Feeder Protection Relay REX 521. Product Guide

Feeder Protection Relay Product Guide REX 521 Feeder Protection Relay REX 521 1MRS752177-MBG Issued: 20.11.2001 Status: Updated Version: H/18.10....
Author: Guest
34 downloads 0 Views 2MB Size
Feeder Protection Relay Product Guide

REX 521

Feeder Protection Relay

REX 521 1MRS752177-MBG Issued: 20.11.2001 Status: Updated Version: H/18.10.2010 Data subject to change without notice

General

The protection relay REX 521 is designed for protection, control, measuring, and supervision in medium voltage networks. Typical applications include incoming and outgoing feeders as well as substation protection. The

protection relay is provided with energizing inputs for conventional current and voltage transformers. Also a hardware version with inputs for current and voltage sensors is available.

Design

The protection relay is based on a multiprocessor environment. The human-machine interface (HMI)1 including an LCD display with different views makes the local use easy

and informs the user via indication messages. Modern technology is applied both in hardware and software solutions.

1. HMI is referred to as MMI in the relay and in the Relay Setting Tool.

The protection relay is part of the ABB Substation Automation system and extends the functionality and flexibility of the concept further.

3

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features

Standard configuration B01:

Standard configuration B02:

• Three-phase non-directional overcurrent protection with three stages

• Three-phase non-directional overcurrent protection with three stages

• Non-directional earth-fault protection with three stages

• Three-phase transformer inrush and motor start-up current detector

• Phase discontinuity protection for three phases

• Non-directional earth-fault protection with three stages

• Three-phase thermal protection for cables

• Phase discontinuity protection for three phases

• Three-phase transformer inrush and motor start-up current detector

• Three-phase thermal protection for cables

• Supervision function for the energizing current input circuit

• Supervision function for the energizing current input circuit

• Current waveform distortion measurement

• Current waveform distortion measurement

• Three-phase current measurement

• Three-phase current measurement

• Neutral current measurement

• Neutral current measurement

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Transient disturbance recorder

• Transient disturbance recorder

• Trip-circuit supervision

• Trip-circuit supervision

• Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Circuit breaker control with indication

• Automatic reclosing 1...5 shots

• Lockout function

• Circuit breaker control with indication

• Object indication

• Lockout function

• Logic control position selector

• Object indication

• User-configurable I/Os

• Logic control position selector

• Interlocking

• User-configurable I/Os

• User-configurable alarm LEDs

• Interlocking • User-configurable alarm LEDs

3I >

50/51

MCS

I 0>

50N/51N

TCS

3I 2f >

68

I>

46

3

49F

CBFP

62

LO

86

CBCM

3I

3I >

50/51

MCS

I 0>

50N/51N

TCS

3I 2f>

68

CBCM

I>

46

3

49F

I

0 R

3I~harm

REX 521 B01 Fig. 1

000

I0

0

I

79

CBFP

62

LO

86

Block diagram of B01

4

0

I R

3I~harm

3I

REX 521 B02 Fig. 2

000

Block diagram of B02

I0

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features (cont´d)

Standard configuration M01:

Standard configuration M02:

• Three-phase non-directional overcurrent protection with three stages

• Three-phase non-directional overcurrent protection with three stages

• Three-phase transformer inrush and motor start-up current detector

• Three-phase transformer inrush and motor start-up current detector

• Directional earth-fault protection with three stages

• Directional earth-fault protection with three stages

• Phase discontinuity protection for three phases

• Phase discontinuity protection for three phases

• Three-phase thermal protection for cables

• Three-phase thermal protection for cables

• Supervision function for the energizing current input circuit

• Supervision function for the energizing current input circuit

• Current waveform distortion measurement

• Current waveform distortion measurement

• Three-phase current measurement

• Three-phase current measurement

• Neutral current measurement

• Neutral current measurement

• Residual voltage measurement

• Residual voltage measurement

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Transient disturbance recorder

• Transient disturbance recorder

• Trip-circuit supervision

• Trip-circuit supervision

• Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Circuit breaker control with indication

• Automatic reclosing 1...5 shots

• Lockout function

• Circuit breaker control with indication

• Object indication

• Lockout function

• Logic control position selector

• Object indication

• User-configurable I/Os

• Logic control position selector

• Interlocking

• User-configurable I/Os

• User-configurable alarm LEDs

• Interlocking • User-configurable alarm LEDs

3I >

50/51

MCS

67N

TCS

3I 2f>

68

CBCM

I>

46

I 0>

3

000

50/51

MCS

67N

TCS

3I 2f>

68

CBCM

I>

46

3

49F

3I > 0

I

3I~harm

R

I 0>

49F

CBFP

62

LO

86

3I

I0

0 U0

Block diagram of M01

79

CBFP

62

LO

86

REX 521 M01 Fig. 3

I

000

0

I R

3I~harm

3I

I0

U0

REX 521 M02 Fig. 4

Block diagram of M02 5

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features (cont´d)

The main difference between the standard configurations B01/B02 and standard configurations M01/M02 is the directional earthfault protection, which is included in the standard configurations M01 and M02. The difference between configurations B01 and B02, and likewise between M01 and M02, is the auto-reclosure function in B02 and M02. Standard configuration H01: • Three-phase directional overcurrent protection with two stages

• Interlocking • User-configurable alarm LEDs

3I>

• Directional earth-fault protection with three stages • Phase discontinuity protection for three phases • Three-phase thermal protection for cable • Synchro-check/voltage-check function with one stage • Supervision function for energizing current input circuit • Supervision function for energizing voltage input circuit • Current waveform distortion measurement • Voltage waveform distortion measurement • Three-phase current measurement • Neutral current measurement • Three phase-to-earth voltage measurements • Residual voltage measurement • System frequency measurement • Three-phase power and energy measurement

MCS TCS1 CBCM

I 0>

000

67N

0

3I~harm

3I 2f>

68

I>

46

3

49F

25

SYNC 0

I

CBFP LO

I R

3U~harm

3I

I0

P

3U

U

0

Q

f

pf

E

79 */62 86

REX 521 H01

Fig. 5

Block diagram of H01

Note! The standard configuration H01 is available only with the sensor HW version. Standard configuration H02: • Three-phase directional overcurrent protection with two stages • Three-phase non-directional overcurrent protection with two stages • Three-phase transformer inrush and motor start-up current detector • Directional earth-fault protection with three stages • Underfrequency or overfrequency protection with one stage • Phase discontinuity protection for three phases • Three-phase thermal protection for cables

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Supervision function for energizing current input circuit

• Transient disturbance recorder

• Supervision function for energizing voltage input circuit

• Trip-circuit supervision • Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Current waveform distortion measurement

• Automatic reclosing 1...5 shots

• Three-phase current measurement

• Circuit breaker control with indication

• Neutral current measurement

• Lockout function

• Three phase voltage measurements

• Object indication

• Residual voltage measurement

• Logic control position selector

• System frequency measurement

• User-configurable I/Os 6

50

3I>

• Three-phase non-directional overcurrent protection with one stage • Three-phase transformer inrush and motor start-up current detector

67

• Voltage waveform distortion measurement

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features (cont´d)

• Three-phase power and energy measurement

• Synchro-check/voltage-check function with one stage

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Supervision function for energizing current input circuit

• Transient disturbance recorder

• Supervision function for energizing voltage input circuit

• Trip-circuit supervision • Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Current waveform distortion measurement • Voltage waveform distortion measurement

• Automatic reclosing 1...5 shots

• Three-phase current measurement

• Circuit breaker control with indication

• Neutral current measurement

• Lockout function

• Three phase voltage measurements

• Object indication

• Residual voltage measurement

• Logic control position selector

• System frequency measurement

• User-configurable I/Os

• Three-phase power and energy measurement

• Interlocking

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• User-configurable alarm LEDs

• Transient disturbance recorder 3I> 3I >

67

MCS1

50/51

TCS CBCM

I0 >

000

0

67N 3I~harm

• Trip-circuit supervision • Delayed trip output for the circuit-breaker failure protection (CBFP) function

I

• Automatic reclosing 1...5 shots

R

f

81U/81O

3I2f>

68

• Lockout function

I>

46

• Object indication

• Circuit breaker control with indication

3U~harm

3

49F

I

0

CBFP LO

3I

I0

P

3U

U0

Q

f

pf

79 */62 86

• Logic control position selectorUser-configurable I/Os • Interlocking • User-configurable alarm LEDs

E

REX 521 H02

3I >

Fig. 6

Block diagram of H02

Standard configuration H03:

I0 >

• Directional earth-fault protection with three stages • Phase discontinuity protection for three phases • Three-phase thermal protection for cable

67N

3I 2f>

68

I>

46

• Three-phase non-directional overcurrent protection with three stages • Three-phase transformer inrush and motor start-up current detector

50/51

MCS

000

TCS CBCM

0

I R

3I~harm 3U~harm

3

49F

25

SYNC 0

3I

I0

P

3U

U0

Q

f

pf

E

79

I

CBFP

*/62

LO

86

REX 521 H03

Fig. 7

Block diagram of H03

7

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features (cont´d)

Standard configuration H04: • Three-phase non-directional overcurrent protection with three stages • Three-phase directional overcurrent protection with one stage

3I > 3I>

67

I0 >

67N

• Underfrequency or overfrequency protection with one stage • Three-phase transformer inrush and motor start-up current detector

I0 >

50N/51N

f

81U/81O

3I2f>

68

I>

46

• Non-directional earth-fault protection with three stages

• Three-phase thermal protection for cable • Supervision function for energizing current input circuit • Supervision function for energizing voltage input circuit • Current waveform distortion measurement • Voltage waveform distortion measurement • Three-phase current measurement • Neutral current measurement • Three phase voltage measurements • Residual voltage measurement

MCS

000

TCS1 CBCM

0

3I~harm

I R

3U~harm

• Directional earth-fault protection with three stages

• Phase discontinuity protection for three phases

50/51

3

49F

I

79

CBFP

*/62

LO

86

0

3I

I

3U

U0

Q

f

pf

E

0

P

REX 521 H04

Fig. 8

Block diagram of H04

Standard configuration H05: • Three-phase non-directional overcurrent protection with three stages • Non-directional earth-fault protection with three stages • Three-phase overvoltage protection with two stages

• System frequency measurement

• Three-phase undervoltage protection with two stages

• Three-phase power and energy measurement

• Residual overvoltage protection with three stages

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Three-phase transformer inrush and motor start-up current detector

• Transient disturbance recorder

• Three-phase thermal overload protection for devices

• Trip-circuit supervision • Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Supervision function for energizing current input circuit

• Automatic reclosing 1...5 shots

• Supervision function for energizing voltage input circuit

• Circuit breaker control with indication

• Current waveform distortion measurement

• Lockout function

• Voltage waveform distortion measurement

• Object indication

• Three-phase current measurement

• Logic control position selector

• Neutral current measurement

• User-configurable I/Os

• Three phase voltage measurements

• Interlocking

• Residual voltage measurement

• User-configurable alarm LEDs

• System frequency measurement • Three-phase power and energy measurement

8

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features (cont´d)

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

• Supervision function for energizing current input circuit

• Transient disturbance recorder

• Supervision function for energizing voltage input circuit

• Trip-circuit supervision • Delayed trip output for the circuit-breaker failure protection (CBFP) function

• Current waveform distortion measurement • Voltage waveform distortion measurement

• Circuit breaker control with indication

• Three-phase current measurement

• Lockout function

• Neutral current measurement

• Object indication

• Three phase voltage measurements

• Logic control position selector

• Residual voltage measurement

• User-configurable I/Os

• System frequency measurement

• Interlocking

• Three-phase power and energy measurement

• User-configurable alarm LEDs

• Calculation of the accumulated electric breaker wear of the circuit breaker (CB) 3I > I 0> 3I2f

50/51 50N/51N 68

MCS

000

• Trip-circuit supervision

CBCM

0

3I~harm U 0>

59N

3U>

59

3U


50/51

Standard configuration H06:

U 0>

59N

• Three-phase non-directional overcurrent protection with two stages

3U>

59

• Three-phase overvoltage protection with two stages

3U
I0>

I0>

• Three-phase undervoltage protection with two stages

• Three-phase motor start-up supervision • Three-phase thermal overload protection for devices

50N/51N 59

3U


60

27,47,59

CBFP

LO

E

49

3

Fig. 11

81U/81O

46R

F

• Fuse failure protection

• Supervision function for energizing voltage input circuit

TCS

3U>

• Phase sequence voltage protection

• Supervision function for energizing current input circuit

67N

000

3U~harm

• Phase reversal protection

• Three-phase non-directional undercurrent protection with one stage

MCS

3I~harm

• Underfrequency or overfrequency protection with one stage • Negative phase sequence (NPS) protection with two stages

50/51

*/62 86

Block diagram of H07

• Current waveform distortion measurement • Voltage waveform distortion measurement

Standard configuration H08:

• Three-phase current measurement

• Three-phase non-directional overcurrent protection with three stages

• Neutral current measurement • Three-phase voltage measurements • Residual voltage measurement • System frequency measurement • Three-phase power and energy measurement • Calculation of the accumulated electric breaker wear of the circuit breaker (CB) • Transient disturbance recorder • Trip-circuit supervision • Delayed trip output for the circuit breaker failure protection (CBFP) function • Circuit breaker control with indication • Operation time counter

• Non-directional earth-fault protection with three stages • Three-phase overvoltage protection with two stages • Three-phase undervoltage protection with two stages • Residual overvoltage protection with three stages • Three-phase transformer inrush and motor start-up current detector • Three-phase thermal overload protection for devices • Supervision function for energizing current input circuit

• Lockout function

• Supervision function for energizing voltage input circuit

• Object indication

• Current waveform distortion measurement • Voltage waveform distortion measurement

10

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features (cont´d)

• Three-phase current measurement

Standard configuration H09:

• Neutral current measurement

• Three-phase non-directional overcurrent protection with three stages

• Three phase voltage measurements

• Non-directional earth-fault protection with three stages

• Residual voltage measurement • System frequency measurement • Three-phase power and energy measurement • Calculation of the accumulated electric breaker wear of the circuit breaker (CB) • Transient disturbance recorder • Trip-circuit supervision • Delayed trip output for the circuit-breaker failure protection (CBFP) function • Circuit breaker control with indication

• Three-phase overvoltage protection with two stages • Three-phase undervoltage protection with two stages • Residual overvoltage protection with three stages • Three-phase transformer inrush and motor start-up current detector • Underfrequency or overfrequency protection with two stages • Supervision function for energizing current input circuit

• Lockout function • Object indication • Logic control position selector

• Supervision function for energizing voltage input circuit

• User-configurable I/Os

• Current waveform distortion measurement

• Interlocking

• Voltage waveform distortion measurement

• User-configurable alarm LEDs

• Three-phase current measurement • Automatic reclosing 1...5 shots

3I >

50/51

I 0>

50N/51N

3I2f

68

U 0>

59N

3U>

59

3U


50/51

I 0>

50N/51N

3I2f

68

U 0>

59N

3U>

59

3U


50/51

MCS

I0>

50N/51N

TCS

3I2f

68

U0>

59N

3U>

59

3U


• Three-phase transformer inrush and motor start-up current detector • Underfrequency or overfrequency protection with two stages

0

CBCM

I

R

3U~harm

• Three-phase overvoltage protection with two stages • Three-phase undervoltage protection with two stages

000

67

U1< U2> U1>

I

0

P

3U

U 0

Q

f

pf

E

27,47,59 67N

I0 > f O

3I

81U/81O I

79

Fig. 14 Block diagram of H50 Note! The standard configuration H50 is available only with the voltage transformer (VT).

Feeder Protection Relay

REX 521 1MRS752177-MBG

Features (cont´d)

Standard configuration H51:

• Transient disturbance recorder

• Three-phase non-directional overcurrent protection with three stages.

• Trip-circuit supervision

• Three-phase directional overcurrent protection with one stage.

• Delayed trip output for the circuit breaker failure protection (CBFP) function • Circuit breaker control with indication

• Non-directional earth-fault protection with two stages

• Operation time counter

• Directional earth-fault protection with two stages

• Object indication

• Three-phase overvoltage protection with one stage • Three-phase undervoltage protection with one stage

• Lockout function • Logic control position selector • User-configurable I/Os • Interlocking • User-configurable alarm LEDs

• Underfrequency or overfrequency protection with two stages • Negative phase-sequence (NPS) protection with one stage • Three-phase motor start-up supervision • Three-phase thermal overload protection for devices • Residual overvoltage protection with one stage • Phase-sequence voltage protection • Fuse-failure protection • Three-phase non-directional undercurrent protection with one stage • Supervision function for energizing current input circuit • Supervision function for energizing voltage input circuit • Current waveform distortion measurement • Voltage waveform distortion measurement • Three-phase current measurement • Neutral current measurement • Three-phase voltage measurements • Residual voltage measurement • System frequency measurement • Three-phase power and energy measurement • Calculation of the accumulated electric breaker wear of the circuit breaker (CB)

3I> I0 >

50/51

MCS

67N

TCS

I0>

50N/51N

3U>

59

3U


59N

F

3

60 49

U1< U2> U1>

27,47,59

CBFP

*/62

LO

86

3I>

3I

67

Fig. 15 Block diagram of H51 Note! The standard configuration H51 is available only with the voltage transformer (VT).

13

Feeder Protection Relay

REX 521 1MRS752177-MBG

Applications

Several standard configurations are available for the protection relay. Refer to the REX 521 “Technical Reference Manual, Standard Configurations” for more detailed information. The B01 standard configuration for REX 521 is designed to be used in single busbar systems using one circuit breaker for selective short-circuit, time overcurrent and earth-fault protection of radial isolated neutral networks, solidly earthed networks, resistant earthed networks and resonant earthed networks. The B02 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective short-circuit protection, time-overcurrent protection, earthfault protection and automatic reclosing. The configuration can be used in different types of networks such as radial isolated neutral networks, solidly earthed networks, resistant earthed networks and resonant earthed networks. The M01 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective short-circuit, time overcurrent and directional earth-fault protection of radial isolated neutral networks, solidly earthed networks, resistant earthed networks and resonant earthed networks. The M02 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective short-circuit protection, time-overcurrent protection, directional earth-fault protection and automatic reclosing. The configuration can be used in different types of networks such as of radial isolated neutral networks, solidly earthed networks, resistant earthed networks and resonant earthed networks. The H01 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective directional and non-directional short-circuit protection, directional time-overcurrent protection, directional earth-fault protection and automatic reclosing with syncro- and voltagecheck functionality. The H02 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective directional and non-directional short-circuit protection, directional and non-directional time-overcurrent protection, directional earth-fault protection and automatic reclosing.

14

The H03 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective non-directional short-circuit protection, non-directional timeovercurrent protection, directional earth-fault protection and automatic reclosing with syncro- and voltage-check functionality. The H04 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective non-directional short-circuit protection, non-directional timeovercurrent protection, directional and nondirectional earth-fault protection and automatic reclosing. The H05 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective non-directional short-circuit protection, non-directional timeovercurrent protection, non-directional earthfault protection, overvoltage protection, undervoltage protection, residual overvoltage protection and thermal overload protection for devices. The H06 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective non-directional short-circuit protection, non-directional timeovercurrent protection, overvoltage protection, undervoltage protection, residual overvoltage protection, underfrequency protection and overfrequency protection. The H07 standard configuration is designed for protection of large or medium-size threephase AC motors in circuit-breaker controlled motor drives. Due to the large number of protective functions integrated, the relay provides a complete protection against motor damage caused by electrical faults. The H07 configuration can also be applied to other objects needing thermal overload protection, such as power transformers. It can also be used in applications requiring overcurrent protection, under or overvoltage protection and/or directional or non-directional earthfault protection. The H08 standard configuration is designed to be used in single busbar systems using one circuit-breaker for selective non-directional short-circuit protection, non-directional timeovercurrent protection, non-directional earthfault protection, overvoltage protection, undervoltage protection, residual overvoltage protection and thermal overload protection for devices. The protection is based on

Feeder Protection Relay

REX 521 1MRS752177-MBG

Applications (cont´d)

phase-to-earth voltages. In addition, phase-tophase voltages are available in the measurement view. The H09 standard configuration for REX 521 is designed to be used in single busbar systems using one circuit breaker for selective non-directional short-circuit protection, nondirectional time-overcurrent protection, nondirectional earth-fault protection, overvoltage protection, undervoltage protection, residual overvoltage protection, underfrequency protection, overfrequency protection and automatic reclosing. The H50 standard configuration for REX 521 is designed to be used in single busbar systems by using one circuit breaker for selective non-directional short-circuit protection, directional and non-directional time-overcurrent protection, directional and/or non-directional earth-fault protection, overvoltage

protection, undervoltage protection, residual overvoltage protection, underfrequency protection, over-frequency protection and automatic reclosing. The H51 standard configuration for REX 521 is designed for protection of large or mediumsize three-phase AC motors in circuit breaker controlled motor drives. Due to the large number of protective functions integrated, the relay provides a complete protection against motor damage caused by electrical faults. The H51 configuration can be applied to other objects that need the thermal overload protection (such as power transformers). It can also be used in applications requiring overcurrent protection, directional overcurrent protection, under/overvoltage protection, directional or non-directional earth-fault protection, underfrequency protection and/or overfrequency protection.

15

Feeder Protection Relay

REX 521 1MRS752177-MBG

Design, hardware

Different hardware versions of REX 521 are shown in the table below. Table 1: REX 521 hardware versions Sensor REX521xSxxx

Transformers • Current transformers 1/5 A • Current transformers 0.2/1 A • Voltage transformers 100 V

High REX521xHxxx

Transformer modules (MIM)

Medium REX521xMxxx

REX 521 Basic REX521xBxxx

Relay type Version name

1

1

1

1

4

4 1 1

4 1 4

1 1 1

Sensor channels • Current sensor inputs • Voltage sensor inputs Main CPU modules

1

1

1

3 3 1

1

1

1

1

1

1

1

1

CPU_SP (SPA/ IEC plastic) CPU_SG (SPA/ IEC glass) CPU_LP (SPA/ IEC/ LON plastic) CPU_LG (SPA/ IEC/ LON glass) Power supply modules PS_87H (DItresh.=80 VDC) PS_87L (DItresh.=18 VDC) Display module 6 x 16 character display

16

Digital inputs

9

High-speed power outputs

1

Power outputs (PO)

3

Signalling outputs (SO)

2

IRF outputs

1

Trip-circuit supervision (TCS)

1

Feeder Protection Relay

REX 521 1MRS752177-MBG

Design, software

Functionality is available as part of the standard configurations B01, B02, M01, M02, H01, H02, H03, H04, H05, H06, H07, H08, H09, H50 and H51.

Functions available for use in the different standard configurations are listed below.

Table 2: Standard configurations for REX 521 HW versions

Basic

Standard configurations

Medium

High/Sensor

B01 B02 M01 M02 H011 H02 H03 H04 H05 H06 H07 H0823 H0923 H502 H512

ANSI device number

FB name (CD-ROM)

3I> 3I>> 3I>>> Io>

51-1 51-2 51-3 51N-1

NOC3Low NOC3High NOC3Inst NEF1Low

x x x x

x x x x

Io>>

51N-2

NEF1High

x

Io>>>

51N-3

NEF1Inst

x

Io>-->5

67N-1

DEF2Low

x

x

x

x

x

x

Io>>-->5

67N-2

DEF2High

x

x

x

x

x

x

Io>>>-->5 3I>-->

67N-3

DEF2Inst

x

x

x

x

x

x

67-1

DOC6Low

x

x6

3I>>-->

67-2

DOC6High

x

x6

3U> 3U>> 3U< 3U Iub> 3Ith> O-->I Uo> Uo>> Uo>>> f1 f2 SYNC1 Is2t n< 3I() I2> I2>> 3I< FUSEF 3Ithdev> U1U2_1

59-1 59-2 27-1 27-2 68 46 49F 79 59N-1 59N-2 59N-3 81-1 81-2 25-1 48 46R 46-1 46-2 37-1 60 49M/G/T 47-1

OV3Low OV3High UV3Low UV3High Inrush3 CUB3Low TOL3Cab AR5Func ROV1Low ROV1High ROV1Inst Freq1St1 Freq1St2 SCVCSt1 MotStart PREV3 NPS3Low NPS3High NUC3St1 FuseFail Tol3Dev PSV3St1

IEC symbol Protection

x x x

x4

x x x x

x

x4

x

x

x4

x

x x x x

x x x

x x x

x x x

x x x x

x x x

x x x x

x x x x

x x x

x x x

x x x x

x x x x

x x x x

x x x x

x x x x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x x x x

x x x x

x x x x x x

x x x x x

x x

x

x x x x

x x x x x

x x x x

x x x x x

x x x x

x

x

x x x x x

x x x x x

x

x x x x x x

x x x

x

x x

x x

x

x x x x x x x x x

x

x x x

x

x x x

x x x

x x x

x

Control functions IO CB1 COCB1 IO IND1 COIND1 IO IND2 COIND2

COCB1 COIND1 COIND2

x x x

x x x

x x x

x x x

x x x

x x x

x x x

x x x

x x x

x x x

x x x

x x x

x x x

17

Feeder Protection Relay

REX 521 1MRS752177-MBG

Table 2: Standard configurations for REX 521 (continued) HW versions

Basic

ANSI device number

IO IND3 COIND3

High/Sensor

B01 B02 M01 M02 H011 H02 H03 H04 H05 H06 H07 H0823 H0923 H502 H512

Standard configurations IEC symbol

Medium

FB name (CD-ROM) COIND3 x x

x x

x x

x x

x x

x x

x x

x x

x x

x x

x7 x x

MECU3A MECU1A MEVO1A MEDREC MEVO3A MEVO3B MEFR1 MEPE7 MEAI1

x x

x x

x

x

x x x x

x x x x

x x x x x

x x x x x

x x x x x

x x x x x

x x x x x

x x x x x

x x x x x

x x

x x

x x

x x

x x

x x

x x x

CMBWEAR1 CMTCS1 CMCU3 CMVO3 CMTIME1

x x x

x x x

x x x

x x x

x x x x

x x x x

x x x x

x x x x

x x x x

x x x x

IO POS COLOCAT COLOCAT ALARM1-8 ALARM1-8 MMIALAR1-8

x x

x x

x x

x7 x x

x x x x x x x x

x x x x x x x x

x x x x x

x x x x x

x x

x x x

x x x x x

x x x x

x x x x

x x x x

x x x x x

Measurement 3I Io Uo DREC 3U 3U_B f PQE AI1

3I Io Uo DREC 3U 3U_B f PQE AI1

Condition monitoring CB wear1 TCS1 MCS 3I MCS 3U TIME1

CB wear1 TCS1 MCS 3I MCS 3U TIME1

Power quality monitoring PQ 3Inf PQ 3Unf

PQ 3Inf PQ 3Unf

PQCU3H PQVO3H

x

x

x

x

x x

x x

x x

x x

x x

x x

x x

x x

x x

x x

x x

SWGRP

SWGRP

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

Standard SWGRP 1

H01 available only as sensor version

2

Available only as VT version

3

VTs are used to measure phase-to-earth voltages, calculated phase-to-phase voltages are shown by 3U_B

4Configured

fixedly to the Io (1/5 A) channel or Ios if selected

5

Can be used as Io>, Io>> and Io>>> or Uo>, Uo>> and Uo>>> function block with some limitations

6

3I>-> and 3I>>-> cannot be set to operate as 3I>, 3I>> or 3I>>>

7

Motor status indication

Note: Calculated Uo (Uos) is used in the Sensor versions of H01 and H03 configurations. Calculated Io (Ios) is available in H01-H05, H08, H09 and H50 configurations.

18

For more information, see REX 521 Technical Reference Manual, Standard Configurations.

Feeder Protection Relay

REX 521 1MRS752177-MBG

Technical data Table 3: Energizing inputs Rated frequency Current inputs

50.0/60.0 Hz rated current

0,2 A/1 A/5 A

Thermal withstand capability

Voltage inputs

Sensor inputs

continuously

1.5 A/4 A/20 A

for 1 s

20 A/100 A/500 A

dynamic current withstand, half-wave value

50 A/250 A/1250 A

input impedance