Florida Building Code, Fifth Edition (2014) - Energy Conservation EnergyGauge Summit® Fla/Com-2015, Effective Date: June 30, 2015 -- Form 506-2014 ASHRAE 90.1-2010 - Energy Cost Budget Option
Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: This Checklist An Input report generated from the software just after completing compliance calculations without any further changes The full compliance report generated by the software that contains the project summary, complaince summary, certifications and detailed component compliance reports Boxes appropriately checked in the Miscellanous report generated by the software at the end of the compliance report
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 1 of 8
PROJECT SUMMARY
Short Desc: TAM A3
Description:
TAM Building A3
Owner: Enter Owner's name here Address1: Enter Address here
City:
Enter city here
Address2: Enter Address here
State:
Enter state here
Zip: Type: Office
Class:
0 New Finished building
Jurisdiction: MIAMI, MIAMI-DADE COUNTY, FL (232400) Conditioned Area: 67500 SF
Conditioned & UnConditioned Area:
No of Stories: 3
Area entered from Plans
Permit No: 0
Max Tonnage If different, write in:
135000 SF 67500 SF 92 ______________________
Compliance Summary Component
Design
Gross Energy Cost (in $)
83,096.0
Criteria 92,220.0
Result PASSED
LIGHTING CONTROLS
PASSES
EXTERNAL LIGHTING
PASSES
HVAC SYSTEM
FAILS
PLANT
PASSES
WATER HEATING SYSTEMS
PASSES
PIPING SYSTEMS
No Entry
Met all required compliance from Check List?
Yes/No/NA
IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 2 of 8
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: __________________
Building Official: __________________
Date: _________________
Date: __________________
I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: __________________
Date: __________________
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Code Architect: __________________
Reg No: __________________
Electrical Designer: __________________
Reg No: __________________
Lighting Designer: __________________
Reg No: __________________
Mechanical Designer: __________________
Reg No: __________________
Plumbing Designer: __________________
Reg No: __________________
(*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 3 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Building End Uses
Total
ELECTRICITY(MBtu/kWh/$)
AREA LIGHTS
MISC EQUIPMT
PUMPS & MISC
SPACE COOL
SPACE HEAT
VENT FANS
NATURAL-GAS(MBtu/therm/$)
SPACE HEAT
1) Proposed
2) Baseline
5,410.80
5,949.80
$83,096
$92,220
5,352.40 1568261
5,949.70 1743272
$82,804
$92,219
1,058.30 310073
1,270.00 372096
$16,372
$19,684
2,025.20 593376
2,025.20 593376
$31,330
$31,390
0.30 95
0.00 5
$5
$0
1,524.80 446769
2,002.60 586774
$23,589
$31,040
2.00 589
0.00 2
$31
$0
741.80 217359
651.90 191019
$11,477
$10,105
58.40 584
0.10 1
$292
$1
58.40 584
0.10 1
$292
$1
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 4 of 8
Credits Applied: None Passing Criteria = 92220 Design (including any credits) = 83096 Passing requires Proposed Building cost to be at most 100% of Baseline cost. This Proposed Building is at 90.1%
PASSES
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
External Lighting Compliance Description
Category
Tradable?
Ext Light 1
Walk way less than 10 feet wide
Allowance (W/Unit)
Yes
1.00
Area or Length ELPA or No. of Units (W) (Sqft or ft)
150.0
CLP (W)
150
96
PASSES
Tradable Surfaces: 96 (W) Allowance for Tradable: 157.5 (W) All External Lighting: 96 (W) Complicance check includes a excess/Base allowance of 7.50(W) Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Lighting Controls Compliance Acronym
Pr0Zo1Sp1 Pr0Zo2Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo6Sp1 Pr0Zo7Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1 Pr0Zo13Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1
Ashrae ID
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Description
Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan
Area (sq.ft)
14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500
Design CP
Min CP
2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3
2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3
Compliance PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES
PASSES
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 5 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
System Report Compliance Pr0Sy1
Component
Cooling System
Heating System Air Handling System -Supply
Pr0Sy2
Component
Cooling System
Heating System Air Handling System -Supply
Pr0Sy3
Component
Cooling System
Heating System Air Handling System -Supply
System 1
Category
Air Conditioners Air Cooled > 760000 Btu/h Cooling Capacity Warm Air Gas Furnace >= 225000 Btu/h Air Handler (Supply) Variable Volume
Variable Air Volume Packaged System--903 Capacity
Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume
Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume
Design IPLV
12.90
IPLV Criteria
Compliance
12.80
9.50
499500
80.00
80.00
PASSES
30834
1.25
1.12
FAILS
9.60
Capacity
Design Eff
Eff Criteria
Design IPLV
12.90
PASSES
No. of Units
Variable Air Volume Packaged System--903
1 IPLV Criteria
Compliance
457541
12.80
9.80
137430
80.00
80.00
PASSES
8484
1.25
1.12
FAILS
System 3
Category
Eff Criteria
1
1104049
System 2
Category
Design Eff
No. of Units
9.90
No. of Units
Variable Air Volume Packaged System--903 Capacity
Design Eff
Eff Criteria
Design IPLV
8.00
PASSES
1 IPLV Criteria
Compliance
470133
12.80
9.80
9.90
137430
80.00
80.00
PASSES
8484
1.25
1.12
FAILS
FAILS
FAILS
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 6 of 8
Plant Compliance Description
Installed No
Hot Water Boiler (Fuel)
1
Size
Design Eff
Min Eff
1
80.000
80.000
Design IPLV
Min IPLV
Category
Comp liance
Gas Fired >=300,000 and < 2,500,000 Btu/h
PASSES
PASSES
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Water Heater Compliance Description
Water Heater 1
Design Eff
Type
Category
Gas Storage water heater
= 20 Gal
0.58
Min Eff
Design Loss
Max Loss
Comp liance
0.52
PASSES
PASSES
Piping System Compliance Category
Pipe Dia [inches]
Is Runout?
Operating Ins Cond Temp [Btu-in/hr [F] .SF.F]
Ins Thick [in]
Req Ins Compliance Thick [in]
None
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 7 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Other Required Compliance Category
Section
Requirement (write N/A in box if not applicable)
Check
Project: TAM A3
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 8 of 8
Florida Building Code, Fifth Edition (2014) - Energy Conservation EnergyGauge Summit® Fla/Com-2015, Effective Date: June 30, 2015 -- Form 506-2014 IECC 2012 - Total Building Performance Compliance Option
Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: This Checklist An Input report generated from the software just after completing compliance calculations without any further changes The full compliance report generated by the software that contains the project summary, complaince summary, certifications and detailed component compliance reports Boxes appropriately checked in the Miscellanous report generated by the software at the end of the compliance report
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 1 of 8
PROJECT SUMMARY
Short Desc: TAM A3
Description:
TAM Building A3
Owner: Enter Owner's name here Address1: Enter Address here
City:
Enter city here
Address2: Enter Address here
State:
Enter state here
Zip: Type: Office
Class:
0 New Finished building
Jurisdiction: MIAMI, MIAMI-DADE COUNTY, FL (232400) Conditioned Area: 67500 SF
Conditioned & UnConditioned Area:
No of Stories: 3
Area entered from Plans
Permit No: 0
Max Tonnage If different, write in:
135000 SF 67500 SF 92 ______________________
Compliance Summary Component
Design
Gross Energy Cost (in $)
82,902.0
Criteria 79,058.0
Result FAILED
LIGHTING CONTROLS
PASSES
EXTERNAL LIGHTING
PASSES
HVAC SYSTEM
FAILS
PLANT
PASSES
WATER HEATING SYSTEMS
PASSES
PIPING SYSTEMS
No Entry
Met all required compliance from Check List?
Yes/No/NA
IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 2 of 8
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: __________________
Building Official: __________________
Date: _________________
Date: __________________
I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: __________________
Date: __________________
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Code Architect: __________________
Reg No: __________________
Electrical Designer: __________________
Reg No: __________________
Lighting Designer: __________________
Reg No: __________________
Mechanical Designer: __________________
Reg No: __________________
Plumbing Designer: __________________
Reg No: __________________
(*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 3 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Building End Uses
Total
ELECTRICITY(MBtu/kWh/$)
AREA LIGHTS
MISC EQUIPMT
PUMPS & MISC
SPACE COOL
SPACE HEAT
VENT FANS
NATURAL-GAS(MBtu/therm/$)
SPACE HEAT
1) Proposed
2) Baseline
5,398.20
6,000.80
$82,902
$93,009
5,339.80 1564576
6,000.80 1758204
$82,610
$93,009
1,058.30 310073
1,270.00 372096
$16,372
$19,684
2,025.20 593376
2,025.20 593376
$31,330
$31,390
0.30 95
0.00 4
$5
$0
1,512.90 443286
2,064.20 604799
$23,406
$31,994
2.00 590
0.00 0
$31
$0
741.10 217156
641.40 187929
$11,466
$9,941
58.40 584
0
$292
$0
58.40 584
0.00 0
$292
$0
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 4 of 8
Credits Applied: None Passing Criteria = 79058 Design (including any credits) = 82902 Passing requires Proposed Building cost to be at most 85% of Baseline cost. This Proposed Building is at 89.1%
FAILS
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
External Lighting Compliance Description
Category
Tradable?
Ext Light 1
Walk way less than 10 feet wide
Allowance (W/Unit)
Yes
1.00
Area or Length ELPA or No. of Units (W) (Sqft or ft)
150.0
CLP (W)
150
96
PASSES
Tradable Surfaces: 96 (W) Allowance for Tradable: 157.5 (W) All External Lighting: 96 (W) Complicance check includes a excess/Base allowance of 7.50(W) Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Lighting Controls Compliance Acronym
Pr0Zo1Sp1 Pr0Zo2Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo6Sp1 Pr0Zo7Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1 Pr0Zo13Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1
Ashrae ID
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Description
Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan
Area (sq.ft)
14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500
Design CP
Min CP
2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3
2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3
Compliance PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES
PASSES
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 5 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
System Report Compliance Pr0Sy1
Component
Cooling System
Heating System Air Handling System -Supply
Pr0Sy2
Component
Cooling System
Heating System Air Handling System -Supply
Pr0Sy3
Component
Cooling System
Heating System Air Handling System -Supply
System 1
Category
Air Conditioners Air Cooled > 760000 Btu/h Cooling Capacity Warm Air Gas Furnace >= 225000 Btu/h Air Handler (Supply) Variable Volume
Variable Air Volume Packaged System--903 Capacity
Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume
Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume
Design IPLV
12.90
IPLV Criteria
Compliance
12.80
9.70
499500
80.00
80.00
PASSES
30834
1.25
1.12
FAILS
9.80
Capacity
Design Eff
PASSES
No. of Units
Variable Air Volume Packaged System--903
1
Eff Criteria
Design IPLV
IPLV Criteria
12.90
10.10
Compliance
457541
12.80
10.00
137430
80.00
80.00
PASSES
8484
1.25
1.12
FAILS
System 3
Category
Eff Criteria
1
1104049
System 2
Category
Design Eff
No. of Units
No. of Units
Variable Air Volume Packaged System--903 Capacity
Design Eff
PASSES
1
Eff Criteria
Design IPLV
IPLV Criteria
8.00
10.10
Compliance
470133
12.80
10.00
137430
80.00
80.00
PASSES
8484
1.25
1.12
FAILS
FAILS
FAILS
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 6 of 8
Plant Compliance Description
Installed No
Hot Water Boiler (Fuel)
1
Size
Design Eff
Min Eff
1
80.000
80.000
Design IPLV
Min IPLV
Category
Comp liance
Gas Fired >=300,000 and < 2,500,000 Btu/h
PASSES
PASSES
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Water Heater Compliance Description
Water Heater 1
Design Eff
Type
Category
Gas Storage water heater
= 20 Gal
0.58
Min Eff
Design Loss
Max Loss
Comp liance
0.52
PASSES
PASSES
Piping System Compliance Category
Pipe Dia [inches]
Is Runout?
Operating Ins Cond Temp [Btu-in/hr [F] .SF.F]
Ins Thick [in]
Req Ins Compliance Thick [in]
None
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 7 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)
Other Required Compliance Category
Section
Requirement (write N/A in box if not applicable)
Check
Project: TAM A3
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 8 of 8
DOE Based Sizing
PROJECT SUMMARY
Short Desc: TAM A3
Description:
TAM Building A3
Owner: Enter Owner's name here Address1: Enter Address here
City:
Enter city here
Address2: Enter Address here
State:
Enter state here
Zip: Type: Office
Class:
0 New Finished building
Weather File: FL_MIAMI_INTL_AP.tm3 Conditioned Area: 67500 SF No of Stories: 3
Conditioned & UnConditioned Area: Area entered from Plans
Permit No: 0
Max Tonnage If different, write in:
135000 SF 67500 SF 92 ______________________
EnergyGauge Summit® v5.10
6/1/2015
Page 1 of 3
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance as required by the authority of jurisdiction Prepared By: __________________
Building Official: __________________
Date: _________________
Date: __________________
I certify that this building is in compliance as required by the authority of jurisdiction Owner Agent: __________________
Date: __________________
If required by law, I hereby certify (*) that the system design is in compliance as required by the authority of jurisdiction Architect: __________________
Reg No: __________________
Electrical Designer: __________________
Reg No: __________________
Lighting Designer: __________________
Reg No: __________________
Mechanical Designer: __________________
Reg No: __________________
Plumbing Designer: __________________
Reg No: __________________
(*) Signature may be required when law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.
EnergyGauge Summit® v5.10
6/1/2015
Page 2 of 3
DOE 2.1 E Based Sized Parameters (Beta Feature) IdSystem
1
System Name
System Type
System 1
Pr0Sy1
Sized Value
Component Cooling System Heating System Air Handling System -Supply 2
Sized Value
Cooling System Heating System Air Handling System -Supply
457541 137430 8484
Units BTU/HR Btu/h CFM
System 3
Pr0Sy3
Sized Value
Component Cooling System Heating System Air Handling System -Supply 10
BTU/HR Btu/h CFM
System 2
Pr0Sy2
Component
3
1104049 499500 30834
Units
470133 137430 8484
Units BTU/HR Btu/h CFM
Hot Water Boiler (Fuel)
Hot Water Boiler (Fuel)
Sized Value
Component Hot Water Boiler (Fuel)
0.553
Units [Million Btu/h]
EnergyGauge Summit® v5.10
6/1/2015
Page 3 of 3
Florida Building Code, Fifth Edition (2014) - Energy Conservation EnergyGauge Summit® Fla/Com-2015, Effective Date: June 30, 2015 -- Form 506-2014 ASHRAE 90.1-2010 - Energy Cost Budget Option
Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: This Checklist An Input report generated from the software just after completing compliance calculations without any further changes The full compliance report generated by the software that contains the project summary, complaince summary, certifications and detailed component compliance reports Boxes appropriately checked in the Miscellanous report generated by the software at the end of the compliance report
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 1 of 8
PROJECT SUMMARY
Short Desc: TAM A3
Description:
TAM Building A3
Owner: Enter Owner's name here Address1: Enter Address here
City:
Enter city here
Address2: Enter Address here
State:
Enter state here
Zip: Type: Office
Class:
0 New Finished building
Jurisdiction: ORLANDO, ORANGE COUNTY, FL (582100) Conditioned Area: 67500 SF
Conditioned & UnConditioned Area:
No of Stories: 3
Area entered from Plans
Permit No: 0
Max Tonnage If different, write in:
135000 SF 67500 SF 97.6 ______________________
Compliance Summary Component
Design
Gross Energy Cost (in $)
79,928.0
Criteria 88,564.0
Result PASSED
LIGHTING CONTROLS
PASSES
EXTERNAL LIGHTING
PASSES
HVAC SYSTEM
FAILS
PLANT
FAILS
WATER HEATING SYSTEMS
PASSES
PIPING SYSTEMS
No Entry
Met all required compliance from Check List?
Yes/No/NA
IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 2 of 8
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: __________________
Building Official: __________________
Date: _________________
Date: __________________
I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: __________________
Date: __________________
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Code Architect: __________________
Reg No: __________________
Electrical Designer: __________________
Reg No: __________________
Lighting Designer: __________________
Reg No: __________________
Mechanical Designer: __________________
Reg No: __________________
Plumbing Designer: __________________
Reg No: __________________
(*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 3 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)
Building End Uses
Total
ELECTRICITY(MBtu/kWh/$)
AREA LIGHTS
MISC EQUIPMT
PUMPS & MISC
SPACE COOL
SPACE HEAT
VENT FANS
NATURAL-GAS(MBtu/therm/$)
SPACE HEAT
1) Proposed
2) Baseline
5,314.50
5,719.50
$79,928
$88,564
5,095.90 1493095
5,711.40 1673414
$78,835
$88,524
1,058.30 310073
1,270.00 372096
$16,372
$19,684
2,025.20 593376
2,025.20 593376
$31,330
$31,390
2.00 595
0.30 76
$31
$4
1,315.10 385323
1,792.70 525268
$20,345
$27,787
10.60 3116
0.40 132
$165
$7
684.70 200612
622.80 182466
$10,592
$9,652
218.60 2186
8.10 81
$1,093
$41
218.60 2186
8.10 81
$1,093
$41
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 4 of 8
Credits Applied: None Passing Criteria = 88564 Design (including any credits) = 79928 Passing requires Proposed Building cost to be at most 100% of Baseline cost. This Proposed Building is at 90.2%
PASSES
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)
External Lighting Compliance Description
Category
Tradable?
Ext Light 1
Walk way less than 10 feet wide
Allowance (W/Unit)
Yes
1.00
Area or Length ELPA or No. of Units (W) (Sqft or ft)
150.0
CLP (W)
150
96
PASSES
Tradable Surfaces: 96 (W) Allowance for Tradable: 157.5 (W) All External Lighting: 96 (W) Complicance check includes a excess/Base allowance of 7.50(W) Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)
Lighting Controls Compliance Acronym
Pr0Zo1Sp1 Pr0Zo2Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo6Sp1 Pr0Zo7Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1 Pr0Zo13Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1
Ashrae ID
16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Description
Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan
Area (sq.ft)
14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500
Design CP
Min CP
2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3
2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3
Compliance PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES
PASSES
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 5 of 8
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)
System Report Compliance Pr0Sy1
Component
Cooling System
Heating System Air Handling System -Supply
Pr0Sy2
Component
Cooling System
Heating System Air Handling System -Supply
Pr0Sy3
Component
Cooling System
Heating System Air Handling System -Supply
System 1
Category
Air Conditioners Air Cooled > 760000 Btu/h Cooling Capacity Warm Air Gas Furnace >= 225000 Btu/h Air Handler (Supply) Variable Volume
Variable Air Volume Packaged System--903 Capacity
Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume
Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume
Design IPLV
12.90
IPLV Criteria
Compliance
12.80
9.50
541200
80.00
80.00
PASSES
33408
1.25
1.12
FAILS
9.60
Capacity
Design Eff
Eff Criteria
Design IPLV
12.90
PASSES
No. of Units
Variable Air Volume Packaged System--903
1 IPLV Criteria
Compliance
451805
12.80
9.80
136880
80.00
80.00
PASSES
8449
1.25
1.12
FAILS
System 3
Category
Eff Criteria
1
1171205
System 2
Category
Design Eff
No. of Units
9.90
No. of Units
Variable Air Volume Packaged System--903 Capacity
Design Eff
Eff Criteria
Design IPLV
12.90
PASSES
1 IPLV Criteria
Compliance
463985
12.80
9.80
9.90
136880
80.00
80.00
PASSES
8449
1.25
1.12
FAILS
PASSES
FAILS
EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015
6/1/2015
Page 6 of 8
Plant Compliance Description
Installed No
Hot Water Boiler (Fuel)
1
Size
Design Eff
Min Eff
1
80.000
82.000
Design IPLV
Min IPLV
Category
Comp liance
Oil Fired >=300,000 and < 2,500,000 Btu/h
FAILS
FAILS
Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)
Water Heater Compliance Description
Water Heater 1
Design Eff
Type
Category
Gas Storage water heater
>75000 &