Full DC Inverter Heat Pump Modular & Mini VRF

HIGH EFFICIENCY Full DC Inverter Heat Pump Modular & Mini VRF YORK® Variable Refrigerant Flow Systems Efficiency and comfort for your customers. N...
36 downloads 0 Views 6MB Size
HIGH EFFICIENCY

Full DC Inverter Heat Pump Modular & Mini VRF

YORK® Variable Refrigerant Flow Systems Efficiency and comfort for your customers.

New growth opportunities for your business. Building climate control is about comfort and efficiency – delivering just the right heating and cooling to every space using no more energy than necessary. YORK® variable refrigerant flow (VRF) technology lets you do that for customers in innovative ways that present new growth opportunities for your business.

2 WHY VRF?

VRF technology gives building owners, architects, consulting engineers, and mechanical contractors an innovative solution to address the common challenge of reducing operating costs in buildings with varied loads and occupancy rates while delivering comfort to all areas. The systems can offer:

Introducing YORK® VRF

2-4

What is VRF?

5

Why Partner with Johnson Controls?

7-9

Summary of Features and Benefits

10-11

12 INDOOR UNITS Overview 12-14 Ductless Units 15-20 Ducted Units 21-29

• E xceptional efficiency, delivering more energy savings than conventional HVAC systems. • A modular system that can be customized to the exact requirements of each project, with options that include heat pump and fan coil options.

35 OUTDOOR UNITS Overview 35-37 380V Heat Pump 38-50

• Freedom for designers to choose ducted systems with short or long runs, or ductless systems that allow for much lower clearance between building floors and therefore lower overall construction costs.

51 OPTIONAL PARTS & ACCESSORIES

• Impressively quiet, with controls to deliver precisely the correct amount of heating or cooling to each zone.

Optional Parts & Accessories

51-52

53 CONTROLLERS Controllers 53

The information contained in this catalog is for illustration purposes only and is subject to change at the sole discretion of Johnson Controls. Statements, figures, calculations, plans, images and representations are only examples. Johnson Controls encourages you, as the purchaser, to analyze your HVAC requirements and to work with Johnson Controls to determine the exact VRF System to fulfill your needs.

2

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

1

Introducing YORK® VRF from Johnson Controls YORK® VRF systems are modular and controlled solutions that include models with capability to heat or cool different zones. The technology brings an array of advantages over conventional systems. •S  ave on energy. Systems essentially eliminate duct losses. In addition, variable-speed compressors in outdoor units provide extremely high part-load efficiency.

Gain control flexibility Users can deploy from three basic control options: • Indoor fan coil units come with a selection of thermostats, from simple units with on/off, setpoint, load and speed settings, to programmable units that enable scheduling. Wireless units are available to provide remote control of zone space conditions. •C  entral station controllers for larger projects provide remote control and scheduling of the entire system from one or more control points.

•K  eep occupants comfortable. Users can set individual temperature set points for multiple zones. Variable-speed compressors with wide capacity and precise modulation help maintain each zone’s temperature within a narrow range. Indoor units also operate quietly.

• Adapters (gateways) enable control of large buildings or campuses through building automation systems such as Metasys®.

• Go green. VRF technology can help users attain LEED® certification points for resource efficiency.

YORK® VRF systems suit a wide range of buildings in new construction and retrofits. Prime candidates include:

Enjoy design freedom A variety of standard modular components let you customize and size equipment to meet specific project requirements. Because ductwork is generally needed for ventilation, ducts can be smaller, reducing capital cost. Systems can be easily adapted as space is reconfigured. Unlike conventional HVAC systems, VRF systems allow for the addition of capacity to accommodate expansion simply by adding modular units (capacities 8-54 HP). There is no need to remove and replace the original unit or reconfigure ductwork.

Choose multiple applications

•B  uildings with multiple zones that have different comfort needs – such as hotels, schools, medical office buildings, commercial office buildings and others. •H  istorical building renovations in which ducted HVAC options are severely limited and the basic building structure must not be disturbed. •B  uildings in climate zones favorable for heat pump technology.

Install with ease YORK® VRF systems are designed for quick and simple installation, since piping from the outdoor units can be connected from the front, back, or underneath. Indoor units are small and light and easy to transport and handle; outdoor units can be brought into a building for installation on a rooftop via a service elevator – no crane or other heavy equipment is needed. Service is simple, too: Systems need little maintenance beyond changing filters and cleaning coils.

2

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

3

Advanced compressor technology yields the highest efficiency ratings, resulting in energy savings Rated highest for energy efficiency The YORK® VRF Systems boast efficiencies up to: • 4.1 COP

YORK® systems rank impressively high in the ratings that matter most for VRF technology. The traditional measure of HVAC equipment, Coefficient of Performance (COP), measures system efficiency at full load. While this may be appropriate for equipment that operates in a traditional cycle (fully on or fully off), it is not appropriate for properly sized VRF systems, which spend the vast majority of time at part load, reaching full load only on the hottest or coldest days. YORK® VRF systems excel against truer measures of efficiency:

How VRF works A VRF system typically consists of one or more outdoor condensing units from which refrigerant is piped to a series of indoor fan coil units serving individual zones within building spaces. The system conditions the spaces by delivering to the indoor fan coil units only the volume of refrigerant required to meet the heating or cooling needs of each zone (see Figure 1). The basic types of YORK® VRF systems, ranging from 4-54HP capacity: • Heat pump VRF systems are two-pipe systems

Exclusive Hitachi compressor results in high efficiency ratings The core technology of YORK® VRF systems is the exclusive Hitachidesigned high-efficiency scroll compressor. Hitachi invented the first air conditioning scroll compressor in 1983 and in 2008 applied a cuttingedge large-capacity scroll compressor to VRF technology. Its advantages include a high compression ratio, excellent reliability and efficiency, and lower compressor noise level.

Heat pump VRF systems are two-pipe systems that enable design for ductless or ducted applications. Precise heating or cooling is delivered to multiple zones.

Profit from quality and innovation The YORK® VRF line includes a wide selection of products and control options. Numerous innovative features enhance performance, energy efficiency, quiet operation and service life. Quality is built-in, from design through manufacturing in state-of-the-art, ISO-certified facilities.

Figure 1

4

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

5

Get expert advice at every step: select, design, specify, install Your Johnson Controls account team supports you as no one else can, at every step of every project. Effective training, intuitive design and specification software, advanced logistics and delivery, and easily accessible documentation form a powerful support package that adds substantial value to YORK® VRF systems.

Get your team up to speed fast. Efficient performance, quality installations.

Right-size systems with intuitive selection software The YORK® VRF selection software intuitively guides you step by step through equipment selection, so you can quickly and accurately choose an appropriate and cost-effective equipment package for each project.

PC-based program

Comprehensive training programs provide knowledge and skills necessary to effectively and efficiently deploy YORK® VRF technology. Our world-class VRF training center offers a multitude of classes with specialized modules and topics that help:

The PC-based program gives you mobility and flexibility. The software helps you:

• Salespeople submit competitive bids and close deals.

• Accurately select systems using a System Sizing Analysis. The process starts with the indoor fan coil units, so that outdoor units are optimally sized. Proprietary algorithms help determine system size using data input on the indoor units, load, and measurements, so your system does not include capacity that will go unutilized.

• Designers select and configure the right equipment easily and accurately. • Installers learn the proper procedures and complete jobs accurately, on time and on budget. • Service technicians maintain, troubleshoot and repair systems efficiently. The training center includes a dedicated VRF laboratory to provide hands-on experience with the various systems, components and controls. YORK® VRF training programs help deliver peace of mind that your staff is prepared to support your business with the knowledge to compete in a growing industry.

6

Get the tools that give you an edge

JOHNSON CONTROLS | YORK® VRF SYSTEMS

• Design accurate final system drawings including piping and wiring diagrams in an easy, quick, step-by-step process.

• Use intuitively designed features and functionality that make the design process easy, fast, and accurate. You can select options and accessories without referring to additional information or performing additional calculations. • Gain an edge by confidently designing VRF systems that are rightsized, and include the right equipment for each project.

JOHNSON CONTROLS | YORK® VRF SYSTEMS

7

Get winning advice to make the best decisions Consistent delivery: Get the right equipment to the jobsite on time Ample inventory and advanced order management and logistics systems can help you complete installations in a timely manner. Consistent service and predictable deliveries help you prevent delays arising from the wait for essential components and enable you to set a project timeline and schedule labor efficiently. Fast and accurate parts delivery from our main distribution center is our assurance to customers.

YORK® VRF systems bring exciting new possibilities in building space air-conditioning, enabling you to satisfy customers, win more business, and enhance your reputation. When you work with Johnson Controls as your partner, our experts can guide you through a thorough analysis to select the system that best delivers exceptional energy efficiency, increased occupant comfort, and a lower life-cycle cost. You can choose from a wide portfolio of HVAC solutions including: •Y  ORK® VRF systems • YORK® chillers • YORK® rooftop units

Let’s go to work – together YORK® VRF systems can be configured to meet your project requirements and deliver exceptional performance. Select heat pump or cooling only outdoor units with DC inverter-driven compressors offering energy savings and the ability to scale to size. Multiple ventilation options help make sure your systems introduce the right volume of outside air. A host of options and accessories help ensure a custom fit for your project. And users benefit from our variety of control technology options.

YORK® VRF systems

• YORK® custom built-up air handlers • Metasys® building automation systems Our analysis will provide data that helps you appropriately compare all options, so you can make the best-informed decision on every project.

YORK® Chillers

Let’s explore the many advantages of VRF systems together so you can put them to work for your customers. On these pages, you can explore detailed information on the full range of YORK® VRF systems.

YORK® Rooftop units

YORK® Custom built-up air handlers

8

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

9

YORK® VRF Systems: Summary of Features and Benefits BENEFITS

Compact footprint

• Requires less indoor space than conventional systems

• Expands options for positioning outdoor units

Modular components

• Provides flexibility to customize systems to each project’s needs

• Simplifies design process • Allows easy updates as space is reconfigured or expanded

Ductless systems

• Ultimate in design flexibility • Reduces clearance between building floors

• Reduces system costs • Ideal for historic renovations

Ducted systems

• Accommodates retrofits by making use of existing duct infrastructure • Suits unique buildings that include ducted and ductless areas

• Reduces overall construction costs

Heat pump VRF systems

• Precisely heats or cools multiple zones

• Provides extreme system design flexibility

Comprehensive training

• Modules tailored to specific job functions

• Enables effective equipment selection and specification

Installation simplicity

• Outdoor unit piping can be connected from the front, back or underneath. • Small and light indoor units are easy to handle without heavy equipment

• Reduces installation time and cost

• Modules tailored to specific job functions

• Enables professional, high-quality, timely installation

Consistent, reliable product delivery

• Ensures correct components are delivered to job sites on time

• Enhances installation efficiency • Allows efficient labor scheduling

Easy maintenance access

• All components accessible via removal of one panel

• Speeds up time spent on maintenance, repair, and troubleshooting

Refrigerant check

• Checks to make sure system is charged with the correct amount of refrigerant to meet requirements.

• Helps contractor and installer adjust for optimum efficiency and performance

Controls

Comprehensive training

System

• Allows design freedom

Compressor

• Suitable for short or long runs; accommodates nearly all projects

Outdoor Units

Piping flexibility: Design systems with pipe runs up to 1,000 m

FEATURES

Indoor Units

ADVANTAGES

BUILDING OWNER

MECHANICAL CONTRACTOR / INSTALLER

ARCHITECT / SYSTEM DESIGNER

FEATURES

10

JOHNSON CONTROLS | YORK® VRF SYSTEMS

ADVANTAGES

BENEFITS

Rotational operation

• In multiple-unit applications at partial load, outdoor units operate alternately so that operating hours are shared equally.

• Optimizes efficiency • Extends service life • Increases reliability

Backup operation function

• Allows one outdoor unit to be taken off-line for maintenance while remaining units keep operating.

• Avoids system downtime • Protects occupant comfort

Efficiency optimized for part-load operation

• Part Load efficiency among industry’s highest for VRF systems

• Saves energy

Noise reduction preference mode

• Lets users choose from three settings for a “not to exceed” sound level

• Extremely quiet (sound ratings as low as 50 dBA for outdoor units; 27 dBA for indoor units) • Ideal where outdoor units are positioned on side of building or in locations where there are noise restrictions

DC inverter-driven scroll compressor

• Engineered to deliver the optimum efficiency at normal load conditions

• Among industry’s most efficient VRF systems:

Compressor modulation in 1 Hz increments

• Smoothly delivers only the exact amount of refrigerant needed for the load

• Allows fine control for optimum comfort • Saves energy

Demand control

• Users can select from a wide variety of power settings from 100% to 60% and program “not to exceed” a given power level

• Limits electric demand charges • Limits equipment wear and tear • Reduces noise

Load shedding

• Allows programming to turn units on/off in rotation at 10- to 20-minute intervals

• Saves energy • Limits demand charges

Double-blade fan

• Longer fan blades increase airflow quantity by 25%, resulting in higher static pressure

• Reduces noise • Extends motor life

As high as 80 Pa static pressure in ducted systems

• Offers adjustable speeds to match the static pressure requirement

• Flexibility to accommodate long or short ductwork runs

Optional motion and radiant sensors

• Sets back temperature when space is unoccupied, increasing efficiency even further

• Saves energy

H-Link II Protocol

• Controls multiple indoor and outdoor units from one control point • Adds versatility to connect various central control options

• Maximizes indoor comfort • Saves energy • Improves system management

Temperature control

• Adjusts in 1 degree F/C increments • Adjustable fan speeds

• Auto-adjusts for daylight saving time • Provides options to satisfy multiple projects/ buildings

H-LINK II BACnet adapter for integration into BMS

• Enables control of VRF systems by way of a building management system (e.g. Metasys®) for almost unlimited control in a building of campus enterprise.

• Optimizes comfort • Saves energy • Unified interface for all HVAC systems

JOHNSON CONTROLS | YORK® VRF SYSTEMS

11

YORK® VRF INDOOR UNITS

Indoor Units Overview Choose the style and size from the wide selection of indoor units to meet your requirements for layout and design.

Ductless Indoor unit MODEL NUMBERS

4-Way Cassette JTKF028H0PN-0AQ1 JTKF036H0PN-0AQ1 JTKF045H0PN-0AQ1 JTKF050H0PN-0AQ1 JTKF056H0PN-0AQ1 JTKF063H0PN-0AQ1

JTKF071H0PN-0AQ1 JTKF080H0PN-0AQ1 JTKF090H0PN-0AQ1 JTKF112H0PN-0AQ1 JTKF140H0PN-0AQ1 JTKF160H0PN-0AQ1

Wall Mount

Floor Concealed

Floor Ceiling

JTHW022H0NN-0AQ1 JTHW028H0NN-0AQ1 JTHW036H0NN-0AQ1 JTHW045H0NN-0AQ1 JTHW050H0NN-0AQ1 JTHW056H0NN-0AQ1 JTHW063H0NN-0AQ1

JTFC028H0NN-0AQ1 JTFC045H0NN-0AQ1 JTFC056H0NN-0AQ1 JTFC071H0NN-0AQ1

JTFE050H0NN-0AQ1 JTFE056H0NN-0AQ1 JTFE063H0NN-0AQ1 JTFE071H0NN-0AQ1 JTFE084H0NN-0AQ1 JTFE090H0NN-0AQ1 JTFE112H0NN-0AQ1 JTFE142H0NN-0AQ1

Ducted Indoor unit MODEL NUMBERS

Ducted High Static JTDH022H0NN-0AQ1 JTDH028H0NN-0AQ1 JTDH036H0NN-0AQ1 JTDH045H0NN-0AQ1 JTDH050H0NN-0AQ1 JTDH056H0NN-0AQ1 JTDH063H0NN-0AQ1 JTDH071H0NN-0AQ1

Indoor Units YORK® VRF indoor units operate quietly and are easy to install, service and maintain. A wide variety of ductless and ducted units are available in styles and capacities to fit multiple applications. Units operate quietly with sound ratings as low as 27 dBA.

12

4-Way Cassette Wall Mounted Ducted Low Static Ducted High Static Ducted Slim Floor Concealed Floor and Ceiling AHU-Kit

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JTDH080H0NN-0AQ1 JTDH090H0NN-0AQ1 JTDH112H0NN-0AQ1 JTDH140H0NN-0AQ1 JTDH160H0NN-0AQ1 JTDH224H0NM-0AQ1 JTDH280H0NM-0AQ1

Ducted Slim JTDS022H0PN-0AQ1 JTDS028H0PN-0AQ1 JTDS036H0PN-0AQ1 JTDS045H0PN-0AQ1 JTDS050H0PN-0AQ1 JTDS056H0PN-0AQ1

Ducted Low Static JTDL022H0NN-0AQ1 JTDL028H0NN-0AQ1 JTDL036H0NN-0AQ1 JTDL045H0NN-0AQ1 JTDL050H0NN-0AQ1 JTDL056H0NN-0AQ1 JTDL063H0NN-0AQ1 JTDL071H0NN-0AQ1

JTDL080H0NN-0AQ1 JTDL090H0NN-0AQ1 JTDL112H0NN-0AQ1 JTDL140H0NN-0AQ1 JTDL160H0NN-0AQ1 JTDL224H0NM-0AQ1 JTDL280H0NM-0AQ1

AHU-Kit JTDS063H0PN-0AQ1 JTDS071H0PN-0AQ1 JTDN022H0PN-0AQ1 JTDN028H0PN-0AQ1 JTDN036H0PN-0AQ1 JTDN045H0PN-0AQ1

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JDXF-2.0A JDXF-4.0A

JDXF-6.0A JDXF-10.0A

13

YORK® VRF INDOOR UNITS

Indoor Unit Selection

kW 2.2 2.8 3.6 4.5 5 5.6 6.3 7.1 8 9 11.2 14 16 22.4 28 4-Way Cassette

Wall Mount

Ducted High Static Ducted Low Static

Ducted Slim

Floor Concealed

4-Way Cassette Indoor Unit Ceiling mounted 4-way cassettes measuring 33 x 33 inch (84 x 84 cm) are offered with standard decorative panels. Compact, thin and lightweight, they are easy to install even in tight spaces.

Floor Ceiling

HP

2

4

6

8

10

Key Features • Optional motion and radiant heat sensors for shutoff and activation in response to room occupancy

Capacities: 2.8 to 16kW

• Multiple fan speed settings

AHU-Kit

• Optional fresh air kit available • Four air volume settings including Ultra Hi for higher ceilings • 4-way airflow standard but can be configured for 2-way or 3-way • Integrated condensate pumps included in all units • Uniform panel sizing • Optional lift mechanism allows panel to be lowered for convenient service access

14

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

15

YORK® VRF INDOOR UNITS

4-Way Cassette Indoor Unit

4-Way Cassette Indoor Unit

Indoor Unit Type JTKF028H0PN-0AQ1

JTKF036H0PN-0AQ1

Sound Pressure Level (High/Medium/Low)

Outer Dimension

Btu/h

19,100

21,500

24,200

5.6

kW

6.5

7.5

8.5

9.6

Nominal Heating Capacity

kcal/h

5,600

6,500

7,300

8,300

Btu/h

22,200

25,600

29,000

32,800

Sound Pressure Level (High/Medium/Low)

dB (A)

32-30-28

32-30-28

32-30-28

32-30-28

3.3

4.9

4.2

kcal/h

2,800

3,600

4,200

4,800

Btu/h

11,100

14,300

16,700

19,100

dB (A)

32-30-28

32-30-28

32-30-28

248

248

248

32-30-28 248

(9-3/4)

(9-3/4)

(9-3/4)

(9-3/4)

840

840

840

840

(33-1/16)

(33-1/16)

(33-1/16)

(33-1/16)

840

840

840

840

(33-1/16)

(33-1/16)

(33-1/16)

(33-1/16)

23

23

23

24

(51)

(51)

(51)

(53)

13/12/11

15/13.5/12

15/13.5/12

16/14/12

(cfm)

(459/424/388)

(530/477/424)

(530/477/424)

(565/494/424)

W

56

56

56

56

Approximate Packing Measurement

Width

mm (in.)

Depth

mm (in.)

Net Weight

kg (Ibs.)

Air Flow Rate (Hi/Me/Lo) Motor

Φ6.35

Φ6.35

(1/4)

(1/4)

(1/4)

(1/4)

mm

Φ12.7

Φ12.7

Φ12.7

Φ15.88

(in.)

(1/2)

(1/2)

(1/2)

(5/8)

VP25

VP25

VP25

VP25

Condensate Drain

0.22

Approximate Packing Measurement

0.22 P-N23NAQ

0.22

0.22

P-N23NAQ

P-N23NAQ

mm (in.) mm (in.) mm (in.) kg (lbs.) m3

248

248

298

(9-3/4)

(9-3/4)

(11-3/4)

840

840

840

840

(33-1/16)

(33-1/16)

(33-1/16)

(33-1/16)

840

840

840

840

(33-1/16)

(33-1/16)

(33-1/16)

(33-1/16)

24

24

24

26

(53)

(53)

(53)

(57)

P-N23NAQ

m3/min.

16/14/12

19/17/14

20/17/15

26/23/20

(cfm)

(565/494/424)

(671/600/494)

(706/600/530)

(918/812/706)

W

56

56

56

56

mm

Refrigerant Piping

Φ6.35

m3

248 (9-3/4)

R410A (Nitrogen-Charged for Corrosion-Resistance)

Indoor Fan

Φ6.35

Liquid Line Gas Line

Flare-Nut Connection (with Flare Nuts)

(in.)

Φ6.35

Φ9.53

Φ9.53

Φ9.53

(1/4)

(3/8)

(3/8)

(3/8)

mm

Φ15.88

Φ15.88

Φ15.88

Φ15.88

(in.)

(5/8)

(5/8)

(5/8)

(5/8)

VP25

VP25

VP25

VP25

m

3

Adaptable Panel Model

0.22

0.22

0.22

0.26

P-N23NAQ

P-N23NAQ

P-N23NAQ

P-N23NAQ

37

37

37

37

(1-7/16)

(1-7/16)

(1-7/16)

(1-7/16)

Neutral White

Color

37

37

37

37

(1-7/16)

(1-7/16)

(1-7/16)

(1-7/16)

950

950

950

950

(37-3/8)

(37-3/8)

(37-3/8)

(37-3/8)

950

950

950

950

(37-3/8)

(37-3/8)

(37-3/8)

(37-3/8)

6

6

6

6

(13)

(13)

(13)

(13)

0.08

0.08

0.08

0.08

Outer Dimension

Height

mm (in.)

Width

mm (in.)

Depth

mm (in.)

Net Weight Approximate Packing Measurement

kg (lbs.) m3

950

950

950

950

(37-3/8)

(37-3/8)

(37-3/8)

(37-3/8)

950

950

950

950

(37-3/8)

(37-3/8)

(37-3/8)

(37-3/8)

6

6

6

6

(13)

(13)

(13)

(13)

0.08

0.08

0.08

0.08

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

16

mm (in.)

(in.)

Neutral White

Net Weight

Outer Dimension

Height

Connections

Flare-Nut Connection (with Flare Nuts)

Color

Depth

Nominal Cooling Capacity

Refrigerant

m3/min.

Adaptable Panel Model

Width

28,700

4,300

Condensate Drain

Height

7,200

17,000

mm

Approximate Packing Measurement

6,100

3,700

R410A (Nitrogen-Charged for Corrosion-Resistance)

Gas Line

5,400

14,700

kg (Ibs.)

Liquid Line

8.4

4,800

3,100

mm (in.)

Refrigerant Piping

7.1

kcal/h

AC 1Φ,220-240V/50Hz

12,300

Depth

Connections

6.3

9,500

mm (in.)

Air Flow Rate (Hi/Me/Lo)

5.6

2,400

Width

Motor

JTKF080H0PN-0AQ1

Btu/h

Refrigerant

Outer Dimension

5.0

JTKF071H0PN-0AQ1

kcal/h

mm (in.)

Indoor Fan

kW

Indoor Unit Power Supply 4.3

3.6

JTKF063H0PN-0AQ1

2.8

Height

Net Weight

JTKF050H0PN-0AQ1

JTKF056H0PN-0AQ1

kW

kW Nominal Heating Capacity

JTKF045H0PN-0AQ1

4-Way Cassette Type

Model

AC 1Φ,220-240V/50Hz

Indoor Unit Power Supply Nominal Cooling Capacity

Indoor Unit Type

4-Way Cassette Type

Model

(continued)

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

17

YORK® VRF INDOOR UNITS

4-Way Cassette Indoor Unit

(continued)

Indoor Unit Type

4-Way Cassette Type

Model

JTKF090H0PN-0AQ1

JTKF112H0PN-0AQ1

kW

9.0

11.2

14.2

16.0

kcal/h

7,700

9,600

12,200

13,800

Btu/h

30,700

38,000

48,400

54,600

kW

10.0

13.0

16.3

18.0

Nominal Heating Capacity

kcal/h

8,600

11,200

14,000

15,500

Btu/h

34,100

44,400

55,500

61,400

Sound Pressure Level (High/Medium/Low)

dB (A)

34-32-30

41-36-33

43-38-35

44-40-36

Outer Dimension

Height

mm (in.)

Width

mm (in.)

Depth

mm (in.)

Net Weight

kg (Ibs.)

298

298

298

298

(11-3/4)

(11-3/4)

(11-3/4)

(11-3/4)

840

840

840

840

(33-1/16)

(33-1/16)

(33-1/16)

(33-1/16)

840

840

840

840

(33-1/16)

(33-1/16)

(33-1/16)

(33-1/16)

26

29

29

29

(57)

(64)

(64)

(64)

R410A (Nitrogen-Charged for Corrosion-Resistance)

Refrigerant Indoor Fan Air Flow Rate (Hi/Me/Lo) Motor Connections

m3/min.

26/23/20

32/28/24

34/29/25

37/32/27

(cfm)

(918/812/706)

(1,130/989/847)

(1,201/1,024/883)

(1,307/1,130/954)

W

56

108

108

108

mm

Refrigerant Piping Liquid Line Gas Line

Approximate Packing Measurement

Flare-Nut Connection (with Flare Nuts)

(in.)

Φ9.53

Φ9.53

Φ9.53

Φ9.53

(3/8)

(3/8)

(3/8)

(3/8)

mm

Φ15.88

Φ15.88

Φ15.88

Φ15.88

(in.)

(5/8)

(5/8)

(5/8)

(5/8)

VP25

VP25

VP25

VP25

0.26

0.26

0.26

0.26

P-N23NAQ

P-N23NAQ

P-N23NAQ

P-N23NAQ

Condensate Drain m

3

Adaptable Panel Model

Neutral White

Color Height Outer Dimension

JTKF160H0PN-0AQ1

AC 1Φ,220-240V/50Hz

Indoor Unit Power Supply Nominal Cooling Capacity

JTKF140H0PN-0AQ1

mm (in.)

Width

mm (in.)

Depth

mm (in.)

Net Weight Approximate Packing Measurement

kg (lbs.) m3

37

37

37

37

(1-7/16)

(1-7/16)

(1-7/16)

(1-7/16)

950

950

950

950

(37-3/8)

(37-3/8)

(37-3/8)

(37-3/8)

950

950

950

950

(37-3/8)

(37-3/8)

(37-3/8)

(37-3/8)

6

6

6

6

(13)

(13)

(13)

(13)

0.08

0.08

0.08

0.08

Wall Indoor Unit Wall-mount units include wide-angle louvers that distribute airflow comfortably. An auto-swing function ensures efficient air distribution and uniform temperature throughout the conditioned space. Refrigerant and drain piping can be connected at the right, left or rear of the unit for ease of installation.

Key Features • Removable front panel for easy cleaning

• Standard condensate pump

JTHW022H0NN-0AQ1

Nominal Cooling Capacity

Nominal Heating Capacity

Sound Pressure Level (High/Medium/Low) Outer Dimension(H)

Outer Dimension(W)

Net Weight

2.2

2.8

3.6

kcal/h

1,900

2,400

3,100

Btu/h

7,500

9,600

12,300

kw

2.5

3.3

4

kcal/h

2,150

2,800

3,450

Btu/h

8,500

11,100

13,600

dB(A)

38/36/32

38/36/32

40/36/34

mm

280

280

280

(in.)

11

11

11 780

mm

780

780

(in.)

31

31

31

mm

220

220

220

(in.)

9

9

9

kg

10

10

10

(lbs)

22

22

22

R410A (Nitrogen-charged for Corrosion-resistance)

lndoor Fan Air Flow Rate

m3/

(Cooling/Heating)

min w

Gas Line

30

Approximate Packing

JOHNSON CONTROLS | YORK® VRF SYSTEMS

510/450/390

550/450/400

30

30

Flare-nut Connection(with Flare Nuts) mm

Φ6.35

Φ6.35

Φ6.35

(in.)

(1/4)

(1/4)

(1/4)

mm

Φ12.7

Φ12.7

Φ12.7

(in.)

(1/2)

(1/2)

(1/2)

VP16

VP16

VP16

0.12

0.12

0.12

Condensate Drain

JOHNSON CONTROLS | YORK® VRF SYSTEMS

510/450/390

Connections Refrigerant Piping Liquid Line

JTHW036H0NN-0AQ1

kw

Refrigerant

Motor Power

JTHW028H0NN-0AQ1 AC1Φ.220V-240V/50HZ

Power Supply

Measurement

18

Wall Type

Model

Outer Dimension(D)

• Standard wireless controller and built-in wireless sensor

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

lndoor

m3

19

YORK® VRF INDOOR UNITS

Ducted Low Static Indoor Unit Features • High-efficiency DC fan motor • Multiple fan speed settings Capacities: 2.2 to 6.3 kW

• Up to 30 pa static pressure • Bottom access for easy service and troubleshooting

Wall Indoor Unit (continued) lndoor

Wall Type

Model

Capacity

Nominal Heating Capacity Sound Pressure Level (High/Medium/Low) Outer Dimension(H)

Outer Dimension(W)

Outer Dimension(D)

Net Weight

JTHW050H0NN-0AQ1

kw

4

5

Motor Power

5.6

6.3

kcal/h

3,450

4,300

4,800

5,400

Btu/h

13,600

17,000

19,100

21,500

Gas Line

4.5

5.6

6.3

7.1

3,900

4,800

5,400

6,100

Btu/h

15,300

19,100

21,500

24,200

dB (A)

41/38/35

41/38/35

41/38/35

44/41/38

mm

280

290

290

290

(in.)

11

12

12

12

mm

780

1050

1050

1050

(in.)

31

41

41

41

mm

220

220

220

220

(in.)

9

9

9

9

kg

10

13.5

13.5

13.5

(lbs)

22

30

30

30

R410A (Nitrogen-charged for Corrosion-resistance) 600/510/450

720/620/520

720/620/520

820/720/620

w

40

50

50

60

Flare-nut Connection(with Flare Nuts) mm

Φ6.35

Φ6.35

Φ6.35

(in.)

(1/4)

(1/4)

(1/4)

(1/4)

mm

Φ12.7

Φ15.88

Φ15.88

Φ15.88

(in.)

(1/2)

(5/8)

(5/8)

(5/8)

VP16

VP16

VP16

VP16

0.12

0.15

0.15

0.15

m3

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

20

Φ6.35

JTDL022H0NN-0AQ1

2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

JTDL036H0NN-0AQ1

JTDL045H0NN-0AQ1

JTDL050H0NN-0AQ1

AC 1Φ,220-240V/50Hz

Nominal Cooling Capacity

kW kcal/h Btu/h

2.2 1,900 7,500

2.8 2,400 9,500

3.6 3,100 12,300

4.3 3,700 14,700

5.0 4,300 17,000

Nominal Heating Capacity

kW kcal/h Btu/h

2.8 2,400 9,600

3.3 2,800 11,100

4.2 3,600 14,300

4.9 4,200 16,700

5.6 4,800 19,100

dB (A)

29.5-26-24.5

29.5-26-24.5

34-32-30

34-32-30

34-32-30

Height

mm (in.)

270 (10-5/8)

270 (10-5/8)

270 (10-5/8)

270 (10-5/8)

270 (10-5/8)

Width

mm (in.)

650+75 (25-9/16+2-15/16)

650+75 (25-9/16+2-15/16)

650+75 (25-9/16+2-15/16)

650+75 (25-9/16+2-15/16)

650+75 (25-9/16+2-15/16)

Depth

mm (in.)

720 (28-3/8)

720 (28-3/8)

720 (28-3/8)

720 (28-3/8)

720 (28-3/8)

kg (Ibs.)

26 (57)

26 (57)

26 (57)

26 (57)

35 (77)

Sound Pressure Level (High/Medium/Low)

Outer Dimension

Net Weight

Indoor Fan Air Flow Rate (Hi/Me/Lo)

R410A (Nitrogen-Charged for Corrosion-Resistance) m3/min. (cfm)

8/7/6 (283/247/212)

8/7/6 (283/247/212)

13/11/9 (459/388/212)

13/11/9 (459/388/212)

15/13/11 (530/459/358)

External Pressure

pa

30

30

30

30

30

Motor

W

20

20

40

40

45

Connections Refrigerant Piping

Flare-Nut Connection (with Flare Nuts)

Liquid Line

mm (in.)

Φ6.35 (1/4)

Φ6.35 (1/4)

Φ6.35 (1/4)

Φ6.35 (1/4)

Φ6.35 (1/4)

Gas Line

mm (in.)

Φ12.7 (1/2)

Φ12.7 (1/2)

Φ12.7 (1/2)

Φ12.7 (1/2)

Φ15.88 (3/8)

VP25

VP25

VP25

VP25

VP25

0.21

0.21

0.21

0.21

0.27

Condensate Drain Approximate Packing Measurement

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JTDL028H0NN-0AQ1

Indoor Unit Power Supply

Refrigerant

m /min

Condensate Drain Approximate Packing Measurement

Model

kw

3

In-the-Ceiling Type (Low Static Pressure)

JTHW063H0NN-0AQ1

kcal/h

Connections Refrigerant Piping Liquid Line

JTHW056H0NN-0AQ1

AC1Φ.220V-240V/50HZ

Refrigerant lndoor Fan Air Flow Rate (Cooling/Heating)

Indoor Unit Type

JTHW045H0NN-0AQ1

Power Supply Nominal Cooling

Capacities: 2.2 to 28 kW

• Built-in condensate pump

m3

JOHNSON CONTROLS | YORK® VRF SYSTEMS

21

YORK® VRF INDOOR UNITS

Ducted Low Static Indoor Unit (continued) Indoor Unit Type JTDL056H0NN-0AQ1

JTDL063H0NN-0AQ1

kW

Capacity Sound Pressure Level (High/Medium/Low) Height Outer Dimension

Width Depth

Net Weight

5.6

Air Flow Rate (Hi/Me/Lo) External Pressure Motor

Packing Measurement

22

9.0

4,800

5,400

6,100

7,200

7,700

21,500

24,200

28,700

30,700

kW

6.5

7.5

8.5

9.6

10.0

kcal/h

5,600

6,500

7,300

8,300

8,600

Btu/h

22,200

25,600

29,000

32,800

34,100

dB(A)

34-32-30

35-33-31

35-33-31

40-37-33

40-37-33

mm

270

270

270

350

350

(in.)

(10-5/8)

(10-5/8)

(10-5/8)

(13-3/4)

(13-3/4)

mm

900+75

900+75

900+75

900+75

900+75

(in.)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

mm

720

720

720

800

800

(in.)

(28-3/8)

(28-3/8)

(28-3/8)

(31-1/2)

(31-1/2)

kg

35

35

35

46

46

(Ibs.)

(77)

(77)

(77)

(101)

(101)

m3/min.

15/13/11

16/14/12

16/14/12

25/21/17

25/21/17

(cfm)

(530/459/388)

(565/494/424)

(565/494/424)

(883/741/600)

(883/741/600)

pa

30

30

30

60

60

45

45

45

100

100

JTDL140H0NN-0AQ1

AC 1Φ,220-240V-50Hz

JTDL160H0NN-0AQ1

JTDL224H0NM-0AQ1

AC 1Φ,220V/50Hz

JTDL280H0NM-0AQ1

AC 3Φ,380-415V/50Hz

Nominal Cooling Capacity

kW kcal/h Btu/h

12.6 9,600 38,000

14.2 12,200 48,400

16.0 13,800 54,600

22.4 19,300 76,500

28.0 24,100 95,600

Nominal Heating Capacity

kW kcal/h Btu/h

13.0 11,200 44,400

16.3 14,000 55,500

18.0 15,500 61,400

25.0 21,500 85,300

31.5 27,100 107,500

dB(A)

41.5-39-35

42-39-35

43-39-37

50

52

Height

mm (in.)

350 (13-3/4)

350 (13-3/4)

350 (13-3/4)

470 (18-1/2)

470 (18-1/2)

Width

mm (in.)

900+75 (35-7/16+2-15/16)

1,300+75 (51-3/16+2-15/16)

1,300+75 (51-3/16+2-15/16)

1,060 (41-3/4)

1,250 (49-1/4)

Depth

mm (in.)

800 (31-1/2)

800 (31-1/2)

800 (31-1/2)

1,120 (44-1/12)

1,120 (44-1/12)

kg (Ibs.)

46 (101)

58 (128)

58 (128)

94 (207)

106 (234)

Sound Pressure Level (High/Medium/Low)

Outer Dimension

Net Weight

Indoor Fan Air Flow Rate (Hi/Me/Lo)

R410A (Nitrogen-Charged for Corrosion-Resistance) m3/min. (cfm)

27/23/19 (954/812/671)

37/31/25 (1,306/1,095/883)

38/35/29 (1,341/1,236/1,024)

58 (2,048)

72 (2,542)

External Pressure

pa

60

60

60

100

100

Motor

W

100

160

180

900

1,070

Connections Refrigerant Piping

Flare-Nut Connection (with Flare Nuts)

Flare-Nut Connection (with Flare Nuts)

Liquid Line

mm (in.)

Φ9.53 (3/8)

Φ9.53 (3/8)

Φ9.53 (3/8)

Φ9.53 (3/8)

Φ9.53 (3/8)

Gas Line

mm (in.)

Φ15.88 (5/8)

Φ15.88 (5/8)

Φ15.88 (3/8)

Φ19.05 (3/4)

Φ22.2 (7/8)

VP25

VP25

VP25

VP25

VP25

0.38

0.52

0.52

0.90

1.06

mm

Φ6.35

Φ9.53

Φ9.53

Φ9.53

Φ9.53

(in.)

(1/4)

(3/8)

(3/8)

(3/8)

(3/8)

mm

Φ15.88

Φ15.88

Φ15.88

Φ19.05

Φ22.2

(in.)

(5/8)

(5/8)

(3/8)

(3/4)

(7/8)

Condensate Drain

VP25

VP25

VP25

VP25

VP25

Approximate Packing Measurement

0.27

0.27

0.27

0.38

0.38

m3

JTDL112H0NN-0AQ1

Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)

Condensate Drain Approximate

8.4

19,800

Refrigerant Piping

Gas Line

Model

JTDL090H0NN-0AQ1

Btu/h

W

In-the-Ceiling Type (Low Static Pressure)

Indoor Unit Power Supply

7.1

6.3

Connections

Liquid Line

JTDL080H0NN-0AQ1

kcal/h

Refrigerant Indoor Fan

JTDL071H0NN-0AQ1 AC 1Φ,220-240V/50Hz

Indoor Unit Power Supply

Nominal Heating

Indoor Unit Type

In-the-Ceiling Type (Low Static Pressure)

Model

Nominal Cooling Capacity

Ducted Low Static Indoor Unit (continued)

m3

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. With Discharge Duct (2.0m) and Return Duct (1.0m). Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field. 3. The data for external pressure indicates” Standard Pressure Setting values when a filter is not used.

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

23

YORK® VRF INDOOR UNITS

Ducted High Static Indoor Unit

Ducted High Static Indoor Unit (continued)

Features

Indoor Unit Type Model

• High-efficiency DC fan motor • Multiple fan speed settings

Nominal Cooling Capacity

• Bottom access for easy service and troubleshooting Capacities: 2.2 to 28 kW

• Built-in condensate pump

Nominal Heating Capacity

Indoor Unit Type

In-the-Ceiling Type (High Static Pressure) JTDH022H0NN-0AQ1

JTDH028H0NN-0AQ1

JTDH036H0NN-0AQ1

Sound Pressure Level

JTDH045H0NN-0AQ1

JTDH050H0NN-0AQ1

(High/Medium/Low) Height

AC 1Φ,220-240V50Hz

Indoor Unit Power Supply

Nominal Cooling Capacity

Nominal Heating Capacity Sound Pressure Level (High/Medium/Low)

Outer Dimension

Width Depth

Net Weight

5.0

2.2

2.8

kcal/h

1,900

2,400

3,100

3,700

4,300

Btu/h

7,500

9,500

12,300

14,700

17,000

kW

2.8

3.3

4.2

4.9

5.6

kcal/h

2,400

2,800

3,600

4,200

4,800

Btu/h

9,600

11,100

14,300

16,700

19,100

dB(A)

35-33-31

35-33-31

35-33-31

35-33-31

35-33-31

mm

270

270

270

270

270

(in.)

(10-5/8)

(10-5/8)

(10-5/8)

(10-5/8)

(10-5/8)

mm

650+75

650+75

650+75

650+75

900+75

(in.)

(25-9/16+2-15/16)

(25-9/16+2-15/16)

(25-9/16+2-15/16)

(25-9/16+2-15/16)

(35-7/16+2-15/16)

mm

720

720

720

720

720

(in.)

(28-3/8)

(28-3/8)

(28-3/8)

(28-3/8)

(28-3/9)

kg

26

26

26

26

35

(Ibs.)

(57)

(57)

(57)

(57)

(77)

Outer Dimension

Width Depth

Net Weight

Indoor Fan Air Flow Rate (Hi/Me/Lo) External Pressure (Option) Motor

m3/min.

8/7/6

8/7/6

13/11/9

13/11/9

15/13/11

(cfm)

(283/247/212)

(283/247/212)

(459/388/212)

(459/388/212)

(530/459/358)

pa

50(80)

50(80)

50(80)

50(80)

50(80)

35

35

Connections

Gas Line

Packing Measurement

75

Φ6.35

mm

Φ6.35

Φ6.35

Φ6.35

Φ6.35

(in.)

(1/4)

(1/4)

(1/4)

(1/4)

(1/4)

mm

Φ12.7

Φ12.7

Φ12.7

Φ12.7

Φ15.88

(in.)

(1/2)

(1/2)

(1/2)

(1/2)

(5/8)

VP25

VP25

VP25

VP25

VP25

0.21

0.21

0.21

0.21

0.27

Condensate Drain Approximate

60

JTDH080H0NN-0AQ1

JTDH090H0NN-0AQ1

kW

5.6

6.3

7.1

8.4

9.0

4,800

5,400

6,100

7,200

7,700

Btu/h

19,100

21,500

24,200

28,700

30,700

kW

6.5

7.5

8.5

9.6

10.0

kcal/h

5,600

6,500

7,300

8,300

8,600

Btu/h

22,200

25,600

29,000

32,800

34,100

dB(A)

35-33-31

36-34-32

36-34-32

42-39-35

42-39-35

mm

270

270

270

350

350

(in.)

(10-5/8)

(10-5/8)

(10-5/8)

(13-3/4)

(13-3/4)

mm

900+75

900+75

900+75

900+75

900+75

(in.)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

(35-7/16+2-15/16)

mm

720

720

720

800

800

(in.)

(28-3/8)

(28-3/8)

(28-3/8)

(31-1/2)

(31-1/2)

kg

35

35

35

46

46

(Ibs.)

(77)

(77)

(77)

(101)

(101)

R410A (Nitrogen-Charged for Corrosion-Resistance) m3/min.

15/13/11

16/14/12

16/14/12

25/21/17

25/21/17

(cfm)

(530/459/388)

(565/494/424)

(565/494/424)

(883/741/600)

(883/741/600)

External Pressure (Option)

pa

50(80)

50(80)

50(80)

120(90)

120(90)

Motor

W

75

75

75

120

120

Φ9.53

Air Flow Rate (Hi/Me/Lo)

Connections

Flare-Nut Connection (with Flare Nuts)

Refrigerant Piping

Gas Line

mm

Φ6.35

Φ9.53

Φ9.53

Φ9.53

(in.)

(1/4)

(3/8)

(3/8)

(3/8)

(3/8)

mm

Φ15.88

Φ15.88

Φ15.88

Φ15.88

Φ15.88

(in.)

(5/8)

(5/8)

(5/8)

(5/8)

(5/8)

VP25

VP25

VP25

VP25

VP25

Approximate Packing Measurement

0.27

0.27

0.27

0.38

0.38

m3

Flare-Nut Connection (with Flare Nuts)

Refrigerant Piping Liquid Line

60

JTDH071H0NN-0AQ1

kcal/h

Condensate Drain

W

JTDH063H0NN-0AQ1

AC 1Φ,220-240V/50Hz

Refrigerant

Liquid Line

R410A (Nitrogen-Charged for Corrosion-Resistance)

Refrigerant

24

4.3

3.6

kW

Indoor Fan Height

JTDH056H0NN-0AQ1

Indoor Unit Power Supply

• Up to 80 pa static pressure

Model

In-the-Ceiling Type (High Static Pressure)

m3

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

25

YORK® VRF INDOOR UNITS

Ducted High Static Indoor Unit (continued) Indoor Unit Type

Ducted Slim Narrow Indoor Unit Features

In-the-Ceiling Type (High Static Pressure)

Model

JTDH112H0NN-0AQ1

JTDH140H0NN-0AQ1

JTDH224H0NM-0AQ1

AC 1Φ,220V/50Hz

AC 1Φ,220-240V/50Hz

Indoor Unit Power Supply

JTDH160H0NN-0AQ1

JTDH280H0NM-0AQ1

• High-efficiency DC fan motor • Multiple fan speed settings

AC 3Φ,380-415V/50Hz

• Up to 30 pa static pressure

Nominal Cooling Capacity

kW kcal/h Btu/h

11.2 9,600 38,000

14.2 12,200 48,400

16.0 13,800 54,600

22.4 19,300 76,500

28.0 24,100 95,600

Nominal Heating Capacity

kW kcal/h Btu/h

13.0 11,200 44,400

16.3 14,000 55,500

18.0 15,500 61,400

25.0 21,500 85,300

31.5 27,000 107,000

dB (A)

43-40-36

44-41-37

45-41-37

50

52

Indoor Unit

mm (in.)

350 (13-3/4)

350 (13-3/4)

350 (13-3/4)

470 (18-1/2)

470 (18-1/2)

Power Supply

Width

mm (in.)

900+75 (35-7/16+2-15/16)

1,300+75 (51-3/16+2-15/16)

1,300+75 (51-3/16+2-15/16)

1,060 (41-3/4)

1,250 (49-1/4)

Depth

mm (in.)

800 (31-1/2)

800 (31-1/2)

800 (31-1/2)

1,120 (44-1/2)

1,120 (44-1/12)

kg (Ibs.)

46 (101)

58 (128)

58 (128)

96 (211)

108 (238)

Sound Pressure Level (High/Medium/Low) Height Outer Dimension

Net Weight

Indoor Fan Air Flow Rate (Hi/Me/Lo)

m3/min. (cfm)

27/23/19 (954/812/671)

37/31/25 (1,306/1,095/883)

38/35/29 (1,341/1,236/1,024)

58 (2,048)

72 (2,542)

pa

120(90)

120(90)

120(90)

180

180

Motor

W

120

200

280

650

900

Connections Refrigerant Piping

JTDN022H0PN-0AQ1

Nominal Cooling Capacity

Nominal Heating Capacity

Sound Pressure Level (High/Medium/Low)

mm (in.)

Φ9.53 (3/8)

Φ9.53 (3/8)

Φ9.53 (3/8)

Φ9.53 (3/8)

Φ9.53 (3/8)

Gas Line

mm (in.)

Φ15.88 (5/8)

Φ15.88 (5/8)

Φ15.88 (5/8)

Φ19.05 (3/4)

Φ22.2 (7/8)

Condensate Drain m3

Net Weight

VP25

VP25

VP25

VP25

VP25

0.38

0.52

0.52

0.90

1.06

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. With Discharge Duct (2.0m) and Return Duct (1.0m). Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field. 3. The data for external pressure indicates” Standard Pressure Setting values when a filter is not used.

Indoor Fan Air Flow Rate (High /Medium /Low) Motor Power

JTDN028H0PN-0AQ1

Gas Line

2.2

2.8

kcal/h

1,900

2,400

3,100

3,700

Btu/h

7,500

9,500

12,300

14,700

Kw

2.8

3.3

4.2

4.9

kcal/h

2,400

2,800

3,600

4,200

Btu/h

9,600

11,100

14,300

16,700

dB(A)

28-25-22

28-25-22

32-30-28

32-30-28

3.6

4.3

H

mm

192

192

192

192

W

mm

700

700

700

700

D

mm

902

602

602

602

kg

21

21

21

21

(lbs)

46

46

48

48

R410A (Nitrogen-charged for Corrosion-resistance) m3/min

8/7/6

8/7/6

10/8/7

10/8/7

w

50

50

60

60

mm

Φ6.35

Φ6.35

Φ6.35

Φ6.35

(in.)

(1/4)

(1/4)

(1/4)

(1/4)

mm

Φ12.7

Φ12.7

Φ12.7

Φ12.7

(in.)

(1/2)

(1/2)

(1/2)

(1/2)

Flare-nut Connection (with Flare Nuts)

VP25

Condensate Drain External Pressure (Option)

Pa

10(30)

10(30)

10(30)

10(30)

Approximate Packing Measurement

m3

0.15

0.15

0.15

0.15

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JTDN045H0PN-0AQ1

Kw

Connections Refrigerant Piping Liquid Line

JTDN036H0PN-0AQ1

AC 1Φ,220V~240V/50Hz

Refrigerant

Flare-Nut Connection (with Flare Nuts)

Liquid Line

26

Slim In-the Ceiling Type

Model

Outer Dimension

External Pressure (Option)

Approximate Packing Measurement

• Built-in condensate pump

R410A (Nitrogen-Charged for Corrosion-Resistance)

Refrigerant

Capacities: 2.2 to 4.5 kW

• Bottom access for easy service and troubleshooting

JOHNSON CONTROLS | YORK® VRF SYSTEMS

2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. With Discharge Duct (2.0m) and Return Duct (1.0m). Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field. 3. The data for external pressure indicates” Standard Pressure Setting values when a filter is not used.

27

YORK® VRF INDOOR UNITS

Ducted Slim Indoor Unit

Ducted Slim Indoor Unit (continued)

Features

Indoor Unit Type

• High-efficiency DC fan motor

Model

• Multiple fan speed settings Capacities: 2.2 to 7.1 kW

• Bottom access for easy service and troubleshooting

Nominal Cooling Capacity

• Built-in condensate pump

Nominal Heating Capacity Sound Pressure Level

Indoor Unit Type JTDS022H0PN-0AQ1

JTDS028H0PN-0AQ1

(High/Medium/Low) Height Outer Dimension

Width Depth

Net Weight

JTDS036H0PN-0AQ1

Outer Dimension

3.6

2.2

2.8

kcal/h

1,900

2,400

3,100

3,700

Btu/h

7,500

9,500

12,300

14,700

kW

2.8

3.3

4.2

4.9

2,400

2,800

3,600

4,200

Refrigerant

Btu/h

9,600

11,100

14,300

16,700

Indoor Fan Air Flow Rate

dB(A)

27-24-21

27-24-21

31-29-26

31-29-26

mm

192

192

192

192

(in.)

(7-9/16)

(7-9/16)

(7-9/16)

(7-9/16)

mm

900

900

900

900

(in.)

(35-7/16)

(35-7/16)

(35-7/16)

(35-7/16)

mm

447

447

447

447

(in.)

(17-19/32)

(17-19/32)

(17-19/32)

(17-19/32)

21

21

22

22

(46)

(46)

(48)

(48)

kg (Ibs.)

8/7/6

8/7/6

10/8/7

10/8/7

(283/247/212)

(283/247/212)

(353/283/247)

(353/283/247)

External Pressure (Option)

pa

10(30)

10(30)

10(30)

10(30)

Motor

W

16

16

25

25

Connections

Flare-Nut Connection (with Flare Nuts)

Refrigerant Piping

Gas Line

mm

Φ6.35

Φ6.35

Φ6.35

(in.)

(1/4)

(1/4)

(1/4)

(1/4)

mm

Φ12.7

Φ12.7

Φ12.7

Φ12.7

(in.)

(1/2)

(1/2)

(1/2)

(1/2)

VP25

VP25

VP25

VP25

0.15

0.15

0.15

0.15

Condensate Drain Approximate Packing Measurement

28

JTDS056H0PN-0AQ1

m3

Φ6.35

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JTDS063H0PN-0AQ1

JTDS071H0PN-0AQ1

AC 1Φ,220-240V/50Hz kW

5.0

5.6

6.3

7.1

kcal/h

4,300

4,800

5,400

6,100

Btu/h

17,100

19,100

21,500

24,200

kW

5.6

6.5

7.5

8.5

kcal/h

4,800

5,600

6,500

7,300

Btu/h

19,100

22,200

25,600

29,000

dB(A)

34-30-28

34-30-28

35-33-30

35-33-30

mm

192

192

192

192

(in.)

(7-9/16)

(7-9/16)

(7-9/16)

(7-9/16)

mm

1,170

1,170

1,170

1,060

(in.)

(46-1/16)

(46-1/16)

(46-1/16)

(41-3/4)

mm

447

447

447

447

(in.)

(17-19/32)

(17-19/32)

(17-19/32)

(17-19/32)

kg (Ibs.)

27

27

27

27

(59)

(59)

(59)

(59)

R410A (Nitrogen-Charged for Corrosion-Resistance) m3/min.

14.5/12.5/10.5

14.5/12.5/10.5

16/14/12

16/14/12

(cfm)

(512/442/371)

(512/442/371)

(565/494/424)

(565/494/424)

External Pressure (Option)

pa

10(30)

10(30)

10(30)

10(30)

Motor

W

40

40

50

50

(Hi/Me/Lo)

Flare-Nut Connection (with Flare Nuts)

Connections Refrigerant Piping Liquid Line Gas Line

mm

Φ6.35

Φ6.35

Φ9.53

(in.)

(1/4)

(1/4)

(3/8)

(3/8)

mm

Φ15.88

Φ15.88

Φ15.88

Φ15.88

(in.)

(5/8)

(5/8)

(5/8)

(5/8)

VP25

VP25

VP25

VP25

0.18

0.18

0.18

0.18

Condensate Drain

R410A (Nitrogen-Charged for Corrosion-Resistance)

(cfm)

Liquid Line

Net Weight

kcal/h

m3/min.

(Hi/Me/Lo)

Width Depth

4.3

kW

Refrigerant Indoor Fan Air Flow Rate

Height

JTDS045H0PN-0AQ1

AC 1Φ,220-240V/50Hz

Indoor Unit Power Supply

Sound Pressure Level

(High/Medium/Low)

In-the-Ceiling Type (Low Static Pressure)

Model

Nominal Heating Capacity

JTDS050H0PN-0AQ1

Indoor Unit Power Supply

• Up to 30 pa static pressure

Nominal Cooling Capacity

In-the-Ceiling Type (Low Static Pressure)

Approximate Packing Measurement

m3

Φ9.53

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions: 1.5 Meter Beneath the Unit. With Discharge Duct (2.0m) and Return Duct (1.0m). Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field. 3. The data for external pressure indicates” Standard Pressure Setting values when a filter is not used.

JOHNSON CONTROLS | YORK® VRF SYSTEMS

29

YORK® VRF INDOOR UNITS

Floor Concealed

Floor Ceiling

Indoor Unit Type

Floor Concealed Type

Model

JTFC028H0NN-0AQ1

JTFC045H0NN-0AQ1

Nominal Heating Capacity

Sound Pressure Level (High/Medium/Low) Height

Outer Dimension

Width

Depth

Net Weight

Motor

4.3

5.6

7.1

kcal/h

2,400

3,700

4,800

6,100

Btu/h

9,500

14,700

19,100

24,200

kw

3.3

4.9

6.5

8.5

kcal/h

2,800

4,200

5,600

7,300

Btu/h

11,100

16,700

22,200

29,000

dB(A)

35-32-29

38-35-31

39-36-32

42-38-34

mm

620

620

620

620

(in.)

24.41

24.41

24.41

24.41

Motor Power input

mm

900

900

1,170

1,170

(in.)

35.43

35.43

46.06

46.06

mm

202

202

202

202

(in.)

7.95

7.95

7.95

7.95

kg

25

26

31

31

(lbs)

55

57

68

68

R410A/R407C/R22 (Nitrogen-Charged for Corrosion-Resistance) m3/min.

8/7/6

10/8/7

14.5/12.5/10.5

16/14/12

W

16

25

40

50

Liquid Line Gas Line

mm

Φ6.35

Φ6.35

Approximate Packing Measurement

Φ6.35

Φ6.35

(in.)

1/4

1/4

1/4

3/8

mm

Φ12.7

Φ12.7

Φ15.88

Φ15.88

(in.)

(1/2)

(1/2)

(5/8)

(5/8)

VP25

Condensate Drain m3

0.19

0.19

Nominal Cooling Capacity

Nominal Heating Capacity

0.23

0.23

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JTFE063H0NN-0AQ1

JTFE071H0NN-0AQ1

kW

5.0

5.6

6.3

7.1

kcal/h

4,300

4,800

5,400

6,100

Btu/h

17,100

19,100

21,500

24,200

kW

5.6

6.5

7.5

8.5

kcal/h

4,800

5,600

6,500

7,300

Btu/h

19,100

22,200

25,600

29,000

DC Fan motor / three speeds

Fan motor W

40

40

70

70

Air Flow Rate Hi/Me/Lo

m³/min

13/11/9

13/11/9

16.1/14//11.3

16.1/14//11.3

Sound Pressure (Ceiling)

dB(A)

39/35/30

39/35/30

45/41/37

45/41/37

Sound Pressure (Floor)

dB(A)

43/38/35

43/38/35

48/44/40

48/44/40

Outer Dimension of Package

mm

1,110/830/340

1,110/830/340

1,110/830/340

1,110/830/340

Outer Dimension of Unit

mm

990/680/230

990/680/230

990/680/230

990/680/230

Net Weight

kg

31

31

32

32

Gross Weight

kg

38

38

39

39

R410A

Refrigerant

Flare-nut Connection (with Flare Nuts)

Liquid Line

mm

Φ6.35

Φ6.35

Φ9.53

Φ9.53

Gas Line

mm

Φ15.88

Φ15.88

Φ15.88

Φ15.88

No

Drain Pump

VP25 (Outer Diameter Φ32)

Condensate Drain

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20°C DB (68°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions: 1 meter beneath the Unit 1 meter from inlet grille The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

30

JTFE056H0NN-0AQ1

220-240V ~ 50HZ

Pipe Connections

Flare-Nut Connection with Flare Nuts

Refrigerant piping

JTFE050H0NN-0AQ1

Indoor Unit Power Supply

2.8

Connections

Floor Ceiling Type

Model

kw

Refrigerant Indoor Fan Air Flow Rate (Hi/Me/Lo)

JTFC071H0NN-0AQ1

AC 1Φ,220V/50Hz

Indoor Unit Power Supply

Nominal Cooling Capacity

JTFC056H0NN-0AQ1

Indoor Unit Type

Option

Wired Remote Controller Fresh air intake hole

No

Fan Motor Speed-up Setting

Yes

Speed-up Setting HH1

m³/min

14.2

14.2

17.8

17.8

Speed-up Setting HH2

m³/min

16

16

20

20

JOHNSON CONTROLS | YORK® VRF SYSTEMS

31

Floor Ceiling (continued)

AHU-KIT

Indoor Unit Type Model

JTFE084H0NN-0AQ1

JTFE090H0NN-0AQ1

Nominal Heating Capacity

JTFE112H0NN-0AQ1

JTFE142H0NN-0AQ1

220-240V ~ 50HZ

Indoor Unit Power Supply

Nominal Cooling Capacity

AHU-KIT for Air Handling Applications

Floor Ceiling Type

kW

8.4

9.0

11.2

14.2

kcal/h

7,200

7,700

9,600

12,200

Btu/h

28,700

30,700

38,200

48,500

kW

9.6

10.0

13.0

16.3

kcal/h Btu/h

8,300

8,600

32,800

11,200

34,100

44,400

14,000 55,600

The AHU-KIT can integrate external heat exchangers of Air Handling Units (AHU) in a VRF system to be used for air-conditioning, which can provide more flexible air-conditioning solutions and reduce renovation costs. Type

-

Model Capacity(HP) Power Source

DC Fan motor / three speeds

Fan motor Motor Power input

W

70

80

130

160

Control Box

AHU CONNECTION KIT JDXF-2.0A

JDXF-4.0A

JDXF-6.0A

2HP

4HP

6HP

-

220-240V~50/60Hz

Height(H)

mm

341

Width(W)

mm

291

Depth(D)

mm

127

kg

Net Weight

m³/min

18.2/15.2/12.2

19.4/16.3/13.3

24.8/20.5/16.3

33/28/23

Sound Pressure (Ceiling)

dB(A)

43/39/34

45/40/36

51/46/40

50/46/42

Height(H)

mm

200

Sound Pressure (Floor)

dB(A)

46/41/37

48/43/39

54/49/43

55/50/46

Width(W)

mm

165

mm

1,400/830/340

1,400/830/340

1,400/830/340

1,690/830/340

Depth(D)

mm

62

kg

1.7

Outer Dimension of Package

mm

1,285/680/230

1,285/680/230

1,285/680/230

1,580/680/230

Net Weight

kg

39

40

41

47

Gross Weight

kg

46

47

48

56

Outer Dimension of Unit

Net Weight

Compatibility

mm

Φ9.53

Φ9.53

Φ9.53

Φ9.53

Gas Line

mm

Φ15.88

Φ15.88

Φ15.88

Φ15.88

No

Fresh air intake hole Fan Motor Speed-up Setting Speed-up Setting HH1

m³/min

Speed-up Setting HH2

m³/min

19.8 22.3

21.2 23.5

2-6HP

Single Combination

-

8-10HP ø9.53

ø9.53 5

m

2

Installation for Exp. Valve

-

Vertical/Horizontal Indoor/Outdoor Electrical Expansion Valve

Outlet Air Thermistor

2.5m

Inlet Air Thermistor

2.5m

Liquid Pipe Thermistor

2.5m

Yes

Gas Pipe Thermistor

2.5m

27 29.2

36 37.4

ø9.53

Height Difference of the Valve Box and AHU

2.5m

Exp. Valve wire Cooling Temperature Range DB

°C

17~35

Heating Temperature Range DB

°C

10~27

* Cooling capacity data based on the following indoor and outdoor temperature conditions:

Operation conditions

Piping Lift: 0 Meter

Indoor air inlet temperature

2. The sound pressure level is based on following conditions: 1 meter beneath the Unit 1 meter from inlet grille. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

Outdoor air inlet temperature



ø6.35

m

No

NOTES: 1 The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Piping Length: 5.0 Meters

mm

Distance of the Valve Box and AHU

Refrigerant Flow Control Installation

Option

Wired Remote Controller

-

Installation

VP25 (Outer Diameter Φ32)

Condensate Drain

Control/Duty Signal control

Multi Combination

Pipe Size

Liquid Line

Drain Pump

Outlet Air Temperature Control/Inlet air(room air) Temperature

Capacity Control Mode

Flare-nut Connection (with Flare Nuts)

Pipe Connections

Steel Plate+White Grey Coating

Material

R410A

Refrigerant

Steel Plate with White Grey Coating (anti-corrosion)

Casing Material

Box

10HP

5.2

Air Flow Rate Hi/Me/Lo

Expansion Valve

JDXF-10.0A 8HP

Cooling DB

27.0° C

WB

19.0° C

DB

35.0° C

WB

-

DB: dry bulb; WB: wet bulb Pipe length: 7.5m; pipe height: 0m

32

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

33

Summary Table of Outdoor Units Cooling Only VRF

4 to 54 HP

Capacity

64

Maximum connectable indoor unit quantity

50% to 130%

Combination capacity ratio between OD and ID Total piping length

ft (m)

3280 (1000)

Maximum piping length between OD and ID

ft (m)

541 (165)

Maximum equivalent piping length between OD and ID

ft (m)

623 (190)

Maximum piping length between 1st branch and ID

ft (m)

295 (90)

Maximum height difference between OD and ID (when OD is higher than ID)

ft (m)

164 (50)

Maximum height difference between OD and ID (when ID is higher than OD)

ft (m)

131 (40)

Maximum height difference between ID and ID

ft (m)

98 (30)

Cooling Operation Range

F (C)

14 to 118 (-10 to 48)

Heating Operation Range

F (C)

–4 to 60 (-20 to 16)

Outdoor Units Reliable, quiet YORK® VRF outdoor units are available in capacities to fit multiple applications and operate multiple indoor units. Heat pump units provide flexibility to design for a variety of building spaces and ambient conditions. Units operate quietly with sound ratings as low as 50 dBA.

34

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

35

YORK® VRF OUTDOOR UNITS

Outdoor Units Overview

YORK® VRF Outdoor Units

YORK® VRF outdoor units provide maximum flexibility for modular design.

HP 4 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54

380V Heat Pump

380V HP MODELS 8-18 HP Systems

20-36 HP Systems

38-54 HP Systems

JTOH080VPEM-0AQ1 JTOH100VPEM-0AQ1 JTOH120VPEM-0AQ1 JTOH140VPEM-0AQ1 JTOH160VPEM-0AQ1 JTOH180VPEM-0AQ1

JTOH200VPEM-0AQ1 JTOH220VPEM-0AQ1 JTOH240VPEM-0AQ1 JTOH260VPEM-0AQ1 JTOH280VPEM-0AQ1 JTOH300VPEM-0AQ1 JTOH320VPEM-0AQ1 JTOH340VPEM-0AQ1 JTOH360VPEM-0AQ1

JTOH380VPEM-0AQ1 JTOH400VPEM-0AQ1 JTOH420VPEM-0AQ1 JTOH440VPEM-0AQ1 JTOH460VPEM-0AQ1 JTOH480VPEM-0AQ1 JTOH500VPEM-0AQ1 JTOH520VPEM-0AQ1 JTOH540VPEM-0AQ1

Heat Pump 220V Single Phase

Heat Pump 380V 3 Phase

Front Flow HP MODELS YORK® VRF Outdoor Units Single Phase 220-240V/50Hz 220V/60Hz

3 Phase 380-415V/50Hz 380V/60Hz

4-5 HP Unit

5&6 HP Unit

JDOH040HSEN-0AQ1 JDOH050HSEN-0AQ1 JDOH060HSEN-0AQ1

JDOH050HSEM-0AQ1 JDOH060HSEM-0AQ1

YORK® VRF outdoor units, in capacities from 4 to 54 HP with modular system combinations. Heat pump units can either heat or cool spaces. YORK® VRF heat pump units offer an extended operating temperature range: outdoor ambient temperature as low as 14° F (-10° C) in the cooling mode and as low as -4° F (-20° C) in the heating mode.

All outdoor units feature: · Long  refrigerant piping lengths – up to 1000m total pipe run · A  dvanced defrost cycle operation in the heating mode · A  ble to operate up to 64 indoor units on a single piping network · P  ower-saving demand control for reduced peak load and energy savings · A  utomatic delivery of required refrigerant charge · D  iagnostics and malfunction codes available at push of a control panel button

36

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

37

YORK® VRF OUTDOOR UNITS

Outdoor Unit 380V HP

| 8-12 HP Systems

HP

8HP

10HP

12HP

Model

JTOH080VPEM-0AQ1

JTOH100VPEM-0AQ1

JTOH120VPEM-0AQ1

Combination of Base Unit

JTOH080VPEM-0AQ1

JTOH100VPEM-0AQ1

JTOH120VPEM-0AQ1

AC 3 Φ 380-415V/50Hz

Power Supply Nominal Cooling Capacity

kW

22.4

28

33.5

Nominal Heating Capacity

kW

25

31.5

37.5

Ivory White

Cabinet Color dB(A)

56

57

59

mm

1,720 x 950 x 750

1,720 x 950 x 750

1,720 x 950 x 750

Net Weight

kg

224

225

227

Gross Weight

kg

237

238

240

Sound Pressure Level Outer Dimension Height x Width x Depth

R410A

Refrigerant

Micro-Computer Control Expansion Valve

Flow Control

Hermetic (Scroll) Compressor Quantity 1

1

1

Multi-Pass Cross-Finned Tube

Heat Exchanger

Propeller Fan Condenser Fan Quantity

Air Flow Rate Main Refrigerant Piping Liquid Line Gas Line Refrigerant Charge

Outdoor Unit

Packing Dimension Height x Width x Depth

380V HP (Heat PUMP)

Approximate Packing Measurement

Heat pump units can either heat or cool spaces. YORK VRF heat pump units offer an extended operating temperature range: outdoor ambient temperature as low as 14° F (-10° C) in the cooling mode and as low as -4° F (-20° C) in the heating mode. ®

1

1

m3/h

9,300

10,200

10,500

mm

Φ9.53

Φ9.53

Φ12.7

mm

Φ19.05

Φ22.2

Φ25.4

kg

8

8.5

9.9

mm

1,882 x 1,018 x 828

1,882 x 1,018 x 828

1,882 x 1,018 x 828

m3

1.58

1.58

1.58

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

8-18 HP Systems

38

1

JOHNSON CONTROLS | YORK® VRF SYSTEMS

2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

JOHNSON CONTROLS | YORK® VRF SYSTEMS

39

Outdoor Unit 380V HP HP

| 14-18 HP Systems 14HP

16HP

18HP

Model

JTOH140VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH180VPEM-0AQ1

Combination of Base Unit

JTOH140VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH180VPEM-0AQ1

AC 3 Φ 380-415V/50Hz

Power Supply Nominal Cooling Capacity

kW

40

45

50

Nominal Heating Capacity

kW

45

50

56

Ivory White

Cabinet Color dB(A)

59

59

60

mm

1,720 x 1,210 x 750

1,720 x 1,210 x 750

1,720 x 1,210 x 750

Net Weight

kg

312

315

318

Gross Weight

kg

327

330

333

Sound Pressure Level Outer Dimension Height x Width x Depth

R410A

Refrigerant

Micro-Computer Control Expansion Valve

Flow Control

Hermetic (Scroll) Compressor Quantity 2

Propeller Fan

Condenser Fan Quantity

Main Refrigerant Piping Liquid Line Gas Line Refrigerant Charge Packing Dimension Height x Width x Depth Approximate Packing Measurement

2

Multi-Pass Cross-Finned Tube

Heat Exchanger

Air Flow Rate

2

1

1

1

m3/h

11,700

11,700

11,700

mm

Φ12.7

Φ12.7

Φ15.88

mm

Φ25.4

Φ28.6

Φ28.6

kg

10.5

10.5

10.5

mm

1,882 x 1,278 x 828

1,882 x 1,278 x 828

1,882 x 1,278 x 828

m3

1.98

1.98

1.98

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 0°C DB (68°F DB) 19°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

Outdoor Unit

380V HP (Heat PUMP) Heat pump units can either heat or cool spaces. YORK® VRF heat pump units offer an extended operating temperature range: outdoor ambient temperature as low as 14° F (-10° C) in the cooling mode and as low as -4° F (-20° C) in the heating mode.

2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

40

JOHNSON CONTROLS | YORK® VRF SYSTEMS

20-36 HP Systems

JOHNSON CONTROLS | YORK® VRF SYSTEMS

41

YORK® VRF OUTDOOR UNITS

Outdoor Unit 380V HP HP Model Combination of Base Unit

Outdoor Unit 380V HP

| 20-24 HP Systems 20HP

22HP

24HP

JTOH200VPEM-0AQ1

JTOH220VPEM-0AQ1

JTOH240VPEM-0AQ1

JTOH080VPEM-0AQ1

JTOH080VPEM-0AQ1

JTOH100VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH140VPEM-0AQ1

JTOH140VPEM-0AQ1

AC 3Φ 380-415V/50Hz

Power Supply

| 26-30 HP Systems

HP Model Combination of Base Unit

26HP

28HP

30HP

JTOH260VPEM-0AQ1

JTOH280VPEM-0AQ1

JTOH300VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH140VPEM-0AQ1v

JTOH140VPEM-0AQ1

JTOH140VPEM-0AQ1

JTOH140VPEM-0AQ1

JTOH160VPEM-0AQ1

AC 3Φ 380-415V/50Hz

Power Supply

Nominal Cooling Capacity

kW

56

61.5

69

Nominal Cooling Capacity

kW

73

80

85

Nominal Heating Capacity

kW

63

69

77.5

Nominal Heating Capacity

kW

82.5

90

95

Ivory White

Cabinet Color dB(A)

61

61

61

mm

1,720 x (950+950) x 750

1,720 x (950+1,210) x 750

1,720 x (950+1,210) x 750

Net Weight

kg

224+227

224+312

225+312

Gross Weight

kg

237+240

237+327

238+327

Sound Pressure Level Outer Dimension Height x Width x Depth

Flow Control

Micro-Computer Control Expansion Valve

Compressor

Hermetic (Scroll)

Quantity

2

Quantity

Main Refrigerant Piping Liquid Line Gas Line Refrigerant Charge

62

62

mm

1,720 x (950+1,210) x 750

1,720 x (1,210+1,210) x 750

1,720 x (1,210+1,210) x 750

Net Weight

kg

227+312

312+312

312+315

Gross Weight

kg

240+327

327+327

327+330

Outer Dimension Height x Width x Depth

R410A Micro-Computer Control Expansion Valve Hermetic (Scroll)

Compressor 3

Quantity

3

2

2

3

m /h

19,800

21,000

21,900

mm

Φ15.88

Φ15.88

Φ15.88

mm

Φ28.6

Φ28.6

Φ28.6

kg

17.9

18.5

19

Quantity Air Flow Rate Main Refrigerant Piping Liquid Line Gas Line Refrigerant Charge

2

2

2

m3/h

22,200

23,400

23,400

mm

Φ19.05

Φ19.05

Φ19.05

mm

Φ31.75

Φ31.75

Φ31.75

kg

20.4

21

21

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

42

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

4

Propeller Fan

Condenser Fan

2

4 Multi-Pass Cross-Finned Tube

Heat Exchanger

Propeller Fan

Condenser Fan

62

Flow Control

Multi-Pass Cross-Finned Tube

Heat Exchanger

Air Flow Rate

3

dB(A)

Sound Pressure Level

Refrigerant

R410A

Refrigerant

Ivory White

Cabinet Color

43

Outdoor Unit 380V HP HP Model Combination of Base Unit

| 32-36 HP Systems 32HP

34HP

36HP

JTOH320VPEM-0AQ1

JTOH340VPEM-0AQ1

JTOH360VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

AC 3Φ 380-415V/50Hz

Power Supply Nominal Cooling Capacity

kW

90

95

100

Nominal Heating Capacity

kW

100

106

112

Ivory White

Cabinet Color dB(A)

62

63

63

mm

1,720 x (1,210+1,210) x 750

1,720 x (1,210+1,210) x 750

1,720 x (1,210+1,210) x 750

Net Weight

kg

315+315

315+318

318+318

Gross Weight

kg

330+330

330+333

333+333

Sound Pressure Level Outer Dimension Height x Width x Depth

R410A

Refrigerant Flow Control

Micro-Computer Control Expansion Valve

Compressor

Hermetic (Scroll)

Quantity

4

4

4

Heat Exchanger

Multi-Pass Cross-Finned Tube

Condenser Fan

Propeller Fan

Quantity Air Flow Rate Main Refrigerant Piping Liquid Line Gas Line Refrigerant Charge

2

2

2

m3/h

23,400

23,400

23,400

mm

Φ19.05

Φ19.05

Φ19.05

mm

Φ31.75

Φ31.75

Φ38.1

kg

21

21

21

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

44

JOHNSON CONTROLS | YORK® VRF SYSTEMS

Outdoor Unit

380V HP (Heat PUMP) Heat pump units can either heat or cool spaces. YORK ® VRF heat pump units offer an extended operating temperature range: outdoor ambient temperature as low as 14° F (-10° C) in the cooling mode and as low as -4° F (-20° C) in the heating mode.

JOHNSON CONTROLS | YORK® VRF SYSTEMS

38-54 HP Systems

45

YORK® VRF OUTDOOR UNITS

Outdoor Unit 380V HP HP Model

Combination of Base Unit

Outdoor Unit 380V HP

| 38-42 HP Systems 38HP

40HP

42HP

JTOH380VPEM-0AQ1

JTOH400VPEM-0AQ1

JTOH420VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH140VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH180VPEM-0AQ1

Nominal Cooling Capacity

kW

109

112

118

Nominal Heating Capacity

kW

118

125

132

Sound Pressure Level Outer Dimension Height x Width x Depth

44HP

46HP

48HP

Model

JTOH440VPEM-0AQ1

JTOH460VPEM-0AQ1

JTOH480VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH120VPEM-0AQ1

JTOH120VPEM-0AQ1

Combination of Base Unit

JTOH140VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

AC 3Φ 380-415V/50Hz

Nominal Cooling Capacity

kW

125

132

136

Nominal Heating Capacity

kW

140

145

150

Ivory White

Cabinet Color

Ivory White

Cabinet Color

HP

Power Supply

AC 3Φ 380-415V/50Hz

Power Supply

| 44-48 HP Systems

dB(A)

64

64

64

mm

1,720 x (950+950+1,210) x 750

1,720 x (950+950+1,210) x 750

1,720 x (950+950+1,210) x 750

dB(A)

64

64

65

mm

1,720 x (950+1,210+1,210) x 750

1,720 x (950+1,210+1,210) x 750

1,720 x (950+1,210+1,210) x 750

Net Weight

kg

227+312+318

227+315+318

227+318+318

Gross Weight

kg

240+327+333

240+330+333

240+333+333

Sound Pressure Level Outer Dimension Height x Width x Depth

Net Weight

kg

227+227+312

227+227+315

227+227+318

Gross Weight

kg

240+240+327

240+240+330

240+240+333

R410A

Refrigerant

Hermetic (Scroll) 4

Micro-Computer Control Expansion Valve

Flow Control

Compressor Quantity 4

R410A

Refrigerant

Micro-Computer Control Expansion Valve

Flow Control

4

Hermetic (Scroll)

Compressor Quantity

5

Liquid Line Gas Line Refrigerant Charge

3

3

3

m3/h

32,700

32,700

32,700

Air Flow Rate

mm

Φ19.05

Φ19.05

Φ19.05

Main Refrigerant Piping

mm

Φ38.1

Φ38.1

Φ38.1

Gas Line

kg

30.3

30.3

30.3

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

46

Propeller Fan

Condenser Fan

Condenser Fan Quantity

Main Refrigerant Piping

5

Multi-Pass Cross-Finned Tube

Heat Exchanger Propeller Fan

Air Flow Rate

5

Multi-Pass Cross-Finned Tube

Heat Exchanger

JOHNSON CONTROLS | YORK® VRF SYSTEMS

Quantity

Liquid Line

Refrigerant Charge

3

3

3

m3/h

33,900

33,900

33,900

mm

Φ19.05

Φ19.05

Φ19.05

mm

Φ38.1

Φ38.1

Φ38.1

kg

30.9

30.9

30.9

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

JOHNSON CONTROLS | YORK® VRF SYSTEMS

47

Outdoor Unit 380V HP HP Model

Combination of Base Unit

| 50-54 HP Systems 50HP

52HP

54HP

JTOH500VPEM-0AQ1

JTOH520VPEM-0AQ1

JTOH540VPEM-0AQ1

JTOH140VPEM-0AQ1

JTOH160VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

JTOH180VPEM-0AQ1

AC 3Φ380-415V/50Hz

Power Supply Nominal Cooling Capacity

kW

140

145

150

Nominal Heating Capacity

kW

155

160

165

Ivory White

Cabinet Color dB

65

65

65

mm

1,720 x (1,201+1,210+1,210) x 750

1,720 x (1,201+1,210+1,210) x 750

1,720 x (1,201+1,210+1,210) x 750

Net Weight

kg

312+318+318

315+318+318

318+318+318

Gross Weight

kg

327+333+333

330+330+333

333+333+333

Sound Pressure Level Outer Dimension Height x Width x Depth

R410A

Refrigerant

Micro-Computer Control Expansion Valve

Flow Control

Hermetic (Scroll) Compressor Quantity

6

6

6

Multi-Pass Cross-Finned Tube

Heat Exchanger

Propeller Fan Condenser Fan Quantity

Air Flow Rate Main Refrigerant Piping Liquid Line Gas Line Refrigerant Charge

3

3

3

m3/h

35,100

35,100

35,100

mm

Φ19.05

Φ19.05

Φ19.05

mm

Φ38.1

Φ38.1

Φ38.1

kg

31.5

31.5

31.5

NOTES: 1. The cooling and heating performances are the values when combined with our specified indoor units. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19.0°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 6°C WB (43°F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure is based on the following conditions: 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

48

JOHNSON CONTROLS | YORK® VRF SYSTEMS

Outdoor Unit

380V HP (Heat PUMP) Heat pump units can either heat or cool spaces. YORK® VRF heat pump units offer an extended operating temperature range: outdoor ambient temperature as low as 14° F (-10° C) in the cooling mode and as low as -4° F (-20° C) in the heating mode.

4-6 HP Systems

JOHNSON CONTROLS | YORK® VRF SYSTEMS

49

Outdoor Unit 220V/380V HP Model

JDOH040HSEN-0AQ1

| 4-6 HP SYSTEMS JDOH050HSEN-0AQ1

JDOH060HSEN-0AQ1

AC1Φ, 220-240V/50Hz,220V/60Hz

Power Supply

AC3Φ, 380-415V/50Hz

kW

11.2

14.0

15.5

14.0

15.5

Btu/h

38,000

47,800

52,900

47,800

52,900

kw

12.5

16.0

18.0

16.0

18.0

Btu/h

42,700

54,600

61,400

54,600

61,400

(H)

mm

1,380

1,380

1,380

1,380

1,380

(W)

mm

950

950

950

950

950

(D)

mm

370

370

370

370

370

kg

103

103

103

103

103

2.5

2.8

Nominal Cooling Capacity

Nominal Heating Capacity

Dimension

JDOH060HSEM-0AQ1

R410A

Refrigerant

Outer

JDOH050HSEM-0AQ1

Net Weight

Hermetic DC inver

Type of Compressor Output Power of Compressor

kW

2.2

2.5

2.8 Multi-Pass Cross-Finned Tube

Heat Exchanger Condenser Fan Quantity

2

2

2

2

2

Air Flow Rate

m3/min

90

90

100

90

100

Motor Output

W

51x2

51x2

51x2

51x2

51x2

48/50

48/50

50/52

48/50

50/52

42

42

45

42

45

Cooilng/ Sound Pressure Level dB (A)

heating NightShift mode

Micro-Computer Control Expansion Velve

Refrigerant Flow Control

Flare-Nut Connection(With Flare Nuts)

Refrigerant Piping Liquid Connection

mm

Φ9.53

Gas Line

mm

Φ15.88

Pipe Connection

Multi-kit Connection

Model of Multi-Kit

JE-102SN

NOTES: 1. The nominal cooling capacity and heating capacity are based on following conditions: Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB) 19°C WB (66.2°F WB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 6°C WB (43°F WB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

Optional Parts & Accessories Selection software tool indicates which piping kits are needed for your design

2. The sound pressure level is based on following conditions: 1.5 meters from fIoor level, and 1 meter from fhe Unit service cover surface The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field

50

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

51

First Multi-kit Outdoor Unit HP

8 and 10

12 and 18

18 and 24

26 and 54

Multi

JE-102SNQE

JE-162SNQE

JE-242SNQE

JE-302SNQE

Piping Connection Kit (for combined system) Outdoor Unit

JTOH200~240VPEM-0AQ1

JTOH260~360VPEM-0AQ1

JTOH380~420VPEM-0AQ1 JM-30SNQE

JM-30SNQE

JM-20SNQE

JM-30SNQE

JM-20SNQE

JM-30SNQE

Multi-kit 1 Multi-kit 2

JTOH440~540VPEM-0AQ1

Controls First Multi-kit~Last Multi-kit

YORK® VRF systems offer a wide range

Total Indoor Unit HP

Lower than 6

6 to 8.99

9 to 11.99

12 to 15.99

16 to 17.99

18 to 25.99

26 to 35.99

Gas (Ømm)

Ø15.88

Ø19.05

Ø22.2

Ø25.4

Ø28.6

Ø28.6

Ø31.75

Liquid (Ømm)

Ø9.53

Ø9.53

Ø9.53

Ø12.07

Ø15.88

Ø19.05

Multi-kit

Ø12.07 JE-162SNQE

JE-102SNQE

JE-242SNQE

Over 36

of control systems to suit multiple applications.

Ø38.1 Ø19.05 JE-302SNQE

Control Systems

CWH-01QE

Last Multi-kit~Indoor Unit Indoor Unit

Pipe Size (Ømm)

Max. Liquid Pipe Length

Gas Pipe

Liquid Pipe

0.8HP~1.5HP

12.7

6.35

15

1.8HP~2.0HP

15.88

6.35*1

15

2.3HP~6.0HP

15.88

9.53

40

8HP

19.05

9.53

40

10HP

22.2

9.53

40

Notes: 1. When liquid pipe length of indoor unit (0.8~2.0HP) is more than 15m, please change the liquid pipe dimension from Ø6.35 into Ø9.53.

Remote Control Switch Compatible with the H-LINKⅡ

•T  he CWH-01QE has a design that matches the interior. • The new large LCD display permits users to see the operating conditions and settings. • The timer can be set at half-hour intervals up to 72 hours. • All the functions can be selected by remote control switches.

52

JOHNSON CONTROLS | YORK® VRF SYSTEMS

JOHNSON CONTROLS | YORK® VRF SYSTEMS

• The CWH-01QE monitors the operating conditions in the system and an alarm is issued if a problem occurs. • A “self-diagnosis function” checks for problems on printed boards in indoor and outdoor units. • Equipped with energy-saving functions such as a preset temperature range limiting function for preventing excessive cooling/ heating and a preset temperature automatic reset function, as well as an operation locking mechanism and the capability to prevent users from forgetting to turn off the system. (Function selection setting is required)

CRH-01QE

Wireless Remote Control Switch Compatible with the H-LINKⅡ

•O  ne-touch handy operation, no wiring work required.

• Two or more units can be operated simultaneously by remote control. * Receiver kit is required.

53

Head Office: YORK® (MALAYSIA) SALES & SERVICE SDN BHD (168496-T)

Bangunan THK, Suite 2.1, 2nd Floor, No.2A, Jalan 243, Section 51A, 46100 Petaling Jaya, Selangor Darul Ehsan, Malaysia Tel. 03-7628 4100 Fax: 03-7628 4101

Branches: Penang Branch Tel. 04-397 0213 Fax: 04-397 2045

Kota Kinabalu Branch Tel. 088-448 350 Fax: 088-448 352

Johor Bahru Branch Tel. 07-354 9878 Fax: 07-354 9871

Kuching Branch Tel. 082-553 100 Fax: 082-553 200

Authorized Dealer

Customer Care Centre: 1800 – 88 – YORK® (9675) Website: www.york.com/my

PUBL-7988 (0416)