Engineering Data
ED15063-5 Group: Controls Part Number: ED 15063 Date: June 2013 Supersedes: ED15063-4
MicroTech® II Chiller Unit Controller Protocol Information Modbus® Protocol
WSC
Water-Cooled Centrifugal, Single-Compressor
WDC
Water-Cooled Centrifugal, Dual-Compressor
WPV
Water-Cooled Centrifugal, Single-Compressor
HSC
Water-Cooled Single-Compressor Centrifugal, Heat Recovery
HDC
Water-Cooled Dual-Compressor Centrifugal, Heat Recovery
TSC
Water-Cooled Single-Compressor Centrifugal, Templifier
WMC
Water-Cooled Centrifugal, Magnetic Bearing
WCC
Water-Cooled Centrifugal, Counterflow
AGZ
Air-Cooled Global Scroll
ACZ
Air-Cooled Scroll Condensing Unit
WGZ
Water-Cooled Global Scroll
AGS
Air-Cooled Global Screw
WGS
Water-Cooled Global Screw
TGZ
Templifier™ Water Heater
© 2013 Daikin McQuay
Table of Contents TABLE OF CONTENTS........................................................................................................................................................ 2 LIMITED WARRANTY .............................................................................................................................................................. 4 NOTICE .................................................................................................................................................................................. 4 REVISION HISTORY ............................................................................................................................................................... 4 SOFTWARE REVISION ........................................................................................................................................................... 4 REFERENCE DOCUMENTS .................................................................................................................................................... 4 INTRODUCTION .................................................................................................................................................................... 6 CHILLER MODELS ................................................................................................................................................................. 6 CONTROLLER DATA POINTS ................................................................................................................................................. 6 MODBUS PROTOCOL INFORMATION ............................................................................................................................ 7 COMPATIBILITY ...................................................................................................................................................................... 7 PROTOCOL DEFINITIONS ...................................................................................................................................................... 7 VALID FUNCTION CODES ...................................................................................................................................................... 7 VALID ERROR CODES ........................................................................................................................................................... 8 MODBUS DATA POINT ........................................................................................................................................................... 8 EXAMPLE DATA POINT: CHILLER ENABLE ............................................................................................................................ 8 CONFIGURING THE UNIT CONTROLLER ................................................................................................................................ 8 SET UP THE UNIT FOR NETWORK CONTROL ........................................................................................................................ 8 TYPICAL APPLICATION: MINIMUM INTEGRATION ..................................................................................................... 9 DISPLAY IMPORTANT DATA POINTS ..................................................................................................................................... 9 COMPREHENSIVE DATA POINT TABLES ................................................................................................................... 10 MODBUS DATA POINTS ....................................................................................................................................................... 10 DETAILED DATA POINT INFORMATION ...................................................................................................................... 13 ACTIVE SETPOINT ............................................................................................................................................................... 14 ACTUAL CAPACITY .............................................................................................................................................................. 14 ACTUAL RPM ...................................................................................................................................................................... 14 CAPACITY LIMIT OUTPUT .................................................................................................................................................... 14 CAPACITY LIMIT SETPOINT ................................................................................................................................................. 14 CAVITY TEMPERATURE ....................................................................................................................................................... 15 COMPRESSOR DISCHARGE TEMPERATURE ....................................................................................................................... 15 CHILLER ENABLE ................................................................................................................................................................ 15 CHILLER LIMITED................................................................................................................................................................. 15 CHILLER LOCAL/REMOTE ................................................................................................................................................... 15 CHILLER MODE OUTPUT ..................................................................................................................................................... 15 CHILLER MODE SETPOINT .................................................................................................................................................. 16 COMPRESSOR 2 ACTIVE CAPACITY LIMIT ............................................................................................................................ 16 CHILLER STATUS ................................................................................................................................................................ 16 CHILLER POWER .................................................................................................................................................................. 16 COMPRESSOR CURRENT .................................................................................................................................................... 16 COMPRESSOR DISCHARGE TEMPERATURE ....................................................................................................................... 17 COMPRESSOR PERCENT RLA ............................................................................................................................................ 17 COMPRESSOR POWER ....................................................................................................................................................... 18 COMPRESSOR RUN HOURS ................................................................................................................................................ 18 COMPRESSOR SELECT .......................................................................................................................................................... 19 COMPRESSOR STARTS ....................................................................................................................................................... 19 COMPRESSOR SUCTION LINE TEMPERATURE ................................................................................................................... 20 COMPRESSOR VOLTAGE .................................................................................................................................................... 20 CONDENSER ENTERING WATER TEMPERATURE ............................................................................................................... 21 CONDENSER FLOW SWITCH STATUS ................................................................................................................................. 21 2
ED 15063-5
CONDENSER LEAVING WATER TEMPERATURE .................................................................................................................. 21 CONDENSER PUMP RUN HOURS ........................................................................................................................................ 21 CONDENSER REFRIGERANT PRESSURE ............................................................................................................................. 21 CONDENSER SATURATED REFRIGERANT TEMPERATURE .................................................................................................. 21 CONDENSER WATER FLOW RATE ...................................................................................................................................... 22 CONDENSER WATER PUMP STATUS ..................................................................................................................................... 22 COOL SETPOINT .................................................................................................................................................................. 22 DESIGN RPM ...................................................................................................................................................................... 22 EVAPORATOR ENTERING WATER TEMPERATURE .............................................................................................................. 22 EVAPORATOR FLOW SWITCH STATUS ................................................................................................................................ 22 EVAPORATOR LEAVING WATER TEMPERATURE FOR UNIT ................................................................................................ 22 EVAPORATOR LEAVING WATER TEMPERATURE FOR COMPRESSOR ................................................................................. 23 EVAPORATOR PUMP RUN HOURS ...................................................................................................................................... 23 EVAPORATOR REFRIGERANT PRESSURE ........................................................................................................................... 23 EVAPORATOR SATURATED REFRIGERANT TEMPERATURE ................................................................................................ 23 EVAPORATOR WATER FLOW RATE ..................................................................................................................................... 24 EVAPORATOR WATER PUMP STATUS ................................................................................................................................. 24 HEAT RECOVERY ENTERING WATER TEMPERATURE ........................................................................................................ 24 HEAT RECOVERY LEAVING WATER TEMPERATURE ........................................................................................................... 24 HEAT SETPOINT .................................................................................................................................................................. 24 ICE SETPOINT ...................................................................................................................................................................... 24 IGV PERCENTAGE OPEN .................................................................................................................................................... 24 INVERTER TEMPERATURE ................................................................................................................................................... 25 LIQUID LINE REFRIGERANT PRESSURE .............................................................................................................................. 25 LIQUID LINE REFRIGERANT TEMPERATURE ........................................................................................................................ 25 MAXIMUM RPM ................................................................................................................................................................... 25 MINIMUM RPM .................................................................................................................................................................... 25 OIL FEED PRESSURE .......................................................................................................................................................... 26 OIL FEED TEMPERATURE .................................................................................................................................................... 26 OIL SUMP PRESSURE .......................................................................................................................................................... 26 OIL SUMP TEMPERATURE ................................................................................................................................................... 26 OUTDOOR AIR TEMPERATURE ............................................................................................................................................ 27 PUMP SELECT ..................................................................................................................................................................... 27 RUN ENABLED ..................................................................................................................................................................... 27 ALARMS ................................................................................................................................................................................ 28 ALARM CLASSES ................................................................................................................................................................. 28 FAULT ALARMS .................................................................................................................................................................... 28 PROBLEM ALARMS .............................................................................................................................................................. 28 WARNING ALARMS .............................................................................................................................................................. 28 ALARM HANDLING ............................................................................................................................................................... 28 ALARM DIGITAL OUTPUT ..................................................................................................................................................... 28 CLEAR ALARMS ................................................................................................................................................................... 28 ACTIVE ALARMS .................................................................................................................................................................. 29 INDEX OF DETAILED POINT INFORMATION ............................................................................................................... 34
3
ED 15063-5
Limited Warranty Consult your local Daikin McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local Daikin McQuay Representative, go to www.daikinmcquay.com.
Notice © 2013 Daikin McQuay, Minneapolis MN. All rights reserved throughout the world. Daikin McQuay reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application. ™ ® The following are trademarks or registered trademarks of their respective companies. Modbus is a registered trademark of Gould, Inc. Windows is a registered trademark of Microsoft Corporation. MicroTech II is a registered trademark of Daikin McQuay.
Revision History ED 15063-0 ED 15063-1
May 15, 2003 May 18, 2005
ED 15063-2
Nov 22, 2005
ED 15063-3
April 14, 2009
ED 15063-5
Jan 21, 2013
Preliminary release. Added points for Solid State Starter – Current, Voltage, Power and Power Factor Corrected some incorrect register listings Changed doc to have only Holding Registers and Coils Added WGS and WMC data Added WMC, HSC HDC, and TSC to front page and Chiller Model table Added WCC to front page and Chiller Model table Corrected Modbus Alarms table Added Compressor Current, Compressor Power and Compressor Voltage to the Compressor Select Table Added TGZmodel to all applicable tables. Removed reference to OITS panel and added reference to unit keypad details in the “Set up unit for network control” section. Added Index column to Comphrenesive Data Point table; corrected Chiller Status holding register in table and also in detailed data section. Removed reference to Chiller On/Off--use Run Enabled instead. Added individual compressor data points.
Software Revision This edition documents all versions of the standard MicroTech II® Chiller Unit Controller firmware and all subsequent revisions until otherwise indicated.
Reference Documents Company
Number
Title
Source
McQuay International
IOMM WSC WDC
The McQuay DISTINCTION Series Single/Dual Compressor Centrifugal Chillers Installation, Operating and Maintenance Manual
www.mcquay.com
McQuay International
OM CentrifMicro II
McQuay International
IM 743
McQuay International
IMM AGS IMM AGSB
McQuay International
IOMM ACZ/AGZ
McQuay International
IOMM ACZ
McQuay International
4
MicroTech II Controller for Centrifugal Chillers and Templifiers Operating Manual MicroTech II Chiller Unit Controller Modbus Communication Module Installation Manual GeneSys Air-Cooled Screw Compressor Chiller Air-Cooled Scroll Condensing Unit & Air-Cooled Scroll Chiller w/Remote Evaporators Installation, Operation, and Maintenance Manual Air-Cooled Scroll Condensing Unit Installation, Operation, and Maintenance Manual
www.mcquay.com www.mcquay.com www.mcquay.com www.mcquay.com www.mcquay.com
IOMM AGZ IOMM AGZ1
Air-Cooled Scroll Compressor Chiller & Air-Cooled Scroll Compressor Water Chiller Installation, Operation, and Maintenance Manual
www.mcquay.com
McQuay International
IOMM WGZ
Water-Cooled Scroll Compressor Chiller Installation, Operation and Maintenance Manual
www.mcquay.com
McQuay International
IOMM WPV
WPV Centrifugal Compressor Chillers Installation, Operating and Maintenance Manual
www.mcquay.com
ED 15063-5
McQuay International
OM AGS
McQuay International
IOMM TSC
McQuay International
OMM TGZ
Modbus-IDA.ORG Modbus-IDA.ORG
5
GeneSys Air-Cooled Screw Compressor Chiller Operation Manual MicroTech II Templifier Single Compressor Centrifugal Installation, Operation, and Maintenance Manual MicroTech II Templifier TGZ Heat Recovery Water Heaters Operating Manual MODBUS Application Protocol Specification V1.1b MODBUS over Serial Line Specification and Implementation Guide V1.02
www.mcquay.com www.mcquay.com www.mcquay.com www.Modbus.org www.Modbus.org
ED 15063-5
Introduction This document contains the necessary information to incorporate a MicroTech II Chiller Unit Controller from Daikin McQuay into your Building Automation System (BAS). It includes all necessary Modbus variables and corresponding MicroTech II Chiller Unit Controller data points. Modbus terms and principles are not defined. Refer to the appropriate specifications for definitions and details.
Chiller Models The following table lists the model designators of Daikin McQuay Chiller units and the corresponding description. WSC Water-Cooled Centrifugal, Single-Compressor WDC Water-Cooled Centrifugal, Dual-Compressor WPV Water-Cooled Centrifugal, Single-Compressor HSC Water-Cooled Single-Compressor Centrifugal, Heat Recovery HDC Water-Cooled Dual-Compressor Centrifugal, Heat Recovery TSC Water-Cooled Single-Compressor Centrifugal, Templifier WMC Water-Cooled Centrifugal, Magnetic Bearing WCC Water-Cooled Centrifugal, Counterflow AGZ Air-Cooled Global Scroll ACZ Air-Cooled Scroll Condensing Unit WGZ Water-Cooled Global Scroll AGS Air-Cooled Global Screw WGS Water-Cooled Global Screw TGZ Templifier™ Water Heater
Controller Data Points The MicroTech II Chiller Unit Controller contains data points or unit variables that are accessible from three different user interfaces: the unit keypad/display, the Operator Interface Touch Screen, or a Modbus serial network. Not all points are accessible from each interface. This manual lists all important data points and the corresponding network path for each applicable interface. Refer to the applicable Operation Manual for keypad/display and Operator Interface Touch Screen details. See Reference Documents on page 4 for manual part numbers.
6
ED 15063-5
Modbus Protocol Information Compatibility The MicroTech II Chiller Unit Controller can be configured in an interoperable Modbus network. The controller must have the corresponding Modbus Communication Module installed. The MicroTech II Chiller Unit Controller conforms to the Modbus Standards published at www.Modbus.org. See the Reference Documents on page 4.
Protocol Definitions The Modbus protocol is a standardized Application Level (OSI Level 7) protocol used in interoperable Industrial Control networks. Modbus provides the communication infrastructure necessary to integrate products manufactured by different vendors and to integrate control services that are now independent. It specifies how requests from the client are sent to a server and how servers reply. The client constructs a PDU (protocol data unit) and sends it to a specific server or broadcasts it to all servers. The PDU contains a function code that defines the action the client is requesting from the server(s). The PDU also includes a data field that further defines the action to the server, for example, the location of the data to be read. A normal reply from a server includes the same function code and a response data field. In the case of a read operation, the response data field contains the requested data. In the case of a write operation, the response data field contains an echo of the write data of the request command. If the server detects an error in the transmission, the reply to the client includes and exception function code and the response data field contains an exception code. Controllers can communicate on standard Modbus networks using one of two transmission modes: ASCII or RTU. Users select the serial port communication parameters (baud rate, parity mode, etc), during configuration of the controller. The mode and serial parameters must be the same for all devices on a Modbus network. Transmission mode determines how information is packed into the message fields and decoded. In RTU mode, each byte contains two hexadecimal characters, and in ASCII mode, each byte contains one ASCII character. The MicroTech II Chiller Unit Controller uses the RTU mode only. The MicroTech II Chiller Unit Controller uses the following data structure: 8 data bits, 1 or 2 stop bits, and no parity bit. It uses data transmission rates from 1200 to 19200 bps.
Valid Function Codes The MicroTech II Chiller Unit Controller supports eight public function codes. Function Code
Description
Definition
04 (0x04)
Read Input Registers
05 (0x05)
Write Single Coil
This function code reads status from 1 to 2000 contiguous coils in a remote device. This function code reads status from 1 to 2000 contiguous discrete inputs in a remote device. This function code reads the contents of a contiguous block of holding registers in a remote device. This function code reads from 1 to approx. 125 contiguous input registers in a remote device. This function code writes a single output to either ON or OFF in a remote device.
06 (0x06)
Write Single Register
This function code writes a single holding register in a remote device.
15 (0x0F)
Write Multiple Coils
16 (0x10)
Write Multiple Registers
01 (0x01)
Read Coils
02 (0x02)
Read Discrete Inputs
03 (0x03)
Read Holding Registers
7
This function code forces each coil in a sequence of coils to either ON or OFF in a remote device. This function code writes a block of contiguous registers (1 to approx. 120 registers) in a remote device.
ED 15063-5
Valid Error Codes The MicroTech II Chiller Unit Controller supports three error or exception codes. Error Codes Description Definition 01 02 03
Illegal Function Illegal Data Address Illegal Data Value
The function code received in the query is not an allowable action for the server (or slave). The data address received in the query is not an allowable address for the server (or slave). A value contained in the query data field is not an allowable value for server (or slave).
Modbus Data Point Each data point accessible from a Modbus network is described with a table that gives the data type and index. If the data point represents an enumerated variable, the enumerations are also listed.
Example Data Point: Chiller Enable This output data point indicates the current state of the chiller. The OFF state is represented by 0, and the ON state is represented by 1. (D2) Data Type
Index
Measurement
Units
Valid Range
Coil
2
Chiller State
NA
0 = Disable (Off) 1 = Enable (On)
Data Type
Data is represented as either single-bit elements or 16-bit elements. A single-bit element is referred to as a Discrete Input when it refers to read-only data and as a Coil when it refers to read-write data. A 16-bit element is referred to as a Input Register when it refers to read-only data and as an Holding Register when it refers to read-write data. Index
There can be as many as 65,536 elements of each data type in a Modbus device. Data elements are numbered from 1 to 65,536 in each type. Data elements are addressed with an index in the range from 0 to 65,535. The index is not the address of the data element in the unit controller memory. The index is used in Modbus PDUs to specify the location of the data in the unit controller. This means, for example, that data element number 1 is addressed using index 0 in the PDU. Valid Range
Some properties are standard data types and some are enumerated sets. If the property value represents a range of values, e.g., temperature or pressure, a range of values is given. If the property value is an enumerated set, all enumerated values and corresponding meaning are given.
Configuring the Unit Controller The MicroTech II Chiller Unit Controller and the Modbus Communication Module together are designed, programmed, and configured at the factory to be a chiller unit controller accessible over a Modbus network. No additional programming is required to make this a chiller unit controller. The unit controller is ready to operate with the default values of the various parameters set at the factory. Default values may be changed with the unit keypad or via the network. Parameters must be adjusted to accommodate your particular network. See the appropriate Operation Manual for default values and keypad operating instructions and the Modbus Communication Module Installation Manual (see Reference Documents section for manual part numbers.) When you have integrated the unit into your network, you can monitor and control unit operation from your workstation. At a minimum, you can: • Display and monitor data points • Turn the unit on or off • Operate the unit safely
Set up the Unit for Network Control Setup for Centrifugal Chiller MicroTech II Network Control:
1. 2. 8
Disable the chiller. The chiller should not be operating while performing this setup. At the chiller unit keypad: ED 15063-5
a. In the Set Unit Setpoint screen 14, set the BAS Protocol to Modbus. Use the Manager Password of “2001.” b. In the Set Unit Setpoint screen 1, set the Control Source to Local. Verify with the chiller/control company technician that the chiller is operational on BAS. In the Set Unit Setpoint screen 1, set the Control Source to BAS.
3. 4.
Setup for all Other Chillers MicroTech II Network Control:
1. 2. 3. 4.
Set the Set Unit Setpoint screen 1 initially to Source = Keypad. Verify that Modbus is selected as the Protocol in the applicable menu screen shown in the table below. Verify with the chiller/control company technician that the chiller is operational on a BAS. Set the Unit Setpoint screen 1 to Source = Network.
Model Menu Screen Password
AGZ-A
ACZ-A
AGZ-B
ACZ-B
7 2001
6 2001
10 2001
7 2001
AGS-A, B, DP 12 8945
AGS-C
AGS-D
WGS
WGZ/TGZ
16 8453
17 8745
15 8745
10 2001
NOTE: Models AGZ-A/B, ACZ-A/B, and WGZ have one unit controller, while models AGS-B/C and WGS have one unit controller and multiple circuit controllers. Unit settings for AGS-B/C and WGS models are adjusted on the unit controller.
Typical Application: Minimum Integration Display Important Data Points Typical workstation displays of MicroTech II Unit Controller attributes include the following significant data points (page number of detailed description in parenthesis). Each data point is identified with a number that also identifies it in the Comprehensive Data Point Tables. These data points are also shaded in the comprehensive tables so that you can distinguish them. References in the text of this section also identify these data points with a number and shading. Table 1: Significant Data Points
No.
Configuration
No.
1
Chiller Status (12)
2
Chiller Mode Setpoint (12)
5 6
3
Actual Capacity (11)
7
4
Chiller Enable (11)
8
Temperatures Evaporator Entering Water Temperature (16) Evaporator Leaving Water Temperature (16) Condenser Entering Water Temperature (15) Condenser Leaving Water Temperature (15)
No.
Setpoints
No.
Alarms
9
Cool Setpoint (16)
11
Alarm Digital Output (20)
10
Capacity Limit Setpoint (11)
12
Clear Alarms (20)
13
Active Alarms (21)
You can display any number of additional data points based on job requirements or individual preference. See Modbus Data Points on page 8 for lists of all Modbus Variables available to the network. For a more detailed description of all available data points, see the Detailed Data Point Information section on page 13 of this document.
9
ED 15063-5
Comprehensive Data Point Tables Modbus Data Points Note: See the appropriate Operation Manual for specific data ranges and default values. Network Control Property Active Setpoint Actual Capacity (3) Actual RPM Compressor #1 Compressor #2 Capacity Limit (Output) (10) Capacity Limit Setpoint (10) Cavity Temperature Compressor #1 Compressor #2 Chiller Enable (Input) (4) Chiller Limited Chiller Local/Remote Chiller Mode Output Chiller Mode Setpoint Compressor 2 Active Capacity Limit
Page
Read/ Write
14 14 14
R R R
14 14 15
R W R
Data Type
Index
Description
Holding Register Holding Register
40003 40011
-40°- 199°F 0 - 160% 0-32678
Holding Register Holding Register Holding Register Holding Register
40247 40251 40043 40004
0 - 160% 0 - 160%
40086 40106 2 7 6 40148 40146
0=Off, 1=On 0=Not Limited, 1=Limited 0=Remote, 1=Local 1=ICE, 2=COOL, 3=HEAT 1=ICE, 2=COOL, 3=HEAT
40108
15 15 15 15 16
R/W R R R R/W
Holding Register Holding Register Coil Coil Coil Holding Register Holding Register
16
R
Holding Register
*Chiller Status (1)
16
R
Holding Register
40147
Chiller Power Compressor Current Compressor Select Compressor #2 Compressor #3 Compressor #4 Compressor #5 Compressor #6
16 16
R R
Holding Register
40245
Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register
40027 40096 40110 40115 40120 40125
Compressor Discharge Temperature Compressor Select Compressor #2
17
Holding Register Holding Register
40020 40092
Compressor Percent RLA Compressor Select Compressor #2 Compressor #3 Compressor #4 Compressor #5 Compressor #6
17
Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register
40026 40095 40109 40114 40119 40124
Compressor Power Compressor Select Compressor #2 Compressor #3 Compressor #4 Compressor #5 Compressor #6 Compressor Run Hours Compressor Select Compressor #2 Compressor #3
18
Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register
40028 40097 40111 40116 40121 40126
Holding Register Holding Register Holding Register
40175 40236 40239
10
18
WSC, WDC, WPV, 0=Off, 1=Start, WMC, WCC, HSC, 2=Run, 3=PreTSC, HDC Models Shutdown, 4=Service ACZ, AGS, AGZ, 1=Off, 2=Start, WGS, WGZ, TGZ 3=Run, 4=PreModels Shutdown, 5=Service Totalized compressor kilowatts. 0 - 65,535
R
R
R
-460°- 621°F -460°- 621°F 0 -110%
0 - 65,535
R
0 - 65,535
ED 15063-5
Network Control Property Compressor #4 Compressor Select Compressor Starts Compressor Select Compressor #2 Compressor #3 Compressor #4 Compressor Suction Line Temperature Compressor Select Compressor #2 Compressor Voltage Compressor Select Compressor #2 Compressor #3 Compressor #4 Compressor #5 Compressor #6 *Condenser Entering Water Temperature (7) Condenser Flow Switch Status *Condenser Leaving Water Temperature (8) Condenser Pump Run Hours Pump Select Pump #2 Condenser Refrigerant Pressure Compressor Select Compressor #2 Condenser Saturated Refrigerant Temperature Compressor Select Compressor #2
Page
Read/ Write
18 19
R/W R
20
20
Holding Register Holding Register
40242 40161
Holding Register Holding Register Holding Register Holding Register
40174 40235 40238 40241
Holding Register
40016
-40°- 244°F
Holding Register
40089
-40°- 244°F
Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register
40030 40099 40113 40118 40123 40128
R
Description See page 13 0 - 65,535
0 - 65,535
20
R
Holding Register
40008
-40° - 244°F
21
R
Coil
9
0=No Flow, 1=Flow
21
R
Holding Register
40009
-40° - 244°F
21
R Holding Register Holding Register
40177 40233
0 - 65,535 0 - 32767
Holding Register Holding Register
40022 40094
-3276.8 – 3276.7 psi -3276.8 – 3276.7 psi
Holding Register
40021
-40° - 244°F
Holding Register
40093
-40° - 244°F
Holding Register
40025
0 - 65,535 (Requires field provided flow measurement device)
Holding Register Holding Register
40254 40255
Holding Register Holding Register
40249 40253
Holding Register Holding Register
40087 40107
Holding Register Holding Register
40246 40250 40248 40252 32 40002
0=Pump Off Request, 1=Pump On Request 10 - 120°F
21
21
R
R
22
R
Design RPM
22
R
11
Index
R
Condenser Water Flow Rate Compressor #1 Compressor #2 IGV Percentage Open Compressor #1 Compressor #2 Inverter Temperature Compressor #1 Compressor #2 Maximum RPM Compressor #1 Compressor #2 Minimum RPM Compressor #1 Compressor #2 Condenser Water Pump Status *Cool Setpoint (9) *Evaporator Entering Water Temperature (5) Evaporator Flow Switch Status Evaporator Leaving Water Temperature for Unit(6) *Evaporator Leaving Water Temperature for Compressor
Data Type
24 R 25
25
25
R
R
0-32678
R
0-32678
22 22
R R/W
Holding Register Holding Register Coil Holding Register
22
R
Holding Register
40005
-40° - 244°F
22
R
Coil
8
0=No Flow, 1=Flow
22
R
Holding Register
40007
-40° - 244°F
23
R Holding Register
40015
-40° - 244°F
ED 15063-5
Network Control Property
Read/ Write
Page
Compressor Select Compressor #2 Evaporator Pump Run Hours Pump Select Pump #2 Evaporator Refrigerant Pressure Compressor Select Compressor #2
23
23
Evaporator Water Flow Rate
24
Index
Description
Holding Register
40088
-40° - 244°F
Holding Register Holding Register
40176 40232
0 – 65,535 0 – 65,535
Holding Register Holding Register
40018 40091
-3276.8 – 3276.7 psi -3276.8 – 3276.7 psi
Holding Register Holding Register
40017 40090
Holding Register
40019 30
-40° - 244°F -40° - 244°F 0 - 65,535 (Requires field provided flow measurement device) 0=Pump Off Request, 1=Pump On Request
40023
-40° - 244°F
40024
-40° - 244°F
40006 40051
50° - 120°F 15 - 35°F, Default=25°F
40039
-22592 - 22591 psi
40037 40105
-40°- 244°F -40°- 244°F
40033 40101
-22592 - 22591 psi -22592 - 22591 psi
40035 40103
-40° - 244°F -40° - 244°F
40034 40102
-22592 - 22591 psi -22592 - 22591 psi
40036 40104 40040 20 3
-40° - 244°F -40° - 244°F -40° - 244°F 0=Pump No. 1, 1=Pump No. 2 0=OFF, 1=Run Allowed
R
23
Evaporator Saturated Refrigerant Temperature Compressor Select Compressor #2
Data Type
R
R
R
Evaporator Water Pump Status 24 R Coil Heat Recovery Entering Water 24 R Holding Register Temperature Heat Recovery Leaving Water 24 R Holding Register Temperature Heat Setpoint 24 R/W Holding Register Ice Setpoint 24 R/W Holding Register Liquid Line Refrigerant 25 R Holding Register Pressure 25 R Liquid Line Refrigerant Temperature Compressor Select Holding Register Compressor #2 Holding Register 26 R Oil Feed Pressure Holding Register Compressor Select Compressor #2 Holding Register 26 R Oil Feed Temperature Compressor Select Holding Register Compressor #2 Holding Register 26 R Oil Sump Pressure Holding Register Compressor Select Compressor #2 Holding Register 26 R Oil Sump Temperature Compressor Select Holding Register Compressor #2 Holding Register Outdoor Air Temperature 27 R Holding Register Pump Select 27 R/W Coil Run Enabled 27 R Coil *Boldface indicates data points required for typical minimum integration.
Chiller Alarm Variables Network Control Property Alarm Digital Output (11) Clear Alarms (12) Active Alarms (13)
12
Page
Read/Write
28 28 29
Data Type
Index
Description
R
Coil
4
0-No Alarm, 1=Alarm
R/W
Coil
25
Holding Register
4013040145
0=Normal, 1=Clear Alarm 16 Holding Registers: Each bit representing an alarm condition
R
ED 15063-5
Detailed Data Point Information This section lists the information (the data) that is available to the Industrial Control System via the Modbus RTU protocol. This information is used to safely operate and log the performance of the chiller. The systems integrator also uses this information when creating custom graphics. Table 2: Data Points for Chiller Models
Data Point Active Alarms Active Setpoint Actual Capacity Actual RPM Alarm Digital Output Capacity Limit Output Capacity Limit Setpoint Cavity Temperature Chiller Enable Chiller Limited Chiller Local/Remote Chiller Mode Output Chiller Mode Setpoint Chiller Status Compressor Current*** Compressor Discharge Temperature Compressor Percent RLA Compressor Power*** Compressor Run Hours Compressor Select Compressor Starts Compressor Suction Line Temperature Compressor Voltage*** Condenser Entering Water Temperature Condenser Flow Switch Status Condenser Leaving Water Temperature Condenser Pump Run Hours Condenser Refrigerant Pressure Condenser Saturated Refrigerant Temperature Condenser Water Flow Rate Condenser Water Pump Status Cool Setpoint Design RPM Evaporator Entering Water Temperature Evaporator Flow Switch Status Evaporator Leaving Water Temperature for Compressor Evaporator Leaving Water Temperature for Unit Evaporator Pump Run Hours Evaporator Refrigerant Pressure Evaporator Saturated Refrigerant Temperature Evaporator Water Flow Rate Evaporator Water Pump Status Heat Recovery Entering Water Temperature Heat Recovery Leaving Water Temperature Heat Setpoint Ice Setpoint IGV Percentage Open Inverter Temperature Liquid Line Refrigerant Pressure Liquid Line Refrigerant Temperature Maximum RPM Minimum RPM Network Clear Alarm Oil Feed Pressure** Oil Feed Temperature** Oil Sump Pressure** Oil Sump Temperature** Outdoor Air Temperature Pump Select Run Enabled
WSC/WDC/WPV/WMC /WCC/HSC/TSC/HDC
AGZ
ACZ
WGZ/TGZ
AGS
WGS
X X X
X X X
X X
X X X
X X X
X X X
X X X
X X* X*
X X* X
X X X
X X X
X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X* X X X X
X X* X X X X
X X X X X X
X X X X
X X X X X X X X
X X X
X X
X X X X X X X X X X
X
X X X X
X X X
X X
X X X
X X X
X X X X
X X
X X
X X
X
X
X X
X
X X
X
X X
X
X
X
X
X
X X
X X
X X
X X
X X
X
X
X
X
X
X
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
*Dual circuit models only
13
X X X X X X X X X
X X
X
X X X X X
X
ED 15063-5
X
X
**Not in WMC model ***Optional. Solid State Starter required
Active Setpoint This output data point indicates the current value of the Leaving Water Temperature setpoint. Based on the operating mode of the chiller, this value is derived from the Cooling Setpoint, Ice Setpoint or Heating Setpoint. The default mode is Cooling and is used unless changed by the Chiller Mode Setpoint. (A2) Data Type Holding Register
Index 40003
Measurement Temperature
Units °F x 10
Valid Range -40°-199°F
Actual Capacity This output data point indicates the percent of capacity the chiller is currently producing. It may be more or less than the nominal capacity of the chiller. (A10) Data Type Holding Register
Index 40011
Measurement Percent of chiller capacity
Units % x 10
Valid Range 0% to 160%
Actual RPM This variable indicates the actual speed of the compressor. (I118 & I122) Compressor #1
Data Type Holding Register
Index 40247
Measurement Revolutions Per Minute
Units RPM
Valid Range 0-32768
Compressor #2
Data Type Holding Register
Index 40251
Measurement Revolutions Per Minute
Units RPM
Valid Range 0-32768
Capacity Limit Output This output data point is a measure of the ratio of operating capacity to full capacity expressed in percent. It indicates the current value of the Capacity Limit Setpoint. (A42) Data Type Holding Register
Index 40043
Measurement Percent of maximum capacity
Units % x 10
Valid Range 0% to 160%.
Capacity Limit Setpoint Capacity Limit is a measure of the ratio of operating capacity to full capacity expressed in percent. This level may be adjusted via an operator workstation or other network device, but cannot be adjusted above a factory-specified limit. If the chiller control source is set to “network” at the unit keypad, this input data point sets the operating value (input) for the chiller. Refer to the appropriate Operation Manual for suitable data point values. (A3). Data Type Holding Register
14
Index 40004
Measurement Percent of maximum capacity
Units % x 10
Valid Range 0% to 160%.
ED 15063-5
Cavity Temperature This output data point indicates the current temperature of the compressor’s motor stator cavity. (A85 & A105) Compressor #1
Data Type Holding Register
Index 40086
Measurement Temperature
Units
Valid Range
Units
Valid Range
°Fx10
Compressor #2
Data Type Holding Register
Index 40106
Measurement Temperature
°Fx10
Compressor Discharge Temperature This output data point indicates the current compressor refrigerant discharge temperature of the compressor selected with Compressor Select on page 18. (A19) Data Type Holding Register
Index 40020
Measurement Temperature
Units °F x 10
Valid Range -460°-621°F
Compressor #2
Data Type Holding Register
Index 40092
Measurement Temperature
Units °F x 10
Valid Range -460°-621°F
Chiller Enable This input data point enables the chiller to run if operating conditions are satisfied, or disables the chiller from running. (D1) Data Type Coil
Index 2
Measurement Chiller State
Units
Valid Range 0 = Disable (Off) 1 = Enable (On)
NA
Chiller Limited This output data point indicates whether chiller operation is limited in some way. If conditions exist that limit operation, the chiller may be prevented from reaching the Leaving Water Temperature setpoint. (D6) Data Type Coil
Index 7
Measurement Status
Units
Valid Range 0 = Not Limited 1 = Limited
NA
Chiller Local/Remote The Local/Remote output data point indicates whether the chiller is in local control or allowed to be controlled remotely over the network. (D5) Data Type Coil
Index 6
Measurement Mode
Units
Valid Range 0= Remote 1 = Local
NA
Chiller Mode Output This output data point indicates the current operating mode of the chiller. (I19) Data Type
15
Index
Measurement
Units
Valid Range
ED 15063-5
Holding Register
40148
HVAC Mode
1. ICE 2. COOL 3. HEAT
NA
Chiller Mode Setpoint The Chiller Mode input data point sets the mode of operation of the chiller from the network. (I17) Data Type Holding Register
Index 40146
Measurement
Units
HVAC Mode
Valid Range 1. ICE 2. COOL 3. HEAT
NA
Compressor 2 Active Capacity Limit This variable indicates the active capacity limit for compressor 2. (A107) Data Type Holding Register
Index 40108
Measurement
Units
Percent
NA
Valid Range 0-100%
Chiller Status This output data point indicates the current state of the chiller. (I18) Data Type
Holding Register
Index
40147
Measurement
Chiller State
Units
Models
Valid Range
WSC, WDC, WPV, WMC, WCC, HSC, TSC, HDC
0=Off, 1=Start, 2=Run, 3=Pre-Shutdown, 4=Service
ACZ, AGS, AGZ, WGS, WGZ,TGZ
1=Off, 2=Start, 3=Run, 4=Pre Shutdown, 5=Service
NA
Chiller Power This variable indicates the totalized compressor kilowatts. (I116). Data Type Index Measurement Holding Register
40245
Electric Power
Units kiloWatts
Valid Range 0-1000
Compressor Current Compressor Select
This output data point indicates the compressor current of the compressor selected with Compressor Select on page 18. (A26) Data Type Index Measurement Units Valid Range Holding Register
40027
Electric Current
Amperes
0 -65,535
Compressor #2
This output data point indicates the compressor 2 current. (A95) Data Type Index Measurement Holding Register
40096
Electric Current
Units Amperes
Valid Range 0 -65,535
Compressor #3
This output data point indicates the compressor 3 current. (A109) Data Type Index Measurement Holding Register
16
40110
Electric Current
Units Amperes
Valid Range 0 -65,535
ED 15063-5
Compressor #4
This output data point indicates the compressor 4 current. (A114) Data Type Index Measurement Holding Register
40115
Electric Current
Units Amperes
Valid Range 0 -65,535
Compressor #5
This output data point indicates the compressor 5 current. (A119) Data Type Index Measurement Holding Register
40120
Electric Current
Units Amperes
Valid Range 0 -65,535
Compressor #6
This output data point indicates the compressor 6 current. (A124) Data Type Index Measurement Holding Register
40125
Electric Current
Units Amperes
Valid Range 0 -65,535
Compressor Discharge Temperature This output data point indicates the current compressor refrigerant discharge temperature of the compressor selected with Compressor Select on page 18. (A19) Data Type Index Measurement Units Valid Range Holding Register
40020
Temperature
°F x 10
-460°-621°F
Compressor #2
This output data point indicates the compressor 2 discharge temperature. (A91) Data Type Index Measurement Units Holding Register
40092
Temperature
°F x 10
Valid Range -460°-621°F
Compressor Percent RLA This output data point indicates the current percent RLA for the compressor motor of the compressor selected with Compressor Select on page 18. (A25) Data Type Index Measurement Units Valid Range Holding Register
40026
Percent RLA
% x 10
0 -110%
Compressor #2
This output data point indicates the compressor 2 percent RLA. (A94) Data Type Index Measurement Holding Register
40095
Percent RLA
Units % x 10
Valid Range 0 -110%
Compressor #3
This output data point indicates the compressor 3 percent RLA. (A108) Data Type Index Measurement Holding Register
40109
Percent RLA
Units % x 10
Valid Range 0 -110%
Compressor #4
This output data point indicates the compressor 4 percent RLA. (A113) Data Type Index Measurement Holding Register
40114
Percent RLA
Units % x 10
Valid Range 0 -110%
Compressor #5
This output data point indicates the compressor 5 percent RLA. (A118) Data Type Index Measurement Holding Register
17
40119
Percent RLA
Units % x 10
Valid Range 0 -110%
ED 15063-5
Compressor #6
This output data point indicates the compressor 6 percent RLA. (A123) Data Type Index Measurement Holding Register
40124
Percent RLA
Units % x 10
Valid Range 0 -110%
Compressor Power This output data point indicates the current compressor power of the compressor selected with Compressor Select on page 18. (A27) Data Type Index Measurement Units Valid Range Holding Register
40028
Electric Power
kiloWatts
0-65,535
Compressor #2
This output data point indicates the current compressor 2 power. (A96) Data Type Index Measurement Holding Register
40097
Electric Power
Units kiloWatts
Valid Range 0-65,535
Compressor #3
This output data point indicates the current compressor 3 power. (A110) Data Type Index Measurement Holding Register
40111
Electric Power
Units kiloWatts
Valid Range 0-65,535
Compressor #4
This output data point indicates the current compressor 4 power. (A115) Data Type Index Measurement Holding Register
40116
Electric Power
Units kiloWatts
Valid Range 0-65,535
Compressor #5
This output data point indicates the current compressor 5 power. (A120) Data Type Index Measurement Holding Register
40121
Electric Power
Units kiloWatts
Valid Range 0-65,535
Compressor #6
This output data point indicates the current compressor 6 power. (A125) Data Type Index Measurement Holding Register
40126
Electric Power
Units kiloWatts
Valid Range 0-65,535
Compressor Run Hours Note: Value returned must be multiplied by 10 to give run hours. This output data point indicates the number of run hours for the compressor motor of the compressor selected with Compressor Select on page 18. (I46) Data Type Index Measurement Units Valid Range Holding Register
40175
Time
hours/10
0 -65,535
Compressor #2
This output data point indicates the current compressor 2 run hours. (I107) Data Type Index Measurement Holding Register
40236
Time
Units
hours/10
Valid Range 0 -65,535
Compressor #3
This output data point indicates the current compressor 3 run hours. (I110) Data Type Index Measurement Holding Register
18
40239
Time
hours/10
Units
Valid Range 0 -65,535
ED 15063-5
Compressor #4
This output data point indicates the current compressor 4 run hours. (I113) Data Type Index Measurement Holding Register
40242
Time
Units
hours/10
Valid Range 0 -65,535
Compressor Select This input data point selects the compressor (number 1, 2, 3 or 4) that is interrogated. The controller returns the information for the selected compressor. You must first select a compressor, then interrogate the selected compressor. This data point selects a compressor for the following variables. (I32) Name
Page
Compressor Current
13
Compressor Discharge Temperature
16
Compressor Percent RLA
17
Compressor Power
14
Compressor Run Hours
18
Compressor Starts
19
Compressor Suction Line Temperature
20
Compressor Voltage
15
Condenser Refrigerant Pressure
21
Condenser Saturated Refrigerant Temperature
21
Evaporator Leaving Water Temperature for Compressor
23
Evaporator Refrigerant Pressure
23
Evaporator Saturated Refrigerant Temperature
23
Oil Feed Pressure
26
Oil Feed Temperature
26
Oil Sump Pressure
26
Oil Sump Temperature
26
Data Type Holding Register
Index 40161
Measurement Event Count
Units NA
Valid Range 0 -65,535
Compressor Starts This output data point indicates the number of starts for the compressor motor of the compressor selected with Compressor Select on page 19. (I45) Data Type Index Measurement Units Valid Range Holding Register
40174
Count
Starts
0 -65,535
Compressor #2
This output data point indicates the current compressor 2 starts. (I106) Data Type Index Measurement Holding Register
40235
Count
Units Starts
Valid Range 0 -65,535
Compressor #3
This output data point indicates the current compressor 3 starts. (I109) Data Type Index Measurement Holding Register
40238
Count
Units Starts
Valid Range 0 -65,535
Compressor #4
This output data point indicates the current compressor 4 starts. (I112) Data Type Index Measurement Holding Register
19
40241
Count
Units Starts
Valid Range 0 -65,535
ED 15063-5
Compressor Suction Line Temperature This output data point indicates the current suction line refrigerant temperature for the compressor selected with Compressor Select on page 19. (A15) Data Type Index Measurement Units Valid Range Holding Register
40016
Temperature
°F x 10
-40°-244°F
Compressor #2
This output data point indicates the current compressor 2 suction line temperature. (A88) Data Type Index Measurement Units Holding Register
40089
Temperature
°F x 10
Valid Range -40°-244°F
Compressor Voltage This output data point indicates the current compressor voltage of the compressor selected with Compressor Select on page 20. (A29) Data Type Index Measurement Units Valid Range Holding Register
40030
Electric Voltage
Volts
0 -65,535
Compressor #2
This output data point indicates the current compressor 2 voltage. (A98) Data Type Index Measurement Holding Register
40099
Electric Voltage
Units Volts
Valid Range 0 -65,535
Compressor #3
This output data point indicates the current compressor 3 voltage. (A112) Data Type Index Measurement Holding Register
40113
Electric Voltage
Units
Volts
Valid Range 0 -65,535
Compressor #4
This output data point indicates the current compressor 4 voltage. (A117) Data Type Index Measurement Holding Register
40118
Electric Voltage
Units
Volts
Valid Range 0 -65,535
Compressor #5
This output data point indicates the current compressor 5 voltage. (A121) Data Type Index Measurement Holding Register
40123
Electric Voltage
Units
Volts
Valid Range 0 -65,535
Compressor #6
This output data point indicates the current compressor 6 voltage. (A127) Data Type Index Measurement Holding Register
20
40128
Electric Voltage
Volts
Units
Valid Range 0 -65,535
ED 15063-5
Condenser Entering Water Temperature This output data point indicates the current temperature of the entering condenser water. (A7) Data Type Holding Register
Index 40008
Measurement Temperature
Units °F x 10
Valid Range -40°-244°F
Condenser Flow Switch Status This output data point indicates the status of the water flow through the condenser. (D8) Data Type Coil
Index 9
Measurement Flow State
Units
Valid Range 0 = No Flow 1 = Flow
NA
Condenser Leaving Water Temperature This output data point indicates the current temperature of the leaving condenser water. (A8) Data Type Holding Register
Index 40009
Measurement Temperature
Units °F x 10
Valid Range -40°-244°F
Condenser Pump Run Hours Pump Select
This output data point indicates the number of run hours that the selected condenser pump motor. See Pump Select on page 21. (I48) Data Type Index Measurement Units Valid Range Holding Register
40177
Time
hours
0 -65,535
Pump #2
This output data point indicates the number of run hours that for condenser pump #2. (I104) Data Type Index Measurement Units Holding Register
40233
Time
hours
Valid Range 0 -32768
Condenser Refrigerant Pressure This output data point indicates the current refrigerant pressure in the selected condenser. There is a separate output for each compressor. See Compressor Select on page 21. (A21) Data Type Index Measurement Units Valid Range Holding Register
40022
Pressure (gauge)
psi x 10
-22592 - 22591 psi
Compressor #2
This output data point indicates the current compressor 2 refrigerant pressure. (A93) Data Type Index Measurement Units Holding Register
40094
Pressure (gauge)
psi x 10
Valid Range -22592 - 22591 psi
Condenser Saturated Refrigerant Temperature This output data point indicates the current saturated refrigerant temperature in the condenser. There is a separate output for each compressor. See Compressor Select on page 21. (A20) Data Type Index Measurement Units Valid Range Holding Register
40021
Temperature
°F x 10
-40°- 244°F
Compressor #2
This output data point indicates the current compressor 2 saturated refrigerant temperature. (A92) Data Type Index Measurement Units
21
Valid Range
ED 15063-5
Holding Register
40093
Temperature
°F x 10
-40°- 244°F
Condenser Water Flow Rate This output data point indicates the rate of water flow through the condenser. (A24) Note: Requires field provided flow measurement device. Data Type Holding Register
Index 40025
Measurement
Units
Water Flow Rate
Valid Range
gallons per minute
0 -65,535
Condenser Water Pump Status This output data point indicates whether the selected pump has been commanded On or Off. See Pump Select on page 22. (D31) Data Type Coil
Index 32
Measurement
Units
Flow State
Valid Range 0 = Pump Off Request 1 = Pump On Request
NA
Cool Setpoint This input data point sets the temperature of the Leaving Chilled Water when the chiller is operating in the Cooling Mode. The Cooling mode is the normal mode of chiller operation, unless overridden by using the Chiller Mode Setpoint to change to another mode. (A1) Note: See the appropriate Operation Manual for specific data range and default value. Data Type Index Measurement Units Holding Register
40002
Temperature
°F x 10
Valid Range 10 - 120°F
Design RPM This output network variable indicates the Turbocor calculated speed target based on conditions and request demand. (I125 & I126) Compressor #1
Data Type Holding Register
Index 40254
Measurement
Units
Revolutions Per Minute
RPM
Valid Range 0-32768
Compressor #2
Data Type Holding Register
Index 40255
Measurement
Units
Revolutions Per Minute
RPM
Valid Range 0-32768
Evaporator Entering Water Temperature This output data point indicates the temperature of the evaporator entering water temperature. (A4) Data Type Holding Register
Index 40005
Measurement
Units
Temperature
°F x 10
Valid Range -40 - 245°F
Evaporator Flow Switch Status This output data point indicates the status of water flow through the evaporator. (D7) Data Type Coil
Index 8
Measurement Flow State
Units NA
Valid Range 0 = No Flow 1 = Flow
Evaporator Leaving Water Temperature for Unit This output data point indicates the current temperature of the evaporator leaving chilled water. (A6) 22
ED 15063-5
Data Type Holding Register
Index 40007
Measurement Temperature
Units °F x 10
Valid Range -40° - 244°F
Evaporator Leaving Water Temperature for Compressor Compressor Select
This output data point indicates the current temperature of the evaporator leaving chilled water temperature of the compressor selected with Compressor Select on page 18. (A14) Data Type Index Measurement Units Valid Range Holding Register
40015
Temperature
°F x 10
-40°-244°F
Compressor #2
This output data point indicates the current temperature of the evaporator leaving chilled water temperature for compressor 2. (A87) Data Type Index Measurement Units Valid Range Holding Register
40088
Temperature
°F x 10
-40°-244°F
Evaporator Pump Run Hours Pump Select
This output data point indicates the number of run hours for the selected evaporator pump. There is a separate output for each pump. See Pump Select on page 27. (I47) Data Type Index Measurement Units Valid Range Holding Register
40176
Event Count
Hours
0 - 65,535
Pump #2
This output data point indicates the number of run hours for evaporator pump #2. (I103) Data Type Index Measurement Units Holding Register
40232
Event Count
Hours
Valid Range 0 - 65,535
Evaporator Refrigerant Pressure Compressor Select
This output data point indicates the current refrigerant pressure in the evaporator. There is a separate output for each compressor. See Compressor Select on page 18. (A17) Data Type Index Measurement Units Valid Range Holding Register
40018
Pressure (gauge)
psi x 10
-22592 - 22591 psi
Compressor #2
This output data point indicates the current refrigerant pressure in the evaporator for compressor 2. (A90) Data Type Index Measurement Units Valid Range Holding Register
40091
Pressure (gauge)
psi x 10
-22592 - 22591 psi
Evaporator Saturated Refrigerant Temperature Compressor Select
This output data point indicates the current saturated refrigerant temperature in the evaporator. There is a separate output for each compressor. See Compressor Select on page 18. (A16) Data Type Index Measurement Units Valid Range Holding Register
23
40017
Temperature
°F x 10
-40° - 244°F
ED 15063-5
Compressor #2
This output data point indicates the current saturated refrigerant temperature in the evaporator for compressor 2. (A89) Data Type Index Measurement Units Valid Range Holding Register
40090
Temperature
°F x 10
-40° - 244°F
Evaporator Water Flow Rate This output data point indicates the rate of water flow through the evaporator. (A18) Note: Requires field provided flow measurement device. Data Type Holding Register
Index 40019
Measurement Water Flow Rate
Units
Valid Range
gallons per minute
0 - 65,535
Evaporator Water Pump Status This output data point indicates whether the selected pump has been commanded On or Off. See Pump Select on page 27. (D29) Data Type Coil
Index 30
Measurement Flow State
Units
Valid Range 0 = Pump Off Request 1 = Pump On Request
NA
Heat Recovery Entering Water Temperature This output network variable indicates the current temperature of the water entering the heat recovery section. (A22) Data Type Holding Register
Index 40023
Measurement Temperature
Units °F x 10
Valid Range -40° - 244°F
Heat Recovery Leaving Water Temperature This output data point indicates the current temperature of the water leaving the heat recovery section. (A23) Data Type Holding Register
Index 40024
Measurement Temperature
Units °F x 10
Valid Range -40°-244°F
Heat Setpoint This input data point provides the heating setpoint when the chiller is operating in the heat mode. The value is ignored if the controller is in cooling mode. (A5) Note: See the appropriate Operation Manual for specific data range and default value. Data Type Index Measurement Units Holding Register
40006
Temperature
°F x 10
Valid Range 50-120°F
Ice Setpoint This input data point sets the temperature of the Leaving Chilled Water when the chiller is operating in the ice mode. (A50) Note: See the appropriate Operation Manual for specific data range and default value. Data Type Index Measurement Units Holding Register
40051
Temperature
°F x 10
Valid Range 15 - 35°F
IGV Percentage Open This output network variable indicates current percent of vanes open for each compressor (0%=closed, 110%=full capacity-open) (I120 & I124)
24
ED 15063-5
Compressor #1
Data Type Holding Register
Index 40249
Measurement Percent
Units %
Valid Range 0-110%
Compressor #2
Data Type Holding Register
Index 40253
Measurement Percent
Units %
Valid Range 0-110%
Inverter Temperature This output network variable the current drive temperature. There is one variable for each compressor. (A86 & A106) Compressor #1
Data Type Holding Register
Index 40087
Measurement Temperature
Units
Valid Range
Units
Valid Range
°Fx10
Compressor #2
Data Type Holding Register
Index 40107
Measurement Temperature
°Fx10
Liquid Line Refrigerant Pressure This output data point indicates the current liquid line refrigerant pressure. (A38) Data Type Holding Register
Index 40039
Measurement Pressure
Units psi x 10
Valid Range –22592 - 22591 psi
Liquid Line Refrigerant Temperature This output data point indicates the current liquid line refrigerant temperature. (A36) Compressor Select
Data Type Holding Register
Index 40037
Measurement Temperature
Units °F x 10
Valid Range -40° - 244°F
Compressor #2
Data Type Holding Register
Index 40105
Measurement Temperature
Units °F x 10
Valid Range -40° - 244°F
Maximum RPM This output data point indicates the maximum (choke) RPM. This is the speed the Turbocor compressor calculates above which the efficiency of the compressor falls off. (I117 & I121) Compressor #1
Data Type Holding Register
Index 40246
Measurement Revolutions Per Minute
Units RPM
Valid Range 0-32768
Compressor #2
Data Type Holding Register
Index 40250
Measurement Revolutions Per Minute
Units RPM
Valid Range 0-32768
Minimum RPM This output data point indicates the minimum (surge) RPM. This is the speed Turbocor compressor calculates is the minimum safe operating speed above onset of stall. (I119 & I123) Compressor #1
Data Type 25
Index
Measurement
Units
Valid Range ED 15063-5
Holding Register
40248
Revolutions Per Minute
RPM
0-32768
Compressor #2
Data Type Holding Register
Index 40252
Measurement Revolutions Per Minute
Units RPM
Valid Range 0-32768
Oil Feed Pressure Compressor Select
This output data point indicates the current compressor oil feed pressure. There is a separate output for each compressor. See Compressor Select on page 18. (A32) Data Type Index Measurement Units Valid Range Holding Register
40033
Pressure
psi
–22592 - 22591 psi
Compressor #2
This output data point indicates the current compressor 2 oil feed pressure. (A100) Data Type Index Measurement Units Holding Register
40101
Pressure
psi
Valid Range –22592 - 22591 psi
Oil Feed Temperature Compressor Select
This output data point indicates the current compressor oil feed temperature. There is a separate output for each compressor. See Compressor Select on page 18. (A34) Data Type Index Measurement Units Valid Range Holding Register
40035
Temperature
°F x 10
-40° - 244°F
Compressor #2
This output data point indicates the current compressor 2 oil feed temperature. (A102) Data Type Index Measurement Units Holding Register
40103
Temperature
°F x 10
Valid Range -40° - 244°F
Oil Sump Pressure Compressor Select
This output data point indicates the current compressor oil sump pressure. There is a separate output for each compressor. See Compressor Select on page 18. (A33) Data Type Index Measurement Units Valid Range Holding Register
40034
Pressure
psi x 10
-22592 - 22591 psi.
Compressor #2
This output data point indicates the current compressor 2 oil sump pressure. (A101) Data Type Index Measurement Units Holding Register
40102
Pressure
psi x 10
Valid Range -22592 - 22591 psi.
Oil Sump Temperature Compressor Select
This output data point indicates the current compressor oil sump temperature. There is a separate output for each compressor. See Compressor Select on page 18. (A35) Data Type Index Measurement Units Valid Range Holding Register
26
40036
Temperature
°F x 10
-40° - 244°F
ED 15063-5
Compressor #2
This output data point indicates the current compressor 2 oil sump temperature. (A103) Data Type Index Measurement Units Holding Register
40104
Temperature
°F x 10
Valid Range -40° - 244°F
Outdoor Air Temperature This output data point indicates the current outdoor air temperature. (A39) Data Type Holding Register
Index 40040
Measurement Temperature
Units °F x 10
Valid Range -40° -2 44°F
Pump Select This input data point selects which pump (Number 1 or Number 2) supplies the data. The controller returns the information for the appropriate Condenser or Evaporator pump. You must first select a pump then interrogate the selected pump. See Condenser Pump Run Hours on page 21 and Evaporator Pump Run Hours on page 23. (D19) Data Type Coil
Index 20
Measurement Event Count
Units
Valid Range 0 = Pump #1 1 = Pump #2
NA
Run Enabled The Run Enabled output data point indicates that the chiller can start if operating conditions are met. (D2) Data Type Coil
27
Index 3
Measurement Chiller State
Units NA
Valid Range 0 = Off 1 = Run Allowed
ED 15063-5
Alarms Alarm Classes Modbus alarms in a MicroTech II unit controller are divided into three classes: Faults, Problems, and Warnings. Fault alarms have the highest severity level. Problem alarms have medium severity level. Warning alarms have the lowest severity level.
Fault Alarms Fault alarms require an acknowledgment from the operator. These alarms indicate that the compressor is shut down.
Problem Alarms Problem alarms do not cause compressor shutdown but limit operation of the chiller in some way.
Warning Alarms A warning is enunciated whenever an abnormal condition exists which does not affect chiller operation.
Alarm Handling One Modbus network variable indicates an alarm condition and one network variable clears alarms. To determine the particular alarm condition, you must read the status of the 16 Active Alarms Holding Registers.
Alarm Digital Output This network data point indicates whether an alarm condition has occurred. This variable must be polled for alarm notification. (D3) Data Type Coil
Index 4
Measurement NA
Units
Valid Range 0 = No Alarm 1 = Alarm
NA
Clear Alarms This input data point clears all active alarms. It cannot clear all alarms in the Fault category (alarms that shut down the chiller). They would have to be cleared at the chiller panel. The alarms that cannot be cleared over the network (but can be cleared at the chiller) are: (D24) • Low Evaporator Pressure • High Condenser Pressure (by pressure sensor) • High Condenser Pressure (by pressure switch) • Low Oil Pressure • Freeze Protection • High Motor Temperature
Note: The above list is for centrifugal chillers. The flow loss alarm is the only alarm that can be remotely cleared on all other types of chillers. Data Type Coil
28
Index 25
Measurement NA
Units NA
Valid Range 0 = Normal 1 = Clear Alarm
ED 15063-5
Active Alarms The Active Alarms Holding Registers contain a single bit for each alarm condition. You must read the status of these registers to determine the particular alarm condition indicated by the Alarm Digital Output. Table 3 defines the bit location for each alarm condition. (I1-I16) Data Type Holding Registers
Index 40130-40145
Measurement
Units
Alarm Condition
Valid Range 0 = No Alarm 1 = Alarm
NA
Table 3: Modbus Alarms
Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
29
Warnings Entering Condenser Water Temperature Sensor Fault Entering Evaporator Water Temperature Sensor Fault Liquid Line Refrigerant Temperature Sensor Fault Leaving Condenser Water Temperature Sensor Fault Repower After Power Loss 1 Repower After Power Loss 2 Repower After Power Loss 3 Repower After Power Loss 4 (Expansion Alarm – Warning) Problems Low Ambient Temperature Lockout High Condenser Pressure – Inhibit Loading Circuit 1 High Condenser Pressure – Inhibit Loading Circuit 2 High Condenser Pressure – Inhibit Loading Circuit 3 High Condenser Pressure – Inhibit Loading Circuit 4 High Condenser Pressure – Unload High Condenser Pressure – Unload Circuit 1 High Condenser Pressure – Unload Circuit 2 High Condenser Pressure – Unload Circuit 3 High Condenser Pressure – Unload Circuit 4 Condenser Water Freeze Protect Comp 1 Condenser Water Freeze Protect Comp 2 Condenser Water Freeze Protect Comp 3 Condenser Water Freeze Protect Comp 4 Condenser Pump #1 Fault Condenser Pump #2 Fault High Discharge Temperature Comp 1 High Discharge Temperature Comp 2 High Discharge Temperature Comp 3 High Discharge Temperature Comp 4 Entering Evap Temperature Sensor Fault (EWT reset active) Low Evaporator Pressure - Inhibit Loading Low Evaporator Pressure - Inhibit Loading Circuit 1 Low Evaporator Pressure - Inhibit Loading Circuit 2 Low Evaporator Pressure - Inhibit Loading Circuit 3 Low Evaporator Pressure - Inhibit Loading Circuit 4 Low Evaporator Pressure – Unload Low Evaporator Pressure – Unload Circuit 1 Low Evaporator Pressure – Unload Circuit 2 Low Evaporator Pressure – Unload Circuit 3 Low Evaporator Pressure – Unload Circuit 4 High Motor Current On Compressor #1 High Motor Current On Compressor #2 High Motor Current On Compressor #3 High Motor Current On Compressor #4 Evaporator Freeze Protect Comp 1 Evaporator Freeze Protect Comp 2 Evaporator Freeze Protect Comp 3
WSC WDC WPV WMC WCC HSC HDC TSC
AGZ
ACZ
X X X X
WGZ/ TGZ
X X X
AGS
WGS
X
X
X X 2 X
X 5 X 5 X
X 3 X 3 X
6
X 3 X 3 X
X 5 X 5 X
X X X
X
X
X X X
X X X 2 X
X X X
X X
X X 2 X
X X
4
X X
X X
X X X X
X 6
4
X X
X 5 X 5 X
X 3 X 3 X
6
X X
X 5 X 5 X
X 3 X 3 X
X X
X X
X X
X X 2 X
X X
X X
X X 2 X
X X
4
Holding Register
Bit
40130 40130 40130 40130 40130 40130 40130 40130 40130
1 2 3 4 5 6 7 8 9
40130 40130 40130 40130 40130 40130 40131 40131 40131 40131 40131 40131 40131 40131 40131 40131 40131 40131 40131 40131
10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13
40131
14
40131 40132 40132 40132 40132 40132 40132 40132 40132 40132 40132 40132 40132 40132 40132 40132 40132
15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
ED 15063-5
48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115
30
Evaporator Freeze Protect Comp 4 Evaporator Pump #1 Fault Evaporator Pump #2 Fault (Expansion Alarm – Problem) Faults Outside Ambient Temperature Sensor Fault Compressor Current Overload Trip #1 Compressor Current Overload Trip #2 Compressor Current Overload Trip #3 Compressor Current Overload Trip #4 Motor Current Imbalance On Compressor #1 Motor Current Imbalance On Compressor #2 Motor Current Imbalance On Compressor #3 Motor Current Imbalance On Compressor #4 Low Motor Current Comp 1 Low Motor Current Comp 2 Low Motor Current Comp 3 Low Motor Current Comp 4 Motor Protection Motor Protection Circuit 1 Motor Protection Circuit 2 High Motor Temperature Comp 1 High Motor Temperature Comp 2 High Motor Temperature Comp 3 High Motor Temperature Comp 4 Phase Loss At Compressor 1 Phase Loss At Compressor 2 Phase Loss At Compressor 3 Phase Loss At Compressor 4 Phase Reversal At Compressor 1 Phase Reversal At Compressor 2 Phase Reversal At Compressor 3 Phase Reversal At Compressor 4 Overvoltage On Compressor 1 Overvoltage On Compressor 2 Overvoltage On Compressor 3 Overvoltage On Compressor 4 Undervoltage On Compressor 1 Undervoltage On Compressor 2 Undervoltage On Compressor 3 Undervoltage On Compressor 4 Condenser Pressure Sensor Fault Condenser Pressure Sensor Fault Circuit 1 Condenser Pressure Sensor Fault Circuit 2 Condenser Pressure Sensor Fault Circuit 3 Condenser Pressure Sensor Fault Circuit 4 No Condenser Water Flow High Condenser Pressure High Condenser Pressure Circuit 1 High Condenser Pressure Circuit 2 High Condenser Pressure Circuit 3 High Condenser Pressure Circuit 4 No Compressor Stop Comp 1 No Compressor Stop Comp 2 No Compressor Stop Comp 3 No Compressor Stop Comp 4 Discharge Temperature Sensor Fault Circuit 1 Discharge Temperature Sensor Fault Circuit 2 Discharge Temperature Sensor Fault Circuit 3 Discharge Temperature Sensor Fault Circuit 4 High Discharge Temperature Circuit 1 High Discharge Temperature Circuit 2 High Discharge Temperature Circuit 3 High Discharge Temperature Circuit 4 Entering Condenser Water Temperature Sensor Fault No Evaporator Water Flow Evaporator Water Freeze Protect Low Evaporator Pressure Low Evaporator Pressure Circuit 1
X X
X X
X
X 1 X 1 X
X X X
X X
X 1 X
1
X X
X X
X 1 X
1
X X
1
X X
6
X 5 X 5 X
X
X
4
X 3 X 3 X
X X
X X
7
X 7 X
X 1 X
5
X 5 X
3
X X
X 3 X
X 7 X
7
X X
X 7 X
7
X X
7
X X
X 7 X
6
X X
4
X 5 X 5 X
X 3 X 3 X
6
X 3 X 3 X
X X X
X X
X X 2 X
X X 5 X 5 X
X X
X
4
X X
X X 2 X
X X
X X 2 X
X X
X X
X X
X X
X
X
X X
X X 6 X 5 X
X
X X X
X X
X X X
X
X
X
4
X 3 X
40133 40133 40133 40133
0 1 2 3
40133 40133 40133 40133 40133 40133 40133 40133 40133 40133 40133 40133 40134 40134 40134 40134 40134 40134 40134 40134 40134 40134 40134 40134 40134 40134 40134 40134 40135 40135 40135 40135 40135 40135 40135 40135 40135 40135 40135 40135 40135 40135 40135 40135 40136 40136 40136 40136 40136 40136 40136 40136 40136 40136 40136 40136 40136 40136 40136 40136 40137 40137 40137 40137
4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3
ED 15063-5
116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176
31
Low Evaporator Pressure Circuit 2 Low Evaporator Pressure Circuit 3 Low Evaporator Pressure Circuit 4 Evaporator Pressure Sensor Fault Evaporator Pressure Sensor Fault Circuit 1 Evaporator Pressure Sensor Fault Circuit 2 Evaporator Pressure Sensor Fault Circuit 3 Evaporator Pressure Sensor Fault Circuit 4 Ground Fault Protection 1 Ground Fault Protection 2 Ground Fault Protection 3 Ground Fault Protection 4 Below Minimum Lift Pressure Circuit 1 Below Minimum Lift Pressure Circuit 2 Below Minimum Lift Pressure Circuit 3 Below Minimum Lift Pressure Circuit 4 Liquid Line Pressure Sensor Fault Circuit 1 Liquid Line Pressure Sensor Fault Circuit 2 Liquid Line Pressure Sensor Fault Circuit 3 Liquid Line Pressure Sensor Fault Circuit 4 Liquid Line Refrigerant Temperature Sensor Fault Circuit 1 Liquid Line Refrigerant Temperature Sensor Fault Circuit 2 Liquid Line Refrigerant Temperature Sensor Fault Circuit 3 Liquid Line Refrigerant Temperature Sensor Fault Circuit 4 Re-Start Fault Re-Start Fault Circuit 1 Re-Start Fault Circuit 2 Re-Start Fault Circuit 3 Re-Start Fault Circuit 4 Leaving Evaporator Water Temperature Sensor Fault Leaving Evaporator Water Temperature Sensor Fault Comp 1 Leaving Evaporator Water Temperature Sensor Fault Comp 2
Leaving Evaporator Water Temperature Sensor Fault Comp 3 Leaving Evaporator Water Temperature Sensor Fault Comp 4 Mechanical High Pressure Mechanical High Pressure Circuit 1 Mechanical High Pressure Circuit 2 Mechanical High Pressure Circuit 3 Mechanical High Pressure Circuit 4 Low Oil Net Pressure Comp 1 Low Oil Net Pressure Comp 2 Low Oil Net Pressure Comp 3 Low Oil Net Pressure Comp 4 High Oil Feed Temperature Comp 1 High Oil Feed Temperature Comp 2 High Oil Feed Temperature Comp 3 High Oil Feed Temperature Comp 4 Low Oil Feed Temperature Comp 1 Low Oil Feed Temperature Comp 2 Low Oil Feed Temperature Comp 3 Low Oil Feed Temperature Comp 4 Oil Feed Temperature Sensor Fault Comp 1 Oil Feed Temperature Sensor Fault Comp 2 Oil Feed Temperature Sensor Fault Comp 3 Oil Feed Temperature Sensor Fault Comp 4 Low Oil Level Circuit 1 Low Oil Level Circuit 2 Low Oil Level Circuit 3 Low Oil Level Circuit 4 High Oil Pressure Difference Circuit 1 High Oil Pressure Difference Circuit 2
5
X
6
X 3 X 3 X
X
X
X X
X 5 X 5 X
7
X 7 X
3
X
X 2 X
X
40137 40137 40137 40137 40137 40137 40137 40137 40137 40137 40137 40137 40138 40138 40138 40138 40138 40138 40138 40138
4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7
X X
X X 2 X
X X
X X
X 1 X
1
X X
X X 2 X
X X
X
40138
8
X
40138
9
2
40138
10
4
6
X 6 X
X X 2 X
X
6
4
40138
11
40138 40138 40138 40138 40139
12 13 14 15 0 1
X
40139
2
X
40139
3
40139
4
40139
5
40139 40139 40139 40139 40139 40139 40139 40139 40139 40139 40140 40140 40140 40140 40140 40140 40140 40140 40140 40140 40140 40140 40140 40140 40140 40140 40141
6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0
X 5 X 5 X
X 3 X 3 X
X
6
X X
X 5 X 5 X
X X
X 1 X
1
X X
X
X
X
4
X 3 X 3 X
X X
X X 2 X
X X
X X 2 X
X X
X X
X X
X X
X X
X X
X X
ED 15063-5
177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240
32
High Oil Pressure Difference Circuit 3 High Oil Pressure Difference Circuit 4 Oil Feed Pressure Sensor Fault Comp 1 Oil Feed Pressure Sensor Fault Comp 2 Oil Feed Pressure Sensor Fault Comp 3 Oil Feed Pressure Sensor Fault Comp 4 Oil Sump Pressure Sensor Fault Comp 1 Oil Sump Pressure Sensor Fault Comp 2 Oil Sump Pressure Sensor Fault Comp 3 Oil Sump Pressure Sensor Fault Comp 4 Oil Sump Temperature Sensor Fault Comp 1 Oil Sump Temperature Sensor Fault Comp 2 Oil Sump Temperature Sensor Fault Comp 3 Oil Sump Temperature Sensor Fault Comp 4 Phase Voltage Protection Starter Fault Compressor 1 Starter Fault Compressor 2 Starter Fault Compressor 3 Starter Fault Compressor 4 No Starter Transition Comp 1 No Starter Transition Comp 2 No Starter Transition Comp 3 No Starter Transition Comp 4 No Oil Pressure Start Comp 1 No Oil Pressure Start Comp 2 No Oil Pressure Start Comp 3 No Oil Pressure Start Comp 4 Low Subcooling Circuit 1 Low Subcooling Circuit 2 Low Subcooling Circuit 3 Low Subcooling Circuit 4 Surge High Suct SH-Running Comp 1 Surge High Suct SH-Running Comp 2 Surge High Suct SH-Running Comp 3 Surge High Suct SH-Running Comp 4 Surge High Suct SH-Starting Comp 1 Surge High Suct SH-Starting Comp 2 Surge High Suct SH-Starting Comp 3 Surge High Suct SH-Starting Comp 4 Suction Temperature Sensor Fault Circuit 1 Suction Temperature Sensor Fault Circuit 2 Suction Temperature Sensor Fault Circuit 3 Suction Temperature Sensor Fault Circuit 4 Vanes Open No Start Comp 1 Vanes Open No Start Comp 2 Vanes Open No Start Comp 3 Vanes Open No Start Comp 4 (Expansion Alarm- Fault) COMP SHUTDOWN – Comp Fault #1 COMP SHUTDOWN – Comp Fault #2 COMP SHUTDOWN – Comp Fault #3 COMP SHUTDOWN – Comp Fault #4 C-Stop - General Comp Fault#1 C-Stop - General Comp Fault#2 C-Stop - Communication Fault #1 C-Stop - Communication Fault #2 C-Stop - Interlock Fault #1 C-Stop - Interlock Fault #2 C-Stop - Bearing Fault #1 C-Stop - Bearing Fault #2 C-Stop - Motor Fault #1 C-Stop - Motor Fault #2 C-Stop - Drive Fault #1 C-Stop - Drive Fault #2 C-Stop - Internal Control Err#1 C-Stop - Internal Control Err#2 Warn-Chiller Capacity Limited U-Stop - Check Valve Fault #1
2
X X X
X X
X X
6
X
4
X
X X
X X 2 X
X X
X 1 X
X X
1
X X
X 2 X 2 X
2
X X
X X 2 X
X X
X
X
X X
X X
X X
8
X 8 X
X
40141 40141 40141 40141 40141 40141 40141 40141 40141 40141 40141 40141 40141 40141 40141 40142 40142 40142 40142 40142 40142 40142 40142 40142 40142 40142 40142 40142 40142 40142 40142 40143 40143 40143 40143 40143 40143 40143 40143 40143 40143 40143 40143 40143 40143 40143 40143 40144 40144 40144 40144 40144
X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8
ED 15063-5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4
241 U-Stop - Check Valve Fault #2 242 U-Stop - LB Valve Fault #1 243 U-Stop - LB Valve Fault #2
X8 X8 X8
1
-AGS ‘C’ Vintage Only -AGS ‘B’ Vintage Only 3 -ACZ Dual Circuit Only 4 -ACZ Single Circuit Only 5 -AGZ Dual Circuit Only 6 -AGZ Single Circuit Only 7 -Solid State Starter Option required. Not available on WMC. 8 -Should be “No Start - Interlock Switch” on WMC chillers. 2
33
ED 15063-5
Index of Detailed Point Information A
E
Active Alarms ................................................... 9, 12, 29 Active Setpoint ..................................................... 10, 14 Actual Capacity ................................................ 9, 10, 14 Actual RPM .......................................................... 10, 14 Alarm Digital Output ........................................ 9, 12, 28
Evaporator Entering Water Temperature ..............11, 22 Evaporator Flow Switch Status .............................11, 22 Evaporator Leaving Water Temperature for Compressor .......................................................11, 23 Evaporator Leaving Water Temperature for Unit .11, 22 Evaporator Pump Run Hours ................................11, 23 Evaporator Refrigerant Pressure ...........................12, 23 Evaporator Saturated Refrigerant Temperature.....12, 23 Evaporator Water Flow Rate .................................12, 24 Evaporator Water Pump Status .............................12, 24
C Capacity Limit Output .......................................... 10, 14 Capacity Limit Setpoint .................................... 9, 10, 14 Cavity Temperature .............................................. 10, 15 Chiller Enable ................................................... 9, 10, 15 Chiller Limited ..................................................... 10, 15 Chiller Local/Remote ........................................... 10, 15 Chiller Mode Output............................................. 10, 15 Chiller Mode Setpoint ...................................... 9, 10, 16 Chiller Power ........................................................ 10, 16 Chiller Status .................................................... 9, 10, 16 Clear Alarms ..................................................... 9, 12, 28 Compressor 2 Active Capacity Limit ......................... 16 Compressor 2 Active Capacity Limit ......................... 10 Compressor Current.............................................. 10, 16 Compressor Discharge Temperature .............. 10, 15, 17 Compressor Percent RLA ..................................... 10, 17 Compressor Power................................................ 10, 18 Compressor Run Hours ........................................ 10, 18 Compressor Select ................................................ 11, 19 Compressor Starts ................................................. 11, 19 Compressor Suction Line Temperature ................ 11, 19 Compressor Voltage ............................................. 11, 20 Condenser Entering Water Temperature .............. 11, 21 Condenser Flow Switch Status ............................. 11, 21 Condenser Leaving Water Temperature ............... 11, 21 Condenser Pump Run Hours ................................ 11, 21 Condenser Refrigerant Pressure ........................... 11, 21 Condenser Saturated Refrigerant Temperature ..... 11, 21 Condenser Water Flow Rate ................................. 11, 22 Condenser Water Pump Status ............................. 11, 22 Cool Setpoint .................................................... 9, 11, 22
H Heat Recovery Entering Water Temperature ........12, 24 Heat Recovery Leaving Water Temperature .........12, 24 Heat Setpoint .........................................................12, 24 I Ice Setpoint ...........................................................12, 24 IGV Percentage Open ...........................................11, 24 Inverter Temperature .............................................11, 25 L Liquid Line Refrigerant Pressure ..........................12, 25 Liquid Line Refrigerant Temperature ...................12, 25 M Maximum RPM.....................................................11, 25 Minimum RPM .....................................................11, 25 O Oil Feed Pressure ..................................................12, 26 Oil Feed Temperature ...........................................12, 26 Oil Sump Pressure .................................................12, 26 Oil Sump Temperature ..........................................12, 26 Outdoor Air Temperature ......................................12, 27 P Pump Select...........................................................12, 27
D
R
Design RPM ......................................................... 11, 22
Run Enabled ..........................................................12, 27
34
ED 15063-5
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinMcQuay.com.
Daikin McQuay (800) 432-1342, www.DaikinMcQuay.com
35
ED 15063-5