PACKAGE AIR CONDITIONERS FORM NO. A11-179 REV. 2 Supersedes Form No. A11-179 Rev. 1

RSKJ- STANDARD EFFICIENCY 10-SEER SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW]

RSMJ- HIGH EFFICIENCY 12-SEER SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW]

RSNJ- SUPER HIGH EFFICIENCY 13-SEER SERIES NOMINAL SIZES 2-5 TON [7-17.6 kW]

TABLE OF CONTENTS

Unit Features & Benefits ................................................................................3-6 Model Identification Options ..............................................................................7 General Data RSKJ- Series ............................................................................................8-9 RSMJ- Series ........................................................................................10-11 RSNJ- Series ........................................................................................12-14 General Data Notes ........................................................................................15 Performance Data RSKJ- Cooling Series ............................................................................16-18 RSMJ- Cooling Series ............................................................................19-21 RSNJ- Cooling Series ............................................................................22-24 Airflow Performance RSKJ/RSMJ/RSNJ- Series ..........................................25-26 Electrical Data RSKJ- Series ..............................................................................................27 RSMJ- Series..............................................................................................28 RSNJ- Series ..............................................................................................29 Electric Heater Kits ....................................................................................30-37 Dimensional Data ..........................................................................................38 Typical Installations ........................................................................................39 Accessories ..................................................................................................40 Typical Wiring ............................................................................................41-42 Limited Warranty ............................................................................................43

2

UNIT FEATURES & BENEFITS—RSKJ/RSMJ/RSNJ- SERIES

3 1 The RSKJ/RSMJ and RSNJ series of Package Air Conditioners are designed to be the most efficient, quickest to install, easiest to service, and most reliable units in the industry - while still maintaining an affordable price. This platform provides you with a full line of nominal capacities from 2 through 5 tons. RSKJ models are 10 SEER, RSMJ models are 12 SEER, and RSNJ Models are 13 SEER, each ARI-certified.

Starting at the bottom, the base rails ( 1 ) allow for separation between the unit base and the ground level, protecting the base from ground moisture and providing air circulation around the unit. Constructed from sturdy 14-gauge G-90 sheet metal, the base rails also allow for easier maneuverability during installation. In some instances, installers may choose to remove the base rails to allow for the lower installation clearances encountered in some homes. Once the base rails are removed, though, the base of the unit is still positioned above the pad by a shorter secondary base rail ( 2 ).

As with all units offered by Rheem, we started our design process with input from the customer. From fan grille to the base rails, Rheem has combined 30 years worth of package unit design experience with input from Dealers to meet the latest application requirements.

1

1

3

2

UNIT FEATURES & BENEFITS—RSKJ/RSMJ/RSNJ- SERIES

4 3

While other manufacturers have chosen to use pre-painted steel in their equipment, which exposes raw edges and invites rust and sharp edges, Rheem package equipment uses a powder-coat paint system, rated at 1000 hour salt spray per ASTM B117. The powder-coat process also greatly diminishes and dulls sharp edges, reducing the occurrence of cuts and torn clothes.

5

To provide flexibility in space-limited installations, the unit can be installed flush to the structure without blocking airflow over the outdoor coil or making any screws inaccessible for maintenance. Furthermore, the cabinet is a slim 33” wide. Full-louver coil protection ( 3 ) makes Rheem unique in the industry and also totally protects the outdoor coil from vandalism and weather extremes.

7

Two round 14" duct collar ( 4 ) are included with the unit, which makes attaching duct a snap. The collar is crimped around the leading edge, making it easier to install duct onto the collar. A metal bead around the circumference prevents the attached ducting from sliding off after installation.

8 6

Keeping service technicians in mind, Rheem takes pride providing easy access to internal components. The outdoor-section top cover ( 5 ) is easily removed to allow access to the the scroll compressor ( 6 ), outdoor fan motor ( 7 ), and refrigerant tubing ( 8 ).

4

UNIT FEATURES & BENEFITS—RSKJ/RSMJ/RSNJ- SERIES

The controls are located in a large, easy-to-access control box ( 12 ), which provides plenty of space in which to troubleshoot. The transformer ( 13 ) is protected by an in-line fuse, which protects the transformer during a low-voltage electrical short. The lowvoltage ( 14 ) and high-voltage ( 15 ) wiring connections are easily accessed and have ample room around which to maneuver. Troubleshooting is further aided with number- and color-coded wiring, which corresponds with the large, easy-to-read wiring diagram located on the inside of the control box access panel.

10

9 11

The indoor-section top cover also easily opens to access the removable blower housing and motor ( 9 ). This also gains total access to the indoor coil for cleaning and service ( 10 ).

15

The indoor motor and blower system will achieve nominal 400 CFM per ton up to a minimum of .8 inches of static pressure, which helps to eliminate customer dissatisfaction over poor airflow brought about by high-static duct designs.

12 13

Optional electric heat ( 11 ) can be specified as factory installed, or can be easily installed in the field, with either dual- or single-point power connections.

11 14

5

UNIT FEATURES & BENEFITS—RSKJ/RSMJ/RSNJ- SERIES Foil-faced insulation is securely glued and captured to the cabinet. On the base of the unit, closed-cell insulation is used to prevent moisture from being absorbed and help reduce mold content to provide better indoor air quality.

High and low refrigerant pressure can easily and accurately be measured using the two gauge ports ( 16 ) located inside the control box.

16

For reliability and long-lasting operation, Rheem uses 100% scroll compressor technology ( 19 ) on all package platforms. With over 12 years of history, the scroll compressor has proven to be reliable, efficient, and quiet during operation.

A small side panel grants access to a removable, sloped drain pan ( 17 ), which helps to ensure indoor air quality (IAQ) throughout the life of the unit. A 3/4" drain trap ( 18 ) assembly is provided for convenience.

19

17

18

6

MODEL IDENTIFICATION—RSKJ/RSMJ/RSNJ- SERIES

R S K J — A 036 J K 010 Heating Capacity (Factory Installed) 000 = No Resistance Heat 005 = 05 KW Resistance Heat 007 = 07 KW Resistance Heat 010 = 10 KW Resistance Heat 015 = 15 KW Resistance Heat 020 = 20 KW Resistance Heat Drive Package K = Direct Drive Electrical Designation J = 208-230V—1PH—60 Hz C = 208-230V—3PH—60 Hz (13 SEER only) Nominal Cooling Capacity (BTUH) [kW] 024 = 24,000 [7.03] 030 = 30,000 [8.79] 036 = 36,000 [10.55] 042 = 42,000 [12.31] 048 = 48,000 [14.07] 060 = 60,000 [17.59] Future Technical Variations Design Series J = Horizontal Discharge Efficiency Designation K = 10 SEER Standard Efficiency M = 12 SEER High Efficiency N = 13 SEER Super High Efficiency Product Classification S = Package Air Conditioner Tradebrand R = Rheem

[ ] Designates Metric Conversions

7

GENERAL DATA—RSKJ- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSKJ- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2

A024JK

A030JK

A036JK

A042JK

24,800 [7.3] 9.5/10

32,000 [9.4] 9.3/10

38,000 [11.1] 9.1/10

CONTINUED 41,500 [12.2] 9.3/10

800/800 [378/378] 23,800 [7]

1000/1000 [472/472] 30,800 [9]

1200/1200 [566/566] 36,600 [10.7]

1300/1400 [613/661] 40,000 [11.7]

Net Sensible Capacity Btu [kW]

17,800 [5.2]

22,900 [6.7]

27,300 [8]

30,800 [9]

Net Latent Capacity Btu [kW]

6,000 [1.8]

7,900 [2.3]

9,300 [2.7]

9,200 [2.7]

2.5

3.3

4

4.3

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 78

Louvered

Louvered

Louvered

Louvered

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 16 [6]

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 16 [6]

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 20 [8]

Rifled 0.375 [9.5] 12.65 [1.18] 1 / 22 [9]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

4.33 [0.4]

4.33 [0.4]

4.33 [0.4]

5.78 [0.54]

2 / 15 [6] TX Valves 1/.75 [19] Propeller

2 / 15 [6] TX Valves 1/.75 [19] Propeller

2 / 15 [6] TX Valves 1/.75 [19] Propeller

3 / 13 [5] TX Valves 1/.75 [19] Propeller

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

Direct/1

Direct/1

Direct/1

Direct/1

3200 [1510] 1 at 1/3 HP

3200 [1510] 1 at 1/3 HP

3200 [1510] 1 at 1/3 HP

3200 [1510] 1 at 1/3 HP

Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Compressor No./Type Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Indoor Coil—Fin Type Tube Type Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm]3 Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM (Nominal) Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

1

1

1

1

1/4

1/3

1/2

1/2

1075

1075

1075

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x20x16 [25x508x406]

(1)1x20x24 [25x508x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

60 [1701]

60 [1701]

62 [1758]

77 [2183]

Net Weight lbs. [kg]

304 [138]

306 [139]

309 [140]

333 [151]

Ship Weight lbs. [kg]

328 [149]

330 [150]

333 [151]

357 [162]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 15 for Notes.

8

GENERAL DATA—RSKJ- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSKJ- Series

A048JK

A060JK

48,500 [14.2] 8.7/10

61,000 [17.9] 9/10

1600/1600 [755/755] 46,500 [13.6]

2000/1900 [944/897] 58,500 [17.1]

Net Sensible Capacity Btu [kW]

34,700 [10.2]

42,500 [12.5]

Net Latent Capacity Btu [kW]

11,800 [3.5]

16,000 [4.7]

5.3

6.5

1/Copeland Scroll 78

1/Copeland Scroll 78

Louvered

Louvered

Rifled 0.375 [9.5] 16.54 [1.54] 1 / 22 [9]

Rifled 0.375 [9.5] 16.54 [1.54] 2 / 22 [9]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

5.78 [0.54]

5.78 [0.54]

2 / 15 [6] TX Valves 1/.75 [19] Propeller

3 / 13 [5] TX Valves 1/.75 [19] Propeller

1/24 [609.6]

1/24 [609.6]

Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Compressor No./Type Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Indoor Coil—Fin Type Tube Type Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm]3 Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM (Nominal) Motor Frame Size Filter—Type Furnished

Direct/1

Direct/1

4200 [1982] 1 at 1/3 HP

4000 [1888] 1 at 1/3 HP

1075

1075

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

1

1

3/4

3/4

1075

1075

48 Field Supplied

48 Field Supplied

No

No

(1)1x24x30 [25x610x762]

(1)1x24x30 [25x610x762]

92 [2608]

160 [4536]

Net Weight lbs. [kg]

349 [158]

364 [165]

Ship Weight lbs. [kg]

375 [170]

390 [177]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 15 for Notes.

9

GENERAL DATA—RSMJ- SERIES NOMINAL SIZES 2-5 TON [7-17.6 kW] Model RSMJ- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2

A024JK

A030JK

A036JK

A042JK

24,800 [7.3] 11/12

32,000 [9.4] 11.2/12

38,000 [11.1] 11.1/12

CONTINUED 41,500 [12.2] 11/12

800/800 [378/378] 23,800 [7]

1000/1000 [472/472] 30,800 [9]

1200/1200 [566/566] 36,600 [10.7]

1300/1400 [613/661] 40,000 [11.7]

Net Sensible Capacity Btu [kW]

17,800 [5.2]

22,900 [6.7]

27,300 [8]

30,800 [9]

Net Latent Capacity Btu [kW]

6,000 [1.8]

7,900 [2.3]

9,300 [2.7]

9,200 [2.7]

2.2

2.8

3.3

3.6

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 78

Louvered

Louvered

Louvered

Louvered

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 16 [6]

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 16 [6]

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 20 [8]

Rifled 0.375 [9.5] 12.65 [1.18] 1 / 22 [9]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

4.33 [0.4]

4.33 [0.4]

4.33 [0.4]

5.78 [0.54]

2 / 15 [6] TX Valves 1/.75 [19] Propeller

2 / 15 [6] TX Valves 1/.75 [19] Propeller

2 / 15 [6] TX Valves 1/.75 [19] Propeller

3 / 13 [5] TX Valves 1/.75 [19] Propeller

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

Direct/1

Direct/1

Direct/1

Direct/1

3200 [1510] 1 at 1/3 HP

3200 [1510] 1 at 1/3 HP

3200 [1510] 1 at 1/3 HP

3200 [1510] 1 at 1/3 HP

Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Compressor No./Type Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Indoor Coil—Fin Type Tube Type Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm]3 Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM (Nominal) Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

1

1

1

1

1/4

1/3

1/2

1/2

1075

1075

1075

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x20x16 [25x508x406]

(1)1x20x24 [25x508x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

60 [1701]

60 [1701]

62 [1758]

77 [2183]

Net Weight lbs. [kg]

304 [138]

306 [139]

309 [140]

333 [151]

Ship Weight lbs. [kg]

328 [149]

330 [150]

333 [151]

357 [162]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 15 for Notes.

10

GENERAL DATA—RSMJ- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSMJ- Series

A048JK

A060JK

48,500 [14.2] 11/12

61,000 [17.9] 10.6/12

1600/1600 [755/755] 46,500 [13.6]

2000/1900 [944/897] 58,500 [17.1]

Net Sensible Capacity Btu [kW]

34,700 [10.2]

42,500 [12.5]

Net Latent Capacity Btu [kW]

11,800 [3.5]

16,000 [4.7]

4.2

5.5

1/Copeland Scroll 78

1/Copeland Scroll 78

Louvered

Louvered

Rifled 0.375 [9.5] 16.54 [1.54] 1 / 22 [9]

Rifled 0.375 [9.5] 16.54 [1.54] 2 / 22 [9]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

5.78 [0.54]

5.78 [0.54]

2 / 15 [6] TX Valves 1/.75 [19] Propeller

3 / 13 [5] TX Valves 1/.75 [19] Propeller

1/24 [609.6]

1/24 [609.6]

Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Compressor No./Type Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Indoor Coil—Fin Type Tube Type Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm]3 Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM (Nominal) Motor Frame Size Filter—Type Furnished

Direct/1

Direct/1

4200 [1982] 1 at 1/3 HP

4000 [1888] 1 at 1/3 HP

1075

1075

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

1

1

3/4

3/4

1075

1075

48 Field Supplied

48 Field Supplied

No

No

(1)1x24x30 [25x610x762]

(1)1x24x30 [25x610x762]

92 [2608]

160 [4536]

Net Weight lbs. [kg]

349 [158]

364 [165]

Ship Weight lbs. [kg]

375 [170]

390 [177]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 15 for Notes.

11

GENERAL DATA—RSNJ- SERIES NOMINAL SIZES 2-5 TON [7-17.6 kW] Model RSNJ- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW

A024JK

A030JK

A036CK

A036JK

25,600 [7.5] 11.9/13

30,400 [8.9] 11.45/13

36,000 [10.5] 11.5/13

CONTINUED 36,000 [10.5] 11.5/13

800/800 [378/378] 24,600 [7.2]

1000/1000 [472/472] 29,200 [8.6]

1200/1200 [566/566] 34,600 [10.1]

1200/1200 [566/566] 34,600 [10.1]

18,400 [5.4] 6200 [1.8]

22,300 [6.5] 6900 [2]

27,300 [8] 7300 [2.1]

27,300 [8] 7300 [2.1]

2.1

2.6

3

3

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 76

Louvered

Louvered

Louvered

Louvered

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 16 [6]

Rifled 0.375 [9.5] 10.44 [0.97] 1 / 16 [6]

Rifled 0.375 [9.5] 12.65 [1.18] 1 / 22 [9]

Rifled 0.375 [9.5] 12.65 [1.18] 1 / 22 [9]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

4.33 [0.4]

4.33 [0.4]

4.33 [0.4]

4.33 [0.4]

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

2 / 15 [6] TX Valves 1/1 [25.4] Propeller

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

Direct/1

Direct/1

Direct/1

Direct/1

3400 [1604] 1 at 1/3 HP

3400 [1604] 1 at 1/3 HP

3400 [1604] 1 at 1/3 HP

3400 [1604] 1 at 1/3 HP

Compressor No./Type Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Indoor Coil—Fin Type Tube Type Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm]3 Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM (Nominal) Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

FC Centrifugal 1/10x9 [254x228.6] Direct/2

1

1

1

1

1/4

1/3

1/2

1/2

1033

1080

1050

1050

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x20x16 [25x508x406]

(1)1x20x20 [25x508x508]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

Refrigerant Charge Oz. [g]

60 [1701]

58 [1644]

73 [2070]

73 [2070]

Weights Net Weight lbs. [kg]

304 [138]

306 [139]

309 [140]

309 [140]

328 [149]

330 [150]

333 [151]

333 [151]

(No.) Size Recommended in. [mm]

Ship Weight lbs. [kg]

[ ] Designates Metric Conversions

See Page 15 for Notes.

12

GENERAL DATA—RSNJ- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSNJ- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW

A042CK

A042JK

A048CK

A048JK

42,000 [12.3] 11.3/13

42,000 [12.3] 11.3/13

48,000 [14.1] 11.4/13

CONTINUED 48,000 [14.1] 11.4/13

1400/1400 [661/661] 40,500 [11.9]

1400/1400 [661/661] 40,500 [11.9]

1500/1600 [708/755] 46,000 [13.5]

1500/1600 [708/755] 46,000 [13.5]

31,100 [9.1]

31,100 [9.1]

35,800 [10.5]

35,800 [10.5]

9400 [2.8]

9400 [2.8]

10,200 [3]

10,200 [3]

3.6

3.6

4

4

1/Copeland Scroll 76

1/Copeland Scroll 76

1/Copeland Scroll 78

1/Copeland Scroll 78

Louvered

Louvered

Louvered

Louvered

Rifled 0.375 [9.5] 12.65 [1.18] 1 / 22 [9]

Rifled 0.375 [9.5] 12.65 [1.18] 1 / 22 [9]

Rifled 0.375 [9.5] 16.54 [1.54] 1 / 22 [9]

Rifled 0.375 [9.5] 16.54 [1.54] 1 / 22 [9]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

5.78 [0.54]

5.78 [0.54]

5.78 [0.54]

5.78 [0.54]

3 / 13 [5] TX Valves 1/1 [25.4] Propeller

3 / 13 [5] TX Valves 1/1 [25.4] Propeller

3 / 13 [5] TX Valves 1/1 [25.4] Propeller

3 / 13 [5] TX Valves 1/1 [25.4] Propeller

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

1/24 [609.6]

Direct/1

Direct/1

Direct/1

Direct/1

3400 [1604] 1 at 1/3 HP

3400 [1604] 1 at 1/3 HP

4200 [1982] 1 at 1/3 HP

4200 [1982] 1 at 1/3 HP

Compressor No./Type Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Indoor Coil—Fin Type Tube Type Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm]3 Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM (Nominal) Motor Frame Size Filter—Type Furnished

1075

1075

1075

1075

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

1

1

1

1

1/2

1/2

3/4

3/4

1075

1075

1075

1075

48 Field Supplied

48 Field Supplied

48 Field Supplied

48 Field Supplied

No

No

No

No

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

76 [2155]

76 [2155]

102 [2892]

102 [2892]

Net Weight lbs. [kg]

333 [151]

333 [151]

349 [158]

349 [158]

Ship Weight lbs. [kg]

357 [162]

357 [162]

375 [170]

375 [170]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 15 for Notes.

13

GENERAL DATA—RSNJ- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSNJ- Series

A060CK

A060JK

64,000 [18.8] 11.2/13

64,000 [18.8] 11.2/13

2000/1900 [944/897] 61,000 [17.9]

2000/1900 [944/897] 61,000 [17.9]

Net Sensible Capacity Btu [kW]

46,400 [13.6]

46,400 [13.6]

Net Latent Capacity Btu [kW]

14,600 [4.3]

14,600 [4.3]

5.5

5.5

1/Copeland Scroll 78

1/Copeland Scroll 78

Louvered

Louvered

Rifled 0.375 [9.5] 16.54 [1.54] 2 / 22 [9]

Rifled 0.375 [9.5] 16.54 [1.54] 2 / 22 [9]

Louvered Rifled 0.375 [9.5]

Louvered Rifled 0.375 [9.5]

5.78 [0.54]

5.78 [0.54]

4 / 13 [5] TX Valves 1/1 [25.4] Propeller

4 / 13 [5] TX Valves 1/1 [25.4] Propeller

1/24 [609.6]

1/24 [609.6]

Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW]

Net System Power kW Compressor No./Type Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Tube Type Tube Size in. [mm] OD Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Indoor Coil—Fin Type Tube Type Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control Drain Connection No./Size in. [mm]3 Outdoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds CFM [L/s] No. Motors/HP Motor RPM Indoor Fan—Type No. Used/Diameter in. [mm] Drive Type/No. Speeds No. Motors Motor HP Motor RPM (Nominal) Motor Frame Size Filter—Type Furnished

Direct/1

Direct/1

4000 [1888] 1 at 1/3 HP

4000 [1888] 1 at 1/3 HP

1075

1075

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

FC Centrifugal 1/11x9 [279.4x228.6] Direct/2

1

1

3/4

3/4

1075

1075

48 Field Supplied

48 Field Supplied

No

No

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

173 [4905]

173 [4905]

Net Weight lbs. [kg]

364 [165]

364 [165]

Ship Weight lbs. [kg]

390 [177]

390 [177]

(No.) Size Recommended in. [mm] Refrigerant Charge Oz. [g] Weights

[ ] Designates Metric Conversions

See Page 15 for Notes.

14

GENERAL DATA—RSKJ/RSMJ/RSNJ- SERIES NOTES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Standard 3/4" PVC P-Trap provided. [ ] Designates Metric Conversions

15

SYSTEMS PERFORMANCE—RSKJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSKJ-A024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

880 [415] .15

71°F [21.7°C] 800 [378] .13

680 [321] .10

880 [415] .15

67°F [19.4°C] 800 [378] .13

680 [321] .10

880 [415] .15

63°F [17.2°C] 800 [378] .13

680 [321] .10

Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power

28.1 [8.24] 17.0 [4.98] 1.9

27.6 [8.09] 16.3 [4.78] 1.9

26.8 [7.85] 15.1 [4.43] 1.9

27.1 [7.94] 20.6 [6.04] 1.9

26.6 [7.80] 19.7 [5.77] 1.9

25.9 [7.59] 18.3 [5.36] 1.9

24.7 [7.24] 23.6 [6.92] 1.9

24.2 [7.09] 22.6 [6.62] 1.9

23.6 [6.92] 21.0 [6.15] 1.9

Total BTUH [kW] 80 Sens BTUH [kW] [26.7] Power

27.9 [8.18] 16.9 [4.95] 2.0

27.4 [8.03] 16.1 [4.72] 2.0

26.6 [7.80] 15.0 [4.40] 2.0

26.9 [7.88] 20.5 [6.01] 2.0

26.4 [7.74] 19.6 [5.74] 2.0

25.7 [7.53] 18.2 [5.33] 2.0

24.4 [7.15] 23.4 [6.86] 2.0

24.0 [7.03] 22.4 [6.56] 2.0

23.3 [6.83] 20.9 [6.13] 1.9

Total BTUH [kW] 85 Sens BTUH [kW] [29.4] Power

27.5 [8.06] 16.7 [4.89] 2.1

27.0 [7.91] 15.9 [4.66] 2.1

26.3 [7.71] 14.8 [4.34] 2.0

26.5 [7.77] 20.3 [5.95] 2.1

26.0 [7.62] 19.4 [5.69] 2.1

25.3 [7.41] 18.0 [5.28] 2.0

24.0 [7.03] 23.3 [6.83] 2.1

23.6 [6.92] 22.2 [6.51] 2.1

23.0 [6.74] 20.7 [6.07] 2.0

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

26.9 [7.88] 16.4 [4.81] 2.2

26.4 [7.74] 15.6 [4.57] 2.1

25.7 [7.53] 14.5 [4.25] 2.1

25.9 [7.59] 20.0 [5.86] 2.2

25.4 [7.44] 19.1 [5.60] 2.2

24.7 [7.24] 17.7 [5.19] 2.1

23.4 [6.86] 23.0 [6.74] 2.1

23.0 [6.74] 21.9 [6.42] 2.1

22.4 [6.56] 20.4 [5.98] 2.1

26.2 [7.68] 16.0 [4.69] 2.2

25.7 [7.53] 15.3 [4.48] 2.2

25.0 [7.33] 14.2 [4.16] 2.2

25.2 [7.39] 19.6 [5.74] 2.3

24.7 [7.24] 18.7 [5.48] 2.2

24.0 [7.03] 17.4 [5.10] 2.2

22.7 [6.65] 22.5 [6.59] 2.2

22.3 [6.54] 21.6 [6.33] 2.2

21.7 [6.36] 20.1 [5.89] 2.2

25.3 [7.41] 15.6 [4.57] 2.3

24.9 [7.30] 14.9 [4.37] 2.3

24.2 [7.09] 13.9 [4.07] 2.3

24.3 [7.12] 19.2 [5.63] 2.3

23.9 [7.00] 18.3 [5.36] 2.3

23.2 [6.80] 17.1 [5.01] 2.3

21.9 [6.42] 21.9 [6.42] 2.3

21.5 [6.30] 21.2 [6.21] 2.3

20.9 [6.13] 19.7 [5.77] 2.3

Total BTUH [kW] 105 Sens BTUH [kW] [40.6] Power

24.4 [7.15] 15.2 [4.45] 2.4

24.0 [7.03] 14.5 [4.25] 2.4

23.3 [6.83] 13.5 [3.96] 2.4

23.4 [6.86] 18.8 [5.51] 2.4

23.0 [6.74] 18.0 [5.28] 2.4

22.4 [6.56] 16.7 [4.89] 2.4

20.9 [6.13] 20.9 [6.13] 2.4

20.6 [6.04] 20.6 [6.04] 2.4

20.0 [5.86] 19.4 [5.69] 2.3

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

23.4 [6.86] 14.8 [4.34] 2.5 22.4 [6.56] 14.4 [4.22] 2.6

23.0 [6.74] 14.1 [4.13] 2.5 22.0 [6.45] 13.8 [4.04] 2.6

22.4 [6.56] 13.2 [3.87] 2.4 21.4 [6.27] 12.8 [3.75] 2.5

22.4 [6.56] 18.4 [5.39] 2.5 21.4 [6.27] 18.0 [5.28] 2.6

22.0 [6.45] 17.6 [5.16] 2.5 21.0 [6.15] 17.2 [5.04] 2.6

21.4 [6.27] 16.4 [4.81] 2.4 20.4 [5.98] 16.0 [4.69] 2.5

20.0 [5.86] 20.0 [5.86] 2.5 18.9 [5.54] 18.9 [5.54] 2.6

19.6 [5.74] 19.6 [5.74] 2.5 18.6 [5.45] 18.6 [5.45] 2.5

19.1 [5.60] 19.0 [5.57] 2.4 18.1 [5.30] 18.1 [5.30] 2.5

O U T D O O R D R Y B U L B T E M P E R A T U R E

GROSS SYSTEMS PERFORMANCE DATA—RSKJ-A030 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1000 [472] .12

850 [401] .09

1100 [519] .13

67°F [19.4°C] 1000 [472] .12

850 [401] .09

1100 [519] .13

63°F [17.2°C] 1000 [472] .12

850 [401] .09

Total BTUH [kW] 39.4 [11.55] 75 Sens BTUH [kW] 22.9 [6.71] [23.9] 1.9 Power

38.7 [11.34] 21.8 [6.39] 1.8

37.7 [11.05] 20.3 [5.95] 1.8

37.0 [10.84] 27.3 [8.00] 2.5

36.3 [10.64] 26.1 [7.65] 2.5

35.4 [10.37] 24.3 [7.12] 2.4

35.7 [10.46] 31.5 [9.23] 2.4

35.0 [10.26] 30.1 [8.82] 2.4

34.1 [9.99] 28.0 [8.21] 2.4

Total BTUH [kW] 38.2 [11.20] 80 Sens BTUH [kW] 22.3 [6.54] [26.7] 2.0 Power

37.5 [10.99] 21.3 [6.24] 2.0

36.5 [10.70] 19.8 [5.80] 1.9

35.7 [10.46] 26.7 [7.83] 2.6

35.1 [10.29] 25.6 [7.50] 2.6

4.2 [10.02] 23.8 [6.98] 2.6

34.4 [10.08] 30.9 [9.06] 2.5

33.8 [9.91] 29.5 [8.65] 2.5

32.9 [9.64] 27.5 [8.06] 2.5

Total BTUH [kW] 37.0 [10.84] 85 Sens BTUH [kW] 21.8 [6.39] [29.4] 2.1 Power

36.3 [10.64] 20.8 [6.10] 2.1

35.3 [10.35] 19.3 [5.66] 2.1

34.6 [10.14] 26.2 [7.68] 2.7

34.0 [9.96] 25.0 [7.33] 2.7

33.0 [9.67] 23.3 [6.83] 2.7

33.3 [9.76] 30.4 [8.91] 2.7

32.7 [9.58] 29.0 [8.50] 2.6

31.8 [9.32] 27.0 [7.91] 2.6

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

35.9 [10.52] 21.2 [6.21] 2.2

35.3 [10.35] 20.3 [5.95] 2.2

34.3 [10.05] 18.9 [5.54] 2.2

33.5 [9.82] 25.7 [7.53] 2.9

32.9 [9.64] 24.6 [7.21] 2.8

32.0 [9.38] 22.8 [6.68] 2.8

32.2 [9.44] 29.9 [8.76] 2.8

31.6 [9.26] 28.5 [8.35] 2.8

30.8 [9.03] 26.5 [7.77] 2.7

35.0 [10.26] 20.8 [6.10] 2.3

34.4 [10.08] 19.8 [5.80] 2.3

33.4 [9.79] 18.4 [5.39] 2.3

32.6 [9.55] 25.2 [7.39] 3.0

32.0 [9.38] 24.1 [7.06] 3.0

31.1 [9.11] 22.4 [6.56] 2.9

31.2 [9.14] 29.4 [8.62] 2.9

30.7 [9.00] 28.1 [8.24] 2.9

29.8 [8.73] 26.1 [7.65] 2.8

34.2 [10.02] 20.3 [5.95] 2.5

33.5 [9.82] 19.4 [5.69] 2.4

32.6 [9.55] 18.1 [5.30] 2.4

31.7 [9.29] 24.8 [7.27] 3.1

31.2 [9.14] 23.7 [6.95] 3.1

30.3 [8.88] 22.0 [6.45] 3.0

30.4 [8.91] 29.0 [8.50] 3.0

29.9 [8.76] 27.7 [8.12] 3.0

29.1 [8.53] 25.7 [7.53] 3.0

Total BTUH [kW] 33.5 [9.82] 105 Sens BTUH [kW] 19.9 [5.83] [40.6] 2.6 Power

32.9 [9.64] 19.1 [5.60] 2.6

32.0 [9.38] 17.7 [5.19] 2.5

31.0 [9.09] 24.4 [7.15] 3.2

30.5 [8.94] 23.3 [6.83] 3.2

29.7 [8.70] 21.7 [6.36] 3.2

29.7 [8.70] 28.6 [8.38] 3.1

29.2 [8.56] 27.3 [8.00] 3.1

28.4 [8.32] 25.4 [7.44] 3.1

32.3 [9.47] 18.8 [5.51] 2.7 31.9 [9.35] 18.5 [5.42] 2.8

31.4 [9.20] 17.4 [5.10] 2.6 31.0 [9.09] 17.2 [5.04] 2.8

30.5 [8.94] 24.1 [7.06] 3.4 30.1 [8.82] 23.8 [6.98] 3.5

29.9 [8.76] 23.0 [6.74] 3.3 29.5 [8.65] 22.8 [6.68] 3.4

29.1 [8.53] 21.4 [6.27] 3.3 28.7 [8.41] 21.2 [6.21] 3.4

29.1 [8.53] 28.3 [8.29] 3.3 28.7 [8.41] 28.0 [8.21] 3.4

28.6 [8.38] 27.0 [7.91] 3.2 28.2 [8.26] 26.8 [7.85] 3.4

27.8 [8.15] 25.1 [7.36] 3.2 27.4 [8.03] 24.9 [7.30] 3.3

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1100 [519] .13

32.9 [9.64] 19.6 [5.74] 2.7 32.5 [9.52] 19.4 [5.69] 2.8

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

16

SYSTEMS PERFORMANCE—RSKJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSKJ-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1200 [566] .12

1020 [481] .09

1320 [623] .14

67°F [19.4°C] 1200 [566] .12

1020 [481] .09

1320 [623] .14

63°F [17.2°C] 1200 [566] .12

1020 [481] .09

Total BTUH [kW] 44.9 [13.16] 75 Sens BTUH [kW] 27.2 [7.97] [23.9] 3.1 Power

44.1 [12.92] 26.0 [7.62] 3.1

42.9 [12.57] 24.2 [7.09] 3.1

42.1 [12.34] 31.7 [9.29] 3.1

41.4 [12.13] 30.3 [8.88] 3.1

40.2 [11.78] 28.1 [8.24] 3.0

39.5 [11.58] 36.1 [10.58] 3.1

38.8 [11.37] 34.5 [10.11] 3.0

37.7 [11.05] 32.1 [9.41] 3.0

Total BTUH [kW] 44.0 [12.90] 80 Sens BTUH [kW] 26.8 [7.85] [26.7] 3.3 Power

43.3 [12.69] 25.6 [7.50] 3.3

42.1 [12.34] 23.8 [6.98] 3.2

41.3 [12.10] 31.3 [9.17] 3.2

40.5 [11.87] 29.9 [8.76] 3.2

39.4 [11.55] 27.8 [8.15] 3.2

38.6 [11.31] 35.7 [10.46] 3.2

37.9 [11.11] 34.1 [9.99] 3.2

36.9 [10.81] 31.7 [9.29] 3.1

Total BTUH [kW] 43.2 [12.66] 85 Sens BTUH [kW] 26.4 [7.74] [29.4] 3.4 Power

42.4 [12.43] 25.2 [7.39] 3.4

41.3 [12.10] 23.5 [6.89] 3.3

40.4 [11.84] 30.9 [9.06] 3.4

39.7 [11.63] 29.5 [8.65] 3.3

38.6 [11.31] 27.4 [8.03] 3.3

37.8 [11.08] 35.3 [10.35] 3.3

37.1 [10.87] 33.7 [9.88] 3.3

36.1 [10.58] 31.4 [9.20] 3.3

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

42.3 [12.40] 26.0 [7.62] 3.6

41.6 [12.19] 24.8 [7.27] 3.5

40.4 [11.84] 23.1 [6.77] 3.5

39.6 [11.61] 30.4 [8.91] 3.5

38.9 [11.40] 29.1 [8.53] 3.5

37.8 [11.08] 27.0 [7.91] 3.4

36.9 [10.81] 34.9 [10.23] 3.5

36.3 [10.64] 33.3 [9.76] 3.4

35.3 [10.35] 31.0 [9.09] 3.4

41.4 [12.13] 25.6 [7.50] 3.7

40.7 [11.93] 24.4 [7.15] 3.7

39.6 [11.61] 22.7 [6.65] 3.6

38.7 [11.34] 30.0 [8.79] 3.7

38.0 [11.14] 28.7 [8.41] 3.6

36.9 [10.81] 26.7 [7.83] 3.6

36.0 [10.55] 34.4 [10.08] 3.6

35.4 [10.37] 32.9 [9.64] 3.6

34.4 [10.08] 30.6 [8.97] 3.5

40.5 [11.87] 25.1 [7.36] 3.8

39.7 [11.63] 24.0 [7.03] 3.8

38.6 [11.31] 22.3 [6.54] 3.8

37.7 [11.05] 29.5 [8.65] 3.8

37.0 [10.84] 28.2 [8.26] 3.8

36.0 [10.55] 26.2 [7.68] 3.7

35.0 [10.26] 34.0 [9.96] 3.8

34.4 [10.08] 32.4 [9.50] 3.7

33.5 [9.82] 30.2 [8.85] 3.7

Total BTUH [kW] 39.4 [11.55] 105 Sens BTUH [kW] 24.6 [7.21] [40.6] 4.0 Power

38.7 [11.34] 23.5 [6.89] 3.9

37.6 [11.02] 21.8 [6.39] 3.9

36.6 [10.73] 29.0 [8.50] 3.9

35.9 [10.52] 27.7 [8.12] 3.9

35.0 [10.26] 25.8 [7.56] 3.9

34.0 [9.96] 33.4 [9.79] 3.9

33.4 [9.79] 32.0 [9.38] 3.9

32.4 [9.50] 29.7 [8.70] 3.8

37.5 [10.99] 22.9 [6.71] 4.1 36.1 [10.58] 22.3 [6.54] 4.2

36.5 [10.70] 21.3 [6.24] 4.0 35.2 [10.32] 20.8 [6.10] 4.2

35.4 [10.37] 28.4 [8.32] 4.1 34.0 [9.96] 27.8 [8.15] 4.2

34.8 [10.20] 27.2 [7.97] 4.0 33.4 [9.79] 26.6 [7.80] 4.2

33.8 [9.91] 25.3 [7.41] 4.0 32.5 [9.52] 24.7 [7.24] 4.1

32.8 [9.61] 32.8 [9.61] 4.0 31.4 [9.20] 31.4 [9.20] 4.2

32.2 [9.44] 31.4 [9.20] 4.0 30.8 [9.03] 30.8 [9.03] 4.1

31.3 [9.17] 29.2 [8.56] 4.0 30.0 [8.79] 28.6 [8.38] 4.1

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1320 [623] .14

38.2 [11.20] 24.0 [7.03] 4.1 36.8 [10.79] 23.4 [6.86] 4.3

GROSS SYSTEMS PERFORMANCE DATA—RSKJ-A042 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1400 [661] .12

1190 [562] .09

1540 [727] .14

67°F [19.4°C] 1400 [661] .12

1190 [562] .09

1540 [727] .14

63°F [17.2°C] 1400 [661] .12

1190 [562] .09

Total BTUH [kW] 50.3 [14.74] 75 Sens BTUH [kW] 30.4 [8.91] [23.9] 3.2 Power

49.4 [14.48] 29.0 [8.50] 3.2

48.1 [14.10] 27.0 [7.91] 3.2

47.0 [13.77] 36.0 [10.55] 3.2

46.1 [13.51] 34.4 [10.08] 3.2

44.9 [13.16] 32.0 [9.38] 3.2

44.3 [12.98] 41.3 [12.10] 3.2

43.5 [12.75] 39.4 [11.55] 3.2

42.3 [12.40] 36.7 [10.76] 3.1

Total BTUH [kW] 48.9 [14.33] 80 Sens BTUH [kW] 29.7 [8.70] [26.7] 3.4 Power

48.0 [14.07] 28.3 [8.29] 3.4

46.7 [13.69] 26.4 [7.74] 3.3

45.6 [13.36] 35.3 [10.35] 3.4

44.7 [13.10] 33.7 [9.88] 3.4

43.5 [12.75] 31.3 [9.17] 3.3

42.9 [12.57] 40.5 [11.87] 3.3

42.1 [12.34] 38.8 [11.37] 3.3

41.0 [12.02] 36.0 [10.55] 3.3

Total BTUH [kW] 47.7 [13.98] 85 Sens BTUH [kW] 29.1 [8.53] [29.4] 3.6 Power

46.9 [13.75] 27.8 [8.15] 3.5

45.6 [13.36] 25.9 [7.59] 3.5

44.4 [13.01] 34.7 [10.17] 3.5

43.6 [12.78] 33.2 [9.73] 3.5

42.4 [12.43] 30.8 [9.03] 3.5

41.7 [12.22] 40.1 [11.75] 3.5

41.0 [12.02] 38.2 [11.20] 3.5

39.8 [11.66] 35.6 [10.43] 3.4

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

46.7 [13.69] 28.7 [8.41] 3.7

45.9 [13.45] 27.4 [8.03] 3.7

44.6 [13.07] 25.5 [7.47] 3.6

43.3 [12.69] 34.3 [10.05] 3.7

42.6 [12.48] 32.8 [9.61] 3.7

41.4 [12.13] 30.5 [8.94] 3.6

40.7 [11.93] 39.7 [11.63] 3.7

39.9 [11.69] 37.8 [11.08] 3.6

38.9 [11.40] 35.2 [10.32] 3.6

45.7 [13.39] 28.4 [8.32] 3.9

44.9 [13.16] 27.1 [7.94] 3.8

43.7 [12.81] 25.2 [7.39] 3.8

42.4 [12.43] 34.0 [9.96] 3.9

41.6 [12.19] 32.4 [9.50] 3.8

40.5 [11.87] 30.2 [8.85] 3.8

39.7 [11.63] 39.2 [11.49] 3.8

39.0 [11.43] 37.5 [10.99] 3.8

37.9 [11.11] 34.9 [10.23] 3.7

44.8 [13.13] 28.1 [8.24] 4.0

44.0 [12.90] 26.8 [7.85] 4.0

42.8 [12.54] 24.9 [7.30] 3.9

41.5 [12.16] 33.6 [9.85] 4.0

40.7 [11.93] 32.1 [9.41] 4.0

39.6 [11.61] 29.9 [8.76] 3.9

38.8 [11.37] 38.8 [11.37] 4.0

38.1 [11.17] 37.2 [10.90] 3.9

37.0 [10.84] 34.6 [10.14] 3.9

Total BTUH [kW] 43.8 [12.84] 105 Sens BTUH [kW] 27.7 [8.12] [40.6] 4.2 Power

43.0 [12.60] 26.5 [7.77] 4.1

41.9 [12.28] 24.6 [7.21] 4.1

40.5 [11.87] 33.3 [9.76] 4.2

39.7 [11.63] 31.8 [9.32] 4.1

38.7 [11.34] 29.6 [8.67] 4.1

37.8 [11.08] 37.8 [11.08] 4.1

37.1 [10.87] 36.9 [10.81] 4.1

36.1 [10.58] 34.3 [10.05] 4.0

42.0 [12.31] 26.1 [7.65] 4.3 40.7 [11.93] 25.7 [7.53] 4.4

40.8 [11.96] 24.3 [7.12] 4.2 39.6 [11.61] 23.9 [7.00] 4.4

39.4 [11.55] 32.9 [9.64] 4.3 38.1 [11.17] 32.5 [9.52] 4.5

38.7 [11.34] 31.5 [9.23] 4.3 37.4 [10.96] 31.0 [9.09] 4.4

37.6 [11.02] 29.3 [8.59] 4.2 36.4 [10.67] 28.8 [8.44] 4.4

36.7 [10.76] 36.7 [10.76] 4.3 35.4 [10.37] 35.4 [10.37] 4.4

36.0 [10.55] 36.0 [10.55] 4.2 34.8 [10.20] 34.8 [10.20] 4.4

35.0 [10.26] 34.0 [9.96] 4.2 33.8 [9.91] 33.6 [9.85] 4.3

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1540 [727] .14

42.7 [12.51] 27.4 [8.03] 4.3 41.4 [12.13] 26.9 [7.88] 4.5

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

17

SYSTEMS PERFORMANCE—RSKJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSKJ-A048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1600 [755] .15

1360 [642] .12

1760 [831] .17

67°F [19.4°C] 1600 [755] .15

1360 [642] .12

1760 [831] .17

63°F [17.2°C] 1600 [755] .15

1360 [642] .12

Total BTUH [kW] 59.0 [17.29] 75 Sens BTUH [kW] 34.8 [10.20] [23.9] 4.1 Power

58.0 [17.00] 33.3 [9.76] 4.1

56.4 [16.53] 31.0 [9.09] 4.0

54.9 [16.09] 41.1 [12.05] 4.1

53.9 [15.80] 39.2 [11.49] 4.0

52.4 [15.36] 36.5 [10.70] 4.0

52.3 [15.33] 46.8 [13.72] 4.0

51.3 [15.03] 44.7 [13.10] 4.0

49.9 [14.62] 41.6 [12.19] 3.9

Total BTUH [kW] 57.5 [16.85] 80 Sens BTUH [kW] 34.0 [9.96] [26.7] 4.3 Power

56.4 [16.53] 32.5 [9.52] 4.2

54.9 [16.09] 30.2 [8.85] 4.2

53.3 [15.62] 40.2 [11.78] 4.3

52.4 [15.36] 38.4 [11.25] 4.2

50.9 [14.92] 35.7 [10.46] 4.2

50.7 [14.86] 46.0 [13.48] 4.2

49.8 [14.59] 43.9 [12.87] 4.2

48.5 [14.21] 40.8 [11.96] 4.1

Total BTUH [kW] 56.1 [16.44] 85 Sens BTUH [kW] 33.3 [9.76] [29.4] 4.5 Power

55.1 [16.15] 31.8 [9.32] 4.4

53.6 [15.71] 29.6 [8.67] 4.4

51.9 [15.21] 39.5 [11.58] 4.4

51.0 [14.95] 37.7 [11.05] 4.4

49.6 [14.54] 35.1 [10.29] 4.4

49.3 [14.45] 45.3 [13.28] 4.4

48.4 [14.18] 43.2 [12.66] 4.3

47.1 [13.80] 40.2 [11.78] 4.3

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

54.7 [16.03] 32.7 [9.58] 4.6

53.7 [15.74] 31.2 [9.14] 4.6

52.3 [15.33] 29.0 [8.50] 4.5

50.6 [14.83] 38.9 [11.40] 4.6

49.7 [14.57] 37.2 [10.90] 4.6

48.3 [14.16] 34.6 [10.14] 4.5

48.0 [14.07] 44.6 [13.07] 4.6

47.1 [13.80] 42.7 [12.51] 4.5

45.8 [13.42] 39.7 [11.63] 4.5

53.5 [15.68] 32.1 [9.41] 4.8

52.5 [15.39] 30.7 [9.00] 4.8

51.1 [14.98] 28.5 [8.35] 4.7

49.3 [14.45] 38.4 [11.25] 4.8

48.4 [14.18] 36.6 [10.73] 4.8

47.1 [13.80] 34.1 [9.99] 4.7

46.7 [13.69] 44.1 [12.92] 4.8

45.9 [13.45] 42.1 [12.34] 4.7

44.6 [13.07] 39.2 [11.49] 4.7

52.3 [15.33] 31.6 [9.26] 5.0

51.3 [15.03] 30.2 [8.85] 5.0

49.9 [14.62] 28.1 [8.24] 4.9

48.1 [14.10] 37.8 [11.08] 5.0

47.3 [13.86] 36.1 [10.58] 5.0

46.0 [13.48] 33.6 [9.85] 4.9

45.5 [13.33] 43.6 [12.78] 4.9

44.7 [13.10] 41.6 [12.19] 4.9

43.5 [12.75] 38.7 [11.34] 4.8

Total BTUH [kW] 51.1 [14.98] 105 Sens BTUH [kW] 31.1 [9.11] [40.6] 5.2 Power

50.2 [14.71] 29.7 [8.70] 5.1

48.8 [14.30] 27.6 [8.09] 5.1

46.9 [13.75] 37.3 [10.93] 5.2

46.1 [13.51] 35.6 [10.43] 5.1

44.9 [13.16] 33.1 [9.70] 5.1

44.4 [13.01] 43.0 [12.60] 5.1

43.6 [12.78] 41.1 [12.05] 5.1

42.4 [12.43] 38.2 [11.20] 5.0

49.0 [14.36] 29.1 [8.53] 5.3 47.9 [14.04] 28.5 [8.35] 5.5

47.7 [13.98] 27.1 [7.94] 5.3 46.6 [13.66] 26.5 [7.77] 5.4

45.8 [13.42] 36.7 [10.76] 5.4 44.6 [13.07] 36.0 [10.55] 5.6

45.0 [13.19] 35.1 [10.29] 5.3 43.8 [12.84] 34.4 [10.08] 5.5

43.7 [12.81] 32.6 [9.55] 5.3 42.6 [12.48] 32.0 [9.38] 5.4

43.2 [12.66] 42.5 [12.46] 5.3 42.0 [12.31] 41.8 [12.25] 5.5

42.4 [12.43] 40.6 [11.90] 5.3 41.3 [12.10] 39.9 [11.69] 5.4

41.3 [12.10] 37.7 [11.05] 5.2 40.1 [11.75] 37.1 [10.87] 5.4

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1760 [831] .17

49.9 [14.62] 30.5 [8.94] 5.4 48.8 [14.30] 29.8 [8.73] 5.6

GROSS SYSTEMS PERFORMANCE DATA—RSKJ-A060 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1900 [897] .14

1620 [765] .12

2090 [986] .16

67°F [19.4°C] 1900 [897] .14

1620 [765] .12

2090 [986] .16

63°F [17.2°C] 1900 [897] .14

1620 [765] .12

Total BTUH [kW] 72.0 [21.10] 75 Sens BTUH [kW] 42.7 [12.51] [23.9] 4.9 Power

70.7 [20.72] 40.8 [11.96] 4.9

68.8 [20.16] 37.9 [11.11] 4.8

67.8 [19.87] 50.1 [14.68] 4.8

66.6 [19.52] 47.8 [14.01] 4.8

64.8 [18.99] 44.5 [13.04] 4.7

64.1 [18.79] 57.6 [16.88] 4.8

62.9 [18.43] 55.0 [16.12] 4.8

61.2 [17.94] 51.1 [14.98] 4.7

Total BTUH [kW] 70.6 [20.69] 80 Sens BTUH [kW] 42.2 [12.37] [26.7] 5.1 Power

69.3 [20.31] 40.4 [11.84] 5.1

67.5 [19.78] 37.5 [10.99] 5.0

66.4 [19.46] 49.6 [14.54] 5.1

65.2 [19.11] 47.4 [13.89] 5.0

63.4 [18.58] 44.1 [12.92] 5.0

62.7 [18.38] 57.1 [16.73] 5.0

61.5 [18.02] 54.6 [16.00] 5.0

59.9 [17.55] 50.8 [14.89] 4.9

Total BTUH [kW] 69.3 [20.31] 85 Sens BTUH [kW] 41.6 [12.19] [29.4] 5.4 Power

68.0 [19.93] 39.8 [11.66] 5.3

66.2 [19.40] 37.0 [10.84] 5.2

65.1 [19.08] 49.0 [14.36] 5.3

63.9 [18.73] 46.8 [13.72] 5.3

62.1 [18.20] 43.5 [12.75] 5.2

61.3 [17.97] 56.5 [16.56] 5.2

60.2 [17.64] 54.0 [15.83] 5.2

58.6 [17.17] 50.2 [14.71] 5.1

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

67.9 [19.90] 40.8 [11.96] 5.6

66.7 [19.55] 39.0 [11.43] 5.5

64.9 [19.02] 36.3 [10.64] 5.5

63.7 [18.67] 48.2 [14.13] 5.5

62.6 [18.35] 46.0 [13.48] 5.5

60.9 [17.85] 42.8 [12.54] 5.4

60.0 [17.58] 55.7 [16.32] 5.5

58.9 [17.26] 53.2 [15.59] 5.4

57.3 [16.79] 49.5 [14.51] 5.4

66.5 [19.49] 40.0 [11.72] 5.8

65.4 [19.17] 38.2 [11.20] 5.8

63.6 [18.64] 35.5 [10.40] 5.7

62.3 [18.26] 47.3 [13.86] 5.7

61.2 [17.94] 45.2 [13.25] 5.7

59.6 [17.47] 42.1 [12.34] 5.6

58.6 [17.17] 54.8 [16.06] 5.7

57.6 [16.88] 52.4 [15.36] 5.6

56.0 [16.41] 48.7 [14.27] 5.6

65.1 [19.08] 39.1 [11.46] 6.0

64.0 [18.76] 37.4 [10.96] 6.0

62.2 [18.23] 34.7 [10.17] 5.9

60.9 [17.85] 46.5 [13.63] 6.0

59.8 [17.53] 44.4 [13.01] 5.9

58.2 [17.06] 41.3 [12.10] 5.8

57.2 [16.76] 54.0 [15.83] 5.9

56.2 [16.47] 51.6 [15.12] 5.9

54.6 [16.00] 48.0 [14.07] 5.8

Total BTUH [kW] 63.6 [18.64] 105 Sens BTUH [kW] 38.3 [11.22] [40.6] 6.3 Power

62.5 [18.32] 36.6 [10.73] 6.2

60.8 [17.82] 34.0 [9.96] 6.1

59.4 [17.41] 45.7 [13.39] 6.2

58.3 [17.09] 43.6 [12.78] 6.1

56.7 [16.62] 40.6 [11.90] 6.1

55.6 [16.29] 53.2 [15.59] 6.1

54.7 [16.03] 50.8 [14.89] 6.1

53.2 [15.59] 47.3 [13.86] 6.0

60.8 [17.82] 36.0 [10.55] 6.4 59.0 [17.29] 35.5 [10.40] 6.6

59.2 [17.35] 33.4 [9.79] 6.3 57.4 [16.82] 33.0 [9.67] 6.6

57.7 [16.91] 45.0 [13.19] 6.4 55.9 [16.38] 44.6 [13.07] 6.6

56.7 [16.62] 43.0 [12.60] 6.4 54.9 [16.09] 42.6 [12.48] 6.6

55.2 [16.18] 40.0 [11.72] 6.3 53.4 [15.65] 39.6 [11.61] 6.5

54.0 [15.83] 52.5 [15.39] 6.4 52.2 [15.30] 52.1 [15.27] 6.6

53.0 [15.53] 50.2 [14.71] 6.3 51.2 [15.01] 49.7 [14.57] 6.5

51.6 [15.12] 46.7 [13.69] 6.2 49.8 [14.59] 46.3 [13.57] 6.5

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

2090 [986] .16

61.9 [18.14] 37.6 [11.02] 6.5 60.1 [17.61] 37.2 [10.90] 6.7

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

18

SYSTEMS PERFORMANCE—RSMJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSMJ-A024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

880 [415] .18

71°F [21.7°C] 800 [378] .17

680 [321] .14

880 [415] .18

67°F [19.4°C] 800 [378] .17

680 [321] .14

880 [415] .18

63°F [17.2°C] 800 [378] .17

680 [321] .14

Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power

28.1 [8.24] 17.0 [4.98] 1.6

27.6 [8.09] 16.3 [4.78] 1.6

26.8 [7.85] 15.1 [4.43] 1.5

27.1 [7.94] 20.6 [6.04] 1.6

26.6 [7.80] 19.7 [5.77] 1.6

25.9 [7.59] 18.3 [5.36] 1.6

24.7 [7.24] 23.6 [6.92] 1.6

24.2 [7.09] 22.6 [6.62] 1.6

23.6 [6.92] 21.0 [6.15] 1.5

Total BTUH [kW] 80 Sens BTUH [kW] [26.7] Power

27.9 [8.18] 16.9 [4.95] 1.7

27.4 [8.03] 16.1 [4.72] 1.6

26.6 [7.80] 15.0 [4.40] 1.6

26.9 [7.88] 20.5 [6.01] 1.7

26.4 [7.74] 19.6 [5.74] 1.7

25.7 [7.53] 18.2 [5.33] 1.6

24.4 [7.15] 23.4 [6.86] 1.6

24.0 [7.03] 22.4 [6.56] 1.6

23.3 [6.83] 20.9 [6.13] 1.6

Total BTUH [kW] 85 Sens BTUH [kW] [29.4] Power

27.5 [8.06] 16.7 [4.89] 1.7

27.0 [7.91] 15.9 [4.66] 1.7

26.3 [7.71] 14.8 [4.34] 1.7

26.5 [7.77] 20.3 [5.95] 1.7

26.0 [7.62] 19.4 [5.69] 1.7

25.3 [7.41] 18.0 [5.28] 1.7

24.0 [7.03] 23.3 [6.83] 1.7

23.6 [6.92] 22.2 [6.51] 1.7

23.0 [6.74] 20.7 [6.07] 1.7

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

26.9 [7.88] 16.4 [4.81] 1.8

26.4 [7.74] 15.6 [4.57] 1.8

25.7 [7.53] 14.5 [4.25] 1.8

25.9 [7.59] 20.0 [5.86] 1.8

25.4 [7.44] 19.1 [5.60] 1.8

24.7 [7.24] 17.7 [5.19] 1.8

23.4 [6.86] 23.0 [6.74] 1.8

23.0 [6.74] 21.9 [6.42] 1.8

22.4 [6.56] 20.4 [5.98] 1.8

26.2 [7.68] 16.0 [4.69] 1.9

25.7 [7.53] 15.3 [4.48] 1.9

25.0 [7.33] 14.2 [4.16] 1.9

25.2 [7.39] 19.6 [5.74] 1.9

24.7 [7.24] 18.7 [5.48] 1.9

24.0 [7.03] 17.4 [5.10] 1.9

22.7 [6.65] 22.5 [6.59] 1.9

22.3 [6.54] 21.6 [6.33] 1.9

21.7 [6.36] 20.1 [5.89] 1.9

25.3 [7.41] 15.6 [4.57] 2.0

24.9 [7.30] 14.9 [4.37] 2.0

24.2 [7.09] 13.9 [4.07] 1.9

24.3 [7.12] 19.2 [5.63] 2.0

23.9 [7.00] 18.3 [5.36] 2.0

23.2 [6.80] 17.1 [5.01] 2.0

21.9 [6.42] 21.9 [6.42] 2.0

21.5 [6.30] 21.2 [6.21] 2.0

20.9 [6.13] 19.7 [5.77] 1.9

Total BTUH [kW] 105 Sens BTUH [kW] [40.6] Power

24.4 [7.15] 15.2 [4.45] 2.1

24.0 [7.03] 14.5 [4.25] 2.1

23.3 [6.83] 13.5 [3.96] 2.0

23.4 [6.86] 18.8 [5.51] 2.1

23.0 [6.74] 18.0 [5.28] 2.1

22.4 [6.56] 16.7 [4.89] 2.0

20.9 [6.13] 20.9 [6.13] 2.1

20.6 [6.04] 20.6 [6.04] 2.0

20.0 [5.86] 19.4 [5.69] 2.0

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

23.4 [6.86] 14.8 [4.34] 2.1 22.4 [6.56] 14.4 [4.22] 2.2

23.0 [6.74] 14.1 [4.13] 2.1 22.0 [6.45] 13.8 [4.04] 2.2

22.4 [6.56] 13.2 [3.87] 2.1 21.4 [6.27] 12.8 [3.75] 2.2

22.4 [6.56] 18.4 [5.39] 2.2 21.4 [6.27] 18.0 [5.28] 2.2

22.0 [6.45] 17.6 [5.16] 2.1 21.0 [6.15] 17.2 [5.04] 2.2

21.4 [6.27] 16.4 [4.81] 2.1 20.4 [5.98] 16.0 [4.69] 2.2

20.0 [5.86] 20.0 [5.86] 2.1 18.9 [5.54] 18.9 [5.54] 2.2

19.6 [5.74] 19.6 [5.74] 2.1 18.6 [5.45] 18.6 [5.45] 2.2

19.1 [5.60] 19.0 [5.57] 2.1 18.1 [5.30] 18.1 [5.30] 2.2

O U T D O O R D R Y B U L B T E M P E R A T U R E

GROSS SYSTEMS PERFORMANCE DATA—RSMJ-A030 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1000 [472] .12

850 [401] .09

1100 [519] .13

67°F [19.4°C] 1000 [472] .12

850 [401] .09

1100 [519] .13

63°F [17.2°C] 1000 [472] .12

850 [401] .09

Total BTUH [kW] 39.4 [11.55] 75 Sens BTUH [kW] 22.9 [6.71] [23.9] 1.3 Power

38.7 [11.34] 21.8 [6.39] 1.3

37.7 [11.05] 20.3 [5.95] 1.3

37.0 [10.84] 27.3 [8.00] 1.9

36.3 [10.64] 26.1 [7.65] 1.9

35.4 [10.37] 24.3 [7.12] 1.9

35.7 [10.46] 31.5 [9.23] 1.9

35.0 [10.26] 30.1 [8.82] 1.8

34.1 [9.99] 28.0 [8.21] 1.8

Total BTUH [kW] 38.2 [11.20] 80 Sens BTUH [kW] 22.3 [6.54] [26.7] 1.4 Power

37.5 [10.99] 21.3 [6.24] 1.4

36.5 [10.70] 19.8 [5.80] 1.4

35.7 [10.46] 26.7 [7.83] 2.1

35.1 [10.29] 25.6 [7.50] 2.0

34.2 [10.02] 23.8 [6.98] 2.0

34.4 [10.08] 30.9 [9.06] 2.0

33.8 [9.91] 29.5 [8.65] 2.0

32.9 [9.64] 27.5 [8.06] 1.9

Total BTUH [kW] 37.0 [10.84] 85 Sens BTUH [kW] 21.8 [6.39] [29.4] 1.5 Power

36.3 [10.64] 20.8 [6.10] 1.5

35.3 [10.35] 19.3 [5.66] 1.5

34.6 [10.14] 26.2 [7.68] 2.2

34.0 [9.96] 25.0 [7.33] 2.2

33.0 [9.67] 23.3 [6.83] 2.1

33.3 [9.76] 30.4 [8.91] 2.1

32.7 [9.58] 29.0 [8.50] 2.1

31.8 [9.32] 27.0 [7.91] 2.1

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

35.9 [10.52] 21.2 [6.21] 1.7

35.3 [10.35] 20.3 [5.95] 1.6

34.3 [10.05] 18.9 [5.54] 1.6

33.5 [9.82] 25.7 [7.53] 2.3

32.9 [9.64] 24.6 [7.21] 2.3

32.0 [9.38] 22.8 [6.68] 2.3

32.2 [9.44] 29.9 [8.76] 2.2

31.6 [9.26] 28.5 [8.35] 2.2

30.8 [9.03] 26.5 [7.77] 2.2

35.0 [10.26] 20.8 [6.10] 1.8

34.4 [10.08] 19.8 [5.80] 1.8

33.4 [9.79] 18.4 [5.39] 1.7

32.6 [9.55] 25.2 [7.39] 2.4

32.0 [9.38] 24.1 [7.06] 2.4

31.1 [9.11] 22.4 [6.56] 2.4

31.2 [9.14] 29.4 [8.62] 2.3

30.7 [9.00] 28.1 [8.24] 2.3

29.8 [8.73] 26.1 [7.65] 2.3

34.2 [10.02] 20.3 [5.95] 1.9

33.5 [9.82] 19.4 [5.69] 1.9

32.6 [9.55] 18.1 [5.30] 1.9

31.7 [9.29] 24.8 [7.27] 2.5

31.2 [9.14] 23.7 [6.95] 2.5

30.3 [8.88] 22.0 [6.45] 2.5

30.4 [8.91] 29.0 [8.50] 2.5

29.9 [8.76] 27.7 [8.12] 2.4

29.1 [8.53] 25.7 [7.53] 2.4

Total BTUH [kW] 33.5 [9.82] 105 Sens BTUH [kW] 19.9 [5.83] [40.6] 2.0 Power

32.9 [9.64] 19.1 [5.60] 2.0

32.0 [9.38] 17.7 [5.19] 2.0

31.0 [9.09] 24.4 [7.15] 2.7

30.5 [8.94] 23.3 [6.83] 2.6

29.7 [8.70] 21.7 [6.36] 2.6

29.7 [8.70] 28.6 [8.38] 2.6

29.2 [8.56] 27.3 [8.00] 2.6

28.4 [8.32] 25.4 [7.44] 2.5

32.3 [9.47] 18.8 [5.51] 2.1 31.9 [9.35] 18.5 [5.42] 2.2

31.4 [9.20] 17.4 [5.10] 2.1 31.0 [9.09] 17.2 [5.04] 2.2

30.5 [8.94] 24.1 [7.06] 2.8 30.1 [8.82] 23.8 [6.98] 2.9

29.9 [8.76] 23.0 [6.74] 2.8 29.5 [8.65] 22.8 [6.68] 2.9

29.1 [8.53] 21.4 [6.27] 2.7 28.7 [8.41] 21.2 [6.21] 2.8

29.1 [8.53] 28.3 [8.29] 2.7 28.7 [8.41] 28.0 [8.21] 2.8

28.6 [8.38] 27.0 [7.91] 2.7 28.2 [8.26] 26.8 [7.85] 2.8

27.8 [8.15] 25.1 [7.36] 2.6 27.4 [8.03] 24.9 [7.30] 2.8

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1100 [519] .13

32.9 [9.64] 19.6 [5.74] 2.1 32.5 [9.52] 19.4 [5.69] 2.3

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

19

SYSTEMS PERFORMANCE—RSMJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSMJ-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1200 [566] .12

1020 [481] .09

1320 [623] .14

67°F [19.4°C] 1200 [566] .12

1020 [481] .09

1320 [623] .14

63°F [17.2°C] 1200 [566] .12

1020 [481] .09

Total BTUH [kW] 44.9 [13.16] 75 Sens BTUH [kW] 27.2 [7.97] [23.9] 2.4 Power

44.1 [12.92] 26.0 [7.62] 2.4

42.9 [12.57] 24.2 [7.09] 2.4

42.1 [12.34] 31.7 [9.29] 2.4

41.4 [12.13] 30.3 [8.88] 2.3

40.2 [11.78] 28.1 [8.24] 2.3

39.5 [11.58] 36.1 [10.58] 2.3

38.8 [11.37] 34.5 [10.11] 2.3

37.7 [11.05] 32.1 [9.41] 2.3

Total BTUH [kW] 44.0 [12.90] 80 Sens BTUH [kW] 26.8 [7.85] [26.7] 2.5 Power

43.3 [12.69] 25.6 [7.50] 2.5

42.1 [12.34] 23.8 [6.98] 2.5

41.3 [12.10] 31.3 [9.17] 2.5

40.5 [11.87] 29.9 [8.76] 2.5

39.4 [11.55] 27.8 [8.15] 2.4

38.6 [11.31] 35.7 [10.46] 2.5

37.9 [11.11] 34.1 [9.99] 2.4

36.9 [10.81] 31.7 [9.29] 2.4

Total BTUH [kW] 43.2 [12.66] 85 Sens BTUH [kW] 26.4 [7.74] [29.4] 2.7 Power

42.4 [12.43] 25.2 [7.39] 2.7

41.3 [12.10] 23.5 [6.89] 2.6

40.4 [11.84] 30.9 [9.06] 2.6

39.7 [11.63] 29.5 [8.65] 2.6

38.6 [11.31] 27.4 [8.03] 2.6

37.8 [11.08] 35.3 [10.35] 2.6

37.1 [10.87] 33.7 [9.88] 2.6

36.1 [10.58] 31.4 [9.20] 2.5

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

42.3 [12.40] 26.0 [7.62] 2.8

41.6 [12.19] 24.8 [7.27] 2.8

40.4 [11.84] 23.1 [6.77] 2.8

39.6 [11.61] 30.4 [8.91] 2.8

38.9 [11.40] 29.1 [8.53] 2.8

37.8 [11.08] 27.0 [7.91] 2.7

36.9 [10.81] 34.9 [10.23] 2.7

36.3 [10.64] 33.3 [9.76] 2.7

35.3 [10.35] 31.0 [9.09] 2.7

41.4 [12.13] 25.6 [7.50] 3.0

40.7 [11.93] 24.4 [7.15] 2.9

39.6 [11.61] 22.7 [6.65] 2.9

38.7 [11.34] 30.0 [8.79] 2.9

38.0 [11.14] 28.7 [8.41] 2.9

36.9 [10.81] 26.7 [7.83] 2.9

36.0 [10.55] 34.4 [10.08] 2.9

35.4 [10.37] 32.9 [9.64] 2.9

34.4 [10.08] 30.6 [8.97] 2.8

40.5 [11.87] 25.1 [7.36] 3.1

39.7 [11.63] 24.0 [7.03] 3.1

38.6 [11.31] 22.3 [6.54] 3.0

37.7 [11.05] 29.5 [8.65] 3.1

37.0 [10.84] 28.2 [8.26] 3.0

36.0 [10.55] 26.2 [7.68] 3.0

35.0 [10.26] 34.0 [9.96] 3.0

34.4 [10.08] 32.4 [9.50] 3.0

33.5 [9.82] 30.2 [8.85] 3.0

Total BTUH [kW] 39.4 [11.55] 105 Sens BTUH [kW] 24.6 [7.21] [40.6] 3.2 Power

38.7 [11.34] 23.5 [6.89] 3.2

37.6 [11.02] 21.8 [6.39] 3.2

36.6 [10.73] 29.0 [8.50] 3.2

35.9 [10.52] 27.7 [8.12] 3.2

35.0 [10.26] 25.8 [7.56] 3.1

34.0 [9.96] 33.4 [9.79] 3.2

33.4 [9.79] 32.0 [9.38] 3.1

32.4 [9.50] 29.7 [8.70] 3.1

37.5 [10.99] 22.9 [6.71] 3.4 36.1 [10.58] 22.3 [6.54] 3.5

36.5 [10.70] 21.3 [6.24] 3.3 35.2 [10.32] 20.8 [6.10] 3.5

35.4 [10.37] 28.4 [8.32] 3.3 34.0 [9.96] 27.8 [8.15] 3.5

34.8 [10.20] 27.2 [7.97] 3.3 33.4 [9.79] 26.6 [7.80] 3.5

33.8 [9.91] 25.3 [7.41] 3.3 32.5 [9.52] 24.7 [7.24] 3.4

32.8 [9.61] 32.8 [9.61] 3.3 31.4 [9.20] 31.4 [9.20] 3.4

32.2 [9.44] 31.4 [9.20] 3.3 30.8 [9.03] 30.8 [9.03] 3.4

31.3 [9.17] 29.2 [8.56] 3.2 30.0 [8.79] 28.6 [8.38] 3.4

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1320 [623] .14

38.2 [11.20] 24.0 [7.03] 3.4 36.8 [10.79] 23.4 [6.86] 3.5

GROSS SYSTEMS PERFORMANCE DATA—RSMJ-A042 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1400 [661] .12

1190 [562] .09

1540 [727] .14

67°F [19.4°C] 1400 [661] .12

1190 [562] .09

1540 [727] .14

63°F [17.2°C] 1400 [661] .12

1190 [562] .09

Total BTUH [kW] 50.3 [14.74] 75 Sens BTUH [kW] 30.4 [8.91] [23.9] 2.6 Power

49.4 [14.48] 29.0 [8.50] 2.6

48.1 [14.10] 27.0 [7.91] 2.5

47.0 [13.77] 36.0 [10.55] 2.6

46.1 [13.51] 34.4 [10.08] 2.5

44.9 [13.16] 32.0 [9.38] 2.5

44.3 [12.98] 41.3 [12.10] 2.5

43.5 [12.75] 39.4 [11.55] 2.5

42.3 [12.40] 36.7 [10.76] 2.5

Total BTUH [kW] 48.9 [14.33] 80 Sens BTUH [kW] 29.7 [8.70] [26.7] 2.7 Power

48.0 [14.07] 28.3 [8.29] 2.7

46.7 [13.69] 26.4 [7.74] 2.7

45.6 [13.36] 35.3 [10.35] 2.7

44.7 [13.10] 33.7 [9.88] 2.7

43.5 [12.75] 31.3 [9.17] 2.7

42.9 [12.57] 40.5 [11.87] 2.7

42.1 [12.34] 38.8 [11.37] 2.7

41.0 [12.02] 36.0 [10.55] 2.6

Total BTUH [kW] 47.7 [13.98] 85 Sens BTUH [kW] 29.1 [8.53] [29.4] 2.9 Power

46.9 [13.75] 27.8 [8.15] 2.9

45.6 [13.36] 25.9 [7.59] 2.8

44.4 [13.01] 34.7 [10.17] 2.9

43.6 [12.78] 33.2 [9.73] 2.8

42.4 [12.43] 30.8 [9.03] 2.8

41.7 [12.22] 40.1 [11.75] 2.8

41.0 [12.02] 38.2 [11.20] 2.8

39.8 [11.66] 35.6 [10.43] 2.8

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

46.7 [13.69] 28.7 [8.41] 3.0

45.9 [13.45] 27.4 [8.03] 3.0

44.6 [13.07] 25.5 [7.47] 3.0

43.3 [12.69] 34.3 [10.05] 3.0

42.6 [12.48] 32.8 [9.61] 3.0

41.4 [12.13] 30.5 [8.94] 3.0

40.7 [11.93] 39.7 [11.63] 3.0

39.9 [11.69] 37.8 [11.08] 3.0

38.9 [11.40] 35.2 [10.32] 2.9

45.7 [13.39] 28.4 [8.32] 3.2

44.9 [13.16] 27.1 [7.94] 3.2

43.7 [12.81] 25.2 [7.39] 3.1

42.4 [12.43] 34.0 [9.96] 3.2

41.6 [12.19] 32.4 [9.50] 3.2

40.5 [11.87] 30.2 [8.85] 3.1

39.7 [11.63] 39.2 [11.49] 3.1

39.0 [11.43] 37.5 [10.99] 3.1

37.9 [11.11] 34.9 [10.23] 3.1

44.8 [13.13] 28.1 [8.24] 3.3

44.0 [12.90] 26.8 [7.85] 3.3

42.8 [12.54] 24.9 [7.30] 3.3

41.5 [12.16] 33.6 [9.85] 3.3

40.7 [11.93] 32.1 [9.41] 3.3

39.6 [11.61] 29.9 [8.76] 3.3

38.8 [11.37] 38.8 [11.37] 3.3

38.1 [11.17] 37.2 [10.90] 3.3

37.0 [10.84] 34.6 [10.14] 3.2

Total BTUH [kW] 43.8 [12.84] 105 Sens BTUH [kW] 27.7 [8.12] [40.6] 3.5 Power

43.0 [12.60] 26.5 [7.77] 3.5

41.9 [12.28] 24.6 [7.21] 3.4

40.5 [11.87] 33.3 [9.76] 3.5

39.7 [11.63] 31.8 [9.32] 3.5

38.7 [11.34] 29.6 [8.67] 3.4

37.8 [11.08] 37.8 [11.08] 3.5

37.1 [10.87] 36.9 [10.81] 3.4

36.1 [10.58] 34.3 [10.05] 3.4

42.0 [12.31] 26.1 [7.65] 3.6 40.7 [11.93] 25.7 [7.53] 3.8

40.8 [11.96] 24.3 [7.12] 3.6 39.6 [11.61] 23.9 [7.00] 3.7

39.4 [11.55] 32.9 [9.64] 3.6 38.1 [11.17] 32.5 [9.52] 3.8

38.7 [11.34] 31.5 [9.23] 3.6 37.4 [10.96] 31.0 [9.09] 3.8

37.6 [11.02] 29.3 [8.59] 3.6 36.4 [10.67] 28.8 [8.44] 3.7

36.7 [10.76] 36.7 [10.76] 3.6 35.4 [10.37] 35.4 [10.37] 3.8

36.0 [10.55] 36.0 [10.55] 3.6 34.8 [10.20] 34.8 [10.20] 3.7

35.0 [10.26] 34.0 [9.96] 3.5 33.8 [9.91] 33.6 [9.85] 3.7

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1540 [727] .14

42.7 [12.51] 27.4 [8.03] 3.7 41.4 [12.13] 26.9 [7.88] 3.8

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

20

SYSTEMS PERFORMANCE—RSMJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSMJ-A048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1600 [755] .15

1360 [642] .12

1760 [831] .17

67°F [19.4°C] 1600 [755] .15

1360 [642] .12

1760 [831] .17

63°F [17.2°C] 1600 [755] .15

1360 [642] .12

Total BTUH [kW] 59.0 [17.29] 75 Sens BTUH [kW] 34.8 [10.20] [23.9] 3.0 Power

58.0 [17.00] 33.3 [9.76] 2.9

56.4 [16.53] 31.0 [9.09] 2.9

54.9 [16.09] 41.1 [12.05] 3.0

53.9 [15.80] 39.2 [11.49] 2.9

52.4 [15.36] 36.5 [10.70] 2.9

52.3 [15.33] 46.8 [13.72] 2.9

51.3 [15.03] 44.7 [13.10] 2.9

49.9 [14.62] 41.6 [12.19] 2.8

Total BTUH [kW] 57.5 [16.85] 80 Sens BTUH [kW] 34.0 [9.96] [26.7] 3.1 Power

56.4 [16.53] 32.5 [9.52] 3.1

54.9 [16.09] 30.2 [8.85] 3.1

53.3 [15.62] 40.2 [11.78] 3.1

52.4 [15.36] 38.4 [11.25] 3.1

50.9 [14.92] 35.7 [10.46] 3.1

50.7 [14.86] 46.0 [13.48] 3.1

49.8 [14.59] 43.9 [12.87] 3.0

48.5 [14.21] 40.8 [11.96] 3.0

Total BTUH [kW] 56.1 [16.44] 85 Sens BTUH [kW] 33.3 [9.76] [29.4] 3.3 Power

55.1 [16.15] 31.8 [9.32] 3.3

53.6 [15.71] 29.6 [8.67] 3.3

51.9 [15.21] 39.5 [11.58] 3.3

51.0 [14.95] 37.7 [11.05] 3.3

49.6 [14.54] 35.1 [10.29] 3.3

49.3 [14.45] 45.3 [13.28] 3.3

48.4 [14.18] 43.2 [12.66] 3.2

47.1 [13.80] 40.2 [11.78] 3.2

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

54.7 [16.03] 32.7 [9.58] 3.5

53.7 [15.74] 31.2 [9.14] 3.5

52.3 [15.33] 29.0 [8.50] 3.4

50.6 [14.83] 38.9 [11.40] 3.5

49.7 [14.57] 37.2 [10.90] 3.5

48.3 [14.16] 34.6 [10.14] 3.4

48.0 [14.07] 44.6 [13.07] 3.4

47.1 [13.80] 42.7 [12.51] 3.4

45.8 [13.42] 39.7 [11.63] 3.4

53.5 [15.68] 32.1 [9.41] 3.7

52.5 [15.39] 30.7 [9.00] 3.7

51.1 [14.98] 28.5 [8.35] 3.6

49.3 [14.45] 38.4 [11.25] 3.7

48.4 [14.18] 36.6 [10.73] 3.7

47.1 [13.80] 34.1 [9.99] 3.6

46.7 [13.69] 44.1 [12.92] 3.6

45.9 [13.45] 42.1 [12.34] 3.6

44.6 [13.07] 39.2 [11.49] 3.6

52.3 [15.33] 31.6 [9.26] 3.9

51.3 [15.03] 30.2 [8.85] 3.8

49.9 [14.62] 28.1 [8.24] 3.8

48.1 [14.10] 37.8 [11.08] 3.9

47.3 [13.86] 36.1 [10.58] 3.8

46.0 [13.48] 33.6 [9.85] 3.8

45.5 [13.33] 43.6 [12.78] 3.8

44.7 [13.10] 41.6 [12.19] 3.8

43.5 [12.75] 38.7 [11.34] 3.7

Total BTUH [kW] 51.1 [14.98] 105 Sens BTUH [kW] 31.1 [9.11] [40.6] 4.1 Power

50.2 [14.71] 29.7 [8.70] 4.0

48.8 [14.30] 27.6 [8.09] 4.0

46.9 [13.75] 37.3 [10.93] 4.1

46.1 [13.51] 35.6 [10.43] 4.0

44.9 [13.16] 33.1 [9.70] 4.0

44.4 [13.01] 43.0 [12.60] 4.0

43.6 [12.78] 41.1 [12.05] 4.0

42.4 [12.43] 38.2 [11.20] 3.9

49.0 [14.36] 29.1 [8.53] 4.2 47.9 [14.04] 28.5 [8.35] 4.4

47.7 [13.98] 27.1 [7.94] 4.2 46.6 [13.66] 26.5 [7.77] 4.3

45.8 [13.42] 36.7 [10.76] 4.2 44.6 [13.07] 36.0 [10.55] 4.4

45.0 [13.19] 35.1 [10.29] 4.2 43.8 [12.84] 34.4 [10.08] 4.4

43.7 [12.81] 32.6 [9.55] 4.2 42.6 [12.48] 32.0 [9.38] 4.3

43.2 [12.66] 42.5 [12.46] 4.2 42.0 [12.31] 41.8 [12.25] 4.4

42.4 [12.43] 40.6 [11.90] 4.1 41.3 [12.10] 39.9 [11.69] 4.3

41.3 [12.10] 37.7 [11.05] 4.1 40.1 [11.75] 37.1 [10.87] 4.3

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1760 [831] .17

49.9 [14.62] 30.5 [8.94] 4.2 48.8 [14.30] 29.8 [8.73] 4.4

GROSS SYSTEMS PERFORMANCE DATA—RSMJ-A060 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1900 [897] .14

1620 [765] .12

2090 [986] .16

67°F [19.4°C] 1900 [897] .14

1620 [765] .12

2090 [986] .16

63°F [17.2°C] 1900 [897] .14

1620 [765] .12

70.7 [20.72] 40.8 [11.96] 3.9

68.8 [20.16] 37.9 [11.11] 3.8

67.8 [19.87] 50.1 [14.68] 3.9

66.6 [19.52] 47.8 [14.01] 3.8

64.8 [18.99] 44.5 [13.04] 3.8

64.1 [18.79] 57.6 [16.88] 3.8

62.9 [18.43] 55.0 [16.12] 3.8

61.2 [17.94] 51.1 [14.98] 3.7

Total BTUH [kW] 70.6 [20.69] 69.3 [20.31] 80 Sens BTUH [kW] 42.2 [12.37] 40.4 [11.84] [26.7] 4.1 4.1 Power

67.5 [19.78] 37.5 [10.99] 4.1

66.4 [19.46] 49.6 [14.54] 4.1

65.2 [19.11] 47.4 [13.89] 4.0

63.4 [18.58] 44.1 [12.92] 4.0

62.7 [18.38] 57.1 [16.73] 4.0

61.5 [18.02] 54.6 [16.00] 4.0

59.9 [17.55] 50.8 [14.89] 3.9

Total BTUH [kW] 69.3 [20.31] 85 Sens BTUH [kW] 41.6 [12.19] [29.4] 4.4 Power

68.0 [19.93] 39.8 [11.66] 4.3

66.2 [19.40] 37.0 [10.84] 4.3

65.1 [19.08] 49.0 [14.36] 4.3

63.9 [18.73] 46.8 [13.72] 4.3

62.1 [18.20] 43.5 [12.75] 4.2

61.3 [17.97] 56.5 [16.56] 4.3

60.2 [17.64] 54.0 [15.83] 4.2

58.6 [17.17] 50.2 [14.71] 4.2

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

67.9 [19.90] 40.8 [11.96] 4.6

66.7 [19.55] 39.0 [11.43] 4.6

64.9 [19.02] 36.3 [10.64] 4.5

63.7 [18.67] 48.2 [14.13] 4.5

62.6 [18.35] 46.0 [13.48] 4.5

60.9 [17.85] 42.8 [12.54] 4.4

60.0 [17.58] 55.7 [16.32] 4.5

58.9 [17.26] 53.2 [15.59] 4.4

57.3 [16.79] 49.5 [14.51] 4.4

66.5 [19.49] 40.0 [11.72] 4.8

65.4 [19.17] 38.2 [11.20] 4.8

63.6 [18.64] 35.5 [10.40] 4.7

62.3 [18.26] 47.3 [13.86] 4.8

61.2 [17.94] 45.2 [13.25] 4.7

59.6 [17.47] 42.1 [12.34] 4.7

58.6 [17.17] 54.8 [16.06] 4.7

57.6 [16.88] 52.4 [15.36] 4.7

56.0 [16.41] 48.7 [14.27] 4.6

65.1 [19.08] 39.1 [11.46] 5.0

64.0 [18.76] 37.4 [10.96] 5.0

62.2 [18.23] 34.7 [10.17] 4.9

60.9 [17.85] 46.5 [13.63] 5.0

59.8 [17.53] 44.4 [13.01] 4.9

58.2 [17.06] 41.3 [12.10] 4.9

57.2 [16.76] 54.0 [15.83] 4.9

56.2 [16.47] 51.6 [15.12] 4.9

54.6 [16.00] 48.0 [14.07] 4.8

Total BTUH [kW] 63.6 [18.64] 105 Sens BTUH [kW] 38.3 [11.22] [40.6] 5.3 Power

62.5 [18.32] 36.6 [10.73] 5.2

60.8 [17.82] 34.0 [9.96] 5.2

59.4 [17.41] 45.7 [13.39] 5.2

58.3 [17.09] 43.6 [12.78] 5.2

56.7 [16.62] 40.6 [11.90] 5.1

55.6 [16.29] 53.2 [15.59] 5.2

54.7 [16.03] 50.8 [14.89] 5.1

53.2 [15.59] 47.3 [13.86] 5.0

60.8 [17.82] 36.0 [10.55] 5.4 59.0 [17.29] 35.5 [10.40] 5.7

59.2 [17.35] 33.4 [9.79] 5.4 57.4 [16.82] 33.0 [9.67] 5.6

57.7 [16.91] 45.0 [13.19] 5.4 55.9 [16.38] 44.6 [13.07] 5.7

56.7 [16.62] 43.0 [12.60] 5.4 54.9 [16.09] 42.6 [12.48] 5.6

55.2 [16.18] 40.0 [11.72] 5.3 53.4 [15.65] 39.6 [11.61] 5.5

54.0 [15.83] 52.5 [15.39] 5.4 52.2 [15.30] 52.1 [15.27] 5.6

53.0 [15.53] 50.2 [14.71] 5.3 51.2 [15.01] 49.7 [14.57] 5.6

51.6 [15.12] 46.7 [13.69] 5.3 49.8 [14.59] 46.3 [13.57] 5.5

2090 [986] .16

Total BTUH [kW] 72.0 [21.10] 75 Sens BTUH [kW] 42.7 [12.51] [23.9] 3.9 Power

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

61.9 [18.14] 37.6 [11.02] 5.5 60.1 [17.61] 37.2 [10.90] 5.7

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

21

SYSTEMS PERFORMANCE—RSNJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNJ-A024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

880 [415] .13

71°F [21.7°C] 800 [378] .11

680 [321] .08

880 [415] .13

67°F [19.4°C] 800 [378] .11

680 [321] .08

880 [415] .13

63°F [17.2°C] 800 [378] .11

680 [321] .08

Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power

28.9 [8.47] 17.7 [5.19] 1.5

28.4 [8.32] 16.9 [4.95] 1.5

27.6 [8.09] 15.7 [4.60] 1.5

27.9 [8.18] 21.3 [6.24] 1.5

27.4 [8.03] 20.3 [5.95] 1.5

26.7 [7.83] 18.9 [5.54] 1.5

25.5 [7.47] 24.3 [7.12] 1.5

25.0 [7.33] 23.2 [6.80] 1.5

24.3 [7.12] 21.6 [6.33] 1.5

Total BTUH [kW] 80 Sens BTUH [kW] [26.7] Power

28.7 [8.41] 17.5 [5.13] 1.6

28.2 [8.26] 16.7 [4.89] 1.6

27.4 [8.03] 15.6 [4.57] 1.6

27.7 [8.12] 21.1 [6.18] 1.6

27.2 [7.97] 20.2 [5.92] 1.6

26.5 [7.77] 18.8 [5.51] 1.6

25.3 [7.41] 24.1 [7.06] 1.6

24.8 [7.27] 23.0 [6.74] 1.6

24.1 [7.06] 21.4 [6.27] 1.5

Total BTUH [kW] 85 Sens BTUH [kW] [29.4] Power

28.3 [8.29] 17.3 [5.07] 1.7

27.8 [8.15] 16.5 [4.84] 1.7

27.0 [7.91] 15.4 [4.51] 1.6

27.3 [8.00] 20.9 [6.13] 1.7

26.8 [7.85] 20.0 [5.86] 1.7

26.1 [7.65] 18.6 [5.45] 1.6

24.8 [7.27] 23.9 [7.00] 1.7

24.4 [7.15] 22.8 [6.68] 1.6

23.7 [6.95] 21.2 [6.21] 1.6

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

27.7 [8.12] 17.0 [4.98] 1.8

27.2 [7.97] 16.2 [4.75] 1.7

26.5 [7.77] 15.1 [4.43] 1.7

26.7 [7.83] 20.6 [6.04] 1.8

26.2 [7.68] 19.7 [5.77] 1.7

25.5 [7.47] 18.3 [5.36] 1.7

24.3 [7.12] 23.6 [6.92] 1.7

23.8 [6.98] 22.5 [6.59] 1.7

23.2 [6.80] 20.9 [6.13] 1.7

27.0 [7.91] 16.6 [4.86] 1.8

26.5 [7.77] 15.9 [4.66] 1.8

25.8 [7.56] 14.8 [4.34] 1.8

26.0 [7.62] 20.2 [5.92] 1.8

25.5 [7.47] 19.3 [5.66] 1.8

24.8 [7.27] 18.0 [5.28] 1.8

23.5 [6.89] 23.2 [6.80] 1.8

23.1 [6.77] 22.2 [6.51] 1.8

22.5 [6.59] 20.6 [6.04] 1.8

26.1 [7.65] 16.2 [4.75] 1.9

25.7 [7.53] 15.5 [4.54] 1.9

25.0 [7.33] 14.4 [4.22] 1.9

25.1 [7.36] 19.8 [5.80] 1.9

24.7 [7.24] 18.9 [5.54] 1.9

24.0 [7.03] 17.6 [5.16] 1.9

22.7 [6.65] 22.7 [6.65] 1.9

22.3 [6.54] 21.8 [6.39] 1.9

21.7 [6.36] 20.3 [5.95] 1.9

Total BTUH [kW] 105 Sens BTUH [kW] [40.6] Power

25.2 [7.39] 15.8 [4.63] 2.0

24.8 [7.27] 15.1 [4.43] 2.0

24.1 [7.06] 14.1 [4.13] 2.0

24.2 [7.09] 19.4 [5.69] 2.0

23.8 [6.98] 18.6 [5.45] 2.0

23.1 [6.77] 17.3 [5.07] 2.0

21.8 [6.39] 21.8 [6.39] 2.0

21.4 [6.27] 21.4 [6.27] 2.0

20.8 [6.10] 19.9 [5.83] 1.9

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

24.2 [7.09] 15.4 [4.51] 2.1 23.2 [6.80] 15.1 [4.43] 2.2

23.8 [6.98] 14.7 [4.31] 2.1 22.8 [6.68] 14.4 [4.22] 2.1

23.1 [6.77] 13.7 [4.02] 2.0 22.2 [6.51] 13.4 [3.93] 2.1

23.2 [6.80] 19.0 [5.57] 2.1 22.2 [6.51] 18.7 [5.48] 2.2

22.8 [6.68] 18.2 [5.33] 2.1 21.8 [6.39] 17.8 [5.22] 2.2

22.2 [6.51] 16.9 [4.95] 2.0 21.2 [6.21] 16.6 [4.86] 2.1

20.8 [6.10] 20.8 [6.10] 2.1 19.8 [5.80] 19.8 [5.80] 2.2

20.4 [5.98] 20.4 [5.98] 2.1 19.4 [5.69] 19.4 [5.69] 2.1

19.8 [5.80] 19.6 [5.74] 2.0 18.9 [5.54] 18.9 [5.54] 2.1

O U T D O O R D R Y B U L B T E M P E R A T U R E

GROSS SYSTEMS PERFORMANCE DATA—RSNJ-A030 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1000 [472] .12

850 [401] .09

1100 [519] .14

67°F [19.4°C] 1000 [472] .12

850 [401] .09

1100 [519] .14

63°F [17.2°C] 1000 [472] .12

850 [401] .09

Total BTUH [kW] 36.2 [10.61] 75 Sens BTUH [kW] 22.4 [6.56] [23.9] 1.8 Power

35.5 [10.40] 21.4 [6.27] 1.8

34.6 [10.14] 19.9 [5.83] 1.8

34.3 [10.05] 26.6 [7.80] 1.8

33.7 [9.88] 25.4 [7.44] 1.8

32.8 [9.61] 23.6 [6.92] 1.8

32.2 [9.44] 30.8 [9.03] 1.8

31.7 [9.29] 29.4 [8.62] 1.8

30.8 [9.03] 27.3 [8.00] 1.8

Total BTUH [kW] 35.2 [10.32] 80 Sens BTUH [kW] 21.8 [6.39] [26.7] 1.9 Power

34.6 [10.14] 20.8 [6.10] 1.9

33.7 [9.88] 19.3 [5.66] 1.9

33.4 [9.79] 25.9 [7.59] 2.0

32.8 [9.61] 24.8 [7.27] 1.9

31.9 [9.35] 23.0 [6.74] 1.9

31.3 [9.17] 30.1 [8.82] 1.9

30.7 [9.00] 28.8 [8.44] 1.9

29.9 [8.76] 26.7 [7.83] 1.9

Total BTUH [kW] 34.4 [10.08] 85 Sens BTUH [kW] 21.2 [6.21] [29.4] 2.1 Power

33.8 [9.91] 20.3 [5.95] 2.0

32.8 [9.61] 18.8 [5.51] 2.0

32.5 [9.52] 25.4 [7.44] 2.1

31.9 [9.35] 24.2 [7.09] 2.0

31.1 [9.11] 22.5 [6.59] 2.0

30.4 [8.91] 29.6 [8.67] 2.0

29.9 [8.76] 28.2 [8.26] 2.0

29.1 [8.53] 26.3 [7.71] 2.0

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

33.5 [9.82] 20.7 [6.07] 2.2

32.9 [9.64] 19.8 [5.80] 2.1

32.0 [9.38] 18.4 [5.39] 2.1

31.7 [9.29] 24.9 [7.30] 2.2

31.1 [9.11] 23.8 [6.98] 2.2

30.3 [8.88] 22.1 [6.48] 2.1

29.6 [8.67] 29.1 [8.53] 2.2

29.1 [8.53] 27.8 [8.15] 2.1

28.3 [8.29] 25.8 [7.56] 2.1

32.7 [9.58] 20.3 [5.95] 2.3

32.1 [9.41] 19.4 [5.69] 2.3

31.2 [9.14] 18.1 [5.30] 2.2

30.9 [9.06] 24.5 [7.18] 2.3

30.3 [8.88] 23.4 [6.86] 2.3

29.5 [8.65] 21.8 [6.39] 2.2

28.8 [8.44] 28.6 [8.38] 2.3

28.2 [8.26] 27.4 [8.03] 2.2

27.5 [8.06] 25.5 [7.47] 2.2

31.8 [9.32] 20.0 [5.86] 2.4

31.3 [9.17] 19.1 [5.60] 2.4

30.4 [8.91] 17.7 [5.19] 2.3

30.0 [8.79] 24.1 [7.06] 2.4

29.5 [8.65] 23.1 [6.77] 2.4

28.7 [8.41] 21.4 [6.27] 2.3

27.9 [8.18] 27.9 [8.18] 2.4

27.4 [8.03] 27.0 [7.91] 2.4

26.6 [7.80] 25.1 [7.36] 2.3

Total BTUH [kW] 30.9 [9.06] 105 Sens BTUH [kW] 19.6 [5.74] [40.6] 2.5 Power

30.3 [8.88] 18.7 [5.48] 2.5

29.5 [8.65] 17.4 [5.10] 2.4

29.1 [8.53] 23.8 [6.98] 2.5

28.5 [8.35] 22.7 [6.65] 2.5

27.8 [8.15] 21.1 [6.18] 2.5

27.0 [7.91] 27.0 [7.91] 2.5

26.5 [7.77] 26.5 [7.77] 2.5

25.7 [7.53] 24.8 [7.27] 2.4

29.3 [8.59] 18.4 [5.39] 2.6 28.1 [8.24] 18.0 [5.28] 2.7

28.5 [8.35] 17.1 [5.01] 2.6 27.4 [8.03] 16.7 [4.89] 2.7

28.0 [8.21] 23.4 [6.86] 2.6 26.8 [7.85] 23.0 [6.74] 2.7

27.5 [8.06] 22.3 [6.54] 2.6 26.3 [7.71] 21.9 [6.42] 2.7

26.8 [7.85] 20.8 [6.10] 2.6 25.6 [7.50] 20.4 [5.98] 2.7

25.9 [7.59] 25.9 [7.59] 2.6 24.7 [7.24] 24.7 [7.24] 2.7

25.4 [7.44] 25.4 [7.44] 2.6 24.3 [7.12] 24.3 [7.12] 2.7

24.7 [7.24] 24.5 [7.18] 2.5 23.6 [6.92] 23.6 [6.92] 2.7

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1100 [519] .14

29.8 [8.73] 19.2 [5.63] 2.6 28.7 [8.41] 18.8 [5.51] 2.7

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

22

SYSTEMS PERFORMANCE—RSNJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNJ-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1200 [566] .08

1020 [481] .04

1320 [623] .01

67°F [19.4°C] 1200 [566] .08

1020 [481] .04

1320 [623] .01

63°F [17.2°C] 1200 [566] .08

1020 [481] .04

Total BTUH [kW] 42.9 [12.57] 75 Sens BTUH [kW] 26.6 [7.80] [23.9] 2.2 Power

42.1 [12.34] 25.4 [7.44] 2.1

41.0 [12.02] 23.6 [6.92] 2.1

40.2 [11.78] 31.7 [9.29] 2.1

39.5 [11.58] 30.3 [8.88] 2.1

38.4 [11.25] 28.1 [8.24] 2.1

38.2 [11.20] 35.9 [10.52] 2.1

37.5 [10.99] 34.3 [10.05] 2.1

36.5 [10.70] 31.9 [9.35] 2.1

Total BTUH [kW] 42.0 [12.31] 80 Sens BTUH [kW] 26.1 [7.65] [26.7] 2.3 Power

41.2 [12.07] 24.9 [7.30] 2.3

40.1 [11.75] 23.2 [6.80] 2.2

39.2 [11.49] 31.2 [9.14] 2.3

38.5 [11.28] 29.8 [8.73] 2.2

37.5 [10.99] 27.7 [8.12] 2.2

37.2 [10.90] 35.4 [10.37] 2.3

36.6 [10.73] 33.9 [9.94] 2.2

35.6 [10.43] 31.5 [9.23] 2.2

Total BTUH [kW] 41.1 [12.05] 85 Sens BTUH [kW] 25.7 [7.53] [29.4] 2.4 Power

40.3 [11.81] 24.5 [7.18] 2.4

39.2 [11.49] 22.8 [6.68] 2.3

38.3 [11.22] 30.8 [9.03] 2.4

37.6 [11.02] 29.4 [8.62] 2.4

36.6 [10.73] 27.4 [8.03] 2.3

36.3 [10.64] 35.1 [10.29] 2.4

35.7 [10.46] 33.5 [9.82] 2.4

34.7 [10.17] 31.1 [9.11] 2.3

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

40.2 [11.78] 25.3 [7.41] 2.5

39.5 [11.58] 24.2 [7.09] 2.5

38.4 [11.25] 22.5 [6.59] 2.5

37.5 [10.99] 30.4 [8.91] 2.5

36.8 [10.79] 29.0 [8.50] 2.5

35.8 [10.49] 27.0 [7.91] 2.4

35.5 [10.40] 34.7 [10.17] 2.5

34.8 [10.20] 33.1 [9.70] 2.5

33.9 [9.94] 30.8 [9.03] 2.5

39.4 [11.55] 24.9 [7.30] 2.6

38.7 [11.34] 23.8 [6.98] 2.6

37.6 [11.02] 22.1 [6.48] 2.6

36.6 [10.73] 30.0 [8.79] 2.6

36.0 [10.55] 28.7 [8.41] 2.6

35.0 [10.26] 26.7 [7.83] 2.6

34.6 [10.14] 34.2 [10.02] 2.6

34.0 [9.96] 32.7 [9.58] 2.6

33.1 [9.70] 30.4 [8.91] 2.6

38.5 [11.28] 24.5 [7.18] 2.8

37.8 [11.08] 23.4 [6.86] 2.7

36.8 [10.79] 21.8 [6.39] 2.7

35.8 [10.49] 29.6 [8.67] 2.7

35.1 [10.29] 28.3 [8.29] 2.7

34.2 [10.02] 26.3 [7.71] 2.7

33.8 [9.91] 33.8 [9.91] 2.7

33.2 [9.73] 32.3 [9.47] 2.7

32.3 [9.47] 30.1 [8.82] 2.7

Total BTUH [kW] 37.6 [11.02] 105 Sens BTUH [kW] 24.0 [7.03] [40.6] 2.9 Power

36.9 [10.81] 23.0 [6.74] 2.9

35.9 [10.52] 21.4 [6.27] 2.8

34.8 [10.20] 29.2 [8.56] 2.9

34.2 [10.02] 27.9 [8.18] 2.8

33.3 [9.76] 25.9 [7.59] 2.8

32.8 [9.61] 32.8 [9.61] 2.9

32.3 [9.47] 31.9 [9.35] 2.8

31.4 [9.20] 29.7 [8.70] 2.8

35.9 [10.52] 22.5 [6.59] 3.0 34.9 [10.23] 22.0 [6.45] 3.1

35.0 [10.26] 20.9 [6.13] 2.9 33.9 [9.94] 20.4 [5.98] 3.1

33.8 [9.91] 28.7 [8.41] 3.0 32.8 [9.61] 28.1 [8.24] 3.1

33.2 [9.73] 27.4 [8.03] 3.0 32.2 [9.44] 26.8 [7.85] 3.1

32.3 [9.47] 25.5 [7.47] 2.9 31.3 [9.17] 25.0 [7.33] 3.0

31.9 [9.35] 31.9 [9.35] 3.0 30.8 [9.03] 30.8 [9.03] 3.1

31.3 [9.17] 31.3 [9.17] 3.0 30.2 [8.85] 30.2 [8.85] 3.1

30.4 [8.91] 29.2 [8.56] 2.9 29.4 [8.62] 28.7 [8.41] 3.0

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1320 [623] .01

36.6 [10.73] 23.6 [6.92] 3.0 35.5 [10.40] 23.0 [6.74] 3.1

GROSS SYSTEMS PERFORMANCE DATA—RSNJ-A042 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1400 [661] .11

1190 [562] .08

1540 [727] .13

67°F [19.4°C] 1400 [661] .11

1190 [562] .08

1540 [727] .13

63°F [17.2°C] 1400 [661] .11

1190 [562] .08

Total BTUH [kW] 51.2 [15.01] 75 Sens BTUH [kW] 30.0 [8.79] [23.9] 2.6 Power

50.3 [14.74] 28.6 [8.38] 2.6

48.9 [14.33] 26.6 [7.80] 2.5

47.6 [13.95] 36.2 [10.61] 2.6

46.7 [13.69] 34.5 [10.11] 2.5

45.5 [13.33] 32.1 [9.41] 2.5

44.8 [13.13] 41.1 [12.05] 2.5

44.0 [12.90] 39.3 [11.52] 2.5

42.8 [12.54] 36.5 [10.70] 2.5

Total BTUH [kW] 49.6 [14.54] 80 Sens BTUH [kW] 29.6 [8.67] [26.7] 2.7 Power

48.7 [14.27] 28.3 [8.29] 2.7

47.4 [13.89] 26.3 [7.71] 2.7

46.0 [13.48] 35.8 [10.49] 2.7

45.2 [13.25] 34.2 [10.02] 2.7

43.9 [12.87] 31.8 [9.32] 2.7

43.2 [12.66] 40.7 [11.93] 2.7

42.4 [12.43] 38.9 [11.40] 2.7

41.3 [12.10] 36.2 [10.61] 2.6

Total BTUH [kW] 48.4 [14.18] 85 Sens BTUH [kW] 29.1 [8.53] [29.4] 2.9 Power

47.5 [13.92] 27.8 [8.15] 2.9

46.2 [13.54] 25.9 [7.59] 2.8

44.8 [13.13] 35.3 [10.35] 2.9

44.0 [12.90] 33.7 [9.88] 2.8

42.8 [12.54] 31.4 [9.20] 2.8

42.0 [12.31] 40.3 [11.81] 2.8

41.2 [12.07] 38.5 [11.28] 2.8

40.1 [11.75] 35.8 [10.49] 2.8

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

47.4 [13.89] 28.6 [8.38] 3.0

46.5 [13.63] 27.4 [8.03] 3.0

45.3 [13.28] 25.5 [7.47] 3.0

43.8 [12.84] 34.8 [10.20] 3.0

43.0 [12.60] 33.3 [9.76] 3.0

41.8 [12.25] 30.9 [9.06] 3.0

41.0 [12.02] 39.8 [11.66] 3.0

40.2 [11.78] 38.0 [11.14] 3.0

39.1 [11.46] 35.4 [10.37] 2.9

46.5 [13.63] 28.1 [8.24] 3.2

45.7 [13.39] 26.8 [7.85] 3.2

44.5 [13.04] 25.0 [7.33] 3.1

42.9 [12.57] 34.3 [10.05] 3.2

42.1 [12.34] 32.7 [9.58] 3.1

41.0 [12.02] 30.4 [8.91] 3.1

40.1 [11.75] 39.2 [11.49] 3.2

39.4 [11.55] 37.5 [10.99] 3.1

38.3 [11.22] 34.9 [10.23] 3.1

45.7 [13.39] 27.5 [8.06] 3.4

44.9 [13.16] 26.3 [7.71] 3.3

43.6 [12.78] 24.5 [7.18] 3.3

42.1 [12.34] 33.7 [9.88] 3.3

41.3 [12.10] 32.2 [9.44] 3.3

40.2 [11.78] 29.9 [8.76] 3.3

39.3 [11.52] 38.7 [11.34] 3.3

38.6 [11.31] 36.9 [10.81] 3.3

37.5 [10.99] 34.4 [10.08] 3.2

Total BTUH [kW] 44.7 [13.10] 105 Sens BTUH [kW] 26.9 [7.88] [40.6] 3.5 Power

43.9 [12.87] 25.7 [7.53] 3.5

42.7 [12.51] 23.9 [7.00] 3.4

41.1 [12.05] 33.1 [9.70] 3.5

40.4 [11.84] 31.6 [9.26] 3.5

39.3 [11.52] 29.4 [8.62] 3.4

38.3 [11.22] 38.1 [11.17] 3.5

37.6 [11.02] 36.4 [10.67] 3.4

36.6 [10.73] 33.8 [9.91] 3.4

42.8 [12.54] 25.2 [7.39] 3.6 41.3 [12.10] 24.6 [7.21] 3.8

41.6 [12.19] 23.4 [6.86] 3.6 40.2 [11.78] 22.9 [6.71] 3.7

40.0 [11.72] 32.5 [9.52] 3.6 38.5 [11.28] 31.9 [9.35] 3.8

39.2 [11.49] 31.1 [9.11] 3.6 37.8 [11.08] 30.5 [8.94] 3.8

38.2 [11.20] 28.9 [8.47] 3.6 36.7 [10.76] 28.3 [8.29] 3.7

37.1 [10.87] 37.1 [10.87] 3.6 35.7 [10.46] 35.7 [10.46] 3.8

36.5 [10.70] 35.8 [10.49] 3.6 35.0 [10.26] 35.0 [10.26] 3.7

35.5 [10.40] 33.3 [9.76] 3.5 34.1 [9.99] 32.8 [9.61] 3.7

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

1540 [727] .13

43.6 [12.78] 26.3 [7.71] 3.7 42.1 [12.34] 25.7 [7.53] 3.8

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

23

SYSTEMS PERFORMANCE—RSNJ- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNJ-A048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1600 [755] .10

1360 [642] .06

1760 [831] .12

67°F [19.4°C] 1600 [755] .10

1360 [642] .06

1760 [831] .12

63°F [17.2°C] 1600 [755] .10

1360 [642] .06

Total BTUH [kW] 55.9 [16.38] 75 Sens BTUH [kW] 34.4 [10.08] [23.9] 2.9 Power

54.9 [16.09] 32.9 [9.64] 2.8

53.4 [15.65] 30.6 [8.97] 2.8

52.7 [15.44] 41.5 [12.16] 2.9

51.7 [15.15] 39.6 [11.61] 2.8

50.3 [14.74] 36.8 [10.79] 2.8

49.8 [14.59] 46.1 [13.51] 2.8

48.9 [14.33] 44.0 [12.90] 2.8

47.6 [13.95] 41.0 [12.02] 2.8

Total BTUH [kW] 55.3 [16.21] 80 Sens BTUH [kW] 33.8 [9.91] [26.7] 3.0 Power

54.3 [15.91] 32.3 [9.47] 3.0

52.8 [15.47] 30.1 [8.82] 3.0

52.1 [15.27] 40.9 [11.99] 3.0

51.1 [14.98] 39.1 [11.46] 3.0

49.7 [14.57] 36.3 [10.64] 3.0

49.2 [14.42] 45.5 [13.33] 3.0

48.3 [14.16] 43.5 [12.75] 3.0

47.0 [13.77] 40.5 [11.87] 2.9

Total BTUH [kW] 54.4 [15.94] 85 Sens BTUH [kW] 33.4 [9.79] [29.4] 3.2 Power

53.4 [15.65] 31.9 [9.35] 3.1

52.0 [15.24] 29.6 [8.67] 3.1

51.2 [15.01] 40.4 [11.84] 3.2

50.3 [14.74] 38.6 [11.31] 3.1

48.9 [14.33] 35.9 [10.52] 3.1

48.3 [14.16] 45.0 [13.19] 3.1

47.5 [13.92] 43.0 [12.60] 3.1

46.2 [13.54] 40.0 [11.72] 3.1

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

53.3 [15.62] 32.9 [9.64] 3.3

52.3 [15.33] 31.4 [9.20] 3.3

50.9 [14.92] 29.2 [8.56] 3.3

50.1 [14.68] 40.0 [11.72] 3.3

49.2 [14.42] 38.2 [11.20] 3.3

47.8 [14.01] 35.5 [10.40] 3.3

47.2 [13.83] 44.6 [13.07] 3.3

46.4 [13.60] 42.6 [12.48] 3.3

45.1 [13.22] 39.6 [11.61] 3.2

52.0 [15.24] 32.4 [9.50] 3.5

51.1 [14.98] 31.0 [9.09] 3.5

49.7 [14.57] 28.8 [8.44] 3.4

48.8 [14.30] 39.5 [11.58] 3.5

47.9 [14.04] 37.7 [11.05] 3.4

46.6 [13.66] 35.1 [10.29] 3.4

46.0 [13.48] 44.1 [12.92] 3.4

45.2 [13.25] 42.2 [12.37] 3.4

43.9 [12.87] 39.2 [11.49] 3.4

50.7 [14.86] 31.9 [9.35] 3.6

49.8 [14.59] 30.5 [8.94] 3.6

48.4 [14.18] 28.4 [8.32] 3.6

47.4 [13.89] 39.0 [11.43] 3.6

46.6 [13.66] 37.2 [10.90] 3.6

45.3 [13.28] 34.6 [10.14] 3.6

44.6 [13.07] 43.6 [12.78] 3.6

43.8 [12.84] 41.7 [12.22] 3.6

42.6 [12.48] 38.8 [11.37] 3.5

Total BTUH [kW] 49.2 [14.42] 105 Sens BTUH [kW] 31.3 [9.17] [40.6] 3.8 Power

48.3 [14.16] 29.9 [8.76] 3.8

47.0 [13.77] 27.8 [8.15] 3.7

46.0 [13.48] 38.3 [11.22] 3.8

45.2 [13.25] 36.6 [10.73] 3.8

43.9 [12.87] 34.1 [9.99] 3.7

43.1 [12.63] 43.0 [12.60] 3.8

42.4 [12.43] 41.1 [12.05] 3.7

41.2 [12.07] 38.2 [11.20] 3.7

46.9 [13.75] 29.1 [8.53] 3.9 45.5 [13.33] 28.1 [8.24] 4.1

45.6 [13.36] 27.1 [7.94] 3.9 44.3 [12.98] 26.2 [7.68] 4.0

44.5 [13.04] 37.5 [10.99] 3.9 43.1 [12.63] 36.5 [10.70] 4.1

43.7 [12.81] 35.9 [10.52] 3.9 42.3 [12.40] 34.9 [10.23] 4.1

42.5 [12.46] 33.4 [9.79] 3.9 41.2 [12.07] 32.4 [9.50] 4.0

41.7 [12.22] 41.7 [12.22] 3.9 40.3 [11.81] 40.3 [11.81] 4.1

40.9 [11.99] 40.3 [11.81] 3.9 39.6 [11.61] 39.3 [11.52] 4.0

39.8 [11.66] 37.5 [10.99] 3.8 38.5 [11.28] 36.6 [10.73] 4.0

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power

1760 [831] .12

47.8 [14.01] 30.5 [8.94] 4.0 46.3 [13.57] 29.5 [8.65] 4.1

GROSS SYSTEMS PERFORMANCE DATA—RSNJ-A060 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀

O U T D O O R D R Y B U L B T E M P E R A T U R E

71°F [21.7°C] 1900 [897] .03

1620 [765] 0

2090 [986] .05

67°F [19.4°C] 1900 [897] .03

1620 [765] 0

2090 [986] .05

63°F [17.2°C] 1900 [897] .03

1620 [765] 0

Total BTUH [kW] 73.8 [21.63] 75 Sens BTUH [kW] 44.8 [13.13] [23.9] 3.8 Power

72.5 [21.25] 42.8 [12.54] 3.8

70.5 [20.66] 39.8 [11.66] 3.7

70.1 [20.54] 53.8 [15.77] 3.8

68.9 [20.19] 51.4 [15.06] 3.8

67.0 [19.64] 47.8 [14.01] 3.7

64.3 [18.84] 60.4 [17.70] 3.7

63.2 [18.52] 57.7 [16.91] 3.7

61.5 [18.02] 53.6 [15.71] 3.7

Total BTUH [kW] 73.6 [21.57] 80 Sens BTUH [kW] 45.0 [13.19] [26.7] 4.0 Power

72.3 [21.19] 43.0 [12.60] 4.0

70.3 [20.60] 40.0 [11.72] 4.0

70.0 [20.51] 54.0 [15.83] 4.0

68.7 [20.13] 51.6 [15.12] 4.0

66.8 [19.58] 48.0 [14.07] 3.9

64.2 [18.82] 60.5 [17.73] 4.0

63.0 [18.46] 57.8 [16.94] 3.9

61.3 [17.97] 53.8 [15.77] 3.9

Total BTUH [kW] 72.6 [21.28] 85 Sens BTUH [kW] 44.6 [13.07] [29.4] 4.3 Power

71.3 [20.90] 42.6 [12.48] 4.2

69.3 [20.31] 39.6 [11.61] 4.2

68.9 [20.19] 53.6 [15.71] 4.2

67.7 [19.84] 51.2 [15.01] 4.2

65.8 [19.28] 47.6 [13.95] 4.1

63.1 [18.49] 60.2 [17.64] 4.2

62.0 [18.17] 57.4 [16.82] 4.1

60.3 [17.67] 53.4 [15.65] 4.1

Total BTUH [kW] 90 Sens BTUH [kW] [32.2] Power Total BTUH [kW] 95 Sens BTUH [kW] [35] Power Total BTUH [kW] 100 Sens BTUH [kW] [37.8] Power

70.9 [20.78] 43.7 [12.81] 4.5

69.6 [20.40] 41.8 [12.25] 4.4

67.7 [19.84] 38.9 [11.40] 4.4

67.2 [19.69] 52.7 [15.44] 4.4

66.0 [19.34] 50.4 [14.77] 4.4

64.2 [18.82] 46.8 [13.72] 4.3

61.4 [17.99] 59.4 [17.41] 4.4

60.3 [17.67] 56.6 [16.59] 4.4

58.7 [17.20] 52.7 [15.44] 4.3

68.7 [20.13] 42.6 [12.48] 4.7

67.5 [19.78] 40.7 [11.93] 4.7

65.7 [19.25] 37.9 [11.11] 4.6

65.1 [19.08] 51.6 [15.12] 4.7

63.9 [18.73] 49.3 [14.45] 4.6

62.2 [18.23] 45.8 [13.42] 4.6

59.3 [17.38] 58.1 [17.03] 4.6

58.2 [17.06] 55.6 [16.29] 4.6

56.6 [16.59] 51.7 [15.15] 4.5

66.3 [19.43] 41.4 [12.13] 4.9

65.1 [19.08] 39.5 [11.58] 4.9

63.4 [18.58] 36.8 [10.79] 4.8

62.7 [18.38] 50.4 [14.77] 4.9

61.6 [18.05] 48.1 [14.10] 4.8

59.9 [17.55] 44.8 [13.13] 4.8

56.9 [16.68] 56.9 [16.68] 4.8

55.9 [16.38] 54.4 [15.94] 4.8

54.3 [15.91] 50.6 [14.83] 4.7

Total BTUH [kW] 63.9 [18.73] 105 Sens BTUH [kW] 40.2 [11.78] [40.6] 5.1 Power

62.8 [18.40] 38.4 [11.25] 5.1

61.1 [17.91] 35.7 [10.46] 5.0

60.3 [17.67] 49.2 [14.42] 5.1

59.2 [17.35] 47.0 [13.77] 5.1

57.6 [16.88] 43.7 [12.81] 5.0

54.5 [15.97] 54.5 [15.97] 5.0

53.5 [15.68] 53.3 [15.62] 5.0

52.0 [15.24] 49.5 [14.51] 4.9

60.6 [17.76] 37.5 [10.99] 5.3 58.8 [17.23] 36.9 [10.81] 5.5

58.9 [17.26] 34.9 [10.23] 5.2 57.2 [16.76] 34.3 [10.05] 5.5

58.0 [17.00] 48.2 [14.13] 5.3 56.2 [16.47] 47.6 [13.95] 5.5

57.0 [16.71] 46.1 [13.51] 5.3 55.2 [16.18] 45.5 [13.33] 5.5

55.4 [16.24] 42.9 [12.57] 5.2 53.7 [15.74] 42.3 [12.40] 5.4

52.2 [15.30] 52.2 [15.30] 5.3 50.4 [14.77] 50.4 [14.77] 5.5

51.3 [15.03] 51.3 [15.03] 5.2 49.5 [14.51] 49.5 [14.51] 5.4

49.9 [14.62] 48.7 [14.27] 5.2 48.1 [14.10] 48.1 [14.10] 5.4

Total BTUH [kW] 110 Sens BTUH [kW] [43.3] °F Power [°C] Total BTUH [kW] 115 Sens BTUH [kW] [46.1] Power DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

2090 [986] .05

61.7 [18.08] 39.2 [11.49] 5.4 59.8 [17.53] 38.6 [11.31] 5.6

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)]. [ ] Designates Metric Conversions

24

25

Low

5.0 [17.6]

1750/2250

1400/1800

1225/1575

1050/1350

875/1125

700/900

Manufacturer Recommended Air-Flow Range (Min/Max) CFM

[ ] Designates Metric Conversions

Low

Low

3.0 [10.55]

4.0 [14.07]

Low

2.5 [8.79]

Low

Low

2.0 [7.03]

3.5 [12.31]

Motor Speed from Factory

Nominal Cooling Capacity Tons [kW]

11x9 3/4 HP [559] 2 Speed Motor

11x9 3/4 HP [559] 2 Speed Motor

11x9 1/2 HP [373] 2 Speed Motor

10x9 1/2 HP [373] 2 Speed Motor

10x9 1/3 HP [249] 2 Speed Motor

10x9 1/4 HP [186] 2 Speed Motor

Blower Size/ Motor HP [W] & # of Speeds

High

Low

High

Low

High

Low

High

Low

High

Low

High

Low

Motor Speed

725 758

477 1984 [936] 696 769 1601 [756]

Watts CFM RPM Watts CFM

905 1408

RPM Watts

2640 [1246]

CFM

1988 [938]

CFM 860

770 697

669

RPM Watts RPM

767

1996 [942]

CFM

Watts

699

558

1401

913

2619 [1236]

854

706

1975 [932]

1976 [933]

548

566

RPM Watts

620

1567 [740]

1945 [918]

471

552

602

1395 [658]

814

875

2024 [955]

410

662

1280 [604]

473

646

1301 [614]

331

570

1030 [486]

468

643

1223 [577]

273

533

811 [383]

0.2 [.05]

RPM

1452 [685]

837

CFM

843

RPM

2105 [993]

CFM Watts

415

1302 [615]

CFM 588

482

Watts RPM

592

RPM

Watts

1312 [619]

1032 [487]

CFM

CFM

479

336

575

RPM Watts

Watts

1230 [581]

CFM

533

278

Watts

RPM

450

827 [390]

RPM

CFM

0.1 [.02]

INDOOR AIRFLOW PERFORMANCE—230 VOLTS

1394

920

2586 [1220]

841

749

1950 [920]

754

730

1947 [919]

542

677

1527 [721]

740

763

1899 [896]

458

663

1343 [634]

799

902

1974 [932]

402

738

1253 [592]

466

712

1292 [610]

326

659

1014 [478]

455

703

1216 [574]

269

626

782 [369]

0.3 [.07]

1382

930

2542 [1200]

834

775

1912 [903]

745

780

1909 [901]

533

713

1480 [698]

725

799

1846 [871]

452

704

1292 [610]

774

927

1936 [914]

394

772

1217 [574]

454

768

1276 [602]

314

746

979 [462]

448

767

1211 [571]

254

742

740 [349]

0.4 [.10]

1356

949

2486 [1173]

824

805

1862 [879]

726

815

1863 [879]

526

752

1426 [673]

709

828

1785 [842]

443

746

1239 [585]

752

957

1893 [893]

386

831

1165 [550]

433

824

1246 [588]

303

795

923 [436]

431

819

1187 [560]

244

799

684 [323]

0.5 [.12]

1321

965

2419 [1142]

798

846

1799 [849]

719

842

1808 [853]

513

787

1366 [645]

689

869

1713 [808]

430

797

1180 [557]

729

980

1827 [862]

372

884

1091 [515]

421

883

1196 [564]

280

863

843 [398]

416

877

1125 [531]

227

894

614 [290]

0.6 [.15]

1292

979

2340 [1104]

780

879

1724 [814]

695

875

1744 [823]

501

829

1298 [613]

665

898

1632 [770]

418

836

1110 [524]

689

1009

1722 [813]

333

976

990 [467]

401

933

1117 [527]

271

934

735 [347]

357

976

1020 [481]

216

932

531 [251]

0.7 [.17]

External Static Pressure—Inches W.C. [kPa]

CFM [L/s] Air Delivery/RPM/Watts—230 Volts Side Discharge—Wet Coil 0.8 [.20]

1254

997

2249 [1061]

759

909

1636 [772]

676

908

1671 [789]

480

878

1224 [578]

643

925

1538 [726]

410

871

1025 [484]

649

1036

1560 [736]

325

995

855 [404]

349

1012

1003 [473]

227

1019

596 [281]

341

1001

874 [412]

198

985

435 [205]

1210

1013

2148 [1014]

721

953

1536 [725]

653

936

1590 [750]

466

908

1143 [539]

607

966

1432 [676]

388

920

922 [435]

595

1064

1323 [624]

305

1026

681 [321]

329

1035

845 [399]

210

1050

423 [200]

279

1072

696 [328]







0.9 [.22]

1168

1030

2034 [960]

690

991

1423 [672]

618

978

1500 [708]

446

947

1055 [498]

587

984

1312 [619]







509

1106

994 [469]

266

1086

461 [218]













259

1092

504 [238]







1.0 [.25]

AIRFLOW PERFORMANCE—RSKJ/RSMJ/RSNJ- SERIES

26

Low

5.0 [17.6]

1750/2250

1400/1800

1225/1575

1050/1350

875/1125

700/900

Manufacturer Recommended Air-Flow Range (Min/Max) CFM

[ ] Designates Metric Conversions

Low

Low

3.0 [10.55]

4.0 [14.07]

Low

2.5 [8.79]

Low

Low

2.0 [7.03]

3.5 [12.31]

Motor Speed from Factory

Nominal Cooling Capacity Tons [kW]

11x9 3/4 HP [559] 2 Speed Motor

11x9 3/4 HP [559] 2 Speed Motor

11x9 1/2 HP [373] 2 Speed Motor

10x9 1/2 HP [373] 2 Speed Motor

10x9 1/3 HP [249] 2 Speed Motor

10x9 1/4 HP [186] 2 Speed Motor

Blower Size/ Motor HP [W] & # of Speeds

High

Low

High

Low

High

Low

High

Low

High

Low

High

Low

Motor Speed

685 639

651 1766 [833] 653 651 1403 [662]

CFM RPM Watts CFM

827 1219

RPM Watts

2429 [1146]

CFM

1771 [836]

CFM 716

651 628

619

RPM Watts RPM

639

1758 [830]

CFM

Watts

652

465

1214

834

2413 [1139]

712

657

1747 [824]

1722 [813]

456

528

RPM Watts

574

1382 [652]

1727 [815]

639

653

RPM

685

1221 [576]

696

812

1842 [869]

343

623

1133 [535]

398

596

1154 [545]

278

543

904 [427]

393

618

1062 [501]

222

528

692 [327]

0.2 [.05]

Watts

1259 [594]

710

CFM

778

RPM

1915 [904]

CFM Watts

346

1169 552]

CFM 540

401

RPM

526

RPM Watts

Watts

1164 [549]

923 [436]

CFM

CFM

396

280

528

RPM Watts

Watts

1062 [501]

CFM

498

230

Watts

RPM

443

723 [341]

RPM

CFM

0.1 [.02]

INDOOR AIRFLOW PERFORMANCE—208 VOLTS

1206

843

2386 [1126]

704

697

1716 [810]

624

698

1680 [793]

449

631

1350 [637]

628

716

1684 [795]

628

716

1178 [556]

684

849

1798 [849]

338

681

1099 [519]

388

670

1143 [539]

268

648

874 [412]

384

674

1058 [499]

219

651

654 [309]

0.3 [.07]

1193

873

2346 [1107]

692

738

1676 [791]

619

738

1633 [771]

443

682

1308 [617]

618

757

1636 [772]

618

757

1129 [533]

662

887

1767 [834]

331

757

1060 [500]

379

744

1124 [530]

259

728

832 [393]

376

735

1043 [492]

214

710

609 [287]

0.4 [.10]

1171

896

2295 [1083]

685

775

1628 [768]

610

781

1581 [746]

440

733

1254 [592]

598

807

1581 [746]

598

807

1075 [507]

647

924

1731 [817]

324

814

1010 [477]

371

803

1090 [514]

252

806

774 [365]

361

812

1013 [478]

202

819

556 [262]

0.5 [.12]

1148

922

2232 [1053]

669

816

1572 [742]

599

816

1524 [719]

432

775

1189 [561]

590

845

1518 [716]

590

845

1013 [478]

623

958

1676 [791]

300

906

942 [445]

350

864

1034 [488]

243

853

698 [329]

335

895

962 [454]

196

863

496 [234]

0.6 [.15]

1126

940

2158 [1018]

651

865

1507 [711]

586

856

1462 [690]

416

824

1113 [525]

560

889

1445 [682]

560

889

943 [445]

599

985

1586 [749]

290

931

852 [402]

322

945

948 [447]

219

947

602 [284]

318

936

884 [417]

184

914

428 [202]

0.7 [.17]

External Static Pressure—Inches W.C. [kPa]

CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil

1096

961

2071 [977]

632

899

1435 [677]

569

887

1394 [658]

406

855

1026 [484]

538

926

1360 [642]

538

926

864 [408]

561

1019

1443 [681]

279

971

732 [345]

310

971

826 [390]

201

989

483 [228]

297

985

774 [365]







0.8 [.20]

1053

990

1973 [931]

604

937

1355 [639]

544

927

1322 [624]

385

912

929 [438]

515

957

1261 [595]

515

957

774 [365]

508

1055

1233 [582]

255

1018

576 [272]

259

1051

660 [311]







244

1055

627 [296]







0.9 [.22]

998

1018

1863 [879]

586

968

1267 [598]

527

956

1244 [587]

357

968

820 [387]

493

984

1147 [541]

493

984

672 [317]

441

1095

939 [443]

226

1074

379 [179]

235

1078

445 [210]







223

1080

437 [206]







1.0 [.25]

AIRFLOW PERFORMANCE—RSKJ/RSMJ/RSNJ- SERIES

ELECTRICAL DATA—RSKJ- SERIES Model No. RSKJA024JK A030JK A036JK A042JK A048JK A060JK

Unit Information Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253 187-253

Minimum Circuit Ampacity 17/17 21/21 24/24 29/29 31/31 44/44

Evaporator Fan

Minimum Overcurrent Protection Device Size 20/20 25/25 30/30 35/35 40/40 60/60

Maximum Overcurrent Protection Device Size 25/25 30/30 40/40 45/45 50/50 70/70

No.

Volts

Phase

HP

1 1 1 1

208/230 208/230 208/230 208/230

1 1 1 1

1/4 1/3 1/2 1/2

1

208/230

1

3/4

1

208/230

1

3/4

Compressor Motor

Model No. RSKJ-

No.

Volts

Phase

HP2

RPM

A024JK A030JK

1 1

208/230 208/230

1 1

2 2.5

3450 3450

A036JK

1

208/230

1

3

3450

A042JK A048JK A060JK

1 1 1

208/230 208/230 208/230

1 1 1

3.5 4 4.5

3450 3450 3450

Amps (FLA) 1.5 1.8 2.5 2.8 3.1 5.8

Amps (LRA) 2.6 2.6 5 4.6 4.4 9.6

Condenser Motor Amps1 (RLA) 10.9/10.9 14.1/14.1 16.0/16.0 19.2/19.2 20.2/20.2 28.8/28.8

Amps1 (LRA) 54/54 72.8/72.8 88/88 104/104 137/137 148/148

1. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps. 2. Horsepower Per Compressor.

27

No.

Volts

Phase

HP2

1 1

208/230 208/230

1 1

1/3 1/3

1

208/230

1

1/3

1 1 1

208/230 208/230 208/230

1 1 1

1/3 1/3 1/3

Amps1 (FLA) 1.5 1.5 1.5 1.5 1.8 1.8

Amps1 (LRA) 3 3 3 3 4 4

ELECTRICAL DATA—RSMJ- SERIES Model No. RSMJA024JK A030JK A036JK A042JK A048JK A060JK

Unit Information Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253 187-253

Minimum Circuit Ampacity 17/17 21/21 24/24 29/29 31/31 44/44

Evaporator Fan

Minimum Overcurrent Protection Device Size 20/20 25/25 30/30 35/35 40/40 60/60

Maximum Overcurrent Protection Device Size 25/25 30/30 40/40 45/45 50/50 70/70

No.

Volts

Phase

HP

1 1 1 1 1

208/230 208/230 208/230 208/230 208/230

1 1 1 1 1

1/4 1/3 1/2 1/2 3/4

1

208/230

1

3/4

Compressor Motor

Model No. RSMJ-

No.

Volts

A024JK A030JK

1 1

A036JK A042JK A048JK A060JK

Phase

2

HP

RPM

208/230 208/230

1 1

2 2.5

3450 3450

1

208/230

1

3

3450

1 1

208/230 208/230

1 1

3.5 4

3450 3450

1

208/230

1

4.5

3450

Amps (FLA) 1.5 1.8 2.5 2.7 3.2 5.8

Amps (LRA) 2.6 2.6 5.0 4.6 4.4 11.3

Condenser Motor Amps1 (RLA) 10.9/10.9 14.1/14.1 16.0/16.0 19.2/19.2 20.2/20.2 28.8/28.8

Amps1 (LRA) 54./54 72.8/72.8 88/88 104/104 137/137 148/148

1. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps. 2. Horsepower Per Compressor.

28

No.

Volts

Phase

HP2

1 1

208/230 208/230

1 1

1/3 1/3

1

208/230

1

1/3

1 1

208/230 208/230

1 1

1/3 1/3

1

208/230

1

1/3

Amps1 (FLA) 1.5 1.5 1.5 1.5 1.8 1.8

Amps1 (LRA) 3.0 3.0 3.0 3.0 4.0 4.0

ELECTRICAL DATA—RSNJ- SERIES Model No. RSNJA024JK A030JK A036CK A036JK A042CK A042JK A048CK A048JK A060CK A060JK

Unit Information Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253

Minimum Circuit Ampacity 17/17 21/21 16/16 21/21 18/18 25/25 21/21 28/28 30/30 40/40

Evaporator Fan

Minimum Overcurrent Protection Device Size 20/20 25/25 20/20 25/25 20/20 30/30 25/25 35/35 35/35 50/50

Maximum Overcurrent Protection Device Size 25/25 35/35 25/25 30/30 25/25 40/40 30/30 45/45 45/45 60/60

No.

Volts

Phase

HP

1 1 1 1

208/230 208/230 208/230 208/230

1 1 1 1

1/4 1/3 1/2 1/2

1

208/230

1

1/2

1 1 1 1 1

208/230 208/230 208/230 208/230 208/230

1 1 1 1 1

1/2 3/4 3/4 3/4 3/4

Compressor Motor

Model No. RSNJ-

No.

Volts

Phase

HP2

RPM

A024JK A030JK

1 1

208/230 208/230

1 1

2 2.5

3450 3450

A036CK

1

208/230

3

3

3450

A036JK A042CK A042JK A048CK A048JK A060CK A060JK

1 1 1 1 1 1 1

208/230 208/230 208/230 208/230 208/230 208/230 208/230

1 3 1 3 1 3 1

3 3.5 3.5 4 4 4.5 4.5

3450 3450 3450 3450 3450 3450 3450

Amps (FLA) 1.5 1.8 2.5 2.5 2.8 2.8 3.2 3.2 5.8 5.8

Amps (LRA) 2.6 2.6 5 5 4.6 4.6 4.4 4.4 9.6 9.6

Condenser Motor Amps1 (RLA) 10.9/10.9 14.1/14.1 9.6/9.6 13.5/13.5 10.3/10.3 16.5/16.5 12.4/12.4 17.9/17.9 17.3/17.3 25.3/25.3

Amps1 (LRA) 54/54 68/68 63/63 73/73 77/77 95/95 88/88 104/104 123/123 141/141

1. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps. 2. Horsepower Per Compressor.

29

No.

Volts

Phase

HP2

1 1

208/230 208/230

1 1

1/3 1/3

1

208/230

1

1/3

1 1 1 1 1 1 1

208/230 208/230 208/230 208/230 208/230 208/230 208/230

1 1 1 1 1 1 1

1/3 1/3 1/3 1/3 1/3 1/3 1/3

Amps1 (FLA) 1.5 1.5 1.5 1.5 1.5 1.5 1.8 1.8 1.8 1.8

Amps1 (LRA) 3 3 3 3 3 3 4 4 4 4

ELECTRIC HEATER KITS—RSKJ- SERIES 208-240 VOLT, SINGLE POWER SUPPLY FOR UNIT AND HEATER KIT Model No. RSKJ-

A024J

A030J

A036J

A042J

A048J

A060J

RXQJ-C Heater Kit Nominal kW

No. of Elements

No. of Sequence Steps

Rated Heater kW @ 208-240 V

Heater KBTU/Hr @ 208-240 V

Heater Amps. @ 208-240 V

Unit Min. Ckt. Ampacity @ 208-240 V

No Heat 05J 07J 10J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J

— 1 1 2 — 1 1 2 3 — 1 1 2 3 — 1 1 2 3 4 — 1 1 2 3 4 — 1 1 2 3 4

— 1 1 1 — 1 1 1 2 — 1 1 1 2 — 1 1 1 2 2 — 1 1 1 2 2 — 1 1 1 2 2

— 3.6/4.8 5.4/7.2 7.2/9.6 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2

— 12.28/16.38 18.42/24.56 24.57/32.76 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52

— 17.33/20.00 26.00/30.00 34.67/40.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00

17/17 24/27 34/39 45/52 21/21 24/27 35/40 46/52 67/77 24/24 25/28 35/40 46/53 68/78 29/29 29/29 36/41 47/53 68/78 90/103 31/31 31/31 36/41 47/54 69/79 90/104 44/44 44/44 44/44 50/56 71/81 93/106

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

30

Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 25/25 30/30 35/35 40/40 45/45 60/60 25/30 25/30 25/30 30/30 35/35 40/40 50/50 60/60 70/70 80/80 30/40 30/40 30/40 30/40 35/40 40/40 50/50 60/60 70/70 80/80 35/45 35/45 35/45 35/45 40/40 45/45 50/50 60/60 70/70 80/80 90/90 110/110 40/50 40/50 40/50 40/50 40/50 45/50 50/50 60/60 70/70 80/80 90/90 110/110 60/60 60/60 60/60 60/60 60/60 60/60 60/70 60/70 80/80 90/90 100/100 110/110

ELECTRIC HEATER KITS—RSKJ- SERIES 208-240 VOLT, SEPARATE POWER SUPPLY FOR UNIT AND HEATER KIT Model No. RSKJ-

A024J

A030J

A036J

A042J

A048J

A060J

Heat Pump Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 — — — — — — 25/30 25/30 — — — — — — — — 30/40 30/40 — — — — — — — —

RXQJ-C Heater Kit Nominal kW

Heater Kit Min. Ckt. Ampacity

Heater Kit Max. Fuse Size

Heated Pump Min. Ckt. Ampacity 208-240

No Heat 05J 07J 10J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J

— 22/25 33/38 44/50 — 22/25 33/38 44/50 65/75 — 22/25 33/38 44/50 65/75

— 25/25 35/40 45/50 — 25/25 35/40 45/50 70/80 — 25/25 35/40 45/50 70/80

17/17 — — — 21/21 — — — — 24/24 — — — —

No Heat 05J 07J 10J 15J 20J

— 22/25 33/38 44/50 65/75 87/100

— 25/25 35/40 45/50 70/80 90/100

29/29 — — — — —

35/45 — — — — —

35/45 — — — — —

No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J

— 22/25 33/38 44/50 65/75 87/100 — 22/25 33/38 44/50 65/75 87/100

— 25/25 35/40 45/50 70/80 90/100 — 25/25 35/40 45/50 70/80 90/100

31/31 — — — — — 44/44 — — — — —

40/50 — — — — — 60/60 — — — — —

40/50 — — — — — 60/60 — — — — —

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

31

ELECTRIC HEATER KITS—RSMJ- SERIES 208-240 VOLT, SINGLE POWER SUPPLY FOR UNIT AND HEATER KIT Model No. RSMJ-

Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 25/25 30/30 35/35 40/40 45/45 60/60 25/30 25/30 25/30 30/30 35/35 40/40 50/50 60/60 70/70 80/80

RXQJ-C Heater Kit Nominal kW

No. of Elements

No. of Sequence Steps

Rated Heater kW @ 208-240 V

Heater KBTU/Hr @ 208-240 V

Heater Amps. @ 208-240 V

Unit Min. Ckt. Ampacity @ 208-240 V

No Heat 05J 07J 10J No Heat 05J 07J 10J 15J

— 1 1 2 — 1 1 2 3

— 1 1 1 — 1 1 1 2

— 3.6/4.8 5.4/7.2 7.2/9.6 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4

— 12.28/16.38 18.42/24.56 24.57/32.76 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13

— 17.33/20.00 26.00/30.00 34.67/40.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00

17/17 24/27 34/39 45/52 21/21 24/27 35/40 46/52 67/77

A036J

No Heat 05J 07J 10J 15J

— 1 1 2 3

— 1 1 1 2

— 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4

— 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13

— 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00

24/24 25/28 35/40 46/53 68/78

30/40 30/40 35/40 50/50 70/70

30/40 30/40 40/40 60/60 80/80

A042J

No Heat 05J 07J 10J 15J 20J

— 1 1 2 3 4

— 1 1 1 2 2

— 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2

— 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52

— 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00

29/29 29/29 36/41 47/53 68/78 90/103

35/45 35/45 40/40 50/50 70/70 90/90

35/45 35/45 45/45 60/60 80/80 110/110

No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J

— 1 1 2 3 4 — 1 1 2 3 4

— 1 1 1 2 2 — 1 1 1 2 2

— 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2

— 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52

— 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00

31/31 31/31 36/41 47/54 69/79 90/104 44/44 44/44 44/44 50/56 71/81 93/106

40/50 40/50 40/50 50/50 70/70 90/90 60/60 60/60 60/60 60/70 80/80 100/100

40/50 40/50 45/50 60/60 80/80 110/110 60/60 60/60 60/60 60/70 90/90 110/110

A024J

A030J

A048J

A060J

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

32

ELECTRIC HEATER KITS—RSMJ- SERIES 208-240 VOLT, SEPARATE POWER SUPPLY FOR UNIT AND HEATER KIT Model No. RSMJ-

A024J

A030J

A036J

A042J

A048J

A060J

Heat Pump Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 — — — — — — 25/30 25/30 — — — — — — — — 30/40 30/40 — — — — — — — —

RXQJ-C Heater Kit Nominal kW

Heater Kit Min. Ckt. Ampacity

Heater Kit Max. Fuse Size

Heated Pump Min. Ckt. Ampacity @ 208-240 V

No Heat 05J 07J 10J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J

— 22/25 33/38 44/50 — 22/25 33/38 44/50 65/75 — 22/25 33/38 44/50 65/75

— 25/25 35/40 45/50 — 25/25 35/40 45/50 70/80 — 25/25 35/40 45/50 70/80

17/17 — — — 21/21 — — — — 24/24 — — — —

No Heat 05J 07J 10J 15J 20J

— 22/25 33/38 44/50 65/75 87/100

— 25/25 35/40 45/50 70/80 90/100

29/29 — — — — —

35/45 — — — — —

35/45 — — — — —

No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J

— 22/25 33/38 44/50 65/75 87/100 — 22/25 33/38 44/50 65/75 87/100

— 25/25 35/40 45/50 70/80 90/100 — 25/25 35/40 45/50 70/80 90/100

31/31 — — — — — 44/44 — — — — —

40/50 — — — — — 60/60 — — — — —

40/50 — — — — — 60/60 — — — — —

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

33

ELECTRIC HEATER KITS—RSNJ- SERIES 208-240 VOLT, SINGLE POWER SUPPLY FOR UNIT AND HEATER KIT Model No. RSNJ-

A024J

A030J

A036J

A042J

A048J

A060J

RXQJ-C Heater Kit Nominal kW

No. of Elements

No. of Sequence Steps

Rated Heater kW @ 208-240 V

Heater KBTU/Hr @ 208-240 V

Heater Amps. @ 208-240 V

Unit Min. Ckt. Ampacity @ 208-240 V

No Heat 05J 07J 10J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J

— 1 1 2 — 1 1 2 3 — 1 1 2 3 — 1 1 2 3 4 — 1 1 2 3 4 — 1 1 2 3 4

— 1 1 1 — 1 1 1 2 — 1 1 1 2 — 1 1 1 2 2 — 1 1 1 2 2 — 1 1 1 2 2

— 3.6/4.8 5.4/7.2 7.2/9.6 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 14.4/19.2

— 12.28/16.38 18.42/24.56 24.57/32.76 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52 — 12.28/16.38 18.42/24.56 24.57/32.76 36.85/49.13 49.12/65.52

— 17.33/20.00 26.00/30.00 34.67/40.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00 — 17.33/20.00 26.00/30.00 34.67/40.00 52.00/60.00 69.33/80.00

17/17 24/27 34/39 45/52 21/21 24/27 35/40 46/52 67/77 21/21 25/28 36/41 47/53 68/78 25/25 25/29 36/41 47/54 69/79 90/104 28/28 28/29 37/42 47/54 69/79 91/104 40/40 40/40 40/45 51/57 72/82 94/107

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

34

Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 25/25 30/30 40/40 35/35 50/50 60/60 25/35 25/35 25/35 30/35 35/35 40/40 50/50 60/60 70/70 80/80 25/30 25/30 25/30 30/30 40/40 45/45 50/50 60/60 70/70 80/80 30/40 30/40 30/40 30/40 40/40 45/45 50/50 60/60 70/70 80/80 100/100 110/110 35/45 35/45 35/45 35/45 40/40 45/45 50/50 60/60 70/70 80/80 100/100 110/110 50/60 50/60 50/60 50/60 50/60 50/60 60/60 60/60 80/80 90/90 100/100 110/110

ELECTRIC HEATER KITS—RSNJ- SERIES 208-240 VOLT, SEPARATE POWER SUPPLY FOR UNIT AND HEATER KIT Model No. RSNJ-

A024J

A030J

A036J

A042J

A048J

A060J

RXQJ-C Heater Kit Nominal kW

Heater Kit Min. Ckt. Ampacity

Heater Kit Max. Fuse Size

Heated Pump Min. Ckt. Ampacity @ 208-240 V

No Heat 05J 07J 10J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J

— 22/25 33/38 44/50 — 22/25 33/38 44/50 65/75 — 22/25 33/38 44/50 65/75 — 22/25 33/38 44/50 65/75 87/100 — 22/25 33/38 44/50 65/75 87/100 — 22/25 33/38 44/50 65/75 87/100

— 25/25 35/40 45/50 — 25/25 35/40 45/50 70/80 — 25/25 35/40 45/50 70/80 — 25/25 35/40 45/50 70/80 90/100 — 25/25 35/40 45/50 70/80 90/100 — 25/25 35/40 45/50 70/80 90/100

17/17 — — — 21/21 — — — — 21/21 — — — — 25/25 — — — — — 28/28 — — — — — 40/40 — — — — —

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

35

Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 — — — — — — 25/35 25/35 — — — — — — — — 25/30 25/30 — — — — — — — — 30/40 30/40 — — — — — — — — — — 35/45 35/45 — — — — — — — — — — 50/60 50/60 — — — — — — — — — —

ELECTRIC HEATER KITS—RSNJ- SERIES 208-240 VOLT, SINGLE POWER SUPPLY FOR UNIT AND HEATER KIT THREE PHASE Model No. RSNJA036C

A042C

A048C

A060C

RXQJ-C Heater Kit Nominal kW

No. of Elements

No. of Sequence Steps

Rated Heater kW @ 208-240 V

Heater KBTU/Hr @ 208-240 V

Heater Amps. @ 208-240 V

Unit Min. Ckt. Ampacity @ 208-240 V

No Heat 10C 15C No Heat 10C 15C 20C No Heat 10C 15C 20C No Heat 10C 15C 20C

— 2 3 — 2 3 4 — 2 3 4 — 2 3 4

— 1 2 — 1 2 2 — 1 2 2 — 1 2 2

— 7.2/9.6 10.8/14.4 — 7.2/9.6 10.8/14.4 14.4/19.2 — 7.2/9.6 10.8/14.4 14.4/19.2 — 7.2/9.6 10.8/14.4 14.4/19.2

— 24.57/32.76 36.85/49.13 — 24.57/32.76 36.85/49.13 49.12/65.52 — 24.57/32.76 36.85/49.13 49.12/65.52 — 24.57/32.76 36.85/49.13 49.12/65.52

— 20/23.1 30/34.6 — 20/23.1 30/34.6 40/46.2 — 20/23.1 30/34.6 40/46.2 — 20/23.1 30/34.6 40/46.2

16/16 29/32 41/47 18/18 29/33 41/47 54/62 21/21 29/33 42/48 54/62 30/30 40/40 45/51 58/65

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

36

Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 30/30 35/35 45/45 50/50 20/25 20/25 30/30 35/35 45/45 50/50 60/60 70/70 25/30 25/30 30/30 35/35 45/45 50/50 60/60 70/70 35/45 35/45 40/40 40/40 45/45 60/60 60/60 70/70

ELECTRIC HEATER KITS—RSNJ- SERIES 208-240 VOLT, SEPARATE POWER SUPPLY FOR UNIT AND HEATER KIT THREE PHASE Model No. RSNJ-

A036C

A042C

A048C

A060C

RXQJ-C Heater Kit Nominal kW

Heater Kit Min. Ckt. Ampacity

Heater Kit Max. Fuse Size

Heated Pump Min. Ckt. Ampacity @ 208-240 V

No Heat 10C 15C No Heat 10C 15C 20C No Heat 10C 15C 20C No Heat 10C 15C 20C

— 25/29 38/44 — 25/29 38/44 50/58 — 25/29 38/44 50/58 — 25/29 38/44 50/58

— 25/30 40/45 — 25/30 40/45 50/60 — 25/30 40/45 50/60 — 25/30 40/45 50/60

16/16 — — 18/18 — — 21/21 — — — 30/30

— — 25/30 — — — 35/45

— — 25/30 — — — 35/45

— —

— —

— —

WARNING ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

37

Overcurrent Protective Device Size Min./Max. Min./Max. @ 208 V @ 240 V 20/25 20/25 — — — — 20/25 20/25

UNIT DIMENSIONS—RSKJ/RSMJ/RSNJ- SERIES DIMENSIONS

FRONT VIEW

Model

Height “A”

024, 030, 036, 042 048, 060

29 1/8" 37 1/8"

59 [1498.6 mm]

CONDENSATE DRAIN PAN ACCESS A

CONTROL BOX ACCESS

91/2 [241.3 mm] 211/16 [266.7 mm]

235/16 [592.1 mm]

C L 151/2 [393.7 mm]

31/16 [77.7 mm]

531/2 [1358.9 mm]

REAR VIEW

BOTTOM VIEW

ELECTRICAL CONNECTIONS

(FRONT)

RECOMMENDED UNIT DISCONNECT LOCATION

AUXILIARY HIGH VOLTAGE ENTRANCE 123/32 [43.7 mm] 313/64 [81.2 mm]

LOW VOLTAGE ENTRANCE 7/8 [22.2 mm]

33/4 [95.3 mm]

721/32 [194.3 mm] PRIMARY HIGH VOLTAGE 413/32 ENTRANCE [111.8 mm] 23 1 /32 [43.7 mm] 59/64 [130.5 mm]

57/8 [149.5 mm] 197/8 [505 mm]

31/2 [88.9 mm]

(REAR)

[ ] Designates Metric Conversions

38

TYPICAL INSTALLATIONS

SERVICE ACCESS PANELS. DO NOT BLOCK ACCESS

SUPPLY PLENUM

[ ] Designates Metric Conversions

39

ACCESSORIES ACCESSORY EQUIPMENT Accessory Description Outdoor Thermostat

Model Application RSKJ/RSMJ/RSNJ

Accessory Model No. RXPT-A01

[ ] Designates Metric Conversions

40

WIRING SCHEMATICS—RSKJ/RSMJ/RSNJ- SERIES

41

WIRING SCHEMATICS—RSKJ/RSMJ/RSNJ- SERIES

42

BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.

GENERAL TERMS OF LIMITED WARRANTY Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty. For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

*Compressor (1 Phase, 12 & 13 SEER models).Ten (10) Years *Compressor in Comm. Application ..................Five (5) Years *Any Other Part..............................................Five (5) Years *All other parts and components carry a limited warranty of five years, provided they are single-phase products installed in a residential application. Products installed in commercial applications have a one (1) year limited parts warranty.

RHEEM AIR CONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72908

“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.” PRINTED IN U.S.A.

12-04 DC

FORM NO. A11-179 Rev. 2 Supersedes Form no. A11-179 Rev. 1