10"x10"

V

T

G 2

1

L

2

S

1 CD-1 170

F

TRPL SUITE

JK

MATCHLINE: 1/ M-110

R

CORRIDOR C-401

402

Q

1

I.6

P TRPL SUITE (MIR)

1

O N

403

?

KEY PLAN

MATCHLINE: 1/ M-110

F

A

?

1 M-109

HVAC PLAN - 4TH FLOOR - AREA A SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:43 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 4TH FLOOR - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-109

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M 15

14

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

1

2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

F MATCHLINE: 1/ M-109

TRPL SUITE

JK

STRUCTURAL ENGINEER

CORRIDOR

WBCM

C-401

402

100 STERLING PARKWAY, SUITE 108

Q

MECHANICSBURG, PA 17050

I

403

D 3

MATCHLINE: 1/ M-109

CD-1 190

F

?

H.2 H

P O N

1

TRPL SUITE (MIR)

?

LAUNDRY

G

406

I 2 FCU E

F.3

RG-A ---

3

SD-3 350

ER-1 200

SD-2 150

RD-3 --(TYP 2)

8"x8"

1 1

T

RG-A --10"x10"

F IDFT

8"ø

408

14"x4" 12"x8" FTR

ELEC 404

DSS

14"x4"

411

421

FCU

LD-2 225 (TYP. 4)

B

6"x4" 6"x4" 6"x4" 8"ø

1 SD-2 225 (TYP. 2) 14"x4"

E

D 2

12"x12"

LOUNGE 409

QUAD SUITE B

T

CD-1 190

14"x4"

(TYP. 10)

RA SUITE

B-8

T

A

E D

1

A

DSS B-9

2

DBL SUITE - CW 413 2

1

1

2

1

415

2

1

1

12"x10"

20"x10"

22"x10"

22"x10"

25 J

1

2

1

1

1

16"x10"

CORRIDOR

14"x10"

C-402

2

CD-1 190

412

410

F

2

C.2 I

419

2

1

1

2

C

10"x10" 14"x4"

10"x10"

1 1

TRPL SUITE (MIR)

QUAD SUITE C

4

DBL SUITE - CW

417

2 34"x10"

B

G 4 QUAD SUITE - CW

4 F TRPL SUITE (MIR) - CW

4

2

1

DBL SUITE

DBL SUITE

414

416

2 CD-1 190

G

B

B

1

2

QUAD SUITE

DBL SUITE (MIR)

418

420

B

B

1 8"ø 1 4

A.5

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1

I.6

SR-1 1170

STAIR 03 D 5

S-403

A

LD-2 190

8

7

6

5.3

5

4

3

2

1

4.4 1 M-110

KEY PLAN

HVAC PLAN - 4TH FLOOR - AREA B

A

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:46 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 4TH FLOOR - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-110

9

11 19

18

17.4

17

1514.8

16

1312.8

14.1 14

10

12

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

IDF

DSS A-8

QUAD SUITE D K

STAIR 01

RG-A ---

G

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

1 CD-1 170

20"x10"

ELEC.

2

1

A

JC

(TYP. 8)

542 SD-2 230

LD-2 230

10"x10"

ER-1 50 2

DBL SUITE

1

T

(TYP. 3) 16"x10"

CORRIDOR C-500

EF

1 FTR

2

T

535

3

1

1

DOUBLE SUITE 532

5-1

D

B

10"x10"

539

RA SUITE

B

537

2

16"x10" 2

F TRPL SUITE (MIR)

1 2

533

1 1

1

LD-1 170

1

2

2

LOUNGE

Y.5

WBCM

2

F

Z

STRUCTURAL ENGINEER

CD-1 170

538

S-501

FCU

534

T

LD-1 180

543

1

QUAD SUITE 14"x10"

STAIR 02

530

S-502

21

TRPL SUITE

Y X.5 X.3 X

G

20.8

F

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

D 4

536

STAE COLLEGE, PA 16801

QUAD SUITE (MIR)

1

F

541

1

TRPL SUITE

21.5

1

531

22"x10"

22 W

D 4

1

23

V.8

U.3

D 1

V.7

M

23.6

U

18"x10"

24

T.5

QUAD SUITE (MIR) 501

10"x10" 10"x10"

V

T

G 2

1

L

2

S

1 CD-1 170

F

TRPL SUITE

JK

MATCHLINE: 1/ M-112

R

CORRIDOR C-501

444

Q

1

I.6

P TRPL SUITE (MIR)

1

O N

503

KEY PLAN

MATCHLINE: 1/ M-112

F

QUAD SUITE B A

C-603

1 M-111

HVAC PLAN - 5TH FLOOR - AREA A SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:50 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 5TH FLOOR - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-111

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M 15

14

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

F MATCHLINE: 1/ M-111

TRPL SUITE

JK

STRUCTURAL ENGINEER

CORRIDOR

WBCM

C-501

444

100 STERLING PARKWAY, SUITE 108

Q

MECHANICSBURG, PA 17050

I

P O N

1

TRPL SUITE (MIR) 503

D 3

CD-1 190

F

QUAD SUITE B

H.2 H

C-603

MATCHLINE: 1/ M-111

LAUNDRY 506

G

I 2 FCU E

F.3

RG-A ---

3

SD-3 350

ER-1 200

SD-2 150

RD-3 --(TYP 2)

8"x8"

1

T

1

F

2

ELEC

RG-A --10"x10"

504 EF

IDFT

B-10

8"ø

508

14"x4" 12"x8" FTR

FCU

511

521

T

CD-1 190

14"x4" 14"x4"

QUAD SUITE B

5-2

509 14"x4"

SD-2 225 (TYP. 2)

DBL SUITE - CW 513 2

1

1

2

1

515

2

B

4 G QUAD SUITE - CW

F 4 TRPL SUITE (MIR) - CW

4

1

2

C.2

DBL SUITE - CW

517 1

4

1

2

1

I

519

2

C

2 34"x10" 12"x10"

LG-2 225 (TYP. 4)

B

6"x4" 6"x4" 6"x4" 8"ø

1

LOUNGE

E

D 2

12"x12"

T

(TYP. 10)

RA SUITE

A

DSS

A

E D

1

20"x10"

22"x10"

22"x10"

25 J

1

1

2

QUAD SUITE C

TRPL SUITE (MIR)

510

512

1

1

16"x10"

CORRIDOR

14"x10"

C-502

2

14"x4"

10"x10"

1 1

CD-1 190

F

10"x10"

2

2

1

DBL SUITE

DBL SUITE

514

516

CD-1 190

G

B

B

1

QUAD SUITE

DBL SUITE (MIR)

518

520

B

B

1

2

8"ø 1 4

A.5

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1

I.6

STAIR 03 D 5

S-503

A

LD-2 190

8

7

6

5.3

5

4

3

2

1

4.4 1 M-112

KEY PLAN

HVAC PLAN - 5TH FLOOR - AREA B

A

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

12/14/2015 11:03:53 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 5TH FLOOR - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-112

9

11 19

18

17.4

17

1514.8

16

1312.8

14.1 14

10

12

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

IDF

DSS A-9

STAIR 01

RG-A ---

(TYP. 8) LD-2 230

Z

SR-1 1170

14"x10"

16"x10"

ELEC.

ER-1 50

642

2

DBL SUITE

T

LD-1 180

CD-1 170 1

DOUBLE SUITE

1

632

639

RA SUITE

B

637

2

B

5

D

1

LOUNGE

2

C-600

T

10"x10" 12"x10"

JC

CORRIDOR

635

1

(TYP. 3)

A-10

2

1 1

SD-2 230

100 STERLING PARKWAY, SUITE 108

DSS

10"x10"

CD-1 170

3

A

G 10"x10"

1

FTR

WBCM

2

F

20"x10"

STRUCTURAL ENGINEER

CD-1 170

MECHANICSBURG, PA 17050

S-601

FCU

634

T

2 54"x18" 54"x16"

1

2

F TRPL SUITE (MIR) 633

1

LD-1 170

1

6

643

1

2

G

2

Y.5

21

TRPL SUITE

Y X.5 X.3 X

QUAD SUITE

20.8

F

1

STAIR 02

630 54"x16"

S-602

40"x16"

F

641

SR-1 1170

TRPL SUITE

21.5

631

22

1 1

30"x20"

W 23

D 1

V.7

D 4

1

40"x16"

V.8

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

D 4

636

QUAD SUITE D K 638

STAE COLLEGE, PA 16801

QUAD SUITE (MIR)

1

U.3

10"x8"

U

M

23.6 24

T.5

QUAD SUITE (MIR) 601

V

T

G 2 1

L

2

S

1

F

R

TRPL SUITE

JK

MATCHLINE: 1/ M-114

CD-1 170

4

Q

CORRIDOR

602

C-601 1

I.6

P 1

TRPL SUITE (MIR)

O N

603

KEY PLAN

MATCHLINE: 1/ M-114

F

4

A

1 M-113

HVAC PLAN - 6TH FLOOR - AREA A SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

12/14/2015 11:03:57 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

5

54"X18" OUTSIDE AIR DOWN FROM ERU-1 ON ROOF.

6

40"X16" EXHAUST AIR UP TO ERU-1 ON ROOF.

F

TRIPLE SUITE - REFER TO........

DATE

AHA PROJECT NUMBER

G1215-004.00

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 6TH FLOOR - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-113

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M 15

14

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

1

2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

F

4

STRUCTURAL ENGINEER MATCHLINE: 1/ M-113

WBCM

TRPL SUITE

JK

602

100 STERLING PARKWAY, SUITE 108

Q

CORRIDOR

MECHANICSBURG, PA 17050

C-601

I.6 1

P O N

TRPL SUITE (MIR)

I

603

D 3

F

H.2 H

QUAD SUITE B

LAUNDRY

C-605

606

G

I 2

SD-3 350

ER-1 200

SD-2 150

RD-3 --(TYP 2)

FCU E

F.3

6

RG-A ---

8"x8"

60"x16"

F

RG-A ---

1 3

T

1

DSS

10"x10"

FCU

IDFT

24"x10"

CD-1 190

2

ELEC 604 DSS

RA SUITE

QUAD SUITE B

611

621

B-11

T

60"x14" 12"x12" 8"ø

T

LOUNGE 609

CD-1 190 SD-2 225

5

1

E

D 2

14"x4" 2

B

6"x4" 6"x4" 6"x4" 8"ø

34"x10"

FTR

20"x10"

E D

1

608

(TYP. 10)

4

A

B-12

A

MATCHLINE: 1/ M-113

DBL SUITE - CW 613 2

1

1

1

2

20"x10"

(TYP. 4)

QUAD SUITE - CW 1

1

2

CD-1 190

4

2

C.2

DBL SUITE - CW I

619

617

1

2

1

C

20"x10"

20"x10"

25 J

1

16"x10"

CORRIDOR

12"x10" LD-2 225

615

2

B

4

10"x10"

(TYP. 2) 10"x10"

G

4 F TRPL SUITE (MIR) - CW

4

14"x4"

10"x10"

C-602

14"x10"

1

1

2

QUAD SUITE C

TRPL SUITE (MIR)

610

612

1

2

1

1

CD-1 190

F

2

2

1

DBL SUITE

DBL SUITE

614

616 G

B

B

2

1

QUAD SUITE

DBL SUITE (MIR)

618

620

B

B

1 8"ø 1

4

A.5

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1

SR-1 1170 LD-2 190

STAIR 03 D 5

S-603

A

8

7

6

5.3

5

4

3

2

1

4.4 1 M-114

KEY PLAN

HVAC PLAN - 6TH FLOOR - AREA B SCALE: 1/8" = 1'-0"

A

B

REVISION NO. DESCRIPTION

12/14/2015 11:04:00 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

C

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

2/M-401

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-401 THROUGH M-403 FOR CONTINUATION.

RA SUITE (AREA A) - REFER TO .....

3/M-401

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

E

DOUBLE SUITE - REFER TO ......

5/M-401

5

70"X20" OUTSIDE AIR DOWN FROM ERU-2 ON ROOF.

6

60"X16" EXHAUST AIR UP TO ERU-2 ON ROOF.

F

TRIPLE SUITE - REFER TO........

DATE

AHA PROJECT NUMBER

G1215-004.00

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DUCTWORK PLAN - 6TH FLOOR - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-114

9

11 19

18

17.4

17

16

1514.8

1312.8

14.1 14

10

12

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050 RH R-1

SPF

Z

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1

CU A

ERU 1

Y.5

20.8 21

Y X.5 X.3 X

SPF 2 RH R-2

21.5 22

EPF

W

1

RH R-4

23

V.8

U.3

RH R-5

V.7

U

M

23.6

T.5

24 EPF 2

T

V L

S R

JK

MATCHLINE: 1/ M-116

Q

I.6 P O N

KEY PLAN

MATCHLINE: 1/ M-116

A

1 M-115

HVAC PLAN - ROOF - AREA A SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

AHA PROJECT NUMBER

12/14/2015 11:04:01 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC PLAN - ROOF - AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-115

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

L

17

16

M 15

14

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER MATCHLINE: 1/ M-115

WBCM

JK

100 STERLING PARKWAY, SUITE 108

Q

MECHANICSBURG, PA 17050

P O N

I

MATCHLINE: 1/ M-115

H.2 H DEF

G

F.3

1

ERU 2

F

CU B

C.2

B

SPF 3

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

I.6

RH R-3

A

8

7

6

5.3

5

4

3

2

1

4.4 1 M-116

KEY PLAN

HVAC PLAN - ROOF - AREA B

A

SCALE: 1/8" = 1'-0"

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

AHA PROJECT NUMBER

12/14/2015 11:04:03 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC PLAN - ROOF - AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-116

9

11 19

18

17.4

17

1514.8

16

13

14.1 14

10

12

ARCHITECT HKS, INC.

19.9 20

x.2

x.4.1

TWO LIVE OAK CENTER

x.6

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

2 M-201

20.8

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

21

MEP ENGINEER 12" PCHWS (FUTURE) 12" PCHWR (FUTURE)

UTILITY TUNNEL

21.5

AHA CONSULTING ENGINEERS

6" LPC 6" HPS

1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

015

22

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES

028.1

LITITZ, PA 17543

027

LOCKER RM

GEOTECHNICAL ENGINEER

028

23.6 24

TRANSFORMER RM

PUBLIC TLT RM F 013 G-1

ADD ALTERNATE: PROVIDE STEAM SNOW MELT SYSTEM. ROUTE STEAM LOOP UNDERNEATH STAIRS.

DSS

029

OFFICE

A-1

024

UH G-1

CUST FAMILY 014 TOILET

TIE 6" HPS AND 6" LPC INTO EXISTING 6" MAIN IN MANHOLE MH-7. REFER TO CIVIL DRAWINGS FOR CONTINUATION.

PUBLIC TLT RM M

FOOD SERVICE PREP

012

018

CIRC

SERVERY #2

010

025

2701 CAROLEAN INDUSTRIAL DRIVE

y.6.5 y.6

015.2

IDF

EF

CMT LABORATORIES, INC. STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM

1 M-405

CENTRAL PLANT

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

015.1

STO. 026

011

FIRE PUMP

ELEC.

GENERATOR RM

015.5

015.4 EWH

015.3

G-2 EF

CUST

Z

G-2

022

EWH

EF

G-3

G-5

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

23

33 SOUTH BROAD STREET

ICE/SODA

T.R

EWH G-1

EF

EF

G-3

G-4

SERVERY #2 023

VESTIBULE

Y.5

CIRC

008

016

POT WASH 020

Y X.5 X.3 X

STAIR 04 S-004

W 8" SCHWR 8" SCHWS 6" HWR 6" HWS

T.R.

V.8

017

M.2

V.7

U.3 U

M T.5

SERVERY #1 FTR

019

A

RECEIVING/ INVENTORY STORAGE

(TYP. 18)

V

2 1/2" SCHWR 2 1/2" SCHWS 2" HWR 2" HWS

PROVIDE FLOW METER IN HWS PIPING. PROVIDE TEMPERATURE SENSORS IN HWS&R KEFPIPING.

DINING HALL

L

009

MAU

T

007

G-1

S

G-1

1 1/4" HWS 1 1/4" HWR KEF

R

G-2

MATCHLINE: 1/ M-101

JK

MATCHLINE: 3/ M-102

Q T FM

I.6 P DSS

ELEC

B-2

007.1

I

O N

MATCHLINE: 1/ M-101 KEY PLAN

MATCHLINE: 3/ M-102

A

1 M-201

HVAC PIPING PLAN - GROUND FLOOR - AREA A

B

SCALE: 1/8" = 1'-0" REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

1ST FLOOR 116' - 0"

12" PCHWS 12" PCHWR

6" HPS 6" LPC AHA PROJECT NUMBER

12/14/2015 11:04:04 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

PIPE SUPPORTS BY GENERAL CONTRACTOR.

CONSTRUCTION DOCUMENTS Level 1 GROUND FLOOR 100' 0" 0' - 0"

2 M-201

SHEET TITLE

HVAC PIPING PLAN - GROUND FLOOR AREA A

SERVICE TUNNEL SECTION SCALE: 1/4" = 1'-0"

REVISED 15 DECEMBER 2015

SHEET NO.

M-201

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M 15

14

M.2

13

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

1 1/4" HWS 1 1/4" HWR

STAE COLLEGE, PA 16801

KEF

STRUCTURAL ENGINEER

G-2

MATCHLINE: 1/ M-101

WBCM

JK

MATCHLINE: 3/ M-102

100 STERLING PARKWAY, SUITE 108

Q

MECHANICSBURG, PA 17050

T FM

I.6 P ELEC

B-2

O N

007.1

I

MATCHLINE: 3/ M-102

DSS B-1

SALES FLOOR FM

ELEC

T

030

FM

002

PROVIDE FLOW METERS IN HWS AND SCHWS PIPING. PROVIDE TEMPERATURE SENSORS IN HWS&R AND SCHWS&R PIPING.

UP

T

H.2 H G

MATCHLINE: 1/ M-101

E D

ATM 031 2 1/2" SCHWR 2 1/2" SCHWS 2" HWR 2" HWS

F.3 F

EUH

OFFICE

G-1

006

VESTIBULE 001

OFFICE 005

C.2

OFFICE 004

C

STORAGE 032

FTR

(TYP. 7)

B.5

EWH

A

25

B

G-4

MECH RM 033 AHU

A.5

G-3

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

DSS

EF G-6 T C o n p tcie r2 g 0 iyh t7

A.3

FTR A

(TYP. 14)

8

7

A

6

5.3

5

4

2

1 KEY PLAN

1 M-202

HVAC PIPING PLAN - GROUND FLOOR - AREA B SCALE: 1/8" = 1'-0"

A

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

AHA PROJECT NUMBER

12/14/2015 11:04:06 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC PIPING PLAN - GROUND FLOOR AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-202

19

18

17.4

17

16

1514.8 x.1

14.1 14 x.2

x.4.1 x.4

13 12.8 x.5

x.6

x.7

1211

10

x.8

9

ARCHITECT HKS, INC. TWO LIVE OAK CENTER

x.9x.10

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER

P 4

MECH

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

EWH 101

LITITZ, PA 17543

1-2

P 4

PUBLIC1-1 TLT RM -M

24

COMMONS

1-1

EF

CMT LABORATORIES, INC. AHU

100

103

OFFICE

PUBLIC TLT RM -F 102

111 EWH

P 4

(TYP. 6)

3 1/2" HWS 3 1/2" HWR 4" SCHWS 4" SCHWR

3/4" HWS 3/4" HWR 1 1/4" SCHWS 1 1/4" SCHWR

MAIL RECEIVING

MAIL LOBBY

1-4

FPT 1-3

CONFERENCE RM

2 1/2" HWS 2 1/2" HWR 2 1/2" SCHWS 2 1/2" SCHWR

110.2

110.1

108 RF 1-1

19.9 20

.

STAIR 04

6" 3 '-

2" HWS 2" HWR 2 1/2" SCHWS 2 1/2" SCHWR

Y.5

S-104

106

P 2

FPT

20.8

1-5

21.5

105

P 2

1-4

STAIR 02 S-102

T

1-2

EWH

T

21

FPT

INTEGRATIVE LEARNING

6" SCHWR 6" SCHWS 4" HWR 4" HWS

LOUNGE

FM

MIN

FM

" 18

Y X.5 X.3 X

110.3

MECHANICSBURG, PA 17050

1-3

FPT

-

MECH

A

1-1

Z

WKSTATIONS

110

FTR

ELEV.

100 STERLING PARKWAY, SUITE 108

MAIL VEST.

P 11

(TYP. 6)

EWH

2" HWS 2" HWR 2" SCHWS 2" SCHWR

STRUCTURAL ENGINEER WBCM

FTR A

FPT

STAE COLLEGE, PA 16801

110.4

S-101 1-1

2701 CAROLEAN INDUSTRIAL DRIVE

y.6.5 y.6

1-2

1 1/2" HWS 1 1/2" HWR 2 1/2" SCHWS 2 1/2" SCHWR

STAIR 01 P 8

GEOTECHNICAL ENGINEER

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

AHU

6" SCHWS 6" SCHWR 4" HWS 4" HWR

RECP.

P 6

107

22 P 6

P 6

W V.8 V.7

EF 1-2

23

M.2 M

23.6

TLT T

ELEV.

DSS A-2

IDF

112

-

STO.

U.3

FPT 1-6

U

107.1

104

OFFICE 113

T.5

EF

JC

V

1-3

T

OFFICE

115

114

L

S F

STAFF BK RM 116

TRPL SUITE

MATCHLINE: 1/ M-103

117

JK

MATCHLINE: 1/ M-104

P 4

R

P 5

Q

CORRIDOR C-101

I.6

PROVIDE ISOLATION VALVES AT THE BOTTOM OF EACH RISER (TYPICAL).

P O N

TRPL SUITE (MIR)

I

118

MATCHLINE: 1/ M-103

KEY PLAN

MATCHLINE: 1/ M-104

F

A

1 M-203

HVAC PIPING PLAN - IST FLOOR - AREA A

B

SCALE: 1/8" = 1'-0"

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

2/M-401

C

RA SUITE (AREA A) - REFER TO .....

3/M-401

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

E

DOUBLE SUITE - REFER TO ......

5/M-401

DATE

KEYED NOTES

12/14/2015 11:04:10 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC PIPING PLAN - 1ST FLOOR AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-203

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

18

17

L

16

M15

14

M.2

13 12.8

11

10

9

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

F

116

TRPL SUITE

MATCHLINE: 1/ M-103

STRUCTURAL ENGINEER WBCM

117

JK

MATCHLINE: 1/ M-104

STAE COLLEGE, PA 16801

STAFF BK RM

P 5

100 STERLING PARKWAY, SUITE 108

Q

MECHANICSBURG, PA 17050

CORRIDOR C-101

I.6

PROVIDE ISOLATION VALVES AT THE BOTTOM OF EACH RISER (TYPICAL).

P O N

TRPL SUITE (MIR)

I

118

MATCHLINE: 1/ M-103 MATCHLINE: 1/ M-104

F

H.2 H

P 5

QUAD SUITE B LAUNDRY

122 I

G

P 10

121

P 1

P 1

P 5

P 9

P 2

FCU E

P 4

ELEC

F.3

FCU A

F

119

RA SUITE

EF

127

1-4 DSS B-4

IDF

T

FTR A

T

MECH

LOUNGE 124

(TYP. 10)

6" SCHWS 6" SCHWR 4" HWS 4" HWR

T

123 T 2 1/2" SCHWS 2 1/2" SCHWR 2" HWS 2" HWR

120

E D

E BDBL SUITE - CW 129

DSS B-3

?

F 3" SCHWS 3" SCHWR 2" HWS 2" HWR

QUAD SUITE A 3" SCHWS 3" SCHWR 1 1/2" HWS 1 1/2" HWR

?

G

133

C.2 HEAT TRACE ALL EXTERIOR PIPING.

C

QUAD SUITE C CORRIDOR

125

P 7

STAIR 05

C-102

4" SCHWS 4" SCHWR 3" HWS 3" HWR

B.5

S-105

25

B

J

TRPL SUITE (MIR) 126

4" SCHWS 4" SCHWR 2 1/2" HWS 2 1/2" HWR

2 M-106

F

DBL SUITE

DBL SUITE

128

130

B

2" SCHWS 2" SCHWR 1" HWS 1" HWR

B

AREA COORD. SUITE (AC)

A

A.5

132

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

P 3

EWH

P 3

STAIR 03

1-5

A.3

S-103

A P 5

8

P 1

7

P 1

6

P 9

5.3

5

P 2

4

2

1

4.4 1 M-204

KEY PLAN

HVAC PIPING PLAN - IST FLOOR - AREA B SCALE: 1/8" = 1'-0"

A

B

REVISION NO. DESCRIPTION

HVAC UNIT PLAN LEGEND

SHEET NOTES

A

STAFF APARTMENT - REFER TO.......

1/M-401

B

GRAD SUITE - REFER TO ....

2/M-401

C

RA SUITE (AREA A) - REFER TO .....

3/M-401

D

RA SUITE (AREA B) - REFER TO .....

4/M-401

E

DOUBLE SUITE - REFER TO ......

5/M-401

DATE

KEYED NOTES

12/14/2015 11:04:13 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

AHA PROJECT NUMBER

F

G1215-004.00 TRIPLE SUITE - REFER TO........

6/M-401 DATE

G

03 DECEMBER 2015 QUAD SUITE - REFER TO........

1/M-402 ISSUE

H

QUAD SUITE A - REFER TO........

2/M-402

I

QUAD SUITE B - REFER TO........

3/M-402

J

QUAD SUITE C - REFER TO........

1/M-403

K

QUAD SUITE D - REFER TO........

2/M-403

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC PIPING PLAN - 1ST FLOOR AREA B

REVISED 15 DECEMBER 2015

SHEET NO.

M-204

9

11 19

18

17.4

17

16

1514.8

1312.8

14.1 14

10

12

ARCHITECT HKS, INC.

x.1

x.2

x.4 x.4.1 x.5

x.6

x.7

x.8

TWO LIVE OAK CENTER

x.9x.10

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER

QUAD SUITE D

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

238

LITITZ, PA 17543

GEOTECHNICAL ENGINEER

IDF

DSS

14" CWR (FUTURE)

14" CWR

14" CWS (FUTURE)

14" CWS

236

A-3

T

K

FCU

CMT LABORATORIES, INC.

HEAT TRACE ALL EXTERIOR PIPING.

G

STAIR 01

QUAD SUITE (MIR)

S-201

234

2701 CAROLEAN INDUSTRIAL DRIVE

y.6.5 y.6

STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM

8" CWR 8" CWS

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

F

GRAD SUITE DSS

232

A-4

T

C

235

JC

FTR A

Z

CORRIDOR

DBL SUITE

242

(TYP. 8)

D

239

146

RA SUITE

B

T

237

LOUNGE 243

F TRPL SUITE (MIR) 233

" 18

MIN

G

.

6" 3 '-

Y.5

CT

CT

1

2

3

(FUTURE)

(FUTURE)

QUAD SUITE 230

20.8

F

STAIR 02

CRCU

CRCU

G-1

G-2

CT

S-202

21

TRPL SUITE

Y X.5 X.3 X

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

ELEC.

2

F

241

TRPL SUITE

21.5

231

22 W

ELEV.

23

V.8

U.3

-

ELEV.

V.7

-

M

23.6

QUAD SUITE (MIR)

U

201

T.5

24 G

T

V L

S F

MATCHLINE: 1/ M-105

TRPL SUITE

JK

MATCHLINE: 1/ M-106

202

R CORRIDOR

Q

147

I.6 P TRPL SUITE (MIR) 203

O N

MATCHLINE: 1/ M-105 KEY PLAN

MATCHLINE: 1/ M-106

F

? A

?

1 M-205

HVAC PIPING PLAN - 2ND FLOOR - AREA A

B

SCALE: 1/8" = 1'-0" REVISION NO. DESCRIPTION

DATE

AHA PROJECT NUMBER

12/14/2015 11:04:16 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC PIPING PLAN - 2ND FLOOR AREA A

REVISED 15 DECEMBER 2015

SHEET NO.

M-205

12.8

17 4

4.4

5

16

11

L

15

5.3 ARCHITECT HKS, INC. TWO LIVE OAK CENTER

5

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

5

SR-A 175

U

SR-A 150

SR-A 150

SR-B 250

SR-A 150

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS

K

SR-A 125

A

D

1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

J

8"ø

8"ø

MEP ENGINEER AHA CONSULTING ENGINEERS

T.5

8"ø

1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

DERCK & EDSON ASSOCIATES

10"x10" 6"ø

10"x10"

SITE/CIVIL ENGINEER 8"ø 10"x10"

8"ø

8"ø

A.3

8"ø

SR-A 100

33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER 10"x10"

CMT LABORATORIES, INC.

4"ø

SR-A 25

14"x10"

$ 8"ø

B

8"ø

T

6"ø

3

B

STRUCTURAL ENGINEER

ER-A 50

FCU

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

3

T RG-A ---

1-5

WBCM

C.2

T RG-A ---

6"x4"

6"x4"

6"x4"

2

C

6"x4"

S

6"x4"

6"x4" ER-A 50

4"ø

3

2-1

EF

SR-A 100

STAE COLLEGE, PA 16801

B

EF

RG-A ---

11

ER-A 50

FCU

2701 CAROLEAN INDUSTRIAL DRIVE

SR-A 25

SR-A 25

2

1

1

$

FCU

1

1 M-401

2

HVAC PLAN - STAFF APARTMENT

7 2

SCALE: 1/4" = 1'-0"

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

D

M-401

HVAC PLAN - UNIT GRAD

3

SCALE: 1/4" = 1'-0"

20.8

M-401

HVAC PLAN - UNIT SINGLE SCALE: 1/4" = 1'-0"

5.3

O

14

15

16

6 4 4

V

O P SR-A 125

8"ø

8"ø

8"ø

SR-A 175

SR-A 125

SR-A 175

8"ø

8"ø

SR-A 175

8"ø

10"ø

18

4

4

A

SR-B 275

4

SR-A 25

ER-A 50

FCU B

V.7

3

V.8

T RG-A --6"x4" 1

10"x10"

4"ø

6"x4"

SR-A 25

SR-A 25

ER-A 50

Q

M-401

SCALE: 1/4" = 1'-0"

SR-A 100

RG-A ---

T

ER-A 50

3

W

RG-A ---

2

6"x4"

D

6"x4"

R

B

5 M-401

6"x4"

1

HVAC PLAN - UNIT DOUBLE SCALE: 1/4" = 1'-0"

6"x4"

6"x4"

2

2

1

1

14.1

A

HVAC PLAN - UNIT SINGLE A

SR-A 25

FCU

FCU

4

ER-A 50

3

T

4"ø

6"ø

4"ø

6"ø

SR-A 75

14"x10"

10"x10"

4"ø

8"ø

10"x10"

6 M-401

HVAC PLAN - UNIT TRIPLE

KEY PLAN

SCALE: 1/4" = 1'-0"

A

B

REVISION NO. DESCRIPTION

SHEET NOTES

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

5

PROVIDE SOLER PALAU MODEL PER-150W PLASTIC LOUVER SHUTTER AT EXHAUST OUTLET. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS, COLOR SELECTION AND PAINT REQUIREMENTS.

TEMPLATE VERSION: 2.6.8.20141012

12/14/2015 11:04:21 PM

PLOT DATE:

DATE

AHA PROJECT NUMBER

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC - ENLARGED PLANS

REVISED 15 DECEMBER 2015

SHEET NO.

M-401

5

5

4

4

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675

4

4

4

ATLANTA, GA 30326

4

ASSOCIATE ARCHITECT

D

MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

SR-A 150 8"ø

SR-A 150

8"ø

SR-A 150

D

SR-A 125

SR-A 125

8"ø

SR-A 150

SR-A 125

MEP ENGINEER

SR-A 125

AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

8"ø

8"ø

8"ø

8"ø

SITE/CIVIL ENGINEER 4"ø

8"ø

12"x10"

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

8"x10"

LITITZ, PA 17543

8"x10"

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

C.2

MECHANICSBURG, PA 17050

10"ø

T

3 6"x4"

4"ø

SR-B 250

FCU

3 6"x4"

C

1

100 STERLING PARKWAY, SUITE 108

SR-A 125

C

2

FCU D

6"x4"

1

T

SR-A 25 4"ø ER-A 50

RG-A --SR-A 25

C.2

ER-A 50

8"x4"

C 4.4 1 M-402

2

HVAC PLAN - UNIT QUAD

2

SCALE: 1/4" = 1'-0"

E

M-402

D

C.2

B

C

A.5

5

4.4

HVAC PLAN - UNIT QUAD A SCALE: 1/4" = 1'-0"

A

1

10"x10"

16"x10"

4"ø

10"x10"

8"ø

SR-A 150

8"ø

SR-A 150

8"ø

SR-A 150

8"ø

SR-A 150

SR-A 25 ER-A 50

4"ø 10"ø

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

RG-A ---

ER-A 50

WBCM

14"x10"

4"ø

STRUCTURAL ENGINEER

SR-A 25

16"x10"

SR-A 25

6"x4"

STAE COLLEGE, PA 16801

4"ø

ER-A 50

T

RG-A ---

3

6"x4"

SR-B 250

ER-A 50 SR-A 25

6"x4"

6"x4"

2

FCU C

2

1

1

KEY PLAN

3 A

3 M-402

HVAC PLAN - UNIT QUAD END

B

SCALE: 1/4" = 1'-0" REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

4

IN UNITS WITH CURTAIN WALL, PROVIDE LD-1 LINEAR SLOTS IN LIEU OF SR-A GRILLES.

5

8"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.

AHA PROJECT NUMBER

12/14/2015 11:04:25 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC - ENLARGED PLANS

REVISED 15 DECEMBER 2015

SHEET NO.

M-402

8

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

A

SR-A 215

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

8"ø SR-A 215

MEP ENGINEER

22

21

AHA CONSULTING ENGINEERS

20

1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

8"ø

SITE/CIVIL ENGINEER

SR-A 150

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

8"ø

12"x10"

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

SR-A 25

2701 CAROLEAN INDUSTRIAL DRIVE

Z

SR-A 150

STAE COLLEGE, PA 16801

SR-A 125

6"ø

ER-A 50

SR-A 125

SR-A 125

LD-1 150

SR-A 125

STRUCTURAL ENGINEER

10"x10"

8"ø

8"ø

8"ø

8"ø

8"ø

8"ø

WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

LD-1 150

12"x10"

6"x4" 8"ø

4"ø

F

B

19

18"x10" 1

ER-A 50

T

3

4"ø

F.3

C

RG-A ---

2

SR-A 25

SR-A 25

FCU

ER-A 50

Y

C

6"x4"

SR-A 50

ER-A 50

3

X

11

12.8

13

HVAC PLAN - UNIT QUAD CURVE A SCALE: 1/4" = 1'-0"

I

H

FCU

6"x4"

6"x4"

1

14

T

RG-A ---

6"x4" 1

M-403

4"ø

X.5

C.2

1

SR-A 25

6"ø

16"x10"

6"x4"

C

1

U

2

G 22 2 M-403

21.5

21

R

20.8

20 19.9

T.5

S

HVAC PLAN - UNIT QUAD CURVE B SCALE: 1/4" = 1'-0"

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

Y.5

8"ø

SR-A 120

KEY PLAN

A

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES 1

6"X4" EXHAUST DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.

2

6"X4" OUTSIDE AIR DUCT WITH FIRE-SMOKE DAMPER AT CORRIDOR WALL PENETRATION. SEE M-103 THROUGH M-114 FOR CONTINUATION.

3

6"X4" OUTSIDE AIR DUCT DOWN TO RETURN AIR DUCTWORK OF FCU. PROVIDE BALANCING DAMPER IN OUTSIDE AIR DUCTWORK DROP. BALLANCE DAMPER TO OUTSIDE AIR FLOW SHOWN ON FCU SCHEDULE.

AHA PROJECT NUMBER

12/14/2015 11:04:28 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC - ENLARGED PLANS

REVISED 15 DECEMBER 2015

SHEET NO.

M-403

17

16

15

14.8

14.114 x.4.1

x.2

x.613

12

11

10 9

ARCHITECT HKS, INC.

PCHWP

PCHWP

PCHWP

3

2

1

TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

(FUTURE)

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499 BT

MEP ENGINEER

1 ET

AS

UH

1

G-3

1

AHA CONSULTING ENGINEERS

CRAC

T

1801 OLD ALABAMA RD, SUITE 125

G-1

ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543 CWP

HXS SCP

GEOTECHNICAL ENGINEER

TRANSFORMER RM

1

1

CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

015.2

1

STRUCTURAL ENGINEER

CWP HEX HXS SCP

WBCM

2

2

100 STERLING PARKWAY, SUITE 108

2

MECHANICSBURG, PA 17050

2

66"x15"

HWP

AS

CWP

2

3

3

(FUTURE)

HEX

1

1 ET

WFS

3

1

y.6

COOLING TOWER FILTRATION SYSTEM.

FD AHU G-1 CH

CH

CH

1

2

3

(FUTURE)

T T

(FUTURE) CRAC

66"x18"

G-2

CENTRAL PLANT 015.1

UH G-2

FD

T T

T

ELEC. 015.4

FIRE PUMP

GENERATOR RM

015.5

92"x24"

015.3

93"x21"

EWH G-2

AHU G-2

FD

ET

EF

EF

2

G-2

G-3

EF

G-1

WL G-4

36"x26"

6"ø

WL G-5

WL G-6

WL G-7

SCHWP SCHWP 1

S M-404

G-4

EWH

78"x24"

1

G-3

92"x24"

AS

FD

EF G-5

T

18"x12"

2

EWH

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

y.6.5

HWP

2

FD

T.5

U

U.3

KEY PLAN

HVAC PLAN - CENTRAL PLANT SCALE: 1/4" = 1'-0"

A

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

AHA PROJECT NUMBER

12/14/2015 11:04:30 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC - ENLARGED PLANS

REVISED 15 DECEMBER 2015

SHEET NO.

M-404

17

16

15

14.8

14.114

x.2

x.4.1

x.6

13

12

11

10

9

ARCHITECT HKS, INC.

PROVIDE 12"Ø PCHWS&R FLANGED CONNECTIONS FOR A TEMPORARY EMERGENCY AIR COOLED CHILLER ON GRADE.

PCHWP

PCHWP

PCHWP

3

2

1

TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

(FUTURE)

ASSOCIATE ARCHITECT 12" PCHWS

MURRAY AND ASSOCIATES ARCHITECTS

12" PCHWS

1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

BT

MEP ENGINEER

1

4" HPS

ET

AS

UH

AHA CONSULTING ENGINEERS

1

G-3

1801 OLD ALABAMA RD, SUITE 125

1

4" LPC

ROSWELL, GA 30076

12" PCHWR

SITE/CIVIL ENGINEER 12" PCHWR

12" PCHWR

DERCK & EDSON ASSOCIATES

4" HPS

33 SOUTH BROAD STREET LITITZ, PA 17543

14" CWS CWP

12" PCHWR 12" PCHWS

1

1

2

2

AS

2

3

6" HWS

14" CWR

HWP

CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER

CWP HEX

14" CWS

2

SCP

8" PCHWS

HXS

GEOTECHNICAL ENGINEER

TRANSFORMER RM 015.2

WBCM

2

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

14" CWS

SCP

14" CWS

HXS

8" PCHWR

CWP 3

(FUTURE)

y.6.5

HEX 1

HWP

ET

WFS

1

3

1

y.6

14" CWR GFS CH

CH

1

2

3

(FUTURE) ROUTE RUPTURE DISC DISCHARGE PIPING FROM CHILLER TO OUTSIDE, NOT LESS THAN 20 FEET FROM ALL OPENINGS INTO BUILDING.

AHU G-1

1

CH

(FUTURE)

CENTRAL PLANT 015.1

UH

T

6" HWR

6" HWS

G-2

PROVIDE FLOW METERS IN SCHWS AND HWS PIPING SERVING AHU-G-1 AND AHUG-2. PROVIDE TEMPERATURE SENSORS IN HWS&R AND SCHWS&R PIPING.

FM

FIRE PUMP

ELEC.

GENERATOR RM

015.5

015.4

015.3

8" SCHWR 8" SCHWS ET 2 AS 2

AHU G-2

8" SCHWR

REFRIGERANT DETECTION SYSTEM BY MSE MODEL CHILLGARD LE, OR APPROVED EQUAL. SYSTEM SHALL HAVE AUDIBLE AND VISUAL ALARMS. PROVIDE ADDITIONAL AUDIBLE AND VISUAL ALARM DIRECTLY OUTSIDE OF CENTRAL PLANT. INTERFACE CONTROLS WITH THE BUILDING AUTOMATION SYSTEM AND EXHAUST FAN EF-G-2.

SCHWP SCHWP

2

1

S

1 M-405

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

4" LPC

1

T.5

U

KEY PLAN

A

PIPING PLAN - CENTRAL PLANT SCALE: 1/4" = 1'-0"

B

REVISION NO. DESCRIPTION

SHEET NOTES

DATE

KEYED NOTES

AHA PROJECT NUMBER

12/14/2015 11:04:32 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC - ENLARGED PLANS

REVISED 15 DECEMBER 2015

SHEET NO.

M-405

SHEET NOTES 19

18

17.4

17

16

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ER-3 125

ER-2 75

ASSOCIATE ARCHITECT

SD-1 60

MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER

15

SD-3 235

AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

KD-1 485

KD-1 485

SITE/CIVIL ENGINEER

RG-1 --(TYP 6)

DERCK & EDSON ASSOCIATES

48"x20"

33 SOUTH BROAD STREET

14.8

LITITZ, PA 17543

SD-2 125

Y

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

24"x16"

1

STRUCTURAL ENGINEER

X 32"x20"

KEYED NOTES

52"x20"

EXHAUST AIR CONNECTION DOWN TO KITCHEN HOOD. TRANSITION TO HOOD CONNECTION SIZE IN DROP. SEE FOOD SERVICE DRAWINGS FOR HOOD CONNECTION SIZE, LOCATION, AND AIRFLOW.

2

SUPPLY AIR CONNECTION DOWN TO KITCHEN HOOD. TRANSITION TO HOOD CONNECTION SIZE IN DROP. SEE FOOD SERVICE DRAWINGS FOR HOOD CONNECTION SIZE, LOCATION, AND AIRFLOW.

KD-1 485

KD-1 485

W

U.3

KD-1 485

16"x14"

KD-1 485

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

1 KD-1 485 2

SD-1 60

KD-1 485 SD-2 175

U

V.7 93"x21"

40"x14"

2

12"x10"

24"x16"

T.5 1

12"x12"

SD-2 175

KD-1 485

19.9 20

KD-1 485

AHU-G-1 T 80"x20"

V

14.1 14

20.8 SD-3 275

S

16"x14"

KD-1 485 40"x10"

21

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

16"x14"

SD-2 175

WBCM

R

20"x16" KD-1 485

Q KEY PLAN

8"x14" KD-1 485 SD-2 215

M.2

1

A

1

2 KD-1 485

M

B

30"x16"

REVISION NO. DESCRIPTION

SD-2 215 14"ø

DATE

KD-1 485

P O

KD-1 485

13 L

MAU G-1 AHA PROJECT NUMBER

12/14/2015 8:00:08 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC - ENLARGED PLANS 1 M-406

HVAC PLAN - KITCHEN SCALE: 1/4" = 1'-0"

REVISED 15 DECEMBER 2015

SHEET NO.

M-406

PRESSURE GAUGE W/NEEDLE VALVE MANUAL AIR VENT

BALANCING VALVE

HIGH CAPACITY, AUTOMATIC AIR VENT

UNION, TYPICAL

PRESSURE REDUCING VALVE - (SET AT 4 PSIG HIGHER THAN PRESSURE AT HIGH POINT IN SYSTEM)

STEAM SUPPLY LINE

GLOBE VALVE

CENTRIFUGAL AIR SEPARATOR (PROVIDE LINE SIZE)

RETURN PIPING

SEE NOTE 1

HWS

ARCHITECT

HWR

UNION, TYPICAL

HKS, INC.

FILL LINE - REFER TO PLBG DWG

2-WAY CONTROL VAVLE

T&P RELIEF VALVE - (WHEN NOT PROVIDED ON HEAT TRANSFER DEVICE) PIPED TO FLOOR DRAIN

FROM SYSTEM

TO PUMP SUCTION LOW CAPACITY, AUTOMATIC AIR VENT

BRACKET SUPPORTS W/OVERHEAD SUPPORTS (WHERE REQUIRED)

HVAC COIL/CONDENSER

MEP ENGINEER

DRAIN VALVE W/HOSE CONNECTION

1/2" PRESSURE RELIEF VALVE. SEE NOTE 4

CONCRETE HOUSEKEEPING PAD. REFER TO STRUCTURAL DWGS.

AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER

F&T TRAP NOTES: 1. MAX. AUTOMATIC CONTROL VALVE SIZE 2 1/2". FOR STEAM FLOW RATE GREATER THAN 2 1/2" VALVE CAPACITY, FURNISH TWO CONTROL VALVES IN PARALLEL AS INDICATED. ONE SIZED FOR 1/3 AND ONE SIZED FOR 2/3 TOTAL CAPACITY. 2. BY-PASS PIPING AROUND F & T TRAP LEG SHALL BE SAME SIZE AS TRAP. 3. PROVIDE PIPE UNIONS, FLANGES & ARRANGE WATER PIPING TO FACILITATE TUBE BUNDLE REMOVAL WITH MINIMUM DISTURBANCE TO PIPING. 4. PRESSURE RELIEF VALVE SET AT 20% OVER WORKING PRESSURE.

AIR CHARGING VALVE (PRESSURIZED DRY TANK EQUAL TO FILL VALVE PRESSURE)

UNDERSLUNG CONNECTION CREATES THERMAL TRAP (12" MIN DROP)

HOSE END DRAIN VALVE

HARRISBURG, PA 17102-2499

3/4" GATE VALVE & CAPPED CONNECTION

SEE NOTE 3

EXPANSION TANK, FLOOR MOUNTED REPLACEABLE BLADDER TYPE

COMBINATION TEMPERATURE/PRESSURE TEST PORT , TYPICAL

1600 NORTH SECOND STREET

6" DIRT POCKET

STRAINER WITH BLOW-OFF VALVE

ATLANTA, GA 30326

MURRAY AND ASSOCIATES ARCHITECTS

PRESSURE GAUGE W/NEEDLE VALVE

SYSTEM CONNECTION (CONNECT TO SIDE OR BOTTOM OF MAIN HEADER)

3445 PEACHTREE ROAD, NE, SUITE 675

ASSOCIATE ARCHITECT

3/4" VACUUM BREAKER

PROVIDE TEE WHEN PARALLEL TANKS ARE TO BE USED

BLOWDOWN AND DRAIN VALVE W/HOSE CONNECTION

SHUT-OFF VALVE , TYPICAL (BUTTERFLY OR GATE)

MANUAL AIR VENT

BYPASS SAME SIZE AS CONTROL VALVES

12"MIN.

SUPPLY PIPING

TWO LIVE OAK CENTER

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

1 M-501

2-WAY VALVE COIL/CONDENSER CONNECTION

2

SCALE: N.T.S.

M-501

AIR SEPARATOR & EXPANION TANK

3

SCALE: N.T.S.

M-501

STEAM TO WATER HEAT EXCHANGER PIPING DETAIL

STRUCTURAL ENGINEER WBCM

SCALE: N.T.S.

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

AIR FLOW

TRANSITION TO ROUND OR FLAT OVAL BOX INLET CONNECTION AS REQUIRED

AQUASTAT

VD

VD

UNION STANDAR 45º RECTANGULAR TO ROUND BOOT CONNECTION MODEL 33000

45° RECTANGULAR TAKE OFF

BRANCH

RECTANGULAR BRANCH DUCT TAKE OFFS

MANUAL AIR VENT

STRAP HANGER - TYP. FOUR (4) PER BOX ATTACHED TO STRUCTURE TRANSITION TO SUPPLY DUCT SIZE SHOWN ON DWGS. BY SHEET METAL CONTRACTOR

ROUND BRANCH DUCT TAKE OFFS

M COIL

HWR HWS

NOTES:

SHUT-OFF BALL VALVE ALL ROUND AND RECTANGULAR BELL MOUTH FITTINGS SHALL BE INCLUDED WITH THE FOLLOWING STANDARD FEATURES: 1. NEOPRENE GASKET TO MINIMIZE AIR LEAKAGE. 2. PRE-DRILLED HOLES FOR QUICK MOUNTING. 3. CONSTRUCTED OF HEAVY DUTY GALVANIZED STEEL. 4. 26 GAUGE GALVANIZED QUADRANT VOLUME DAMPER WITH TIGHT FITTING GASKETING TO MINIMIZE LEAKAGE AT DAMPER PIVOT POINTS.

4 M-501

STRAINER SEE SPECIFICATION FOR FLEXIBLE DUCTWORK UTILIZATION

AUTOMATIC CONTROL VALVE. SEE SPECIFICATION FOR CONTROL SEQUENCE. 3/4" DRAIN VALVE W/ DIRT LEG & CAP

RUN OUTS FROM SUPPLY DUCT MAIN TO BOXES SHALL BE 2" LARGER THAN BOX INLET SIZE UNLESS NOTED OTHERWISE ON FLOOR PLANS.

BELL MOUTH CONNECTION DETAIL

5

SCALE: N.T.S.

M-501

NOTES: 1. FOR PIPE SIZES AND LOCATIONS SEE DRAWINGS. 2. VALVES SHALL BE INSTALLED WITHIN CABINET WHERE POSSIBLE. PROVIDE ACCESS TO ALL VALVES. 3. PROVIDE UNIT MOUNTED OR REMOTE THERMOSTAT AS SHOWN ON DRAWINGS.

VARIABLE + CONSTANT AIR VOLUME BOX DETAIL

6

SCALE: N.T.S.

M-501

CABINET UNIT HEATER DETAIL (HOT WATER) SCALE: N.T.S.

3-1/2" OPENING 1" I.P.T

FLEX DUCT MAX LENGTH = 5'-0"

PETCOCK 1/4" I.P.S.

BELLMOUTH TAKE-OFF

SUPPLY DUCT

T. & P. RELIEF VALVE - (WHEN NOT PROVIDED ON HEAT TRANSFER DEVICE) PIPED TO FLOOR DRAIN

1" I.P.T. FLEX DUCT SIZE SHALL MATCH DIFFUSER NECK SIZE.

CHECK VALVE

GLOBE VALVE

PRESSURE GAUGE W/ NEEDLE VALVE

BALANCING VALVE ADJUST TO PREVENT EXCESSIVE CIRCULATION THRU FEEDER

UNION (TYP)

BALL VALVE

VOLUME DAMPER

BALL VALVE W/MEMORY STOP

DRAW BAND WITH SILICONE SEALER

REFER TO PLBG DWGS FOR RPZ AND ADDITIONAL TRIM

1" BALL TYPE DRAIN VALVE W/CAP WATER SYSTEM

SUPPLY CEILING

PRESSURE REDUCING VALVE (SET AT 4 PSIG HIGHER THAN THE PRESSURE AT THE HIGH POINT IN THE SYSTEM)

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

SHUT-OFF / BALANCING BALL VALVE WITH MEMORY STOP

CEILING DIFFUSER RETURN

REDUCER (WHERE REQ'D.) KEY PLAN

NOTES: 1.

PIPING TO/FROM SHOT FEEDER SHALL BE 1". ENTIRE INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH CHEMICAL TREATMENT SUBCONTRACTOR'S INSTRUCTIONS.

A 7 M-501

CEILING DIFFUSER BRANCH TAKE-OFF DETAIL (FLEX)

8

SCALE: N.T.S.

M-501

CHEMICAL SHOT FEEDER

9

SCALE: N.T.S.

M-501

CITY MAKE-UP WATER PIPE TRIM SCALE: N.T.S.

B 4" DRYER EXHAUST DUCT

REVISION NO. DESCRIPTION

6" WALL FULL SIZE VENT PIPE TO ATMOSPHERE

PUMPED CONDENSATE

PRESSURE GAUGE

OVERFLOW TO SAME SIZE AS DRAIN LINE

OPEN TO ATMOSPHERE

DATE

DRYER VENT BOX DRYERBOX MODEL 425 OR EQUAL

PITCH DOWN TOWARD DRAIN A

GRAVITY RETURN HEADER

A

B

DRAW THRU

2" PLUS X

X

BLOW THRU

1" MINIMUM

2X

GAP = 1"

B 12/14/2015 11:04:35 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

UNIT TYPE

GATE VALVE (TYPICAL)

DRAIN PAN

CLEAN OUT

DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS THE NIPPLE ON THE DRAIN PAN

UNION (TYPICAL)

DRAIN LINE FULL SIZE OF TAPPING TO NEAREST FLOOR DRAIN.

BASEBOARD

CHECK VALVE (TYPICAL) AHA PROJECT NUMBER

FLOOR

G1215-004.00 DATE

OPEN DRAIN BY PLUMBING CONTRACTOR. SEE PLUMBING DRAWINGS FOR LOCATION.

03 DECEMBER 2015 HOUSEKEEPING PAD

WHERE X = STATIC PRESSURE IN PAN

ISSUE

CONSTRUCTION DOCUMENTS

NOTES: 1. INSTALL DRYER VENT BOX PER MANUFACTURER'S RECOMMENDATIONS.

SHEET TITLE

HVAC DETAILS 10 M-501

CONDENSATE DRAIN TRAP SCALE: N.T.S.

11 M-501

CONDENSATE PUMP DETAIL SCALE: N.T.S.

12 M-501

DRYER VENT WALL BOX SCALE: N.T.S.

REVISED 15 DECEMBER 2015

SHEET NO.

M-501

AIR DUCT DETECTORAND AIR SAMPLING CHAMBER

1/2" MIS

SPOT WELD ANGLE TO STRUCTURAL STEEL

INTERGRAL WIRE MESH SCREEN PROVIDED BY UNIT MANUFACTURER WIRE AND CONDUIT TO FIRE ALARM SYSTEM AND FMCS, BY ELECTRICAL CONTRACTOR.

DUCT WIDTH 144" MAX

STRUCTURAL STEEL OR BUILDING STRUCTURE

MOUNTING PLATE

HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

DAMPER ACTUATOR 24VDC, FAIL OPEN (WIRED TO FACP)

NEOPRENE GASKET

DUCT HEIGHT "A" DIM

ANGLES

HANGER STRAPS

ARCHITECT MOTORIZED AUTOMATIC DAMPER FURNISHED BY VENTILATOR MANUFACTURER & INSTALLED BY HVAC SUBCONTRACTOR.

INTAKE TUBE

C-CLAMP (TYPICAL)

LOUVERED CAP, 24" HIGH 2 HR FIRE RATING

OPEN CLOSE INDICATOR

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS

ROOF CURB, 36" HIGH, 2 HR FIRE RATING

1600 NORTH SECOND STREET

ROOF INSULATION WHERE APPLICABLE

HARRISBURG, PA 17102-2499

RETURN TUBE

SEE NOTE 1

MEP ENGINEER AHA CONSULTING ENGINEERS

MOUNTING NUTS STRAP HANGER

1801 OLD ALABAMA RD, SUITE 125

DUCT ELEVATION VIEW

TRAPEZE HANGER

ROSWELL, GA 30076

NOTES: 1. SMOKE DETECTORS SHALL BE IN ACCORDANCE WITH NFPA 72 AND ELECTRICAL SPECIFICATIONS. DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE ALARM SYSTEM BY THE ELECTRICAL CONTRACTOR. INSTALLED BY THE HVAC CONTRACTOR AND WIRED TO THE FMCS BY THE ATC CONTROL. THIS DETAIL APPLIES TO ALL RETURN SHAFT OPENINGS. 2. INSTALL PER MANUFACTURERS INSTALLATION INSTRUCTIONS. 3. PROVIDE ACCESS DOOR AT SAMPLING TUBES.

NOTES: 1. REFER TO OTHER DETAILS ON THIS DRAWING FOR HIGH VELOCITY DUCTWORK DETAILS AS REQUIRED. 2. FOR STRAP AND TRAPEZE HANGER SIZE, REFER TO SMACNA DUCT STANDARDS. 3. NO POP RIVETS ALLOWED, USE SELF-TAPPING SHEET METAL SCREWS ONLY.

"A" DIM 36" 72" 96" 120" 144"

# OF SD 1 2 3 4 5

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES

NOTE: 1.

33 SOUTH BROAD STREET LITITZ, PA 17543

ROOF CURB (MIN. 36" HEIGHT) TO BE FURNISHED BY HVAC & INSTALLED BY GENERAL CONTRACTOR. FLASHING SHALL BE PROVIDED BY GENERAL CONTRACTOR & COUNTERFLASHING BY HVAC SUBCONTRACTOR.

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

1 M-502

DUCT HANGER DETAIL (LOW VELOCITY)

2

SCALE: N.T.S.

M-502

DUCT SMOKE DETECTOR DETAIL

3

SCALE: N.T.S.

M-502

STRUCTURAL ENGINEER

ELEVATOR HOISTWAY VENT DETAIL

WBCM

SCALE: N.T.S.

100 STERLING PARKWAY, SUITE 108

NOTE: PROVIDE AUTOMATIC AIR VENT IN PUMP CASEING

EXTERIOR WALL

PIPE HANGERS (SPRING & NEOPRENE TYPE)

NOTE: 45° ELBOWS SHALL BE CONSIDERED AS STRAIGHT DUCT

SUPPLY DUCT TO DIFFUSER

CAULK WITH ACOUSTICAL SEALANT FROM SYSTEM

JACKETED PIPE INSULATION. REFER TO INSULATION SPECIFICATION

TIGHTLY PACK ANNULAR SPACE WITH A FIRE SAFING MATERIAL

ISOLATION VALVE

1" SOUND LINING FOR ALL LOW PRESSURE DUCTWORK (45° ELBOWS SHALL BE CONSIDERED AS STRAIGHT DUCT)

STAINLESS STEEL BRAIDED CONNECTOR VD

TO SYSTEM

ISOLATION VALVE

1" SOUND LINING SHALL EXTEND A MINIMUN OF 36" FROM TEE (TYP)

CHECK VALVE STAINLESS STEEL BRAIDED CONNECTOR (INCREASER WHERE REQ'D.)

9" INDUSTRIAL THERMOMETER W/ 3/4" NPT COPPER WELL

MULTIPORT PRESSURE INDICATOR (4-PORT)

1/4" O.D. COPPER TUBING W/ COMP. FITTINGS SUCTION DIFFUSER WITH STRAINER

BASE MOUNTED END SUCTION PUMP (LONG COUPLED)

PIPE INSULATION. REFER TO SPECIFICATION FOR INSULATION REQUIREMENTS PIPE SLEEVE

FIELD FABRICATED SUPPORT LEG

GROUTABLE FABRICATED STEEL BASE PLATE

DRAIN: TERMINATE NEAR F.D.

4" TYP

END SUCTION (BASE MOUNTED WATER) PUMP DETAIL

5

SCALE: N.T.S.

M-502

SU PPLY CO N N ECTIO N

SCALE: N.T.S.

6 M-502

3/4" HWS (MIN)

STRAIGHT DUCT AT INLET; MIN. 4x(INLET)

FPT

SU PPLY CO N N ECTIO N

SU PPLY CO N N ECTIO N

TEE RUNOUT

ELBOW RUNOUT

FAN POWERED TERMINAL UNIT SOUND LINING DETAIL SCALE: N.T.S.

3/4" HWR (MIN) ALTERNATE LOCATION FOR ACCESS DOOR

HANG W/RODS AND VIBRATION ISOLATORS CEILING

LOW VELOCITY DUCTWORK, SEE PLANS

ENCLOSURE FIN TUBE RADIATION

RUNOUTS TO BOXES SHALL BE 2" LARGER THAN BOX INLET SIZE UNLESS NOTED OTHERWISE ON FLOOR PLANS.

VD R HW S W H

1

FPT6-16"∅

FPT

STRAIGHT RUNOUT

EXTERIOR WALL ABOVE GROUND PIPE PENETRATION DETAIL

MAIN SUPPLY DUCT, SEE DETAIL FOR FITTINGS AT BRANCHES

FLEXIBLE DUCT (3' MAXIMUM)

DUCT HANGERS

FPT6-16"∅

FPT

3" HIGH CONCRETE HOUSE KEEPING PAD

FINISH FLOOR

4

FPT6-16"∅

CHILLED WATER PIPE

OSHA/ANSI COUPLER GUARD

M-502

1" ACOUSTICAL SOUND LINING SHALL EXTEND A MINIMUM OF 36" FROM FIRST 90° ELBOW

VD

FLOOR

PITCH DN

ESCUTCHEON PLATE

"S" JOINT COLLAR TO DUCT BOTH SIDES OF FIRE DAMPER (TYP.)

PET COCK

ONE PIECE ROLL FORMED GALVANIZED STEEL FRAME

FAN INDUCTION INLET WITH CLEARANCE

DOWN - FEED 1/2" AUTOMATICE CONTROL VALVE

1" THICK ACOUSTICAL SOUND LINING PERIMETER INDUCTION DIFFUSER

1/2" LINE & PET COCK

FLOOR

2.

FAN POWERED TERMINAL BOX (FPT) IS ILLUSTRATED. INLET DUCT CONDITIONS AND DUCT DISCHARGE CONDITIONS ARE TYPICAL FOR ALL TERMINAL BOXES.

3.

PROVIDE 1" THICK FILTER

4.

RETURN AIR FROM CEILING PLENUM THROUGH INTERNALLY LINED SOUND BAFFLE

5.

FOR DUCT SIZES SEE PLAN DRAWINGS.

9/32" DIAMETER GALVANIZED STEEL PIVOT ROD OR RIVET

PITCH UP

NOTES: TAKE OFF BOOT W/ MAXIMUM 3' FLEXIBLE DUCT. ALL ELBOWS OF 90° SHALL BE "HARD" DUCT. PROVIDE QUADRANT DAMPER IN EACH BRANCH.

FASTEN DAMPER TO SLEEVE BY WELDING 6" ON CENTER FLOOR OR WALL BUILDING CONSTRUCTION

FUSIBLE LINK (REPLACEABLE SNAP LINK)

INDUCTION SOUND BAFFLE 4 3 HOT WATER COIL REFER TO HOT WATER PIPING DETAIL 1/M-501

1.

STAINLESS STEEL NEGATOR CLOSURE SPRING

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

MECHANICSBURG, PA 17050

UP - FEED

ACCESS DOOR (MINIMUM 8"x8" FOR DUCT UP TO 12" WIDE; MINIMUM 12"x12" FOR WIDER DUCTWORK)

PIPE SLEEVE 3/4" HWR (MIN)

3/4" HWS (MIN)

BLADE LOCK

NOTE: FIRE DAMPER INSTALLATION TO MEET UL REQUIREMENTS.

KEY PLAN

NOTE: SEE DETAIL 1/M-504 FOR PENETRATION OF CONCRETE FLOORS.

A 7 M-502

FAN POWERED-PARALLEL VAV BOX W/ HOT WATER REHEAT COIL DETAIL SCALE: N.T.S.

8 M-502

FIN TUBE RADIATION DETAIL

9

SCALE: N.T.S.

M-502

FIRE DAMPER WITH BLADE OUTSIDE OF AIRSTREAM SCALE: N.T.S.

B

REVISION NO. DESCRIPTION

1" MINIMUM TYPICAL OVERLAP ON ALL SIDES OF DAMPER

DATE

SHAFT WALL VENT TO ATMOSPHERE

12/14/2015 11:04:38 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

ITEM.

DUCT

DESCRIPTION

1.

ACTUATOR

2.

FIRESTAT

3.

AUXILLARY OPERATING JACK SHAFT

4.

DAMPER

5.

OVER CENTER LOCK

6

SLEEVE

7.

CAULKING MATERIAL

8.

PFMA OR CONVENTIONAL MOUNTING ANGLES

9.

S-JOINT/DUCT MATE, SLEEVE TO DUCT

LONG ANGLES 1/4" (6) MIN. FROM HIGH PRESSURE RETURN

7 1

PROVIDE 1/2 TRAP SIZE

5

BY-PASS LINE

4

FLASH TANK

2

LOW PRESSURE TRAP ASSEMBLY

STRAPS

FLOAT & THERMOSTATIC TRAP

6 DIRT LEG

3

AHA PROJECT NUMBER

TO CONDENSATE RECEIVER

G1215-004.00

MAXIUM FLOOR OPENING

9

DATE

03 DECEMBER 2015 ROOM SIDE

NOTES:

9 SHAFT SIDE

1.

8

DRAIN

SHUT-OFF VALVE

ISSUE

CONSTRUCTION DOCUMENTS

FLASH TANK ELEVATION SHALL BE FIELD DETERMINED TO ALLOW ADEQUATE PITCH OF DISCHARGED CONDENSATE. FURNISH AND INSTALL ALL SUPPORTS TO STRUCTURE.

SHEET TITLE

HVAC DETAILS 10 M-502

FIRE/SMOKE COMBINATION DAMPER DETAIL SCALE: N.T.S.

11 M-502

FLASH TANK DETAIL SCALE: N.T.S.

12 M-502

FLOOR GUIDE DETAIL SCALE: N.T.S.

REVISED 15 DECEMBER 2015

SHEET NO.

M-502

GENERATOR EXHAUST PIPE. PROVIDE ANCHORS, GUIDES, AND EXPANSION COMPENSATORA IN VERTICAL. OFFSET HORIZONTAL PIPING AS REQUIRED TO ALLOW FOR EXPANSION (TYP)

3/4" SYSTEM RELIEF VALVE HOT OR CHILLED WATER PIPE REQUIRING GLYCOL

HEATING COIL

AIR FLOW

SUPPORT FROM STRUCTURE ABOVE W/VIBRATION ISOLATORS (TYP) BY HVAC CONTRACTOR

PROVIDE PIPING REDUCER AND DIELECTRIC UNION AT UNIT COIL CONNECTION WHERE REQUIRED.

ARCHITECT HKS, INC.

REFER TO GENERATOR STACKHEAD DETAIL FOR CONTINUATION

HWR

3/4" GLYCOL INJECTION MANIFOLD W/ BALL VALVE & CHECK VALVE

COOLING COIL

3/4"

TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

HWS

ASSOCIATE ARCHITECT 4" EXHAUST COND. TRAP, 12" LONG W/PET COCK & TRAP PIPE TO FLOOR DRAIN

FLEXIBLE CONNECTION CHWR REDUCERS AS REQUIRED FLANGES AS REQUIRED BY HVAC CONTRACTOR

CHWS

55 GALLON SOLUTION CONTAINER WITH STAND FOR PUMP, PRESSURE TANK, GAUGE AND PRV

MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET

RECOVERY LINE FROM SYSTEM RELIEF VALVE

TO FLOOR DRAIN

MEP ENGINEER 3/4"

EMERGENCY GENERATOR (BY ELEC CONTRACTOR)

1/2" DRAIN VALVE (TYPICAL)

AHA CONSULTING ENGINEERS

GLYCOL FEEDER SYSTEM, GFS-1, SHALL BE BY BELL AND GOSSETT MODEL GMU60P, OR APPROVED EQUAL.

D DRAIN PAN

HARRISBURG, PA 17102-2499

1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES

1/2"

DRAIN PIPING TRAP MINIMUM 2" HEIGHT

33 SOUTH BROAD STREET

SYSTEM BALL VALVE

LITITZ, PA 17543

GEOTECHNICAL ENGINEER

MUFFLER W/COMPANION FLANGES BY GENERATOR MANUFACTURER, INSTALLED BY HVAC CONTRACTOR.

1 M-503

FOUR PIPE FCU PIPING DETAIL

GENERATOR EXHAUST DETAIL

2

SCALE: N.T.S.

M-503

CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

GLYCOL FEEDER DETAIL (LARGE GLYCOL SYSTEM)

3

SCALE: N.T.S.

M-503

STRUCTURAL ENGINEER WBCM

SCALE: N.T.S.

100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

RISER LAST CONNECTION TEST GLOBE VALVE

1/2"

SET SCREW

PIPE GUIDE

STEAM PITCH DOWN FLOW

BOLT

3/4" BYPASS

STEAM BYPASS GATE VALVE

6" DIRT LEG

TRAP TEE

NIPPLE BLANKED FLANGE

CONDENSATE

PIPE

SPICER

FLOW STRAINER

CHECK VALVE

INVERTED BUCKET TRAP

BUCKET TRAP BLANK FLANGE

UNION

CONDENSATE RETURN

STRAINER BLOW 1/2" BALL VALVE 1/2" NIPPLE

CHANNEL OR BUILDING STRUCTURE

HIGH OR MEDIUM PRESSURE MAIN

4 M-503

HIGH PRESSURE STEAM TRAP DETAIL

HIGH/MED STEAM RISER TAKE-OFF DETAIL

5

SCALE: N.T.S.

M-503

HORIZONTAL & VERTICAL PIPE GUIDE DETAIL

6

SCALE: N.T.S.

M-503

SCALE: N.T.S.

NOTE: INSULATION

D + 1"

4D

INSULATED AS SPECIFIED INSULATION PROTECTION SADDLE WELDED TO PIPE

1. DUCTWORK RUNOUT SIZE TO LINEAR DIFFUSER SHALL MATCH THE INLET SIZE TO PLENUM NOTED ON THE SCHEDULES UNLESS SHOWN OTHERWISE ON FLOOR PLANS.

VOLUME DAMPER TYP 48" MAX. LENGTH OF FLEXIBLE CONNECTION TYP. SEE SPECIFICATION

SEE NOTE 2

PIPE ROLL 6"

INLET CENTERED BOLT (TYP)

INSULATED LOW PRESSURE DUCT PLENUM LINED W/1" SOUND LINING THROUGHOUT

PIPE SADDLE ON HOT WATER

D

INSULATION PROTECTION SHIELD

BRACKET UPPER STACK TO DISCHARGE DUCT SPIN-IN DUCT COLLAR

ANGLE IRON SUPPORT BY HVAC

ARCH. SOFFIT OR CEILING

NOTES:

INSULATED FLEXIBLE DUCT FASTENED WITH BAND CLAMPS, SCREWS ON BOTH SIDES

REFER TO FLOOR PLANS FOR SIZE

1. FOR TYPE OF HANGER AND INSULATION REQUIREMENTS REFER TO SPECIFICATIONS. 2. SERVICE PIPING AS INDICATED IN SPECIFICATIONS SHALL BE INSTALLED ON ROLLER HANGERS.

KEY PLAN

SEE DRAWINGS FOR DIRECTION OF BLOW

A 7 M-503

PIPE HANGER & PIPE ROLLER DETAIL SCALE: N.T.S.

GENERATOR STACKHEAD DETAIL

8 M-503

LINEAR DIFFUSER DETAIL (TYPICAL)

9

SCALE: 1/8" = 1'-0"

M-503

SCALE: N.T.S.

B

REVISION NO. DESCRIPTION

WEATHER-PROOF INSULATION BUILDING STRUCTURE

REFER TO SPECIFICATION FOR PACKING OF SPACE BETWEEN PIPE & SLEEVE

DRAW BAND

DATE

MASTIC PROVIDE A 1" AIR SPACE (MINIMUM) AROUND PIPE.

STEEL PIPE SLEEVE BY HVAC

FLASHING BY HVAC SUB-CONTRACTOR

PIPE 12" MIN.

FLASHING BY GENERAL CONTRACTOR STANDARD WEIGHT STEEL PIPE SLEEVE

SEE NOTES

ROOF MEMBRANE

12/14/2015 11:04:38 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

ESCUTCHEON AROUND ALL PIPE PENETRATIONS, SEE SPECIFICATION

NOTES:

AHA PROJECT NUMBER

THICKNESS VARIES ANCHOR PLATE IMBEDDED IN CONCRETE SLAB OR RESTING ON TOP OF AND TACK WELDED TO METAL DECKING UNDER ROOF INSULATION

PIPE SLEEVE SHALL BE LARGE ENOUGH TO ALLOW PIPE & INSULATION WHERE PIPES ARE COVERED. THEY SHALL ALSO ALLOW EXPANSION & CONTRACTION.

G1215-004.00

3" DATE

03 DECEMBER 2015

NOTES: 1. 2. 3.

ISSUE

WEATHER PROOFING OF INSULATION TO BE EXTENDED BELOW COUNTERFLASHING INSULATION SHALL BE CONTINUOUS THROUGH THE PIPE SLEEVE CONTERFLASHING TO HAVE MINIMUM CLEARANCE BETWEEN ROOF SLEEVE FLASHING & SHALL EXTEND DOWN A MINIMUM OF 3" BELOW TOP SLEEVE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DETAILS 10 M-503

PIPE SLEEVE THROUGH WALL DETAIL SCALE: N.T.S.

11 M-503

PIPE THROUGH ROOF OR WALL DETAIL SCALE: N.T.S.

REVISED 15 DECEMBER 2015

SHEET NO.

M-503

3

A

3

3 A

5

2

1

4

1

5 1A

SYSTEM NO. F-A-5011 F RATING - 3 HR T RATING - 1 HR L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3) L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)

3 4

2 A

SECTION A-A

SYSTEM NO. C-AJ-1008 (FORMERLY SYSTEM NO. 111)

1. FLOOR-CEILING ASSEMBLY - THE FIRE-RATED UNPROTECTED STEEL DECK FLOOR-CEILING ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW: A. NORMAL WEIGHT OR LIGHTWEIGHT CONCRETE - CONCRETE THICKNESS ABOVE THE CREST OF THE DECK SHALL BE MIN. 3-1/4 IN. NORMAL WEIGHT CONCRETE WITH CARBONATE OR SILICEOUS AGGREGATE, 145 TO 155 PCF UNIT WEIGHT, MIN. 3000 PSI COMPRESSIVE STRENGTH. LIGHTWEIGHT CONCRETE WITH EXPANDED SHALE, CLAY OR SLATE AGGREGATE, 105 TO 115 PCF UNIT WEIGHT, MIN. 3000 PSI COMPRESSIVE STRENGTH. B. WELDED WIRE FABRIC - 6x6, W1.4xW1.4 C. STEEL FLOOR AND FORM UNITS*-COMPOSITE OR NONCOMPOSITE 1-5/16 TO 3 IN. DEEP GALV. UNITS OR AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGNS. MAX AREA OF OPENING IS 300 SQ IN. WITH MAX DIMENSION OF 30 IN.

3A A

1B

SECTION A-A

1. FLOOR OR WALL ASSEMBLY - REINFORCED LIGHT WEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE HAVING A MIN THICKNESS AS SPECIFIED IN THE TABLE BELOW (ITEM 3). WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER OF OPENNING IS 8 IN. SEE CONCRETE BLOCK (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. 2. METALIC SLEEVE - (OPTIONAL) - NOM 8 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CAST GROUNTED INTO WALL OR FLOOR ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.

1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM. 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN. 3-5/8 IN. WIDE AND SPACED MAX. 24 IN. OC. B. GYPSUM BOARD* - 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAMETER OF OPENING IS 9 IN. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WLL ASSEMBLY IN WHICH IT IS INSTALLED.

3. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE ANNULAR SPACE SHALL BE AS SPECIFIED IN THE TABLE BELOW. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED. A. STEEL PIPE - NOM 6 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METTALIC TUBING. C. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) RIGID GALV STEEL CONDUIT. THE F AND T RATING OF THE SYSTEM IS DEPENDENT UPON THE DIAM OF THE PIPE OR CONDUIT AND ANNULAR SPACE BETWEEN THE PIPE OR CONDUIT AND THE PERIPHERY OF THE OPENING AS SHOWN IN THE TABLE BELLOW.

2. THROUGH PENETRANTS - ONE METALIC PIPE OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALIC TUBING MAY BE USED. A. STEEL PIPE - NOM. 4 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. IRON PIPE - NOM. 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. C. COPPER TUBING - NOM. 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE. D. COPPER PIPE - NOM. 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

MAX DIAM.

MIN.

OR WALL

OR WALL THCKNS IN.

OF STEEL PIPE OR CONDIUT IN.

ANNULAR SPACE IN.

3-3/4 3-3/4 3-3/4 4-1/2 4-1/2 4-1/2 5-1/2 5-1/2 6-1/2 6-1/2

1-1/2 6 6 1-1/2 6 6 1-1/2 6 1-1/2 6

3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

2-1/8 1 3/4 1 1 2 2-1/8 1 3/4 1 1 2 2-1/8 1 3/4 1 2-1/8 2 1 2

2-3/4 2-3/4 1-3/4 3-1/2 3-1/2 2-1/2 3-1/2 3-1/2 2-1/2 2-1/2

ANNULAR SPACE IN.

2 2 2

MIN. FORMING

F RATING

T RATING

METAL THCKNS IN.

METAL THCKNS IN.

HR

HR

0 0 0

3 3 3

3/4

3

3/4 1 0

5. FILL, VOID OR CAVITY MATERIAL* - CAULK - MIN THICKNESS OF FILL MATERIAL AS SPECIFIED IN THE ABOVE TABLE (ITEM 3) APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF THE WALL. USG INTERIORS INC - TYPE SS *BEARING THE UL CLASSIFICATION MARK

NTS

2. THROUGH PENETRANTS - A MAX OF TWO METALLIC PIPES OR TUBINGS TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUIT OR TUBING MAY BE USED: A. STEEL PIPE - NOM. 6 IN. DIAMETER (0R SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE WITH 1 IN. MINERAL FIBER PIPE INSULATION. B. STEEL PIPE - NOM. 4 IN. DIAMETER (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE WITH 1 IN. GLASS FIBER OR MINERAL FIBER PIPE INSULATION. C. COPPER PIPE - NOM. 4 IN. DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE WITH 1 IN. MINERAL FIBER PIPE INSULATION. D. COPPER TUBING - NOM. 4 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER PIPE WITH 1 IN. MINERAL FIBER PIPE INSULATION. E. COPPER PIPE - NOM. 2 IN. DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE WITH 1 IN. GLASS FIBER PIPE INSULATION. F. COPPER TUBING - NOM. 2 IN. DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING WITH 1 IN. GLASS FIBER PIPE INSULATION. 3. PIPE COVERINGS - ONE OF THE FOLLOWING TYPES OF PIPE COVERINGS MAY BE USED: A. PIPE AND EQUIPMENT COVERING MATERIALS* - NOM. 1 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. THE ANNULAR SPACE WITHIN THE FIRESTOP SYSTEM SHALL BE MIN. 7/8 IN. TO MAX 15-1/2 IN. SEE PIPE AND EQUIPMENT COVERING MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED. B. PIPE COVERING MATERIALS* - NOM. 1 IN. THICK UNFACED MINERAL FIBER PIPE INSULATION HAVING A NOM. DENSITY OF 3.5 PCF (OR HEAVIER) AND SIZED TO THE OUTSIDE DIAM. OF THE PIPE OR TUBE. PIPE INSUALTION SECURED WITH A MIN. 8 AWG STEEL WIRE SPACED MAX 12 IN. OC. THE ANNULAR SPACEWITHIN THE FIRESTOP SYSTEM SHALL BE MIN. 7/8 IN. TO MAX 15-1/2 IN. OWENS CORNING HT INC, DIVISION OF OWENS CORNING - HIGH TEMPERATURE PIPE INSULATION 1200, HIGH TEMPERATURE PIPE INSULATION BWT OR HIGH TEMPERATURE PIPE INSULATION THERMALOC L RATINGS NOT APPLICABLE WHEN MINERAL WOOL PIPE COVERING MATERIAL IS USED. C. SHEATHING MATERIAL*-(OPTIONAL)-USED IN CONJUNCTION WITH ITEM 3B. FOIL-SCRIM-KRAFT OR ALL SERVICE JACKET MATERIAL SHALL BE WRAPPED AROUND THE OUTER CIRCUMFERENCE OF THE PIPE INSULATION (ITEM 3B) WITH THE KRAFT SIDE EXPOSED. LONGITUDINAL JOINTS AND TRANSVERSE JOINTS SEALED WITH MATCHING FOIL-SCRIM-KRAFT TAPE. (SEE SHEATHING MATERIALS (BVDV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY SHEATHING MATERIAL MEETING THE ABOVE SPECIFICATION AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.

0 3

HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

2 A 2

A

ASSOCIATE ARCHITECT

1B

MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET

SECTION A-A

SECTION A-A

HARRISBURG, PA 17102-2499

1. WALL ASSEMBLY - THE 1, 2, 3, OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING CONSISTS OF STEEL CHANNEL STUDS. STEEL STUDS TO BE MIN. 3-5/8 IN. WIDE BY 1-3.8 IN. DEEP CHANNELS SPACED MAX. 24 IN. OC. B. GYPSUM BOARD* - NOM. 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OT TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAMETER OF OPENING IS 13-1/2 IN. 2. PIPE OR CONDUIT - NOM. 12 IN. DIAMETER (OR SMALLER) SCHEDULE 10 OR (OR HEAVIER) STEEL PIPE, NOM. 12 IN. DIAMETER (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN. DIAMETER (OR SMALLER) CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE, NOM. 6 IN. DIAMETER (OR SMALLER) STEEL CONDUIT, NOM. 4 IN. DIAMETER (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING, NOM. 6 IN. DIAMETER (OR SAMLLER) TYPE L (OR HEAVIER) COPPER TUBING OR NOM. 1 IN. DIAMETER (OR SMALLER) FLEXIBLE STEEL CONDUIT. WHEN COPPER PIPE IS USED, MAX F RATING OF FIRESTOP SYSTEM (ITEM 3) IS 3 HR. STEEL PIPES OR CONDUITS LARGER THAN NOM. 4 IN. DIAMETER MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL CHANNEL STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 3. FILL, VOID, OR CAVITY MATERIAL*-CAULK- CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN. 1/4 IN. DIAMETER BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM THE WALL. CAULK INSTALLED SYMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:

1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL ALSO MAY BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIM OF OPENING IS 8 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES AND MANUFACTURERS.

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

2. METALLIC PIPE - MAX 6 IN. DIAM (OR SMALLER) RIGID GALV STEEL CONDUIT, SCHEDULE 10 (OR HEAVIER) STEEL PIPE OR MAX 4 IN. DIAM (OR SMALLER) STEEL EMT CONDUIT CENTERED IN THE OPENING. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE T RATING OF THE SYSTEM IS DEPENDENT ON THE SIZE OF THE CONDUIT AND THROUGH OPENING AS SHOWN IN THE TABLE BELOW. (SEE ITEM 5)

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

3. FORMS - (NOT SHOWN, OPTIONAL) - USED AS A FORM TO PREVENT LEAKAGE OF FILL MATERIAL DURING INSTALLATION. FORMS TO BE A RIGID SHEET MATERIAL, CUT TO FIT THE CONTOUR OF THE PENETRATING ITEM. FORMS FRICTION FITTED INTO THE OPENING OR LOCATED ON THE UNDERSIDE OF FLOOR ON BOTH SIDES OF WALL TO PREVENT THE LEAKAGE OF FILL MATERIAL. THE FORMS TO BE REMOVED AFTER THE FILL MATERIAL HAS CURED.

LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

4. PACKING MATERIAL - (NOT SHOWN, OPTIONAL) - MINERAL WOOL BATT INSULATION FIRMLY PACKED BETWEEN THE FORMS AND PENETRATING ITEMS TO PREVENT THE LEAKAGE OF FILL MATERIAL. THE PACKING MATERIAL MAY BE REMOVED AFTER THE FILL MATERIAL HAS CURED.

2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

5. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. THE T RATING OF THE SYSTEM IS DEPENDENT UPON THE SIZE OF THE OPENING, SIZE OF THE PENETRATING ITEM, NOM ANNULAR SPACE WITHIN OPENING AND THICKNESS OF THE FILL MATERIAL AS SHOWN IN THE TABLE BELOW:

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108

NTS

PIPE PENETRATION OF FIRE RATED FLOOR

MECHANICSBURG, PA 17050 MAX OPENING SIZE IN.

MAX PIPE OR CONDUIT DIAM., IN.

4. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING: A. FORMS-(NOT SHOWN) USED AS A FORM TO PREVENT LEAKAGE OF FILL MATERIAL DURING INSTALLATION. FORMS TO BE RIGID SHEET MATERIAL, CUT TO FIT THE CONTOUR OF THE PENETRATING ITEM AND FASTENED TO THE UNDERSIDE OF FLOOR. FORMS TO BE REMOVED AFTER FILL MATERIAL HAS CURED. B. FILL, VOID, OR CAVITY MATERIAL*-MORTAR-MIN. 3-1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP OF SURFACE FLOOR. MORTAR IS TO BE MIXED WITH WATER AT A RATE OF 1.9 TO 2.4 GAL. PER 25 LB. BAG IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ANNULAR SPACE IN.

F RATING HR.

T RATING HR.

1

0 TO 3/16

1 OR 2

1

1/4 TO 1/2

3 OR 4

4

0 TO 1-1/2

1 OR 2

0

6

1/4 TO 1/2

3 OR 4

0

12

3/16 TO 3/8

1 OR 2

0

0+, 1 OR 2 3 OR 4

NTS

PIPE PENETRATION OF FIRE RATED WALL

MAX DIAM. PENETRATION ITEM IN.

NOM ANNULAR SPACE IN.

MIN FILL MTL. THK. IN.

T RATING HR

3

1-1/2

9/16

4-1/2

1-1/2

5

3

3/4

4-1/2

1/2

5

1/2

2

3-1/2

3

8

6

11/16

3-1/2

0

8

6

11/16

4-1/2

1/2

*BEARING THE UL CLASSIFICATION MARK THIS DETAIL SHALL BE USED FOR ALL PENETRATIONS OF MECHANICAL ROOM 110A AND PENETRATIONS OF OTHER 2 HOUR SEPARATIONS.

*BEARING THE UL CLASSIFICATION MARK

*BEARING THE UL CLASSIFICATION MARK

CONDUIT/STEEL PIPE PENETRATION OF CONCRETE WALL/FLOOR

ARCHITECT

1

SEE ARCHITECTURAL DRAWINGS FOR FIRE RATING OF WALLS.

0 0

3 3

MIN. FILL

4. FORMING MATERIAL* - MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM AT THE MIN THICKNESS SPECIFIED IN THE ABOVE TABLE (ITEM 3). FORMING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. THERMAFIBER LLC - TYPE SAF

*BEARING THE UL CLASSIFICATION MARK

INSULATED PIPE PENETRATION OF FIRE RATED WALL

MIN. FLOOR

F F F F F F W W W W

3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING. A. PIPE AND EQUIPMENT COVERING MATERIALS* - MAX 2 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH MEATL FASTENERS OR FACTORY APPLIED SELFSEALLING LAP TAPE. PIPE COVERING TO BE WRAPPED AROUND THE THROUGH PENETRANT AND EXTEND A MIN 2-1/2 IN. BEYOND BOTH SURFACES OF THE WALL. THE ANNULAR SPACE BETWEEN PIPE COVERING AND THE EDGE OF THE THROUGH OPENING SHALL BE MIN. 0 IN. (CONTINUOUS POINT CONTACT) TO MAX 1/2 IN. SEE PIPE AND EQUIPMENT COVERING MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVEING MATERIAL MEETING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED. B. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. THICKNESS MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. A MIN 1/4 IN. CROWN OF FILL MATERIAL SHALL BE APPLIED TO THE PIPE COVERING/GYPSUM WALLBOARD INTERFACE AT THE POINT CONTACT LOCATION ABD LAPPING 1/4 IN. BEYIND THE PERIPHERY OF THE OPPENING ON BOTH SIDES OF THE WALL. SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, 101, 102 AND 105 SEALANT.

MAX.

FLOOR

5

A

F RATING - 3 HR T RATINGS - 0,1/2,1 1/2 AND 3 HR (SEE ITEM 5)

SYSTEM NO. C-AJ-1020 (FORMERLY SYSTEM NO. 165) F RATING - 2 AND 3 HR (SEE ITEM 3) T RATING - 0, 3/4, AND 1 HR (SEE ITEM 3) L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT L RATING AT 400 F - LESS THAN 1 CFM/SQ FT

2

5

UL DETAIL

3

SECTION A-A 3B

M-504

3

A 2

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

A A

1

1A

F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3) T RATINGS - 0,1,2,3 AND 4 HR (SEE ITEM 3) L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT L RATING AT 400 F - LESS THAN 1 CFM/SQ FT

2

System No. W-L-1101 F Rating - 1&2 Hr (See Item 1) T Rating - 0 Hr

SYSTEM NO. W-L-1001 (FORMERLY SYSTEM NO. 147)

NTS

CONDUIT/STEEL PIPE PENETRATION OF CONCRETE WALL/FLOOR

NTS

UL DETAILS SCALE: N.T.S.

DUCT SUPPORT 3/8" FOAM GASKET FLEX CONNECTOR SOUND BARRIER PACKAGE (SEE NOTE 8)

1 1/2" / 3# F.G BOARD AT TOP RAIL

NOTE: 1. ROOF CURB SHALL BE FULLY ASSEMBLED AND SHIPPED IN ONE PIECE. MODEL VIBCURB AS MANUFACTURED BY NAI (NOVIA ASSOCIATES, INC.) OR APPROVED EQUAL.

TOP RAIL AND FLASHING 14 Ga. - Zc.

2. HVAC CONTRACTOR SHALL COORDINATE AND FIELD VERIFY FINAL LOCATIONS OF HVAC UNITS AND DUCT RISERS WITH GENERAL CONTRACTOR BASED ON ACTUAL STRUCTURAL, ARCHITECTURAL, UNIT, CURB SIZES AND CONNECTION CONDITIONS.

AIR / WEATHER SEAL BOTTOM FLASHING

3. FIELD COORDINATE AND VERIFY FINAL STRUCTURAL STEEL LAYOUT FOR RTU SUPPORT WITH GENERAL CONTRACTOR, HVAC CONTRACTOR & CURB SUPPLIER BASED ON FINAL APPROVED RTU AND CURB SUBMITTALS. 4. ROOFING MEMBRANE SHALL BE EXTENDED TO THE TOP OF THE SHEET METAL SIDES AND ENDS OF CURB BY THE GENERAL CONTRACTOR. 5. CURB MANUFACTURER SHALL CONSTRUCT THE SHEET METAL SIDES AND ENDS OF CURBS TO CONTINUOUSLY CONFORM WITH ROOF SLOPE. POINT LOADING IS NOT ACCEPTABLE.

WOOD NAILERS SIDES AND ENDS 12 Ga. - ZC. 3 1/2" R-21 .7 FACED FOAM BOARD 2 LAYERS 1/2" DUROCK (SEE NOTE 8)

6. THE 14" HIGH CURB SHALL BE PROVIDED BY THE HVAC SUB-CONTRACTOR AND SHALL BE FASTENED TO THE ROOF AND UNIT. THE CURB SHALL NOT INTERFERE WITH THE OPERATING CHARACTERISTICS OF THE UNIT. ALL FLASHING AND COUNTERFLASHING BY ROOF CURB MANUFACTURER. 7. THE ENTIRE FLOOR AREA (ROOF DECK) WITHIN THE ROOF CURB SHALL HAVE ONE LAYER OF 2" - 3# DENSITY RIGID BOARD FIBERGLASS INSULATION AND TWO LAYERS OF 1/2" DUROCK BOARD ON TOP OF THE INSULATION. THE THREE LAYERS SHALL BE FASTENED TO THE ROOF. PROVIDE ONE ADDITIONAL LAYER OF 1/2" DUROCK BOARD AT TOP FLOATING RAIL OF CURB. HVAC CONTRACTOR SHALL BE REQUIRED TO PROVIDE ALL LAYERS PRIOR TO PLACING ROOFTOP UNITS ON CURBS. PROTECT ALL LAYERS FROM THE WEATHER UNTIL UNIT IS INSTALLED. OFFSET SEAMS WHEN INSTALLING BOARDS. SEAL ALL JOINTS.

2" - 3# FIBERGLASS BOARD (SEE NITE 8) ROOFING MEMBRANE * CANT STRIP *

ROOF INSULATION *

* MATERIALS FURNISHED AND INSTALLED BY GENERAL CONTRACTOR ** MATERIALS FURNISHED AND INSTALLED BY GENERAL CONTRACTOR

METAL DECK **

2 M-504

ERU CURB DETAIL SCALE: N.T.S. KEY PLAN

A

B

REVISION NO. DESCRIPTION

DATE

AHA PROJECT NUMBER

12/14/2015 11:04:40 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC DETAILS

REVISED 15 DECEMBER 2015

SHEET NO.

M-504

AHU

AIR HANDLING UNIT CFM SYMBOL

AHU-G-1 AHU-G-2 AHU-G-3 AHU-1-1 AHU-1-2

SERVICE

LOCATION

KITCHEN DINING BOOKSTORE COMMON MAIL ROOM

GROUND FL GROUND FL GROUND FL FIRST FL FIRST FL

SELECTION BASED ON:

SUPPLY FAN WITH VFD

TYPE

SINGLE ZONE-VAV SINGLE ZONE-VAV SINGLE ZONE-VAV MULTI ZONE-VAV SINGLE ZONE-VAV

EXHAUST FAN WITH VFD

HOT WATER PRE-HEAT COIL

CHILLED WATER COIL

TOTAL

OA

CFM

ESP

TOT. S.P.

FAN RPM

BHP

MOTOR HP

CFM

ESP

TOT. S.P.

FAN RPM

BHP

MOTOR HP

EAT

LAT

GPM

WPD FT

APD IN

EWT

LWT

9,000 16,000 12,000 9,500 2,400

1,000 5,100 2,500 1,400 300

9,000 16,000 12,000 9,500 2,400

1.0 1.0 1.0 1.5 0.5

2.51 2.60 2.43 3.29 1.16

1,966 1,110 1,237 1,503 -

7.04 12.09 8.68 9.10 0.88

7.5 15.0 10.0 10.0 1.0

9,000 16,000 12,000 9,500 -

0.5 0.5 0.5 0.5 -

0.83 0.80 0.76 0.79 -

2,036 1,745 1,350 1,127 -

7.02 13.69 6.48 3.88 -

7.5 15.0 7.5 5.0 -

20.0 -

59.3 -

21.5 -

10.9 -

0.05 -

180 -

140 -

EAT DB WB 76.2 79.0 77.0 76.2 75.0

LAT

66.8 68.0 66.0 63.8 65.0

DB

WB

56.5 56.5 56.8 52.3 57.6

56.1 56.1 56.5 52.1 57.4

HOT WATER RE-HEAT COIL

FILTERS

MOTORS REMARKS

GPM

WPD FT

APD IN

EWT

LWT

EAT

LAT

GPM

WPD FT

APD IN

EWT

LWT

EFF.

V

P

Hz

65.0 129.5 76.6 69.7 12.2

14.6 18.7 6.7 18.7 8.05

0.82 0.70 0.61 0.87 -

44 44 44 44 45

54 54 54 54 55

55 55 55 70

98.7 95.0 96.4 94.2

22.7 37.0 28.7 3.4

10.9 0.9 0.4 4.11

0.11 0.09 0.13 -

180 180 180 180

140 140 140 140

MERV 8 MERV 8 MERV 8 MERV 8 MERV 8

460 460 460 460 460

3 3 3 3 3

60 60 60 60 60

1 1 1 1 1

2 2 2 2 2

3 3 3 3 3

4 4 4 4 4

ARCHITECT

5 5 5

HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

5

ASSOCIATE ARCHITECT

JCI/YORK

MURRAY AND ASSOCIATES ARCHITECTS

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT. 2. PROVIDE ALL COILS WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER. 3. PROVIDE WITH WATER LEVEL DETECTION DEVICE FOR CONDENSATE OVERFLOW. 4. CHILLED WATER AND HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL. 5. PROVIDE WALL MOUNTED BAS TEMPERATURE AND HUMIDITY SENSORS (ONE EACH) AS SHOWN ON FLOOR PLANS FOR SUPPLY AIR TEMPERATURE AND HUMIDITY CONTROL.

1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

ERU-1 ERU-2

SERVICE

LOCATION

AREA A AREA B

ROOF ROOF

SELECTION BASED ON:

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

SUPPLY FAN WITH VFD SYMBOL

SITE/CIVIL ENGINEER

ERU

ENERGY RECOVERY UNIT (100% OA) EXHAUST FAN WITH VFD

CFM

ESP

TOT. S.P.

FAN RPM

7,800 11,775

2.0 2.0

4.64 4.99

1,922 10.43 1,865 17.08

BHP

ENERGY RECOVERY WHEEL

MOTOR HP

CFM

ESP

TOT. S.P.

FAN RPM

BHP

15.0 20.0

5,000 7,650

2.0 2.0

3.18 3.29

2,154 1,050

8.72 9.45

MOTOR OUTSIDE AIR HP DB WB 10.0 15.0

90.8 90.8

EXHAUST AIR DB WB

72.8 72.8

75 75

MBH COOLING TOTAL SENS.

BASE EFF.%

63 63

HOT WATER PRE-HEAT COIL

76.3 74.2

137.8 204.6

CHILLED WATER COIL

MBH HEATING

EAT

LAT

GPM

WPD FT

APD IN

EWT

LWT

370.9 550.4

4.5 4.5

39.9 38.6

17.7 25.8

4.6 11.1

0.03 0.04

180 180

140 140

-

EAT DB WB 82.2 82.2

LAT

68.0 68.0

DB

WB

54.0 53.4

53.9 53.2

HOT WATER RE-HEAT COIL

FILTERS

MOTORS

LITITZ, PA 17543

REMARKS

GPM

WPD FT

APD IN

EWT

LWT

EAT

LAT

GPM

WPD FT

APD IN

EWT

LWT

EFF.

V

P

Hz

70.5 109.7

12.3 13.7

0.56 0.74

44 44

54 54

35.0 35.0

76.5 75.4

19.5 28.7

5.5 13.6

0.04 0.05

180 180

140 140

MERV 8 MERV 8

460 460

3 3

60 60

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

1 2 3 4 5 6 7 1 2 3 4 5 6 7

2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

JCI/YORK

STRUCTURAL ENGINEER

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT. 2. PROVIDE ALL COILS WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER. 3. PROVIDE WITH WATER LEVEL DETECTION DEVICE FOR CONDENSATE OVERFLOW. 4. CHILLED WATER AND HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL. 5. PROVIDE FACTORY INSULATED ROOF CURB. 6. PROVIDE WALL MOUNTED TEMPERATURE AND HUMIDITY SENSORS (ONE EACH) ON EACH FLOOR AS SHOWN ON FLOOR PLANS FOR SUPPLY AIR TEMPERATURE AND HUMIDITY CONTROL. 7. PROVIDE BYPASS DAMPERS ON ENERGY RECOVERY WHEEL.

MAU-G-1

SUPPLY FAN WITH VFD

LOCATION

KITCHEN

GROUND FL

SELECTION BASED ON:

MECHANICSBURG, PA 17050

TOTAL

OA

CFM

ESP

TOT. S.P.

3,350

3,350

3,350

1.0

1.23

HOT WATER PRE-HEAT COIL

FAN RPM

MOTOR BHP HP

1,135

1.95

EAT

LAT

GPM

WPD FT

3

75

16.4

5.4

3.0

FILTERS

STEAM CONDENSATE PUMPS PUMP

MOTORS REMARKS

APD IN

EWT

LWT

EFF.

V

P

Hz

0.08

180

140

MERV 8

460

3

60

1 2 3 4 5

GREENHECK

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT. 2. PROVIDE ALL COILS WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER. 3. HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL. 4. PROVIDE A VFD WITH MAIN DISCONNECT SWITCH, 3 CONTACTOR BYPASS, 120V FUSED CONTROL TRANSFORMER, POWER/CONTROL WIRING, AND TERMINAL STRIP FOR FIELD CONTROL WIRING. 5. INTERFACE CONTROLS WITH BAS.

EXHAUST FAN WITH VFD SERVICE

LOCATION CFM

KEF-G-1

KITCHEN

GROUND FL

SELECTION BASED ON:

ESP

5,805

4.25

TOT. S.P.

FAN RPM

BHP

4.6

2,310

6.47

PRE-FILTERS

MAIN-FILTERS

FINAL-FILTERS

CH-1

400

EVAP

COND

ENT

LVG

GPM

PD FT

EFF.

10.0

30%, MERV 8

0.00010

0.00025

52

42

956

15.0

SELECTION BASED ON:

CONDENSER WATER

DEPTH

EFF.

4"

DEPTH

95%, MERV 14

22"

EFF.

DEPTH

95%, MERV 16

V

12"

P

ENT

LVG

GPM

COMPRESSOR DATA PD FT QTY VOLT. KW PH

85

95

1,127

17.8

460

1

460

3

LBS. OF REFRIGERANT REFRIGERATION TYPE

3

CT-1

SERIES 3000

MAIL ROOM ROOF

SELECTION BASED ON:

DB(ºF) WB(ºF) 85.0

75.8

1,200

228

1,334

85.0

TEMPLATE VERSION: 2.6.8.20141012

12/14/2015 11:04:43 PM

DD-12

-

-

-

-

324

80

-

CENTRAL PLANT

PT3508

-

-

-

-

324

80

-

CENTRAL PLANT

PT3508

-

-

-

-

324

80

-

ARMSTRONG

HXS

R-134A

0.571

0.363

1

20.0

98,800

2

SYMBOL

SERVICE

LOCATION

HXS-1

HEATING HOT WATER

HXS-2

HEATING HOT WATER

PPH

INLET TEMP

CENTRAL PLANT

9,400

324

CENTRAL PLANT

9,400

324

35% GLYCOL SIDE EWT

LWT

GPM

PD (FT)

MODEL NUMBER

80

140

180

450

1.8

WS-12

1 2

80

140

180

450

1.8

WS-12

1 2

INLET PRESS

REMARKS

ARMSTRONG

REMARKS: 1. ASME CERTIFIED. 2. HEAT EXCHANGER, RECEIVER, STEAM TRAP, AND PUMP PACKAGE SHALL BE PROVIDED BY THE SAME MANUFACTURER AND SKID MOUNTED.

FINNED TUBE RADIATION (WATER) SYMBOL

MOUNTING

LENGTH

FTR-A

PEDISTAL

48"

SELECTION BASED ON: 1. 2.

1 2 3 4 5

ELECTRICAL CONTROL OPTIONS

WEIGHT

VFD

18,330

9.0

V

PH

460

3

REMARKS 1 2 3 4 5 6 7 8 9 10

OUTPUT (BTU) PER LINEAR FOOT 638

FTR AWT

EAT

160

65

GPM

WTD/FT

FINS/FT

FPS

REMARKS

5

0.25

50

3

1 2

MODINE MODEL PA

PROVIDE WITH DOUBLE POLE THERMOSTAT. THERMAL LIMIT SWITCH.

BT

SYMBOL

SERVES

LOCATION

BT-1

CHILED WATER SYSTEM

CENTRAL PLANT

SELECTION BASED ON:

TANK

TANK

TANK

TANK

VOLUME

DIAMETER

HEIGHT

WEIGHT

2500

84

138

5,340

REMARKS 1 2 3

TACO BTH

REMARKS: 1. MOUNT ON CONCRETE HOUSEKEEPING PAD. REFER TO STRUCTURAL DOCUMENTS. 2. TANK SHALL BE INSULATED PER SPECIFICATIONS. 3. TANK SHALL BE ASME CERTIFIED.

BALTIMORE AIRCOIL

HEAT EXCHANGERS - PLATE & FRAME

HEAD FT.

NPSHR

BHP

MOTOR HP

9.375

14.3

21.12

25.0

END SUCTION

9.375

14.3

21.12

75

END SUCTION

9.375

14.3

100

END SUCTION 10.875

9.4

SYMBOL

SERVES

GPM

TYPE

PCHWP-1

PRIMARY CHW

960

75

END SUCTION

PCHWP-2

PRIMARY CHW

960

75

PCHWP-3 (FUTURE)

PRIMARY CHW

960

SCHWP-1

SECONDARY CHW

960

IMP. DIA.

MOTOR RPM

V

PH

EMERGENCY POWER

1,770

460

3

N

1 2 3 4 5

25.0

1,770

460

3

N

1 2 3 4 5

21.12

25.0

1,770

460

3

N

1 2 3 4 5

30.69

40.0

1,770

460

3

N

1 2 3 4 5

REMARKS

SCHWP-2

SECONDARY CHW

960

100

END SUCTION 10.875

9.4

30.69

40.0

1,770

460

3

N

1 2 3 4 5

HWP-1

HOT WATER

450

75

END SUCTION

9.125

7.2

10.39

15.0

1,770

460

3

Y

1 2 3 4 5

HWP-2

HOT WATER

450

75

END SUCTION

9.125

7.2

10.39

15.0

1,770

460

3

Y

1 2 3 4 5

CWP-1

CONDENSER WATER

1,200

75

END SUCTION

9.25

12.1

28.87

40.0

1,770

460

3

N

1 2 3 4 5

CWP-2

CONDENSER WATER

1,200

75

END SUCTION

9.25

12.1

28.87

40.0

1,770

460

3

N

1 2 3 4 5

CWP-3 (FUTURE)

CONDENSER WATER

1,200

75

END SUCTION

9.25

12.1

28.87

40.0

1,770

460

3

N

1 2 3 4 5

BELL & GOSSETT

REMARKS: 1. PROVIDE A VFD WITH MAIN DISCONNECT SWITCH, 3 CONTACTOR BYPASS, 120V FUSED CONTROL TRANSFORMER, POWER/CONTROL WIRING, TERMINAL STRIP FOR FIELD CONTROL WIRING AND INTERFACE TO SIEMENS DEMAND FLOW CONTROLLER. 2. INVERTER DUTY MOTOR. 3. MOUNT ON CONCRETE HOUSEKEEPING PAD. REFER TO STRUCTURAL DOCUMENTS. 4. SUCTION DIFFUSER WITH INTEGRAL STRAINER. 5. DDC CONTROL TO INTERFACE WITH BAS.

KEY PLAN

HX

SYMBOL

MODEL/ SERIES

SERVES

LOCATION

EWT (ºF)

HEX-1 HEX-2

A/S PHE A/S PHE

PRIMARY ECONOMIZER SECONDARY CHW

CENTRAL PLANT CENTRAL PLANT

52 54

SELECTION BASED ON:

PUMPS

PLOT DATE:

CENTRAL PLANT

SELECTION BASED ON:

REMARKS: 1. INVERTER CAPABLE, PREMIUM EFFICIENT FAN MOTORS. 2. 3-PROBE ELECRONIC WATER LEVEL CONTROL PACKAGE. 3. ELECTRIC HEATERS W/CONTACTOR FOR HEATER PACKAGE. 4. SUMP SWEEPER PIPING. 5. VIBRATION CUTOUT SWITCH. 6. 304 STAINLESS STEEL COLD WATER BASIN WITH STRAINER. 7. LADDER AND RAILING SYTEM PROVIDED BY MANUFACTURER. 8. DDC CONTROLER WITH BAS INTERFACE. 9. LOW SOUND FAN. 10. PROVIDE VIBRATION ISOLATORS AT EACH CONNECTION TO STEEL SUPPORT.

SELECTION BASED ON:

-

REMARKS

BUFFER TANK

FAN DATA HEATER DATA MOTOR HP # KW EWT (ºF) LWT (ºF) # FANS CFM EA HEATERS EA EA 95.0

80

SCP-4

1 2 3 4 5 6 7 8 9 10 11 12

60

100% DUTY IPLV KW/TON KW/TON REMARKS

WATER

GPM

324

PRESS

STEAM SIDE

CT OUTDOOR AIR

-

SCP-3

Hz

COOLING TOWERS LOCATION

-

TEMP

SHELL AND TUBE HEAT EXCHANGER

REMARKS: 1. VARIABLE SPEED DRIVE. 2. PROVIDE TOUCH SCREEN INTERFACE. 3. PROVIDE INTERFAC TO BAS. 4. MOUNT ON HOUSEKEEPING PAD WITH NEOPRENE MOUNTS. REFER TO STRUCTURAL DOCUMENTS FOR HOUSEKEEPING PAD. 5. SELECTION BASED ON 0% GLYCOL.

MODEL/ SERIES

-

PPH

REMARKS: 1. HEAT EXCHANGER, RECEIVER, STEAM TRAP, AND PUMP PACKAGE SHALL BE PROVIDED BY THE SAME MANUFACTURER AND SKID MOUNTED.

JCI/YORK MODEL YMC2

SYMBOL

-

SCP-2

CH

CHILLED WATER

DD-12

CENTRAL PLANT

GREENHECK TRIPLE PLAY KITCHEN EXHAUST SYSTEM

FOULING FACTOR

EDR

SCP-1

MOTORS

CENTRIFUGAL LIQUID CHILLER TONS

GPM

MODEL

REMARKS

MOTOR HP

STEAM

DISCHARGE PRESSURE

LOCATION

SELECTION BASED ON:

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT. 2. PROVIDE WITH BONDED ACTIVATED CARBON PANELS AFTER FINAL FILTERS. 3. UNIT SHALL BE ETL LISTED TO UL-710. 4. FAN SHALL BE UL-762 LISTED. 5. FILTERS SHALL BE SEALED AGAINST AIR BYPASS. 6. PROVIDE WITH REMOTE FILTER STATUS INDICATOR FOR PRE, MAIN, AND FINAL FILTERS. 7. PRE-FILTERS SHALL BE PLEATED FILTERS. 8. MAIN- FILTERS SHALL BE BAG FILTERS. 9. FINAL FILTER SHALL BE RIGID FILTERS. 10. FACTORY PIPED ANSUL SYSTEM. ANSUL TANKS AND CONTROLS SHALL BE FIELD INSTALLED. 11. PROVIDE A VFD WITH MAIN DISCONNECT SWITCH, 3 CONTACTOR BYPASS, 120V FUSED CONTROL TRANSFORMER, POWER/CONTROL WIRING, TERMINAL STRIP FOR FIELD CONTROL WIRING. 12. INTERFACE CONTROLS WITH BAS.

SYMBOL

SYMBOL

KEF

KITCHEN EXHAUST FAN WITH SCRUBBER SYMBOL

SCP

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

CFM SERVICE

100 STERLING PARKWAY, SUITE 108

MAU

KITCHEN MAKEUP AIR UNIT SYMBOL

WBCM

HOT SIDE LWT GPM (ºF) 42 44

960 960

WATER PD (PSI)

EWT (ºF)

6.64 10.05

40 42

COLD SIDE LWT GPM WATER PD (ºF) (PSI) 48 52

1,200 960

OPERATING WEIGHT

10.05 8.96

8,893 8,313

REMARKS

A 1 2 1 3

SONDEX

B

REMARKS: 1. MOUNT ON CONCRETE HOUSEKEEPING. REFER TO STRUCTURAL DOCUMENTS. 2. HEAT EXCHANGER FRAME SHALL HAVE AN EXTRA PLATE CAPACITY OF 200%. 3. HEAT EXCHANGER FRAME SHALL HAVE AN EXTRA PLATE CAPACITY OF 50%.

REVISION NO. DESCRIPTION

EXPANSION TANK & AIR SEPARATOR

ET & AS

TANK/ACCEP.

TANK

AIR SEPARATOR

MAX. CAP.

AIR SEPARATOR

VOLUME

DIMENSIONS

MODEL NO.

GPM

DIMENSIONS

SYMBOL

SERVES

ET-1/AS-1

PRIMARY CHW

53

24"Ø X 37"H

RL-12

4,800

-

1 2 3

ET-2/AS-2

SECONDARY CHW

792

48"Ø X 119"H

RL-8

1,900

-

1 2 3

ET-3/AS-3

HEATING HOT WATER

528

48"Ø X 84"H

RL-5

530

-

1 2 3

SELECTION BASED ON:

DATE

REMARKS

BELL AND GOSSETT

REMARKS: 1. MOUNT ON CONCRETE HOUSEKEEPING PAD. REFER TO STRUCTURAL DOCUMENTS. 2. EXPANSION TANK SHALL BE ASME CERTIFIED. 3. EXPANSION TANK SHALL HAVE A PRE-CHARGED BLADDER. AHA PROJECT NUMBER

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC SCHEDULES

REVISED 15 DECEMBER 2015

SHEET NO.

M-601

VRF - DUCTLESS SPLIT SYSTEMS - INDOOR UNITS

DIFFUSERS, REGISTERS & GRILLES

COOLING SYMBOL

MODEL

TYPE

CFM

ELECTRICAL

SERVED BY

SERVES

DSS-A-1 DSS-A-2 DSS-A-3 DSS-A-4 DSS-A-5 DSS-A-6 DSS-A-7 DSS-A-8 DSS-A-9 DSS-A-10

CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A

GND FL IDF 1ST FL IDF 2ND FL IDF 2ND FL ELEC 3RD FL IDF 4TH FL IDF 4TH FL ELEC 5TH FL IDF 6TH FL IDF 6TH FL ELEC

FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU FXAQ18PVJU FXAQ24PVJU FXAQ24PVJU FXAQ07PVJU FXAQ24PVJU FXAQ24PVJU FXAQ07PVJU

WALL WALL WALL WALL WALL WALL WALL WALL WALL WALL

635 635 635 500 635 635 260 635 635 260

24.0 24.0 24.0 18.0 24.0 24.0 7.5 24.0 24.0 7.5

18.0 18.0 18.0 13.7 18.0 18.0 6.4 18.0 18.0 6.4

208 208 208 208 208 208 208 208 208 208

1 1 1 1 1 1 1 1 1 1

Y Y Y Y Y Y Y Y Y Y

1 1 1 1 1 1 1 1 1 1

DSS-B-1 DSS-B-2 DSS-B-3 DSS-B-4 DSS-B-5 DSS-B-6 DSS-B-7 DSS-B-8 DSS-B-9 DSS-B-10 DSS-B-11 DSS-B-12

CU-B CU-B

GND FL IDF GND FL ELEC

FXAQ24PVJU FXAQ12PVJU

WALL WALL

635 290

24.0 12.0

18.0 8.9

208 208

1 1

Y Y

1 2 3 4 5 6 7 1 2 3 4 5 6 7

CU-B CU-B CU-B CU-B CU-B CU-B CU-B CU-B CU-B CU-B

1ST FL MDF 1ST FL IDF 2ND FL ELEC 2ND FL IDF 3RD FL IDF 4TH FL ELEC 4TH FL IDF 5TH FL IDF 6TH FL ELEC 6TH FL IDF

FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU FXAQ18PVJU FXAQ24PVJU FXAQ24PVJU FXAQ18PVJU FXAQ24PVJU

WALL WALL WALL WALL WALL WALL WALL WALL WALL WALL

635 635 635 635 635 500 635 635 500 635

24.0 24.0 24.0 24.0 24.0 18.0 24.0 24.0 18.0 24.0

18.0 18.0 18.0 18.0 18.0 13.7 18.0 18.0 13.7 18.0

208 208 208 208 208 208 208 208 208 208

1 1 1 1 1 1 1 1 1 1

Y Y Y Y Y Y Y Y Y Y

1 1 1 1 1 1 1 1 1 1

TOT. MBH SENS. MBH

V

EMERGENCY REMARKS POWER

PH

2 2 2 2 2 2 2 2 2 2

2 2 2 2 2 2 2 2 2 2

3 3 3 3 3 3 3 3 3 3

3 3 3 3 3 3 3 3 3 3

4 4 4 4 4 4 4 4 4 4

4 4 4 4 4 4 4 4 4 4

5 5 5 5 5 5 5 5 5 5

5 5 5 5 5 5 5 5 5 5

6 6 6 6 6 6 6 6 6 6

6 6 6 6 6 6 6 6 6 6

7 7 7 7 7 7 7 7 7 7

SYMBOL

MODEL / SERIES

FUNCTION

NECK SIZE (IN)

FACE SIZE (IN)

RANGE (CFM)

MATERIAL

DAMPER (Y/N)

SD-1 SD-2 SD-3 SD-4 SD-5

TDC-AA TDC-AA TDC-AA TDC-AA TDC-AA

SUPPLY SUPPLY SUPPLY SUPPLY SUPPLY

6"ø 8"ø 10"ø 12"ø 14"ø

24x24 24x24 24x24 24x24 24x24

0 - 100 101 - 230 231 - 380 381 - 500 501 - 640

ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM

N N N N N

CEILING CEILING CEILING CEILING CEILING

1 1 1 1 1

CD-1

TDC-AA

SUPPLY

8"ø

24x24

0 - 230

ALUMINUM

N

CEILING

1 7

KD-1

PAS-AA

SUPPLY

14"ø

24x24

0 - 500

ALUMINUM

N

CEILING

1 8

HARRISBURG, PA 17102-2499

SR-A SR-1

301FS 301FS

SUPPLY SUPPLY

18X6 20X20

18X6 20X20

0 - 380 0 - 1300

ALUMINUM ALUMINUM

Y N

CEILING WALL

2 ---

MEP ENGINEER

LD-1 LD-2 LD-3 LD-4

TBDI-80 TBDI-80 TBDI-80 TBDI-80

SUPPLY SUPPLY SUPPLY SUPPLY

6" 8" 10" 12"

2 SLOTS, 1x48 EA 2 SLOTS, 1x48 EA 2 SLOTS, 1x48 EA 2 SLOTS, 1x48 EA

0 - 180 181 - 230 231 - 270 271 - 340

ALUMINUM ALUMINUM ALUMINUM ALUMINUM

N N N N

CEILING/WALL CEILING/WALL CEILING/WALL CEILING/WALL

3 3 3 3

TYPE

REMARKS

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET

7 7 7 7 7 7 7 7 7 7

AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125

4 4 4 4

5 5 5 5

ROSWELL, GA 30076

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

RD-1 RD-2 RD-3 RD-4 RD-5

PAR-AA PAR-AA PAR-AA PAR-AA PAR-AA

RETURN RETURN RETURN RETURN RETURN

8"ø 10"ø 12"ø 14"ø 14x14

24x24 24x24 24x24 24x24 24x24

0 - 230 231 - 380 381 - 500 501 - 640 641 - 1,000

ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM

N N N N N

CEILING CEILING CEILING CEILING CEILING

LITITZ, PA 17543

-----------

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

DAIKIN

RG-1 RG-A

REMARKS: 1. DISCONNECT SWITCH BY ELECTRICAL. 2. PROVIDE WITH CONDENSATE PUMP. ROUTE CONDENSATE TO DRAIN IN NEAREST FAN COIL UNIT CLOSET. 3. PROVIDE UNIT WITH REMOTE WALL MOUNTED THEMOSTAT. 4. PROVIDE ISOLATION VALVES IN REFRIGERANT LINES FOR MAINTENANCE. 5. INSTALL PER MANUFACTURERS RECOMMENDED CLEARANCES AND GUIDELINES. 6. COOLING AND HEATING CAPPACITIES SHALL INCLUDE REFRIGERANT LINE LOSS. 7. PROVIDE WATER LEVEL DETECTION DEVICE (WLDD) IN UNIT SUPPLIED DRAIN PAN AND LOCATE AT A POINT HIGHER THAN THE PRIMARY DRAIN LINE. WLDD SHALL BE WIRED TO SHUT OFF UNIT IN EVENT THE PRIMARY LINE IS BLOCKED.

PAR-AA PAR-AA

ER-1 ER-2 ER-3 ER-4 ER-5

COOLING

CU-A CU-B

REYQ192PBYD REYQ264PBYD

SELECTION BASED ON:

ELECTRICAL

TOT. MBH

V

PH

192 264

460 460

3 3

IEER

EMERGENCY POWER

18.7 18.7

Y Y

REMARKS 1 2 3 4 1 2 3 4

DAIKIN

50F 50F 50F 50F 50F

AIR CONDITIONING UNIT CRAC-G-1 TRANSFORMER ROOM CRAC-G-2 TRANSFORMER ROOM

CRAC CURRENT

CFM

O.A. CFM

MBH TOTAL

MBH SENS.

RH KW

FAN HP

V

PH

HTZ

3750

0

102.4

102.4

11.5

2.0

460

3

60

3750

0

102.4

102.4

11.5

2.0

CRCU-G-1

CRAC-G-1

ROOF

95

CRCU-G-2

CRAC-G-2

ROOF

95

0 - 100 0 - 100 101 - 230 231 - 380 381 - 500

ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM

N N N N N

CEILING CEILING CEILING CEILING CEILING

2 2 2 2 2

100 STERLING PARKWAY, SUITE 108

6 6 6 6 6

MECHANICSBURG, PA 17050

TITUS

PRIMARY AIR CFM RANGE

INLET SIZE

FPT-1-1 FPT-1-2

620 - 2,070

16"ø

760 - 2,525

16"ø

FPT-1-3

515 - 1,705

FPT-1-4

360 - 1,195

460

3

60

FPT

FAN S.P.

FILTER S.P.

HP

V

PH

EAT

LAT

COIL SIZE MAX H 2O GPM P.D. FT.

0.37

0.35

0.1

1

277

1

68

96.3

3.66

0.38

0.35

0.1

1

277

1

68

94.2

4.21

14"ø

0.40

0.35

0.1

3/4

277

1

68

100.7

12"ø

0.38

0.35

0.1

1/2

277

1

68

102.4

MIN. OPER. SP

MOTOR

MAX COIL AIR P.D.

EMERGENCY POWER

0.69

0.11

N

-

0.9

0.16

N

-

3.44

4.35

0.08

N

-

2.50

2.08

0.06

N

-

REMARKS

12"ø

0.37

0.35

0.1

1/2 1/4

277

1

68

103.3

2.33

1.83

0.05

N

-

12345678

340 - 1,120

12"ø

0.37

0.35

0.1

1/2 1/4

277

1

68

103.0

2.38

1.90

0.05

N

-

MMD96

SELECTION BASED ON 1. NC'S ARE DERIVED FROM SOUND POWER LEVELS, WHICH ARE OBTAINED IN ACCORDANCE WITH ARI STANDARD 880-98 AND ASHRAE STANDARD 130-1996. 2. PROVIDE ECM MOTOR, FACTORY WIRED 24 VOLT TRANSFORMER AND ELECTRIC REHEAT COIL WITH SINGLE POINT POWER CONNECTION AND DISCONNECT SWITCH. 3. PROVIDE 277 VOLT TO 24 VOLT CONTROL TRANSFORMER. 4. WHERE MEDIUM PRESSURE BRANCH DUCT EXCEEDS TWENTY (20) FEET, INCREASE TO NEXT HIGHER SIZE (i.e. 6" INLET -> 8" DUCT). REMARKS: 1.

FAN COIL UNITS CHILLED/HOT WATER 4-PIPE

ELECTRICAL DATA

REMARKS

MODEL

WSA

FLA

OPD

V

PH

HTZ

8

19.9

17.4

25

460

3

60

PFH096

1

8

19.9

17.4

25

460

3

60

PFH096

1

FCU

COOLING COIL

SYMBOL

CFM

OA CFM

ESP

HP

UNIT STYLE

EDB

FCU-A

350

45

0.5

0.25

VERTICAL

77

64

11.0

EWB TOT.MBH

HEATING COIL

SENS.MBH

GPM

PD EWT

LWT EDB

MBH

GPM

9.2

2.3

7.4

45

55

70

12.0

0.6

ELECTRICAL

PD EWT

EMERGENCY REMARKS POWER

LWT

V

PH

HTZ

0.14 180

140

277

1

60

N

1 2 3 4 5 6 7

FCU-B

300

30

0.5

0.25

VERTICAL

77

64

10.3

8.4

2.2

6.6

45

55

70

11.5

0.6

0.13 180

140

277

1

60

N

1 2 3 4 5 6 7

FCU-C

900

75

0.5

0.25

VERTICAL

77

64

20.2

18.2

6.0

6.7

45

55

70

22.1

1.2

1.75 180

140

277

1

60

N

1 2 3 4 5 6 7

FCU-D

675

75

0.5

0.25

VERTICAL

77

64

18.0

16.4

3.8

6.7

45

55

70

20.8

1.1

1.66 180

140

277

1

60

N

1 2 3 4 5 6 7

FCU-E

1,350

100

0.5

(2) 0.25

VERTICAL

77

64

32.1

30.0

6.9

6.2

45

55

70

33.8

1.8

0.82 180

140

277

1

60

N

1 2 3 4 5 6 7

FCU-F

1,100

75

0.5

(2) 0.25

VERTICAL

77

64

28.7

25.8

6.2

5.2

45

55

70

29.5

1.6

0.65 180

140

277

1

60

N

1 2 3 4 5 6 7

SELECTION BASED ON:

JCI/YORK

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED AND WIRED DISCONNECT. 2. PROVIDE COOLING COIL WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER. 3. PROVIDE HEATING COIL WITH 2-WAY CONTROL VALVE, SHUT OFF VALVES, BALANCING VALVE, AND STRAINER. 4. PROVIDE NETWORKED THERMOSTAT BY BAS MANUFACTURER. SETPOINT ADJUSTMENT RANGE SHALL BE CONTROLLED BY THE BAS. 5. PROVIDE WITH WATER LEVEL DETECTION DEVICE FOR CONDENSATE OVERFLOW. 6. PROVIDE BALANCING VALVE AND MOTORIZED DAMPER IN OUTSIDE AIR DUCT. BALANCE DAMPER TO OA FLOW SHOWN ON SCHEDULE. MOTORIZED DAMPER SHALL OPEN WHEN FAN IS ENERGIZED. 7. CHILLED WATER AND HOT WATER COILS SELECTED WITH 35% PROPYLENE GLYCOL.

ELECTRIC WALL HEATER

EWH COIL DATA

KEY PLAN

FAN SCHEDULE

KW

STAGES

V

PH

AMPS

MBH

CONTROL OPTIONS REMOTE THERMOSTAT/ INTEGRAL THERMOSTAT

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

DEF-1

ENERVEX

BEF500

ROOF

DRYER VENT

3,960

0.981

2,000

-

5.0

208

3

60

1 3 4

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-G-1

GREENHECK

CSP-A1410

INLINE

GROUND FL

925

0.375

1,039

-

822 (W)

115

1

60

1 2 5

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-G-2

GREENHECK

BSQ-180-30

INLINE

GROUND FL

5,000

0.375

1,484

2.31

3.0

460

3

60

1 2 5

EWH-G-4

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-G-3

GREENHECK

CSP-A1050

INLINE

GROUND FL

1,000

0.25

1,090

-

455 (W)

115

1

60

1 2 5

EWH-1-1

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-G-4

GREENHECK

CSP-B200

INLINE

GROUND FL

150

0.25

913

-

173 (W)

115

1

60

1 2 5

EWH-1-2

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-G-5

GREENHECK

BSQ-240-15

INLINE

GROUND FL

7,000

0.25

765

1.2

1.5

460

3

60

1 2 5

EWH-1-3

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-G-6

GREENHECK

CSP-A510

INLINE

GROUND FL

400

0.25

977

-

217 (W)

115

1

60

1 2 5

EWH-1-4

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-1-1

GREENHECK

CSP-A700

INLINE

FIRST FL

450

0.375

785

-

350 (W)

115

1

60

1 2 5

EWH-1-5

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-1-2

GREENHECK

SP-B110

CEILING

FIRST FL

75

0.25

950

-

80 (W)

115

1

60

1 2

EWH-3-1

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-1-3

GREENHECK

SP-B90

CEILING

FIRST FL

50

0.25

586

-

50 (W)

115

1

60

1 2

EWH-3-2

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-1-4

GREENHECK

CSP-B200

INLINE

FIRST FL

150

0.25

913

-

173 (W)

115

1

60

1 2 5

EWH-3-3

AWH4407F

100

2.0

1

277

1

7.22

6.8

INTEGRAL THERMOSTAT

NO

1 2 3

EF-1-5

GREENHECK

SP-B150

CEILING

FIRST FL

150

0.25

1,050

-

128 (W)

115

1

60

1 2

EF-2-1

GREENHECK

SP-B150

CEILING

SECOND FL

150

0.25

1,050

-

128 (W)

115

1

60

1 2

EF-3-1

GREENHECK

CSP-B200

INLINE

THIRD FL

150

0.25

913

-

173 (W)

115

1

60

1 2 5

EF-3-2

GREENHECK

CSP-B200

INLINE

THIRD FL

150

0.25

913

-

173 (W)

115

1

60

1 2 5

EF-5-1

GREENHECK

CSP-B200

INLINE

FIFTH FL

150

0.25

913

-

173 (W)

115

1

60

1 2 5

EF-5-2

GREENHECK

CSP-B200

INLINE

FIFTH FL

150

0.25

913

-

173 (W)

115

1

60

1 2 5

SPF-1

GREENHECK

VAD-18H14-16-M30

VANE AXIAL

STAIR PRES.

3,505

2.0

3,500

2.81

3.0

460

3

60

-

SPF-2

GREENHECK

VAD-18H14-16-M30

VANE AXIAL

STAIR PRES.

3,505

2.0

3,500

2.81

3.0

460

3

60

-

SPF-3

GREENHECK

VAD-18H14-16-M30

VANE AXIAL

STAIR PRES.

3,505

2.0

3,500

2.81

3.0

460

3

60

-

EPF-1

GREENHECK

VAD-20H14-23-M75

VANE AXIAL

ELEV. PRES.

8,000

2.0

3,500

6.09

7.5

460

3

60

-

EMERGENCY POWER

EPF-2

GREENHECK

VAD-20H14-23-M75

VANE AXIAL

ELEV. PRES.

8,000

2.0

3,500

6.09

7.5

460

3

60

-

RF-1-1

GREENHECK

SQ-130-A

INLINE

FIRST FL

2,100

0.25

1,629

0.47

0.75

115

1

60

1 2 5

N

KEF-G-2

GREENHECK

QEI-9-II-3

MIXED FLOW

FIRST FL

650

0.50

1,273

0.13

0.33

460

3

60

1 2 5

SYMBOL

MODEL

CFM

EWH-G-1

AWH4407F

EWH-G-2 EWH-G-3

SELECTION BASED ON:

EMERGENCY POWER

REMARKS

QMARK

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION. 2. PROVIDE WITH SURFACE MOUNT INSTALLATION KIT. 3. UNIT FINISH SHALL BE DETERMINED BY ARCHITECT DURRING SUBMITTAL PHASE.

WATER FILTRATION SYSTEM SYMBOL WFS-1

MODEL

SERVES

PF-63-030

SELECTION BASED ON: TEMPLATE VERSION: 2.6.8.20141012

12X12 24X24 24X24 24X24 24X24

330 - 1,090

REMARKS: 1. UNIT SHALL BE PROVIDED WITH LOW AMBIENT CONTROLS DOWN TO 0°F.

12/14/2015 11:04:47 PM

6"Ø 6"Ø 8"Ø 10"Ø 12"Ø

FPT-1-6

SELECTION BASED ON: LIEBERT

PLOT DATE:

EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST

FPT-1-5

CRCU TONS

STRUCTURAL ENGINEER

12345678

AIR COOLED CONDENSING UNIT O.A. AMB

-----

MMD96

REMARKS: 1. FACTORY MOUNTED DISCONNECT SWITCH. 2. FACTORY 120V/1PH CONDENSATE PUMP. 3. WALL MOUNTED MICROPROCESSOR CONTROL AND MONITOR PANEL. INTERFACE WITH THE BUILDING BAS. 4. HOT GAS BYPASS CAPACITY CONTROL 5. HIGH TEMPERATURE SENSOR. 6. FILTER CLOG INDICATOR. 7. SUPPLY AND RETURN AIR DISTRIBUTION PLENUM WITH MERV 8 FILTERS. 8. PROVIDE WITH ELECTRIC REHEAT.

LOCATION

CEILING WALL

REMARKS

GENERAL NOTES: (APPLICABLE TO ALL OF THE ABOVE) A. R-407C REFRIGERANT. B. MECHANICAL CONTRACTOR SHALL VERIFY MCA AND MOCP WITH EQUIPMENT MANUFACTURER AND COORDINATE WITH ELECTRICAL CONTRACTOR. C. SELECTION BASED ON ENTERING AIR TEMPERATURE OF 85 DEG DB/63.6 DEG WB.

SERVES

N N

MODEL

SELECTION BASED ON: LIEBERT

SYMBOL

ALUMINUM ALUMINUM

FAN POWERED TERMINAL (HOT WATER) (PARALLEL FLOW) SYMBOL

SERVICE

0 - 1,500 0 - 1,350

REMARKS: 1. INSULATED BACKPAN. 2. OPPOSED BLADE DAMPER. 3. FACTORY INSULATED PLENUM. 4. VOLUME CONTROL DAMPER KIT W/OPERATOR ACCESSIBLE THROUGH DIFFUSER FACE. 5. CONCEALED FRAME, DRYWALL 6. 1/2"x1/2"x1/2" GRID CORE. 7. PROVIDE TWO WAY THROW ALONG LENGTH OF CORRIDOR. 8. PROVIDE PERFORATED SUPPLY GRILLE WITHOUT PATTERN CONTROLLERS.

REMARKS: 1. PROVIDE WITH FACTORY CONTROLLER WITH BAS INTERFACE. 2. UNIT SHALL BE PROVIDED WITH LOW AMBIENT CONTROLS DOWN TO 0°F. 3. UNIT COMPOSED OF MULTIPLE UNITS MANIFOLDED TOGETHER. INSTALL PER MANUFACTURERS RECOMENDATIONS. 4. CAPACITIES INCLUDE PIPING LOSSES.

SYMBOL

24x24 20x20

GENERAL NOTES: (APPLICABLE TO ALL OF THE ABOVE) A. COORDINATE FRAME WITH CEILING TYPE AND/OR SUSPENSION SYSTEM. REFER TO ARCHITECTURAL DRAWINGS. B. FINISH SHALL BE OF THE TYPE AND COLOR SELECTED BY THE ARCHITECT. SUBMIT COLOR/FINISH CHART AS PART OF SHOP DRAWINGS.

VRF - DUCTLESS SPLIT SYSTEMS - CONDENSING UNITS MODEL

N/A N/A

WBCM

SELECTION BASED ON:

SYMBOL

RETURN RETURN

LOCATION

CT-1

CENTRAL PLANT

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

SELECTION BASED ON:

TYPE

GPM

CENTRIFUGAL

220

HP

GALLONS WEIGHT

7.5

15

ELECTRICAL V PH

809

460

3

SYMBOL

MANUFACTURER

MODEL

TYPE

SERVICE

CFM

S.P. (IN.)

FAN RPM

BHP

HP

VOLTS

PH

HZ

REMARKS

A

B

REVISION NO. DESCRIPTION

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION. 2. PROVIDE WITH FACTORY MOUNTED DISCONNECT. 3. PROVIDE WITH ROOF CURB. 4. PROVIDE WITH VFD, ENERVEX MEC18 CONTROL PANEL, AND REMOTE DUCT MOUNTED PRESSURE SENSOR. 5. PROVIDE SPRING ISOLATORS IN HANGER RODS.

PUROFLUX

PROPELLER UNIT HEATER (HOT WATER) FAN DATA

AHA PROJECT NUMBER

G1215-004.00 DATE

03 DECEMBER 2015

UH COIL DATA

ELECTRICAL

DATE

ISSUE

CONSTRUCTION DOCUMENTS

CFM

HP

RPM

EAT

LAT

EWT

LWT

MBH

GPM

V

PH

HZ

EMERGENCY POWER

HC165

3,240

1/3

1,075

65

97.5

180

161

103.9

13.6

115

1

60

Y

1 2

SHEET TITLE

HC165

3,240

1/3

1,075

65

97.5

180

161

103.9

13.6

115

1

60

Y

1 2

HVAC SCHEDULES

HC165

3,240

1/3

1,075

65

97.5

180

161

103.9

13.6

115

1

60

Y

1 2

SYMBOL

MODEL

UH-G-1 UH-G-2 UH-G-2

SELECTION BASED ON:

REMARKS

MODINE

REMARKS: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION. 2. PROVIDE WITH WALL MOUNTED THERMOSTAT.

REVISED 15 DECEMBER 2015

SHEET NO.

M-602

EUH

ELECTRIC UNIT HEATERS SYMBOL

MODEL/ SERIES

SERVICE

MOUNTING

CFM

KW

EUH-G-1

MUH

032 STORAGE

WALL

350

5.0

LENGTH STAGES (FT) N/A

1

ELECTRICAL V PH 460

3

REMARKS 1 2 3 4 5

ARCHITECT HKS, INC.

SELECTION BASED ON: EQUAL PRODUCTS BY:

QMARK INDEECO, BERKO, CHROMALOX, MARKEL, MARLEY, TRANE

TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

REMARKS: 1. INTEGRAL THERMOSTAT. 2. FACTORY DISCONNECT SWITCH. 3. FAN DELAY SWITCH. 4. THERMAL CUTOUT. 5. STEEL FRONT PANEL WITH BAKED ENAMEL FINISH.

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125

WALL LOUVERS

WL

MODEL/ SERIES

SERVICE

SIZE WXH (IN)

MIN FREE AREA (SQ FT)

CFM

MAX PRESS. DROP (IN WC)

WL-G-1 WL-G-2 WL-G-3 WL-G-4 WL-G-5 WL-G-6 WL-G-7 WL-G-8 WL-G-9 WL-G-10 WL-G-11 WL-1-1 WL-1-2 WL-1-3 WL-1-4 WL-1-5 WL-1-6 WL-1-7

ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635 ESD-635

MAIN MECHANICAL EF-G-1 KEF-G-1, G-2 EF-G-2 AHU-G-1, AHU-G-2 EF-G-3 EF-G-5 AHU-G-3 AHU-G-3 EF-G-6 EF-G-6 EF-1-1 AHU-1-1 AHU-1-1 AHU-1-2 RF-1-1 MAU-G-1 AHU-G-1

78 X 36 24 X 24 66 X 36 48 X 36 114 X 66 24 X 24 36 X 60 186 X 24 90 X 48 18 X 18 18 X 18 18 X 18 114 X 30 90 X 42 54 X 24 66 X 18 226 X 28 162 X 24

10.0 1.25 8.25 6.25 31.25 1.25 8.75 15.0 17.25 0.5 0.5 0.75 12.0 13.75 3.5 3.0 22.5 13.0

7,000 925 6,450 5,000 25,000 1,000 7,000 12,000 12,000 400 400 450 9,500 9,500 2,400 2,100 16,250 8,750

0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

SELECTION BASED ON: EQUAL PRODUCTS BY:

OPERATOR INTERLOCK

FRAME

SITE/CIVIL ENGINEER REMARKS

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET

MOD MOD -

-

ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM ALUMINUM

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

3 4 3 3 3 3 3 3 3 3 3 4 3 3 3 3 3 3 3 3

LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

GREENHECK ARROW, RUSKIN, NAILOR

REMARKS: 1. BIRD SCREEN. 2. BAKED ENAMEL FINISH. 3. INSULATED PLENUM, MINIMUM 24" DEEP, FULL-SIZE OF LOUVER CONNECTION. 4. 120V MOTOR OPERATOR.

RELIEF HOODS

RH

SYMBOL

MODEL/ SERIES

TYPE

SERVICE

THROAT AREA (SF)

MAX SP (IN WC)

RH-R-1 RH-R-2 RH-R-3 RH-R-4 RH-R-5

GRSR GRSR GRSR GRSR GRSR

RELIEF RELIEF RELIEF RELIEF RELIEF

STAIRWELL STAIRWELL STAIRWELL ELEVATOR SHAFT ELEVATOR SHAFT

12.83 12.83 12.83 12.83 12.83

0.013 0.013 0.013 0.066 0.066

SELECTION BASED ON: EQUAL PRODUCTS BY:

REMARKS 1 1 1 1 1

2 2 2 2 2

3 3 3 3 3

4 4 4 4 4

5 5 5 5 5

GREENHECK LOREN COOK, PENN BARRY

REMARKS: 1. INSULATED HOOD. 2. ALUMINUM BIRDSCREEN. 3. 120V MOTORIZED DAMPER (FAIL OPEN) TO INTERLOCK WITH FIRE ALARM PANEL. 4. INSULATED ROOF CURB. 5. ADJUSTABLE BAROMETRIC RELIEF DAMPER.

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

SYMBOL

ROSWELL, GA 30076

KEY PLAN

A

B

REVISION NO. DESCRIPTION

DATE

AHA PROJECT NUMBER

12/14/2015 11:04:47 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC SCHEDULES

REVISED 15 DECEMBER 2015

SHEET NO.

M-603

ARCHITECT HKS, INC. TWO LIVE OAK CENTER SPF

3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

2 DEF

ASSOCIATE ARCHITECT

1

SPF

60X14 EXHAUST AIR DUCT FROM ERU-2. SEE M-114 FOR CONTINUATION.

40X16 EXHAUST AIR DUCT TO ERU-1. SEE M-113 FOR CONTINUATION.

AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125

34X10 OUTSIDE AIR DUCT. SEE M-114 FOR CONTINUATION.

ROSWELL, GA 30076

44"x18"

18"ø

4"ø 4"ø TAKEOFF ABOVE FIFTH FLOOR CEILING.

40"x14"

54X18 SUPPLY AIR DUCT FROM ERU-1. SEE M-113 FOR CONTINUATION.

22"x22"

10X8 EXHAUST AIR DUCT. SEE M-113 FOR CONTINUATION.

TAKEOFF ABOVE SIXTH FLOOR CEILING.

12"x44"

PROVIDE TURNDOWN ABOVE ROOF FOR DRYER VENT EXHAUST.

6"ø

6"ø

HARRISBURG, PA 17102-2499

MEP ENGINEER

20"x56"

6"ø

1600 NORTH SECOND STREET

70X20 OUTSIDE AIR DUCT DOWN FROM ERU-2. SEE M-114 FOR CONTINUATION.

60"x14"

6"ø

MURRAY AND ASSOCIATES ARCHITECTS

3

PROVIDE BIRD SCREEN AND DOWNWARD CAMFER ON DUCT.

PROVIDE BIRD SCREEN AND DOWNWARD CAMFER ON DUCT.

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

6TH FLOOR

6TH FLOOR

GEOTECHNICAL ENGINEER 14X18 SUPPLY AIR DUCT. SEE M-111 FOR CONTINUATION.

SR-1 1170

22X10 EXHAUST AIR DUCT. SEE M-112 FOR CONTINUATION.

CMT LABORATORIES, INC.

SR-1 1170

2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

34X10 OUTSIDE AIR DUCT. SEE M-112 FOR CONTINUATION.

18X10 EXHAUST AIR DUCT. SEE M-111 FOR CONTINUATION.

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108

6"ø 20"x46"

34X10 OUTSIDE AIR DUCT. SEE M-110 FOR CONTINUATION.

18X10 EXHAUST AIR DUCT. SEE M-109 FOR CONTINUATION.

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

42"x16"

34"x14"

6"ø

22X10 EXHAUST AIR DUCT. SEE M-110 FOR CONTINUATION.

12"x32"

TAKEOFF ABOVE FOURTH FLOOR CEILING.

14X18 SUPPLY AIR DUCT. SEE M-109 FOR CONTINUATION.

18"x22"

4"ø 4"ø

MECHANICSBURG, PA 17050

10X10 SUPPLY AIR DUCT. SEE M-111 FOR CONTINUATION.

18"ø

34"x18"

6"ø

4"ø 4"ø

TAKEOFF ABOVE THIRD FLOOR CEILING.

34"x10"

10X10 SUPPLY AIR DUCT. SEE M-109 FOR CONTINUATION.

14X18 SUPPLY AIR DUCT. SEE M-107 FOR CONTINUATION.

6"ø

4TH FLOOR

20"x36"

18"ø

34"x14"

6"ø

40"x14"

6"ø

4TH FLOOR

22X10 EXHAUST AIR DUCT. SEE M-108 FOR CONTINUATION.

SR-1 1170

SR-1 1170

34X10 OUTSIDE AIR DUCT. SEE M-108 FOR CONTINUATION.

18X10 EXHAUST AIR DUCT. SEE M-107 FOR CONTINUATION.

16"x34"

22X10 EXHAUST AIR DUCT. SEE M-106 FOR CONTINUATION.

TAKEOFF ABOVE SECOND FLOOR CEILING.

6"ø

12"x22"

18"x10"

14X18 SUPPLY AIR DUCT. SEE M-105 FOR CONTINUATION.

12"x22"

4"ø 4"ø

10X10 SUPPLY AIR DUCT. SEE M-107 FOR CONTINUATION.

18"ø

20"x14"

6"ø

40"x10"

6"ø

34X10 OUTSIDE AIR DUCT. SEE M-106 FOR CONTINUATION.

18X10 EXHAUST AIR DUCT. SEE M-105 FOR CONTINUATION.

6"ø

PROVIDE FIRE SMOKE DAMPER AT PENETRATION OF SHAFT WALL. (TYP)

4"ø

2ND FLOOR 2ND FLOOR

10"x30"

10X10 SUPPLY AIR DUCT. SEE M-105 FOR CONTINUATION.

18"ø

20"x10"

6"ø

4"ø 20X10 EXHAUST AIR DUCT. SEE M-104 FOR CONTINUATION.

TAKEOFF ABOVE FIRST FLOOR CEILING. 6"ø

SR-1 1170

SR-1 1170

30X10 OUTSIDE AIR DUCT. SEE M-104 FOR CONTINUATION.

LOCATE SYSTEM DP SENSOR AT BOTTOM OF VENT STACK.

PROVIDE FIRE SMOKE DAMPER AT PENETRATION OF SHAFT WALL. (TYP)

6"ø 6"ø PROVIDE CLEANOUT AT BOTTOM OF VENT STACK. 4"ø 4"ø

1 M-701

4" TAKEOFF TO DRYER VENT BOX. (TYP)

MECH. RISER DIAGRAM - D-3 SCALE: N.T.S.

2 M-701

MECH. RISER DIAGRAM - D-1 SCALE: N.T.S.

3 M-701

MECH. RISER DIAGRAM - D-2 SCALE: N.T.S.

4 M-701

MECH. RISER DIAGRAM - D-4 SCALE:

5 M-701

MECH. RISER DIAGRAM - D-5 SCALE:

KEY PLAN

A

B

REVISION NO. DESCRIPTION

DATE

AHA PROJECT NUMBER

12/14/2015 11:04:50 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC RISERS

REVISED 15 DECEMBER 2015

SHEET NO.

M-701

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

ROOF

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE

3/4" HWR 3/4" HWS 3/4" SCHWR 3/4" SCHWS

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

3/4" SCHWR 3/4" SCHWS 3/4" HWR 3/4" HWS

STAE COLLEGE, PA 16801

3/4" SCHWR 3/4" SCHWS 3/4" HWR 3/4" HWS

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

6TH FLOOR

3/4" C 3/4" C

3/4" C

3/4" C

3/4" C

3/4" C

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

1 1/4" SCHWR 1 1/4" SCHWS 3/4" HWR 3/4" HWS

3/4" HWR 3/4" HWS 1 1/4" SCHWR 1 1/4" SCHWS

1" SCHWR 1" SCHWS 3/4" HWR 3/4" HWS

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

3/4" CONDENSATE FROM FCU (TYP)

1" C 1" C

1" C

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

1" C

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

1" C

1" C

1 1/4" SCHWR 1 1/4" SCHWS 3/4" HWR 3/4" HWS

3/4" HWR 3/4" HWS 1 1/4" SCHWR 1 1/4" SCHWS

5TH FLOOR

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

1" SCHWR 1" SCHWS 3/4" HWR 3/4" HWS 4TH FLOOR

1 1/2" C 1 1/2" C

1 1/2" C

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

1 1/2" C

3/4" HWR 3/4" HWS 1 1/2" SCHWR 1 1/2" SCHWS

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

1 1/2" C

1 1/2" C

3/4" CONDENSATE FROM FCU (TYP)

1 1/2" SCHWR 1 1/2" SCHWS 3/4" HWR 3/4" HWS

1 1/4" SCHWS 1 1/4" SCHWR 3/4" HWS 3/4" HWR

1 1/4" SCHWR 1 1/4" SCHWS 3/4" HWR 3/4" HWS 3RD FLOOR

1 1/2" C 1 1/2" C

1 1/2" C

1 1/2" C

1 1/2" C

1 1/2" C 3/4" RUNNOUTS TO FCU (TYP)

3/4" RUNOUTS TO FCU (TYP.)

1 1/4" SCHWS 1 1/4" SCHWR 3/4" HWS 3/4" HWR

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

1" HWR 1" HWS 2" SCHWR 2" SCHWS

1" SCHWS 1" SCHWR 3/4" HWS 3/4" HWR

2" SCHWR 2" SCHWS 1" HWR 1" HWS

2" SCHWR 2" SCHWS 1" HWR 1" HWS

1" HWR 1" HWS 1 1/2" SCHWR 1 1/2" SCHWS

1 1/4" SCHWS 1 1/4" SCHWR 3/4" HWS 3/4" HWR

1 1/4" SCHWR 1 1/4" SCHWS 3/4" HWR

1" HWS 1" HWR 1 1/2" SCHWS 1 1/2" SCHWR

1 1/2" C 3/4" CONDENSATE FROM FCU (TYP.)

1 1/2" C

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

1 1/2" C

3/4" HWR 3/4" HWS 3/4" SCHWR 3/4" SCHWS

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

2ND FLOOR

1 1/2" C

1 1/2" C

3/4" HWS 3/4" SCHWR 3/4" SCHWS 3/4" HWR 3/4" HWS

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

3/4" SCHWR 3/4" SCHWS 3/4" HWR 3/4" HWS

1" HWR 1" HWS 2" SCHWR 2" SCHWS

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

3/4" RUNNOUTS TO FCU (TYP)

KEY PLAN

3/4" RUNOUTS TO FCU (TYP.) 1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

1 M-702

SCALE: N.T.S.

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

3/4" CONDENSATE FROM FCU (TYP.)

MECH. RISER DIAGRAM - P-1

3/4" RUNNOUTS TO FCU (TYP).

3/4" RUNOUTS TO FCU (TYP.) 1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

3/4" CONDENSATE FROM FCU (TYP.)

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

2 M-702

MECH. RISER DIAGRAM - P-2 SCALE: N.T.S.

3 M-702

MECH. RISER DIAGRAM - P-3 SCALE: N.T.S.

4 M-702

MECH. RISER DIAGRAM - P-4 SCALE: N.T.S.

5 M-702

MECH. RISER DIAGRAM - P-5 SCALE: N.T.S.

6 M-702

3/4" CONDENSATE FROM FCU (TYP).

A 1ST FLOOR

MECH. RISER DIAGRAM - P-6

B

SCALE: N.T.S. REVISION NO. DESCRIPTION

DATE

AHA PROJECT NUMBER

12/14/2015 11:04:53 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC RISERS

REVISED 15 DECEMBER 2015

SHEET NO.

M-702

ARCHITECT HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675 ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125 ROSWELL, GA 30076

ROOF

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES

3" CHWS/R AND 2" HWS/R UP TO ERU-1 ON ROOF.

3 1/2" CHWS/R AND 2 1/2" HWS/R UP TO ERU-2 ON ROOF.

33 SOUTH BROAD STREET LITITZ, PA 17543

1" CHWS/R AND 3/4" HWS/R TO FCU.

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

3/4" CHWS/R AND 3/4" HWS/R TO FCU.

3/4" HWR 3/4" HWS

2701 CAROLEAN INDUSTRIAL DRIVE

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

3/4" SCHWR 3/4" SCHWS 3/4" HWR 3/4" HWS

3" SCHWR 3" SCHWS 2" HWR 2" HWS

3 1/2" SCHWS 3 1/2" SCHWR 2 1/2" HWS 2 1/2" HWR

STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

3/4" C

1" CHWS/R AND 3/4" HWS/R TO FCU.

3/4" C

3/4" C 1" HWR 1" HWS 1" SCHWR 1" SCHWS 3/4" C

1" HWS/R TO FTR.

3/4" CHWS/R AND 3/4" HWS/R TO FCU.

1" HWR 1" HWS

1" HWR 1" HWS

3/4" C

3/4" RUNNOUTS TO FCU (TYP)

1 1/4" SCHWS 1 1/4" SCHWR 3/4" HWS 3/4" HWR

1 1/4" SCHWR 1 1/4" SCHWS 1" HWR 1" HWS

3/4" CONDENSATE FROM FCU (TYP)

3" SCHWR 3" SCHWS 2" HWR 2" HWS

3 1/2" SCHWS 3 1/2" SCHWR 2 1/2" HWS 2 1/2" HWR

1" C 1" C

1" C

3/4" HWS/R TO FTR. 1" CHWS/R AND 3/4" HWS/R TO FCU.

5TH FLOOR

1 1/4" HWR 1 1/4" HWS 1 1/4" SCHWR 1 1/4" SCHWS 1" C

1" HWS/R TO FTR.

3/4" CHWS/R AND 3/4" HWS/R TO FCU.

1 1/4" HWR 1 1/4" HWS

1" C

1 1/4" HWR 1 1/4" HWS

1 1/2" SCHWS 1 1/2" SCHWR 3/4" HWS 3/4" HWR

1 1/4" SCHWR 1 1/4" SCHWS 1 1/4" HWR 1 1/4" HWS

3" SCHWR 3" SCHWS 2" HWR 2" HWS

3 1/2" SCHWS 3 1/2" SCHWR 2 1/2" HWS 2 1/2" HWR

4TH FLOOR

1 1/2" C 3/4" HWS/R TO FTR. 1" CHWS/R AND 3/4" HWS/R TO FCU.

1 1/2" C

1 1/2" C

1 1/2" HWR 1 1/2" HWS 1 1/2" SCHWR 1 1/2" SCHWS 1 1/2" C

1" HWS/R TO FTR.

3/4" CHWS/R AND 3/4" HWS/R TO FCU.

1 1/2" HWR 1 1/2" HWS

3/4" CONDENSATE FROM FCU (TYP).

1 1/2" C

1 1/2" HWR 1 1/2" HWS

1 1/2" SCHWR 3/4" HWS 3/4" HWR 3/4" CONDENSATE FROM FCU (TYP)

3" SCHWR 3" SCHWS 2" HWR 2" HWS

3 1/2" SCHWS 3 1/2" SCHWR 2 1/2" HWS 2 1/2" HWR

1 1/2" SCHWS

1 1/2" SCHWR 1 1/2" SCHWS 1 1/2" HWR 1 1/2" HWS

1 1/2" C

3RD FLOOR 1 1/2" C

3/4" HWS/R TO FTR. 1" CHWS/R AND 3/4" HWS/R TO FCU.

2" HWR 2" HWS 2" SCHWR 2" SCHWS 1 1/2" C 2" HWR 2" HWS 2" SCHWR 2" SCHWS

1" HWS/R TO FTR.

3/4" CHWS/R AND 3/4" HWS/R TO FCU. 2" SCHWS 2" SCHWR 2" HWS 2" HWR

2" HWR 2" HWS

3/4" RUNNOUTS TO FCU (TYP)

2" SCHWR 2" SCHWS 2" HWR 2" HWS

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

3/4" HWS/R TO FTR. 1" HWS/R TO FTR. 1" CHWS/R AND 3/4" HWS/R TO FCU.

3/4" CONDENSATE FROM FCU (TYP).

1 1/2" C

1 1/2" C

1" HWR 1" HWS 1" SCHWR 1" SCHWS 1 1/2" C

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

3 1/2" SCHWS 3 1/2" SCHWR 2 1/2" HWS 2 1/2" HWR

3/4" RUNNOUTS TO FCU (TYP)

3 1/2" SCHWS 3 1/2" SCHWR 2 1/2" HWS 2 1/2" HWR

3" SCHWR 3" SCHWS 2" HWR 2" HWS

3/4" CONDENSATE FROM FCU (TYP) 1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

2ND FLOOR

1 1/2" C

3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

1 1/2" C 3/4" SCHWS 3/4" SCHWR 3/4" HWS 3/4" HWR

2" SCHWR 2" SCHWS 2" HWR 2" HWS

3/4" HWR 3/4" HWS

2" SCHWS 2" SCHWR 3/4" HWS 3/4" HWR 1" HWR 1" HWS 2" SCHWR 2" SCHWS

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

3/4" HWS/R TO FTR.

6TH FLOOR

3" SCHWR 3" SCHWS 2" HWR 2" HWS

KEY PLAN

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

A

1 1/2" CONDENSATE TO HUB DRAIN. HUB DRAIN BY PLUMBING.

1ST FLOOR

3/4" HWS/R TO FTR.

B 1 M-703

MECH. RISER DIAGRAM - P-7 SCALE:

2 M-703

MECH. RISER DIAGRAM - P-8 SCALE:

3 M-703

MECH. RISER DIAGRAM - P-9 SCALE:

4 M-703

MECH. RISER DIAGRAM - P-10 SCALE:

5 M-703

MECH. RISER DIAGRAM - P-11

REVISION NO. DESCRIPTION

SCALE:

DATE

AHA PROJECT NUMBER

12/14/2015 11:04:56 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

G1215-004.00 DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC RISERS

REVISED 15 DECEMBER 2015

SHEET NO.

M-703

PERMANENT VICTAULIC TYPE HARD CONNECTION FOR FUTURE TEMPORARY/EMERGENCY CHILLER. LOCATE ON BUILDING EXTERIOR WALL. FM

PCHWS TO FUTURE CAMPUS LOOP

T

12" PCHWS

ARCHITECT HKS, INC. TWO LIVE OAK CENTER

12" PCHWS PIPING WITH HIGH PERFORMANCE LUG TYPE BUTTERFLY VALVE, SPOOL, AND BLIND FLANGE FOR FUTURE CONNECTION. MINIMIZE DEAD LEG.

CH-1 8" PCHWS

ATLANTA, GA 30326

ASSOCIATE ARCHITECT MURRAY AND ASSOCIATES ARCHITECTS

12" PCHWR

12" PCHWR

8" PCHWR

3445 PEACHTREE ROAD, NE, SUITE 675

1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

MEP ENGINEER AHA CONSULTING ENGINEERS

CH-2 (FUTURE)

1801 OLD ALABAMA RD, SUITE 125

FUTURE 8" PCHWR

ROSWELL, GA 30076

FUTURE 8" PCHWS

SITE/CIVIL ENGINEER DERCK & EDSON ASSOCIATES

8" CWS PIPING WITH HIGH PERFORMANCE LUG TYPE BUTTERFLY VALVE, SPOOL, AND BLIND FLANGE FOR FUTURE CONNECTION. MINIMIZE DEAD LEG.

33 SOUTH BROAD STREET LITITZ, PA 17543

GEOTECHNICAL ENGINEER CMT LABORATORIES, INC.

CH-3 (FUTURE)

2701 CAROLEAN INDUSTRIAL DRIVE

FUTURE 8" PCHWR

STAE COLLEGE, PA 16801

FUTURE 8" PCHWS

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108 MECHANICSBURG, PA 17050

CHILLER MINIMUM FLOW BYPASS

12" PCHWR

12" PCHWS

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

MANUAL BYPASS VALVE (NC)

HEX-2

HEX-1

VFD

12” PCHWR

8" PCHWR

8" PCHWR

CWP-1 LEAD VFD

CWP-2 STANDBY

8" PCHWR

12” PCHWR

8" PCHWR

EXPANSION TANK AND AIR SEPARATOR SHALL BE LOCATED IN CENTRAL MECHANICAL ROOM. PROVIDE MAKE-UP WATER, DRAIN CONNECTIONS, AND PIPING.

VFD

FUTURE 8" PCHWR

CWP-3 FUTURE

SYSTEM FILL AIR VENT AIR SEPARATOR AS-1

FUTURE 8" PCHWR

PCHWR FROM FUTURE CAMPUS LOOP

T 12" PCHWR

8" PCHWR PIPING WITH HIGH PERFORMANCE LUG TYPE BUTTERFLY VALVE, SPOOL, AND BLIND FLANGE FOR FUTURE CONNECTION. MINIMIZE DEAD LEG.

AUTOMATIC AIR VENT

BUFFER TANK BT-1

DRAIN EXPANSION TANK ET-1

1 M-801

DICTRICT CHILLED WATER SCHEMATIC SCALE: N.T.S. T

COOLING TOWER BYPASS

14" CWR

14" CWR

14" CWR PIPING WITH HIGH PERFORMANCE LUG TYPE BUTTERFLY VALVE, SPOOL, AND BLIND FLANGE FOR FUTURE CONNECTION. MINIMIZE DEAD LEG.

CH-1 8" CWS

14" CWS

14" CWR

8" CWS

14" CWR

FUTURE 8” CWR (TYPICAL 2)

8” CWR CH-2 (FUTURE) FUTURE 8" CWS

FUTURE 14" CWR

FUTURE 8" CWS

KEY PLAN

2 POSITION AUTOMATIC CONTROL VALVE (TYPICAL INLETS AND OUTLETS)

8" CWS PIPING WITH HIGH PERFORMANCE LUG TYPE BUTTERFLY VALVE, SPOOL, AND BLIND FLANGE FOR FUTURE CONNECTION. MINIMIZE DEAD LEG.

A CH-3 (FUTURE) FUTURE 8" CWS

FUTURE 8" CWS

B

REVISION NO. DESCRIPTION

CT-1 HEX-1 14" CWS

CT-2 (FUTURE)

DATE

CT-3 (FUTURE)

14" CWS

VFD

14" CWS

8" CWS

COOLING TOWER DUNNAGE. SEE STRUCTURAL DRAWINGS. VFD

12/14/2015 11:04:58 PM

CWP-2 STANDBY

8" CWS

VFD

FUTURE 8" CWS

CWP-3 FUTURE

ROUTE 2” OVERFLOW AND 2” DRAIN TO FLOOR DRAIN IN CENTRAL PLANT.

AHA PROJECT NUMBER

G1215-004.00 14" CWS

TEMPLATE VERSION: 2.6.8.20141012

8" CWS

PLOT DATE:

VIBRATION ISOLATION.

8" CWS

CWP-1 LEAD

1-1/2” MAKE-UP WATER PIPING

WFS-1

8” CWS

FUTURE 8” CWS (TYPICAL 2) 14" CWS

FUTURE 8" CWS

DATE

SYSTEM FILL

03 DECEMBER 2015 ISSUE

FUTURE 14" CWS

CONSTRUCTION DOCUMENTS

TO FLOOR DRAIN IN CENTRAL PLANT

T 14" CWS

2 M-801

DICTRICT CONDENSER WATER SCHEMATIC SCALE: N.T.S.

8" CWS PIPING WITH HIGH PERFORMANCE LUG TYPE BUTTERFLY VALVE, SPOOL, AND BLIND FLANGE FOR FUTURE CONNECTION. MINIMIZE DEAD LEG.

SHEET TITLE

14" CWS

HVAC SCHEMATICS

REVISED 15 DECEMBER 2015

SHEET NO.

M-801

VFD SEE STEAM TO WATER HEAT EXHCHANGER DETAIL FOR PIPING LAYOUT AND TRIM REQUIRED. 6” HWS T HWS TO BUILDING

HWP-2 STANDBY

FM

6” HWS

6” HWS

ARCHITECT VFD

HKS, INC. TWO LIVE OAK CENTER 3445 PEACHTREE ROAD, NE, SUITE 675

6” HWS

HWP-1 LEAD

6” HWS

6” HPS

ATLANTA, GA 30326

HXS-1

ASSOCIATE ARCHITECT

HPS FROM CAMPUS LOOP

MURRAY AND ASSOCIATES ARCHITECTS 1600 NORTH SECOND STREET HARRISBURG, PA 17102-2499

6” HPS

MEP ENGINEER AHA CONSULTING ENGINEERS 1801 OLD ALABAMA RD, SUITE 125

HXS-2

ROSWELL, GA 30076

SITE/CIVIL ENGINEER

LPC TO CAMPUS LOOP

DERCK & EDSON ASSOCIATES 33 SOUTH BROAD STREET LITITZ, PA 17543

T

GEOTECHNICAL ENGINEER

HWR FROM BUILDING

6” HWR

CMT LABORATORIES, INC. 2701 CAROLEAN INDUSTRIAL DRIVE STAE COLLEGE, PA 16801

STRUCTURAL ENGINEER WBCM 100 STERLING PARKWAY, SUITE 108

HEATING HOT WATER SCHEMATIC

1

SCALE: N.T.S.

BLOOMSBURG UNIVERSITY RESIDENCE HALL & BOOKSTORE

M-802

MECHANICSBURG, PA 17050

VFD

8” SCHWR T SCHWR FROM BUILDING

SCHWP-2 STANDBY

8” SCHWR PCHWR TO CAMPUS LOOP

8” SCHWR VFD

8” SCHWR

SCHWP-1 LEAD

8” SCHWR 8” SCHWR

8” PCHWR

HEX-2 MANUAL BYPASS VALVE (NC)

MANUAL BYPASS VALVE (NC)

8” SCHWS

T SCHWS TO BUILDING

8” PCHWS

FM

PCHWS FROM CAMPUS LOOP

8” SCHWS

SECONDARY CHILLED WATER SCHEMATIC

2 M-802

SCALE: N.T.S.

LUZERNE HALL

HX

KEY PLAN

NEW RESIDENCE HALL

LYCOMING HALL

BEN FRANKLIN HALL

A

FROM DISTRICT CHILLED WATER PLANT HX HX

CAPPED VALVES IN SERVICE TUNNEL. SEE FLOOR PLANS FOR LOCATION.

B

REVISION NO. DESCRIPTION

DATE

ELWELL HALL

HX

12/14/2015 11:04:59 PM

PLOT DATE:

TEMPLATE VERSION: 2.6.8.20141012

3 M-802

DISTRICT CHILLED WATER SITE SCHEMATIC

AHA PROJECT NUMBER

G1215-004.00

SCALE: N.T.S.

DATE

03 DECEMBER 2015 ISSUE

CONSTRUCTION DOCUMENTS SHEET TITLE

HVAC SCHEMATICS

REVISED 15 DECEMBER 2015

SHEET NO.

M-802