Check List. Florida Building Code, Fifth Edition (2014) - Energy Conservation

Florida Building Code, Fifth Edition (2014) - Energy Conservation EnergyGauge Summit® Fla/Com-2015, Effective Date: June 30, 2015 -- Form 506-2014 ASH...
Author: Raymond Rice
1 downloads 0 Views 620KB Size
Florida Building Code, Fifth Edition (2014) - Energy Conservation EnergyGauge Summit® Fla/Com-2015, Effective Date: June 30, 2015 -- Form 506-2014 ASHRAE 90.1-2010 - Energy Cost Budget Option

Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: This Checklist An Input report generated from the software just after completing compliance calculations without any further changes The full compliance report generated by the software that contains the project summary, complaince summary, certifications and detailed component compliance reports Boxes appropriately checked in the Miscellanous report generated by the software at the end of the compliance report

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 1 of 8

PROJECT SUMMARY

Short Desc: TAM A3

Description:

TAM Building A3

Owner: Enter Owner's name here Address1: Enter Address here

City:

Enter city here

Address2: Enter Address here

State:

Enter state here

Zip: Type: Office

Class:

0 New Finished building

Jurisdiction: MIAMI, MIAMI-DADE COUNTY, FL (232400) Conditioned Area: 67500 SF

Conditioned & UnConditioned Area:

No of Stories: 3

Area entered from Plans

Permit No: 0

Max Tonnage If different, write in:

135000 SF 67500 SF 92 ______________________

Compliance Summary Component

Design

Gross Energy Cost (in $)

83,096.0

Criteria 92,220.0

Result PASSED

LIGHTING CONTROLS

PASSES

EXTERNAL LIGHTING

PASSES

HVAC SYSTEM

FAILS

PLANT

PASSES

WATER HEATING SYSTEMS

PASSES

PIPING SYSTEMS

No Entry

Met all required compliance from Check List?

Yes/No/NA

IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 2 of 8

CERTIFICATIONS

I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: __________________

Building Official: __________________

Date: _________________

Date: __________________

I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: __________________

Date: __________________

If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Code Architect: __________________

Reg No: __________________

Electrical Designer: __________________

Reg No: __________________

Lighting Designer: __________________

Reg No: __________________

Mechanical Designer: __________________

Reg No: __________________

Plumbing Designer: __________________

Reg No: __________________

(*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 3 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Building End Uses

Total

ELECTRICITY(MBtu/kWh/$)

AREA LIGHTS

MISC EQUIPMT

PUMPS & MISC

SPACE COOL

SPACE HEAT

VENT FANS

NATURAL-GAS(MBtu/therm/$)

SPACE HEAT

1) Proposed

2) Baseline

5,410.80

5,949.80

$83,096

$92,220

5,352.40 1568261

5,949.70 1743272

$82,804

$92,219

1,058.30 310073

1,270.00 372096

$16,372

$19,684

2,025.20 593376

2,025.20 593376

$31,330

$31,390

0.30 95

0.00 5

$5

$0

1,524.80 446769

2,002.60 586774

$23,589

$31,040

2.00 589

0.00 2

$31

$0

741.80 217359

651.90 191019

$11,477

$10,105

58.40 584

0.10 1

$292

$1

58.40 584

0.10 1

$292

$1

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 4 of 8

Credits Applied: None Passing Criteria = 92220 Design (including any credits) = 83096 Passing requires Proposed Building cost to be at most 100% of Baseline cost. This Proposed Building is at 90.1%

PASSES

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

External Lighting Compliance Description

Category

Tradable?

Ext Light 1

Walk way less than 10 feet wide

Allowance (W/Unit)

Yes

1.00

Area or Length ELPA or No. of Units (W) (Sqft or ft)

150.0

CLP (W)

150

96

PASSES

Tradable Surfaces: 96 (W) Allowance for Tradable: 157.5 (W) All External Lighting: 96 (W) Complicance check includes a excess/Base allowance of 7.50(W) Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Lighting Controls Compliance Acronym

Pr0Zo1Sp1 Pr0Zo2Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo6Sp1 Pr0Zo7Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1 Pr0Zo13Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1

Ashrae ID

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Description

Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan

Area (sq.ft)

14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500

Design CP

Min CP

2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3

2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3

Compliance PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES

PASSES

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 5 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

System Report Compliance Pr0Sy1

Component

Cooling System

Heating System Air Handling System -Supply

Pr0Sy2

Component

Cooling System

Heating System Air Handling System -Supply

Pr0Sy3

Component

Cooling System

Heating System Air Handling System -Supply

System 1

Category

Air Conditioners Air Cooled > 760000 Btu/h Cooling Capacity Warm Air Gas Furnace >= 225000 Btu/h Air Handler (Supply) Variable Volume

Variable Air Volume Packaged System--903 Capacity

Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume

Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume

Design IPLV

12.90

IPLV Criteria

Compliance

12.80

9.50

499500

80.00

80.00

PASSES

30834

1.25

1.12

FAILS

9.60

Capacity

Design Eff

Eff Criteria

Design IPLV

12.90

PASSES

No. of Units

Variable Air Volume Packaged System--903

1 IPLV Criteria

Compliance

457541

12.80

9.80

137430

80.00

80.00

PASSES

8484

1.25

1.12

FAILS

System 3

Category

Eff Criteria

1

1104049

System 2

Category

Design Eff

No. of Units

9.90

No. of Units

Variable Air Volume Packaged System--903 Capacity

Design Eff

Eff Criteria

Design IPLV

8.00

PASSES

1 IPLV Criteria

Compliance

470133

12.80

9.80

9.90

137430

80.00

80.00

PASSES

8484

1.25

1.12

FAILS

FAILS

FAILS

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 6 of 8

Plant Compliance Description

Installed No

Hot Water Boiler (Fuel)

1

Size

Design Eff

Min Eff

1

80.000

80.000

Design IPLV

Min IPLV

Category

Comp liance

Gas Fired >=300,000 and < 2,500,000 Btu/h

PASSES

PASSES

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Water Heater Compliance Description

Water Heater 1

Design Eff

Type

Category

Gas Storage water heater

= 20 Gal

0.58

Min Eff

Design Loss

Max Loss

Comp liance

0.52

PASSES

PASSES

Piping System Compliance Category

Pipe Dia [inches]

Is Runout?

Operating Ins Cond Temp [Btu-in/hr [F] .SF.F]

Ins Thick [in]

Req Ins Compliance Thick [in]

None

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 7 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Other Required Compliance Category

Section

Requirement (write N/A in box if not applicable)

Check

Project: TAM A3

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 8 of 8

Florida Building Code, Fifth Edition (2014) - Energy Conservation EnergyGauge Summit® Fla/Com-2015, Effective Date: June 30, 2015 -- Form 506-2014 IECC 2012 - Total Building Performance Compliance Option

Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: This Checklist An Input report generated from the software just after completing compliance calculations without any further changes The full compliance report generated by the software that contains the project summary, complaince summary, certifications and detailed component compliance reports Boxes appropriately checked in the Miscellanous report generated by the software at the end of the compliance report

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 1 of 8

PROJECT SUMMARY

Short Desc: TAM A3

Description:

TAM Building A3

Owner: Enter Owner's name here Address1: Enter Address here

City:

Enter city here

Address2: Enter Address here

State:

Enter state here

Zip: Type: Office

Class:

0 New Finished building

Jurisdiction: MIAMI, MIAMI-DADE COUNTY, FL (232400) Conditioned Area: 67500 SF

Conditioned & UnConditioned Area:

No of Stories: 3

Area entered from Plans

Permit No: 0

Max Tonnage If different, write in:

135000 SF 67500 SF 92 ______________________

Compliance Summary Component

Design

Gross Energy Cost (in $)

82,902.0

Criteria 79,058.0

Result FAILED

LIGHTING CONTROLS

PASSES

EXTERNAL LIGHTING

PASSES

HVAC SYSTEM

FAILS

PLANT

PASSES

WATER HEATING SYSTEMS

PASSES

PIPING SYSTEMS

No Entry

Met all required compliance from Check List?

Yes/No/NA

IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 2 of 8

CERTIFICATIONS

I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: __________________

Building Official: __________________

Date: _________________

Date: __________________

I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: __________________

Date: __________________

If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Code Architect: __________________

Reg No: __________________

Electrical Designer: __________________

Reg No: __________________

Lighting Designer: __________________

Reg No: __________________

Mechanical Designer: __________________

Reg No: __________________

Plumbing Designer: __________________

Reg No: __________________

(*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 3 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Building End Uses

Total

ELECTRICITY(MBtu/kWh/$)

AREA LIGHTS

MISC EQUIPMT

PUMPS & MISC

SPACE COOL

SPACE HEAT

VENT FANS

NATURAL-GAS(MBtu/therm/$)

SPACE HEAT

1) Proposed

2) Baseline

5,398.20

6,000.80

$82,902

$93,009

5,339.80 1564576

6,000.80 1758204

$82,610

$93,009

1,058.30 310073

1,270.00 372096

$16,372

$19,684

2,025.20 593376

2,025.20 593376

$31,330

$31,390

0.30 95

0.00 4

$5

$0

1,512.90 443286

2,064.20 604799

$23,406

$31,994

2.00 590

0.00 0

$31

$0

741.10 217156

641.40 187929

$11,466

$9,941

58.40 584

0

$292

$0

58.40 584

0.00 0

$292

$0

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 4 of 8

Credits Applied: None Passing Criteria = 79058 Design (including any credits) = 82902 Passing requires Proposed Building cost to be at most 85% of Baseline cost. This Proposed Building is at 89.1%

FAILS

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

External Lighting Compliance Description

Category

Tradable?

Ext Light 1

Walk way less than 10 feet wide

Allowance (W/Unit)

Yes

1.00

Area or Length ELPA or No. of Units (W) (Sqft or ft)

150.0

CLP (W)

150

96

PASSES

Tradable Surfaces: 96 (W) Allowance for Tradable: 157.5 (W) All External Lighting: 96 (W) Complicance check includes a excess/Base allowance of 7.50(W) Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Lighting Controls Compliance Acronym

Pr0Zo1Sp1 Pr0Zo2Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo6Sp1 Pr0Zo7Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1 Pr0Zo13Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1

Ashrae ID

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Description

Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan

Area (sq.ft)

14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500

Design CP

Min CP

2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3

2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3

Compliance PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES

PASSES

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 5 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

System Report Compliance Pr0Sy1

Component

Cooling System

Heating System Air Handling System -Supply

Pr0Sy2

Component

Cooling System

Heating System Air Handling System -Supply

Pr0Sy3

Component

Cooling System

Heating System Air Handling System -Supply

System 1

Category

Air Conditioners Air Cooled > 760000 Btu/h Cooling Capacity Warm Air Gas Furnace >= 225000 Btu/h Air Handler (Supply) Variable Volume

Variable Air Volume Packaged System--903 Capacity

Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume

Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume

Design IPLV

12.90

IPLV Criteria

Compliance

12.80

9.70

499500

80.00

80.00

PASSES

30834

1.25

1.12

FAILS

9.80

Capacity

Design Eff

PASSES

No. of Units

Variable Air Volume Packaged System--903

1

Eff Criteria

Design IPLV

IPLV Criteria

12.90

10.10

Compliance

457541

12.80

10.00

137430

80.00

80.00

PASSES

8484

1.25

1.12

FAILS

System 3

Category

Eff Criteria

1

1104049

System 2

Category

Design Eff

No. of Units

No. of Units

Variable Air Volume Packaged System--903 Capacity

Design Eff

PASSES

1

Eff Criteria

Design IPLV

IPLV Criteria

8.00

10.10

Compliance

470133

12.80

10.00

137430

80.00

80.00

PASSES

8484

1.25

1.12

FAILS

FAILS

FAILS

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 6 of 8

Plant Compliance Description

Installed No

Hot Water Boiler (Fuel)

1

Size

Design Eff

Min Eff

1

80.000

80.000

Design IPLV

Min IPLV

Category

Comp liance

Gas Fired >=300,000 and < 2,500,000 Btu/h

PASSES

PASSES

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Water Heater Compliance Description

Water Heater 1

Design Eff

Type

Category

Gas Storage water heater

= 20 Gal

0.58

Min Eff

Design Loss

Max Loss

Comp liance

0.52

PASSES

PASSES

Piping System Compliance Category

Pipe Dia [inches]

Is Runout?

Operating Ins Cond Temp [Btu-in/hr [F] .SF.F]

Ins Thick [in]

Req Ins Compliance Thick [in]

None

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 7 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_MIAMI_INTL_AP.tm3)

Other Required Compliance Category

Section

Requirement (write N/A in box if not applicable)

Check

Project: TAM A3

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 8 of 8

DOE Based Sizing

PROJECT SUMMARY

Short Desc: TAM A3

Description:

TAM Building A3

Owner: Enter Owner's name here Address1: Enter Address here

City:

Enter city here

Address2: Enter Address here

State:

Enter state here

Zip: Type: Office

Class:

0 New Finished building

Weather File: FL_MIAMI_INTL_AP.tm3 Conditioned Area: 67500 SF No of Stories: 3

Conditioned & UnConditioned Area: Area entered from Plans

Permit No: 0

Max Tonnage If different, write in:

135000 SF 67500 SF 92 ______________________

EnergyGauge Summit® v5.10

6/1/2015

Page 1 of 3

CERTIFICATIONS

I hereby certify that the plans and specifications covered by this calculation are in compliance as required by the authority of jurisdiction Prepared By: __________________

Building Official: __________________

Date: _________________

Date: __________________

I certify that this building is in compliance as required by the authority of jurisdiction Owner Agent: __________________

Date: __________________

If required by law, I hereby certify (*) that the system design is in compliance as required by the authority of jurisdiction Architect: __________________

Reg No: __________________

Electrical Designer: __________________

Reg No: __________________

Lighting Designer: __________________

Reg No: __________________

Mechanical Designer: __________________

Reg No: __________________

Plumbing Designer: __________________

Reg No: __________________

(*) Signature may be required when law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.

EnergyGauge Summit® v5.10

6/1/2015

Page 2 of 3

DOE 2.1 E Based Sized Parameters (Beta Feature) IdSystem

1

System Name

System Type

System 1

Pr0Sy1

Sized Value

Component Cooling System Heating System Air Handling System -Supply 2

Sized Value

Cooling System Heating System Air Handling System -Supply

457541 137430 8484

Units BTU/HR Btu/h CFM

System 3

Pr0Sy3

Sized Value

Component Cooling System Heating System Air Handling System -Supply 10

BTU/HR Btu/h CFM

System 2

Pr0Sy2

Component

3

1104049 499500 30834

Units

470133 137430 8484

Units BTU/HR Btu/h CFM

Hot Water Boiler (Fuel)

Hot Water Boiler (Fuel)

Sized Value

Component Hot Water Boiler (Fuel)

0.553

Units [Million Btu/h]

EnergyGauge Summit® v5.10

6/1/2015

Page 3 of 3

Florida Building Code, Fifth Edition (2014) - Energy Conservation EnergyGauge Summit® Fla/Com-2015, Effective Date: June 30, 2015 -- Form 506-2014 ASHRAE 90.1-2010 - Energy Cost Budget Option

Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: This Checklist An Input report generated from the software just after completing compliance calculations without any further changes The full compliance report generated by the software that contains the project summary, complaince summary, certifications and detailed component compliance reports Boxes appropriately checked in the Miscellanous report generated by the software at the end of the compliance report

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 1 of 8

PROJECT SUMMARY

Short Desc: TAM A3

Description:

TAM Building A3

Owner: Enter Owner's name here Address1: Enter Address here

City:

Enter city here

Address2: Enter Address here

State:

Enter state here

Zip: Type: Office

Class:

0 New Finished building

Jurisdiction: ORLANDO, ORANGE COUNTY, FL (582100) Conditioned Area: 67500 SF

Conditioned & UnConditioned Area:

No of Stories: 3

Area entered from Plans

Permit No: 0

Max Tonnage If different, write in:

135000 SF 67500 SF 97.6 ______________________

Compliance Summary Component

Design

Gross Energy Cost (in $)

79,928.0

Criteria 88,564.0

Result PASSED

LIGHTING CONTROLS

PASSES

EXTERNAL LIGHTING

PASSES

HVAC SYSTEM

FAILS

PLANT

FAILS

WATER HEATING SYSTEMS

PASSES

PIPING SYSTEMS

No Entry

Met all required compliance from Check List?

Yes/No/NA

IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 2 of 8

CERTIFICATIONS

I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: __________________

Building Official: __________________

Date: _________________

Date: __________________

I certify that this building is in compliance with the FLorida Energy Efficiency Code Owner Agent: __________________

Date: __________________

If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida Energy Efficiency Code Architect: __________________

Reg No: __________________

Electrical Designer: __________________

Reg No: __________________

Lighting Designer: __________________

Reg No: __________________

Mechanical Designer: __________________

Reg No: __________________

Plumbing Designer: __________________

Reg No: __________________

(*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans.

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 3 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)

Building End Uses

Total

ELECTRICITY(MBtu/kWh/$)

AREA LIGHTS

MISC EQUIPMT

PUMPS & MISC

SPACE COOL

SPACE HEAT

VENT FANS

NATURAL-GAS(MBtu/therm/$)

SPACE HEAT

1) Proposed

2) Baseline

5,314.50

5,719.50

$79,928

$88,564

5,095.90 1493095

5,711.40 1673414

$78,835

$88,524

1,058.30 310073

1,270.00 372096

$16,372

$19,684

2,025.20 593376

2,025.20 593376

$31,330

$31,390

2.00 595

0.30 76

$31

$4

1,315.10 385323

1,792.70 525268

$20,345

$27,787

10.60 3116

0.40 132

$165

$7

684.70 200612

622.80 182466

$10,592

$9,652

218.60 2186

8.10 81

$1,093

$41

218.60 2186

8.10 81

$1,093

$41

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 4 of 8

Credits Applied: None Passing Criteria = 88564 Design (including any credits) = 79928 Passing requires Proposed Building cost to be at most 100% of Baseline cost. This Proposed Building is at 90.2%

PASSES

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)

External Lighting Compliance Description

Category

Tradable?

Ext Light 1

Walk way less than 10 feet wide

Allowance (W/Unit)

Yes

1.00

Area or Length ELPA or No. of Units (W) (Sqft or ft)

150.0

CLP (W)

150

96

PASSES

Tradable Surfaces: 96 (W) Allowance for Tradable: 157.5 (W) All External Lighting: 96 (W) Complicance check includes a excess/Base allowance of 7.50(W) Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)

Lighting Controls Compliance Acronym

Pr0Zo1Sp1 Pr0Zo2Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo3Sp1 Pr0Zo6Sp1 Pr0Zo7Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1 Pr0Zo13Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo2Sp1 Pr0Zo6Sp1

Ashrae ID

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Description

Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan Office - Open Plan

Area (sq.ft)

14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500 14,400 2,025 2,025 2,025 2,025 22,500

Design CP

Min CP

2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3

2 1 1 1 1 3 2 1 1 1 1 3 2 1 1 1 1 3

Compliance PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES

PASSES

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 5 of 8

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)

System Report Compliance Pr0Sy1

Component

Cooling System

Heating System Air Handling System -Supply

Pr0Sy2

Component

Cooling System

Heating System Air Handling System -Supply

Pr0Sy3

Component

Cooling System

Heating System Air Handling System -Supply

System 1

Category

Air Conditioners Air Cooled > 760000 Btu/h Cooling Capacity Warm Air Gas Furnace >= 225000 Btu/h Air Handler (Supply) Variable Volume

Variable Air Volume Packaged System--903 Capacity

Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume

Air Conditioners Air Cooled 240000 to 760000 Btu/h Cooling Capacity Warm Air Gas Furnace < 225000 Btu/h Air Handler (Supply) Variable Volume

Design IPLV

12.90

IPLV Criteria

Compliance

12.80

9.50

541200

80.00

80.00

PASSES

33408

1.25

1.12

FAILS

9.60

Capacity

Design Eff

Eff Criteria

Design IPLV

12.90

PASSES

No. of Units

Variable Air Volume Packaged System--903

1 IPLV Criteria

Compliance

451805

12.80

9.80

136880

80.00

80.00

PASSES

8449

1.25

1.12

FAILS

System 3

Category

Eff Criteria

1

1171205

System 2

Category

Design Eff

No. of Units

9.90

No. of Units

Variable Air Volume Packaged System--903 Capacity

Design Eff

Eff Criteria

Design IPLV

12.90

PASSES

1 IPLV Criteria

Compliance

463985

12.80

9.80

9.90

136880

80.00

80.00

PASSES

8449

1.25

1.12

FAILS

PASSES

FAILS

EnergyGauge Summit® Fla/Com-2014. Section 506.4 Compliant Software. Effective Date: June 30, 2015

6/1/2015

Page 6 of 8

Plant Compliance Description

Installed No

Hot Water Boiler (Fuel)

1

Size

Design Eff

Min Eff

1

80.000

82.000

Design IPLV

Min IPLV

Category

Comp liance

Oil Fired >=300,000 and < 2,500,000 Btu/h

FAILS

FAILS

Project: TAM A3 Title: TAM Building A3 Type: Office (WEA File: FL_ORLANDO_INTL_ARPT.tm3)

Water Heater Compliance Description

Water Heater 1

Design Eff

Type

Category

Gas Storage water heater

>75000 &