AC/DC Converter LS03-16BxxSS Series
FEATURES
3W, AC/DC converter
z Ultra wide input voltage range: 90 - 528VAC/100 - 745VDC z AC and DC dual-use (input from the same terminal) z Operating temperature range: -40℃ to +85℃ z Compact size, high power density z Isolation voltage: 4KVAC z Used in such as electrical, instrumentation industries z Output short circuit, over-current protection z Meets UL60950, EN60950, FCC part 15 standards
CB RoHS
(Pending)
LS03-16BxxSS series ---- a compact size power converter offered by Mornsun. It features ultra wide input voltage, taking both DC and AC input voltage, low power consumption, high efficiency, high reliability, safer isolation. Meets UL60950, EN60950, FCC part 15 standards. Widely used in industrial control and instrumentation, such as electric power for demanding volume, the requirement of wide input voltage range, the need to meet UL / CE certification and EMC less demanding applications. EMC application circuit must be added if the products need to be applied to EMC harsh environment.
Selection Guide Part No.
Output Power
Nominal Output Voltage and Current(Vo/Io)
LS03-16B03SS
1.65W
3.3V/500mA
63
2200
LS03-16B05SS
2.5W
5V/500mA
67
1100
9V/333mA
70
680
12V/250mA
76
680
15V/200mA
76
560
24V/125mA
76
470
Certification
UL/CE/CB (Pending)
LS03-16B09SS LS03-16B12SS LS03-16B15SS
3W
LS03-16B24SS
Efficiency (230VAC, %/Typ.)
Max. Capacitive Load (μF)
Input Specifications Item Input Voltage Range
Operating Conditions
Min.
Typ.
Max.
Unit
AC input
90
--
528
VAC
DC input
100
--
745
VDC
47
--
63
Hz
115VAC
--
--
0.12
230VAC
--
--
0.06
480 VAC
--
--
0.04
115VAC
--
9
--
230VAC
--
15
--
27
--
Input Frequency Input Current
Inrush Current
480 VAC
A
0.25mA RMS typ. 230VAC/50Hz
Leakage current
2.0A, slow fusing, necessary
Recommended External Input Fuse Hot Plug
Unavailable
Output Specifications Item Output Voltage Accuracy
Operating Conditions
Min.
Typ.
Max.
LS03-16B03SS
--
±6
--
Others
--
±5
--
LS03-16B03SS
--
±2.5
--
Others
--
±1.5
--
±2.5
--
Unit
%
Line Regulation
Full load
Load Regulation
10% - 100% load
--
Ripple & Noise*
20MHz bandwidth (peak-peak value)
--
--
180
mV
--
±0.15
--
%/℃
Temperature Coefficient
2016.11.02-A/0
Page 1 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter LS03-16BxxSS Series Stand-by Power Consumption
230VAC Input
--
--
0.3
528VAC Input
--
--
0.5
W
Short Circuit Protection
Hiccup, continuous, self-recovery
Over-current Protection
150 - 300%Io self-recovery
Min. Load Hold-up Time
230VAC input
10
--
--
%
--
40
--
ms
Note: *Parallel line test method is adopted to test the ripple and noise, please see AC-DC Converter Application Notes for specific operation methods.
General Specifications Item
Operating Conditions
Min.
Typ.
Max.
Unit
Isolation Voltage
Test time: 1min
4000
--
--
VAC
-40
--
+85
-40
--
+105
--
--
85
Input-output
Work in the power drop curve range
Operating Temperature Storage Temperature Storage Humidity
360 ± 10℃; time: 3 - 5s
Manual-welding
Switching Frequency Power Derating
%RH
260 ± 5℃; time: 5 - 10s
Wave-soldering
Welding Temperature
℃
--
70
--
+55℃ to +85℃
2.0
--
--
-40℃ to -20℃
3.0
--
--
kHz %/℃
Safety Standard
IEC60950/EN60950/UL60950
Safety Certification
IEC60950/EN60950/UL609509 (Pending) CLASS I I
Safety Class MIL-HDBK-217F@25℃
MTBF
≥ 300,000 h
Physical Specifications Dimension
44.50*13.00*24.00mm
Weight
8g (Typ.)
Cooling Method
Free air convection
EMC Specifications CISPR22/EN55022/FCC part 15 CLASS A (See Fig. 1 for typical application circuit)
CE
CISPR22/EN55022/FCC part 15 CLASS B (See Fig. 2 for recommended circuit)
EMI*
CISPR22/EN55022/FCC part 15 CLASS A (See Fig. 1 for typical application circuit)
RE
CISPR22/EN55022/FCC part 15 CLASS B (See Fig. 2 for recommended circuit)
ESD
IEC/EN 61000-4-2
RS
IEC/EN61000-4-3 10V/m (See Fig. 2 for recommended circuit)
perf. Criteria A
IEC/EN 61000-4-4
±2KV
perf. Criteria B
IEC/EN 61000-4-4
±4KV (See Fig. 2 for recommended circuit)
perf. Criteria B
IEC/EN 61000-4-5
line to line ±1KV (See Fig. 1 for typical application circuit)
perf. Criteria B
EFT
EMS
Contact ±4KV
Perf. Criteria B
(See Fig. 1 for typical application circuit)
Surge
IEC/EN 61000-4-5
CS
IEC/EN61000-4-6 3 Vr.m.s (See Fig. 2 for recommended circuit)
perf. Criteria A
Voltage dips, short interruptions and voltage variations immunity
IEC/EN61000-4-11
perf. Criteria B
line to line ±2KV/ line to ground ±4KV (See Fig. 2 for recommended circuit)
perf. Criteria B
0%,70% (See Fig. 2 for recommended circuit)
*This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
2016.11.02-A/0
Page 2 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter LS03-16BxxSS Series
O u tp u t P o w e r P e rc e n ta g e (% )
O u t p u t P o w e r P e rc e n t a g e (% )
Product Characteristic Curve Te m p e r a t u re D e r a ti n g C u r v e 10 0 80 70 60
In p u t Vo lt a g e :9 0 - 1 6 5 VA C
40
10 0-2 30V D C
20 -40
-20
55
70
85
Te m p e r a t u re D e r a t in g C u r v e 10 0 80 70 60
In p u t v o l t a g e : 1 6 5 -5 2 8 VA C 23 0-7 45V D C
40 20
-40
O u tp u t P o w e r P e rc e n ta g e ( % )
A m b ie n t Te m p e ra t u re (℃ )
55
70
A m b i e n t Te m p e r a t u r e ( ℃)
85
In p u t V o lt a g e D e ra tin g C u r v e 100 80 60 A m b i e n t t e m p e ra t u r e : 2 5 ℃
40 20
110 155
90 100
480 675 I n p u t V o lt a g e
528 745
VA C VDC
Note: ①When input 90 - 110VAC / 480 - 528VAC/100 - 155VDC/675-745VDC, it need to be voltage derated on basis of temperature derating; Please refer to typical application circuit; ②If the product is working at full load at ambient temperature of -40℃ to -20℃, Please refer to typical application circuit; ③This product is suitable for use in natural air cooling environments, if in a closed environment, please contact our company’s FAE.
Design Reference 1. Typical application circuit FUSE
R3
NTC
L2
A C (L)
+ V (c a p )
C1+
M OV1
C2
①
A C (L) R1
+
R2
+ Vo
A C -D C
C3
+
L1
C4
TVS C 5 RL
+
- V (c a p ) - Vo AC (N)
AC (N)
CY1
Fig. 1
Note:① is Pi filter circuit Part No. LS03-16B03SS LS03-16B05SS LS03-16B09SS LS03-16B12SS LS03-16B15SS LS03-16B24SS
MOV1
C1/C2 (necessary)
10μF/450V
S14K550
(-25℃ to +85℃)
22μF/450V
(-40℃ to +85℃)
R1/R2 L2
(nece ssary)
C3 (necessary)
L1 (nece ssary)
C4
(necessary)
C5
CY1
FUSE (necessary)
NTC
R3
(neces
(neces
sary)
sary)
270μF/16V 1.2 mH
3MΩ
(Solid Capacitor)
4.7μH
100μF/ 35V
0.1μF/ 50V
470pF/ 500VAC
2.0A
5D-9
470μF/35V
7.5Ω /1W
TVS SMBJ7.0A SMBJ7.0A SMBJ12A SMBJ20A SMBJ20A SMBJ30A
Note: 1. C1/C2: filtering electrolytic capacitor (which is required), recommended the same brand, the same model, the same batch of electrolytic capacitors; 2. R1/R2: max operation voltage of R1/R2 should be above 450V. While using chip resistors, it is recommended to use several chip resistors in series to meet operation voltage; 3. R3(which is required): winding resistance; 4. C3 and C4 are output filer capacitors (which is required), they are recommended to be high frequency and low impedance electrolytic capacitors. Capacitance and rated ripple current of capacitors refer to the datasheets provided by the manufactures. Voltage derating of capacitors should be 80% or above. C5 is a ceramic capacitor, which is used to filter high frequency noise. C3, C4 and L1 form a pi-type filter circuit. Current of L1 and L2 refer to the datasheets provided by the manufactures, current derating should be 80% or above. TVS is a recommended component to protect post-circuits (If converter fails); 5. When working at full load at ambient temperature of -40 ℃ to -20 ℃ , following circuit parameters values are recommended: C1/C2(necessary): 33μF/450V; R1/R2(necessary): 1 MΩ; R3(necessary): 12Ω/2W; NTC(necessary): 10D-10.
2016.11.02-A/0
Page 3 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter LS03-16BxxSS Series 2. EMC solution-recommended circuit A C (L)
L2
M OV 2
FU S E
R3 CY2
M OV 1
LC M
CX CY3
NTC
A C (L) + C1
R1
C 2+
R2
+ V (c a p )
A C -D C - V (c a p ) AC (N)
A C (N ) M OV 3
+ Vo
① C3 +
L1
C 4 TVS C 5 RL +
- Vo
CY1
Fig. 2 Element model MOV1 MOV2、MOV3 CY2、CY3 CX LCM L2 NTC R3 FUSE
Recommended value S14K550 S07K300 470pF/500VAC 0.1μF/530VAC 4.5mH 1.2mH 10D-10 12Ω/2W 2.0A, slow fusing, necessary
Note: The recommended value of other components refers to typical application circuit.
3. For more information Please find the application note on www.mornsun-power.com
Dimensions and Recommended Layout
2016.11.02-A/0
Page 4 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter LS03-16BxxSS Series
Notes: 1. Packing information please refer to Product Packing Information which can be downloaded from www.mornsun-power.com. Packing bag number: 58220032; 2. If the product is not operated within the required load range, the product performance cannot be guaranteed to comply with all parameters in the datasheet; 3. This part is open frame, at least 10mm safety distance between the primary and secondary external components of the module is needed to meet the safety requirement; 4. Unless otherwise specified, parameters in this datasheet were measured under the conditions of Ta=25℃, humidity