MULTI-TOWER INTERCONNECTION MODBUS-RTU/CRS-ASCII NETWORK CONTROL The control master box for Modbus-RTU/CRS-ASCII network control of multi-tower machines is an electronic device needed when the following control types are required: A. Manual control through the operator control panel of the control master box. B. Automatic control through a host PC/PLC system offering Modbus-RTU or CRS-ASCII The control master box can be placed up to 5m away from the towers. If network control through Profibus-DP or DeviceNet protocol is required see our Multi-tower interconnection - Profibus-DP/DeviceNet network control product sheet. If Manual or PLC control is required see our Multi-tower interconnection – Manual/PLC control product sheet. INCLUDED: A plastic case An operator control panel which includes: - 8 keys - 8 LED indicators - 1 line by 16 characters display

Technical Specifications Supply voltage Power consumption

24Vdc 0.75A max

WAVEFORM PROGRAMMING Binary or keyboard selection COMMUNICATION PORTS Number Type 1 Type 2

2 N.01 RS232 + N.01 RS485 N.02 RS485

Mechanical Dimensions (mm) FRONT VIEW

SIDE VIEW

228

120

Standard Control Master Boxes REM311

• Protocol: Modbus-RTU • Weight: 2.5kg

REM312

• Protocol: CRS-ASCII • Weight: 2.5kg

LINE CHECK THERM

ON

305

Modify

Automatic

OFF

Manual

Menu

Select

Volt

Ampere

Software Available Software

Comm. Protocols CRS- ASCII ModbusRTU

Description

Machine Types DC

DCR

R30MBASC

Standard software for remote control of DC machines through a RS485 network serial port with CRS-ASCII protocol.

R30MBMOD

Standard software for remote control of DC machines through a RS485 network serial port with Modbus-RTU protocol.

CRS_Q500_MT_MB-ASCII_ENG_20120116

www.crspower.com | [email protected] | Tel. + 39 039 928.5507 | Fax +39 039 598.3566

2| 5

MULTI-TOWER INTERCONNECTION MODBUS-RTU/CRS-ASCII NETWORK CONTROL Connection Tables CN1 Internal connector - input 1

Power input: 24Vdc (0.75A max)

CN2 Internal connector - rectifier's output power bars 1 2 3

(+) Voltage input from rectifier's output power bars USED BY CRS (-) Voltage input from rectifier's output power bars

CN3 Internal connector - analogue inputs/outputs 1 2 3 4

(+) RS485 input (-) RS485 input (+) PC/PLC output (-) PC/PLC output

CN4 Internal connector - digital inputs from PLC or external contacts 1-2 3 4 5-6-7 8 - 14 15 16 17 18 19 20 21

USED BY CRS Power output for potentiometer (+10V) ADC0 (+) 0 - 10V potentiometer cursor input Analogue common (0V) - Power output for potentiometer USED BY CRS Digital input 0 Digital input 1 Digital input 2 Digital input 3 Digital input 4 Digital input 5 Digital common (+5V)

CN5 Internal connector - male 25 pin Sub-D 2 3 7 9 11

RS232 RX RS232 TX RS232 GND RS485 A(+) RS485 B( - )

CN6 Internal connector - digital outputs from relay contacts 1-2 3-4 5-6 7-8 9 - 10 11 - 12 13 - 14 15 - 16

Digital output 0 Digital output 1 Digital output 2 Digital output 3 Digital output 4 Digital output 5 Digital output 6 Digital output 7

NOTE: Contact max. rating 48Vac/0.1A with resistive load.

CN7 External connector - male 25 pin Sub-D 2 3 7 9 11

RS232 RX RS232 TX RS232 GND RS485 A(+) RS485 B( - )

CRS_Q500_MT_MB-ASCII_ENG_20120116

www.crspower.com | [email protected] | Tel. + 39 039 928.5507 | Fax +39 039 598.3566

RS422/RS485

(+) 24 Vdc (-)

RS232/CMOS-RS422/RS485

CONVERTER*

RS232/CMOS

Non ferromagnetic material pipe

Detail A

Electrical Connections

25

22 24

14

13

7

1 2 3

Rectifier CPU card

RS485

CN5 connector

CN6 connector

Cable I

RS485

A

Cable I

RS485

14

Select

B

Manual

Automatic

OFF Menu

Modify

ON

Ampere

Volt

THERM

CHECK

LINE

REMxxx

1

PE

+ -

2

25

9 11 13

REM - CN7 external connector Male 25 pin Sub-D

Detail B

www.crspower.com | [email protected] | Tel. + 39 039 928.5507 | Fax +39 039 598.3566

CRS_Q500_MT_MB_ASCII_ENG_20120116

1

TX+

RS485 (+)

TX–

RS485 (–)

3

1

Pin

Cable II

Voltage Input (+) Voltage Input (–)

+ -

2 RS485 host (–)

1 RS485 host (+)

To/From Modbus-RTU or CRS-ASCII Network

* See Converter Details paraghraph for further information

Cable I (Detail A and B) - SHIELDED TWISTED PAIR CABLE (STP) - Type: Brand BELDEN 3105A or equivalent - 22 AWG stranded tinned copper - Temperature range: from −20oC to +60oC - Max. length from REMxxx to converter: 5m - Max. length between converters of towers: 5m - All shields must be connected together 1 - One point of the shield must be connected to PE (Protective Earth) on the REMxxx side only 2 Cable II - Max length from REMxxx to the output power bars of - Min. Ø 0.25mm2 - Temperature range: from -10oC to +55oC

Max. number of towers: 4

From Q500 rectifier's output power bars

REM - CN2 internal connector

2

Power input: 24Vdc (0.75A max)

Pin

Pin

1

REM - CN3 internal connector

REM - CN1 internal connector

MULTI-TOWER INTERCONNECTION MODBUS-RTU/CRS-ASCII NETWORK CONTROL

3| 5

4| 5

MULTI-TOWER INTERCONNECTION MODBUS-RTU/CRS-ASCII NETWORK CONTROL Internal Connections Control Master Box REM311 / REM312

21

17

2

CN4 connector (21 pin)

10

6

4 (+)

5 (-)

2

3

CN5 connector (Male 25 pin Sub-D) 7

2

3

9

9 11

Loc/Rem switch

1 0V

6 +24V

Cabur CWAA 7-0530 Art. X756530 0÷10Vdc/0÷10Vdc Isolating Amplifier

3(+)

RS232 port

Converter RS232/RS485 SYS-SCU02-OEEI

2(-)

+ Power input gnd

100nF

RS485 port (S+) (S-)

R1

1 2 3 + -

1 2 + CN1

Power input: 24Vdc

R2

CN2

Voltage input from rectifier’s output power bars

1 2 3 4 + - + CN3

7 CN7

RS485 input from PC/PLC

RS485 output to PC/PLC

9 11

(Male 25 pin Sub-D)

RS485 to/from rectifier

CRS_Q500_MT_MB-ASCII_ENG_20120116

www.crspower.com | [email protected] | Tel. + 39 039 928.5507 | Fax +39 039 598.3566

5| 5

MULTI-TOWER INTERCONNECTION MODBUS-RTU/CRS-ASCII NETWORK CONTROL Configuration Parameters The control master box configuration parameters are stored in a CONFIGURATION MENU, which is accessible by the following operations: - Press OFF key to turn off the control master box and disconnect the RS485 serial cable. - Press OFF key again to turn on the remote control and hold it down for a few seconds until message 'DEBUG!!!' appears on the display. - Press the OFF key again and hold it down for a few seconds until 'CONFIGURATION' message appears on the display. - Press MANUAL/SELECT key to access inside the configuration menu; the first parameter will be displayed with its actual value. - Use keys to scroll up and down the parameter list. Modification of a parameter value - To modify a particular parameter value, choose the desired parameter and press MANUAL/SELECT key. At this point, the MODIFY modality will be activated and the parameter value will appear between the symbols . - Press the keys to increase/decrease the value of the chosen parameter. - Press ON/MODIFY key to accept the modification of the parameter value; symbols will disappear around the modified parameter value. - Press OFF/MENU key to exit configuration menu and to save all parameter values on a static memory. - After visualizing or modifying the configuration parameters, turn off and then turn on the control master box by pressing the OFF key in order to activate all parameter values and then connect back the RS485 serial cable.

Converter Details CRS uses two different brands of converters for multi-tower interconnection, each one requiring its particular switch settings. Please refer to the below pictures to identify the converter installed and verify its corresponding settings.

Brand: Omron Model: SYS-SCU02-OEEI

Brand: Renu Electronics Pvt. Ltd. Model: CNV-02-B

Switch Settings: Position ON Switch #

1

RS485(+) RS485(–)

Switch Settings: ON 2

ON 3

OFF 4

NOT USED

Position ON Switch #

1

RS485(+) RS485(–)

CRS_Q500_MT_MB-ASCII_ENG_20120116

www.crspower.com | [email protected] | Tel. + 39 039 928.5507 | Fax +39 039 598.3566

ON 2

OFF OFF 3 4

NOT USED