The Handbook

2012 EDITION

Only the names have been changed to protect the innocent. Envirolex

®

Pyrolex

®

Alsecure

®

The cables that have been keeping Australians safe and secure for 30 years have a new name. Alsecure is now the name to specify for the cables you’ve always relied on where safety and security are critical – to maintain circuit integrity for mains power, lighting, alarms, pumps and other essential services when under fire. Now, backed by the global resources of Nexans, Olex is, more than ever, your one-stop-shop for the most complete range of performance cables.

SAFETY WARNING Cables are insulated and sheathed with stable materials which may contain certain toxic sub­stances including lead. Insulation and sheathing materials should not be chewed or ingested. Should you require more detailed data regarding materials, please contact our Group Safety Manager on 03 9281 4444 or refer to our web site, www.olex.com.au Installation Cables must be installed in accordance with the requirements of Section 3 – Selection and Installation of Wiring Systems in the latest issue of AS/NZS 3000 or the appropriate ruling standard in the country of installation. Cables must also be connected by a licensed electrician, as ruled in the state or country of installation. In particular your attention is drawn to Section 1.5 of the Wiring Rules (AS/NZS 3000) – Fundamental Principles. Designers and installers can be assured the products provided by Olex meet the requirements of the relevant cable standard, but must ensure appropriate selection of cables for the electrical installation conditions. Hazardous Areas Installation of wiring and fittings for hazardous areas, e.g. flammable or explosive gas, liquid, dust or solids must comply with Section 7.7 – Hazardous Areas, of AS/NZS 3000, and other relevant Australian Standards for specific hazards and occupancies. Technical Note PVC 90°C Thermal Rating The current carrying capacities for thermoplastic cables, including flexible cords used as fixed wiring, insulated with V-90 and V-90HT PVC compounds have been based on a conductor operating temperature of 75°C (refer AS/NZS 3008.1 Table 1 Note 2).

CONTENTS

The 2012 Handbook

Alsecure ® Envirolex ® Cables

7

Low Voltage 1 Core 1 Core 1 Core 2 & 3 Core 2 & 3 Core+Earth 2 & 3 Core+Earth 2 & 3 Core+Earth 4 Core+Earth 4 Core+Earth 2 & 3 Core+Earth 2 & 3 Core+Earth 4 Core+Earth 4 Core+Earth Multicore+Earth Multicore+Earth 4 Core 2, 3 & 4 Core

PVC Insulated PVC SDI XLPE/PVC Single Core PVC Flat PVC Flat PVC Circular XLPE/PVC Multicore PVC Circular XLPE/PVC Multicore PVC SWA Circular XLPE/PVC SWA Multicore PVC SWA Circular XLPE/PVC SWA Multicore PVC Control PVC SWA Control XLPE URD Power XLPE Aerial Bundled

Industrial 2 Core, 2, 3 & 4 Core+Earth 2 Core, 2, 3 & 4 Core+Earth 1, 2 & 3 Core 1 Core 2, 3 & 4 Core 5 Core 4 & 5 Core 1 Core 2 Core, Multicore+Earth 2, 3 & 4 Core+Earth 3 & 4 Core+Earth 3 Core+3 Earths Multicore+Earth Multicore+Earth 1 Core Multicore Pairs Pairs

Powerlex™ PVC OD Cords 28 Powerlex™ PVC HD Cords 29 Powerlex™ PVC Cords 30 Versolex® HD Single Core 31 Versolex ® HD Unscreened 32 Versolex ® HD Unscreened 33 Versolex ® HD Braid Screened 34 Titanex ® Single Core 35 Titanex ® Multi Core 36 Flexolex ® HD Unscreened 37 Flexolex ® HD Screened 38 Varolex ® VSD/EMC 39 PVC Flexible Control 40-41 PVC/EMC Flexible Control 42 Silicone Single Core 43 Silicone Multicore 44 Instrolex® Instrumentation 45 Instrolex ® Instrumentation SWA 46

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

3

CONTENTS Fire Performance 1 Core Multicore Single & Multipair

48 Alsecure ® Premium Ceramifiable ® Single Core Flex 49 Alsecure ® Premium Ceramifiable ® Multicore ® ® Alsecure Premium Ceramifiable Instrumentation & Data 51

Data/Comms Security Security/Audio LAN Coaxial Optical Fibre Telephone Internal Telephone External PVC Garden Lighting Fire Alarm Data

53 54 55 56-57 58 59 60 61 62 63

Accessories Alco Metal Cable Glands EMC, UW, HUW, AW, HAW Alco Earth Tags – Nickel Plated Alco Gland Shrouds

65-69 70 71

4

The 2012 Handbook

Current Ratings Flexible Cable Cord Colours PVC Flexible Cords Flexible Installation Versolex ® & Flexolex ® Welding Aluminium Aerial Copper Aerial Single Phase 2x1 Core PVC, XLPE, 110°C Single Phase 2 Core PVC, XLPE Three Phase 3x1 Core PVC, XLPE, 110°C Three Phase 3 & 4 Core PVC, XLPE, 110°C

72 73 74 75 76 77 78-80 81-82 83-85 86-88

General Data Cable Selection Cable Installation Minimum Size of Copper Earthing Conductors Maximum Operating Temperatures DC Resistance 3 Phase Formulae M.C.M. & A.W.G. Conductor Size Conversion Bending Radii & Motor Current Number of Cables in Conduit Cables in Conduit – Space Factors Pulling Tension Abbreviations

89-91 92 93 93 94 95 96 97 98-99 100 100 101

Locations Locations

102

The Olex Cable Range Handbook Subscription The Olex Cable Range

107 108

5

ALSECURE® ENVIROLEX® CABLES Alsecure® Envirolex ® cables are an extensive range of enhanced performance cables for the construction industry engineered to dramatically reduce environmental impact, particularly under fire conditions, while retaining the excellent mechanical and electrical properties designed into Olex’ cables. Olex uses a variety of inorganically filled polyolefin based materials to engineer the cables in the Alsecure® Envirolex ® range to meet a wide variety of end uses and performance requirements.

Advantages of Alsecure® Envirolex® cables  Conductor range up to 630mm2  Cable types from building wires to SWA, to multicore control  90°C rated for superior thermal performance  Improved performance under fire conditions:



– Flame retardant/self-extinguishing – Reduced acid, gas and smoke generation – Non-corrosive in fire situations – Reduced toxicity of fumes during fire  Halogen free (i.e. no chlorine, bromine etc.)  Lead free  No special termination or installation requirements  Made in accordance with Australian Standards Alsecure® Envirolex ® cables have been tested according to and comply with the requirements of the single flame tests specified in AS 1660. Alsecure® Envirolex ® products include readily strippable cables for general construction purposes as well as the tougher products commonly found in cables with higher fire performance capability. Alsecure® Envirolex ® materials can also be used as alternatives to all other low voltage power and control cables (refer tables on pages 8 to 25). Cables are available on request, subject to minimum production run. Information on the Alsecure® Fire Performance range of cables can be found on pages 47 to 51 of this handbook.

6

ALSECURE® ENVIROLEX® FLAT 2 & 3 core+earth flat, 450/750V X-90 (XLPE) insulated, HFS-90-TP sheathed to AS/NZS 5000.2, copper conductors, 90°C.

Nom. Main cond. conductor area type mm 2

Nom. insul. thick. mm

Nom. sheath thick. mm

1.0 1.5 2.5 2.5 4.0 6.0 10.0 16.0

Solid Cu Strand Cu Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu

0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7

0.9 0.9 1.0 1.0 1.1 1.1 1.2 1.3

1.5 2.5

Strand Cu Strand Cu

0.6 0.6

0.9 1.0

Earth cond. area mm 2

Nominal overall diameter mm

2C+E 1.0 9.04.2 1.5 10.04.6 2.5 11.25.0 2.5 11.75.3 2.5 13.46.2 2.5 14.56.8 4.0 17.07.8 6.0 19.78.9 3C+E 1.5 12.74.6 2.5 14.95.3

Approx. mass

Product code

kg/100m 5.7 7.2 11.0 11.1 15.2 19.2 29.8 43.7

CTCP02JA002 CTCP05JA002 CTCP06JA002 CTCP07JA002 CTCP09JA002 CTCP11JA002 CTCP13JA002 CTCP15JA002

9.4 14.6

ETCP05JA003 ETCP07JA003

Note: Alsecure ® Envirolex ® cables are lead and halogen free and are suitable for “green” building installations.

7

TAGE

LOW VOLTAGE

RIAL

INDUSTRIAL

TAGE

HIGH VOLTAGE

where we live. RATED ATED PoweringFIRE

MMS

Olex has a proud history of cable manufacturing expertise, with more than half a century of experience in the industry. Offering a comprehensive range of low voltage power and control cables, Olex has the cable you need.

DATA/COMMS

NING

MINING 8

PVC INSULATED LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Single core, 0.6/1kV V-90 insulated, to AS/NZS 5000.1 (unsheathed), copper conductors, 90°C.

Nominal Main conductor conductor area type mm 2

Nominal insulation thickness mm

0.5 1.0 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

0.8 2.4 1.0 0.8 2.8 1.6 0.8 2.8 1.5 0.8 3.1 2.0 0.8 3.6 3.2 1.0 4.5 5.1 1.0 5.1 7.1 1.0 6.0 11.1 1.0 6.9 17 1.2 8.4 26 1.2 9.4 35 1.4 10.9 48 1.4 12.4 67 1.6 15.2 96 1.6 17.3 118 1.8 18.8 144 2.0 21.1 180 2.2 24.1 236 2.4 26.9 296 2.6 30.6 376 2.8 34.1 477 2.8 37.8 613 PVC Insulated Copper Earth Conductor 0.6 2.7 1.8 0.7 3.4 3.0



1.5 2.5

Solid Cu Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Single Core Strand Cu Strand Cu

Nominal overall diameter mm

Approximate mass

Product code

kg/100m

Note: Other temperature grades subject to minimum production runs.

BAAP01AA001 BAAP02AA001 BAAP03AA001 BAAP05AA001 BAAP07AA001 BAAP09AA001 BAAP11AA001 BAAP13AA001 BAAP15AA001 BAAC17AA001 BAAC18AA001 BAAC19AA001 BAAC20AA001 BAAC22AA001 BAAP23AA001 BAAP24AA001 BAAP25AA001 BAAP26AA001 BAAP27AA001 BAAP28AA001 BAAP30AA001 BAAP32AA001 AATP05AA001 AATP07AA001

9

PVC SDI LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Single core, V-90 insulated, PVC sheathed to AS/NZS 5000, copper conductors, 90°C.  1.0 to 16mm2 450/750V to AS/NZS 5000.2  25 to 630mm2 0.6/1kV to AS/NZS 5000.1 Nominal Main conductor conductor area type mm 2

Nominal insulation thickness mm

Nominal sheath thickness mm

Nominal overall diameter mm

Approx. Product mass code

1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

0.6 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8

0.8 0.8 0.8 0.9 0.9 0.9 1.0 1.4 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2

4.0 4.4 5.1 6.0 6.6 7.8 8.9 11.1 12.1 13.7 15.3 18.2 20.4 22.1 24.5 27.8 30.8 34.7 38.4 42.2

2.7 3.2 4.8 7.1 9.4 14.3 20.8 32.3 43 56 77 107 130 158 197 257 320 406 510 653

10

Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu

kg/100m AABP02AA001 AABP05AA001 AABP07AA001 AABP09AA001 AABP11AA001 AABP13AA001 AABP15AA001 BABC17AA001 BABC18AA001 BABC19AA001 BABC20AA001 BABC22AA001 BABP23AA001 BABP24AA001 BABP25AA001 BABP26AA001 BABP27AA001 BABP28AA001 BABP30AA001 BABP32AA001

XLPE/PVC SINGLE CORE LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Single core, 0.6/1kV X-90 insulated, PVC sheathed to AS/NZS 5000.1, copper or aluminium conductors, 90°C.

Nom. Main cond. conductor area type mm 2

Nominal insulation thickness mm

16 25 35 50 70 95 120 150 185 240 300 400 500 630

Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compressed Cu Compressed Cu Compressed Cu Compressed Cu Compressed Cu Compressed Cu Strand Cu Strand Cu Strand Cu

0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4

25 35 50 70 95 120 150 185 240 300 400 500 630

Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact Compact

0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4

Al Al Al Al Al Al Al Al Al Al Al Al Al

Nominal sheath thickness mm

Nominal overall diameter mm

Copper Conductor 1.4 9.3 1.4 10.5 1.4 11.5 1.4 12.9 1.4 14.7 1.5 17.2 1.5 19.6 1.6 21.3 1.6 23.5 1.7 26.6 1.8 29.4 1.9 33.3 2.0 37.0 2.2 41.4 Aluminium Conductor 1.4 10.7 1.4 11.8 1.4 13.1 1.4 14.9 1.5 16.8 1.5 18.4 1.6 20.5 1.6 22.4 1.7 25.1 1.8 27.6 1.9 31.1 2.0 35.3 2.2 39.5

Approximate Product mass code kg/100m 21 30 40 52 73 101 123 152 189 246 306 386 491 635

BDBP15AA001 BDBC17AA001 BDBC18AA001 BDBC19AA001 BDBC20AA001 BDBC22AA001 BDBP23AA001 BDBP24AA001 BDBP25AA001 BDBP26AA001 BDBP27AA001 BDBP28AA001 BDBP30AA001 BDBP32AA001

15 18 23 31 40 49 60 72 91 112 142 185 233

BDBA17AA001 BDBA18AA001 BDBA19AA001 BDBA20AA001 BDBA22AA001 BDBA23AA001 BDBA24AA001 BDBA25AA001 BDBA26AA001 BDBA27AA001 BDBA28AA001 BDBA30AA001 BDBA32AA001

11

PVC FLAT LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

2 & 3 core flat, 450/750V V-90 insulated, PVC sheathed to AS/NZS 5000.2, copper conductors, 90°C.

Nom. Main cond. conductor area type mm 2

Nominal insulation thickness mm

Nominal sheath thickness mm

Nominal overall diameter mm

Approximate Product mass code kg/100m

2C 1.0 1.5 2.5 4 6 10 16

Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu

0.6 0.6 0.7 0.8 0.8 1.0 1.0

0.9 0.9 1.0 1.1 1.1 1.2 1.3

1.5 2.5

Strand Cu Strand Cu

0.6 0.7

0.9 1.0

12

6.54.2 7.24.5 8.95.4 10.56.3 11.66.9 14.28.3 16.39.5 3C 9.94.5 12.35.4

5.04 6.17 9.68 14.19 18.59 29.42 42.48

CACP02AA002 CACP05AA002* CACP07AA002 CACP09AA002 CACP11AA002 CACP13AA002 CACP15AA002

8.84 14.03

EACP05AA003 EACP07AA003

Note: *Red sheath 450/750V version available for fire alarm wiring systems. A 0.6/1kV red sheath version is also available: DACP05AA002.

PVC FLAT LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

2 & 3 core+earth flat, 450/750V V-90 insulated, PVC sheathed to AS/NZS 5000.2, copper conductors, 90°C.

Nom. Main cond. conductor area type mm 2

Nom. insul. thick. mm

Nom. sheath thick. mm

1.0 1.5 2.5 2.5 4.0 6.0 10.0 16.0

Solid Cu Strand Cu Solid Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu

0.6 0.6 0.7 0.7 0.8 0.8 1.0 1.0

0.9 0.9 1.0 1.0 1.1 1.1 1.2 1.3

1.5 2.5

Strand Cu Strand Cu

0.6 0.7

0.9 1.0

Earth cond. area mm 2

Nominal overall diameter mm

2C+E 1.0 8.94.2 1.5 9.94.5 2.5 11.85.4 2.5 12.25.4 2.5 13.96.3 2.5 15.06.9 4.0 18.38.3 6.0 21.09.5 3C+E 1.5 12.64.5 2.5 15.75.4

Approx. mass

Product code

kg/100m 7.74 8.86 13.68 14.03 18.65 23.04 36.05 51.46

CNCP02AA002 CNCP05AA002 CNCP06AA002 CNCP07AA002 CNCP09AA002 CNCP11AA002 CNCP13AA002 CNCP15AA002

11.54 18.31

ENCP05AA003 ENCP07AA003

13

PVC CIRCULAR LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

2 & 3 core+earth, circular, V-90 insulated, PVC sheathed to AS/NZS 5000, copper conductors, 90°C.  1.5 to 6mm2 450/750V to AS/NZS 5000.2  10 to 300mm2 0.6/1kV to AS/NZS 5000.1 Nom. Main cond. conductor area type mm 2

Nom. insul. thick. mm



1.5 2.5 4 6 10 16 25 35 50

Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu

0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu

0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4

14

Nom. Earth sheath cond. thick. area mm mm 2 2C+E 1.2* 1.5 1.2* 2.5 1.3* 2.5 1.3* 2.5 1.8 4 1.8 6 1.8 6 1.8 10 1.8 16 3C+E 1.2* 1.5 1.3* 2.5 1.3* 2.5 1.3* 2.5 1.8 4 1.8 6 1.8 6 1.8 10 1.8 16 1.9 25 2.1 25 2.2 35 2.3 50 2.5 70 2.7 95 2.9 120

Nom. Approx. overall mass dia. mm kg/100m

Product code

8.4* 10.6* 9.8* 15.9* 11.4* 20.8* 12.4* 25.7* 16.1 43.5 18.0 59.7 20.5 80.3 22.5 103 25.6 138

CNHP05AA002 CNHP07AA002 CNHP09AA002 CNHP11AA002 DNHP13AA002 DNHP15AA002 DNHC17AA002 DNHC18AA002 DNHC19AA002

9.2* 11.1* 12.5* 13.5* 17.5 19.6 22.2 24.6 28.0 32.0 37.6 42.4 46.3 51.7 59.4 66.2

ENHP05AA003 ENHP07AA003 ENHP09AA003 ENHP11AA003 FNHP13AA003 FNHP15AA003 FNHC17AA003 FNHC18AA003 FNHC19AA003 FNHC20AA003 FNHC22AA003 FNHP23AA003 FNHP24AA003 FNHP25AA003 FNHP26AA003 FNHP27AA003

12.7* 19.7* 26.3* 33.2* 56.1 78.2 107 141 188 264 360 442 542 686 902 1124

Note: Earth cores smaller than 25mm 2 are not compacted. 2C+E, 35mm 2 and above, subject to minimum production run. *D ue to a change in standard AS/NZS 5000.2, the minimum calculated value of the sheath thickness for circular multicore cables has reduced, therefore also reducing the OD and mass for 1.5mm 2 –6mm 2 cables.

XLPE/PVC MULTICORE LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

2 & 3 core+earth, circular, 0.6/1kV X-90 insulated, PVC sheathed to AS/NZS 5000.1, copper conductors, 90°C.

Nominal Main conductor conductor area type mm 2

Nom. insul. thick. mm

Nom. sheath thick. mm

16 25 35 50 70 95 120

Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu

0.8 0.9 0.9 1.0 1.1 1.1 1.2

1.8 1.8 1.8 1.8 1.8 1.9 2.0

16 25 35 50 70 95 120 150 185 240 300

Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu

0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8

1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8

Earth cond. area mm 2

Nom. Approx. Product overall mass code dia. mm kg/100m

2C+E 6 6 10 16 25 25 35 3C+E 6 6 10 16 25 25 35 50 70 95 120

17.1 19.3 21.3 24.0 27.6 32.5 37.3

54 74 96 128 180 240 298

DTHP15AA002 DTHC17AA002 DTHC18AA002 DTHC19AA002 DTHC20AA002 DTHC22AA002 DTHP23AA002

18.6 20.8 23.2 26.3 30.5 35.2 40.3 44.3 49.7 56.8 63.3

71 98 132 175 249 337 417 516 655 856 1066

FTHP15AA003 FTHC17AA003 FTHC18AA003 FTHC19AA003 FTHC20AA003 FTHC22AA003 FTHP23AA003 FTHP24AA003 FTHP25AA003 FTHP26AA003 FTHP27AA003

Note: Earth cores smaller than 25mm 2 are not compacted. For insulation thickness refer to page 9. 3½ core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.

15

PVC CIRCULAR LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

4 core+earth, circular, V-90 insulated, PVC sheathed to AS/NZS 5000, copper conductors, 90°C.  1.5 to 6mm2 450/750V to AS/NZS 5000.2  10 to 300mm2 0.6/1kV to AS/NZS 5000.1 Earth cond. area mm 2

Nom. Approx. Product overall mass code dia. mm kg/100m

Nominal Main conductor conductor area type mm 2

Nom. insul. thick. mm

Nom. sheath thick. mm

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu

0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4

1.2* 1.3* 1.4* 1.4* 1.8 1.8 1.8 1.8 1.9 2.1 2.2 2.4 2.5 2.7 2.9 3.1

16

Note: Earth cores smaller than 25mm 2 are not compacted. *D ue to a change in standard AS/NZS 5000.2, the minimum calculated value of the sheath thickness for circular multicore cables has reduced, therefore also reducing the OD and mass for 1.5mm 2 –6mm 2 cables.

4C+E 1.5 2.5 2.5 2.5 4 6 6 10 16 25 25 35 50 70 95 120

10.0* 15.1* 12.0* 23.6* 13.8* 33.0* 15.0* 42.1* 19.2 70 21.5 98 24.5 136 27.2 180 31.2 242 35.8 339 42.0 465 47.5 573 51.8 700 57.9 885 66.9 1166 74.5 1446

GNHP05AA004 GNHP07AA004 GNHP09AA004 GNHP11AA004 HNHP13AA004 HNHP15AA004 HNHC17AA004 HNHC18AA004 HNHC19AA004 HNHC20AA004 HNHC22AA004 HNHP23AA004 HNHP24AA004 HNHP25AA004 HNHP26AA004 HNHP27AA004

XLPE/PVC MULTICORE LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

4 core+earth, circular, 0.6/1kV X-90 insulated, PVC sheathed to AS/NZS 5000.1, copper conductors, 90°C.

Nominal Main conductor conductor area type mm 2

Nom. insul. thick. mm

Nom. sheath thick. mm

16 25 35 50 70 95 120 150 185 240 300

0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8

1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.0

Earth cond. area mm 2

Nom. Approx. Product overall mass code dia. mm kg/100m

4C+E Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu

6 6 10 16 25 25 35 50 70 95 120

20.4 22.9 25.5 29.3 34.0 39.3 45.2 49.5 55.7 63.5 71.2

Note: Earth cores smaller than 25mm 2 are not compacted.

89 124 167 224 320 436 543 665 842 1100 1385

HTHP15AA004 HTHC17AA004 HTHC18AA004 HTHC19AA004 HTHC20AA004 HTHC22AA004 HTHP23AA004 HTHP24AA004 HTHP25AA004 HTHP26AA004 HTHP27AA004

17

PVC SWA CIRCULAR LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

2 & 3 core+earth, circular, 0.6/1kV V-90 insulated, PVC bedded, steel wire armoured, PVC sheathed cable to AS/NZS 5000.1, copper conductors, 90°C. Nom. Main cond. cond. area type mm 2

Nom. Earth insul. cond. thick. area mm mm 2



1.5 2.5 4 6 10 16 25 35 50

Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu

0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu

0.8 1.5 0.8 2.5 0.8 2.5 1.0 2.5 1.0 4 1.0 6 1.2 6 1.2 10 1.4 16 1.4 25 1.6 25 1.6 35 1.8 50 2.0 70 2.2 95 2.4 120

18

1.5 2.5 2.5 2.5 4 6 6 10 16

Nom. dia. over bedding mm

Nom. dia. over armour mm

2C+E 10.5 11.6 13.3 14.5 17.0 18.9 22.1 24.1 27.2 3C+E 9.5 11.3 10.9 12.7 12.6 15.1 13.8 16.3 15.9 18.4 18.0 21.2 20.6 23.8 23.0 26.2 26.4 29.6 30.6 34.6 35.8 39.8 40.4 44.4 44.5 49.5 49.7 54.7 57.2 62.2 63.5 68.5 8.7 9.8 11.5 12.7 14.5 16.4 18.9 20.9 24.0

Nom. Approx. Product overall mass code dia. mm kg/100m 14.1 15.2 16.9 18.1 20.6 22.5 25.7 27.8 30.9

37.0 44.7 54.6 62.7 90.4 105 151 182 226

DNMP05AA002 DNMP07AA002 DNMP09AA002 DNMP11AA002 DNMP13AA002 DNMP15AA002 DNMC17AA002 DNMC18AA002 DNMC19AA002

15.0 16.3 18.7 20.0 22.1 24.9 27.5 29.9 33.7 38.9 44.3 49.2 54.5 60.1 68.8 75.6

41.8 51.1 72.4 84 108 140 184 226 287 406 522 627 785 966 1219 1474

FNMP05AA003 FNMP07AA003 FNMP09AA003 FNMP11AA003 FNMP13AA003 FNMP15AA003 FNMC17AA003 FNMC18AA003 FNMC19AA003 FNMC20AA003 FNMC22AA003 FNMP23AA003 FNMP24AA003 FNMP25AA003 FNMP26AA003 FNMP27AA003

Note: 3½ core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.

XLPE/PVC SWA MULTICORE LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

2 & 3 core+earth, circular, 0.6/1kV X-90 insulated, PVC bedded, steel wire armoured, PVC sheathed cable to AS/NZS 5000.1, copper conductors, 90°C. Nom. Main cond. cond. area type mm 2

Nom. insul. thick. mm

Earth cond. area mm 2

16 25 35 50 70 95 120

Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu

0.8 0.9 0.9 1.0 1.1 1.1 1.2

6 6 10 16 25 25 35

16 25 35 50 70 95 120 150 185 240 300

Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu

0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8

6 6 10 16 25 25 35 50 70 95 120

Nom. dia. over bedding mm

Nom. dia. over armour mm

2C+E 18.0 20.2 22.9 25.6 29.2 34.7 39.7 3C+E 17.0 19.5 19.2 22.4 21.6 24.8 24.7 27.9 29.1 33.1 33.6 37.6 38.5 42.5 42.5 47.5 47.7 52.7 54.8 59.8 60.9 65.9 15.5 17.7 19.7 22.4 26.0 30.7 35.7

Nom. Approx. Product overall mass code dia. mm kg/100m 21.6 23.8 26.6 29.3 33.1 38.8 44.0

98 128 169 210 276 377 459

DTMP15AA002 DTMC17AA002 DTMC18AA002 DTMC19AA002 DTMC20AA002 DTMC22AA002 DTMP23AA002

23.1 26.1 28.4 31.8 37.4 42.1 47.2 52.6 58.0 66.2 72.7

118 171 212 267 384 491 592 749 915 1157 1402

FTMP15AA003 FTMC17AA003 FTMC18AA003 FTMC19AA003 FTMC20AA003 FTMC22AA003 FTMP23AA003 FTMP24AA003 FTMP25AA003 FTMP26AA003 FTMP27AA003

Note: 3½ core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.

19

PVC SWA  CIRCULAR LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

4 core+earth, circular, 0.6/1kV V-90 insulated, PVC bedded, steel wire armoured PVC sheathed to AS/NZS 5000.1, copper conductors, 90°C.

Nom. Main cond. cond. area type mm 2

Nom. insul. thick. mm

Earth cond. area mm 2

Nom. dia. over bedding mm

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4

1.5 2.5 2.5 2.5 4 6 6 10 16 25 25 35 50 70 95 120

10.4 11.9 13.8 15.2 17.6 19.9 22.9 25.6 29.8 34.0 40.0 45.5 49.6 55.7 64.3 71.8

20

Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu

Nom. dia. over armour mm

4C+E 12.2 13.7 16.3 17.7 20.8 23.1 26.1 28.8 33.8 38.0 44.0 50.5 54.6 60.7 69.3 78.1

Nom. Approx. Product overall mass code dia. mm kg/100m 15.9 17.3 20.0 21.4 24.4 26.8 29.8 32.6 38.1 42.5 48.8 55.8 60.1 67.4 76.3 85.8

46 58 83 97 139 166 220 275 380 494 646 824 970 1192 1516 1936

HNMP05AA004 HNMP07AA004 HNMP09AA004 HNMP11AA004 HNMP13AA004 HNMP15AA004 HNMC17AA004 HNMC18AA004 HNMC19AA004 HNMC20AA004 HNMC22AA004 HNMP23AA004 HNMP24AA004 HNMP25AA004 HNMP26AA004 HNMP27AA004

Note: 3½ core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.

XLPE/PVC SWA MULTICORE LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

4 core+earth, circular, 0.6/1kV X-90 insulated, PVC bedded, steel wire armoured, PVC sheathed to AS/NZS 5000.1, copper conductors, 90°C. Nom. Main cond. cond. area type mm 2

Nom. insul. thick. mm

Earth cond. area mm 2

Nom. dia. over bedding mm

16 25 35 50 70 95 120 150 185 240 300

0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8

6 6 10 16 25 25 35 50 70 95 120

18.8 21.3 23.9 27.5 32.4 37.5 43.4 47.5 53.7 61.1 68.4

Strand Cu Compact Cu Compact Cu Compact Cu Compact Cu Compact Cu Strand Cu Strand Cu Strand Cu Compact Cu Strand Cu

Nom. dia. over armour mm

4C+E 22.0 24.5 27.1 31.5 36.4 41.5 48.4 52.5 58.7 66.1 73.4

Nom. Approx. Product overall mass code dia. mm kg/100m 25.6 28.2 31.0 35.5 40.9 46.1 53.5 57.7 64.4 73.0 80.7

155 203 257 350 470 608 780 925 1134 1443 1759

Note: 3½ core (3 core+reduced neutral with or without earth) available on request subject to minimum production runs.

HTMP15AA004 HTMC17AA004 HTMC18AA004 HTMC19AA004 HTMC20AA004 HTMC22AA004 HTMP23AA004 HTMP24AA004 HTMP25AA004 HTMP26AA004 HTMP27AA004

21

PVC CONTROL LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Multicore circular+earth, 0.6/1kV V-90 insulated, PVC sheathed to AS/NZS 5000.1, copper conductors, 90°C.

Number of cores

Nominal overall diameter mm

5+E 6+E 8+E 10+E 12+E 15+E 16+E 20+E 25+E 30+E 36+E 40+E 50+E

13.1 13.1 15.4 16.1 17.0 18.2 19.1 20.1 22.2 24.3 25.2 27.5 29.4

5+E 6+E 8+E 10+E 12+E 15+E 16+E 20+E 25+E 30+E 36+E 40+E 50+E

14.6 14.6 17.3 18.1 19.0 20.6 21.6 22.8 25.2 27.6 28.7 31.5 33.7

22

Approximate mass kg/100m

1.5mm2 (7/0.50mm) 22 24 30 35 40 46 51 59 71 83 95 107 129 2.5mm2 (7/0.67mm) 31 34 43 50 57 68 73 85 104 122 141 160 194

Product code

BFAP05AA005 BFAP05AA006 BFAP05AA008 BFAP05AA010 BFAP05AA012 BFAP05AA015 BFAP05AA016 BFAP05AA020 BFAP05AA025 BFAP05AA030 BFAP05AA036 BFAP05AA040 BFAP05AA050 BFAP07AA005 BFAP07AA006 BFAP07AA008 BFAP07AA010 BFAP07AA012 BFAP07AA015 BFAP07AA016 BFAP07AA020 BFAP07AA025 BFAP07AA030 BFAP07AA036 BFAP07AA040 BFAP07AA050

Note: 450/750V rated cables to AS/NZS 5000.3 available on request.

PVC SWA CONTROL LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Multicore circular+earth, 0.6/1kV V-90 insulated, PVC bedded, steel wire armoured, PVC sheathed to AS/NZS 5000.1, copper conductors 90°C. Number of cores

Nominal dia. over bedding mm

5+E 6+E 8+E 10+E 12+E 15+E 16+E 20+E 25+E 30+E 36+E 40+E 50+E

11.5 11.5 13.8 14.5 15.2 16.6 17.5 18.5 20.6 22.7 23.6 25.9 28.0

5+E 6+E 8+E 10+E 12+E 15+E 16+E 20+E 25+E 30+E 36+E 40+E 50+E

13.0 13.0 15.7 16.5 17.4 19.0 20.0 21.2 23.6 26.0 27.1 30.1 32.1

Nominal dia. over armour mm

Nominal overall diameter mm

1.5mm2 (7/0.50mm) 13.3 16.9 13.3 16.9 16.3 20.0 17.0 20.7 17.7 21.4 19.1 22.8 20.7 24.4 21.7 25.4 23.8 27.4 25.9 29.6 26.8 30.7 29.1 32.9 32.0 36.2 2 2.5mm (7/0.67mm) 15.5 19.1 15.5 19.1 18.2 21.9 19.0 22.7 20.6 24.2 22.2 25.8 23.2 26.9 24.4 28.1 26.8 30.6 29.2 33.1 30.3 34.4 34.1 38.3 36.1 40.6

Approximate Product mass code kg/100m 51 52 74 80 87 97 118 128 147 167 182 202 260

BFCP05AA005 BFCP05AA006 BFCP05AA008 BFCP05AA010 BFCP05AA012 BFCP05AA015 BFCP05AA016 BFCP05AA020 BFCP05AA025 BFCP05AA030 BFCP05AA036 BFCP05AA040 BFCP05AA050

72 75 91 100 122 138 148 164 191 219 243 299 342

BFCP07AA005 BFCP07AA006 BFCP07AA008 BFCP07AA010 BFCP07AA012 BFCP07AA015 BFCP07AA016 BFCP07AA020 BFCP07AA025 BFCP07AA030 BFCP07AA036 BFCP07AA040 BFCP07AA050

Note: 450/750V rated cables to AS/NZS 5000.3 available on request.

23

XLPE URD POWER LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

4 core annealed aluminium sector or circular copper, 0.6/1kV X-90 insulated, PVC sheathed Low Voltage Underground Residential Distribution Cable to AS/NZS 4026, 90°C. Nominal conductor area mm 2

Nominal insulation thickness mm

Diameter over insulation mm

185 240 185 240

1.6 1.7 1.6 1.7

17.2 20.2 18.2 20.6



1.5 1.7 1.7 1.8

7.9 9.3 10.3 11.6

16 25 35 50

24

Nominal overall diameter mm

LV Distribution 43.0 49.8 47.5 53.4 LV Service 22.1 25.5 27.9 31.2

Approximate mass

Product code

kg/100m 280 363 288 366

XDDS25AA004* XDDS26AA004* XDDA25AA004• XDDG37AA004•

86 127 166 217

HEVP15AA004 HEVC17AA004 HEVC18AA004 HEVC19AA004

Note: *Solid conductor. •Stranded conductor.

XLPE AERIAL BUNDLED LOW VOLTAGE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

2, 3 & 4 core aerial bundled cable 0.6/1kV X-90UV insulated compacted aluminium conductors, to AS/NZS 3560.1, 90°C.

Nominal conductor area mm 2

Nominal insulation thickness mm

Diameter over insulation mm



25 35 50 95

1.3 1.3 1.5 1.7

8.6 9.6 11.2 14.9



25 35 50 70

1.3 1.3 1.5 1.5

8.6 9.6 11.2 12.8

25 35 50 70 95 120 150

1.3 1.3 1.5 1.5 1.7 1.7 1.7

8.6 9.6 11.2 12.8 14.9 16.3 17.7

Diameter over laid-up cores mm 2C 17.2 19.3 22.3 29.8 3C 18.5 20.8 24.1 27.5 4C 20.8 23.2 27.0 30.8 36.0 39.3 42.8

Approx. mass

Product code

kg/100m 19 25 34 64

XDAB17AA002 XDAB18AA002 XDAB19AA002 XDAB22AA002

29 37 50 70

XDAB17AA003 XDAB18AA003 XDAB19AA003 XDAB20AA003

38 50 67 93 127 156 188

XDAB17AA004 XDAB18AA004 XDAB19AA004 XDAB20AA004 XDAB22AA004 XDAB23AA004 XDAB24AA004

Note: A range of PVC insulated neutral screened cables and PVC insulated Hard Drawn Copper Aerials are also available on request.

25

RIAL

INDUSTRIAL

AGE

HIGH VOLTAGE

ATED

FIRE RATED Industrial power.

/ COMMS MMS Olex specialisesDATA in a range of industrial cables

NING

designed in accordance with local and international standards. The quality and toughness of these products make them much sought after on world markets from industrial power, to control cable, robotics, BUS technology, instrumentation and specialist applications.

MINING

Olex widens its range of Industrial cables.

New to the Olex Cable Range: • Titanex® Single & Multi Core Flexible Cable • HO7VVH6-F PVC Flat Cable • VCVH6-F Screened PVC Flat Cable • Buflex ®X’Prem Reeling Cable • Rheyhalon Cable • Rheyflat ®-N Screened & Unscreened Rubber Flat Festoon Cable • Boitalyon ®R PVC Pendant Overhead Crane Cable For more information on the range of new products check out the new Olex Industrial Catalogue or visit www.olex.com.au

POWERLEX™ PVC OD CORDS GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

250/440V V-90 insulated and sheathed ordinary duty flexible cord to AS/NZS 3191 and AS/NZS 60227.

Nominal conductor area mm 2

Maximum diameter of wires mm

Nominal overall diameter mm

Approximate mass

Product code

kg/100m

2C 0.75 1.0 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

0.75 1.0 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

0.75 1.0 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

0.75 1.0 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

28

6.2 6.6 7.5 9.2 10.4 2C+E 6.6 6.9 8.1 9.9 11.2 3C+E 7.2 7.8 9.1 10.9 12.3 4C+E 8.0 8.5 10.1 12.1 13.9

5 6 8 13 18

CAHR02AA002 CAHR03AA002 CAHR04AA002 CAHR05AA002 CAHR06AA002

7 8 11 17 23

EAHR02AA003 EAHR03AA003 EAHR04AA003 EAHR05AA003 EAHR06AA003

8 10 13 20 29

GAHR02AA004 GAHR03AA004 GAHR04AA004 GAHR05AA004 GAHR06AA004

9 10 15 26 36

APAR02AA005 APAR03AA005 APAR04AA005 APAR05AA005 APAR06AA005

Note: For core colour, flexible cords refer to page 72. V-90HT is available on request subject to minimum production runs.

POWERLEX™ PVC HD CORDS GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV V-90 insulated and PVC sheathed heavy duty flexible cord to AS/NZS 3191.

Nominal conductor area mm 2

Maximum diameter of wires mm

Nominal overall diameter mm

Approximate mass

Product code

kg/100m

2C 0.75 1.0 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

0.75 1.0 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

0.75 1.0 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

1.0 1.5 2.5 4

0.21 0.21 0.21 0.31

8.0 8.3 9.3 11.0 12.7 2C+E 8.6 9.0 9.9 11.7 13.6 3C+E 9.5 9.9 10.9 12.9 15.0 4C+E 10.9 12.0 14.2 16.7

8 9 12 17 24

CBGR02AA002 CBGR03AA002 CBGR04AA002 CBGR05AA002 CBGR06AA002

10 11 14 21 30

EBGR02AA003 EBGR03AA003 EBGR04AA003 EBGR05AA003 EBGR06AA003

12 14 18 25 37

GBGR02AA004 GBGR03AA004 GBGR04AA004 GBGR05AA004 GBGR06AA004

18 23 32 50

BSBR03AA005 BSBR04AA005 BSBR05AA005 BSBR06AA005

Note: For core colour, flexible cords refer to page 72. Conductor stranding may vary according to production method and relevant Standard. V-90HT is available on request subject to minimum production runs.

29

POWERLEX™ PVC CORDS GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Other flexible cords to AS/NZS 3191.

Nominal conductor area mm

0.75 1.0 1.5 2.5 4

0.75 (2C) 0.75 (3C)

4

30

Maximum diameter of wires mm

Nominal overall diameter mm

Approximate mass

Product code

kg/100m

Single Core 0.6/1kV V-90 Insulated, Flexible Cord 0.21 2.7 1.3 0.21 2.9 1.6 0.21 3.2 2.1 0.21 3.8 3.3 0.31 4.6 5.2 2 and 3 Core 250/250V V-90 Insulated, PVC Sheathed LIGHT Duty Flexible Cord 0.21 5.4 4.3 0.21 5.8 5.4 2 Core 250/250V V-90 Insulated, PVC Sheathed LIGHT Duty Flat Flexible Cord 0.31 3.45.4 3.2

BAAR02AA001 BAAR03AA001 BAAR04AA001 BAAR05AA001 BAAR06AA001

CBER02AA002 EBER02AA003

CBLR02AA002*

Note: For core colour, flexible cords refer page 72. *2 core light duty flat cords supplied in red and white insulation, red sheath for fire alarm wiring systems.

VERSOLEX® HD SINGLE CORE GE

INDUSTRIAL

HIGH VOLTAGE

90°C

FIRE RATED

DATA/COMMS

MINING

110°C

90°C: 0.6/1kV cables, flexible X-90 (XLPE) insulated and TPE sheathed to AS/NZS 5000.1 (Power) and AS/NZS 1995 (Welding), copper conductors, 90°C. 110°C: 0.6/1kV cables, flexible, X-110 (XLPE) insulated and HFS-110-TP sheathed to AS/NZS 5000.1 (Power) and AS/NZS 1995 (Welding, copper conductors, 110°C continuous, LSOH. Nominal conductor area mm 2

Maximum diameter of wires mm

Nominal Approx. overall mass diameter mm kg/100m

Product code 90°C

Product code 110°C

10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

0.21 0.21 0.21 0.21 0.31 0.31 0.31 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

8.5 9.8 11.3 12.6 14.2 16.2 18.3 20.7 22.6 24.6 27.7 31.0 35.4 40.0 44.0

BDSX01AA001 BDSX02AA001 BDSX03AA001 BDSX04AA001 BDSX05AA001 BDSX06AA001 BDSX07AA001 BDSE87AA001 BDSE88AA001 BDSE89AA001 BDSE90AA001 BDSE91AA001 BDSE92AA001 BDSE93AA001 BDSE94AA001

BZHX01AA001 BZHX02AA001 BZHX03AA001 BZHX04AA001 BZHX05AA001 BZHX06AA001 BZHX07AA001 BZHE87AA001 BZHE88AA001 BZHE89AA001 BZHE90AA001 BZHE91AA001 BZHE92AA001 BZHE93AA001 BZHE94AA001

14 20 30 40 54 74 99 125 150 179 240 290 389 498 629

31

VERSOLEX® HD UNSCREENED GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV multicore cords & cables, flexible X-90 (XLPE) insulated and TPE sheathed to AS/NZS 3191 (cords) and where applicable AS/NZS 5000.1 (cables), copper conductors, 90°C. Nom. cond. area mm 2

Max. dia. of wires mm

Nom. ins. thick. mm

Nom. sheath thick. mm

Nom. overall dia. mm

Approx. mass

Product code

kg/100m

2C

0.75 1 1.5 2.5 4

0.21 0.21 0.21 0.21 0.31

0.7 0.7 0.7 0.7 0.7



0.75 1 1.5 2.5 4 6

0.21 0.21 0.21 0.21 0.31 0.31

0.7 0.7 0.7 0.7 0.7 0.7

0.75 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120

0.21 0.21 0.21 0.21 0.31 0.31 0.21 0.21 0.21 0.21 0.31 0.31 0.31 0.51

0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.2

32

1.3 7.6 1.3 7.9 1.5 8.9 1.7 10.2 1.8 11.6 3C (2C+E) 1.4 8.2 1.4 8.5 1.6 9.5 1.8 10.9 1.9 12.4 1.8 13.4 4C (3C+E or 3C+3E) 1.5 9.0 1.5 9.4 1.7 10.5 1.9 12.0 2.0 13.6 1.8 15.3 1.8 16.6 1.8 18.9 1.8 22.0 1.8 24.7 1.8 28.4 2.0 33.0 2.0 36.7 2.2 42.2

6.4 7.3 9.4 13 19

CFGR02AA002 CFGR03AA002 CFGR04AA002 CFGR05AA002 CFGR06AA002

7.7 8.8 12 16 23 30

EFGR02AA003 EFGR03AA003 EFGR04AA003 EFGR05AA003 EFGR06AA003 FEHR07AA003

9.4 11 14 20 29 38 50 72 108 147 205 279 371 464

GFGR02AA004 GFGR03AA004 GFGR04AA004 GFGR05AA004 GFGR06AA004 FTAR07AA003 FTAX01AA003 FTAX02AA003 FTAX03AA003 FTAX04AA003 FTAX05AA003 FTAX06AA003 FTAX07AA003 FTAE87AA003

Note: 3C and 4C suitable for fixed installation only beyond 4mm 2.

VERSOLEX® HD UNSCREENED GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV multicore cords & cables, flexible X-90 (XLPE) insulated and TPE sheathed to AS/NZS 3191 (cords) and where applicable AS/NZS 5000.1 (cables), copper conductors, 90°C. Nom. cond. area mm 2 0.75 1 1.5 2.5 4 6 10 16 25 35 50 70

Max. dia. of wires mm 0.21 0.21 0.21 0.21 0.31 0.31 0.21 0.21 0.21 0.21 0.31 0.31

Nom. ins. thick. mm

Nom. sheath thick. mm

Nom. overall dia. mm

0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1

5C (4C+E) 1.6 9.9 1.6 10.4 1.8 11.5 2.0 13.2 2.2 15.2 1.8 16.4 1.8 19.1 1.8 22.1 1.8 26.3 1.9 31.1 2.1 34.7 2.3 40.6

Note: Suitable for fixed installation only beyond 4mm 2.

Approx. mass

Product code

kg/100m 12 13 17 24 36 45 70 101 152 207 285 399

BWBR02AA005 BWBR03AA005 BWBR04AA005 BWBR05AA005 BWBR06AA005 BWBR07AA005 BWBX01AA005 BWBX02AA005 BWBX03AA005 BWBX04AA005 BWBX05AA005 BWBX06AA005

33

VERSOLEX® HD BRAID SCREENED GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV multicore cords & cables flexible X-90 (XLPE) insulated, TPE bedded, copper wire braid screened, TPE sheathed to AS/NZS 3191 (cords) and AS/NZS 5000.1 (cables), copper conductors, 90°C. Nom. cond. area mm 2

Max. dia. of wires mm

Nom. ins. thick. mm

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

0.21 0.21 0.31 0.31 0.21 0.21 0.21 0.21 0.31 0.31 0.31 0.50 0.50 0.50 0.50 0.50

0.7 0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8



0.21 0.21 0.31 0.31 0.21 0.21 0.21 0.21 0.31 0.31

0.7 0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1

1.5 2.5 4 6 10 16 25 35 50 70

34

Nom. dia. under braid mm

Nom. sheath thick. mm

Nom. overall dia. mm

4C (3C+E or 3C+3E) 9.1 1.7 13.9 10.2 1.9 15.2 11.6 2.0 17.0 13.8 1.8 18.7 15.0 1.8 20.0 17.4 1.8 22.8 20.5 1.8 26.0 23.2 1.8 28.9 27.1 1.8 32.9 31.1 1.9 37.6 35.2 2.1 41.9 40.2 2.2 47.7 44.7 2.3 52.5 49.7 2.5 57.9 55.8 2.6 64.5 62.0 2.9 69.7 5C (4C+E) 10.1 1.8 15.1 11.4 2.0 16.6 12.8 2.2 18.4 15.6 1.8 21.1 17.2 1.8 22.5 21.7 1.8 26.4 24.9 1.8 30.1 28.5 1.9 33.7 33.7 2.1 39.9 38.4 2.3 43.9

Approx. mass

Product code

kg/100m 24 31 41 42 66 96 137 174 237 331 428 526 642 756 988 1206

GETR04AA004 GETR05AA004 GETR06AA004 FTTR07AA003 FTTX01AA003 FTTX02AA003 FTTX03AA003 FTTX04AA003 FTTX05AA003 FTTX06AA003 FTTX07AA003 FTTE87AA003 FTTE88AA003 FTTE89AA003 FTTE90AA003 FTTE91AA003

28 36 46 63 83 124 143 247 344 406

BWTR04AA005 BWTR05AA005 BWTR06AA005 BWTR07AA005 BWTX01AA005 BWTX02AA005 BWTX03AA005 BWTX04AA005 BWTX05AA005 BWTX06AA005

TITANEX ® SINGLE CORE GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV cables, cross-linked synthetic EPR rubber insulated and sheathed, lead free. Copper conductors to DIN VDE 0295 class 5. Core identification to HD 308 S2.

Cross section mm 2

Perm. current rating open air A

Minimum outer diameter mm

Maximum outer diameter mm

Approx. mass

2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

32 43 56 77 102 136 168 203 254 315 363 416 475 559 637

6.3 7.2 7.2 9.5 10.8 12.7 14.3 16.5 18.6 20.8 22.8 25.2 27.6 30.6 33.5

7.9 9 9.8 11.9 13.4 15.8 17.9 20.6 23.3 26.0 28.6 31.4 34.4 38.3 41.9

66 94 109 182 256 369 482 662 895 1164 1430 1740 2160 2730 3480

Product code

kg/km HAR1X2.5 HAR1X4 HAR1X6 HAR1X10 HAR1X16 HAR1X25 HAR1X35 HAR1X50 HAR1X70 HAR1X95 HAR1X120 HAR1X150 HAR1X185 HAR1X240 HAR1X300

35

TITANEX ® MULTI CORE GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV cables, cross-linked synthetic EPR rubber insulated and sheathed, lead free. Copper conductors to DIN VDE 0295 class 5. Core identification to HD 308 S2. No. cores xcross section mm 2

36

Perm. current rating open air A

Minimum outer diameter mm

2x2.5 2x4 2x6 2x10 2x16 2x25

32 43 56 77 102 136

10.2 11.8 13.1 17.7 20.2 24.3

3 3 3 3 3 3 3

G G G G G G G

2.5 4 6 10 16 25 35

32 43 56 77 102 136 168

10.9 12.7 14.1 19.1 21.8 26.1 29.3

4 4 4 4 4 4 4 4 4 4 4

G G G G G G G G G G G

2.5 4 6 10 16 25 35 50 70 95 120

29 38 50 68 92 122 150 182 232 281 325

12.5 14 15.7 20.8 23.8 28.9 32.5 37.7 42.7 48.4 53

5 G 2.5 5 G 4 5 G 6

29 38 50

13.3 15.6 17.5

12 G 1.5

11

17.6

18 G 1.5

9

20.7

Maximum outer diameter mm 2C 13.1 15.1 16.8 22.6 25.7 30.7 2C+E 14 16.2 18 24.2 27.6 33 37.1 3C+E 15.5 18 20 26.5 30.1 36.6 41.1 47.5 54 61 66 4C+E 17 19.9 22.2 11C+E 22.14 17C+E 26.3

Approx. mass

Product code

kg/km 161 238 279 533 744 1074

HAR2X2.5 HAR2X4 HAR2X6 HAR2X10 HAR2X16 HAR2X25

195 290 346 663 924 1345 1760

HAR3G2.5 HAR3G4 HAR3G6 HAR3G10 HAR3G16 HAR3G25 HAR3G35

245 357 443 818 1150 1700 2180 3030 3990 5360 6500

HAR4G2.5 HAR4G4 HAR4G6 HAR4G10 HAR4G16 HAR4G25 HAR4G35 HAR4G50 HAR4G70 HAR4G95 HAR4G120

297 453 557

HAR5G2.5 HAR5G4 HAR5G6

510

HAR12G1.5

730

HAR18G1.5

FLEXOLEX® HD UNSCREENED GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV cords and cables R-EP-90 (EPR) insulated and CPE sheathed to AS/NZS 3191 (cords) and AS/NZS 5000.1 (cables), bunched tinned copper conductors, 90°C, for flexible applications. Nominal conductor area mm 2

0.75 1.0 1.5 2.5 4

Maximum diameter of wires mm

Nominal insulation thickness mm

0.21 0.21 0.26 0.26 0.31

0.8 0.8 0.8 0.9 1.0

1.5 2.5 4 6 10 16 25

0.26 0.26 0.31 0.31 0.41 0.41 0.41

0.8 0.9 1.0 1.0 1.2 1.2 1.4

1.5 2.5 4 6 10 16 25 35

0.26 0.26 0.31 0.31 0.41 0.41 0.41 0.41

0.8 0.9 1.0 1.0 1.2 1.2 1.4 1.4

Nominal sheath thickness mm 2C+E 1.4 1.4 1.6 1.8 1.9 3C+E 1.7 1.9 2.0 2.2 3.4 3.6 4.0 4C+E 1.8 2.0 2.2 2.4 3.6 3.8 4.3 4.6

Nominal overall diameter mm

Approx. mass

Product code

kg/100m

8.8 9.1 10.5 12.5 13.5

11 12 15 22 31

RDER52AA003 RDER53AA003 RDER54AA003 RDER55AA003 RDER56AA003

11.5 13.5 15.5 18.0 24.4 27.4 32.9

19 27 39 53 94 130 198

RDER54AA004 RDER55AA004 RDER56AA004 RDHR57AA004 RDHR58AA004 RDHR59AA004 RDHR60AA004

12.3 14.5 17.5 20.0 26.8 30.2 36.4 40.6

23 33 48 65 115 159 244 309

RDER54AA005 RDER55AA005 RDER56AA005 RDHR57AA005 RDHR58AA005 RDHR59AA005 RDHR60AA005 RDHR61AA005

Note: Other sizes and conductor configurations are available upon request.

37

FLEXOLEX® HD SCREENED GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

0.6/1kV cords and cables R-EP-90 (EPR) insulated, EPR bedded, tinned copper wire braid screened, CPE sheathed to AS/NZS 3191 (cords) and AS/NZS 5000.1 (cables), tinned copper conductors, 90°C, for flexible applications. Nominal conductor area mm 2

Maximum Nominal diameter insul. of wires thick. mm mm

Nominal sheath thick. mm

1.5 2.5 4 6 10 16

0.26 0.26 0.31 0.31 0.41 0.41

0.8 0.9 1.0 1.0 1.2 1.2

1.8 1.9 2.2 2.4 3.5 3.8

1.5 2.5 4 6 10 16

0.26 0.26 0.31 0.31 0.41 0.41

0.8 0.9 1.0 1.0 1.2 1.2

1.9 2.1 2.3 2.5 3.7 4.0

38

Nominal Nominal Approx. dia. under overall mass braid diameter mm mm kg/100m 3C+E 9.6 11.2 13.1 15.3 19.2 21.8 4C+E 10.5 12.3 14.4 16.9 21.2 24.2

Product code

14.6 16.4 18.9 21.8 28.4 31.6

30 39 54 74 123 164

RDLR54AA004 RDLR55AA004 RDLR56AA004 RDXR57AA004 RDXR58AA004 RDXR59AA004

15.7 17.9 20.4 23.9 30.8 34.4

35 47 64 89 147 195

RDLR54AA005 RDLR55AA005 RDLR56AA005 RDXR57AA005 RDXR58AA005 RDXR59AA005

Note: Other sizes are available upon request.

VAROLEX® VSD/EMC GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Fixed conductor variable speed drive cables. 0.6/1kV X-90 (XLPE) insulated, 3 core +3 earths, PVC bedded, copper tape screened, PVC sheathed to AS/NZS 5000.1, copper conductors, 90°C. Nominal conductor area mm 2

Nomimal insulation thickness mm

Combined earth size area mm 2

Nominal dia. over screen mm

Nominal Approx. overall mass diameter mm kg/100m

Product code

2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

0.7 0.7 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8

2.5* 4.5 4.5 4.5 7.5 12 18 30 30 48 48 75 75 105 150

10.9 13.0 13.8 14.8 17.0 19.2 21.9 25.1 28.1 33.9 38.9 42.6 47.5 53.6 59.6

14.6 16.6 17.5 18.5 20.6 22.8 25.6 28.8 32.0 38.0 43.2 47.3 52.0 58.9 65.2

FTDP07AA003 FTDP09AA003 FTDP11AA003 FTDP13AA003 FTDP15AA003 FTDC17AA003 FTDC18AA003 FTDC19AA003 FTDC20AA003 FTDC22AA003 FTDP23AA003 FTDP24AA003 FTDP25AA003 FTDP26AA003 FTDP27AA003

*Split earth not feasible, therefore a single earth conductor is utilised.

32 44 51 62 86 121 160 211 277 390 467 585 711 918 1154

39

PVC FLEXIBLE CONTROL GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

300/500V cables, flexible PVC insulated and PVC sheathed to DIN VDE 0281 part 1 and HD 21.1, PVC self extinguishing and flame retardant, copper conductors. Flexing –5°C to 80°C, fixed –40°C to 80°C. Min. bending radius 7.5xcable o.d. Number cores xcross section mm 2

Nomimal diameter

Approximate mass

mm

Product code

kg/km 2C+E

3 3 3 3 3

G G G G G

0.5 0.75 1 1.5 2.5

5.1 5.5 6 6.7 8.3

4 4 4 4

G G G G

0.5 0.75 1 1.5

5.7 6.2 6.6 7.3

5 5 5 5 5

G G G G G

0.5 0.75 1 1.5 2.5

6.2 6.8 7.2 8.2 10.2

7 7 7 7 7

G G G G G

0.5 0.75 1 1.5 2.5

7.4 8.1 8.6 9.8 12.1

46 54 72 90 148

CC3G0.5 CC3G0.75 CC3G1 CC3G1.5 CC3G2.5

56 66 86 109

CC4G0.5 CC4G0.75 CC4G1 CC4G1.5

65 80 104 131 221

CC5G0.5 CC5G0.75 CC5G1 CC5G1.5 CC5G2.5

80 110 141 184 306

CC7G0.5 CC7G0.75 CC7G1 CC7G1.5 CC7G2.5

3C+E

4C+E

6C+E

40

Note: Black cores with continuous white numbering according to DIN VDE 0293. Not suitable for open air applications. G = green-yellow earth core.

PVC FLEXIBLE CONTROL GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

300/500V cables, flexible PVC insulated and PVC sheathed to DIN VDE 0281 part 1 and HD 21.1, PVC self extinguishing and flame retardant, copper conductors. Flexing –5°C to 80°C, fixed –40°C to 80°C. Min. bending radius 7.5xcable o.d. Number cores xcross section mm 2

Nomimal diameter

Approximate mass

mm

Product code

kg/km 11C+E

12 12 12 12 12

G G G G G

0.5 0.75 1 1.5 2.5

9.1 9.9 10.7 12.1 15.2

18 18 18 18

G G G G

0.5 0.75 1 1.5

10.7 11.9 12.7 14.5

25 25 25 25

G G G G

0.5 0.75 1 1.5

13 14.5 15.6 17.8

135 179 230 309 498

CC12G0.5 CC12G0.75 CC12G1 CC12G1.5 CC12G2.5

196 257 343 440

CC18G0.5 CC18G0.75 CC18G1 CC18G1.5

270 365 485 620

CC25G0.5 CC25G0.75 CC25G1 CC25G1.5

668

CC36G1

936

CC50G1

17C+E

24C+E

35C+E 36 G 1

17.4 49C+E

50 G 1

19.1

Note: Black cores with continuous white numbering according to DIN VDE 0293. Not suitable for open air applications. G = green-yellow earth core.

41

PVC/EMC FLEXIBLE CONTROL GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

300/500V cables, flexible PVC insulated, tinned copper braided with transparent PVC sheath, copper conductors to DIN VDE 0295 class 5 and IEC 60228 class 5. Flexing –5°C to 80°C, fixed –40°C to 80°C. Min. bending radius 10xcable o.d. Number cores xcross section mm 2

Nomimal diameter

Approximate mass

mm

Product code

kg/Km 2C+E

3 3 3 3 3

G G G G G

0.5 0.75 1 1.5 2.5

7.2 7.8 8.2 9 10.7

4 4 4 4 4

G G G G G

0.5 0.75 1 1.5 2.5

7.8 8.3 8.9 9.6 11.4

5 5 5 5 5 5

G G G G G G

0.5 0.75 1 1.5 2.5 4

8.3 9.1 9.5 10.5 12.5 14.8

7 7 7 7

G G G G

0.5 0.75 1 1.5

9.5 10.4 11 12.1

83 98 103 152 216

CY3G0.5 CY3G0.75 CY3G1 CY3G1.5 CY3G2.5

94 113 146 168 267

CY4G0.5 CY4G0.75 CY4G1 CY4G1.5 CY4G2.5

108 130 169 202 347 502

CY5G0.5 CY5G0.75 CY5G1 CY5G1.5 CY5G2.5 CY5G4

136 184 219 304

CY7G0.5 CY7G0.75 CY7G1 CY7G1.5

195 292 350

CY12G0.5 CY12G0.75 CY12G1

3C+E

4C+E

6C+E

11C+E 12 G 0.5 12 G 0.75 12 G 1

42

11.3 12.5 13.1

Note: Black cores with continuous white numbering according to DIN VDE 0293. G = green-yellow earth core.

Silicone Single Core GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

500V cables, fixed or flexible conductor silicone insulated with or without glass fibre braiding, halogen free to IEC 60754-2, tinned copper conductors, fixed –60°C to 180°C. Min. bending radius 15xcable o.d. Number cores xcross section mm 2

Nomimal diameter mm

kg/km

1 1 1.5 1.5 2.5 2.5 4 4 6 6

2.5 2.5 2.8 2.8 3.4 3.4 4.2 4.2 5.2 5.2

13.5 13.5 18.5 18.5 30 30 47.3 47.3 71.1 71.1

Note: G = green-yellow earth core.

Approximate mass

Product code

SIF2351BK SIF2351RD SIF2361.5BK SIF2361.5RD SIF2372.5BK SIF2372.5RD SIF2384BK SIF2384RD SIF2396BK SIF2396RD

43

Silicone Multicore GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

300/500V cables, silicone insulated, silicone sheathed, halogen free to IEC 60754-2, tinned copper conductors, fixed –60°C to 180°C (peak 220°C). Min. bending radius 7.5xcable o.d. Number cores xcross section mm 2

Nomimal diameter mm

kg/km

2 x1 3 G 1 4 G 1 5 G 1 7 G 1 12 G 1 3 G 1.5 4 G 1.5 5 G 1.5 3 G 2.5 4 G 2.5 5 G 2.5

6.6 7.4 8 8.8 9.5 11.5 8 8.8 9.6 9.7 10.6 11.6

59 77 94 115 144 231 98 122 147 152 188 228

44

Approximate mass

Note: G = Green-yellow earth core 2 Core = Brown/Blue 3 Core = Brown/Blue/Green-Yellow 4 Core = Brown/Blue/Black/Green-Yellow 5 Core = Brown/Blue/Black/Grey/Green-Yellow 6 Core & above = Black cores with white numbering

Product code

SF2X1 SF3G1 SF4G1 SF5G1 SF7G1 SF12G1 SF3G1.5 SF4G1.5 SF5G1.5 SF3G2.5 SF4G2.5 SF5G2.5

INSTROLEX® INSTRUMENTATION GE

INDUSTRIAL

HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Plain annealed copper conductor, V-90 RP PVC insulated, twisted pairs, overall screened with aluminium polyester tape plus tinned annealed copper drain wire, rip cord, 5V-90 RP PVC sheathed. Number and Number nominal diameter of pairs of wires No./mm 7/0.30 7/0.50 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30

Nominal outside diameter mm

Approximate mass

Product code

kg/100m

Single Pair – Screened 1 5.2 3.5 1 6.6 6.0 Overall Screened Pairs 2 7.8 6.3 4 8.4 9.4 6 10.0 13 8 11.2 17 10 12.5 21 12 13.4 24 16 15.1 31 20 16.8 38 24 18.1 45 36 22.0 66 50 25.6 90 Individually and Overall Screened Pairs 2 8.1 7.3 4 10.4 12 6 12.2 17 8 13.9 22 10 14.6 26 12 16.0 31 16 18.0 39 20 20.1 48 24 21.9 57 36 26.3 83 50 30.6 112

Note: 1 . A complete range of 7/0.50 pairs is available. 2. 7/0.30 is equivalent to 20 AWG. 3. 7/0.50 is equivalent to 16 AWG.

IEB183AA001 IEB184AA001 IEC183AA002 IEC183AA004 IEC183AA006 IEC183AA008 IEC183AA010 IEC183AA012 IEC183AA016 IEC183AA020 IEC183AA024 IEC183AA036 IEC183AA050 IED183AA002 IED183AA004 IED183AA006 IED183AA008 IED183AA010 IED183AA012 IED183AA016 IED183AA020 IED183AA024 IED183AA036 IED183AA050

45

GE

INDUSTRIAL

INSTROLEX® INSTRUMENTATION SWA HIGH VOLTAGE

FIRE RATED

DATA/COMMS

MINING

Plain annealed copper conductor, V-90 RP PVC insulated, twisted pairs, overall or individually and overall screened with aluminium polyester tape plus tinned annealed copper drain wire, rip cord, PVC bedding, steel wire armour, 5V-90 RP PVC sheathed. Number & nom. dia. of wires No./mm 7/0.50 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.30 7/0.50 7/0.50 7/0.30 7/0.30 7/0.30

46

No. of pairs (or triples where applicable)

Nominal dia. over bedding mm

Nominal dia. over armour mm

Nominal outside diameter mm

Single Pair Screened – SWA 1 6.2 8.0 10.2 Overall Screened Pairs – SWA 2 7.4 9.2 11.4 4 8.0 9.8 12.0 6 9.4 11.2 13.6 8 10.6 12.4 14.8 10 11.7 13.5 16.1 12 12.6 14.4 17.0 16 14.3 16.1 18.9 Individually & Overall Screened Pairs – 2 7.7 9.5 11.7 4 9.8 11.6 14.0 6 11.6 13.4 16.0 8 13.1 14.9 17.5 10 13.8 15.6 18.2 Single Triple Screened 1 6.9 Single Triple Screened – SWA 1 6.6 8.4 10.6 Overall Screened Triples 4 10.0 6 11.7 12 16.1

Note: Other pair and triple counts available. 7/0.50 SWA pairs and triples available.

Approx. Product mass code kg/100m 22

IEF184AA001

25 28 36 42 48 54 65 SWA 26 35 45 52 58

IEG183AA002 IEG183AA004 IEG183AA006 IEG183AA008 IEG183AA010 IEG183AA012 IEG183AA016

7.8

IEH183AA002 IEH183AA004 IEH183AA006 IEH183AA008 IEH183AA010 IGB184AA001

24

IGF184AA001

13 19 35

IGC183AA004 IGC183AA006 IGC183AA012

RATED

FIRE PERFORMANCE

OMMS

DATA /COMMS

INING

MINING The cables Australians trust to stay safe and secure have a new name – Alsecure. ®

Alsecure® is now the name to specify for the cables you’ve always relied on for safety and security – to maintain circuit integrity for lighting, alarms, pumps, process applications and other essential services, even under fire.

47

AGE

ALSECURE® PREMIUM CERAMIFIABLE® SINGLE CORE FLEX

FIRE RATED

DATA/COMMS

MINING

0.6/1kV, single conductor, Stranded Flexible (Class 6) AS/NZS 1125 Plain Annealed Copper conductor, INFIT™(Ceramifiable®) R-HF-110 to AS/NZS 3808) Insulated, (HFFR) Halogen Free Flame Retardant HFS-110-TP to AS/NZS 3808) Sheathed and to AS/NZS 5000.1, 110°C, WS52W Fire Rated to AS/NZS 3013:2005. Nom. Nom. Nom. cond. insul. sheath cross thick. thick. section area mm mm 2 mm

Nom. Approx. overall mass cable diameter mm

kg/100m mm

kN

10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

9.4 10.4 12.0 13.6 15.6 17.3 19.6 21.7 23.8 26.4 29.6 32.7 36.6 41.9 45.6

18 24 35 45 61 82 109 131 160 194 255 310 398 517 657

0.2 0.3 0.5 0.8 1.1 1.5 2.1 2.6 3.3 4.0 5.2 6.5 8.7 10.9 13.7

1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8

1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2

Min. bending Max. radius during pulling installation tension

55 60 70 80 95 105 120 130 145 160 180 195 220 250 275

Colours – insulation white (natural), outer sheath red only.

48

Product code

PEKX01AA001 PEKX02AA001 PEKX03AA001 PEKX04AA001 PEKX05AA001 PEKX06AA001 PEKX07AA001 PEKX08AA001 PEKX09AA001 PEKX10AA001 PEKX11AA001 PEKX68AA001 PEKX69AA001 PEKX70AA001 PEKX71AA001

AGE

FIRE RATED

ALSECURE® PREMIUM CERAMIFIABLE® MULTICORE DATA/COMMS

MINING

Multicore ES90. Copper conductor 0.6/1kV INFIT™(Ceramifiable®) HFI-90-TP to AS/ANZ 3808 Insulated, (HFFR) Halogen Free Flame Retardant HFS-90-TP to AS/NZS 3808 sheathed, and to AS/NZS 5000.1, 90ºC. WS52W fire rated to AS/NZ 3013:2005.

Number of cores

Nominal conductor cross section area mm 2

Nominal insulation thickness

Nominal sheath thickness

Nominal overall diameter

Approx. mass

mm

mm

mm

kg/100m

10.6 11.1 12.0 10.7 11.2 12.1 11.3 11.8 11.8 12.8 12.7 14.0 12.3 13.0 13.0 14.0 13.8 13.4 13.8 14.1 15.0 16.4

14.1 16.0 18.6 14.2 16.1 18.7 17.0 19.0 19.0 22.0 20.7 30.0 21.0 25.0 25.0 30.0 26.0 26.0 29.0 31.2 36.0 43.0

Product code

90°C 2 3 4 2 3 4 2 2+E 3 3+E 4 4+E 2 2+E 3 3+E 4+E 2 2+E 3 3+E 4+E

0.75 0.75 0.75 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 4.0 4.0 4.0 4.0 4.0

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

PEKE99AA002 PEKE99AA003 PEKE99AA004 PEKP03AA002 PEKP03AA003 PEKP03AA004 PEKP05AA002 PDKP05AA002 PEKP05AA003 PDKP05AA003 PEKP05AA004 PDKP05AA004 PEKP07AA002 PDKP07AA002 PEKP07AA003 PDKP07AA003 PDKP07AA004 PEKP09AA002 PDKP09AA002 PEKP09AA003 PDKP09AA003 PDKP09AA004

Colours – insulation see core chart, outer sheath red only.

49

AGE

FIRE RATED

ALSECURE® PREMIUM CERAMIFIABLE® MULTICORE DATA/COMMS

MINING

Multicore ES110. Copper conductor 0.6/1kV INFIT™(Ceramifiable®) R-HF-110 to AS/ANZ 3808 Insulated, (HFFR) Halogen Free Flame Retardant HFS-110-TP to AS/NZS 3808 sheathed, and to AS/NZS 5000.1, 90ºC. WS52W fire rated to AS/NZ 3013:2005.

Number of cores

Nominal conductor cross section area mm 2

Nominal insulation thickness

Nominal sheath thickness

Nominal overall diameter

Approx. mass

mm

mm

mm

kg/100m

14.7 16.0 17.6 16.3 17.9 19.7 20.1 22.2 22.6 25.0 25.3 28.0 32.3

35 44 53 48 60 74 84 103 117 145 156 195 265

Product code

110°C 2+E 3+E 4+E 2+E 3+E 4+E 3+E 4+E 3+E 4+E 3+E 4+E 4+E

6 6 6 10 10 10 16 16 25 25 35 35 50

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.2 2.0

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0

Colours – insulation see core chart, outer sheath red only.

50

PDKP11AA002 PDKP11AA003 PDKP11AA004 PDKP13AA002 PDKP13AA003 PDKP13AA004 PDKP15AA003 PDKP15AA004 PDKP17AA003 PDKP17AA004 PDKP18AA003 PDKP18AA004 PDKP19AA004

AGE

FIRE RATED

ALSECURE® PREMIUM CERAMIFIABLE® INSTRUMENTATION & DATA DATA/COMMS

MINING

Alsecure® Premium with INFIT™ Cermifiable® Instrumentation and Data are a range of (HFFR) Halogen Free Flame Retardant multipair cable rated to WS51W under fire test standard AS/NZ 3013:2005. These new cables are the only fire rated multipair product available that do not require glass-mica tapes, thus reducing installation time and eliminating the need for respirators and special gloves. Number Nominal Approx. of diameter mass pairs kg/100m mm 2 1 2 4 6 8 10 12 16 20 24

7.8 12.2 13.5 16.3 18.6 20.4 22.3 25.5 28.3 30.9

6.6 13.0 20.5 29.3 38.2 46.2 55.0 71.7 88.5 105.2

1 2 4 6 8 10 12 16 20 24

8.4 13.2 14.7 17.6 20.2 22.4 24.5 28.0 31.1 33.9

8.0 15.8 25.6 36.9 48.2 59.6 71.0 92.7 114.5 136.2

Minimum bending radius during installation mm

Conductor 0.75mm 2 115 185 200 240 280 310 340 380 430 460 Conductor 1.5mm2 125 200 220 270 300 340 370 420 470 500

Maximum pulling tension kN

Product code

0.06 0.12 0.24 0.36 0.48 0.60 0.72 0.96 1.20 1.40

PBKP03AA001 PBKP03AA002 PBKP03AA004 PBKP03AA006 PBKP03AA008 PBKP03AA010 PBKP03AA012 PBKP03AA016 PBKP03AA020 PBKP03AA024

0.12 0.24 0.48 0.72 0.96 1.20 1.40 1.90 2.40 2.90

PBK184AA001 PBK184AA002 PBK184AA004 PBK184AA006 PBK184AA008 PBK184AA010 PBK184AA012 PBK184AA016 PBK184AA020 PBK184AA024

Colours – insulation natural/black, outer sheath red only.

51

MMS

DATA/COMMS

NING

MINING

Designed for the future. The Olex range of data and communications cables are designed to meet the needs of customers today and in the future. Our comprehensive Datolex range has been specifically designed with the installer in mind while our Audiolex cables will provide you with superior home theatre. The Gardolex range of extra low voltage cables make garden lighting simple, reliable and economical.

D

SECURITY DATA/COMMS

MINING

Unscreened Security Number of conductors

Nominal conductor area mm 2

4 6

0.22 0.22

4 6 8

0.50 0.50 0.50

Nominal Approx. overall mass diameter mm kg/100m 7/0.20mm Conductor 3.6 1.4 4.9 3.1 14/0.20mm Conductor 4.7 3.2 5.6 4.7 6.5 5.8

Max. DC resistance @20°C Ohms/km

Product code

86.5 86.5

JSC.2xx4C* JSC.2xx6C*

44.5 44.5 44.5

JSC.5xx4C* JSC.5xx6C* JSC.5WT8C*

xx Sheath colour: GY Grey; WT White. *Pack size: 1 – 100m spool; B – 300m box; C – 250m spool (JSC.5xx6C only); 5 – 500m spool; B2 – 200m box (JSC.5xx6C only). Insulation colours: 4C – Red, Black, White, Blue; 6C – Red, Black, White, Blue, Green, Yellow. 8C – Red, Blue, White, Black, Yellow, Green, Violet, Brown.

Screened Security Number of conductors

Nominal conductor area mm 2

Nominal Approx. overall mass diameter mm kg/100m

Max. DC resistance @20°C Ohms/km

Product code

2 pair• 2 pair•

0.35 0.35

7/0.25mm Conductor 4.2 2.8 4.3 2.9

55.0 55.0

JD2PIS † JD2PISFPA3

*Pack size: 1 – 100m spool; B – 300m box (JD2PIS only); A3 – 300m spool (JD2PISFPA3 only); 5 – 500m spool. Note: Grey PVC Sheath, 7/0.20mm T/C drain wire. •Individually screened pairs. Also available in jelly filled version JD2PISFP3). Insulation colours: 4C – Red, Blue, White, Black; 7C – Red, Blue, White, Black, Orange, Yellow, Green; 2 Pair – Black and Red, Green and White. † Polypropylene insulated.

53

Nom. cond. area mm 2 0.35 0.22 0.75 6.2 1.5 0.5 0.22 0.54

Nom. Stranding Approx. mass overall dia. for cable mm No./mm kg/100m 4.3 7/0.25 3 5.3 1/0.50 3.2 3.0x6.0 24/0.20 3.1 – 1/0.60 5.5 5.3 7/0.50 5 4.7 14/0.20 3.4 5.5 7/0.20 4.7 6.0 1/0.54 –

54

1

7.03.4 9.04.5

2.0 2.6

Max. volt. drop @ mV/A.m

23.9 16.3

97.8 57.1

Product code JTS1.2VT2CA3 JTS2.5VT2C* JTS1.2VT4CA3

Pack size B A, B B

0.8 1.0

0.5 0.8

A, C A

A, C A, B, C

Insul. Pack thick. size mm

JSF2.OCL* JSF2.6CL1

JSF.5xx* JSF.75xx*1

Product code

Pack sizes – A-100m; B-300m spool.

Nom. cond. res. @ 20°C ohm/km 17.2 7.80 17.2

Rated voltage ELV. 2 One plain copper & one tinned copper conductor. Pack sizes – A – 100m spool; B – 250m spool; C – 300m spool.

64/0.20 84/0.20

5.2 8.1

2.0 3.0

14/0.20 24/0.20

4.31.8 5.92.9

0.5 0.75

Maximum DC resistance Ohms/km Standard 44.5 26.0 Oxygen Free Copper 10.9 7.4

Approx. mass area kg/100m

Nom. cond. Nominal Stranding area overall 2 mm size mm No./mm

Product code

Grey 300m box JD2PISLSOHB30 Black 300m reel JCAT5ELSZHA3 White/blk stripe 100m reel JSF.75WTBKLSOH1 Black 100m reel JBCRG59CCTVLSOH Red 300m reel JRS1502A3LSOH White 300m box JSC.5WT4LSOHB30 Grey 300m box JD6CSLSOH Grey 300m box JCAT6LSOH

Sheath Pack size colour

No. of Nom. cond. Stranding Approx. Nom. insul. Nom. overall cores area mass thickness diameter mm 2 No./mm kg/100m mm mm 1.2 70/0.15 5.8 2.2 6.5 2 2 2.5 140/0.15 10 3.3 8.5 4 1.2 70/0.15 8.6 2.2 6.9 Figure 8

Max. cond. res. @ 20°C ohm/km 55 93.8 26.4 62 13.6 45.2 95.3 89

DATA/COMMS

Audiolex Oxygen Free Copper Audio

No. of cores/ pairs 2 pairs 4 pairs N/A N/A 2 cores 4 cores 6 cores 4 pairs

LSOH (Low Smoke, Zero Halogen)

D

SECURITY/AUDIO MINING

*Only in blue.

– –

– – –

✓ –

– ✓ –

– ✓

✓ – ✓









✓*



JCAT6LSOH

JCAT6FPA3

JCAT6

JCAT5ESCRB30

JCAT5ELSZHA3

JCAT5EFPA3

JCAT5Exx

DATA/COMMS

Category 5E – Solid 4 0.22 5.3 1/0.50 3.2 N/A 93.8 100 51 Blue, Green, Grey, Red, Yellow Category 5E – Underground 4 0.22 5.7 1/0.50 3.2 N/A 93.8 100 51 Black Category 5E – Low Smoke Zero Halogen (LSOH) 4 0.22 5.3 1/0.50 3.2 N/A 93.8 100 51 Black Category 5E – Screened 4 0.22 5.3 1/0.50 5 Aluminium 93.8 100 50 Grey Foil + DW Category 6 4 0.22 6.3 1/0.50 4.5 N/A 93.8 100 51 Blue, Grey Category 6 – Underground 4 0.22 6.3 1/0.54 4.15 N/A 93.8 100 51 Black Category LSOH 4 0.54 6.0 1/0.54 – N/A 89 100 Grey

Maximum Nom. Mutual Sheath Pack Product conductor impedence capacitance colour sizes code resistance @ 20°C 300m 300m 305m ohm/km ohms pF/m box spool spool

Bare copper conductor, polyolefin insulated, twisted pairs, PVC sheathed, compatible with RJ type connector.

No. of Nominal Nominal Stranding Approximate Shielding pairs conductor overall mass area diameter mm No./mm kg/100m mm2

D

LAN MINING

55

56

5.0

19/0.18 T/C

4.2

95% T/C

1/0.60 1/0.60

5.2 6.0

RG59 – Closed Circuit Television (CCTV) 86% B/C Braid Solid PE 62.2 67 95% B/C Braid Solid PE 62.2 67

Pack sizes: A – 100m spool; B – 250m spool; C – 300m box; D – 500m spool. Composite cables: RG59 Coaxial and Figure 8 cables available on request.

6.1 6.2

Max. cond. Nom. resistance cap. @ 20°C Ohm/km pF/m

101

66 66

Nom. velocity prop. %

66

A, B, D A, C, D

Pack size

A, B

Max. cond. Nom. Nom. Pack resistance cap. velocity size @ 20°C prop. Ohm/km pF/m %

Coaxial 50 Ohm Solid PE 32.6

Nom. Stranding Approx. Shielding Dielectric overall mass diameter mm No./mm kg/100m

Coaxial 75 Ohm

Pack sizes: A – 100m spool; B – 500m spool.

RG58

Nom. Stranding Approx. Shielding Dielectric overall mass diameter mm No./mm kg/100m

JBCRG59BUCCTV JBCRG59PREM

Product code

JBCRG58CUMIL1

Product code

DATA/COMMS

Type

Coaxial 50 Ohm

D

COAXIAL MINING



5.1

8.7

4.5

1/1.0

1/1.63

1/1.0

RG6 – TV Downlead Premium/Antenna Al Foil, 60% Braid. Al Foil, 40% Braid Foamed PE 100 RG11 – Internal use Al Foil, 60% Braid. Al Foil, 40% Braid Foamed PE 36.1 Air Space Al Foil, 35% B/C Braid Air Space PE 22.4

Pack sizes: A – 100m spool; B – 300m spool; C – 300m box; D – 305m spool.

6.6

10.3

7.5

55

53

53

Max. cond. Nom. resistance cap. @ 20°C Ohm/km pF/m

82

83

84

Product code

A

D

JBCTVCOAX1

JBCRG11QUAD

A, B, C JBCRG6QUAD

Nom. Pack velocity size prop. %

DATA/COMMS

Nom. Stranding Approx. Shielding Dielectric overall mass dia. mm No./mm kg/100m

Coaxial 75 Ohm

D

COAXIAL MINING

57

D

OPTICAL FIBRE DATA/COMMS

MINING

Nylon Underground Description Nom. Approx. O.D. mass mm kg/100m

Max. Min. bending Product pulling radius mm code tension During kN installation installed

Single Mode (0S1) 8.5 6.0 1.5 170 8.5 6.0 1.5 170 11.0 9.5 2.3 220 Multi Mode (0M1) 62.5/125µm MM 6 Fibre 8.5 6.0 1.5 170 62.5/125µm MM 8 Fibre 8.5 6.0 1.5 170 62.5/125µm MM 12 Fibre 8.5 6.0 1.5 170 62.5/125µm MM 24 Fibre 11.0 9.5 2.3 220 Multi Mode (0M3) 50/125µm MM 12 Fibre 8.5 6.0 1.5 170 10/125µm SM 6 Fibre 10/125µm SM 12 Fibre 10/125µm SM 24 Fibre

58

85 85 110

FIB06SMJN FIB12SMJN FIB24SMJN

85 85 85 110

FIB06MMJN FIB08MMJN FIB12MMJN FIB24MMJN

85

FIB120M3JN

Options Fibre counts up to 324 fibre are available upon request for loose tube cables Corrugated Steel Tape (CST) Armouring Composite (combination of single and multi mode) ADSS (All Dielectric Self Supporting) Sacrificial Sheath Low Smoke Zero Halogen (LSZH) outer sheath Rodent Resistance Note: Minimum order quantity applies to these options. The OS1 fibre is specified to ITU-T G652.D (low water peak).

D

TELEPHONE INTERNAL DATA/COMMS

MINING

Internal, PVC Insulated, PVC Sheath Pairs

Nominal overall diameter mm

Wire size

Approx. mass

mm

kg/100m



4.1 4.6 8.5 11.2 12.8 17.0

0.5 0.5 0.5 0.5 0.5 0.5

1.3 2.6 7.6 15.0 18.0 34.0

2 3 10 20 25 50

Sheath colour

Product code

Cream Cream Grey Grey Grey Grey

TINT002 TINT003 TINT010 TINT020 TINT025 TINT050

Note: 2 pair and 3 pair available in 100 metre and 300 metre spools. 10 pair available in 200 and 500 metre spools (no cuts). 20 pair and above available in bulk drum (will cut to length).

Telephone Jumper Wire Pairs

Nominal overall diameter mm

Wire size

Approx. mass

mm

kg/100m

2 core

1.0 1.9

0.5

0.5

*Pack Size.

Sheath colour

Product code

Red & White

JUMPRW*

59

D

TELEPHONE EXTERNAL DATA/COMMS

MINING

Aerial Pairs

Nominal overall size mm

1 10

7.94.9 16.012.0

Max. conductor Approx. resistance mass @ 20°C Ohm/km kg/100m 0.64mm Diameter Conductor 58.6 4.0 58.6 19

Product code

TEXT64IB001A5 TEXT64IB010*

*Includes aluminium foil screen over the twisted pair. These cables are not power cables or for direct connection of equipment to mains power supplies.

External No. of pairs 10 20 50 2

2

10 30 50 100

Nominal Wire Approx. overall size mass diameter kg/100m mm mm

Max. cond. Pack Product resistance size code @ 20°C Ohm/km

Jelly Filled, Polyethylene Sheath 0.40 5.6 150 B 0.40 10.0 150 B 0.40 25.0 150 B 0.64 3.1 58.6 A Jelly Filled, Polyethylene/Nylon Sheath 9 0.90 9 27.9 B Jelly Filled, Moisture Barrier Polyethylene/Nylon 14.1 0.90 25 27.9 B 21.25 0.90 63 27.9 B 27.29 0.90 104 27.9 B 36.8 0.90 204.0 27.9 B 7.0 8.59.5 12.8 5.7

Pack sizes: A – 500m spool; B – Bulk drum (i) Telstra Approved.

60

TEXT40FP010 TEXT40FP020 TEXT40FP050 TEXT64FP002A5 TEXT90FN002AA Sheath TEXT90FMBN010AA(i) TEXT90FMBN030AA(i) TEXT90FMBN050AA(i) TEXT90FMBN100AA

7 9 10 12 16 25

4.08.6 4.06.7 4.09.35 5.010.4 6.012.5 6.713.9

26/0.25 26/0.30 76/0.20 56/0.30 81/0.30 348/0.20

1.3 1.8 2.5 4.0 6.0 10

*Pack sizes. Note: This cable is non divisible.

2 2 2 2 2 2

Nominal Approx. overall mass size mm kg/100m

Nominal Stranding conductor area No./mm mm 2 15.3 9.7 8.0 4.95 3.30 1.91

Max DC resistance @ 20°C ohm/km 33.6 20.7 17.6 10.9 7.25 4.20 ✓ ✓ ✓ ✓ ✓ ✓

✓ – – – – –

Voltage drop Pack sizes single phase @ 45°C 100m 200m mV/A.m spool spool JSF1.3GLBK* JTS1.8BK2C* JSF2.5GLBK* JSF4GLBK* JSF6GLBK* JSF10GLBK*

Product code

DATA/COMMS

No. of cores

Figure 8, plain annealed copper, PVC insulated.

D

PVC GARDEN LIGHTING MINING

61

62

7/0.50

*Pack sizes.

1.5

Nominal Stranding conductor area mm 2 No./mm

7.0

Nom. o’all diameter/ mm

7

Red, Black

ELV

Max. cond. Voltage res. @ 20°C rating ohm/km

JRS1502SA5

Product code

Max. cond. Voltage Product resistance rating code @ 20°C ohm/km 13.6 ELV JRS1502A5* 26.0 250/250 CBLR02* 21.2 450/750 CACP03* 13.6 450/750 CACP05*

Aluminium Foil + DW 13.6

Approx. Core Shielding mass colours kg/100m

Screened (Aluminium Foil)

Nominal Approx. Core Sheath overall mass colours colour diameter/size mm kg/100m 7.0 7 Red, White Red 3.45.5 4 Red, White Red 4.36.7 6 Red, White Red 4.67.3 10 Red, White Red

DATA/COMMS

Nominal Stranding conductor area No./mm mm2 1.5 7/0.50 0.75 24/0.20 1.0 7/0.40 1.5 7/0.50

Unscreened

D

Fire Alarm MINING

D

DATA DATA/COMMS

MINING

RS485 Screened (Low Capacitance) Pairs

Nominal O.D. mm

Nom. pair capacitance pF/m

Product code

1 2

5.9 8.6

50 50

JD1PS485A3 JD2PS485A3

Available in 300m spools.

RS422 Screened Data (pair) Pairs

Nominal O.D. mm

Nom. pair capacitance pF/m

Product code

1 2 3

4.4 5.5 6.0

70 70 70

JD1PS JD2PS JD3PS

Available in 100m and 300m spools.

RS232 Screened Data (cores) Cores

Nominal O.D. mm

Nom. pair capacitance pF/m

Product code

4 6

4.8 5.5

90 90

JD4CSAA JD6CSAA

Available in 100m spools.

Traffic Feeder Cable No. of pairs

Nom. Nom. insul. O.D. thick. mm mm

Charac- teristic impedance Ohms

Mutual capaci- tance nF/km

Capaci- Water tance pene- un- tration* balance*

Pack Product size code

1 1

0.5 0.5

80–100 80–100

65–85 65–85