550.38-TG2Y (1095)

®

STELLAR 2000 SPLIT-SYSTEM AIR CONDITIONERS “DB” SERIES - 10.00 SEER Models H*DB012 thru H*DB060 Nominal Capacity: 12 thru 60 MBH

DESCRIPTION The HDB Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be custom-matched with one of YORK’s complete line of evaporator sections, each designed to serve a specific function. Matching Air Handlers are available for upflow, downflow or horizontal application to provide a complete system. Electric heaters are available if required. Add-On coils are available for use with upflow, downflow or horizontal furnaces.

LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided,if required. Both quick connect and sweat connect models are available. Both service valves are firmly affixed to the unit. The sweat unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof.

FEATURES

TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.

QUALITY CONDENSER COILS - The coil is constructed of copper tube and hardened aluminum fins for durability and long lasting efficient operation. The fins on the unit are protected with a decorative grille. PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the compressor if undesirable operating conditions occur. DURABLE FINISH - Cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and glossy earth tone finish insure less fading when exposed to sunlight.

LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. LOW MAINTENANCE - Long life permanently lubricated motorbearings need no annual servicing. EASY SERVICE ACCESS - Fully exposed refrigerant connections and a single panel covering the electrical controls make servicing easy. SECURED SERVICE VALVES - Secured re-useable service valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

550.38-TG2Y

COOLING CAPACITY - With Air Handler and Coils UNIT MODEL

AIR HANDLER MODEL4

ELECT. HT. KW

W

COIL4 MODEL

COOLING7 NET MBH RATED CFM TOTAL SENS.

KW

SEER

SEER/ B.O.D.1

SEER/ S.V.2

EER3

8.7 12.4 12.6 17.0 16.9 19.3 20.7 25.9 27.0 29.0 28.2 33.7 35.2 41.7

1.42 2.05 2.11 2.45 2.47 2.94 2.96 3.77 3.85 4.30 4.33 5.20 5.22 5.98

10.00 10.00 10.30 10.10 10.50 10.30 10.30 10.10 10.40 10.00 10.20 10.00 10.20 10.00

N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R

-

8.70 8.50 8.50 9.40 9.70 9.70 9.50 9.30 9.50 9.10 9.10 8.80 9.10 9.80

1 & 3 PHASE HDB WITH AIR HANDLERS AND COILS H1DB012

N2AHD06 N2AHD06 N2AHD10

5,8,10,13 5,8,10,13 5,8,10,13,15,20

12 12 16

H1DB024

N2AHD10

5,8,10,13,15,20

16

H1DB030

N2AHD10 N4AHD14

5,8,10,13,15,20 5,8,10,13,15,20,25

16 22

H1DB036

N4AHD14

5,8,10,13,15,20,25

22

N2AHD14 N4AHD16 N2AHD16 N4AHD20 N4AHD20

5,8,10,13,15,20,25 5,8,10,13,15,20,25,30

22 26

5,8,10,13,15,20,25,30

26

5,8,10,13,15,20,25,30

26

H1DB018

H1DB042 H1DB048 H1DB060

G3HC018 G3HC018 G3HC024 G3HC024 G3HC030 G3HC030 G3HC036 G3HC036 G3HC042 G3HC042 G3HC048 G3HC048 G3HC060 G3HC060

450 650 650 850 850 1050 1050 1290 1290 1400 1400 1650 1650 1950

12.4 17.5 18.0 23.0 24.0 28.6 28.0 35.0 36.6 39.2 39.4 46.2 47.4 58.5

1 & 3 PHASE HDB WITH VARIABLE SPEED AIR HANDLERS AND COILS H1DB018

N1VSD10

5,8,10,13,15,20

16

H1DB024

N1VSD10

5,8,10,13,15,20

16

H1DB030

N1VSD10 N1VSD14

5,8,10,13,15,20

16 22

H1DB036

N1VSD14

5,8,10,13,15,20

22

H1DB042

N1VSD14 N2VSD20

5,8,10,13,15,20

22

H1DB048

N2VSD20

5,8,10,13,15,20

22

H1DB060

N2VSD20

5,8,10,13,15,20

22

G3HC024 G3HC024 G3HC030 G3HC030 G3HC036 G3HC036 G3HC042 G3HC042 G3HC048 G3HC048 G3HC060 G3HC060

650 850 850 1050 1050 1290 1290 1400 1400 1650 1650 1950

18.5 24.0 25.0 29.0 28.5 35.0 36.5 39.2 39.4 46.2 47.4 58.5

13.1 18.0 17.3 19.5 19.3 27.9 27.0 28.0 28.2 33.7 35.2 41.7

1.85 2.33 2.35 2.90 2.71 3.57 3.65 4.10 4.10 5.02 5.02 5.77

11.00 10.8 11.0 11.0 11.00 10.90 11.20 11.00 11.20 10.50 10.80 11.20

N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R

-

10.00 10.30 10.60 10.00 10.50 9.80 10.00 9.60 9.60 9.20 9.40 10.10

650 650 800 800 1035 1035 1250

18.0 18.5 23.2 23.4 28.2 28.4 34.4

13.5 13.1 16.7 16.8 20.8 21.0 25.1

1.99 2.05 2.58 2.55 2.89 2.85 3.85

10.00 10.50 10.00 10.00 10.40 10.80 10.00

10.58 -

-

9.00 9.10 9.00 9.10 9.75 10.00 8.95

800 800 1035 1250 1400

24.0 24.2 28.6 36.0 39.5

17.2 17.5 21.0 26.6 27.6

2.64 2.64 2.85 3.80 4.43

10.2 10.4 10.8 10.5 10.0

10.58 11.08 -

-

9.1 9.2 8.9 9.4 8.9

1 & 3 PHASE HDB WITH COOLING COIL AIR HANDLERS H1DB018 H1DB024 H1DB030 H1DB036

F1RC 018 F1RC 024 F1RC 024 F1RC 030 F1RC 030 F1RC 036 F1RC 036

2.5,5,7.5 5,7.5,10 5,7.5,10 5,7.5,10,15 5,7.5,10,15 5,7.5,10,15 5,7.5,10,15

18

-

1 & 3 PHASE HDB WITH HEAT PUMP COIL AIR HANDLERS H1DB024 H1DB030 H1DB036 H1DB042

F1RP024 F1RP030 F1RP030 F1RP036 F1RP042

5,7.5,10 5,7.5,10,15 5,7.5,10,15 5,7.5,10,15 5,7.5,10,15

18 21.5

-

Rated in accordance with DOE test procedures (Federal Register 12-27-79) and ARI Standards 210 and 270. MBH based on 80°F entering air temperature, 50% RH, and rated air flow. KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 1

B.O.D. = Blower Off Delay (Model #2FD06700224). S.V. = Solenoid Valve Kit (Model #2SV06700124). 3 EER (Energy Efficiency Ratio) is the total cooling output in BTU’s is at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. 4 To meet Florida R=4.2 insulation code requirements, substitute N1FA for N2AH, N3FA for N4AH, G1FC for G3HC and F1FC for F1RC models. All ratings remain the same. 5 P2MP, P2MPV and P2UR furnaces have B.O.D. standard. 6 Field transition required between furnace and coil. 7 Standard Cooling Operation is limited to 45 ° F outdoor ambient. 8 TXV = Thermal Expansion Valve Kit. Must be used with Hard Start Kit Accessory. N/R = Not Required. Blower Off Delay standard with air handler. 2

2

Unitary Products Group

550.38-TG2Y

COOLING CAPACITY - With 80% Furnace and Coils UNIT MODEL

FURNACE OUTPUT MBH

MODEL

W

COIL MODEL

RATED CFM

COOLING7 NET MBH KW TOTAL SENS.

SEER

EER3

1 & 3 PHASE HDB WITH UPFLOW FURNACE COILS H1DB012

H1DB018

H1DB024

H1DB030

H1DB036

H1DB042

H1DB048

H1DB060

G3US018 M3UF024 G3US018 M3UF024 G3UA024 M3UF032 G3UA030 M3UF024 G3UA024 G3UA036 M3UF032 G3UA037 M3UF044 G3UA036 M3UF032 G3UA037 M3UF044

450 450 650 650 650 650 800 800 850 850 850 850 850 1050 1050 1050 1050

13.1 13.1 18.2 18.0 18.0 18.0 24.4 23.0 24.0 24.8 23.0 24.8 23.8 29.6 27.6 29.6 28.8

9.5 9.1 13.6 12.9 12.8 12.8 18.2 16.8 18.0 18.8 16.8 18.8 17.3 21.9 18.7 21.9 21.0

1.40 1.43 1.98 1.99 2.00 2.00 2.42 2.39 2.50 2.53 2.49 2.54 2.57 2.98 2.85 2.98 2.99

10.00 10.00 10.40 10.10 10.40 10.40 10.30 10.10 10.10 10.50 10.10 10.50 10.20 10.30 10.30 10.40 10.30

9.40 9.20 9.20 9.00 9.00 9.00 10.10 9.60 9.60 9.80 9.20 9.80 9.30 9.90 9.70 9.90 9.60

16

G3UA036

1200

36.0

26.6

3.83

10.00

9.40

22

G3UA037 M3UF044 G3UA048

1250 1250 1250

36.0 36.0 37.0

26.6 24.9 27.0

3.83 3.72 3.49

10.10 10.50 10.30

9.40 9.70 10.60

22

G3UA048 G3UA060 M3UF044

1400 1400 1350

42.0 42.4 39.2

31.7 32.4 29.4

4.27 4.34 4.24

10.00 10.20 10.00

9.80 9.80 9.20

112

26

G3UA061 M3UF052

1400 1400

42.6 39.2

33.6 29.8

4.43 4.32

10.40 10.00

9.60 9.10

P2MPD165 P2MPD145 P2MPD165 P2MPD205

64 80 96 96

22

G3UA048 G2UT048 G3UA060

1600 1600 1600

48.2 48.0 48.6

36.4 36.2 36.7

5.13 5.10 5.21

10.00 10.00 10.20

9.40 9.40 9.30

P2MPD205

112

26

G3UA061 M3UF052

1600 1600

48.0 45.5

36.4 32.8

5.19 4.91

10.20 10.00

9.20 9.30

P2MPD205 P2MPD205 P2MPD205 P3UCB30

80 96 112 122

22

G3UA060

1950

60.0

42.4

5.97

10.00

10.00

26 32

G3UA061 M3UF064

1950 1975

60.0 56.5

42.1 40.8

5.98 5.91

10.00 10.00

10.00 9.60

P2MPD085

32

12

P2MPD085

32

12

P2MPD08 P2MPD125

48

16

P2MPD085

32

12

5

P2MPD12

48

P2MPD125

64

P2MPD145

80

22

P2MPD125 P2MPD125

48 64

16

P2MPD145

80

22

5

P2MPD12 P2MPD125 P2MPD165 P2MPD145 P2MPD165 P2MPD165 P2MPD145 P2MPD165 P2MPD205

48 64 64 80 96 64 80 96 96

P2MPD205

5

16

See Notes on Page 2.

SOUND RATINGS (ARI STANDARD 270) UNIT MODEL

H1DB UNIT

012 018 024 030 036 042 048 060

7.8 7.6 7.8 8.0 8.2 8.0 8.2* 8.0

SOUND RATING BELS H1DB WITH COMPRESSOR BLANKET ACCESSORY 7.6 7.6 -

CERTIFICATION APPLIES ONLY WHEN USED WITH PROPER COMPONENTS AS LISTED WITH ARI

* Compressor Blanket Factory Installed.

Unitary Products Group

3

550.38-TG2Y

COOLING CAPACITY - With 90% Furnace and Coils UNIT MODEL

MODEL

FURNACE OUTPUT MBH

W

COIL MODEL

RATED CFM

COOLING7 NET MBH KW TOTAL SENS.

SEER

EER3

1 & 3 PHASE HDB WITH UPFLOW FURNACE COILS H1DB012

P2URD08

37

14

P2URD08

37

14

P2URD08

55

17

H1DB018

H1DB024

H1DB030

P2URD10

55

P2URD12

74

17

P2URD14

98

21

P2URD10 P2URD10

55 74

17

P2URD14

98

21

74 76 98 112 76 94 112

17

H1DB042

P2URD12 P2URD16 P2URD14 P2URD20 P2URD16 P2URD20 P2URD20 P2URD20

130

24

76 94 112

21

H1DB048

P2URD16 P2URD20 P2URD20 P2URD20

130

24

P2URD20 P2URD20

94 130

21 24

H1DB036

H1DB060

21

21

G3US018 M3UF024 G3US018 M3UF024 G3UA024 M3UF032 G3UA024 G3UA036 M3UF032 G3UA037 M3UF044 G3UA036 M3UF032 G3UA037 M3UF044 G3UA036 G3UA037 M3UF044 G3UA048

450 450 650 650 650 650 850 850 850 850 850 1050 1050 1050 1050 1200 1250 1250 1250

13.1 13.1 18.2 18.0 18.0 18.0 24.0 24.8 23.0 24.8 23.8 29.6 27.6 29.6 28.8 36.0 36.0 36.0 37.0

9.5 9.1 13.6 12.9 12.8 12.8 18.0 18.8 16.8 18.8 17.3 21.9 18.7 21.9 21.0 26.6 26.6 24.9 27.0

1.40 1.43 1.98 1.99 2.00 2.00 2.50 2.53 2.49 2.54 2.57 2.98 2.85 2.98 2.99 3.83 3.83 3.72 3.49

10.00 10.00 10.40 10.10 10.40 10.40 10.10 10.50 10.10 10.50 10.20 10.30 10.30 10.40 10.30 10.00 10.10 10.50 10.30

9.40 9.20 9.20 9.00 9.00 9.00 9.60 9.80 9.20 9.80 9.30 9.90 9.70 9.90 9.60 9.40 9.40 9.70 10.60

G3UA048 G3UA060 M3UF044 G3UA061 M3UF052 G3UA048 G2UT048 G3UA060 G3UA061 M3UF052 G3UA060 G3UA061

1400 1400 1350 1400 1400 1600 1600 1600 1600 1600 1950 1950

42.0 42.4 39.2 42.6 39.2 48.2 48.0 48.6 48.0 45.5 60.0 60.0

31.7 32.4 29.4 33.6 29.8 36.4 36.2 36.7 36.4 32.8 42.4 42.1

4.27 4.34 4.24 4.43 4.32 5.13 5.10 5.21 5.19 4.91 5.97 5.98

10.00 10.20 10.00 10.40 10.00 10.00 10.00 10.20 10.20 10.00 10.00 10.00

9.80 9.80 9.20 9.60 9.10 9.40 9.40 9.30 9.20 9.30 10.00 10.00

See Notes on Page 2.

4

Unitary Products Group

550.38-TG2Y

COOLING CAPACITY - With 78% Furnace and Coils UNIT MODEL

FURNACE MODEL MODEL # MBH

W

COIL MODEL

RATED CFM

COOLING NET MBH KW TOTAL SENS.

SEER

EER

1 Phase HDB / UPFLOW FURNACE & COILS H1DB 018

P1SPD10 P1SPD12

H1DB 024 P1SPD16 P1SPD12 H1DB 030 P1SPD16 P1SPD12 H1DB 036 P1SPD16 P1SPD16 H1DB 042 P1SPD20 P1SPD16 H1DB 048 P1SPD20

H1DB 060

P1SPD20

40

17

40 60 60 80 40 60 60 80 40 60 60 80 60 80 100 120 60 80 80 80 100 120 80 100 120

17 17 20 20 17 17 20 20 17 17 20 20 20 20 23 23 20 20 23 23 23 23 23 23 23

G3UA024 M3UF032 G3UA036 M3UF032 G3UA037 M3UF044 G3UA036 M3UF032 G3UA037 M3UF044 G3UA036 M3UF044 G3UA037 G3UA048

650 650 850 850 850 850 1050 1050 1050 1050 1200 1250 1250 1250

18.0 18.0 24.8 23.0 24.8 23.8 29.6 27.6 29.6 28.8 36.0 36.0 36.0 37.0

12.8 12.8 18.8 16.8 18.8 17.3 21.9 18.7 21.9 21.0 26.6 24.9 26.6 27.0

2.00 2.00 2.53 2.49 2.54 2.57 2.98 2.85 2.98 2.99 3.83 3.72 3.83 3.49

10.4 10.4 10.5 10.1 10.5 10.2 10.30 10.30 10.40 10.30 10.0 10.5 10.1 10.3

9.0 9.0 9.8 9.2 9.8 9.3 9.9 9.7 9.9 9.6 9.4 9.7 9.4 10.6

G3UA048 G3UA060 M3UF044

1400 1400 1350

42.0 42.4 39.2

31.7 32.4 29.4

4.27 4.34 4.24

10.0 10.2 10.0

9.8 9.8 9.2

G3UA048 G3UT048

1600 1600

48.2 48.0

36.4 36.2

5.13 5.10

10.0 10.0

9.4 9.4

G3UT048 G3UA060

1600

48.6

36.7

5.21

10.2

9.3

G3UA060

1950

60.0

42.4

5.97

10.0

10.0

See Notes on Page 2

Unitary Products Group

5

550.38-TG2Y

COOLING CAPACITY UNIT MODEL

FURNACE OUTPUT MBH

MODEL

W

COIL MODEL

COOLING7 RATED CFM

NET MBH TOTAL SENS.

KW

SEER

SEER/ B.O.D.1

EER3

1 & 3 PHASE HDB WITH HORIZONTAL FURNACE COILS H1DB012

P2MPD085

H1DB018

P2MPD085

1.38 1.42 2.12 2.05 2.11

10.10 10.10 10.00

10.00 10.00 10.30

9.50 8.70 8.50 8.50 8.50

-6

M3HD024 M3HD036

850 850

24.0 24.8

17.8 19.2

2.60 2.60

10.20 10.40

-

9.20 9.50

16

G3HC024 G3HC030

850 850

23.0 24.0

17.0 16.2

2.45 2.47

10.00 10.50

10.10 10.50

9.40 9.70

-6

M3HD036

1050

29.0

21.5

2.99

10.20

-

9.70

16

G3HC030

1050

28.6

19.4

2.94

10.00

10.30

9.70

22

G3HC036

1050

28.0

20.1

2.96

10.00

10.30

9.50

-6

M3HD036 M3HD048

1200 1200

34.0 35.0

24.1 25.2

3.79 3.87

10.00 10.00

-

9.00 9.00

-6

G3HC036

1290

35.0

25.9

3.77

10.00

10.10

9.30

22

G3HC036 G3HC042

1290 1300

35.0 36.6

25.9 27.0

3.77 3.79

10.00 10.00

10.10 10.40

9.30 9.60

-6

M3HD048

1400

40.0

28.7

4.31

10.00

-

9.30

22

G3HC042

1400

39.2

28.0

4.30

-

10.00

9.10

26

G3HC048

1400

39.4

28.2

4.33

-

10.20

9.10

-6

M3HD048 M3HD060

1600 1600

47.2 47.6

33.6 33.7

5.19 5.21

10.00 10.00

-

9.10 9.10

-6

G3HC048 G3HC060

1650 1650

46.2 47.2

33.7 35.2

5.20 5.22

-

10.00 10.20

8.90 9.00

-

G3HC048 G3HC060 M3HD060

1650 1650 1950

46.2 47.2 58.0

33.7 35.2 40.9

5.20 5.22 5.91

10.00

10.00 10.20 -

8.90 9.00 9.80

-6

G3HC060

2000

58.5

41.3

5.97

10.00

-

9.80

26

G3HC060

2000

58.5

41.3

5.97

10.00

-

9.80

115 80 96 112

6

P2MPD14

P2HED12 P2HED16 P1HDD12 P1HDD16 P2MPD125

H1DB060

9.5 8.7 13.8 12.4 12.6

26

5

H1DB048

13.1 12.4 18.0 17.5 18.0

112

P1HDD12 P2MPD125

H1DB042

450 450 650 650 650

P2MPD205

P2HED12

H1DB036

M3HD024 G3HC018 M3HD024 G3HC018 G3HC024

P2MPD165 P2MPD145 P2MPD165 P2HED16 P2HED20 P1HDD16 P1HDD20 P2MPD165 P2MPD145 P2MPD165 P2MPD205 P2MPD205 P2HED16 P2HED20 P1HDD16 P1HDD20 P2MPD165 P2MPD205 P2MPD165 P2MPD205

P1HDD12 P2MPD125

H1DB030

32

-6 12 -6 12 16

48 40 60 47 69 48 64 40 60 47 69 48 64 80 40 60 80 47 69 92 48 64 64 80 96 80 100 92 115 64 80 96 96 112 80 100 92 115 64 80 96 96

P2HED12 H1DB024

32

P1HDD20 P2MPD205 P2MPD205 P2MPD205

See Notes on Page 2.

6

Unitary Products Group

550.38-TG2Y

COOLING CAPACITY UNIT MODEL

MODEL

FURNACE OUTPUT MBH

W

COIL MODEL

RATED CFM

COOLING7 NET MBH KW TOTAL SENS.

SEER

EER3

1 & 3 PHASE HDB WITH DOWNFLOW FURNACE COILS H1DB012 H1DB018

H1DB024

H1DB030

H1DB036

P2DPD105

48

P2DPD105 P1CDD10 P2DPD105 P2DPD125 P1CDD10 P1CDD12 P2DPD105 P2DPD125 P1CDD10 P1CDD12

48 57 48 64 57 76 48 64 57 76

P2DPD125

80

P2DPD125

80 80 92 95 80 92 95 104 114 104 114

5

P2DPD16

P1CDD16 H1DB042 H1DB048 H1DB060

P2DPD165 P1CDD16 P2DPD205 P1CDD20 P2DPD205 P1CDD20

G3CN030 M3CF032 G3CN030 M3CF032

450 450 650 650

13.5 13.2 18.0 18.0

9.3 9.4 13.0 12.6

1.40 1.36 1.93 1.92

10.20 10.20 10.10 10.10

9.60 9.70 9.30 9.40

16

G3CN030 M3CF032

850 850

23.0 23.0

17.2 17.2

2.48 2.47

10.00 10.00

9.30 9.40

16

G3CN030 M3CF032

1050 1050

28.0 27.5

20.1 20.0

3.08 2.96

10.00 10.00

9.10 9.30

22

G3CN042 M3CF044

1050 1050

28.0 29.0

20.1 20.8

3.00 2.96

10.00 10.00

9.30 9.70

22

G3CN042 M3CF044

1250 1250

36.0 35.0

26.5 25.1

3.80 3.78

10.00 10.00

9.20 9.20

22

G3CN042 M3CF044

1400 1400

39.0 39.0

27.9 27.8

4.28 4.29

10.00 10.00

9.10 9.10

26

G3CN060 M3CF052

1600 1600

46.2 46.0

33.7 33.2

5.20 4.91

10.00 10.00

8.90 9.40

26

G3CN060

1950

56.5

39.5

5.98

10.00

9.40

16 16

See Notes on Page 2.

COOLING PERFORMANCE MODEL

H1DB012

H1DB018

H1DB024

H1DB030

SUCT. T/P @ COMPR. TEMP. PSIG 35 61.5 40 68.5 45 76.0 50 84.0 35 61.5 40 68.5 45 76.0 50 84.0 35 61.5 40 68.5 45 76.0 50 84.0 35 61.5 40 68.5 45 76.0 50 84.0

AIR TEMP ON CONDENSER 75°F 95°F 115°F MBH KW MBH KW MBH KW 13.2 1.14 11.2 1.24 9.2 1.34 14.7 1.17 12.6 1.28 10.4 1.40 16.4 1.21 14.0 1.33 11.6 1.46 18.0 1.24 15.5 1.37 12.8 1.51 17.3 1.38 14.7 1.51 12.0 1.66 19.3 1.43 16.5 1.58 13.7 1.74 21.4 1.48 18.4 1.65 15.4 1.83 23.5 1.53 20.4 1.73 17.1 1.92 23.4 1.84 19.9 2.01 16.2 2.19 26.1 1.91 22.3 2.11 18.3 2.32 28.9 1.99 24.7 2.22 20.6 2.44 31.7 2.07 27.3 2.32 22.8 2.57 27.4 2.11 23.7 2.34 20.0 2.54 30.0 2.17 26.2 2.43 22.3 2.66 32.8 2.23 28.7 2.52 24.6 2.78 35.7 2.29 31.3 2.61 27.0 2.89

MODEL

H1DB036

H1DB042

H1DB048

H1DB060

SUCT. T/P @ COMPR. TEMP. PSIG 35 61.5 40 68.5 45 76.0 50 84.0 35 61.5 40 68.5 45 76.0 50 84.0 35 61.5 40 68.5 45 76.0 50 84.0 35 61.5 40 68.5 45 76.0 50 84.0

AIR TEMP ON CONDENSER 75°F 95°F 115°F MBH KW MBH KW MBH KW 34.4 2.80 30.0 3.09 25.5 3.35 37.7 2.89 33.0 3.21 28.2 3.51 41.1 2.98 36.2 3.34 31.1 3.67 44.6 3.06 39.4 3.46 34.1 3.82 37.4 3.20 32.1 3.49 26.7 3.71 41.5 3.37 35.8 3.67 30.1 3.92 45.7 3.52 39.5 3.85 33.0 4.14 49.7 3.67 43.3 4.01 36.3 4.33 45.0 3.54 36.9 3.84 30.5 4.03 47.9 3.69 41.1 4.03 34.4 4.27 52.2 3.84 45.1 4.24 38.0 4.53 56.7 3.99 49.3 4.44 41.5 4.80 50.2 4.52 45.1 5.45 39.9 6.39 54.7 4.65 49.1 5.60 44.0 6.45 59.2 4.80 53.5 5.69 47.9 6.58 63.8 4.97 57.8 5.83 51.4 6.79

NOTES: 1. For condensing unit only. Does not include effect of evaporator motor power or heat. 2. Performance based on 15° superheat and 15° sub-cooling at condensing unit. a. Increase capacity 1% for each 2° increase in sub-cooling. b. Decrease capacity 1% for each 2° decrease in sub-cooling. 3. Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°. Maximum recommended condensing temperature is 140°F.

Unitary Products Group

7

550.38-TG2Y

PHYSICAL AND ELECTRICAL DATA - 1 Ø MODELS H1DB... UNIT SUPPLY VOLTAGE NORMAL VOLTAGE RANGE 1 MIN. CIRCUIT AMPACITY MAX. OVERCURRENT DEVICE AMPS 2 COMPRESSOR TYPE RATED LOAD COMPRESSOR AMPS LOCKED ROTOR CRANKCASE HEATER RATED LOAD FAN MOTOR AMPS LOCKED ROTOR MIN. FIELD WIRE SIZE AWG 60°C COPPER CONDUCTORS 208V MAX. WIRE LENGTH FEET BASED ON 3% VOLTAGE DROP 230V FAN DIAMETER INCHES RATED HP FAN MOTOR NOMINAL RPM NOMINAL CFM FACE AREA SQ. FT. COIL ROWS DEEP FIN / INCH LIQUID LINE OD VAPOR LINE OD OPERATING WEIGHT LBS. 1

012

018

024

10.8 15 Recip. 8.0 35.0 NO 0.8 1.7

13.0 20 Recip. 9.7 54.0 NO 0.8 1.7

16.0 25 Recip. 12.1 57.0 NO 0.8 1.7

14

12

12

10

90 100 18 1/8 1075 1950 9.4 1 16 3/8 5/8 120

115 130 18 1/8 1075 1950 9.4 1 16 3/8 5/8 124

95 105 18 1/8 1075 1950 11.3 1 18 3/8 5/8 134

140 155 18 1/8 1075 1950 11.3 1 20 3/8 3/4 135

Utilization range “A” in accordance with ARI standard 110.

030 036 208/230-1-60 187 to 252 17.7 23.2 25 35 Inertia Inertia 13.5 17.3 68.0 94.0 NO YES 0.8 1.6 1.7 3.8

042

048

060

27.2 40 Recip. 20.5 120 YES 1.6 3.8

30.3 45 Inertia 23.0 105 YES 1.6 3.8

37.2 50 Scroll 28.5 170 NO 1.6 3.5

10

10

8

6

105 120 18 1/4 1075 2350 11.3 1 20 3/8 3/4 140

135 150 18 1/4 1075 2200 14.1 1 18 3/8 7/8 155

125 140 18 1/4 1075 2150 17.0 1 20 3/8 7/8 175

115 125 24 1/4 850 3000 20.0 1 18 3/8 7/8 210

H1DB060

8.0 15 Inertia 5.8 40 YES 0.8 1.8

H1DB048 46 460-3-60 432 to 504 9.7 15 Inertia 7.1 64 YES 0.8 1.8

2

Dual element fuses or HACR circuit breaker.

PHYSICAL AND ELECTRICAL DATA - 3 Ø MODELS UNIT SUPPLY VOLTAGE NORMAL VOLTAGE RANGE 1 MIN. CIRCUIT AMPACITY MAX. OVERCURRENT DEVICE AMPS 2 COMPRESSOR TYPE RATED LOAD COMPRESSOR AMPS LOCKED ROTOR CRANKCASE HEATER RATED LOAD FAN MOTOR AMPS LOCKED ROTOR MIN. FIELD WIRE SIZE AWG 60°C COPPER CONDUCTORS 208V 230V MAX. WIRE LENGTH FEET 460V BASED ON 3% VOLTAGE DROP 575V FAN DIAMETER INCHES RATED HP NOMINAL RPM FAN MOTOR NOMINAL CFM FACE AREA SQ. FT. ROWS DEEP COIL FIN / INCH LIQUID LINE OD VAPOR LINE OD OPERATING WEIGHT LBS. 1 2

8

H1DB036

15.2 25 Inertia 10.9 78 YES 1.6 3.8

H1DB048 H1DB060 25 208/230-3-60 187 to 253 20.0 22 30 30 Inertia Scroll 14.7 16.3 130 124 YES YES 1.6 1.6 3.8 3.5

H1DB036

11.4 15 Scroll 8.5 59.6 YES 0.8 2.0

H1DB048 H1DB060 58 575-3-60 517 to 633 8.5 8.0 15 15 Inertia Scroll 6.4 5.9 52 49.4 YES YES 0.5 0.6 1.1 1.5

12

10

10

14

14

14

14

14

105 120 18 1/4 1075 2350 11.3 1 20 3/8 3/4 140

145 160 18 1/4 1075 2150 17.0 1 20 3/8 7/8 169

155 170 24 1/4 850 3000 20 1 18 3/8 7/8 200

310 18 1/4 1075 2350 11.3 1 20 3/8 3/4 140

300 18 1/4 1075 2150 17.0 1 20 3/8 7/8 169

150 24 1/4 850 3000 20 1 18 3/8 7/8 200

425 18 1/4 1075 2150 17.0 1 20 7/8 7/8 169

440 24 1/4 850 3000 20 1.0 18 7/8 7/8 200

Utilization range “A” in accordance with ARI standard 110. Dual element fuses or HACR circuit breaker.

Unitary Products Group

550.38-TG2Y

DIMENSIONS 48" OVERHEAD CLEARANCE

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

C

B

H1DB012 THRU H1DB048

STANDARD GRILLE H1DB060

A

H

AIR IN 4 SIDES

G

VAPOR CONNECTION

5-1/2

LIQUID CONNECTION

MODEL H1DB012 H1DB018 H1DB024 H1DB030 H1DB036 H1DB042 H1DB048 H1DB060

3-1/8

A Height 20-1/8 20-1/8 24-1/8 24-1/8 24-1/8 30-1/8 36-1/8 31-1/8

Dimensions B Width 24 24 24 24 24 24 24 34-1/2

2-3/8

C Depth 24 24 24 24 24 24 24 34-1/2

Wiring K.O.’s* G H Power Control

Refrigerant Connections Line Size Quick Conn Liquid Vapor Liquid Vapor 5/8

7/8 1-1/8

7/8

3/8

3/4

M-6

M - 11

7/8

*Use the 7/8" KO with a 1/2" conduit fitting for #8 AWG wire or smaller. Use the 1-1/8" KO with a 3/4" conduit fitting for #6 AWG wire or smaller.

Unitary Products Group

9

550.38-TG2Y

TYPICAL FIELD WIRING - 1 Ø

ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC) AND/OR LOCAL CODES POWER WIRING 208/230-1-60

POWER 24 VOLT CONTROL WIRING

FURNACE OR AIR HANDLER TERMINAL BLOCK C

Y

R

G

CONTROL FACTORY

W

CONTROL WIRING

CONTACTOR TERMINALS GROUND SCREW

COIL

Y

R

G

W

*

POWER WIRING

* Terminal W is only required on systems with heat.

ROOM THERMOSTAT ALL OUTDOOR WIRING MUST BE WEATHERPROOF.

USE COPPER CONDUCTORS ONLY.

TYPICAL FIELD WIRING - 3 Ø ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC) AND/OR LOCAL CODES

POWER

POWER WIRING 208/230-3-60 460-3-60 575-3-60

CONTROL FACTORY 24 VOLT CONTROL WIRING

FURNACE OR AIR HANDLER TERMINAL BLOCK C

Y

R

G

W

Y

R

G

W

CONTACTOR TERMINALS GROUND SCREW

COIL

*

ROOM THERMOSTAT ALL OUTDOOR WIRING MUST BE WEATHERPROOF.

10

* Terminal W is only required on systems with heat.

USE COPPER CONDUCTORS ONLY.

Unitary Products Group

550.38-TG2Y

TYPICAL INSTALLATION THERMOSTAT TO BLOWER MOTOR RELAY

WEATHERPROOF DISCONNECT SWITCH

TO POWER SUPPLY

12" REAR AND SIDES

NEC CLASS 1 WIRING

Sit unit on rubber elevator grommets to reduce noise and allow for proper drainage.

NEC CLASS 2 WIRING

TO COIL

48" OVERHEAD CLEARANCE

NOTE: All outdoor wiring must be weatherproof

Seal opening(s) with permagum or equivalent

Unitary Products Group

24" SERVICE ACCESS CLEARANCE

11

MATCHING INDOOR COMPONENTS Typical Application

Add-On Coils - For Furnace Application





UPFLOW FLATTOP M3UF

UPFLOW G3UA

3

1

6

4 2

5

Air Handlers - For Non-Furnace Application

➂ HORIZONTAL M3HD

F1RC / F1FC or F1RP / F1FP FAN COIL UNITS

N2AH, N4AH or N1FA, N3FA BLOWER

G3HC or G1FC COIL

➁ DOWNFLOW FLATTOP M3CF

➁ DOWNFLOW G3CN

➃ UPFLOW ➄ DOWNFLOW ➅ HORIZONTAL

➃ UPFLOW ➅ HORIZONTAL

ACCESSORIES Refer to Price Manual for specific model numbers. Stub Adapters - Available to adapt sweat connect units to quick connect coils or sweat connect coils to quick connect units. Precharged Line Sets - Available in 15, 25, 35 and 50 foot lengths for connection of quick connect models. Outdoor liquid ends have F-6 connectors, vapor ends have F-11 connectors. Indoor liquid ends have M-6 connectors, vapor ends have M-11 connectors. All indoor vapor ends are provided with a 90° bend. A 30 foot line set with straight ends is available for splicing to other lines for longer runs. All vapor lines are insulated with 1/2 sponge rubber. Start Assist Kit - Provides increased starting torque for areas with low voltage conditions. Hard Start Kits - Provides required starting torque for use with Solenoid Valve Kit.

Unitary Products Group P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in U.S.A. Copyright  by York International Corporation 1995. All Rights Reserved.

Off Cycle Timer - Provides a 5 minute off cycle to prevent rapid recycling of the compressor. Room Thermostats - A wide selection of matching thermostats is available to provide features required for any installation. 2TH07700124 - One stage heat / One stage cool / Nonprogrammable. 2ET07700224 - One stage heat / One stage cool / Programmable, Electronic. 2ET07700324 - One stage heat / One stage cool / Programmable, Electronic. Blower Off Delay - Available to increase efficiency when using Yorkmate control. Installs on indoor section to maintain blower operation for approximately 1 minute on shutdown. Solenoid Valve Kit - Used to improve system performance. Compressor Blanket - Designed to further reduce the normal operating sounds for H1DB units.

SHU 15M 1195 .66

Code: EBY,EGY

550.38-TG2Y Supersedes: 550.38-TG1Y (295)