(1) Address code setting
CCM
Outdoor unit
Indoor unit
Address code setting for outdoor unit Address setting switch (network)
Address setting switch (outdoor communication)
Address code setting for outdoor unit Address setting switch for communication among outdoor unit Each outdoor unit need a independent address code Address setting 0
Master unit
1
Salve unit
2
Salve unit
3
Salve unit
≥4
Invalid address, cause system error
Caution: The address can be not beyond 0~3; The address of each outdoor unit must be different.
Address code setting for outdoor unit Address setting switch for communication of network (CCM02) Because the CCM02 can be connected with 8 groups of outdoor units, each outdoor unit need two switches to label the address
For the address of different group
For the address of different outdoor unit in one group
Caution: Only when outdoor units are connected with CCM02, the above two switch need to be changed.
Address code setting for indoor unit Address setting switch ( for communication with outdoor unit)
Address setting switch (network)
Address code setting for indoor unit Indoor unit Address code for communication between indoor units and outdoor units: Switch
Address Code
00 ~ 15
Eg: 33
16 ~ 31 32 ~ 47 48 ~ 63
Caution: The address of each indoor unit must be different.
Address code setting for indoor unit Indoor unit Address code for network
Switch
(between indoor units and CCM):
Address Code
00 ~ 15 16 ~ 31 32 ~ 47 48 ~ 63
Caution: The address of each indoor unit must be different.
Electric Wiring
Electric Wiring All wires, parts and material must conform to local standards All wiring work must be done by qualified person
Voltage range: rated voltage ±10%;
(2) Power supply
Basic requirement
Independe nt power supply;
Capacity of power device is bigger enough;
Well and reliable PE line
Electric Wiring
(2) Power supply
Power supply for outdoor unit
Creepage breaker Manual switch
3-phase 380/400/415V
earth
Electric Wiring
(2) Power supply
Power supply for outdoor unit •
The power supply of outdoor units are in series connection
earth
3-phase 380/400/415V
Creepage breaker Manual switch
We don’t suggest power wiring like this, because the power wire of the first outdoor unit is too big to be fixed in the terminal of outdoor unit.
Electric Wiring
(2) Power supply
Power supply for indoor unit
(1)
(2)
6.860 kW MDV-D71T2/N1-A3 IU-1 6.860 kW MDV-D71Q4/N1 IU-2
(3)
5.411 kW MDV-D56G/N1Y-C IU-3 8.696 kW MDV-D90T2/N1-A3 IU-4
Electric Wiring
(2) Power supply
Power supply for indoor unit (1)
Wiring branch box
Wiring (2) branch box
6.860 kW MDV-D71T2/N1-A3 IU-1 6.860 kW MDV-D71Q4/N1 IU-2
Manual switch Creepage switch (3)
5.411 kW
Wiring branch box 230v 50Hz 1N Power supply
MDV-D56G/N1Y-C IU-3 8.696 kW MDV-D90T2/N1-A3 IU-4
Strongly recommend: all the indoor units are connected with the same power supply •95
Electric Wiring
(2) Power supply
Power supply for indoor unit (1)
230v 50Hz 1N
Creepage switch
Manual switch
Wiring (2) branch box
6.860 kW MDV-D71T2/N1-A3 IU-1 6.860 kW MDV-D71Q4/N1 IU-2
230v 50Hz 1N
Creepage switch
Manual switch
(3)
5.411 kW
Wiring branch box
MDV-D56G/N1Y-C IU-3 8.696 kW MDV-D90T2/N1-A3 IU-4
If not possible, please guarantee that the power supply for all the indoor units are switched on when the system is running
Electric Wiring
L1 L2 L3N
(2) Power supply The spec of the outdoor power supply wire is selected according to the max. total current of outdoor units
L N
The spec of the wire is selected according to the max. total current of indoor units
Indoor unit
Controller
2
Electric Wiring
(3) Signal wire
Signal wire: The signal wire should use •
Between outdoor units in one combination;
•
Between outdoor unit and indoor unit; Master unit
P,Q, E
H1,H2, E
P,Q, E
Slave unit
H1,H2, E
P,Q, E
3-core shielding wire
Slave unit
H1,H2, E
P,Q, E
P,Q, E
2
Electric Wiring
(3) Signal wire
Signal wire: The signal wire should use •
Between outdoor units and CCM02;
Master unit
K1,K2, E
Slave unit
K1,K2, E
3-core shielding wire
Slave unit
K1,K2, E K1,K2, E
•Max. 32 outdoor units in 8 combination can be connected with CCM02; •All the outdoor units are in series connection.
2
Electric Wiring Signal wire: •
Between outdoor units and digital ammeter;
(3) Signal wire
2
Electric Wiring
(3) Signal wire
Signal wire: •
Wring terminals of ammeter
Between outdoor units and digital ammeter; Terminals of signal wire
Terminals of power supply
400v 50Hz 3N
2
Electric Wiring
(3) Signal wire
Signal wire: •
Back
Wring terminals of ammeter;
To power supply
Supply power to outdoor unit
2
Electric Wiring
(3) Signal wire
Signal wire: • •
The signal wire should use
Between indoor unit and CCM;
3-core shielding wire
Between CCM and computer.
X,Y, E
F1,F2, E
X,Y, E
F1,F2, E
X,Y, E
F1,F2, E
X,Y, E
X,Y, E
Electric Wiring
(3) Signal wire
Key point: 1.Signal wire should be 3-core shielding wire 2.The shielding skin is connected with PE 3. Keep away from the strong wire 4. Correct polarity; (P-P, Q-Q, X-X…………..) 5. Series connection