Systems Integration Services Europe Product Bulletin Issue Date 0216
PRODUCT BULLETIN
Extended Data Engine
Introduction
2
System Requirements
3
Protocols
4
Modbus Functionalities
4
N2 Functionalities
4
M-Bus Functionalities
4
BACnet Server Functionalities
5
BACnet Client Functionalities
5
OPC Server Functionalities
5
OPC Client Functionalities
5
SNMP Functionalities
5
Additional Functions
6
Web Services Functionalities
6
Trending Functionalities
6
Ordering Codes
7
Standard Protocols Codes
7
Custom Protocols Codes
7
Additional Options
7
© 2016 Johnson Controls, Systems Integration Services Europe Order No. Extended Data Engine - Rev. 3.0 Tuesday, February 23, 2016
1 of 8
Introduction
Extended Data Engine (EDE) is a multiprotocol software application. It allows creating multiple connectivity with the most common used protocols both serial and over IP. EDE normalizes all the data coming from the different protocols, in an internal database. This approach allows the data manipulation and bridging, between protocols and media. Extended Data Engine can manage the following protocols:
Modbus RTU (Master and Slave)
Modbus IP (Client and Server)
N2 System91 and N2 Open (Master and Slave)
M-Bus (Master)
M-Bus IP (Master)
BACnet IP (Client and Server)
OPC (Client and Server)
SNMP (Polling using GET and Traps Receive])
SOAP WebServices (Server)
REST WebServices (Server)
management
[Send
and
Each of these protocols can be linked to any other available, making EDE acting as gateway.
2 of 8 Extended Data Engine
In addition to the connectivity capability, EDE has the following features:
System Requirements
Data manipulation with mathematical and logical functions
Trend, using embedded database or any other database (ODBC)
Alarm management
Extended Data Engine (EDE) has the following system requirements. Recommended Computer
Recommended
Intel® Core™ 2 Duo E6700 or better (Intel Core 2 Duo E4300 minimum) 20 GB free hard disk space available (600 MB minimum) DVD drive Computer Platforms: 2 GB RAM (1 GB RAM minimum)
Memory Supported Operating Systems
Microsoft Windows XP® OS Professional Edition (32-bit) with SP2 or SP3 Microsoft® Windows® 7 OS Professional, Enterprise, and Ultimate Editions (32-bit) with SP1 Microsoft® Windows® 7 OS Professional, Enterprise, and Ultimate Editions (64-bit) with SP1
Extended Data Engine 3 of 8
Protocols Modbus Functionalities
N2 Functionalities
Extended Data Engine can manage communication with Modbus devices through:
Local COM port using RS232/RS485 converter
Modbus IP communication
TCP/IP tunneling using Lantronix UDS-10/USD-100/USD-1100 device server (Serial to Ethernet)
Extended Data Engine can manage communication with N2 compatible (System 91 and N2Open) controllers, through:
Local COM port using RS232/RS485 converter
System 91 compatible devices:
DC9100 / LCP
DR9100
TC9100 / TC9102 / TC9100 / SC9100
DX9100
XT9105
XTM9100
N2Open compatible devices:
MIG
VND
FX-Controllers
FEC/FAC
N2B compatible devices:
M-Bus Functionalities
VMA
Extended Data Engine can manage communication directly with M-Bus devices through:
local COM port using RS232/M-Bus Level converter.
4 of 8 Extended Data Engine
BACnet Server Functionalities
Extended Data Engine can act as a BACnet Server. It supports BACnet data access, alarm, and event operation. Acting as BACnet server, Extended Data Engine supplies, via BACnet, all the integrated data via different protocols. EDE supports BACnet Version 1.5. and profile BBC. The following standard BACnet objects are supported:
Device
Analog Input
Analog Output
Analog Value
Binary Input
Binary Output
Binary Value
Notification Class
The following functions are supported:
BACnet Broadcast Management
Foreign Device Registration
BACnet Client Functionalities
Extended Data Engine can act as BACnet client, integrating, in its database, values coming from any BACnet device on the same IP network. It works on property level and it supports any numeric BACnet property. It supports BACnet data access and COV operations. Using combination of the protocols Extended Data Engine allows “converting” BACnet data, for example, in Modbus.
OPC Server Functionalities
Extended Data Engine can supply all the data, in its internal database via OPC Server. It acts as OPC Server Data Access and OPC Server Alarms & events.
OPC Client Functionalities
Extended Data Engine can act as OPC DA client, reading and writing numeric values from OPC Server DA 1.x and 2.x.
SNMP Functionalities
Extended Data Engine can get data from devices, on IP network, supplying data via SNMP protocol, supporting GET and SET commands. This application is a standard in IT environments.
Extended Data Engine 5 of 8
Additional Functions Web Services Functionalities
Extended Data Engine can supply all the data, in its internal database via Web Services (SOAP and REST). This application is used to supply a standard and modern way to exchange data.
Trending Functionalities
Extended Data Engine supplies the possibly of creating local trends on the points in its internal database. The stored data can be retrieved via Web Services.
6 of 8 Extended Data Engine
Ordering Codes Standard Protocols Codes
Custom Protocols Codes
Additional Options
The following table shows all the standard codes, available via standard ordering system: MW-EDE-0E
Extended Data Engine Standalone version for OPC Linking and Bridging. Can also be used with M5i and is required for the LON Connectivity Options. (License only – software shipped on DVD order code: MWSIS-SW-CD).
MW-EDE-02-05-0E
EDE N2 protocol connectivity for System 91 or N2Open devices (including MIG3x20) for max. 500 N2 items.
MW-EDE-02-15-0E
EDE N2 protocol connectivity for System 91 or N2Open devices (including MIG3x20) for max. 1500 N2 items.
MW-EDE-02-50-0E
EDE N2 protocol connectivity for System 91 or N2Open devices (including MIG3x20) for max. 5000 N2 items.
MW-EDE-04-05-0E
EDE Modbus serial driver (RTU and ASCII) max. 500 points.
MW-EDE-04-15-0E
EDE Modbus serial driver (RTU and ASCII) max. 1500 points.
MW-EDE-04-50-0E
EDE Modbus serial driver (RTU and ASCII) max. 5000 points.
MW-EDE-05-05-0E
EDE Modbus IP driver for max. 500 points.
MW-EDE-05-15-0E
EDE Modbus IP driver for max. 1500 points.
MW-EDE-05-50-0E
EDE Modbus IP driver for max. 5000 points.
SIS-EDE-BAC-0E
EDE BACnet IP driver for max. 20000 points
The following table shows all the custom connectivity, available contacting Systems Integration and Services Europe: MW-EDE-11-05-0E
EDE SNMP driver for max. 500 points.
MW-EDE-11-15-0E
EDE SNMP driver for max. 1500 points.
MW-EDE-11-50-0E
EDE SNMP driver for max. 5000 points.
The following table shows additional options, available contacting Systems Integration and Services Europe: MW-EDE-14-05-0E
EDE Trend driver for max. 500 points.
MW-EDE-14-15-0E
EDE Trend driver for max. 1500 points.
MW-EDE-14-50-0E
EDE Trend driver for max. 5000 points.
MW-EDE-15-05-0E
EDE WebService driver for max. 500 points.
MW-EDE-15-15-0E
EDE WebService driver for max. 1500 points.
MW-EDE-15-50-0E
EDE WebService driver for max. 5000 points.
Extended Data Engine 7 of 8
Johnson Controls Systems Integration Services Europe , Milan
www.johnsoncontrols.com .
8 of 8 Extended Data Engine