Ducted Split Air Conditioner SERVICE MANUAL MODELS: TN-C090BT00 TN-C120BT00 TN-C180BT00 TN-C240BT00
Contents Model Number Nomenc lature ...............................................................................................2 General Data ..........................................................................................................................3 Dimensions ............................................................................................................................5 Wiring Dia gram ......................................................................................................................6 Troub leshooting Guide .........................................................................................................7 Features of Contr oller .........................................................................................................18 Exploded View and Replacement Parts List
.....................................................................23
Model Number Nomenc lature T N - C 0 9
0 B T 0 0 Development Sequence Model Type A(0): Gold Fin A: 3/4/5RT
0:Over 5RT
B: Basic Outdoor Fan Discharge
S: Side Discharge T: Top Discharge Electric Standard (Volts / Freq. / Phase) 8 : 380-415V / 50Hz / 3Ø B : 380-415V / 60Hz / 3Ø Cooling Capacity 090B : 88,000 Btu/h 120B : 118,000 Btu/h 240B : 180,000 Btu/h 240B : 230,000 Btu/h Model Type C: Cooling Only H: Heat Pump Type of Air Conditioner TN: LGETA Ducted Split Air Conditioner 2
General Data List of Functions Features Model No.
TN-C090BT00
TN-C120BT00
O
O
Auto Restart Operation
-
-
Wired Remote Control
O
O
Group Control
-
-
Child Lock Function
-
-
Self Diagnosis Function
-
-
Weekly Program
-
-
Time Delay Relay
O
O
Two Thermistor Control
-
-
Central Control
-
-
Zone Control
-
-
Energy Saving Gold Fin
-
-
Wireless Remote Control
-
-
Accessory
Accessory
Fire Alarm Function
-
-
Electronic Thermostat
-
-
Low Pressure Switch
O
O
High Pressure Switch
O
O
Phase Protection
O
O
Cooling & Fan Operation
Electric Heater
Notes: :Applied
- :Not applied
× :No relation
* Option : Model name & price are different according to options, and assembled in factory with main unit. * Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
3
General Data
Model No.
TN-C180BT00
TN-C240BT00
Cooling & Fan Operation
O
O
Auto Restart Operation
O
O
Wired Remote Control
O
O
Group Control
-
-
Child Lock Function
O
O
Self Diagnosis Function
O
O
W eekly Program
O
O
Time Delay safety
O
O
Two Thermistor Control
-
-
Central Control
-
-
Zone Control
-
-
Energy Saving Gold Fin
O -
O -
Option -
Option -
-
-
Low Pressure Switch
O
O
High Pressure Switch
O
O
Phase Protection
O
O
Features
W ireless Remote Control Electric Heater Fire Alarm Function Electronic Thermostat
Notes: O :Applied
- :Not applied
* Option : Model name & price are different according to options, and assembled in factory with main unit. * Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
4
General Data Nominal RT
(RT)
Models Btu/h kcal/h(W) Btu/h kcal/h(W) V,PH,Hz
Gross Cooling Capacity Capacity Net Cooling Capacity Power Supply Electrical Data
Performance
M.C.A(with standard motor) Power Input Air Circulation EER SEER Sound Rating Type
Cooling Cooling Nominal CFM Cooling Cooling
Indoor Coil
Indoor Fan
Type No. Used Diameter ( Width ) Drive Type / Motor Step
40
51 13,500 4,000 8.43 -
6.3 High efficiency 3/8 9.52 2R / 24C / 17FPI 55 1/8 1,400 9.19 0.85 Centrifugal Blower 1EA 12.7 (15) Pully /1 1EA 1 / N.A 1030 / N.A 2 1 Scroll 2 C-SB303H6B SANYO 14,400(49,133) Three Phase 4,400 SAY56T 1,700 High efficiency 9/32 7
6.3 High efficiency 9/32 7.0 3R / 29C / 17FPI 55 1/8 1,400 9.19 0.85 Centrifugal Blower 1EA 12.7 (15) Pully /1 1EA 1 / N.A 1030 / N.A 2 1 Scroll 2 SR061R LG 14,400(49,133) Three Phase 5,100 SUNISO 4GSI 1,950 High efficiency 9/32 7
2R / 36C / 17FPI * 2EA 2R / 17C /17FPI * 2EA
2R / 36C / 17FPI * 2EA 2R / 17C /17F3 , 2EA
27.6 700 16.2 1.55 Propeller 1EA / 18 1/8 Direct Top
27.6 1170 27 2.58 Propeller 1EA / 18 1/8 Direct Top
1EA / 0.1
2EA / 0.1
1050 1/2(12.7) 3/4(19.05) 1/2(12.7) 3/4(19.05) 295 9/32(7.5) 5.6 1 1/4 2.9*2 6.39*2 R22 Capillary Tube 69 1/8 *36 1/32 * 33 1/16 1760 *890 * 840 33 3/8 * 61 5/8*29 1/8 855 * 1570 *740 190 418 140 308 12/24/39 19/42/42
1050 1/2(12.7) 3/4(19.05) 1/2(12.7) 3/4(19.05) 295 9/32(7.5) 5.6 1 1/4 3.5*2 7.72*2 R22 Capillary Tube 69 1/8 *36 1/32 * 33 1/16 1760 *890 * 840 52 3/8 * 61 5/8 * 29 1/8 1330 * 1570 * 740 190 418 300 661 12/24/39 12/25/25
inch
No.motors Motor output(standard / oversized) Motor rpm(Standard / oversized)
Hp Hp
No of System Cycles No of Outdoor Units
Compressor
Type Quantity Model Maker Capacity Motor Type Motor Input Oil Type Oil Charge Type Tube size(O.D)
Outdoor Coil
Face area
Outdoor Fan
Service Valve
Connecting Tube
Type No. Used / Diameter(inch) Drive Type CFM Discharge No. Motor / Motor output(Hp) Motor RPM Liquid Gas Liquid Gas Length(Standard)
Dehumidification Rate Drain Connection Size(inch)
Refrigerant
kcal/h(Btu/h) W cc inch mm
Row / Column / FPI Length
Refrigerant Charge
inch mm sq.ft
Side / Top
inch(mm) inch(mm) inch(mm) inch(mm) inch(m) Ɛ /h kg lbs Type
Refrigerant Control Indoor unit (W * H * D) Dimensions Outdoor unit (W * H * D) Indoor unit Net Weight Outdoor unit Stuffing Quantity
Without S/Parts
122,094 30,774˄35,784˅ 118,000 29,742(34,583) 220-240 ,3,60
11 3000 8.98 -
inch mm sq.ft
Face area
90,600 22,836˄26,553˅ 88,000 22,180(25,791) 220-240 ,3,60
W CFM Btu/h.W Btu/h.W bell
Row / Column / FPI Length
10 TN-C120BT00
Amps
inch mm
Tube size(O.D)
7.5 TN-C090BT00
inch mm inch mm kg lbs kg lbs INDOOR /OUTDOOR(20ft / 40ft / 40ft HI)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 26.7ć(80) DB/19.4ć(67) WB - Outdoor Temperature 35ć(95) DB/24ć(75.2) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Nominal CFM : Fan operation mode with clean filter, dry coil. 3. The specification may be subject to change without prior notice for purpose of improvement.
5
Conversion Formula kcal/h = kW x 860 Btu/h = kW x 3412 cfm = m 3 /min x 35.3
General Data Nominal RT
(RT)
Models Gross Cooling Capacity Capacity
Net Cooling Capacity Net Heating Capacity
Electrical Data
Power Input
kW
53.54
70.41
Btu/h
182 700
240 239
kW
52.75
67.41
Btu/h
180 000
230 000
kW
-
-
Btu/h
3/220ѝ240/60 140
Ø / V / Hz Cooling
A
76
Heating
A
-
-
Cooling
W
22 000
25 500
Heating
W
-
-
CFM
5 300
7 500
EER
Btu/h.W
8.18
9. 02
SEER
Btu/h.W
-
-
COP
W/W
-
-
Sound Rating˄indoor˅ Sound Rating˄outdoor˅
bell+3
67
69
bell+3
75
75
High efficiency
High efficiency
Air Circulation(Nominal)
Performance
Type Tube Size(O.D) Evaporator
mm(inch)
Rows / Column / FPI
1500(59 17/32)
༇(sq.ft)
1.14(12.33)
1.14(12.33)
Centrifugal Blower
Centrifugal Blower
Diameter
mm(inch)
393(15 15/32)
393(15 15/32)
Width
mm(inch)
557(21 15/16)
557(21 15/16)
WEITELI
WEITELI
Belt/1
Belt/1
No. Motors Motor Output(Standard / Oversized)
Hp
Motor RPM(Standard / Oversized) No. of Outdoor Units Model
SR049RAC LG
SR061RBA LG
Capacity
Btu/h
Motor Type
Tube Size(O.D)
W cc mm(inch)
Rows / Column / FPI Length Face Area
mm(inch) ༇(sq.ft)
Type * No. Used Diameter
inch
Maker Drive Type Air Circulation
5538 SUNISO 4GSI
1800
1950
High efficiency
High efficiency
9.52(3/8)
9.52(3/8)
3R / 40C / 14FPI*2
3R / 40C / 14FPI*2
-
-
0.50
0.50
Propeller * 2
Propeller * 2
-
-
-
-
Direct
Direct 8200
2EA / 1.5
2EA / 1.5
970
970
Liquid
mm(inch)
15.88(5/8)
15.88(5/8)
Gas
mm(inch)
28(9/8)
28(9/8)
Liquid
mm(inch)
15.88(5/8)
15.88(5/8)
Gas
mm(inch)
28(9/8)
28(9/8)
m(inch) ˜/h
7.5(295 9/32)
7.5(295 9/32)
Dehumidification Rate Drain Connection Size(inch) Refrigerant Charge
Indoor Unit (W * H * D) Outdoor Unit (W * H * D)
17
17
1 1/4
1 1/4 7.6*2
kg
7.5*2
lbs
-
-
Type
R22
R22
Capillary Tube
Capillary Tube
mm
1800*890*1000
1800*890*1000
inch
70 7/8* 35 3/8 *39 3/8
70 7/8* 35 3/8 *39 3/8
mm
1560*1100*880
1760*1100*970
inch
69 1/4* 43 5/16 * 38 3/16 250˄550˅
Refrigerant Control
Fliter
4625 SUNISO 4GSI
Hp
Length(Standard)
Net Weight
62 000 One Phase
8200
Motor RPM
Dimensions
49 500 One Phase
CFM
No. Motor / Motor Output(Hp)
Refrigerant
1720/ 1730 1
Type
Connecting Pipe
1720/ 1730
SCROLL * 4
Oil Charge
Service Valve
4.0/6.0
SCROLL * 4
Oil Type
Outdoor Motor
1
4.0/6.0
Type * Quantity
Motor Input
Outdoor Fan
1
1
Maker
Condenser
1500(59 17/32)
mm(inch)
Drive Type / Motor Step
Compressor
9.52(3/8) 3R / 30C / 17FPI
Face Area
Maker Indoor Motor
9.52(3/8) 3R / 30C / 17FPI
Length Type * No. Used Indoor Fan
20 TN-C240BT00
3/220ѝ240/60
Power Supply M.C.A (with Standard Motor)
15 TN-C180BT00
Indoor Unit
kg(lbs)
61 7/16* 43 5/16 * 34 5/8 250˄550˅
Outdoor Unit or S/Package
kg(lbs)
340(748)
340(748)
-
-
-
-
Size * No. Used Filter Rack Thickness
inch
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27.0 (80.6°F ) DB/19.0 (66.2°F) WB - Outdoor Temperature 35 (95°F) DB/24 (75.2°F) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Nominal CFM : Fan operation mode with clean filter, dry coil. 3. The specification may be subject to change without prior notice for purpose of improvement.
6
Conversion Formula kcal/h = kW x 860 Btu/h = kW x 3412 cfm = m 3 /min x 35.3
Dimensions Model No.: TN-C120BT00
69
˅
35.0˄890˅
60
61.8(1570)
.3˄ 17
0˅
4 ˄8 3.0
3
52.4(
0)
74
( 9.1
1330
)
2
Model No.: TN-C120BT00
69
˅
35.0˄890˅
60
61.8(1570)
.3˄ 17
0˅
4 ˄8 3.0
3
52.4(
7
0)
74
1330
)
2
( 9.1
Dimensions Model No.: TN-C180BT00 1. Indoor units
18
890
00
00
10
1100
2. Oudoor units
156
0
0
88
Note: All dimensions are in mm
8
Dimensions Model No.: TN-C240BT00 1. Indoor units
18
890
00
00
10
1100
2. Oudoor units
176
0
0
97
Note: All dimensions are in mm
9
Wiring Diagrams Model No.:TN-C090BT00
Notes: RY YL WH
RELAY YELLOW WHITE FACTORY WIRING
BK BR BL
BLACK BROWN BLUE OPTIONAL WIRING
OR RD GN/YL
ORANGE RED GREEN/YELLOW FIELD WIRING
Model No.:TN-C120BT00
Notes: BK BR BL
BLACK BROWN BLUE FACTORY WIRING
OR RD GN/YL
ORANGE RED GREEN/YELLOW OPTIONAL WIRING
10
YL WH COMP
YELLOW WHITE COMPRESSOR FIELD WIRING
Wiring Diagrams Model No.:TN-C180BT00
11
Wiring Diagrams
MEZ62337701
Model No.:TN-C240BT00
12
Troubleshooting Guide In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but ineffective cooling
Ineffective Cooling
Check of cold air circulation for smooth flow.
Check of outdoor coil (heat exchanger) & the fan operation.
Dirty indoor coil (heat exchanger.)
Check gas leakage.
Check heat load increase in cooling operation.
Unexpected residue
Added electrical utencil Malfunction of fan.
Repair gas leak.
Clogging of air filter.
Replacement of unit if the unit is beyond repair.
Obstruction at air outlet.
Check of inside gas pressure.
Adjust refrigerant charge.
Countermeasure against above trouble. Malfunction of compressor. Check clogging in refrigeration circuit.
Repair clogging in refrigeration circuit.
Satisfactory operation with temperature difference of inlet & outlet air ; ʚ COOLING : 7~10 C
13
Replacement of compressor
Troubleshooting Guide Fails to Start
Check power source.
Check of circuit breaker and fuse.
Check control switch setting.
Check control switch.
Compressor only fails to start.
Fan only fails to start.
Improper wiring. Drop of power voltage.
Defect of compressor capacitor.
Loose terminal connection.
Improper wiring
Defect of fan motor capacitor.
Irregular motor resistance (ē) Irregular motor insulation (ē)
Capacitor check.
Replacement of capacitor. Replacement of fan motor.
Irregular motor resistance ( ē )
Regular but fails to start.
Irregular motor insulation ( ē ) Replacement of compressor. Replacement of compressor
14
Troubleshooting Guide VOLTAGE LIMITS NAME PLATE RATING
MINIMUM
MAXIMUM
380 - 415 V
342 V
456 V
1. No cooling and heating operation performed 1) Both the blower and the compressor do not work WHAT TROUBLED Other parts except the unit
COMPLAINTS
HOW TO CHECK
Electric supply interrupted Defective power wiring Cut off power fuse
Too low voltage
Measure power sypply with a tester in case that the same power source is supplied to other equipment except the unit, what and where troubled can be discovered by checking the operation of other equipment.
REMEDY Repair a switch box and relative instrument. Replacement of fuse Request a power supplier to repair.
Measure it with a tester.
Check the power source. Use a thick cable if necessary.
Magnetic switch for compressor & fan motor
Control point is on condition of "OFF" due to trouble.
Make short-circuit, then measure it with tester.
Replace it if necessary.
Operating switch
Troubled or defective contactor
Check it with the eyes or tester.
Repair or replace it.
2) Only Indoor blowers do not work WHAT TROUBLED Motor
Capacitor
Electric wiring
COMPLAINTS
HOW TO CHECK
Over heated Wiring short Defected Cut- OFF of wiring Short circuited on operation
15
REMEDY
Check it with tester
Repair or replace it.
Check it with a tester.
Replace it.
Check it with a tester.
Rewiring or Repair.
Troubleshooting Guide 3) Only outdoor fan does not work WHAT TROUBLED Motor Electric Wiring
COMPLAINTS
HOW TO CHECK
Over-heated Wire short Cut off of wiring
REMEDY
Check how it is insulated.
Repair or replace it.
Check it with a tester.
Rewiring or repair.
Short circuited on operation
4) Only compressor does not work WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Magnetic switch for compressor motor
Defective contact, magnetic coil troubled.
Check it with the eyes on with a tester.
Repair or replace it.
Compressor motor
Troubled over-heated (layer short)
Check how it is insulated.
Replace or repair the compressor.
High pressure switch
Troubled or defective contact or operating
Check it with a tester.
Replace it if necessary.
Electric circuit
Defective connection or disconnection of the circuit for compressor.
Check it with a tester.
Rewiring or push reset button.
16
Troubleshooting Guide 2. The Units discontinue after the operation started WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Outdoor coil
Coil is dirty *1
Checking
Wash it by means of something like chemical washing.
In-condensable gas blended.
Air intruded into the refrigerant pipe line *1
In the event that difference between the saturating temperature corresponding to high pressure and the temperature of air discharged from the outdoor coil is more than ʚ 15 C, incondensable gas may be blended.
Extract air by vacuum pump, then replenish (charge) the refrigerant.
Improper adjustment
Check it with a pressure gauge.
Read just it to normal operating pressure. (Note) Don't alternate the specified adjusting pressure. If the adjusted pressure exceed the specified range, it will cause a great accident.
A shortage of refrigerant amount.
Check pressure
Replenish the refrigerant. Repair the spot where it is leaked.
Reverse rotation of fan Obstacle
Confirm the wind blowing out upward.
Air short circuit *1
Check it with eyes.
If reversed, connect interchanged wires to each terminal. Power wirings.
High pressure switch (Option part)
Refrigerant
Outdoor Fan
Note: Use an appropriate measuring instrument for readjustment. *1: High-pressure switch moves.
17
Troubleshooting Guide 3. The unit is working, but not cooling and heating sufficiently (Both blower and compressor are working) WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Load
Much Cooling or Heating load
Heat load increased. Window or door has many cracks or gaps.
Do necessary disposal respectively.
Air flow
Obstacle disturbs Intake of uniform airflow.
Checking
Correct it.
Short air volume
Reverse rotation of blower.
Checking
Correct it.
Refrigerant
Shortage in the charged refrigerant.
Coil inlet pipe is frosted
Recharge it. (Repair the leakage spot).
Air passage
Improper or foreign bodies
Checking
Correct or clear the foreign bodies.
Air filter
Clogged with dust
Checking
Cleaning
4. All the functions are performed as specified, but very noisy and vibrant WHAT TROUBLED Compressor
Blower
COMPLAINTS
HOW TO CHECK
REMEDY
Liquid refrigerant flooding back from the evaporator.
Check for refrigerant over-charge. Check to see if the intake air temperature is extremely cold. Check for insufficient air flow quantity.
Faulty Discharge valve and suction valve.
Checking
Fan broken.
Replace the compressor
Checking
Repair or replace it. Clear the foreign bodies.
Foreign matters intruded. Screws
Looseness or fail-off of screws
Checking
Correct
Electric troubles (Magnetic contactor)
Defective contact. Defective contact point. Rusting and foreign matters in the iron core contact face. Defective contact of the operating switch.
Checking
Repair and clean or replace it.
Others
Improper installation
Checking
Correct it.
18
Electronic parts Troubleshooting Guide Possible trouble 1 Is the input voltage of transformer AC220V?
: The unit does not operate. NO
1. Check the Fuse. 2. Check the wiring of AC220V.
NO
1. Exchange the transformer. 2. Check the connector of transformer.
YES
Is the output voltage of transformer AC24V & AC13V? YES
Is the output voltage of IC02D(7805) on the main PCB DC5V?
NO
1. Exchange IC02D(7805) on the main PCB. 2. Check the D01D~D05D, R05C on the main PCB.
YES
Is the output voltage of IC01D(7812 ) on the main PCB DC12V?
NO
1. Exchange IC01D(7812) on the main PCB. 2. Check the D01D~D05D, R05C on the main PCB.
YES
Is the output voltage of IC01A(7036) on the main PCB DC5V?
NO
1. Exchange IC01A(7036) on the main PCB.
YES
OSC vibration?
NO
1. Exchange OSC. 2. Check the pattern around OSC on the main PCB.
YES
1. Exchange main PCB ASS'Y
Possible trouble 2 Is the power ON?
: The remote-controller does not operate. NO
1. Exchange or exchange FUSE. 2. Check the input voltage of Main PCB ASS'Y.
YES
Is the input voltage of remote-controller DC12V?
NO
1. Check or exchange the IC01D on the Main PCB. 2. Check or exchange the Connector (RED, BROWN) of the remote controller.
YES
1. Exchange remote-controller 2. Check or exchange the Main PCB ASS'Y.
19
Electronic parts Troubleshooting Guide Possible trouble 3 Is the connection between MAIN PCB and remote-controller correct?
: Key input of remote-controller does not respond. 1. Check or repair Connector wiring. 2. Exchange the Connector.
NO
YES
Is any key on the remote-controller keeping pressed?
1. Replace the pressed key. 2. Exchange the Knob or Key.
YES
NO
Is there Check(F**) on the remote controller LCD?
YES
1. Remove cause of Check. 2. Reenergize the power supply.
NO
Is the input power voltage of remote-controller DC12V?
NO
1. Check or exchange IC01D (7812) on the MAIN PCB.
YES
Is there OSC vibration on the remote-controller PCB?
NO
1. Exchange OSC 2. Check the pattern around OSC on the remote-controller PCB.
YES
Do Keys have troubles?
YES
1. Check Keys. 2. Repair or exchange Key.
NO
Exchange remote-controller.
Possible trouble 4 Are there trouble in LCD parts?
: LCD display on the remote-controller shows some trouble. YES
1. Check crack, damage of LCD. 2. Check LCD pattern.
NO
Is there trouble in the remote-controller PCB ASS'Y?
YES
1. Check or repair all IC with dust or moisture on the PCB. 2. Exchange remote-controller PCB.
NO
Exchange remote-controller.
20
Electronic parts Troubleshooting Guide Possible trouble 5
Is the unit operating?
: No cooling operation performed. NO
1. Press power ON/OFF button.
YES
Is the cooling mode?
NO
1. Press cooling operation key. 2. After reenergizing power supply, press power "ON/OFF" button.
NO
1. Set flowing. 'Set Temp. < Room Temp.'
YES
Set Temp. < Room Temp.?
YES
Is the output voltage of Micom's 4PIN on the MAIN PCB DC0V?
NO
1. Check or exchange IC02D. 2. Check 3-minutes time delay.
YES
Is the voltage between 1PIN of CN-COMP and NEUTRAL 220V?
NO
1. Check or exchange RY4.
YES
Is the magnetic contactor for compressor OK?
NO
1. Check the wiring of Magnetic contactor. 2. Exchange Magnetic contactor.
YES
1. Check Compressor and Capacitor for Compressor. NOTE: 3Đmodel has not capacitor for compressor.
21
Electronic parts Troubleshooting Guide Possible trouble 7 Is the indoor fan operation?
: No humidifier operation performed. 1. Press cooling or fan operation or heater operation key.
NO
YES
Is the HUMID LCD "ON"?
NO
1. Press humidifier Key.
YES
Is the output voltage of Micom's 3PIN on the MAIN PCB 5V?
1. Check or exchange IC02D on the MAIN PCB.
NO
YES
Is the voltage between 1PIN of CN5 and NEUTRAL 220V?
NO
1. Check or exchange RY3.
YES
Is the magnetic contactor for humidifier OK?
NO
1. Check the wiring or Magnetic contactor. 2. Exchange Magnetic contactor.
YES
Check the humidifier.
22
Electronic parts Troubleshooting Guide Possible trouble 8
Is the unit operating?
: Indoor motor does not operate.
NO
1. Press power ON/OFF button. 2. Reconnect the power supply.
YES
Is the output voltage of Micom's 10PIN on the MAIN PCB 5V?
NO
1. Check or exchange IC01D, IC02D on the main PCB.
YES
Is the voltage between 1PIN of CN8 and NEUTRAL 220V?
NO
1. Check or exchange RY10.
YES
Is the "Power relay" for indoor motor OK?
NO
1. Check the wiring of "Power relay". 2. Exchange "Power relay".
YES
Check the indoor motor.
Possible trouble 9
Is it cooling operation?
: Outdoor motor does not operate.
NO
1. Press power "ON/OFF" button. 2. Select cooling operation.
YES
Is the compressor operating?
NO
1. Set following. Set temp. < Room temp. 2. Wait, if the unit has operating with 3-minute time delay.
YES
1. Check wiring for outdoor motor and magnetic contactor. 2. Check outdoor motor & capacitor.
23
Features of Controller 1. Main Controller Circuit Diagram
24
2. Feature of Main Controller Model No.:TN-C090BT00 TN-C120BT00
25
Model No.:TN-C180BT00 TN-C24 0BT00
26
3. Feature of Remote-Controller PCB ASS'Y
4. Feature of Remote-Controller LCD
27
5. Error Mode & Corrective Method Error mode
Cause of error
Sensing condition of error
CH01
OPEN/SHORT of Voltage of sensing: Over 4.8V room temp. Voltage of sensing: Less than sensor 0.5V
CH02
OPEN/SHORT of Voltage of sensing: Over 4.8V indoor pipe temp. Voltage of sensing: Less than 0.5V sensor Communication Error
CH03
CH05
CH18
Communication interruption between remote controller and Main PCB for 2 minutes.
Communication of Connecting cable connected to indoor and outdoor indoor and outdoor unit connect wrong or badness. Error
Pressure Error
Pressure of system: Higher than high pressure switch spec / lower than low pressure switch spec.
28
Method of SVC
Remark
RoomDŽ 1. Check the voltage of "CO1H" temp.(25 C) on the remote controller. = DC 2.5V 2. Check the temp. sensor of remtote controller. DŽ 1. Check the voltage between PIN 3 Pipe temp.(25 C) and 4 of CN-A cycle/CN-B cycle. = DC 2.2V 2. Check the temp. sensor of indoor pipe. 1. Check the connecting wire between main PCB remote controller. 2. Check the input voltage of remote-controller. 3. Check the wiring of remote-controller. 1. Check the connection between connecting cable and T/B. 2. Check the sequence of the connecting cable. 1. Check the refrigerant of the system. 2. Check the leakage of system. 3. Check the pressure switch.
Input voltage of remote-controller = DC 12V
For all models
For TN-C180BT00/ TN-C240BT00.It may at least one of the four switches has action.
9. Explanation of principal function Flow Chart START(Power supply) YES
1. Initialize "micom". 2. A/D convert. 3. Main PCB: Waiting cooling operation. 4. Remote controller: Waiting input. Dehumidification Mode? A
YES YES
Power ON?
NO
Dehumidification operating YES NO
Cooling Mode?
Stop condition?
YES
YES
Go to A
NO
Set Temp. < Indoor Temp.
YES YES
Time delay mode
NO
Cooling operating
NO
Stop condition?
YES
Go to A
29
Exploded View and Replacement Parts List 1. Indoor Unit Exploded View
437210
135515
137211
137213
152302
336610
359012
354210
W4400
352118
346811
352114 330870
263230-1
267110 263230-2 130411 263230-3
268711
249951
30
Exploded View and Replacement Parts List
135515
137211
137213
152302 336610
354210
W4400 346810
352118 330870 352114
263230-1
267110 263230-2 130411
268711C
249951
Exploded View and Replacement Parts List 2. Outdoor Unit Exploded View 435311
559010 549610
346811
330870
W4811 554030-1
554030-2
237204-1
554030-3
554030-4
649950 548490 268711
237204-2 554160
552203-2 552203-1
Exploded View and Replacement Parts List
559010
346811
554030B
268711
566001
554160A
554030A
Exploded View and Replacement Parts List
559010
554030B 346811
268711
554030A 566001
554160A
Memo
26
Memo
27
P/No.: 3828A25001C
JULY, 2007 Printed in CHINA