A. This Section includes the following domestic water piping specialties:

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION SECTION 22 11 19 - DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 A. 1.2 A. REL...
Author: Duane Owens
3 downloads 0 Views 128KB Size
ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION

SECTION 22 11 19 - DOMESTIC WATER PIPING SPECIALTIES

PART 1 - GENERAL

1.1 A.

1.2 A.

RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

SUMMARY This Section includes the following domestic water piping specialties: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

B.

Related Sections include the following: 1.

1.3 A.

1.4

Vacuum breakers. Backflow preventers. Water pressure-reducing valves. Balancing valves. Temperature-actuated water mixing valves. Strainers. Outlet boxes. Hose bibbs. Wall hydrants. Drain valves. Water hammer arresters. Air vents.

Division 22 Section "Meters and Gages for Plumbing Piping" for thermometers, pressure gages, and flow meters in domestic water piping.

PERFORMANCE REQUIREMENTS Minimum Working Pressure for Domestic Water Piping Specialties: psig unless otherwise indicated.

125

SUBMITTALS

A.

Product Data:

For each type of product indicated.

B.

Shop Drawings:

C.

Field quality-control test reports.

D.

Operation and Maintenance Data: For domestic water piping specialties to include in emergency, operation, and maintenance manuals.

Diagram power, signal, and control wiring.

DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 1

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION 1.5

QUALITY ASSURANCE

A.

Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B.

NSF Compliance: 1.

Comply with NSF 61, "Drinking Water System Components - Health Effects; Sections 1 through 9."

PART 2 - PRODUCTS

2.1 A.

VACUUM BREAKERS Hose-Connection Vacuum Breakers: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2. 3. 4. 5. B.

Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Woodford Manufacturing Company. Zurn Plumbing Products Group; Light Commercial Operation.

Standard: ASSE 1011. Body: Bronze, nonremovable, with manual drain. Outlet Connection: Garden-hose threaded ASME B1.20.7. Finish: Chrome or nickel plated.

complying

with

Pressure Vacuum Breakers: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c.

2. 3. 4. 5.

Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Zurn Plumbing Products Group; Wilkins Div.

Standard: ASSE 1020. Operation: Continuous-pressure applications. Pressure Loss: 5 psig maximum, through middle 1/3 of flow range. Accessories: a.

Valves:

Ball type, on inlet and outlet.

DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 2

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION

2.2 A.

BACKFLOW PREVENTERS Reduced-Pressure-Principle Backflow Preventers: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2. 3. 4. 5.

6. 7. 8.

Standard: ASSE 1013. Operation: Continuous-pressure applications. Pressure Loss: 12 psig maximum, through middle 1/3 of flow range. Body: Bronze for NPS 2 and smaller; cast iron with interior for lining complying with AWWA C550 or that is FDA approved NPS 2-1/2 and larger. End Connections: Threaded for NPS and smaller; flanged for NPS 2-1/2 and larger. Configuration: Designed for horizontal, straight through flow. Accessories: a.

b.

B.

Ames Co. Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Zurn Plumbing Products Group; Wilkins Div.

Valves: Ball type with threaded ends on inlet and outlet of NPS 2 and smaller; outside screw and yoke gate-type with flanged ends on inlet and outlet of NPS 2-1/2 and larger. Air-Gap Fitting: ASME A112.1.2, matching backflow-preventer connection.

Double-Check Backflow-Prevention Assemblies: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2. 3. 4. 5.

6. 7.

Ames Co. Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Zurn Plumbing Products Group; Wilkins Div.

Standard: ASSE 1015. Operation: Continuous-pressure applications, unless otherwise indicated. Pressure Loss: 5 psig maximum, through middle 1/3 of flow range. Body: Bronze for NPS 2 and smaller; cast iron with interior lining complying with AWWA C550 or that is FDA approved for NPS 2-1/2 and larger. Threaded for NPS 2 and smaller; flanged for End Connections: NPS 2-1/2 and larger. Configuration: Designed for horizontal, straight through flow.

DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 3

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION 8.

Accessories: a.

C.

Dual-Check-Valve Backflow Preventers: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c.

2. 3. 4. D.

Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Zurn Plumbing Products Group; Wilkins Div.

Standard: ASSE 1024. Operation: Continuous-pressure applications. Body: Bronze with union inlet.

Double-Check, Detector-Assembly Backflow Preventers: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2. 3. 4. 5. 6. 7. 8.

Ames Co. Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Zurn Plumbing Products Group; Wilkins Div.

Standard: ASSE 1048 and FMG approved or UL listed. Operation: Continuous-pressure applications. Pressure Loss: 5 psig maximum, through middle 1/3 of flow range. Body: Cast iron with interior lining complying with AWWA C550 or that is FDA approved. End Connections: Flanged. Configuration: Designed for horizontal, straight through flow. Accessories: a. b.

E.

Valves: Ball type with threaded ends on inlet and outlet of NPS 2 and smaller; outside screw and yoke gate-type with flanged ends on inlet and outlet of NPS 2-1/2 and larger.

Valves: Outside screw and yoke gate-type with flanged ends on inlet and outlet. Bypass: With displacement-type water meter, shutoff valves, and reduced-pressure backflow preventer.

Hose-Connection Backflow Preventers: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c.

2.

Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Woodford Manufacturing Company.

Standard:

ASSE 1052. DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 4

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION 3. 4. 5. 6. F.

Operation: Up to 10-foot head of water back pressure. Inlet Size: NPS 3/4. Outlet Size: Garden-hose thread complying with ASME B1.20.7. Capacity: At least 3-gpm flow.

Backflow-Preventer Test Kits: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c.

2.

2.3 A.

Description: Factory calibrated, with gages, fittings, hoses, and carrying case with test-procedure instructions.

WATER PRESSURE-REDUCING VALVES Water Regulators: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c.

2. 3. 4.

5. 6.

2.4 A.

Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Zurn Plumbing Products Group; Wilkins Div.

Conbraco Industries, Inc. Watts Industries, Inc.; Water Products Div. Zurn Plumbing Products Group; Wilkins Div.

Standard: ASSE 1003. Pressure Rating: Initial working pressure of 150 psig. Body: Bronze for NPS 2 and smaller; cast iron with interior lining complying with AWWA C550 or that is FDA approved for NPS 2-1/2 and larger. Valves for Booster Heater Water Supply: Include integral bypass. Threaded for NPS 2 and smaller; flanged for End Connections: NPS 2-1/2 and larger.

BALANCING VALVES Copper-Alloy Calibrated Balancing Valves: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2.

Armstrong International, Inc. ITT Industries; Bell & Gossett Div. NIBCO INC. Taco, Inc.

Type: Ball indicator.

valve

with

two

readout

ports

DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 5

and

memory

setting

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION 3. 4. 5.

2.5 A.

Body: Brass or bronze. Size: Same as connected piping, but not larger than NPS 2. Accessories: Meter hoses, fittings, valves, differential pressure meter, and carrying case.

TEMPERATURE-ACTUATED WATER MIXING VALVES Primary, Thermostatic, Water Mixing Valves: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2. 3. 4. 5. 6. 7. 8. 9. 10. 11.

2.6 A.

Armstrong International, Inc. Lawler Manufacturing Company, Inc. Leonard Valve Company. Powers; a Watts Industries Co.

Standard: ASSE 1017. Pressure Rating: 125 psig. Type: Exposed-mounting or Cabinet-type, as described on drawings, thermostatically controlled water mixing valve. Material: Bronze body with corrosion-resistant interior components. Connections: Threaded union inlets and outlet. Accessories: Manual temperature control, check stops on hot- and cold-water supplies, and adjustable, temperature-control handle. Valve Pressure Rating: 125 psig minimum, unless otherwise indicated. Valve Finish: Chrome plated. Piping Finish: Copper. Cabinet: Factory-fabricated, stainless steel, for [recessed] [surface] mounting and with hinged, stainless-steel door.

STRAINERS FOR DOMESTIC WATER PIPING Y-Pattern Strainers: 1. 2.

3. 4. 5.

Pressure Rating: 125 psig minimum, unless otherwise indicated. Body: Bronze for NPS 2 and smaller; cast iron with interior lining complying with AWWA C550 or FDA-approved, epoxy coating and for NPS 2-1/2 and larger. Threaded for NPS 2 and smaller; flanged for End Connections: NPS 2-1/2 and larger. Screen: Stainless steel with round perforations, unless otherwise indicated. Perforation Size: a. b. c.

6.

Strainers NPS 2 and Smaller: 0.033 inch. Strainers NPS 2-1/2 to NPS 4: 0.062 inch. Strainers NPS 5 and Larger: 0.125 inch.

Drain:

Factory-installed, hose-end drain valve.

DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 6

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION 2.7 A.

OUTLET BOXES Clothes Washer Outlet Boxes: 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2. 3. 4.

5. 6. 7.

8.

2.8 A.

Acorn Engineering Company. Guy Gray Manufacturing Co., Inc. IPS Corporation. Zurn Plumbing Products Group; Light Commercial Operation.

Mounting: Recessed. Material and Finish: Enameled-steel or epoxy-painted-steel box and faceplate. Faucet: Combination, valved fitting or separate hot- and coldwater, valved fittings complying with ASME A112.18.1. Include garden-hose thread complying with ASME B1.20.7 on outlets. Supply Shutoff Fittings: NPS 1/2 ball valves and NPS 1/2 copper, water tubing. Drain: NPS 2 standpipe and P-trap for direct waste connection to drainage piping. Inlet Hoses: Two 60-inch- long, rubber household clothes washer inlet hoses with female, garden-hose-thread couplings. Include rubber washers. Drain Hose: One 48-inch- long, rubber household clothes washer drain hose with hooked end.

HOSE BIBBS Hose Bibbs: (HB-1) 1. 2. 3. 4. 5. 6. 7.

8. 9. 10. 11. 12. 13. 14. 15.

Standard: ASME A112.18.1 for sediment faucets. Body Material: Bronze. Seat: Bronze, replaceable. Supply Connections: NPS 1/2 or NPS 3/4 threaded or solder-joint inlet. thread complying with Outlet Connection: Garden-hose ASME B1.20.7. Pressure Rating: 125 psig. Vacuum Breaker: Integral or field-installation, nonremovable, drainable, hose-connection vacuum breaker complying with ASSE 1011. Finish for Equipment Rooms: Rough bronze, or chrome or nickel plated. Finish for Service Areas: Chrome or nickel plated. Finish for Finished Rooms: Chrome or nickel plated. Operation for Equipment Rooms: Wheel handle or operating key. Operation for Service Areas: Wheel handle. Operation for Finished Rooms: Operating key. Include operating key with each operating-key hose bibb. Include integral wall flange with each chrome- or nickel-plated hose bibb.

DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 7

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION 2.9 A.

WALL HYDRANTS Nonfreeze Exterior Wall Hydrants: (WH-1) 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b. c. d.

2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

2.10 A.

A.

Standard: ASME A112.21.3M for concealed -outlet, self-draining wall hydrants. Pressure Rating: 125 psig. Operation: Loose key. Casing and Operating Rod: Of length required to match wall thickness. Include wall clamp. Inlet: NPS 3/4. Outlet: Concealed, with integral vacuum breaker and garden-hose thread complying with ASME B1.20.7. Box: Deep, flush mounting with cover. Box and Cover Finish: Polished nickel bronze. Outlet: Exposed, with integral vacuum breaker and garden-hose thread complying with ASME B1.20.7. Nozzle and Wall-Plate Finish: Polished nickel bronze. Operating Keys: One with each wall hydrant.

DRAIN VALVES Ball-Valve-Type, Hose-End Drain Valves: 1. 2. 3. 4. 5. 6. 7. 8. 9.

2.11

Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. Watts Drainage Products Inc. Woodford Manufacturing Company. Zurn Plumbing Products Group; Light Commercial Operation.

Standard: MSS SP-110 for standard-port, two-piece ball valves. Pressure Rating: 400-psig minimum CWP. Size: NPS 3/4. Body: Copper alloy. Ball: Chrome-plated brass. Seats and Seals: Replaceable. Handle: Vinyl-covered steel. Inlet: Threaded or solder joint. Outlet: Threaded, short nipple with garden-hose thread complying with ASME B1.20.7 and cap with brass chain.

WATER HAMMER ARRESTERS Water Hammer Arresters: (WHA) 1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following: a. b.

MIFAB, Inc. PPP Inc. DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 8

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION c. d. 2. 3. 4.

2.12 A.

Standard: ASSE 1010 or PDI-WH 201. Type: Copper tube with piston. Size: ASSE 1010, Sizes AA and A through F or PDI-WH 201, Sizes A through F.

AIR VENTS Bolted-Construction Automatic Air Vents: 1. 2. 3. 4. 5. 6.

B.

Sioux Chief Manufacturing Company, Inc. Watts Drainage Products Inc.

Body: Bronze. Pressure Rating: 125-psig minimum pressure rating at 140 deg F. Float: Replaceable, corrosion-resistant metal. Mechanism and Seat: Stainless steel. Size: NPS 1/2 minimum inlet. Inlet and Vent Outlet End Connections: Threaded.

Welded-Construction Automatic Air Vents: 1. 2. 3. 4. 5. 6.

Body: Stainless steel. Pressure Rating: 150-psig minimum pressure rating. Float: Replaceable, corrosion-resistant metal. Mechanism and Seat: Stainless steel. Size: NPS 3/8 minimum inlet. Inlet and Vent Outlet End Connections: Threaded.

PART 3 - EXECUTION

3.1

INSTALLATION

A.

Refer to Division 22 Section "Common Work Results for Plumbing" for piping joining materials, joint construction, and basic installation requirements.

B.

Install backflow preventers in each water supply to mechanical equipment and systems and to other equipment and water systems that may be sources of contamination. Comply with authorities having jurisdiction. 1. 2.

3.

Locate backflow preventers in same room as connected equipment or system. Install drain for backflow preventers with atmospheric-vent drain connection with air-gap fitting, fixed air-gap fitting, or equivalent positive pipe separation of at least two pipe diameters in drain piping and pipe to floor drain. Locate airgap device attached to or under backflow preventer. Simple air breaks are not acceptable for this application. Do not install bypass piping around backflow preventers.

DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 9

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION C.

Install water regulators with bypass with memory-stop valve. outlet.

D.

Install balancing adjusted.

E.

Install temperature-actuated water mixing valves with check stops or shutoff valves on inlets and with shutoff valve on outlet. 1.

valves

in

inlet and outlet shutoff valves and Install pressure gages on inlet and

locations

where

they

can

easily

be

Install thermometers and water regulators if specified.

F.

Install Y-pattern strainers for water on supply side of each water pressure-reducing valve, solenoid valve, and pump.

G.

Install outlet boxes recessed in wall. Install 2-by-4-inch fireretardant-treated-wood blocking wall reinforcement between studs. Fire-retardant-treated-wood blocking is specified in Division 06 Section "Rough Carpentry."

H.

Install WH 201.

I.

Install air vents at high points of water piping. Install drain piping and discharge onto floor drain.

3.2

water

hammer

arresters

in

water

piping

according

to

PDI-

CONNECTIONS

A.

Piping installation requirements are specified in other Division 22 Sections. Drawings indicate general arrangement of piping and specialties.

B.

Ground equipment according to Bonding for Electrical Systems."

C.

Connect wiring according to Division 26 Electrical Power Conductors and Cables."

3.3 A.

Section

"Grounding

Section

and

"Low-Voltage

LABELING AND IDENTIFYING Equipment Nameplates and Signs: Install engraved plastic-laminate equipment nameplate or sign on or near each of the following: 1. 2. 3. 4. 5.

B.

Division 26

Reduced-pressure-principle backflow preventers. Double-check backflow-prevention assemblies. Double-check, detector-assembly backflow preventers. Water pressure-reducing valves. Primary, thermostatic, water mixing valves.

Distinguish among multiple units, inform operator of operational requirements, indicate safety and emergency precautions, and warn of hazards and improper operations, in addition to identifying unit. Nameplates and signs are specified in Division 22 Section "Identification for Plumbing Piping and Equipment." DOMESTIC WATER PIPING SPECIALTIES 22 11 19 - 10

(45307035)

ST. VINCENT COLLEGE SIS AND HERMAN DUPRÉ SCIENCE PAVILION 3.4 A.

FIELD QUALITY CONTROL Perform the following tests and prepare test reports: 1.

B.

3.5

Test each pressure vacuum breaker, reduced-pressure-principle backflow preventer, double-check backflow-prevention assembly and double-check, detector-assembly backflow preventer according to authorities having jurisdiction and the device's reference standard.

Remove and replace malfunctioning domestic water piping specialties and retest as specified above.

ADJUSTING

A.

Set field-adjustable pressure set points of water pressure-reducing valves.

B.

Set field-adjustable flow set points of balancing valves.

C.

Set field-adjustable temperature set points of temperature-actuated water mixing valves.

END OF SECTION 22 11 19