MECHANICAL ABBREVIATIONS: AIR TRANSFER
TG TAG-# CFM
DIFFUSER / REGISTER TAG WALL SUPPLY REGISTER TURNING VANES INTAKE LOUVER W/ SCREEN BACK DRAFT DAMPER
FIRE DAMPER
M
DAMPER - MOTORIZED
A
DAMPER - PNEUMATIC
FIRE / SMOKE DAMPER MANUAL VOLUME DAMPER
DUCT TANSITION
SPIN-IN W/O VOLUME DAMPER
SPIN-IN W/ VOLUME DAMPER
M
DAMPER MOTORIZED
CEILING DIFFUSER - 2 WAY
A
DAMPER CONTROL PNEUMATIC
CEILING DIFFUSER - 3 WAY TEXT BRACKET
CEILING DIFFUSER - 4 WAY
CONNECTION TO EXISTING. CEILING DIFFUSER - CORNER
CEILING DIFFUSER - ROUND
P PS
PRESSURE STAT
PRESSURE SWITCH
LINEAR DIFFUSER
FS
FLOW SWITCH
LINEAR SLOT DIFFUSER - UP
BRANCH SUPPLY/RETURN
T
BULB T-STAT
THERMOMETER DUCT - EXHAUST DUCT - RETURN DUCT - SUPPLY
T T
T-STAT - ELECTRIC
T-STAT - PNEUMATIC
DIRECTIONAL FLOW
DD
DUCT DETECTOR
ELEVATION CHANGE
FS-1
FIRE STAT
DUCT FLEX
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
RETURN AIR - DOWN
FZ-1
H
FREEZE STAT
HUMIDISTAT
RETURN AIR - UP
SD
SMOKE DETECTOR
SUPPLY AIR - DOWN DUCT FAN
SUPPLY AIR - UP FAN INLINE
ROUND DUCT - UP
ROUND DUCT - DOWN
DUCT FAN AIR DIRECTION
DUCT FAN AXIAL - SCHEMATIC
UNIT HEATER ROUND PIPE/DUCT SECTION MUSHROOM FAN
R
STANDARD BRANCH RETURN ROOF EXHAUST FAN / HOOD
# NUMBER, POUND % PERCENT & AND @ AT °F DEGREES FAHRENHEIT °C DEGREES CENTIGRADE ABAN ABANDONED AC AIR CONDITIONER AD AUTOMATIC DAMPER AFF ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT APD AIR PRESSURE DROP APPROX APPROXIMATELY ASHRAE AMERICAN SOCIETY OR HEATING, REFRIGERATION, AND AIR CONDITIONING ENGINEERS ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASTM AMERICAN SOCIETY OF TESTING MATERIALS AWS AMERICAN WELDING SOCIETY BDD BACKDRAFT DAMPER BFF BELOW FINISHED FLOOR BOD BOTTOM OF DUCT BOS BOTTOM OF STEEL BTU BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNIT PER HOUR CAP CAPACITY CD CEILING DIFFUSER CFH CUBIC FEET PER HOUR CFM CUBIC FEET PER MINUTE CFS CUBIC FEET PER SECOND CUH CABINET UNIT HEATER CV CONTROL VALVE CWR COOLING WATER RETURN CWS COOLING WATER SUPPLY DEG, ° DEGREES DEMO DEMOLITION DG DOOR GRILLE DHU DEHUMIDIFICATION UNIT DN DOWN DX DIRECT EXPANSION EA EACH EAD EXHAUST AIR DIFFUSER EAG EXHAUST AIR GRILLE EAT ENTERING AIR TEMPERATURE EDB ENTERING DRY BULB TEMPERATURE EFF EFFICIENCY EAR EXHAUST AIR REGISTER ESP EXTERNAL STATIC PRESSURE EWB ENTERING WET BULB TEMPERATURE EWT ENTERING WATER TEMPERATURE EXA EXHAUST AIR EXH EXHAUST EXST EXISTING F FILTER FAI FRESH AIR INTAKE FCU FAN COIL UNIT FD FIRE DAMPER FF FINISHED FLOOR FG FLOOR GRILLE FL FLANGE FLEX FLEXIBLE FPM FEET PER MINUTE FT, ' FOOT, FEET FTR FIN TUBE RADIATOR HC HEATING COIL HDPE HIGH DENSITY POLYETHYLENE HOA HAND OFF AUTO HP HORSE POWER HPC HIGH PERFORMANCE COATING HTG HEATING HTR HEATER HVAC HEATING VENTILATION AND COOLING HW HOT WATER (DOMESTIC) HWC HOT WATER CIRCULATION HWH HOT WATER HEATER HWP HOT WATER PUMP HWR HOT WATER RETURN HWS HOT WATER SUPPLY HWT HOT WATER TANK ID INSIDE DIAMETER IDEN INDENTIFY, INDENTITY IL INTAKE LOUVER IN, " INCH KW KILOWATT L LENGTH LAT LEAVING AIR TEMPERATURE LDB LEAVING DRY BULB LPC LOW PRESSURE CONDENSATE LVR LOUVER LWB LEAVING WET BULB LWT LEAVING WATER TEMPERATURE MAU MAKE-UP AIR UNIT MAX MAXIMUM MCC MOTOR CONTROL CENTER MD MOTORIZED DAMPER MECH MECHANICAL MEZZ MEZZANINE MFR MANUFACTURER MIN MINIMUM N.C. NORMALLY CLOSED N.A. NORMALLY OPEN N/A NOT APPLICABLE NTS NOT TO SCALE OA OUTSIDE AIR OAD OUTSIDE AIR DAMPER OCU ODOR CONTROL UNIT OD OUTSIDE DIAMETER PD PRESSURE DROP PH / PHASE PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE PVC POLYVINYL CHLORIDE
R RA RAD RAG RAR RCU RED REG RET RHC RPM SA SAD SAG SAR SF SP SQ SST T TA TAG TBD TOC TOD TOF TOG TOM TOP TOS TOW TSP TYP UH UV VAV VD VFD VTR WB WR XP
RADIUS RETURN AIR RETURN AIR DAMPER RETURN AIR GRILLE RETURN AIR REGISTER REMOTE CONDENSING UNIT REDUCER REGISTER RETURN REHEAT COIL REVOLUTIONS PER MINUTE SUPPLY AIR SUPPLY AIR DIFFUSER SUPPLY AIR GRILLE SUPPLY AIR REGISTER SQUARE FEET, SUPPLY FAN STATIC PRESSURE SQUARE STAINLESS STEEL THERMOMETER TRANSFER AIR TRANSFER AIR GRILLE TO BE DETERMINED TOP OF CONCRETE TOP OF DUCT TOP OF FOOTING, TOP OF FASCIA TOP OF GRATE TOP OF MASONRY TOP OF PIPE TOP OF STEEL TOP OF WALL TOTAL STATIC PRESSURE TYPICAL UNIT HEATER UNIT VENTILATOR VARIABLE AIR VOLUME VOLUME DAMPER VARIABLE FREQUENCY DRIVE VENT TO ROOF WET BULB WALL REGISTER EXPLOSION PROOF
1.
2.
3.
4.
ALL MECHANICAL WORK SHALL BE IN STRICT COMPLIANCE WITH THE INTERNATIONAL MECHANICAL CODE (IMC) AND APPLICABLE PROVISIONS OF THE INTERNATIONAL FUEL GAS CODE (IFGC).
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
ALL REFERENCES TO REFERENCE STANDARDS HEREIN ARE TO MOST RECENT ISSUE IN EFFECT AS OF THE DATE OF THESE DOCUMENTS, UNLESS NOTED OTHERWISE IN PROJECT SPECIFICATIONS OR ON THE DRAWINGS. ALL MECHANICAL EQUIPMENT SHALL BE IN STRICT COMPLIANCE WITH THE INTERNATIONAL MECHANICAL CODE AND OTHER STATE AND LOCAL REGULATIONS. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE PLANS, MANUFACTURER'S SPECIFICATIONS AND GOVERNING INTERNATIONAL MECHANICAL CODE AND INTERNATIONAL FUEL GAS CODE PROVISIONS. THESE SHEETS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES, AND CONTROLS. THE SYSTEM SHALL BE COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL PARAMETERS GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY CONFORMED TO. ANY ITEM AND LABOR REQUIRED FOR A COMPLETE SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, AND THESE CONTRACT DOCUMENTS SHALL BE FURNISHED WITHOUT INCURRING ANY ADDITIONAL COST TO THE OWNER. CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE PREPARING SHOP DRAWINGS.
5.
THESE GENERAL NOTES PRESENT AND/OR SUMMARIZE KEY PROJECT INFORMATION FOR THE DRAWING READER'S CONVENIENCE. SEE ALSO INDIVIDUAL DRAWING NOTES AND PROJECT SPECIFICATIONS FOR FURTHER DETAILS AND REQUIREMENTS.
6.
SUBMIT SHOP DRAWINGS, PROJECT DATA AND SAMPLES AS SPECIFIED IN THE PROJECT SPECIFICATIONS.
7.
ALL EXISTING DIMENSIONS SHOWN WITH THE ± SYMBOL ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR BEFORE FABRICATION AND CONSTRUCTION.
8.
DIMENSIONS MARKED WITH AN “X” SHALL BE DETERMINED BY EQUIPMENT MANUFACTURER.
9.
PROVIDE INSECT SCREEN AT THE OPENING OF ALL VENTS THAT TERMINATE OUTDOORS.
10.
ALL AIR EXHAUST AND INTAKE OPENINGS THAT TERMINATE OUTDOORS SHALL BE PROTECTED BY CORROSION-RESISTANT SCREENS, LOUVERS, OR GRILLES. OPENINGS IN SCREENS, LOUVERS OR GRILLES SHALL BE SIZED ACCORDING TO THE INTERNATIONAL MECHANICAL CODE AND SHALL BE PROTECTED AGAINST LOCAL WEATHER CONDITIONS.
12.
ALL LOW PRESSURE SUPPLY DUCTWORK SHALL BE INSULATED. SEE SPECIFICATION FOR ADDITIONAL INSULATION REQUIREMENTS.
13.
OUTSIDE AIR DUCTWORK SHALL BE INSULATED. EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE INSULATED AND PROTECTED WITH ALUMINUM JACKET.
14.
EXHAUST AIR DUCTWORK SHALL NOT REQUIRE INSULATION EXCEPT WHERE INDICATED ON THE DRAWINGS.
15.
ALL DUCTWORK IS SHOWN AS FREE AREA INSIDE DIMENSIONS.
16.
USE SPIN-INS WITH SCOOP AND VOLUME DAMPER FOR ROUND TAKE-OFFS FROM SQUARE DUCT.
17.
USE 45 DEGREE TAPS FOR ROUND TO ROUND TAKE-OFFS, PROVIDE VOLUME DAMPERS AT EACH TAKE OFF.
18.
DO NOT CONSTRUCT OR INSTALL TAPS OUT OF REDUCERS, TEES OR ELBOWS.
19.
ALLOW FOR FIELD MEASURED OFFSETS OR TRANSITIONS, ELBOWS, ECT.
20.
DOVETAIL AND/OR SEAL TIGHT FACE MOUNTED TAP-INS ARE NOT ACCEPTABLE.
21.
SUPPORT ALL FLEXIBLE DUCTWORK AS SHOWN IN SMACNA FIGURE 3-9, 1985. TOTAL LENGTH OF FLEX DUCT NOT TO EXCEED 5 FEET.
22.
DO NOT USE FLEX DUCT IN EXPOSED AREAS. MAXIMUM FLEX DUCT LENGTH AT ANY CONNECTION SHALL NOT EXCEED 5 FEET. FLEX DUCT SHALL NOT BE USED FOR ELBOWS EXCEPT FOR DIFFUSER CONNECTIONS.
23.
GRILLES, REGISTERS, AND DIFFUSERS CONNECTED BY FLEXIBLE DUCT SHALL BE SUPPORTED INDEPENDENTLY FROM THE FLEXIBLE DUCT.
24.
ELBOWS SHALL BE 90 DEGREE ELLS WITH DOUBLE THICKNESS TURNING VANES OR WHERE SPACE PERMITS RADIUS FITTING WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES THE DUCT WIDTH CENTERLINE. NO OTHERS WILL BE ALLOWED.
25.
COORDINATE FINAL LOCATION OF ALL REGISTERS, GRILLES, DIFFUSERS WITH ARCHITECTURAL DRAWINGS, AND LIGHTING PLANS.
26.
COORDINATE THE EXACT LOCATION AND SIZE OF ALL ROOF, WALL AND SLAB PENETRATIONS WITH THE ARCHITECTURAL DRAWINGS.
27.
MOUNT THERMOSTATS WHERE INDICATED ON PLANS, 4'-0” A.F.F. UNLESS NOTED OTHERWISE.
28.
ALL EXPOSED DUCTWORK IN AREAS WITHOUT CEILINGS SHALL BE DOUBLE WALL SPIRAL DUCT.
29.
ALL PRODUCTS LISTED ARE SHOWN FOR BASIS OF DESIGN ONLY. PRODUCTS MAY BE SUPPLIED ON AN “OR EQUAL” BASIS.
30.
COORDINATE WITH ELECTRICAL CONTRACTOR FOR CONTROL VOLTAGE AND EQUIPMENT VOLTAGE, PHASE AND FREQUENCY. SUPPLY EQUIPMENT ACCORDINGLY.
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
2900 W JEFFERSON STREET JOLIET, ILLINOIS
TAG-#
EQUIPMENT TAG
REHAB + ADDITION TO JOLIET FMS 12
TAG-#
MECHANICAL NOTES:
ILLINOIS ARMY NATIONAL GUARD
MECHANICAL SYMBOLS:
ISSUED
1
03/25/14 TYPE B-3 FINAL SUBMITTAL
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
IL ARNG PN:
DO NOT SCALE DRAWINGS SHEET CONTENTS
MECHANICAL NOTES AND LEGEND
S STANDARD BRANCH SUPPLY
3/24/2014 4:42:34 PM
SHEET NO.:
ROOF SUPPLY FAN / HOOD RECT. TO ROUND TRANSITION
M-001
KEYED NOTES
6.102
6.101
DEMOLISH AND REMOVE EXISTING HVAC UNIT, DUCTWORK, PIPING, AND CONTROLS LOCATED IN EXISTING MAINTENANCE AREA ASSOCIATED WITH REMOVED HVAC UNIT. DEMOLISH AND REMOVE EXISTING ELECTRICAL CONDUIT AND WIRING ASSOCIATED WITH HVAC UNIT BACK TO SOURCE, OR NEAREST JUNCTION BOX TO STAY IN SERVICE.
6.102
DEMOLISH AND REMOVE ALL EXISTING DUCTWORK AND ASSOCIATED DUCTWORK ACCESSORIES.
6.103
DEMOLISH AND REMOVE EXISTING HOOD, ROOF EXHAUST FAN, AND ROOF CURB. PATCH ROOF AS REQUIRED PER ROOF MODIFICATIONS.
6.104
DEMOLISH AND REMOVE EXISTING ROOF EXHAUST FAN AND ROOF CURB, AND ALL DUCTWORK AND ASSOCIATED DUCTWORK ACCESSORIES. PATCH ROOF AS REQUIRED, SEE AD-101 AND A-103 FOR ROOF REPAIRS.
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
6.101
NORTH
1
MECHANICAL DEMOLITION PLAN 1/8" = 1'-0"
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
0
4
8
16
ILLINOIS ARMY NATIONAL GUARD
6.104
2900 W JEFFERSON STREET JOLIET, ILLINOIS
REHAB + ADDITION TO JOLIET FMS 12
6.103
ISSUED
1
03/25/14 TYPE B-3 FINAL SUBMITTAL
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
IL ARNG PN:
DO NOT SCALE DRAWINGS SHEET CONTENTS
MECHANICAL DEMOLITION PLAN
3/24/2014 4:42:35 PM
SHEET NO.:
M-002
GENERAL NOTES 1. 2.
3. 4. 5.
SEE PLUMBING DRAWINGS FOR NATURAL GAS PIPING LAYOUT. CONTRACTOR SHALL PROVIDE REQUIRED ANCILLARY STEEL TO ATTACH EQUIPMENT, PIPING, DUCTWORK, AND DEVICES TO BUILDING STRUCTURAL STEEL. ATTACHMENT TO THE INSULATED METAL PANEL IS NOT ALLOWED. THERMOSTATS FOR INFRARED HEATERS SHALL BE MOUNTED 48" ABOVE FINISHED FLOOR. MECHANICAL CONTRACTOR TO PROVIDE ALL CONTROL WIRING AND CONDUIT REQUIRED. CONTRACTOR SHALL COORDINATE AND BALANCE EXHAUST FANS (EF-1 & EF-2) WITH MAKE-UP AIR UNIT (MAU-1) EXHAUST FAN AND VERIFY MAU-1 RESPONDS TO EF-1 & EF-2 ACTIVATION.
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
KEYED NOTES
MAINTENANCE CHIEF/ PRODUCTION CONTROLLER 100
BREAK ROOM 102
6.202
MOUNT EF-1 ON WALL ABOVE DOOR.
6.203
12" DIA. VEHICLE EXHAUST DUCTWORK UP TO ROOF LEVEL, PROVIDE WITH MANUFACTURER'S RECOMMENDED RAIN CAP. MAINTAIN MINIMUM 10'-0" FROM ALL OUTSIDE AIR INTAKES. SEE DETAIL ON M-500.
6.204
MOUNT EF-2 TO UNDERSIDE OF MAU-1 PLATFORM USING 3x3x5/16" ANCILLARY STEEL MINIMUM.
6.205
4" DIA. COMBUSTION AIR INTAKE THRU WALL WITH VENT CAP, PER MANUFACTURER'S RECOMMENDATIONS.
6.206
4" DIA. EXHAUST FLUE, REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR VENT TERMINATIONS.
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
COMPRESSOR ROOM 103
PARTS / TOOLS STORAGE 109
MEN'S LOCKER 108 6.206
WOMEN'S LOCKER 107
6.206
T
4
T
6.205
6.205
IR-1
IR-2
6.201
6.202
1 M-300
3 EF-1
6.203
VEHICLE MAINTENANCE BAY 110
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
2 M-300
6.204
ILLINOIS ARMY NATIONAL GUARD
5
2900 W JEFFERSON STREET JOLIET, ILLINOIS
BATTERY ROOM 104
MOUNT INFRARED HEATERS AT 45 DEGREE ANGLE FACING INTO ROOM. TOP OF EQUIPMENT SHALL BE 11'-0" AFF.
REHAB + ADDITION TO JOLIET FMS 12
VEHICLE MAINTENANCE BAY 105
6.201
2 ISSUED
EF-2
1
IR-3
03/25/14 TYPE B-3 FINAL SUBMITTAL
6.206
T
1 6.203
D
3 M-301
6.205
5 M-301
C
B
A
IL ARNG PN:
NORTH
1
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
HVAC PLAN - INFRARED HEATER & VEHICLE EXHAUST
DO NOT SCALE DRAWINGS
1/8" = 1'-0" SHEET CONTENTS
MECHANICAL HVAC PLAN 0
4
8
16
3/24/2014 4:42:37 PM
SHEET NO.:
M-100
GENERAL NOTES 1. 2. 3. 6.301
5 M-301
4.
6.302
SEE PLUMBING DRAWINGS FOR NATURAL GAS PIPING LAYOUT. PROVIDE FLEX CONNECTIONS AT ALL DUCTWORK CONNECTIONS TO EQUIPMENT. MECHANICAL CONTRACTOR TO PROVIDE ALL CONTROL WIRING AND CONDUIT REQUIRED. CONTRACTOR SHALL COORDINATE AND BALANCE EXHAUST FANS (EF-1 & EF-2) WITH MAKE-UP AIR UNIT (MAU-1) EXHAUST FAN AND VERIFY MAU-1 RESPONDS TO EF-1 & EF-2 ACTIVATION.
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
AC-1
KEYED NOTES SAG-2 175 CFM
SAG-2 175 CFM
BD
SAG-2 175 CFM
EAG-2 525 CFM
6.304 T
18"x10" 20"x12" SA 8"x10" SA RA
6.305
VEHICLE MAINTENANCE BAY 105
CO/NOx 6.312
EF-3
PARTS / TOOLS STORAGE 109
EAG-2 200 CFM
BD EAG-2 170 CFM
8"ø RA
SAG-2 170 CFM
8"ø SA
SF-1 LV-5 AD-5 COMPRESSOR RM 103
8"ø RA
AD-4 LV-4
BD
MEN'S LOCKER 108
WOMEN'S LOCKER 107
4 16"x36" SA SAG-1 840 CFM
16"x26" SA
SAG-1 840 CFM
16"x16" SAG-1 SA 840 CFM
SAG-1 840 CFM
6.311
SAG-1 840 CFM
3
16"x36" SA
1 M-300
CO/NOx CONTROL PANEL AND SENSOR, MAU-1 TEMPERATURE SENSOR AND ON/OFF SWITCH
T
EAG-1 525 CFM
EAG-1 525 CFM
24"ø RA
EAG-1 525 CFM
24"ø RA
24"ø RA
EAG-1 525 CFM
6.307
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
BOD 23'-0" AFF
EAG-1 525 CFM 24"ø RA
2 M-300
EAG-1 525 CFM
6.311
EAG-1 525 CFM
EAG-1 525 CFM
FLEX CONNECTION
VEHICLE MAINTENANCE BAY 110
CO/NOx 16"x36" EXA (UNDER OA DUCT)
6.310
6.304
4" DIA. EXHAUST FLUE, REUSE EXISTING ROOF PENETRATION.
6.305
COOLING COIL, PROVIDE TRAPPED CONDENSATE DRAIN TO SANITARY DRAIN. SEE PLUMBING DRAWINGS.
6.306
PROVIDE HANGERS FROM CEILING STRUCTURE FOR SUPPLY/EXHAUST GRILLES.
6.307
ROUTE SUPPLY DUCTWORK ABOVE OVERHEAD DOOR.
6.308
PROVIDE TRAPPED CONDENSATE DRAIN TO SANITARY DRAIN. SEE PLUMBING DRAWINGS.
6.309
INSTALL COMBUSTION AIR AND EXHAUST PER MANUFACTURER'S RECOMMENDATIONS FOR SIZE AND SEPARATION DISTANCE. EXHAUST FLUE SHALL BE A MINIMUM OF 10'-0" FROM` ALL OUTSIDE AIR INTAKES. PROVIDE MANUFACTURER'S RECOMMENDED RAIN CAP/TERMINATION KIT.
6.310
PROVIDE DUCT SMOKE DETECTOR, REFER TO ELECTRICAL DRAWINGS.
6.311
MOUNT ALL CO/NOx SENSORS AT 60" ABOVE FINISHED FLOOR. MOUNT CO/NOx CONTROL PANEL AT 48" ABOVE FINISHED FLOOR. CONNECT REMOTE SENSORS TO GAS DETECTION CONTROL PANEL AND MAU-1.
6.312
MOUNT ALL CO/NOx SENSORS AT 60" ABOVE FINISHED FLOOR. MOUNT CO/NOx CONTROL PANEL AT 48" ABOVE FINISHED FLOOR. CONNECT REMOTE SENSORS TO GAS DETECTION CONTROL PANEL.
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
2 ISSUED
1
48"x36" 16"x36" OA EXA EXHAUST FLUE
PROVIDE 2" WIDE FILTER SECTION FOR DISPOSABLE FILTERS.
5
500 CFM EXA
EAG-2 70 CFM
6.303
500 CFM OA T
SAG-2 70 CFM
PROVIDE REFRIGERANT GAS/LIQUID LINES PER MANUFACTURER'S REQUIREMENTS.
EUH-1
EAG-2 80 CFM
BD BD BD
8"ø SA
8"ø RA
LV-7
BREAK ROOM 102
SAG-2 50 CFM
8"ø SA
520 CFM EXA SAG-2 200 CFM
SAG-2 165 CFM
T
BD
10"ø RA
4 M-301
SAG-2 165 CFM
10"x8" SA
BD
12"x8" SA
BD
BD
BD
BD
BD
10"ø RA
CO/NOx CONTROL PANEL 6.306
BD
12"x8" SA EAG-2 300 CFM
12"x10" SA
BATTERY ROOM 104
BD
BD
6.302
8"ø SA
HVAC-1
MAINTENANCE CHIEF/ PRODUCTION CONTROLLER 100
PROVIDE NEW CONCRETE EQUIPMENT PAD FOR CONDENSING UNIT.
2900 W JEFFERSON STREET JOLIET, ILLINOIS
BD
6.303
6.312
CO/NOx
8"ø SA
18"x10" RA
8"ø SA
28"x24" OA
6.301
REHAB + ADDITION TO JOLIET FMS 12
EAG-2 75 CFM
ILLINOIS ARMY NATIONAL GUARD
LV-3 AD-3 520 CFM OA
03/25/14 TYPE B-3 FINAL SUBMITTAL
36"x36" EXA
MAU-1
COMBUSTION AIR INLET
1 6.309
6.308
4,200 CFM OA
6.309
D
AD-1 LV-1
AD-2 LV-2
4,200 CFM EXA
C
B
A
3 M-301
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
IL ARNG PN:
NORTH
1
HVAC PLAN - AIR HANDLING 1/8" = 1'-0"
DO NOT SCALE DRAWINGS
0
4
8
16
SHEET CONTENTS
MECHANICAL HVAC PLAN
3/24/2014 4:42:41 PM
SHEET NO.:
M-101
KEYED NOTES
D
C
B
A
6.401
4" DIA. EXHAUST FLUE.
6.402
MOUNT INFRARED HEATERS SO TOP OF EQUIPMENT IS 11'-0" ABOVE FINISHED FLOOR.
6.403
4" DIA. COMBUSTION AIR INTAKE THRU WALL WITH VENT CAP PER MANUFACTURER'S RECOMMENDATIONS.
6.404
ROUTE DUCTWORK ABOVE OVERHEAD DOOR.
6.405
12" DIA. VEHICLE EXHAUST DUCTWORK, MAINTAIN MINIMUM 10'-0" FROM ALL OUTSIDE AIR INTAKES. SEE DETAIL ON M-500. EF-2 SHALL BE MOUNTED TO THE UNDERSIDE OF PLATFORM FOR MUA-1. EXHAUST DUCT FROM UNIT SHALL BE MOUNTED BELOW PLATFORM.
6.406
4" DIA. COMBUSTION AIR INLET.
6.407
PLATFORM FOR MAU-1 AT 111'-0", SEE STRUCTURAL DRAWINGS. COORDINATE PLATFORM SIZE WITH MAU-1 SELECTION.
HIGH EAVE HEIGHT 126' - 0"
12"Ø RA TO MAU-1
16"x36" SA FROM MAU-1
16"x36" SA
36"x16" SA
26"x16" SA
16"x16" SA
JB EXISTING HIGH ROOF 118' - 0"
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
EF-1 SAG-1 840 CFM
SAG-1 840 CFM
SAG-1 840 CFM
SAG-1 840 CFM
SAG-1 840 CFM
LOW EAVE HEIGHT 112' - 0"
6.403 6.402
IR-2
HVAC SECTION 1 3/16" = 1'-0"
0
A
4
8
12
B
C
D
HIGH EAVE HEIGHT 126' - 0"
3/24/2014 4:42:44 PM
6.404
ISSUED
JB EXISTING HIGH ROOF 118' - 0"
AD-1 (LV-1 BEHIND) 36"x16" EXA
AD-2 (LV-2 BEHIND)
1
03/25/14 TYPE B-3 FINAL SUBMITTAL
16"x36" SA
MAU-1
LOW EAVE HEIGHT 112' - 0"
6.403
14"x16" EXA
IR-3 6.402
16"x36" SA
6.406
6.405
EF-2
6.407 W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
8' - 8"
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
24"ø RA
ILLINOIS ARMY NATIONAL GUARD
1
REHAB + ADDITION TO JOLIET FMS 12
FIRST FLOOR 100' - 0"
2900 W JEFFERSON STREET JOLIET, ILLINOIS
6.401
16' - 6"
6.401
IR-1
6.403
IL ARNG PN:
FIRST FLOOR 100' - 0"
DO NOT SCALE DRAWINGS SHEET CONTENTS
2
MECHANICAL SECTIONS
HVAC SECTION 2 3/16" = 1'-0"
0
4
8
12
SHEET NO.:
M-300
KEYED NOTES 2
3
4
5
24"ø RA
24"ø RA
HIGH EAVE HEIGHT 126' - 0"
4" DIA. EXHAUST FLUE, REUSE EXISTING ROOF PENETRATION.
6.502
COOLING COIL, PROVIDE TRAPPED CONDENSATE DRAIN TO SANITARY DRAIN. SEE PLUMBING DRAWINGS.
6.503
12" DIA. VEHICLE EXHAUST DUCTWORK. MAINTAIN MINIMUM 10'-0" FROM ALL OUTSIDE AIR INTAKES. SEE DETAIL ON M-500.
6.504
PROVIDE REFRIGERANT GAS/LIQUID LINES TO COOLING COIL PER MANUFACTURER'S REQUIREMENTS.
6.505
PROVIDE MANUFACTURER'S RECOMMENDED RAIN CAP/TERMINATION KIT.
6.501 6.505 JB EXISTING HIGH ROOF 118' - 0"
36"x16" SA
JB EXISTING HIGH ROOF 118' - 0"
6.502
24"x24" OA AD-3
24' - 7"
MAU-1 16"x36" SA IR-1
18' - 6"
20"x12" SA
LOW EAVE HEIGHT 112' - 0"
LV-3 8"x12" SA
EF-3
LOW EAVE HEIGHT 112' - 0"
8"ø SA
EAG-2 525 CFM
SAG-2 175 CFM
SAG-2 175 CFM
HVAC SECTION 3
4
3/16" = 1'-0"
0
4
8
12
HVAC SECTION 4 3/16" = 1'-0"
0
5
4
3
2
4
8
12
1
HIGH EAVE HEIGHT 126' - 0"
EAG-1 525 CFM
6.501
EAG-1 525 CFM 24"ø RA
6.505
JB EXISTING HIGH ROOF 118' - 0"
AD-3 (LV-3 BEHIND)
24"x28" RA
HVAC-1
12"x20" SA
10"x18" SA
16"x16" SA
10"x12" SA
SAG-1 840 CFM
8"ø RA
4,200 CFM EXA IR-2
12"x8" SA
10"x8" RA
10"x12" SA
8"ø SA EAG-2 170 CFM
AC-1
IR-3
03/25/14 TYPE B-3 FINAL SUBMITTAL
LOW EAVE HEIGHT 112' - 0"
LV-2 AD-2
11' - 5"
10"x18" RA
EF-1
ISSUED
1
36"x36" EXA
6.503
8"ø SA
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
6.502
2900 W JEFFERSON STREET JOLIET, ILLINOIS
FIRST FLOOR 100' - 0"
REHAB + ADDITION TO JOLIET FMS 12
FIRST FLOOR 100' - 0"
3
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
(LV-7 BEHIND)
10"x18" RA
6.504
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
ILLINOIS ARMY NATIONAL GUARD
1
6.501
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
IL ARNG PN:
FIRST FLOOR 100' - 0"
DO NOT SCALE DRAWINGS
5
SHEET CONTENTS
HVAC SECTION 5
MECHANICAL SECTIONS
3/16" = 1'-0"
0
4
8
12
3/24/2014 4:42:47 PM
SHEET NO.:
M-301
MOUNT ANGLE ON SUPPLY FAN WALL COLLAR TO INSIDE OF WALL
M
NAMEPLATE COLOR SCHEME:
EQUIPMENT DIMENSION +8"
LETTER COLOR = EMERGENCY (WHITE) NORMAL (BLACK) NAMEPLATE COLOR = EMERGENCY (RED) NORMAL (WHITE)
WALL LOUVER #4@12EW TOP MIDSPAN
EQUIPMENT DESIGNATION (LETTERING SHALL BE 1/2" HIGH)
PAVEMENT 4"
FILTER RACK FOR 1" DISPOSABLE FILTER
AHU-1
ATTACH NAMEPLATE WITH 2 SCREWS
6"
AIR HANDLING UNIT
TYPE OF EQUIPMENT (LETTERING SHALL BE 1/4" HIGH)
8"
1
NOTE: MUST PROVIDE NAMEPLATE FOR ALL NEW AND EXISTING EQUIPMENT
1
GRANULAR BACKFILL
ATTACH TO WALL
3
6"
2x2x1/8 STRUCTURAL STEEL (3 TOTAL, ONE ON EACH SIDE OF UNIT, ONE AT BACK OF UNIT)
2
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
MECHANICAL NAMEPLATE DETAIL SCALE: NONE
EQUIPMENT PAD DETAIL SCALE: NONE
2x2x1/8 STRUCTURAL STEEL (ONE ON EACH SIDE OF UNIT)
WALL PROPELLER FAN MOUNTING DETAIL SCALE: NONE
ESCUTCHEON (WHERE EXPOSED)
WATERPROOF MASTIC 360° AROUND SLEEVE, COLOR TO MATCH WALL
DUCTWORK / PIPE
WALL SLEEVE
DUCT INSULATION AND JACKETING
BUILDING WALL 12" DIA. GALV. ALUM EXHAUST DUCT
1-1/2" x 1-1/2" x 1/4" ANGLE FOR DUCT SUPPORT RIGID ROUND RUNOUT
PROVIDE FLEXIBLE ROUND RUNOUT DOWN TO DIFFUSER 5' MAX.
PROVIDE ANCILLARY STEEL TO BUILDING STRUCTURAL STEEL
DIFFUSER CEILING
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
4
FLASHING
WALL FRAME: 1-1/2" x 1-1/2" x 1/4"
7
DIFFUSER RUN-OUT DETAIL (ROUND DUCT) SCALE: NONE
BRACING: 1-1/2" x 1-1/2" x 3/16"
VIBRATION ISOLATORS RAIL LOAD RANGE 300 LBS.
FLEXIBLE CONNECTION
L DAMPER PLATE
SCALE: NONE
1
03/25/14 TYPE B-3 FINAL SUBMITTAL
FAN
45 o
OPPOSED BLADE DAMPER AS PER SPECIFICATIONS 25' LENGTH OF 6" HIGH TEMP TUBING
W 12 "M IN.
PROVIDE CONCEALED DAMPER REGULATOR METAL FASTENERS: OMARK INSUL-PINS,DURO DYNE FASTENERS OR GRIP NAILS. (GRIP NAILS SHALL BE INSTALLED BY "GRIP NAIL AIR HAMMER" OR BY "AUTOMATIC FASTENER EQUIP")
RECTANGLE TO ROUND TRANSITION
DUCT / PIPE PENETRATION THROUGH EXTERIOR WALL
ISSUED
NOTE: L = %%130W (4" MIN.)
AIR FLOW
TIGHTLY PACKED WITH FOAMED - IN PLACE INSULATION
MANUFACTURER'S RECOMMENDED WEATHER PROOF AND BIRD PROOF EXHAUST TERMINATION
2900 W JEFFERSON STREET JOLIET, ILLINOIS
TIGHTLY CAULK WITH SILICONE SEALANT FOR MIN. 2" EACH END
REHAB + ADDITION TO JOLIET FMS 12
EXTERIOR WALL
ILLINOIS ARMY NATIONAL GUARD
WALL PROPELLER FAN, WITH WALL COLLAR, OSHA WIRE GUARD, AND MOTORIZED DAMPER
1
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
MOTOR
STAINLESS STEEL TAILPIPE ADAPTER WITH HEAT RESISTANT HANDLES
NOTE: ALL SUPPLY AIR DUCTS SHALL BE WRAPPED EXTERNALLY AS PER SPECIFICATIONS
MOUNT AT HEIGHT AS SHOWN ON DRAWINGS
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
MOUNTED PUSH BUTTON ON / OFF CONTROL
IL ARNG PN:
DO NOT SCALE DRAWINGS
5
BRANCH DUCT TAKE-OFF & DAMPER DETAIL SCALE: NONE
6
CARBON MONOXIDE EXHAUST SYSTEM DETAIL SCALE: NONE
SHEET CONTENTS
MECHANICAL DETAILS
3/24/2014 4:42:47 PM
SHEET NO.:
M-500
GENERAL NOTES 1. 2.
CO/NOx
MECHANICAL CONTRACTOR TO PROVIDE ALL CONTROL WIRING AND CONDUIT REQUIRED. CONTRACTOR SHALL COORDINATE AND BALANCE EXHAUST FANS (EF-1 & EF-2) WITH MAKE-UP AIR UNIT (MAU-1) EXHAUST FAN AND VERIFY MAU-1 RESPONDS TO EF-1 & EF-2 ACTIVATION.
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
(SEE PLANS FOR SENSOR LOCATIONS) CO/NOx CO CONTROL PANEL
TO MAU-1 CONTROL PANEL
OA
HEAT EXCHANGER BYPASS
M
T EF
OUTSIDE AIR
NO
NO
M
FILTER
M
M
VFD
AD-2 (PROVIDED SEPARATELY)
NC
AD-1 (PROVIDED SEPARATELY)
NO
EXHAUST AIR
AD-2 (PROVIDED SEPARATELY)
EF
TO MAU-1 CONTROL PANEL
EF-1
M EF-1 STARTER
FILTER
M EF
TO MAU-1 CONTROL PANEL
AIR TO AIR ENERGY RECOVERY HEAT EXCHANGER
T
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
SF
EF-2
M
RA
SA
EF-2 STARTER T
T
SUPPLY AIR
Gas
DX (PROVIDED SEPARATELY SHIPPED LOOSE)
TO MAU-1 CONTROL PANEL
M
FILTER
M
SD
SF
RETURN AIR
(PROVIDED SEPARATELY)
OCCUPIED SWITCH
Gas MODULATING GAS HEAT
T
ZONE TEMPERATURE SENSOR AND SETPOINT
OUTSIDE AIR TEMPERATURE SENSOR
MAU-1 CONTROLS DIAGRAM
2
SCALE: NONE
HVAC-1 CONTROLS DIAGRAM SCALE: NONE
SEQUENCE OF OPERATION: MAU-1
3/24/2014 4:42:48 PM
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
RUN CONDITIONS:
HVAC-1 •
HVAC-1 SHALL BE CONTROLLED BY PROGRAMMABLE CONTROLLER WITH ROOM TEMPERATURE SENSOR AND 7DAY OCCUPANCY SCHEDULER WITH OCCUPANCY OVERRIDE.
•
UNIT SHALL RUN WHEN BUILDING IS OCUPPIED. OCCUPANCY SHALL BE DETERMINED BY MANUAL OCCUPIED/UNOCCUPIED SWITH AND CO/NOx SENSOR.
•
WHEN OCCUPIED, THE FAN SHALL RUN CONTINUOUSLY AND THE HEATING AND COOLING SHALL BE CYCLED TO MAINTAIN ROOM SETPOINT.
•
SUPPLY FAN SHALL RUN CONTINUOUSLY WHILE IN OCCUPIED MODE OR WHILE CO/NOx SENSOR IS IN ALARM, UNLESS SHUTDOWN BY UNIT SAFETIES.
•
CONDENSING UNIT (AC-1) SHALL CYCLE UPON CALL FROM HVAC-1.
•
EXHAUST FAN SHALL RUN CONTINUOUSLY WHILE SUPPLY FAN IS ACTIVE, UNLESS SHUTDOWN BY UNIT SAFETIES.
•
DURING UNOCCUPIED MODE, THE FAN CYCLE BASED ON SATISFYING THE ROOM TEMPERATURE SETPOINT.
•
SUPPLY FAN SHALL BE INTERLOCKED WITH AD-1. AD-1 SHALL OPEN WHEN UNIT IS ENABLED. SUPPLY FAN SHALL START WHEN AD-1 IS PROVEN OPEN.
•
AD-3 SHALL OPEN WHEN BUILDING IN IS OCCUPIED MODE AND CLOSED WHEN BUILDING IS IN UNOCCUPIED MODE.
•
EXHAUST FAN SHALL BE INTERLOCKED WITH AD-2. AD-2 SHALL OPEN WHEN UNIT IS ENABLED. EXHAUST FAN SHALL START WHEN AD-2 IS PROVEN OPEN.
•
EXHAUST FAN SHALL BE CONTROLLED BY VARIABLE FREQUENCY DRIVE (VFD) (SUPPLIED BY EQUIPMENT MANUFACTURER). EXHAUST FAN SHALL OPERATE AT SCHEDULED VALUE. VFD SHALL REDUCE FAN SPEED BY THE AMMOUNT REQUIRED TO OFFSET THE EXHAUST RATE OF ONE OR TWO EXHAUST FANS RUNNING, AS DETERMINED BY THE TEST AND BALANCE CONTRACTOR. THE EXHAUST FANS EF-1 & EF-2 SHALL PROVIDE DRY CONTACTS TO MAU-1 CONTROLLER TO DETERMINE NUMBER OF FANS RUNNING.
VENTILATION: •
•
HEATING SHALL BE ENABLED WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 60°F UNLESS SHUTDOWN BY UNIT SAFETIES.
•
UNIT SHALL MODULATE BURNER TO MAINTAIN BUILDING SETPOINT OF 65°F (USER ADJ.)
ENERGY RECOVERY:
•
•
EXHAUST FAN (EF-3) SHALL RUN CONTINUOUSLY. ISSUED
EF-1 & EF-2 • •
ENERGY RECOVERY SHALL BE ENABLED WHEN BURNER IS ENABLED. THE UNIT SHALL BYPASS THE ENERGY RECOVERY WHEN BURNER IS DISABLED.
AD-1 & AD-2 •
SEE MAU-1 INTERLOCKS
SF-1 & AD-4 / AD-5 •
SUPPLY FAN SF-1 SHALL BE CONTROLLED BY LOCAL THERMOSTAT. ON RISE IN TEMPERATURE ABOVE SETPOINT, THE UNIT SHALL BE ENABLED.
•
SUPPLY FAN SHALL OPEN AUTOMATIC DAMPERS (AD-4 & AD-5) PRIOR TO FAN STARTING.
•
AD-4 AND AD-5 SHALL BE OPEN WHEN SF-1 IS ENERGIZED AND CLOSE WHEN SF-1 IS DE-ENERGIZED.
WHEN THE UNIT IS SHUTDOWN, THE OUTDOOR AIR DAMPER (AD-1) ON THE SUPPLY AND (AD-2) ON THE EXHAUST SHALL CLOSE.
UNIT SHALL SHUTDOWN ON UNIT SAFETY ALARMS AND GENERATE A VISUAL AND AUDIABLE WARNING LIGHT. UNIT SHALL DE-ENERGIZE SUPPLY AND EXHAUST FAN ON DETECTION OF SMOKE BY DUCT DETECTOR.
EUH-1 •
INDICATION: UNIT SHALL HAVE LOCAL INDICATION FOR: • SUPPLY FAN RUNNING • EXHAUST FAN RUNNING • BURNER ENABLED • SMOKE DETECTED • UNIT FAULT / SAFETY SHUTDOWN
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: SKU CHECKED BY: JLH NGB PN.:
IL ARNG PN:
ENERGY RECOVERY UNIT SHALL MODULATE THE ENERGY RECOVERY DAMPERS TO PREVENT FROST BUILD-UP ON THE HEAT EXCHANGER.
ALARMS: • •
03/25/14 TYPE B-3 FINAL SUBMITTAL
EXHAUST FANS FOR THE VEHICLE EXHAUST SHALL BE CONTROLLED BY LOCAL START/STOP CONTROL. PROVIDE DRY CONTACTS TO MAU-1 THAT CLOSE WHEN EXHAUST FAN IS RUNNING.
UNIT SHUTDOWN: •
1
UNIT SHALL SUPPLY 100% OUTSIDE AIR WHEN SUPPLY FAN IS ENABLED.
HEATING:
•
EF-3
2900 W JEFFERSON STREET JOLIET, ILLINOIS
T
ILLINOIS ARMY NATIONAL GUARD
1
T
REHAB + ADDITION TO JOLIET FMS 12
ZONE TEMPERATURE SENSOR AND SETPOINT
ELECTRICAL UNIT HEATER SHALL BE CONTROLLED BY LOCAL THERMOSTAT AND SHALL MAINTAIN A SETPOINT OF 55°F (USER ADJ.).
DO NOT SCALE DRAWINGS SHEET CONTENTS
MECHANICAL SEQUENCE OF OPERATION
IR-1, IR-2, & IR-3 •
INFRARED HEATER SHALL BE CONTROLLED BY LOCAL THERMOSTAT AND SHALL MAINTAIN A SETPOINT OF 55°F (USER ADJ.).
SHEET NO.:
M-600
EXHAUST FAN SCHEDULE S.P. (IN. W.C.)
RPM
EF-1
CARMON CMW-13
1,420
3.0
EF-2
CARMON CMW-13
1,420
3.0
EF-3
-
520
0.75
ELECTRICAL
LOCATION
TYPE
DRIVE
WEIGHT
REMARKS
208 / 3 / 60
MAINTENANCE BAY
CENTRIFUGAL REEL MOUNTED
DIRECT
~300 lbs
PROVIDE PREMIUM EFFICIENCY MOTOR, WITH STARTER AND DISCONNECT
208 / 3 / 60
MAINTENANCE BAY
CENTRIFUGAL REEL MOUNTED
DIRECT
~300 lbs
PROVIDE PREMIUM EFFICIENCY MOTOR, WITH STARTER AND DISCONNECT
115 / 1 / 60
MAINTENANCE BAY
~75 lbs
12" DIAMETER. PROVIDE WITH MOTOR STARTER AND DISCONNECT.
H.P.
VOLTS/PH./HZ.
1796
1.5
1796
1.5
1320
1/3
INLINE DUCT
BELT
CARBON MONOXIDE EXHAUST UNIT SCHEDULE VMB CARMON UNITS WITH EF-1 & EF-2 TUBING STORAGE REEL SHALL BE WALL MOUNTED, MOTOR-OPERATED WITH 25' 6" DIAMETER TYPE CLX HIGH TEMPERATURE FLEXIBLE TUBING. EXHAUST FAN SHALL BE SINGLE INLET, SINGLE WIDTH, BACKWARD INCLINED, DIRECT DRIVE, CENTRIFUGAL TYPE. AIR FLOW SHALL BE 1,420 CFM AT 3" E.S.P. FAN ELECTRICAL DATA: 208 VOLTS, 3 PHASE, AND 1.5 HP MOTOR. PROVIDE MANUAL STARTER WITH OVERLOAD PROTECTION, AND STOP/START PUSH BUTTON CONTROL PANEL. THE CARBON MONOXIDE EXHAUST UNIT SHALL BE EQUAL TO A CAR-MON TSR-P32. THE EXHAUST FAN SHALL BE EQUAL TO A CAR-MON CMW-13.
DESCRIPTION
MOUNTING
TYPE
MATERIAL
NOMINAL SIZE
VOLUME (CFM)
LV-1
LOUVER
WALL
INTAKE
ALUM
72" x 36"
4,200
500
0.05
8.8 SQ/FT MIN FREE AREA SEE NOTE 2
LV-2
LOUVER
WALL
EXHAUST
ALUM
36" x 36"
4,200
1,000
0.175
4.3 SQ/FT MIN FREE AREA SEE NOTE 2
LV-3
LOUVER
WALL
INTAKE
ALUM
24" x 24"
520
350
0.05
1.5 SQ/FT MIN FREE AREA SEE NOTE 1
LV-4
LOUVER
WALL
EXHAUST
ALUM
24" x 24"
500
325
0.05
1.5 SQ/FT MIN FREE AREA SEE NOTE 1
LV-5
LOUVER
WALL
INTAKE
ALUM
24" x 24"
500
325
0.05
1.5 SQ/FT MIN FREE AREA SEE NOTE 1
LV-7
LOUVER
WALL
EXHAUST
ALUM
16" x 16"
520
850
0.175
0.6 SQ/FT MIN FREE AREA SEE NOTE 2
CFM
S.P. (IN. W.C.)
RPM
SF-1
-
476
0.25
860
ELECTRICAL H.P.
VOLTS / Hz /
.07
115 / 1 / 60
LOCATION
TYPE
DRIVE
REMARKS
COMPRESS RM
WALL FAN
DIRECT
PROVIDE WITH MOTOR GUARD, 120V AUTOMATIC DAMPER, MOTOR STARTER AND DISCONNECT
GAS FIRED HVAC UNIT (NAT. GAS HTG, DX COOLING) SUPPLY FAN MARK
HVAC-1
LOCATION
VEH. MAINT. BAY 110
HEATING SECTION
CFM
ESP
HP
MBH INPUT
1345
1
3/4
52/80
COOLING COIL
MBH BURNER ID FAN OUTPUT MOTOR MOTOR 41/64
MBH (SENS)
EAT
50
35.7
80
-
0.02
VOLTS
MBH TOTAL
WEIGHT
REMARKS
115
~250 lbs (with coiling coil)
1
520 CFM OA
MARK
LOCATION
MAU-1
VEH. MAINT. BAY, 110
CFM
ESP (in/wg)
HP
CFM
ESP (in/wg)
4,200
0.75
5
4,200
1.0
HEATING SECTION
HEAT EXCH. HP
EFF PD (%) (in/wg)
5
66%
REHEAT COIL
HP
MBH
EAT
MBH
EAT
.
320 OUTPUT
0
N/A
N/A
0.75
VOLTS PHASE 208
3
BASIS OF DESIGN MAKE / MODEL
WEIGHT
REMARKS
TRANE CSAA-4
~5,000 lbs
SEE NOTES
3/24/2014 5:11:58 PM
C:\Users\scott.ulrey\Documents\REVIT Projects\Joiliet\3288700-121973.01-MP-Central_scott.ulrey.rvt
NOTES: 1. PROVIDE WITH 10:1 TURNDOWN MODULATING GAS CONTROL. 2. PROVIDE WITH INTEGRATED PLATE AND FRAME HEAT EXCHANGER WITH BYPASS DAMPERS. 3. PROVIDE EXHAUST FAN WITH VARIABLE FREQUENCY DRIVE (VFD). 4. PROVIDE SUPPLY FAN WITH MAGNETIC MOTOR STARTER. 5. PROVIDE PARALLEL PLATE ENERGY RECOVERY HEAT EXCHANGER WITH AIR BYPASS DAMPERS. 6. INTERLOCK UNIT WITH SUPPLY AND EXHAUST DAMPERS AD-1 AND AD-2. 7. SEE SPECIFICATIONS AND SEQUENCE OF OPERATION FOR CONTROL REQUIREMENTS. 8. OTHER MANUFACTURER'S INCLUDE: DAIKIN MCQUAY - MODEL CAH, MAMMOTH, VENTROL.
MARK
LOCATION
MBH
EUH-1
VOLTS
CFM HP
COMPRESSOR ROOM
--
300
KW -
--
PHASE
MANUFACTURER MODEL NO.
REMARKS
-
PROVIDE WITH REMOTE THERMOSTAT
208 2
1
AUTOMATIC DAMPER SCHEDULE (AD) MARK
QUANTITY
LOCATION
CAPACITY CFM
NOMINAL SIZE (W x H)
DESCRIPTION
NOMINAL BURNER TUBE LENGTH
WEIGHT
REMARKS
120/1
20 FT
~175 lbs
PROVIDE 3" SIDEWALL VENT KIT, 45 DEG ANGLE MOUNTING BRACKET
50.0
120/1
30 FT
~175 lbs
PROVIDE 3" SIDEWALL VENT KIT, 45 DEG ANGLE MOUNTING BRACKET
50.0
120/1
30 FT
~175 lbs
PROVIDE 3" SIDEWALL VENT KIT, 45 DEG ANGLE MOUNTING BRACKET
DESCRIPTION
IR-1
TUBE INFRARED UNIT HEATER STRAIGHT TUBE 20 FT LONG
65.0
50.0
IR-2
TUBE INFRARED UNIT HEATER STRAIGHT TUBE 30 FT LONG
65.0
IR-3
TUBE INFRARED UNIT HEATER STRAIGHT TUBE 30 FT LONG
65.0
MARK
DESCRIPTION
PANEL SIZE
NECK
CFM RANGE
FRAME
STYLE
FINISH
MATERIAL
DAMPER
MAX NC
REMARKS
EAG-1
EXHAUST REGISTER
18"x12"
SEE PLAN
525
LAY-IN
LOUVER 0 DEG FIXED
WHITE
STEEL
OPPOSED BLADE
30
-
EAG-2
EXHAUST GRILLE
24"x24"
SEE PLAN
70 - 525
LAY-IN
-
WHITE
STEEL
-
30
-
SAG-1
SUPPLY REGISTER
24"x10"
SEE PLAN
840
CUT-IN
DBL DEFLECT
WHITE
STEEL
OPPOSED BLADE
30
-
SAG-2
SUPPLY DIFFUSER
24"x24"
SEE PLAN
70 - 200
CUT-IN
-
WHITE
STEEL
-
30
-
CONDENSING UNIT (CU)
ELECTRIC UNIT HEATERS (EUH) RPM
HEAT HIGH STG LOW STG VOLTS/ MBH MBH PHASE
MARK
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
MAKE-UP AIR UNIT (MAU-1) INDIRECT FIRED WITH ENERGY RECOVERY EXHAUST
© Copyright 2014 This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
PHASE
NOTES: 1. PROVIDE WITH MOTOR STARTER AND DISCONNECT. 2. PROVIDE WITH SEPARATE 24"x24" DIRECT EXPANSION COOLING COIL, MAKE TO MATCH HVAC-1. 3. REFER TO SPECIFICATIONS AND SEQUENCE OF OPERATION FOR UNIT CONTROLS.
SUPPLY
OPERATOR P-E (VOLTS)
Mead & Hunt, Inc. 6501 Watts Road Madison, WI 53719 phone: 608-273-6380 meadhunt.com
RADIANT TUBE HEATER SCHEDULE
SUPPLY FAN SCHEDULE BASIS OF DESIGN MAKE / MODEL
REMARKS
NOTES: 1. PROVIDE WITH INSECT SCREEN. 2. PROVIDE WITH BIRD SCREEN.
OTHER SUITABLE MANUFACTURERS: NEDERMAN INC. MONOXIVENT
SYMBOL
VELOCITY MAX. APD. (FT/MIN) (in/wg)
MARK
REMARKS
AD-1
1
VEH. MAINT. BAY 110
4,200
72" x 36"
PARALLEL BLADE
120 V
-
AD-2
1
VEH. MAINT. BAY 110
4,200
36" x 36"
PARALLEL BLADE
120 V
-
AD-3
1
VEH. MAINT. BAY 105
520
24" x 24"
PARALLEL BLADE
120 V
-
AD-4
1
COMPRESSOR RM 103
500
24" x 24"
PARALLEL BLADE
120 V
-
AD-5
1
COMPRESSOR RM 103
500
24" x 24"
PARALLEL BLADE
120 V
-
MARK
TONS
KILOWATTS
AC-1
4
-
AMBIENT TEMP.
90
SUCTION TEMP. -
VOLTS PHASE 200-230 3
MAKE MODEL
SEER
REMARKS
-
13.75
R-410 REFRIGERANT
2900 W JEFFERSON STREET JOLIET, ILLINOIS
CFM
REHAB + ADDITION TO JOLIET FMS 12
BASIS OF DESIGN MAKE / MODEL
ILLINOIS ARMY NATIONAL GUARD
SYMBOL
LOUVER SCHEDULE
ISSUED
1
NOTES: 1. COORDINATE SELECTED WITH HVAC-1
03/25/14 TYPE B-3 FINAL SUBMITTAL
GAS DETECTION (CONOX) MARK
DESCRIPTION
LOCATION
# OF SENSORS
CO ALARM LIMIT (PPM)
NOx ALARM LIMIT (PPM)
ELECTRICAL
MANUFACTURER MODEL NO.
CONOX-1
GAS DETECTION CONTROL PANEL
ROOM 105
3
25
1
120 / 1 / 60
SEE NOTES
CONOX-2
GAS DETECTION CONTROL PANEL
W90FYQ-10-D-0009-9E01 17090578 M&H NO.: 3288700-121973.01 DATE: 03/25/14 DESIGNED BY: WSK DRAWN BY: WSK CHECKED BY: JLH NGB PN.:
ROOM 110
4
25
1
120 / 1 / 60
NOTES: 1.MANUFACTURER/MODEL BASIS OF DESIGN: BRASCH MODEL GSS-NCM-1 2.OTHER ACCEPTABLE MANUFACTURER'S INCLUDE: MINE SAFETY APPLIANCES (MSA) AND MEASUREMENT AND CONTROL INSTRUMENTS (MCI). 3.PROVIDE DRY ALARM CONTACT RELAYS RATED AT 125 VAC, 5 AMP RESISTIVE, 250 VA INDUCTIVE, 0.125 HP. 4.PROVIDE INTERNAL ALARM WITH AUDIBLE ALARM.
SEE NOTES
IL ARNG PN:
DO NOT SCALE DRAWINGS SHEET CONTENTS
MECHANICAL SCHEDULES
SHEET NO.:
M-601