DG DemoNetz Validierung Innovative Spannungsregelung von der Simulation zum Feldtest
EnInnov12 - 12. Symposium Energieinnovation, TU Graz 15-17.02.2012
Matthias Stifter, B. Bletterie, H. Brunner, D. Burnier, H. Sawsan, F. Andrén, R. Schwalbe, W. Tremmel , A. Abart, R. Nenning, F. Herb, and R. Pointner
DG DemoNet Keeping voltage limits by integration of distributed generation (DG)
DG DemoNet (1) Distributed control (level control) Control of tap changer according to voltage measurements from the grid (critical nodes) Information about the grid state is required ICT necessary
06.03.2012
3
DG DemoNet (2) Coordinated control (level + range control) Control of tap changer according to voltage measurements from the grid (critical nodes) Control of reactive power (Q) and as a last measurement reactive power (P) Impact of Q/P on the critical nodes (voltage sensitivity) are in a linearised model – the contribution matrix Local controller (in case of failure) Information about the grid state is required ICT necessary 06.03.2012
4
DG DemoNet – critical nodes Nodes which have the highest or lowest voltage within a year Determined by offline power flow calculation based on historical generation and load profiles Representation of the voltage situation in the grid during operation
Voltage drop diagram of node 835 at min_time 28.1.2005 | 19:30
Voltage drop diagram of node 83902 at max_time 8.5.2005 | 03:15
1.01
1.02
1
83902
Voltage (p.u.)
Voltage( p.u.)
1.01
1
0.99
0.98
0.99 0.98 0.97 0.96 0.95
0
5 Knoten
06.03.2012
10
15 Distance (km)
kritische Knoten
20
kritische Knoten
25
30 Wasserkraft
835 0
5 Knoten
10
15 20 Distance (km) kritische Knoten kritische Knoten
25
30 Wasserkraft
5
DG DemoNet – contribution matrix Linearised model of the network With the matrices
CN DG
a P |1,1 aP P |2,1 M a P|n ,1
∂U ∂P
CN
a P |1,2
L
a P |2,2 M
L O
a P|n ,2
L
a P|1, m a P|2, m M a P|n , m
for active power
06.03.2012
DG
aQ|1,1 aP Q|2,1 M aQ|n ,1
and
∂U ∂Q aQ|1,2 L aQ|1, m aQ|2,2 L aQ|2, m M O M aQ|n ,2 L aQ|n , m
reactive power
6
DG DemoNet – controller concept The following indicators are used: over voltage voltage band lower voltage range: distance between highest and lowest voltage measurement
Two separate controllers: level control: tap changer position at the substation range control: control of Q(P) at the distributed generator (if the range is greater than the voltage band) 06.03.2012
7
DG DemoNet – controller design
Level Control
Range Control
06.03.2012
8
DG DemoNet – level control Level control (centered) U set =U UL − Rng = u
EVB − Rng
max
2 −u
− (u
max
−u
curr
)
(1) ( 2)
min
Effective Voltageband ∆ ∆
∆
0,011 0,7
1,060 1,050 1,040 1,030
Voltage (p.u.)
modes of operation centered upper limit lower limit tap only if necessary
1,020
ucurr
1,010
umax
1,000
umin
0,990
UUL
0,980 ULL
0,970 0,960
UDB-up
0,950
Uset
0,940
UDB-low
0,930 0,920 0,910 06.03.2012
Cases (before / after "Level control" action)
9
DG DemoNet – range control Range control n 2 min ∑ (Qi + ∆Qi ) ∆Q i=1 Qi + ∆Qi ≤ Pi tan(arccos( PFmin )) Qi + ∆Qi ≤
2 2 S n − Pi
max(U i + AQ∆Qi ) − min(U i + AQ∆Qi ) ≤ EVB EVB = VB − ∆U
DB
− ∆U
reserve
(3) ( 4) (5) (6) (7)
standalone (without level control) keep within fixed voltage band fixed critical node limit voltage rise relative to reference node
06.03.2012
10
DG DemoNet implementation (CVCU) System architecture
CVCU system architecture
06.03.2012
12
Optimisation Minimum of a nonlinear function under linear constraints Commercial optimisation library Matlab (Optimisation Toolbox) Intervallarithmetic (with University of Vienna) Open Source Optimisation library (Opt++) Development of an optimisation algorithm (constraints + minimum)
06.03.2012
13
Optimisation algorithm: principle Minimum of a nonlinear function under linear constraints (Q-control) or nonlinear constraint (PQ-control) convex problem • Constraints define convex polyeder, where the valid minimum can be found • Minimum is always definite Solution by declining gradients Two steps to solve two different problems 1. Find the valid area 2. Optimum without leaving the area
06.03.2012
14
Requirement on topology information
03312-010
03336-040
03355
03336-030
04100-200
03600-070
04100-210
03314-010
03302-160
03600-010
0.62MW 03633-010
03314-020
03302-170
03302-180
03347-020
03337
03312-040
03314-030 03314-040
03314-050
03312-020
04200-080
03312-010
03381
04200-060
04100-140
04100-150 04231
04100-130
04100-160
04100-120
04200-070
DEA_0234-KW
04200-040
04200-050
Internal switching
04230-020
04200-020
04230-010
04200-030
normal operation
04230-020
04200-020
04100-110
04134
04100-100
04200-050
04230-010
04200-040
04200-100
04200-090 04139
04136
04100-150
04200-030
04002-040
04002-050
04002-060
04002-070
04002-080
04002-090
04530
04002-100
04002-110
04002-120
04002-130
04002-140
04002-150
04002-160 04002-170
04300-010
04002-030
0411 Predlitzort
04300-020
04002-020
04044
04002-010
04046
04200-010
04001-120
04034
04001-110
04040-010
04001-100
A_ DE
04001-090
04041
04001-080
04035-020
04033-020
04001-070
-KW
04002-160 04002-170
10 04
04002-150
04500-010
04002-140
04037
04002-130
04043
04002-120
04035-010
04002-110
04500-020
04034
_0 D EA
41
W 0-K
04500-020
06.03.2012
04002-100
04033-010
04002-090
04032
04002-080
04300-010
04002-070
PREDLITZ-LÄNGSREGLER
0411 Predlitzort
04300-020
04002-060
04530
04046
04002-050
04044
04002-040
04040-010
04002-030
04041
04002-020
04500-010
04002-010
04037
04200-010
04001-120
04043
04001-110
04035-010
04001-100
04035-020
04033-020
04001-090
04033-010
04032
04001-080
03302-200
0208 Tamsweg
PREDLITZ-LÄNGSREGLER
04001-070
03302-190
03352
03302-150
03339
03302-145
03330
03302-140
03342
03302-130
03347-010
03338
03302-120
03312-060
03313
03600-020
DE A_ 02 35 -K W
03345-020
03600-060
K
22-
_02
04100-190
03600-030
03312-050
03600-040
03633-020
03600-050
03302-110
~ G
0.62MW
W
04160-050
0.49MW 04100-180
03302-100 0821-KKW
0821-Trafo
03345-030
03630
DEA_0270-KW
DEA_0247-KW
DEA_0219-KW
03302-090
03312-030
03302-080
DEA_0216-KW
03383
03336-020 03336-010
03302-070
DEA_0209-KW
03381
04200-060
04100-140
04231
04100-130
04200-070
04100-160
04134
04100-120
03302-060
0.9MW
04100-170
03312-020
04200-080
DEA_0234-KW
04136
04100-110
03302-050
0.346MW
03314-050
03354
03336-050
04160-020
03349
5 0337
04160-010
03302-040
03610-030
04132-020
03302-030
03610-010 03610-020
04137
04132-010
03312-040
04200-100
04100-170
04200-090 04139
04100-100
03302-020
34
03364-020
03302-010
0.384MW
0.54MW
036
03364-010
0208 Tamsweg
03301-180
03344
03301-170
03335
03301-160
04110-020 04110-010(1)
03301-150
03376
03301-140
03350
03353
03301-130
03366-020
DEA_0830-KW
03345-010
03362-050
03334-020 03334-010
03301-120
04110-030
03332-010
03301-110
03351
03301-111
03301-100
03301-112
03302-230
03311-010
03302-220
03311-020
03302-210
03309
03352
03339
03302-200
03370
03366-010
04133
03314-030 03314-040
03302-190
-KW 0820 A_ DE
0820 Graggaber 0.7MW
D EA
03633-010
03302-180
03368
03385
03334-050
0.62MW
03330
03342
03340-010
03600-010
03314-020
03337
03312-060
03600-020
03302-170 03347-010
03302-160
03347-020
03383
03338
03302-150
03378
03334-040
03 37 9
03314-010
03302-145
03362-040
4160-020
04100-210
03302-140
03362-030
04110-010
03600-070
D E A_
04100-200
03302-130
03362-020
04133
04100-190
03600-030
03312-050
03345-020
W 2-K
022
0.49MW 04100-180
03302-120
03362-010
03312-030
03600-040
03600-060
04160-050
4160-020
0.62MW 03600-050
03302-110
~ G
03345-030
03630
DEA_0270-KW
03302-100 0821-KKW
0821-Trafo
03633-020
03344
DEA_0219-KW
03302-090
03334-030
03336-030 03336-020
03302-080
DEA_0216-KW
0.346MW
04110-010
03302-070
DEA_0209-KW
03313
04160-020
03302-060
0.9MW
DE A_ 02 35 -K W
04160-010
03302-050
03336-010
5 0337
04132-020
03302-040
03610-030
04137
04132-010
03302-030
03349
03302-020
4
03364-020
03302-010
0.384MW
03340-020
0.54MW
03 63
03364-010
03301-180
03335
03301-170
04110-020 04110-010(1)
03301-160
04110-030
03301-150
03376
03301-140
03350
03301-130
03353
03334-010
03301-111
03301-112
03301-120
03309
03301-110
03351
03366-020
DEA_0830-KW
DEA_0247-KW
03370
03366-010
03336-040
-KW 0820 A_
0820 Graggaber 0.7MW
03355
DE
03354
03336-050
03368
03610-010 03610-020
03362-050
03362-040
03385
03378
03362-030
03345-010
03 37 9
03362-020
03334-020
03340-010 03311-010 03311-020
03332-010
03334-030
03340-020
03301-100
03362-010
03334-040
03334-050
Information about Critical Node (CN) / Distributed Generation (DG) connection status feeder assignment (DG CN) intra-feeder changes
15
03302-210
03302-220
03302-230
Simulation Real time behaviour and offline simulation
Simulation and testing 54301-030 54301-040
03354
03355
03312-010
03381
04200-060
204
04231
04100-13004100-14004100-150
04200-020
CN_andere Schaltzustände Regelnden Anlagen
04046
04062 04061
Ko ns tant e_ La st_ BF1 b
04044
04040-010
04034
W
04531
04310 DEA_0840-KW
0840 Kendlbruck 2.39MW
Achtung! Profil 0447 für 0447-LAST & 0427-LAST verwenden
0443
04320
DEA_0443-KW
CN_Normal
04530
04300-050 04300-040 04300-030 04300-020 04300-010
04036-070 04036-080 04036-065
BF 1b konstante Last
04002-01004002-02004002-03004002-04004002-05004002-06004002-07004002-08004002-09004002-10004002-11004002-12004002-13004002-14004002-15004002-16004002-170
10-K 04 A_ DE
04047
04063
04041
04200-010
04001-120
04037
04001-110
PREDLITZ-LÄNGSREGLER
04043
04001-100
04035-010 04035-020
04001-090
04033-010 04033-020
04032
04001-080
0411 Predlitzort
04300-070 04300-060
04100-030
04200-04004200-050 04230-020 04230-010
04200-030
04300-080
04030-030
04001-070
03352
03312-020
223 DEA_0234-KW
04300-100 04300-090
04030-040
04001-060
03339
03312-050
03312-030
03312-040
04040-020
04030-050
04001-03004001-04004001-050 04042
0166-Kupp
04001-020
03330
03342
03383
03338
03347-020 03347-010
03313
03633-020
03600-060
W 22 -K
A_ 02
04100-170
04100-120
03337
03345-010 03345-020 03345-030 03610-010 03610-020 03610-030
03312-060
03349
DEA_0247-KW
03344
DE
03633-010
03314-02003314-03003314-04003314-050
04200-100
03314-010
04100-160
04100-110
04134
04100-100 04136
04135-010 04135-020
0208 Tamsweg 0235 gelöscht
04200-090 04200-080 04200-070
04140
04131
04130 04138
04100-040 04100-05004100-06004100-07004100-08004100-090
208
04330 04300-110
Achtung! Hälfte des Profils von 0108 in 0813 verwenden und die andere Hälfte in 0108
04100-210
04133
04100-200
03600-070 03 63 4
04110-010 4160-020
0.49MW
04500-050 04500-040 04500-030 04500-02004500-010
04036-060
03335
03350
03301-010
03200-090
03200-080
03100-080
004038-030 04038-040
0402904030-060
0.346MW
04100-180 04100-190
0821-Trafo
0.62MW
03630 03600-05003600-04003600-03003600-02003600-010
DEA_0270-KW
04031-03004031-020 04031-010
DEA_0113-KW
04001-010
04030-010
8- 02
DEA_0219-KW
03302-11003302-12003302-13003302-14003302-14503302-15003302-16003302-17003302-18003302-19003302-20003302-21003302-22003302-230
~ G
247
DEA_0209-KW 04137
04132-01004132-020
04139
03000-030
04030-020
04 03
04036-09004036-100
04038-010
04036-050
03100-030
0156-HILFTR
0.384MW
04160-01004160-020
04100-020
04045
02300-030
03134
213 03302-100 0821-KKW
03100-020
03000-020
02300-020
03100-040 03100-050 03100-060
03000-060
03133-030 03133-010
03001 03160-030
03111-040
03031
156
0132-SS-K.. 0132-SSB 03102
03111-030
0132
03100-010
03000-040 03000-050
03160-010 03160-020
03161
03136-01003136-020
03112-050
03130-030
03133-020
03138
03111-010
179
03111-020
03112-040 03112-030 03110-01003110-020
UW-LUN-NETZ30_O 03112-060
03110-05003110-06003110-07003130-01003130-020
5 0337 03336-010 03336-020 03336-030 03336-040 03336-050
DEA_0850-KW
03362-050 03362-060 03362-070 03362-080
03385
03378 03353
03364-020
03200-100
02100-030
0.54MW DEA_0830-KW
0216 gelöscht
04160-050
03364-010
04110-030 04110-02004110-010(1..
03351
03366-01003366-020
03301-12003301-13003301-14003301-15003301-16003301-17003301-18003302-01003302-02003302-03003302-04003302-05003302-06003302-07003302-08003302-090 03376
03311-020 03311-010
03374
03301-110
03370
03360
03332-04003332-03003332-02003332-010
03301-111 03301-112
03301-07003301-08003301-09003301-100
W 20-K A_08 DE
820
03309
03372
03340-010
03367-01003367-020
03384
03362-01003362-02003362-03003362-040 03368
03340-020
03369
F0327
03 37 9 03334-010 03334-020 03334-030 03334-040 03334-050 03334-060 03334-07003334-080 03334-090
03363-050_1 03363-050_203363-060
03331-020 03331-030 03331-040 03331-050 03331-06003331-070
03348-020
03363-030 03363-040 03301-020
03343-030 03346-020 03346-010
03261
03211-040
03000-080 03200-040
03000-090
02100-040
02002
03200-060
DEA_0306-KW
02001
02110-01002110-020
03361
03346-030
03000-070
02000-020
03200-020 03211-010 03232-010 03232-020
0602-UM1
02101-02002101-030 02101-040 02101-05002101-060
02102-050
02102-030
0602-UM2
0600-UM
03341-010 03341-020 03341-030
DEA_5538-KW
DEA_5540-KW
02140
02130-02002130-010 UW-LUN-110-SSKU UW-LUN-30.. 03101
G ~
04400-07004400-06004036-01004036-02004036-030 04036-040
KATSCHBGTU-LÄNGSREGLER
05110-030
KATSCHBGTU S
03365
03331-010
DEA_5566-KW SL_UW_LUN UM-LUN1
UM-LUN2
183/4-130
05100-130
05002-010
03110-040
03112-01003112-020
02300-010
06001-010
04400-010 04400-030
05100-090
05100-070(1..
0108-SS-KUPP-2 0108-SS-KUPP-1
05100-04005100-05005100-060
03200-070
03301-060
850 03373
03377
04420
05134
05100-030
0304
0304-SS1
03380
03363-02003363-010
0850 Zaunschirm 0.6MW
03100-070
03110-030
~ G
04410
05100-110(1..
05110-020
05100-020
05100-070
05132-030
05132-010
05132-020
05100-010
05130
05031
05002-050
05110-010
KW- HIM
05100-100
03310
0304-SSKU 03200-050
03200-010
04100-010
05100-080
05001-03005001-040 05001-050
0104
03200-M4
1
03211-030
03200-030
03000-010
DEA_KW-MUR
05001-015 05001-020
03211-020
03371
03301-04003301-050 03301-030
0313 Mauterndorf
DEA_0308-KW
UW-LUN-NETZ30_W
04400-020
05002-030 05002-020
13
05002-040
05030-010 05030-020
05001-010
KW- RTG
02101-010
02100-020
DEA_0114-KW
05033
05032-010
06001-020
05100-110 05100-120
06030-010 06030-020
06045
06031
06001-080 06001-090
06001-105 06001-100
06001-140
06001-07006001-06006001-05006001-04006001-030
06033
06037-010 06037-020
06035
06034
06001-250
06001-130
0310 Twengort
03343-020
03359-010
DEA_KW-HIM
UW-LUN-30-SS1
KW- ZED
DEA_KW-RTG
DEA_5535-KW
54301-110 54301-100 54301-090 54301-080 54301-070 54301-060 54301-050 54302-040 54302-030 54302-020 54302-010 54302-050
02100-010
SL_LUN_110
06001-110
03343-010
02000-03002000-04002000-05002000-060 02000-070 03000-110 03000-100
02
UW-LUN-110-SS2
06001-120 06036
06002-050 05032-020 05032-030
187
DEA_KW-ZED
54302-070 54302-080 54302-090
54531-010 54531-020 54311-080
54311-075 54311-070
54312 54311-050 54311-060
54311-020 54361-010 54361-020
54360-050
0602-10-SSB 0602-10-SSA
UW-LUN-30-SS2
135
0600-10-SS
UW-LUN-NETZ110
DEA_0814-KW
06002-040 06002-030 06002-020 06002-01006001-24006001-23006001-22006001-21006001-20006001-19006001-18006001-17006001-16006001-150
DEA_0600-KW
02101-070
54700
04400-050 04400-040
p up -K 21 183/4-100
DEA_0167-KW
0602
02000-010
01
46
Störkabel .. 54110-080
02102-02002102-015 02102-010
54360-04054362-010 54362-020 54362-030 54362-040
183/4-080
5493
54302-060
0600
0602-10-SSKU
183/4-070
54102-270 54102-280
183/4-120
01130-010
183/4-110
188 54110-070
06.03.2012
02102-08002102-07002102-060
UW-LUN-110-SS1
0 06
54110-060
54110-050
54110-010
54334
54102-290
5478 LS/TR Sch..
0812-SS-KUPPL
183/4-060
5478-SS1
54333
54360-010 54311-01054311-005
183/4-040 54110-02554110-020 Störkabel 5478-LS-Tauri ski.. 183/4-050
54144-010
54144-030 54110-030
54311-030
54360-03054360-020
DEA_5562-KW
52338-110
52336
0812-SSB
54311-16054311-150
54105
52338-120
54110-040
54365
54311-130 54311-120 54311-110 54311-140
54311-170 183/4-030
54136 54102-22054102-230 54102-260 54102-25554102-25054102-240
52338-06052338-05052338-04552338-04052338-030
54137
0812-SSA
54044
183/4-020
54131
54102-140 54102-130 54102-12054102-110 54102-100
54112
54102-210
54102-200
54311-090
534
10
52332
54063-030
54311-100
52335
52337
54063-020
54133
54139
54138
54132
54150
52338-070
54032-05054032-040 54061
54102-17054102-16054102-150
52338-020 52338-010 54102-190 54102-180
52300-040
54111-02054111-03054111-04054111-05054111-06054111-07054111-080
52338-10052338-09052338-080
54500-08054500-08554500-09054500-10054500-11054500-12054500-13054500-14054332-01054332-020 54032-030 54032-020
54063-010 54032-060
54500-010
54142-040 54102-04054102-030
5457-kupp 54111-090 54111-100 54111-11054111-120 54111-130 54111-140
52047 52362
52010-010
52300-10052300-09052300-080
52334
54500-070
8-0
52339
52333-010
54500-04054500-05054500-060
54143
54134-020 54134
52330-01052330-02052330-03052330-040
52300-06052300-050 54111-010 52300-070
52061
52333-03052333-020
52300-030
54500-030
34 03
52300-21052300-200 52300-190 52300-180 52300-17052300-160 52300-150 52300-140 52300-130 52300-125 52300-12052300-110 52010-040 52010-030
52010-020
54500-020
5458-LS 54111-150 54102-05054102-06054102-07054102-08054102-090
52043
52000-20052000-21052000-22052000-23052000-24052000-25052000-260 52033
52000-190
52046
52000-16052000-17052000-180
52045
52035 52042
52060
52034-01052034-020
52036
52300-020 52300-010
52032-010 52032-02052032-030
53230-09052032-04052032-04552032-05052032-060
54142-030 54142-020
52037-02052037-010
183/4-010
54102-010
54142-010
52000-270 52000-28052000-290 52000-300 52000-310 52000-320
Distribution network „Lungau“
17
Simulation and testing Application in planning and operation
R EAL PROC ESS MV N etwork
IEC 104 Telecontr ol interface
R eal Tim e Sim ulation
Power F actory SIM ULAT ION
06.03.2012
SICAM 230
COM
Process Interface via SC AD A
COM OPC
Offline Sim ulation
CVCU
OPC VOLT AGE CONT R OLLER
18
Offline simulation
RANGE - EVB (p.u.)
RANGE - EVB (p.u.)
Offline-Simulation: Simulation and analysis of functionality One year 0.02 0 -0.02 -0.04 -0.06 0.02 0 -0.02 -0.04 -0.06
Q (kvar)
0
-500
-1000 JAN
06.03.2012
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
19
Realtime simulation Dynamic simulation controller cycles latency in communication generators and transformer (OLTC)
06.03.2012
20
Field tests Open loop and closed loop tests
Requirements on ICT Overview Vorarlberg
06.03.2012
22
Communication Großes Walsertal
Different communication media fibre cable PLC WiMax radio link 06.03.2012
23
Field test - DG Brunnenfeld / Substation Bürs
06.03.2012
24
Field test DG Brunnenfeld (Substation Bürs) Without range control
Voltage on 10kV side
Voltage on 0,4kV side
Reactive Power (Q) Active Power (P)
06.03.2012
25
Field test DG Brunnenfeld (Substation Bürs) With range control
Voltage on 10kV side
Voltage on 0,4kV side
Reactive Power (Q) Active Power (P)
06.03.2012
26
Experiences from the field tests dUTap: Voltage step of a tap is not linear: 1,667% at 110kV/30kV nominal Depending on primary voltage and the current tap position Lungau: Narrow voltage band. Range not controllable and higher than EVB Danger of „Hunting“: Adaption of the controller algorithm Different communication bandwidths and delays of measurements Event filtering and analysis of timestamps Tresholds to reduce communication bandwidth and keep the dynamic low Filtering of measurement samplings Deviations of setpoints and actual measurements – robustness
06.03.2012
27
Comparision of the tap steps
Salzburg
Vorarlberg
dUTap
Minimales UDeadband
dUTap
Minimales UDeadband
Nennwert Neutralstellung
1,667%
2,000%
1,062%
1,274%
-10 Taps von Neutralstellung
1,96%
2,35%
1,17%
1,40%
+10 Taps von Neutralstellung
1.43%
1,72%
0,96%
1.15%
06.03.2012
28
„Hunting effect“ (wrong dUTap)
Real dUTap is higher than estimated and voltageband is violated
06.03.2012
29
DIgSILENT
Control strategy: Effective voltage band (independent) 1,0300
1,0200
1,0100
1,0000
Range control tries to keep voltages within EVB with Q from the DG
0,9900
0,9800 2.045E+5
2.049E+5
2.053E+5
2.057E+5
[s]
2.061E+5
2.049E+5
2.053E+5
2.057E+5
[s]
2.061E+5
0,80
0,40
0,00
-0,40
-0,80
-1,20 2.045E+5
06.03.2012
30
DIgSILENT
Control strategy: Full voltage band (cooperative) 1,0300
1,0200
1,0100
1,0000
Range control only activates Q when voltage limits are to get violated
0,9900
0,9800 2.045E+5
2.048E+5
2.051E+5
2.054E+5
2.057E+5
[s]
2.060E+5
2.048E+5
2.051E+5
2.054E+5
2.057E+5
[s]
2.060E+5
1,00
0,50
0,00
-0,50
-1,00
-1,50
-2,00 2.045E+5
06.03.2012
31
„Hunting effect“ (wrong dUTap)
Real dUTap is higher than estimated and voltageband is violated
Range control activates DG to consume Q to keep voltages within limits
06.03.2012
32
Communication delay of measurements
06.03.2012
33
Filtering E.g.: 1min RMS CVCU_MEAS_20120208_12-10-00.csv/CVCU_MEAS_20120208_12-10-00 1,02
1,015
1,01
1,005
06.03.2012
08.02. 14:21
08.02. 14:20
08.02. 14:19
08.02. 14:18
08.02. 14:17
08.02. 14:16
1
34
Outlook Next steps
Outlook DG DemoNet Validation Open und closed loop operation in „Großes Walsertal“ and „Lungau“ experiences and long term tests Mastering different network states topology recognition Interaction with local controller Strategies to start and stop the controller Analyse influence of the HV grid Interoperability with other simulation and SCADA systems Communication based on IEC61850 Optimise overall losses (reactive power) Consider thermal constraints in addition to voltage constraints Dynamic assessment of voltage sensitivity / topology coupling with state estimator 06.03.2012
36
AIT Austrian Institute of Technology your ingenious partner Matthias Stifter Energy Department Electric Energy Systems AIT Austrian Institute of Technology Österreichisches Forschungs- und Prüfzentrum Arsenal Ges.m.b.H. Giefinggasse 2 | 1210 Vienna | Austria T +43(0) 50550-6673 | M +43(0) 664 81 57 944 | F +43(0) 50550-6613
[email protected] | http://www.ait.ac.at
Zusätzliche Folien Backup
„Range Control“: Beitragsmatrix-Konzept ∂U ∂P a P |1,1 aP P |2,1 M a P |n ,1
∂U ∂Q
a P |1,2
L
a P |2,2 M
L O
a P |n ,2
L
a P |1, m a P |2, m M a P |n , m
aQ|1,1 aP Q|2,1 M aQ|n ,1
aQ|1,2 L aQ|1, m aQ|2,2 L aQ|2, m M O M aQ|n ,2 L aQ|n , m
In der Beitragsmatrix wird in der CVCU hinterlegt wie groß die Auswirkung einer regelbaren Erzeugungsanlage auf die Spannungen an den einzelnen kritischen Knoten ist (Basis für die Verkleinerung der Spreizung) Entsprechend der Reihung in der Beitragsmatrix werden Blindleistungssollwerte an die Anlagen gesendet bis die Spreizung der Spannung der kritischen Knoten wieder innerhalb des zur Verfügung stehenden Spannungsbandes liegt bzw. so klein ist, dass eine Stufenschaltung (über den Level Controller) möglich ist 06.03.2012
39
„Range Control“: Berechnung der Blindleistungssollwerte für die zu regelnden Anlagen n _ DG
2 ( Q + ∆ Q ) Minimiere ∑ i i i
unter den Randbedingungen U CN 1 ∆U CN 1 U CN 1 aQ|1,1 U ∆U U a Q|2 ,1 0.94 < CN 2 + CN 2 = CN 2 + M M M M U CNn ∆U CNn U CNn aQ|n ,1
aQ|1, 2 aQ|2 , 2 M aQ|n , 2
L aQ|1,m ∆Q1 L aQ|2, m ∆Q2 < 1.03 O M M L aQ|n ,m ∆Qm
Qi + ∆Qi ≤ Pi tan(arccos( PF min))
Qi + ∆Qi ≤ Si2,max − Pi 2
06.03.2012
40
Topologieerkennung Ausgehend von einem Normalschaltzustand des Netzes müssen Änderungen der Topologie dem Regelalgorithmus mitgeteilt werden, damit die CVCU mit dem richtigen Netzmodell (Beitragsmatrix) arbeiten kann. Die Änderung des Einflusses eines regelbaren Kraftwerks auf die korrespondierenden kritischen Knoten (Messpunkt) kann zu falschen Berechnungen führen. Die Anforderungen für den zuverlässigen Betrieb der CVCU an die Fernwirktechnik werden in vier Stufen eingeteilt, wobei die Informationen für die ersten beiden Stufen unbedingt notwendig sind: 1. Kritischer Knoten (KK) oder regelbares Kraftwerk (rKW) am Netz. 2. Kritischer Knoten (KK) oder regelbares Kraftwerk (rKW) im Einflussbereich des Umspanners 3. Änderung der Zugehörigkeit zum Abzweig eines kritischen Knotens (KK) oder eines regelbaren Kraftwerks (rKW) 4. Dynamische Ermittlung der Beitragsmatrix nach Änderung der Topologie 06.03.2012
41
Field test - DG Brunnenfeld (Substation Bürs) Set points for reactive and active power [math.] 1.0000
V[V] 500.000
kV[kV] 50.000
kW[kW] 500.000
400.000
40.000
300.000
300.000
30.000
100.000
200.000
20.000
-100.000
100.000
10.000
-300.000
0.0000
15:05:37 15.09.2011
06.03.2012
15:19:17 15.09.2011
15:32:58 15.09.2011
15:46:38 15.09.2011
16:00:19 15.09.2011
42