Washington University St. Louis Environmental Health & Safety Indoor Air Quality

Washington University – St. Louis Environmental Health & Safety Indoor Air Quality Strategies for investigating indoor air quality problems are very s...
Author: Camron Lloyd
1 downloads 0 Views 571KB Size
Washington University – St. Louis Environmental Health & Safety Indoor Air Quality Strategies for investigating indoor air quality problems are very straightforward in that information is gathered and conclusions are drawn based on findings. In the absences of specific contaminant sources or obvious ventilation problems, EH&S will try to characterize the scope of the problem and systematically identify or eliminate elements which are specifically associated with IAQ episodes. Outlined below is the process you should expect from a campus IAQ investigation. I. II. III. IV. V. VI. VII. VIII. IX. X.

Initial contact—An EH&S staff person will speak, either in person or telephone, with someone familiar with the problem, usually the affected person(s), or their supervisor to identify specific concerns (i.e. comfort, odors, health, ventilation) Walk Through Investigation—An initial, walk-through investigation is conducted by EH&S to identify immediately correctable causes or to develop a plan for conducting a more thorough investigation Define Scope—Strategies are developed to evaluate suspected problems (e.g., ventilation system, chemical sources, microorganisms, or circulate questionnaires to better define the nature, scope, and exact location of the problem) Initial Monitoring—Preliminary air sampling is conducted. Normally it will involve the use of real time analyzers for carbon dioxide and other easy-to-measure air contaminants, or cursory testing with smoke tubes. Involve Other Divisions—Building Services will assist in ventilation system evaluation and preventative maintenance. An occupational physician will be consulted for medical concerns. The insurance department will be contacted for workers’ compensation concerns Detailed Monitoring—Ventilation system testing and/or sampling for chemical and biological contaminants is conducted as warranted. Evaluate Findings—Conditions and monitoring results are compared to criteria established through standards, codes, guidelines and good practice. Identify Solutions—The need for corrective actions and controls is identified, and solutions are recommended Correction—Controls and recommendations are implemented as necessary. Follow-up—Findings and results are communicated to concerned parties.

Initial (Phone) Questionnaire Name? Location? Symptoms? Is there an odor, if so what does it smell like? When did the symptoms/odor start? How often do you experience the symptoms/odors? When are the symptoms/odors most prevalent? When do symptoms/odors go away (how long do they last)? Is there anyone else affected, if so where are they in the building relative to you? What do you think the source is? Do you have allergies (what are they)? Do you have asthma? Do you smoke? Have you noticed any events in the building (weather, temperature/humidity changes, activities in the building) that correspond with the symptoms/odors? Have you seen a doctor for your symptoms? What is the approximate size of the room you work in? How many others work in this room? Approximately how many hours a day do you spend in this room?

Indoor Air quality - Initial Walkthrough I. Contact for assistance during the walk-through:  Building Maintenance Contact  Business Manager or Office Supervisor  Employee(s) complaining or with symptoms II. At the Site of the problem or complaint:  Conduct interviews or distribute questionnaires  Check for obvious sources of the problem (improper pressure differences, mold growth, dust, odors, temperature or humidity extremes etc.).  Check temperature, humidity, carbon dioxide and carbon monoxide levels using the Q-Trak. III.

Check the HVAC Systems:

 Outdoor Air Intakes -

Location of intakes Position of damper (open or closed) Location of exhaust Contaminant sources nearby

-

Intact, connected Dry Clean

 Ductwork

 Supply Air Diffusers -

Position: open or closed Distribution of air (too much, too little) Location in the room Clean

 Return Air or exhaust Grills -

Location in the room Position: open or closed Clean

Indoor Air Quality Survey Some individuals working in this building have reported health complaints. To help investigate the possible presence or absence of similar complaints this survey is being distributed to all or some occupants. Your assistance is requested. Please complete this survey as accurately as possible.

1. Symptoms:

2. When do these symptoms occur?

3. How long have you had symptoms?

4. How often do symptoms occur?

5. When do you experience relief from these symptoms?

6. Is there a noticeable odor?

7. Have you noticed any events in or near the building (weather, temperature/humidity changes, construction activities) that correspond with the symptoms?

8. Have you seen a physician for these symptoms?

9. Do you have any of the following? _____Hay fever, pollen allergies

_____Skin allergies/dermatitis

_____Sinus problems

_____Cold/flu

_____Other allergies

_____Asthma

10. What area do you primarily work in?

11. Approximately how many hours per day do you spend in this area?

12. Is there a history of indoor air quality issues that you are aware of in this area?

13. Briefly describe your primary job tasks.

14. Can you offer any other comments or observations concerning your office environment?

15. Your name and telephone number?

Symptoms

Eye irritation Dry or sore throat Skin irritation Skin rash Tightness in chest Runny nose Asthma exacerbation Cough Wheezing or other breathing Chest pain Changes in rate or depth of breathing Changes in pulse rate Visual disturbances Dizziness Fatigue Depression Clumsiness Drowsiness Headache Fever Repeated throat infections Sinus irritation Muscular pains Change in heart rhythm Tingling or numbness in extrimities Nausea or vomitting Abdominal pain Diarrhea Loss of appetite Cold/flu symptoms Difficulty in sleeping Irritablity Bachache/neckache Eye strain

Irritant

Asphyxiant

Anesthetic

Systemic Toxicant

Airborne pathogen/ allergen

Temperature

X X X

Humidity

Light/Noise

X X X X

X X X X X X

X

X X X X X X X X

X X X X X X

X X X X X

X X X X X X

X X X

X X X X X X X

X X X

X X

X (noise)

X X

X X

X X

X X

X (noise) X X X

X X X

X X X X

Indoor Air Quality Dust/Particulates Symptoms Dry or sore throat Runny nose Skin irritation Eye irritation Excessive dust Black “dust”

Exposure Limits OSHA 29 CFR 1910.1000 Particulates (not otherwise regulated)

Total Dust 15 mg/m3 Respirable fraction 10 mg/m3

EPA Outside Particulate Matter Standards

PM 2.5 65 µg/m3 PM 10 15 µg/m3

Sampling Sampling should only be conducted when there are the above symptoms reported For particulate sampling a pre-weighed filter cassettes with a PVC filter should be obtained from an outside laboratory. Using a personal sampling pump, sample at 4-5 L/m for 24 hours. Samples then should be brought to the same outside laboratory for analysis. Contact: Bill Lowry at EnviroHealth Technologies Inc. (314) 531-9868 FMD Assistance The following should be completed before sampling is conducted: Custodial Services should dust area that has complaint initially Building Services should check/change filters

Indoor Air Quality Light Symptoms Headache/Backache/Neckache Fatigue Depression Drowsiness Eye Strain Irritability Difficulty Sleeping

Exposure Limits Refer to the following typical light levels for office work areas provided by Extech Instruments. Lux 75 - 100 100 - 200 200 - 750 750 – 1,500 1,500 – 2,000

Foot Candles 7 – 10 10 - 20 20 - 75 75 - 150 150 – 200

Office Area Indoor Emergency Stairs Corridor Stairs Conference, Reception Room Clerical Work Typing, Drafting

Sampling Sampling may be conducted using the Heavy Duty Light Meter (Model 40726) Solutions Have custodial services or building services replace the light bulbs and/or ballasts Consult with Building Services and/or outside contractors experienced with lighting FMD Assistance Building Services Electricians may assist by installing, removing and/or adjusting light fixtures

Indoor Air Quality Mold/Fungi Symptoms Sore throat Headache Cold-like symptoms Exposure Limits There are no strict numerical guidelines which are appropriate for assessing whether the contamination in an area is acceptable or not. Further investigation of contamination sources is warranted in the following circumstances. 1.

Total indoor counts are greater than outdoor counts. This comparison is not valid when the outdoor sample was taken immediately after precipitation. It is probably not valid during some winter months where outdoor fungal counts are usually below that of indoor counts.

2.

Comparison of indoor and outdoor levels of fungal organisms show on of the following: A. B.

3.

Organisms are present in the indoor samples that are not present in the outdoor sample. The predominant organism found in the indoor sample is different than the predominant organism in the outdoor sample.

If either of the criteria from #2 are met and the organism is capable of producing toxins.

Sampling Determine the temperature and relative humidity of the affected area. Relative humidity should be between 3060%. Determine through visible inspection and/or interviews if there is or was water infiltration in the area. Run the Andersen single-stage sampler for 5 minutes in the affected area(s) and as close to the air intakes as possible outdoors. If the outdoor temperature is below 30 degrees run a sample in an entryway or foyer. Do not run comparison samples outdoors during or shortly after precipitation. Plates should be delivered to Barnes microbiology as soon as possible after sampling.

Indoor Air Quality On-going Diesel Odors Symptoms 10 ppm may cause Fatigue 25 ppm for 24 hours may lead to visual impairment 50 ppm for 24 hours may lead to irregular heartbeat 500 ppm for 1 hour may lead to nausea, headache and mental confusion. 1500 ppm for one hour may lead to death. Sources Tobacco Smoke, Malfunctioning heating equipment and vents, Motor vehicle exhaust, Internal combustion engines Exposure Limits ACGIH - TLV CO

25 ppm – 8 hr. avg.

CO2

-----

USEPA 35 ppm

ASHRAE 62-1989

9ppm annual avg. -----

same as USEPA 1000 ppm

Sampling Use Q-Trak, Solutions Dilution ventilation Remoting of air handling unit Isolating vehicle carburetors Restricting smoking FMD Assistance Call maintenance or design & construction personnel responsible for the building involved in IAQ investigation to get information on air handler location, HVAC and ductwork etc. Call maintenance supervisor(s) to notify the contractor using heavy diesel equipment that vehicle carburetors need to be isolated and turned off when not in use.

Indoor Air Quality Ergonomics Symptoms Headaches Muscle pain Dry itchy eyes Blurred vision Tiredness Uncomfortable feeling Exposure Limits OSHA General Duty Clause Sampling Conduct an ergonomic evaluation FMD Assistance Custodial Services may be needed to replace burned out lights Building Services/In-house Renovation may be needed to add lighting, attach keyboard trays, adjust desk levels, etc.

Indoor Air Quality Thermal Discomfort Symptoms Headache Drowsiness Discomfort Sources Inadequate ventilation, blocked plenums, closed dampers, malfunctioning fan, radiant heat loss (windows) Exposure Limits Relative Humidity Winter Temperature Summer Temperature 30% 68.5 F - 76.0 F 74.0 F - 80.0 F 40% 68.5 F - 75.5 F 73.5 F - 79.5 F 50% 68.5 F - 74.5 F 73.0 F - 79.0 F 60% 68.0 F - 74.0 F 72.5 F - 78.0 F Source: Adapted from ASHRAE standard 55-1981, Thermal Environmental Conditions for Human Occupancy. Sampling Use the Q-Trak Solutions Measure Indoor and outdoor temperature and humidity. Determine if extreme conditions exceed design capacity of HVAC equipment Measure Carbon Dioxide (CO2) in the complaint area to see whether it indicates ventilation problems. CO2 exceeding 1000 ppm may indicate poor ventilation Check for drafts and stagnant areas Check for excessive radiant heat gain or loss (i.e. where there are large or numerous windows) Open, adjust, or repair air distribution system (supply, return) to see if air is moving (using chemical smoke)

Ensure proper air distribution: Balance the air handling system Make sure that there is an air gap at tops and bottoms of partitions to prevent dead air space Relocate supply and/or return diffusers to improve air distribution Seal leaky ductwork Remove obstructions from return air plenums Control pressure relationships Move occupants closer to supply diffusers FMD Assistance Call maintenance personnel responsible for building involved in IAQ investigation to get information on air handler location, HVAC and ductwork etc.