The Tyco Fire Products (TFP) Residential Fire Protection Package offers a diverse line of products that are aesthetically pleasing, as well as functional. Our residential sprinklers are among the most water and pressure efficient in the fire protection industry. They are available in recessed pendent, sidewall and recessed sidewall types, as well as low profile concealed and flush styles. Adequate water supply to fire sprinklers is critical for proper fire protection. The residential domestic shutoff valve, which automatically shuts off essentially all of the water flow to the domestic system when a sprinkler operates, assures that nearly the entire water supply is diverted to the fire sprinkler system. BlazeMaster CPVC pipe and fittings, along with the necessary hangers and pipe joint adhesives help make the TFP Residential Fire Protection Package the best and most complete in the industry.

Customer Service TFP residential package consists of products manufactured by TFP and distributed through local TFP locations or independent distributors that are strategically located to provide our customers with the quickest delivery possible of their complete order.

Research & Development TFP has the largest research and development staff in the fire protection industry. We combine new technologies with proven fire protection science to provide the products necessary to meet the present and future building needs. 2

TFP ResBro REVISION10

6/28/04

10:35 AM

Page 3

Table of Contents Series LFII Residential Sprinklers Series LFII Pendent . . . . . . . . . . . . . . . . . .4 Series LFII Horizontal Sidewall . . . . . . . .5 Series LFII Concealed Pendent . . . . . . . . .6 Series LFII Domed Concealed Pendent . . .6 Series LFII Flush Pendent . . . . . . . . . . . . .7 CPVC Pipe & Piping Systems CPVC Pipe & Fittings . . . . . . . . . . . . . . .8 CPVC Piping Systems . . . . . . . . . . . . . . .9 Sprinkler System Components Valves, Resi-Riser & Riser Manifold . . . .10 Waterflow Detector & Alarm Bell . . . . .11 Hangers & Installation Equipment . . . . .11 Installation Guidelines . . . . . . . . . . . . . .12 3

TFP ResBro REVISION10

6/28/04

10:36 AM

Page 4

Series LFII (TY2234) Residential Pendent Sprinklers & Series LFII (TY1334) Residential Horizontal Sidewall Sprinklers are decorative, fast response sprinklers designed for use in residential occupancies such as homes, apartments, dormitories and hotels. When aesthetics and optimized flow characteristics are the major consideration, Series LFII Residential Pendent & Horizontal Sprinklers should be the first choice. The Residential Pendent and Recessed Pendent Sprinklers are listed for special applications with beamed ceilings. The full line of LFII Sprinklers can be used for horizontal and SLOPED ceilings. Series LFII are to be used in: • Wet pipe residential sprinkler systems for one/two– family dwellings and mobile homes per NFPA 13D • Wet pipe residential occupancies up to and including four stories in height per NFPA 13R • Wet pipe sprinklers systems for the residential portions of any occupancy per NFPA 13

Series LFII (TY2234)

Residential Pendent & Recessed Pendent Sprinklers Finishes: White, Chrome or Natural Brass MAXIMUM MINIMUM FLOW (b) & COVERAGE AREA (a) RESIDUAL PRESSURE ft x ft (m x m)

For Horizontal Ceiling (Max. 2" rise for 12" run)

MINIMUM FLOW (b) & RESIDUAL PRESSURE

For Sloped Ceiling (Greater than 2" rise up to max. 4" rise for 12" run)

MINIMUM FLOW (b) & RESIDUAL PRESSURE

For Sloped Ceiling (Greater than 4" rise up to max. 8" rise for 12" run)

155°F/68°C or 175°F/79°C

155°F/88°C

175°F/79°C

155°F/88°C

175°F/79°C

12 X12 (3,7 X 3,7)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

18 GPM (68,1 LPM) 13.5 psi (0.93 bar)

14 X 14 (4,3 X 4,3)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

18 GPM (68,1 LPM) 13.5 psi (0.93 bar)

16 X 16 (4,9 X 4,9)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

13 GPM (49,2 LPM) 7.0 psi (0,48 bar)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

18 GPM (68,1 LPM) 13.5 psi (0.93 bar)

18 X 18 (5,5 X 5,5)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

23 GPM (87,1 LPM) 22.0 psi (1,52 bar)

20 X 20 (6,1 X 6,1)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

21 GPM (79,5 LPM) 18.4 psi (1,27 bar)

N/A N/A

See Technical Data Sheet: TFP400 prior to design & installation for all criteria (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.

4

TFP ResBro REVISION10

6/28/04

10:38 AM

Page 5

Series LFII (TY1334)

Residential Horizontal Sidewall & Recessed Horizontal Sidewall Sprinklers Finishes: White, Chrome, or Natural Brass MAXIMUM COVERAGE ft x ft (m x m)

MINIMUM FLOW & PRESSURE 4" – 6" (100mm – 150mm) below ceiling

6" – 12" (150mm – 300mm) below ceiling

155°F/68°C

175°F/79°C

155°F/68°C

175°F/79°C

12 x 12 (3,7 x 3,7)

12 GPM (45,4 LPM) 8.2 psi (0,57 bar)

12 GPM (45,4 LPM) 8.2 psi (0,57 bar)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

14 x 14 (4,3 X 4,3)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

16 GPM (60,6 LPM) 14.5 psi (1.00 bar)

17 GPM (64, 3 LPM) 16.4 psi (1,13 bar)

18 GPM (68, 1 LPM) 18.4 psi (1,27 bar)

16 x 16 (4,9 X 4,9)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

16 x 18 (4,9 x 5,5)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

21 GPM (79,5 LPM) 25.0 psi (1,72 bar)

21 GPM (79,5 LPM) 25.0 psi (1,72 bar)

16 x 20 (4,9 x 6,1)

23 GPM (87,1 LPM) 30.0 psi (2,07 bar)

23 GPM (87,1 LPM) 30.0 psi (2,07 bar)

26 GPM (98,4 LPM) 38.3 psi (2,64 bar)

26 GPM (98,4 LPM) 38.3 psi (2,64 bar)

See Technical Data Sheet: TFP410 prior to design & installation for all criteria

C

Series LFII (TY1334)

A B

Residential Horizontal Sidewall & Recessed Horizontal Sidewall Sprinklers

A D E

E

Sprinklers located along the slope and positioned to discharge across the slope. MAXIMUM COVERAGE

MINIMUM FLOW & PRESSURE For Sloped Ceilings max. 4" rise for 12" run

For Sloped Ceilings* max. 8" rise for 12" run

155°F/68°C • 175°F/79°C

155°F/68°C • 175°F/79°C

12 x 12 (3,7 x 3,7)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

14 x 14 (4,3 x 4,3)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 x 16 (4,9 x 4,9)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

16 x 18 (4,9 x 5,5)

22 GPM (83,3 LPM) 27.4 psi (1,89 bar)

— —

ft x ft (m x m)

See Technical Data Sheet: TFP410 prior to design & installation for all criteria * Three sprinkler design when there are more than two sprinklers in a compartment.

5

TFP ResBro REVISION10

6/28/04

10:39 AM

Page 6

The Series LFII (TY2596) Residential Concealed Pendent Sprinklers are decorative, fast response, sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels. • Can be used for horizontal and sloped ceilings • Wet pipe residential sprinkler systems for oneand two-family dwellings and mobile homes per NFPA 13D

• Wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R • Wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

Series LFII (TY2234)

Residential Domed Concealed Pendent Sprinklers Cover Plate Finishes: White Painted* or Chrome Plated MAXIMUM COVERAGE AREA (a)

MINIMUM FLOW (b) & RESIDUAL PRESSURE

ft x ft (m x m)

(Max. 2" rise for 12" run) 155°F/68°C

155°F/88°C

12 X12 (3,7 X 3,7)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

14 X 14 (4,3 X 4,3)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

16 X 16 (4,9 X 4,9)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

13 GPM (49,2 LPM) 7.0 psi (0.48 bar)

18 X 18 (5,5 X 5,5)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

17 GPM (64,3 LPM) 12.0 psi (0,83 bar)

20 X 20 (6,1 X 6,1)

20 GPM (75,7 LPM) 16.7 psi (1,15 bar)

21 GPM (79,5 LPM) 18.4 psi (1,27 bar)

For Horizontal Ceiling

MINIMUM FLOW (b) & RESIDUAL PRESSURE For Sloped Ceiling (Greater than 2" rise up to max. 4" rise for 12" run)

*Custom colors upon request. See Technical Data Sheet: TFP450 prior to design & installation (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.

Series LFII (TY2596)

Residential Concealed Pendent Sprinklers Cover Plate Finishes: White Painted* or Chrome Plated MAXIMUM COVERAGE AREA (a)

MINIMUM FLOW (b) & RESIDUAL PRESSURE

MINIMUM FLOW (b) & RESIDUAL PRESSURE For Sloped Ceiling (Greater than 2" rise up to max. 4" rise for 12" run)

MINIMUM FLOW (b) & RESIDUAL PRESSURE

ft x ft (m x m)

For Horizontal Ceiling (Max. 2" rise for 12" run)

For Sloped Ceiling (Greater than 4" rise up to max. 8" rise for 12" run)

160°F/71°C

160°F/71°C

160°F/71°C

12 x 12 (3,7 x 3,7)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

14 x 14 (4,3 x 4,3)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

16 x 16 (4,9 x 4,9)

16 GPM (60,6 LPM) 14.5 psi (1,00 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

18 x 18 (5,5 x 5,5)

20 GPM (75,7 LPM) 22.7 psi (1,57 bar)

20 GPM (75,7 LPM) 22.7 psi (1,57 bar)

N/A N/A

20 x 20 (6,1 x 6,1)

24 GPM (90,8 LPM) 32.7 psi (2,25 bar)

26 GPM (98,4 LPM) 38.3 psi (2,64 bar)

N/A N/A

*Custom colors upon request. See Technical Data Sheet: TFP440 prior to design & installation (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.

6

TFP ResBro REVISION10

6/28/04

10:40 AM

Page 7

Series LFII (TY2284) Residential Flush Pendent Sprinklers are decorative, fast response, fusible solder sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels and can be installed in beamed*, sloped and horizontal ceilings. When aesthetics is the major consideration, the Series LFII (TY2284) should be the first choice. • Residential Flush Pendent and Sprinklers approved for special applications with beamed ceilings • Used in wet pipe residential sprinkler systems for one- and twofamily dwellings and mobile homes per NFPA 13D • Wet pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R • Wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 * Pendent, recessed pendent, and flush pendent sprinklers are approved for use with beamed ceilings.

Series LFII (TY2284)

Residential Flush Pendent Sprinklers Sprinkler & Escutcheon Finishes: White and Chrome MAXIMUM COVERAGE AREA (a)

MINIMUM FLOW (b) & RESIDUAL PRESSURE

MINIMUM FLOW (b) & RESIDUAL PRESSURE

MINIMUM FLOW (b) & RESIDUAL PRESSURE

162°F/72°C

162°F/72°C

162°F/72°C

12 x 12 (3,7 x 3,7)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

17 GPM (64,3 LPM) 16.4 psi (1,13 bar)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

14 x 14 (4,3 x 4,3)

13 GPM (49,2 LPM) 9.6 psi (0,66 bar)

17 GPM (64,3 LPM) 16.4 psi (1,13 bar)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

16 x 16 (4,9 x 4,9)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

17 GPM (64,3 LPM) 16.4 psi (1,13 bar)

14 GPM (53,0 LPM) 11.1 psi (0,77 bar)

18 x 18 (5,5 x 5,5)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

19 GPM (71,9 LPM) 20.5 psi (1,41 bar)

18 GPM (68,1 LPM) 18.4 psi (1,27 bar)

20 x 20 (6,1 x 6,1)

22 GPM (83,3 LPM) 27.4 psi (1,89 bar)

24 GPM (90,8 LPM) 32.7 psi (2,25 bar)

N/A N/A

ft x ft (m x m)

For Horizontal Ceiling (Max. 2" rise for 12" run)

For Sloped Ceiling (Max. 8" rise for 12" run)

For Sloped Ceiling* (Max. 8" rise for 12" run)

See Technical Data Sheet: TFP420 prior to design & installation * Three sprinkler design when there are more than two sprinklers in a compartment. (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.

7

TFP ResBro REVISION10

6/28/04

10:42 AM

Page 8

Tyco Fire Products CPVC Pipe & Fittings manufactured with Noveon's BlazeMaster® compound are Listed by Underwriters Laboratories, Inc. for use in: • Light Hazard occupancies as defined in the Standard for Installation of Fire Sprinkler Systems, NFPA 13. • Residential occupancies as defined in the Standard for Installation of Fire Sprinkler Systems in Residential Occupancies up to Four Stories in Height, NFPA 13R. • Residential occupancies as defined in the Standard for Fire Sprinkler Systems In One and Two Family Dwellings and Manufactured Homes, NFPA 13D. • Air plenums, as defined by the installation of Air Conditioning and Ventilating Systems, NFPA 90A and model mechanical codes. • Underground Water Pressure Service, NFPA 24. • Unfinished Basements.

CPVC to Copper Fitting Tyco Fire Products make transition from one piping material to another simple. The transition to steel or BlazeMaster® CPVC Fire Sprinkler System piping from traditional copper tube for plumbing services is fast, easy, and readily available in the most complete Fire Sprinkler package in the industry.

TFP BlazeMaster® CPVC can be used with the entire LFII line in residential occupancies.

The “Back-to-Back” Fitting is included in the

(Note: for complete Listing and Approval information, please refer to the Installation Instructions and Technical Manual No. 19-1.0 or call Technical Services at 800-381-9312)

8

TFP line of BlazeMaster® CPVC products.This TEE allows two sidewall sprinklers to be piped into one fitting. This is ideal when the CPVC piping is located in a 3-1/2" (2x4) vertical wall, eliminating the need for extra nipples, fittings and sprinkler head adapters typically associated with supplying two rooms with the same pipe.The “Back-to-Back” TEE has been specially designed and dimensioned to enable the sidewall sprinklers to be recessed with 1/2" or 5/8" sheet-rock wall covering.

TFP ResBro REVISION10

6/28/04

10:43 AM

Page 9

The Tyco Fire Products CPVC Piping Systems, an extremely fast method of installing fire protection piping, is UL and cUL Listed and FM approved. The CPVC products exceed ASTM standards, and includes our 10 Year Warranty from an ISO 9001-2000 Certified Company. Benefits over traditional piping systems include: • Easily field fabricates with low tooling investment • Resistant to rust, scale and foreign contaminant build-up • Superior flow characteristics for increased hydraulic capabilities (C-Factor=150) • Easily transported, handled and modified on site • Can be easily connected to copper and steel piping • Resists sweating and condensation • Immune to microbiologically influenced corrosion (MIC)

Fire Performance • CPVC has an LOI (Limited Oxygen Index) that is better than wood, PVC, PB or other common building materials. It will not support combustion; therefore, it cannot be the source of a fire or cause a fire to spread. • Does not contribute to flashover

TFP's Revolutionary “No Block™” Hanger is a simple two-hole strap that eliminates “blocking” to the beam when hanging CPVC.The “No Block™” Hanger positions the face of the CPVC pipe 1-1/2" off the face of the joist or stud.

• Low smoke generation • Toxicity is extremely low when compared with common building and finishing materials. Equal to wood and less than wool or cotton (University of Pittsburgh protocol).

9

TFP ResBro REVISION10

6/28/04

10:44 AM

Page 10

Residential Domestic Shutoff Valve • 1" and 2" (25.4 and 50.8 mm) are used in piping systems that supply water to both the domestic service and the fire sprinkler system designed per NFPA 13D in one and two-family dwellings and mobile homes • In the set position, water is available on demand to the domestic system and the valve acts as a check valve for the fire protection system • When a sprinkler operates, the supply to the domestic system is automatically shut off • Maximum use of available water supply on demand for fire protection • Eliminates the need for expensive pumps, pressurized tanks, or electrically operated domestic shutoff valves Model F540, Residential Domestic Shutoff Valve

“Butterball” Butterfly Valves “Butterball” Butterfly valves are ideal for use in small fire sprinkler systems as sectional or main control valves. As an alternative to bulky OS&Y valves, they provide the mandated visual indicator showing that the valve is open or closed.They are available in sizes from 1" through 2-1/2".

Resi-Riser • • • •

Compact, pre-assembled, ready to install sprinkler riser Brass construction for use in potable water supply Available in 1"-2" (25-50 mm) sizes Integral test and drain assembly, flow switch with retard mechanism, 300 psi gauge, and check valve • Compact size allows for easy installation between 2" x 4" studs in wall • Molded mounting points allow for fast and easy left or right hand installation • Available with or without pressure relief valve feature and flow switch retard mechanism

Riser Manifold The Riser Manifold provides all of the accessory equipment for a system riser in a single assembly.The availability of the Riser Manifold in different configurations allows cost-effective riser installation in commercial (NFPA 13) systems, high rises requiring floor control assemblies, and residential systems (NFPA 13R/13D). 10

TFP ResBro REVISION10

6/28/04

10:45 AM

Page 11

Model VS-SP Waterflow Detector • Used with wet pipe fire sprinkler systems in residential dwellings

and mobile homes • Actuation of the switch can initiate an alarm indicating that the sprinkler system is operating • Sustained flow of 8 gallons per minute will deflect the vane and actuate a single-pole, double-throw snap action switch • Can be wired to a local bell and/or protection panel for outside notification an alarm company for fire department Model VS-SP, Residential Waterflow Detector

Alarm Bell • The Tyco Fire Electric Alarm Bell is ideally suited for residential applications • This alarm is meant to be unobtrusive to the homeowner, yet absolutely dependable in a fire event • When used with a flow switch, if water flow occurs in a sprinkler system protecting residential occupancies, an audible alarm occurs to alert the occupants and neighbors of trouble

Sprinkler Head Cabinet Spare sprinkler head cabinets are available as well as Residential 3 capacity sprinkler cabinet. All cabinets have ample room for sprinkler wrench storage.

Hangers for BlazeMaster® CPVC Products TFP offers a full-line of pipe hangers designed especially for use with CPVC Products. They meet the requirements of NFPA 13 and have been manufactured to meet the quality standards that the industry demands. • Models 22, 23, and 24 pipe hangers are designed for ease of installation • Hangers have rounded edges to prevent damage to pipe and fittings • Meets requirements specified in NFPA 13, 13R, and 13D

CPVC Installation Equipment • • • • •

Retrofit Tools Cutting and Deburring Tools BlazeMaster® Caulk & Walk® Firestop One-Step CPVC Cement and Daubers Hangers & Fasteners

11

TFP ResBro REVISION10

6/28/04

10:46 AM

Page 12

WORLDWIDE HEADQUARTERS Tyco Fire & Building Products 451 N. Cannon Avenue Lansdale, PA 19446 215-362-0700, 800-523-6512 Fax 215-362-5385 www.Tyco-Fire.com UNITED STATES Central Sprinkler Company 451 N. Cannon Avenue Lansdale, PA 19446 215-362-0700, Fax 215-362-5385 Brea, CA: Tel: 714-993-6111, Fax 714-993-6043 Decatur, GA: Tel: 404-243-7336, Fax 404-244-7375 King of Prussia, PA: Tel: 610-239-9925, Fax 610-239-9936 Jessup, MD: Tel: 301-604-7133, Fax 301-604-7138 Carol Stream, IL: Tel: 630-871-7700, Fax 630-871-7464 Coppell, TX: Tel: 972-745-0043, Fax 972-745-8594 Kent, WA: Tel: 253-872-6030, Fax 253-872-6547 Avon, MA: Tel: 508-583-8447, Fax 508-583-0034 Pompano Beach, FL: Tel: 954-781-0866, Fax 954-781-1475 Murray, UT: Tel: 801-269-0688, Fax 801-269-0733 Tigard, OR: Tel: 503-620-4203, Fax 503-620-3817 Parma, OH: Tel: 216-265-0505, Fax 216-265-8354 Kansas City, MO: Tel: 816-842-2424, Fax 816-842-4433 National Distribution Facility PO Box 2806 Lubbock, TX 79408-2806 Gem Sprinkler Company & Star Sprinkler Inc. 7071 S. 13th Street, Ste. 103 Oak Creek, WI 53154 877-436-8926, Fax 877-866-9250 CANADA Regional Headquarters 12-16715 Yonge Street, Suite 316 Newmarket, Ontario L3X 1X4 705-422-0010, Fax: 705-422-1396 LATIN AMERICA Regional Headquarters

South America, Central America & Caribbean 1802 S.W. 2nd St. Pompano Beach, FL 33069 954-781-0866, Fax 954-781-9330 Regional Headquarters - Mexico Hamburgo 231A Piso 2 Colonia Juarez Mexico, D.F. 06600 Mexico 525-55-2075766, Fax: 525-55-2077566 EUROPE & MIDDLE EAST Regional Headquarters Kopersteden 1, NL-7547 TJ Enschede P.O. Box 198, 7500 AD Enschede, The Netherlands 31-53-428-4444, Fax 31-53-428-3377 Stockport, UK: Tel: 44-161-477-1886, Fax 44-161-477-6729 Paris Nord II, France: Tel: 33-1-48-178-727, Fax 33-1-48-178-720 Rodgau Germany: Tel: 49-6106-84455, Fax 49-6106-18177 Coslada Madrid, Spain: Tel: 34-1-669-3906, Fax 34-1-669-2018 Lørenskog, Norway: Tel: 47-67-91-77-00, Fax 47-67-91-77-15 Lammhult, Sweden: Tel: 46-472-269-980, Fax 46-472-269-989 Dublin, Ireland: Tel: 353-166-839-82, Fax 353-166-822-54 Bolzano, Italy: Tel: 39-0471-252-091, Fax 39-0471-254-058 Milano, Italy: Tel: 39-0293-548-736, Fax 39-0293-548-690 Dubai, United Arab Emirates: Tel: 971-488-38689, Fax 971-488-38674 Budapest, Hungary: Tel: 36-148-11-383, Fax 36-120-34-427 Wels/Thalheim, Austria: Tel: 43-072-42-65-054, Fax 43-072-42-74-393 ASIA Regional Headquarters No.45 Tuas Avenue 9, Singapore 639189 Central Sprinkler Company Singapore: 65- 6743-3212, Fax 65-6743-9181 Shanghai, China: 86-21-5868-3300, Fax 86-21-5868-1160 Beijing, China: 86-10-6515-6191, Fax 86-10-6515-6157 Chengdu, China: 86-28-689-9440, Fax 86-28-666-2538 Gem Sprinkler Company & Star Sprinkler Inc. Singapore: 65-6861-1655, Fax 65-6861-1312 Kuala Lumpur, Malaysia: 60-3-8024-6773, Fax 60-3-8024-2180 Hong Kong: 852-2595-0686, Fax 852-2505-5826

B

C A

Recognizing that residential sprinklers are being installed in many areas where conditions are not as described specifically in the code standards, TFP has generated a Residential Sprinkler Design Guide to help the fire sprinkler designer and installer correctly apply the sprinkler spacing and hydraulic calculations. This design guide covers many topics including spacing in sloped ceiling conditions, obstructions to the sprinkler pattern, location of sprinklers in odd shaped rooms or near heat sources, and much, much more. This Design Guide can be obtained by contacting any Tyco Fire Products Representative, or at our website at

D

BlazeMaster is a registered trademark of Noveon IP Holding Corp. Caulk & Walk, No Block and Tyco are either registered trademarks or trademarks of Tyco and/or its affiliates in the United States and/or other countries. All other brand names, product names, or trademarks belong to their respective owners.

© 2004 Tyco Fire Products LP. / All rights reserved. / Printed USA / TFP-Res / 4M / CPI / 07-04