All Product Catalogue
Chilled Water System Solution
AP-MSM-08
Chilled Water System Solution McQuay Offers ; Comprehensive Solution ........................ 2 In Air Conditioning Needs Features Of McQuay Chilled Water Products ................... 3 Smart Manager ................................................................. 4 McQuay Air Cooled Mini Chiller Series ............................. 7 Tandem Compressors Air-Cooled Mini Chiller ................ 12
CONTENTS:
Inverter Mini Chiller ......................................................... 13 McQuay Chilled Water Fan Coil Units ..............................15 NIM & NIM PC Networking Control System .....................16 McQuay Chilled Water Fan Coil Units Range ..................17
Specifications Mini Chiller Specifications ............................................... S1 Chilled Water Fan Coil Unit Specifications ..................... S6
GLOBAL DISTRIBUTION NETWORK
Cramlington Minneapolis Faribault Owatonna Stauntan
Auburn
SuZhou
Cecchina
Wuhan ShenZhen
Mexico City Sungai Buloh Cikarang
Manufacturing Plant
Americas • USA • Puerto Rico • Mexico • Paraguay • Uruguay • Guadaloupe •
Oceania • Australia • New Zealand •
Middle East & Africa • Jordan • Lebanon • Oman • Qatar • Saudi Arabia • Bahrain • Morocco • Iraq • U.A.E. • • Mauritius • South Africa • Kenya • Madagascar • Ghana • Nigeria • Tanzania •
Europe • England • Greece • Hungary • Italy • Norway • Poland • Portugal • Russia • Spain • • Belgium • Tunisia • Croatia • Cyprus • Lithuania • Malta • Slovenia • Ukraine • • Turkey • Finland • Czech Republic • Romania •
Asia • Cambodia • China • Hong Kong • Indonesia • Maldives • • Malaysia • Singapore • Thailand • Vietnam • Pakistan •
Product Overview
R22
MAC 020/025/030 C/CR
MAC 040/050/060 C/CR
R407C
M4AC 020/025/030 C/CR
M4AC 040/050/060 C/CR
R410A
M5AC 020/025 CR
R410A Inverter
M5ACV 030 CR
M5ACV 055/075 CR
Cooling Capacity (kW)
5.0 - 8.1
11.7 - 15.5
Heating Capacity (kW)
5.9 - 9.5
12.6 - 17.5
MWM 007/010/015/020 GW MWM 301W
MCK 020/025/030/040/050 AW
Cooling Capacity (kW)
2.34-5.28
6.62-10.80
Heating Capacity (kW)
3.02-6.74
8.40-12.90
MCM 007/010/015 CBW
MCM 020/025/030/040/050 DW
Cooling Capacity (kW)
1.90-3.08
5.19-13.19
Heating Capacity (kW)
2.28-4.19
6.45-15.10
Model Range
Electrical Supply
50Hz 60Hz
Model Range
Electrical Supply
50Hz 60Hz
Model Range
Electrical Supply
50Hz 60Hz
MAC 080/100/120/150/210 C/CR M4AC 080/100/120/150/210 C/CR M5AC 030/040/050/055 CR M5ACV 100/135/210 CR 21.6 - 58.6
7.3 - 14.9
26.4 - 61.5
9.8 - 18.0
MCK 020/025/030/040/050 AWH
MCK 015/020/025 BW
MCK 010/015/020 CW
3.81-5.16
3.66-5.27
2.34-4.25
10.55-13.77
4.69-6.15
3.22-5.42
MCC 010/015/020/025/028 CW MCC 030/038/040/050/060 CW
MCW 200/300/400/600 C/H MCW 800/1000/1200 C/H
MDB 075/100/125/150 BW
2.9-15.8
2.1-4.6
5.6-32.2
4.7-9.6
INTRODUCTION
McQuay Offers ; Chilled Water System McQuay is committed to offer you with the better solution in your air conditioning needs. In the new series of chilled water products, McQuay is not just offering you with wide range of chilled water air conditioning equipments, but a better solution from selecting the equipments, designing the water piping systems to provide easy control of the complete chilled water system. This is facilitated by the user friendly computer selection programs and remote monitoring of the operation of complete system through the Smart Manager. The series of chilled water product has incorporated the technology of advanced communicating controls, microprocessor controlled chillers with a wide range and variety of fan coil unit that offers total flexibility.
2
McQuay Chilled Water Series Of Products FEATURES
Year Round Comfort
Quality, Innovative and Compact Design
Can be used in variety of climates with systems that are available in two versions, cooling only and heat
McQuay chiller is equipped with reliable and quality
pump.
components.
Reliable and More Efficient
Multiple Temperature Zone Control
The refrigerant of the system is confined to within
The operation of the fan coil units can be managed
the chiller itself and therefore no refrigerant is
independently by zones according to similar air
circulating throughout the building. This will be no
conditioning comfort needs.
risk of refrigerant leakages in building or risk of poor oil return that will damage compressor caused by poor installation. Multiple compressors in McQuay chiller series offers stages capacity control that will offer better efficiency.
Long Piping Applications McQuay chilled water system avoids the limitation of piping lengths and bends that exist in Direct Expansion refrigerant system. The chiller can be installed far away from the fan coil units, thus offering flexibility and creativity in the installation.
3
Controller By adopting the McQuay chilled water system, the comfort in residential and light commercial buildings such as offices, hospital, restaurant, hotel and shopping complex can be controlled and managed from just one point, that is through the Smart Manager. The Smart Manager is acting as a center to manage the operation of both the chilled water fan coil units and the chillers. Besides allowing the user to have customized control for each connected unit, the Smart Manager is also able to manage the overall system operating mode of all units based on the air conditioning system load demand of the building.
F E AT U R E S Supported Up To 50 Chillers & 120 Fan Coil Units Through the versatile Smart Manager controller, the operation of each equipments in the McQuay chilled water system connected through the chiller Bus and McQuay own proprietary NIM BUS can be managed and controlled.
Chiller Network BUS
Fan Coil Network BUS
4
Display Up To 46 Types Of Chiller Fault/Alarm And 6 Types Of FCU Fault/Alarm
(Ch 0) Alarm 1
Comp 1 overload
Whenever a fault occurred in either the chiller or fan coil unit, a signal will be sent to Smart Manager and an alarm message will appear on the LCD, showing type of alarm, alarm occurred time, date and unit.
01/01/00
12.00am
This will greatly ease the troubleshooting process and thus reduce the valuable time of service technicians. As soon as the fault is being solved, the alarm will automatically dissolve from the LCD.
Priority Settings Depending on the application requirement, the Smart Manager offers the flexibility to allow user to set the priority on the operation of fan coil unit and chiller in a complete McQuay chilled water product system. If priority is set to Fan Coil Unit, the chiller will be forced to OFF if all fan coil units are OFF. If Chiller Priority is being set, all fan coil units will be OFF if chillers are OFF.
Threshold Value Setting If the priority setting is being preset to fan coil unit, the operating mode of the complete McQuay chilled water system can be synchronized to operate under one same mode. This is achievable through the unique feature called “Threshold Value Setting” Smart Manager can command chiller operating mode to switch from current operating mode if the threshold value is meet. Example, In a network of 10 fan coil units that is currently operating in COOL mode and a threshold of 60% was set for COOL mode and threshold of 50% was set for HEAT mode. Should 6 of the fan coil units are requesting for HEAT mode then the threshold for HEAT is crossed. Signal will be sent by Smart Manager to chiller BUS to switch the operating mode of all chillers to HEAT mode. Requirement of users will be met.
• Heat Treshold • Chiller to operate at Heat Mode
0
1
2
3
4
5
6
7
8
9
10
Chiller to operate at Cool Mode
• Cool Treshold • 5
Energy Saving Programmable Timer The operation of the chiller and each fan coil unit can be preset to operate and to stop at different
MCC
time schedule and at different day of a week. Taking consideration of the fact that certain rooms in a building will be empty at certain period of the day, setting timer to On and to Off the operation of units in those areas will greatly reduce the energy cost of
MCK MCM 2
the building. At the same time, Smart Manager allows setting up to
MCM 1 MWM
five sets of 7 days programmable operating schedules
Unit
(2 On/Off timer per day) for each fan coil unit.
MCC MCK MCM2 MCM1 MWM 8.00 am
9.00 am
10.00 11.00 12.00 am am am
1.00 pm
2.00 pm
3.00 pm
4.00 pm
5.00 6.00 pm pm
7.00 pm
Time
HOLIDAY SETTINGS
Holiday Setting
Holiday 1 Holiday 2 Holiday 3 Holiday 4 Holiday 5
While designing the Smart Manager, the practical aspects of equipment application were always the key points to be considered. Thus resulting in the creation of “Holiday Setting” feature. In this feature, users are allowed to set up to 10 holiday timers with each timer can last for duration
Set Holiday 1 Month Day Duration
of 99 days.
: 1 : 1 : Disable
During the duration of Holiday Timer set earlier, all fan coil units and chiller will automatically be turned Off.
6
Memory Backup (EEPROM), Alarm Memory for Chiller and FCU
Key Parameter Display For easy serviceability and maintenance, Smart
When there is power failure occurs during
Manager is able to display the key parameter such
operation, Smart Manager will load the last state
as defrost and compressor discharge sensor
memory from EEPROM after power On reset.
temperature, water in/out temperature, status of compressor On/Off, Cool/Heat mode water in
Besides, extra memory space inside the Smart
temperature, etc. Thus, it reduces the cumbersome
Manager will allow user to view the previous alarm
of requiring the service technicians to physically go
records even though its have been dissolved. This useful
information
will
benefit
the
to
service
site
of
chiller
installation
to
do
the
troubleshooting process.
technician to view the history of maintenance record done to the unit.
Accumulative Compressor Run Time
Password Protection For Advanced Parameter Settings (Chiller)
User can also check the compressor run time of
A McQuay chilled water product system with key
chiller in Smart Manager. It will provide a guideline
parameters that were set by personal to optimize
as well as posting a reminder for requirement of
operating conditions will need to be protected
routine system service.
against any unauthorized disturbance or changes. The built in “Password Settings” feature will prevent the losing of key parameter settings in the Smart Manager.
Multiple Temperature Zone Control
Low Power Mode (Chiller + FCU)
The operation of the fan coil units can be managed independently by zones according to similar air conditioning comfort needs.
Smart Manager will turn into low power mode during electricity power breakdown. It will operate based on the built in backup battery and only one timer
Real Time Clock (RTC)
and interrupt is active. CPU operation is Off and no display on LCD as well for energy saving purpose.
RTC will always appear at the summary pages and the user is able to set the time and date.
7
McQuay Air Cooled Mini Chiller Series McQuay offering you the range of air cooled chiller that is suitable for many applications from residential to commercial.
The McQuay chiller is incorporated with the basic necessary components such as circulating water pump, expansion tank, compact brazed plate heat exchanger, differential pressure switch and the microprocessor controller and wired control panel.
In addition, the selection of the McQuay chiller could not be more easy than the user friendly yet versatile selection softwares for chiller as well as connecting piping. In short, Smart Manager Chilled Water Product Range offers you the better solution to your chilled water product needs.
8
PRODUCT RANGE
Model : MAC 020/025/030 C/CR M4AC 020/025/030 C/CR M5AC 020/025 CR M5ACV 030 CR Capacity : Cooling : 5 kW to 8.1 kW Heating : 5.9 kW to 9.5 kW Refrigerant : R22, R407C, R410A
Model : MAC 040/050/060 C/CR M4AC 040/050/060 C/CR M5ACV 055/075 CR Capacity : Cooling : 11.7 kW to 15.5 kW Heating : 12.6 kW to 17.5 kW Refrigerant : R22, R407C, R410A
Model : MAC 080/100/120/150 C/CR M4AC 080/100/120/150 C/CR M5ACV 100/135/210 CR Capacity : Cooling : 21.6 kW to 58.6 kW Heating : 26.4 kW to 61.5 kW Refrigerant : R22, R407C, R410A
Model : M5AC 030/040/050/055 CR Capacity : Cooling : 7.3 kW to 14.9 kW Heating: 9.8 kW to 18.0 kW Refrigerant : R410A
9
FEATURES
Compactness
Brazed Plate Heat Exchanger
The MAC/M4AC 020~030 C/CR is such a compact
The heat exchanger is made of AISI 316 stainless
unit that it can be integrated perfectly with any
steel plates closely arranged and brazed together to
architectural design, making it an ideal choice for
maximize possible heat exchange efficiency.
house, offices, restaurant and shop.
Scroll Compressor Scroll Compressors are used for the units to offer a quieter and more reliable performance over a wide operating temperature range. (Except MAC/M4AC 020 C/CR which uses rotary compressor). For MAC/M4AC 030, 040, 050, 060, 080, 100, 120,
Microprocessor Control
150 CR, phase protector is provided to prevent the compressor from rotating in the wrong directions.
McQuay chillers are equipped with microprocessor controller that will control and regulate the operation of the unit.
Fully Equipped Chillers
Besides, the controller that contains the well developed algorithm will provide protection to the
McQuay chiller is fully integrated and equipped with
chiller by accurately sensing the key temperatures
key hydronic components such as expansion tank,
in both the water and refrigerant circuit. Should
water tank, brazed plate heat exchanger and water
there be any abnormal reading received by
circulating pump. The all in one concept will ease
controller, an alarm signal will be sent to chiller
the job of installer.
panel, followed by protection action plans such as to stop the operation of compressor, condenser fan motor or circulating water pump.
Partial Loading Models MAC/M4AC 080~150 C/CR has been designed with two separate refrigerant circuits, i.e. it has two compressors. By doing so, the unit has part loading capabilities, i.e. 0-50-100% of rated capacity. This will improve the reliability and energy efficiency of the unit, especially during low loading operations.
10
Availability Of Connection To Boiler
Anti-Freeze Protection The chiller unit has several anti-freeze protection features:
The microprocessor controller has a built in control
1. Built-in heater in BPHE
algorithms that allowed the chiller to be connected to the boiler. By adding a boiler to the system, it can
The BPHE has a strip heater around it
either work as the sole heating water source in a
prevent water freezing inside.
to
2. Anti-Freeze sensor
Cooling only unit or it can act as the booster heat
BPHE can avoid the frosting as the
source to the Heat Pump chiller.
anti-
freeze sensor will send the signal to cut out the compressor if the water
Safety Protection
temperature
becomes too cold. 3. Water pressure differential switch
The safety protections provided for the McQuay
This protection feature will ensure
chiller are:
there is
water flow in pipings when the chiller is in
• High & Low Pressure Switches
operation. Otherwise, the
• Anti-Freeze Protection Sensor
compressor will
cut out immediately.
• Discharge Temperature Sensor • Over Pressure Relief Valve
Sequencing Control
• Water Pressure Differential Switch • Anti-Freeze Heater on BPHE • Compressor Water Pump &
For MAC/M4AC 080~150 C/CR, both compressors
Fan Motor Overload Protector
will cut in and cut out depending on their accumulative operating time. This sequencing control feature will ensure no single compressor is overload in operation as well as to ensure longer reliability of compressors.
Modular Installation Chiller Bus
The mini chillers are available for modular connection. A network of up to 50 chillers in a system is possible. Control on the operation of the chillers will be done through the microprocessor controller. The external water piping connection can be made either from the left or right side of the unit.
Water In
Water Out
Up to 50 Chillers
11
FEATURES
Easy Installation And Maintenance
Brazed Plate Heat Exchanger
As a chiller, all hydronic components are assembled
The heat exchanger is made of AISI 316 stainless
and wiring jobs on chillers are done and tested in the
steel plates closely arranged and brazed together to
factory. Installation of additional component on site
ensure high heat exchange efficiency.
can be eliminated.
Chiller Control Panel
In addition, unit operation is user friendly and maintenance is simple. By opening the front panel,
The chiller panel controller is designed to control the
you
chiller operation. This device allows the user to have
would
have
immediate
assess
to
all
components.
customized control for each connected unit. Each chiller will have a chiller control panel that
Factory Precharged Refrigerant
comes as a standard accessory. At the same time, the chiller control panel is able to be installed
Each heat exchanger in the chiller is brazed and
remotely through the cable up to a distance of 100
tested against leakages through dried air at 30 bars.
meters. Example, the chiller panel can be installed in
After that, another process to vacuum the system
a centralized plant control room for the building.
before accurately charged with refrigerant to ensure optimum performance. Thus, it saves the hustles of
The chiller control
field charging by installers.
panel has been designed taking
Anti Corrosion Heat Exchanger
into consideration of the user friendly
The condenser heat exchanger of chiller, heat pump
and yet versatile
specification, utilize the special anti corrosion gold
control features.
aluminum fin. Features:
R407C & R410A
•
Whole system configuration.
•
Unique parameter settings.
In line with Montreal Protocol, the Smart Manager is
•
Operation status display.
available in R407C & R410A refrigerant.
•
Tracing fault record (offer quick troubleshooting
* R407C & R410A is having Zero Ozone Depletion
solutions).
Potential (O.D.P). However it is gas whose Global
•
The display is shown in an 8-lines graphical LCD
Warming Potential (GWP) is similiar to the high
display. There are 8 dedicated keys available in
GWP for R22.
the panel.
12
•
Menu selection.
•
Navigation on the screen.
•
Modification of the selected value.
Air - Cooled Mini Chiller This new line of innovative air cooled chiller by McQuay was designed with one purpose in mind, which is to offer user with cost and energy saving for users.
Better Performance •
Usage of higher efficient R410A rotary compressors in tandem configuration
•
Tight tolerances between moving parts resulting in high compressor volumetric efficiency
•
Minimize mechanical losses
•
Minimize gas flow losses and turbulence
•
Optimize compressor oil return
Capacity Step Control • 3 steps compressor loading (0%-40%-60%-100%) for M5AC 040 CR & M5AC 050 CR • 2 steps compressor loading (0%-50%-100%) for M5AC 030 CR & M5AC 055 CR
Sequential Control • Both compressors will cut in cut out depending on water temperature. This is possibly improving the compressor life cycle as well as the compressor reliability.
Elimination of Water Tank •
Combining the Tandem Compressors technology with the algorithm of the microprocessor control, water tank can be eliminated in most instances.
Choices of Single Phase and 3 Phase Power Supply Connection •
Usage of single phase power supply compressors and circulating water pump.
•
13
Offers flexibility to field installation.
The new series of Inverter Mini Chillers are specially designed / developed to achieve better system energy saving as well as towards perfect control during part load condition.
True Dual Circuits BPHE Apply sophisticated technology of true dual circuit BPHE. The true dual BPHE puts the secondary circuit (water)
in
contact
with
2
primary
circuits
(refrigerant). So even if one primary circuit is shut off, each secondary channel is still in contact with a primary channel. These advantages have made the product the natural choice for flexible chillers, climate control applications and high-precision systems food cooling cabinets in supermarkets. Ref.1
Ref.2
Ref.1
Ref.2
Built In Fan Speed
Ref.1
Fan speed is now controlled by the built in algorithm, resulting in cost saving since installation of external FSC (Fan Speed Controller) can be exempted. It is regulated at 100%, 70% and 50% based on the ambient and outdoor condensing water
water
water
temperature.
water
Inverter Compressor
Safety Protection
Inverter compressor is programmed to run at the
• High & Low Pressure Switches
optimum speed, which is regulated by the input
• Anti-Freeze Protection Sensor
frequency as it can varies according to the heat
• Discharge Temperature Sensor
load requirement.
• Over Pressure Relief Valve • Water Pressure Differential Switch
Water In
• Anti-Freeze Heater on BPHE • Compressor, Water Pump Overload Protector Primary Circuit 1
Primary Circuit 2
Anti Corrosion Heat Exchanger Gold Aluminum fin is offered as the standard material of the condenser heat exchanger of this series of chiller.
Water Out
14
Room Temperature
Modular Installation
Precise & Stable Temperature Control
Set Temperature
A network up to 50 chillers in a system is possible. Control on the operation of the chillers will be done
Room Temperature
through the microprocessor controller. The external
Time
Fast Cooling
left or right side of the unit.
Set Temperature
Inverter System
water piping connection can be made either from the Time
Conventional System
Advantages of inverter compressor applications are: LESS START & STOP Frequency regulated compressor resulting in lesser in the sense of start and stop of compressor, which is greatly reduce the energy consumption. FAST COOLING / HEATING Unlike the other conventional systems, inverter
Chiller Panel Comes As The Standard Controller
compressor has the ability to produce faster cooling / heating capacity at the frequency higher than the dominant capacity frequency. BETTER COMPRESSOR RELIABILITY Reliability of inverter compressor is always better since there is lesser ON/OFF of the system especially during the low load condition. LOW STARTING SURGE Inverter compressor require lower starting torque and thus, resulting in lower starting current.
Compatible With Smart Manager
Elimination Of Water Tank Inverter system provide constant water temperature band, or much lesser water temperature fluctuation. With this, water tank of the mini chiller system can be eliminated.
15
McQuay Chilled Water Fan Coil Units
To complement the new innovative Smart Manager range of air cooled chillers, McQuay is offering an extensive range of chilled water fan coil units that will meet most of indoor application requirements covering residential, light commercial and commercial. The aesthetically attractive decorative fan coil units such as Wall Mounted models, Ceiling Cassette and Ceiling Convertible is compact and ergonomic, the ranges can blend in easily to any interior designs whether it is residential houses, office, restaurant or shops.
In addition, the McQuay chilled water fan coil units are designed with easy installation and easy servicing in mind. The fan coil units also include the microprocessor controller that has built in algorithm to control the operation of the fan coil unit as well as to provide protection to the unit.
16
NIM Networking Control System (optional)
For multiple fan coil unit installation in an office, a centralised controlled operation can be achieved through the McQuay proprietary NIM networking system. Network Interface Module (NIM) is a networking system which enables communication among McQuay air conditioners. With the NIM, all your air conditioning systems can be controlled with just a single controller giving you boundless benefits: BENEFITS • Ultimate convenience. No more individually controlling air conditioning units • Quick and easy zone control from the master control unit • Better control of air conditioning systems operating conditions NIM utilizes master-slave type system whereby the master node will issue commands to each of the slave nodes. For NIM PC only NIM NIM
NIM
NIM
NIM
NIM
NIM
NIM
NIM
NIM PC for Global Control Hub With NIM PC, a personal computer will act as a centralised unit for both controlling and monitoring of all the air conditioning units in the HydroNIM network. For controlling, settings can be set from the PC and send out to the system for execution. While for monitoring, there is a graphical user interface for displaying the status of each unit. The NIM PC provides a Global Control Hub that offers control for better system management: • Easy to operate full graphical user interface.
• Real time monitoring of online units.
• Control units globally, as a group,
• Error diagnostic and alerting features for all units. • Data logging and printing ability.
or as individual units. • Configure a super master unit.
• Database to store unit location.
• Support up to 42 On/Off timers per week.
• Login protected by password. 17
McQuay Chilled Water Fan Coil Units Range
Wall Mounted Range Features : • • • • • • • • • • • • •
MWM 07/10/15/20/25 GW
Slim and compact Wide capacity range Wide air flow range Incorporated with NanoGuard. Able to communicate with the versatile NIM for fan coil units networking Light weight Detachable and washable air intake grille Microprocessor control Self diagnosis features Automatic air swing Wireless Control as standard Mode selection, fan speed, 24 hours real timers Optional wired controller
STANDARD
MWM 301 W
G17 Wireless Controller
OPTIONAL
SLM Wired Controller
AC-5300 Wireless Controller
Ceiling Cassette Range Features : • 3 range of ceiling cassette to be chosen from. - MCK-CW - 570mm (w) x 570mm (l) - MCK-BW - 650mm (w) x 650mm (l) - MCK-AW - 820mm (w) x 820mm (I) • Aesthetically attractive and slim front panel • 4 way air discharge to provide better air distribution to room • Automatic air swing • 4 pipes system is available for model MCK020/025/030/040/050AWH • Easy servicing and maintenance • Built in high pressure head drain pump - Ability to pump up condensate water to 700mm high • Built in water float switch to protect the unit from problems of condensate water overflow • Microprocessor control • Able to communicate with the versatile NIM for fan coil units networking • Self diagnosis feature • Wireless Control as standard - Mode selection, fan speed, 24 hours real timers • Optional wired controller
MCK 010/015/020 CW
MCK 015/020/025 BW
2 Pipes System: MCK 020/025/030/040/050 AW
STANDARD
OPTIONAL
G17 Wireless Controller
Netware III Wired Controller
4 Pipes System: MCK 020/025/030/040/050 AWH
18
Ceiling Convertible Range Features : • Ceiling Convertible feature offers flexibility on installation - Installation method of under ceiling or floor standing • 2 way air discharge ensure better air distribution - Horizontal air throw and bottom air throw • Automatic Air swing • Aesthetically attractive with round profile outlook fits into to any indoor architectural • Strong air flow volume and strong air throw distance makes it a perfect choice for light commercial such as restaurant and shop • Microprocessor control • Able to communicate with the versatile NIM for fan coil units networking • Self diagnosis feature • Wireless Control as standard - Mode selection, fan speed, 24 hours real timers • Optional wired controller
MCM 007/010/015 CBW
MCM 020/025/040/050 DW
STANDARD
MCM 15/20/25 EW
G17 Wireless Controller
OPTIONAL
SLM Wired Controller
AC-5300 Wireless Controller
Ceiling Concealed Range Features : • Wide capacity range • 4 speed fan motor offers flexibility for installation to suit application - Each speed will offer different external static pressure and air flow • High External Static Pressure is available up to 18mm • Extra secondary drain pan to provide protection against condensate water leaking • Availability of various optional duct accessories specially designed to fit to MCC-CW range • Microprocessor control • Filter adaptor kit of 1 inch is available as optional accessory • Able to communicate with the versatile NIM for fan coil units networking • Self diagnosis feature • Wired Control as standard - Mode selection, fan speed selection
MCC 010/015/020/025/030/040/050/060 CW
STANDARD
OPTIONAL
SLM Wired Controller
Netware III Wired Controller
MCC 028/038 CW
19
Ceiling Concealed Range Features : • • • • •
Wide capacity range Multiple rooms can be cooled by just 1 unit of MCW Simple design with easy serviceability feature Extremely low height of unit – 251mm for complete range Water piping connection can be easily converted from one side to the other Fan motor assembly is not cased, allowing free return or back return or bottom return with optional return plenum Availability of optional extended drain to receive the condensate water dripping from the water piping connection Availability of 4 pipes MCW series Other optional accessory available: - Wired thermostat - Choice of external static pressure (ESP) - Four types of ESP are available: 0Pa, 30Pa, 60Pa, 80Pa. - PTC (Positive Temperature Coefficient) electric heater - 2 way & 3 way valves
• • • •
2 Pipes System: MCW 200/300/400/600/800/1000/1200 C 4 Pipes System: MCW 200/300/400/600/800/1000/1200 CH
Ducted Blower Range Features :
• These units are design with high air flow and high external static pressure, enables adequate distribution of air to the desired space • Multiple rooms can be cooled by just 1 unit of MDB • Simple design with easy serviceability feature • The robust unit is designed with durability and reliability in mind • MDB125/150BW is using the belt driven fan motor and blower fan thus it offers flexibility for upgrading should higher air flow is required • MDB150BW is designed to cater for either horizontal air discharge or vertical air discharge
MDB 075/100/125/150 BW
Return Bracket Assembly come with Adaptor
Adaptor
(MCC 010CW - 1 outlet; MCC 015~020CW - 2 outlets)
Discharge and Return
Return Grille Assembly come with Adaptor
Y-Joint
Supply Grille Assembly come with Adaptor
(Front View)
(Side View)
(Front View)
Optional Accessories (MCC010CW~MCC025CW) 20
AC8000C Series
AC80000A
AC80000C NIM PC
Smart Manager
OR RS485
FCU
More FCUs
AC8000C
LCD Panel
FCU
AC8000C
LCD Panel
FCU
AC8000C
LCD Panel
A new developed thermostat series, AC8000 is now available to be ordered as Chilled Water Fan Coil unit controller, inclusive of AC8000A and AC8000C. Its adopt micro-computer technology and is designed for the easier of installation. AC8000A practises the most simple and conventional installation method where it consists of a wired controller and a power board. Both of its are attached together while being installed. Same with AC8000A, AC8000C also consist of a wired controller and a power board, but the power board is attached to the fan coil unit while the wired controller will be installed away from it. Moreover AC8000C has the networking capability, with compatibility to the Network Interface Module (NIM); better control over whole operating system can be achieved as it offers quick and easy zone control from the master operating unit.
Features : • Four Operating Modes COOL/ FAN/ HEAT/ AUTO • Variable Indoor Fan Speed Selection High/ Medium/ Low/ Auto • Selectable Function Cooling Only, Cooling and Heating (2 pipes), Cooling and Heating (4 pipes) • LCD display • LED Indication of Power Supply • 7 days Programmable Timer • Real Timer • Selectable Room Temperature/ Set Temperature Display • Temperature Control Precision up to +/- 1°C • High, Low Voltage Separated for Safety • Last State Memory Backup • Networking Capability (Only Applicable for AC8000C) AC8000C is compatible with Smart Manager and NIM PC. By using a RS485 cable, it can easily form a NIM bus as described in schematic diagram.
21
Mini Chiller Specifications MAC020C - MAC060C (Cooling Only, R22) MAC020C
MAC025C
MAC030C
MAC040C
MAC050C
MAC060C
Btu/h
18000
23500
27500
40000
50000
53000
W
5275
6887
8059
11723
14654
15533
W
2669
2730
3491
4470
5245
6361
MODEL NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE
V/Ph/Hz
220-240 / 1 / 50
380-415 / 3 / 50
REFRIGERANT TYPE
R22
CONTROL
UNIT DIMENSION
CAPILLARY TUBE HEIGHT
mm/in
800 / 31.5
1410 / 55.5
WIDTH
mm/in
1160 / 45.7
1160 / 45.7
DEPTH
mm/in
460 / 18.1
460 / 18.1
UNIT WEIGHT
kg/lb
116 / 256
123 / 271
128 / 282
195 / 430
196 / 432
203 / 448
SOUND PRESSURE LEVEL
dBA
57
57
58
60
60
61
l/s/m3/hr
0.25 / 0.9
0.33 / 1.2
0.39 / 1.4
0.56 / 2.0
0.70 / 2.5
0.74 / 2.7
0.25 / 0.9
0.33 / 1.2
0.39 / 1.4
0.56 / 2.0
0.70 / 2.5
0.74 / 2.7
8.4
9.7
8.8
9.2
6.8
6.6
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT PUMP
PIPING
TANK
MAX. WATER OPER. PRESSURE
kPa/psi
WATER FLOW RATE
l/s/m3/hr
INSTALLATION PIPE CONNECITON HEAD
1000 / 145
mm/in m
25.4 / 1
MATERIAL
CAST IRON / STAINLESS STEEL
CAPACITY/VOLUME
22 / 0.78
L/ft3
40 / 1.41
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 100%
MAC020CR - MAC060CR (Heatpump, R22) MAC020CR
MAC025CR
MAC030CR
MAC040CR
MAC050CR
MAC060CR
Btu/h
18000
23000
27500
40000
46000
53000
W
5275
6740
8060
11723
13481
15533
Btu/h
22000
25000
31500
43000
52000
59000
W
6448
7327
9232
12602
15240
17292
COOLING
W
2599
2779
3541
4560
5046
6551
HEATING
W
2770
2614
3561
4629
4999
6247
MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE
V/Ph/Hz
220-240 / 1 / 50
380-415 / 3 / 50
REFRIGERANT TYPE
R22
CONTROL UNIT DIMENSION
CAPILLARY TUBE HEIGHT
mm/in
800 / 31.5
1410 / 55.5
WIDTH
mm/in
1160 / 45.7
1160 / 45.7
DEPTH
mm/in
460 / 18.1
460 / 18.1
UNIT WEIGHT
kg/lb
116 / 256
123 / 271
128 / 282
195 / 430
196 / 432
203 / 448
SOUND PRESSURE LEVEL
dBA
57
57
58
60
60
61
COOLING
l/s/m3/hr
0.25 / 0.9
0.32 / 1.2
0.39 / 1.4
0.56 / 2.0
0.64 / 2.3
0.74 / 2.7
HEATING
l/s/m3/hr
0.31 / 1.1
0.35 / 1.3
0.44 / 1.6
0.60 / 2.2
0.73 / 2.6
0.83 / 3.0
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT MAX. WATER OPER. PRESSURE PUMP
WATER FLOW RATE
TANK
HEAD
1000 / 145
l/s/m3/hr
0.25 / 0.9
0.32 / 1.2
0.39 / 1.4
0.56 / 2.0
0.64 / 2.3
0.74 / 2.7
HEATING
l/s/m3/hr
0.31 / 1.1
0.35 / 1.3
0.44 / 1.6
0.60 / 2.2
0.73 / 2.6
0.83 / 3.0
INSTALLATION PIPE CONNECITON PIPING
kPa/psi
COOLING
mm/in
25.4 / 1
COOLING
m
8.4
9.9
8.8
9.2
8.2
6.6
HEATING
m
6.9
9.4
7.9
8.1
6.0
4.0
MATERIAL CAPACITY/VOLUME
CAST IRON / STAINLESS STEEL L/ft3
22 / 0.78
40 / 1.41
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 100%
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE. b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
S1
Mini Chiller Specifications M4AC020C - M4AC060C (Cooling Only, R407C) M4AC020C
M4AC025C
M4AC030C
M4AC040C
M4AC050C
M4AC060C
Btu/h
21000
23000
27000
40000
50000
52000
W
6154
6740
7912
11723
14654
15240
W
2617
2949
3679
4910
5955
6859
MODEL NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE
V/Ph/Hz
220-240 / 1 / 50
380-415 / 3 / 50
REFRIGERANT TYPE
R407C
CONTROL
UNIT DIMENSION
CAPILLARY TUBE HEIGHT
mm/in
800 / 31.5
1410 / 55.5
WIDTH
mm/in
1160 / 45.7
1160 / 45.7
DEPTH
mm/in
460 / 18.1
460 / 18.1
UNIT WEIGHT
kg/lb
116 / 256
123 / 271
128 / 282
195 / 430
196 / 432
203 / 448
SOUND PRESSURE LEVEL
dBA
57
57
58
60
60
61
l/s/m3/hr
0.29 / 1.0
0.32 / 1.2
0.38 / 1.4
0.56 / 2.0
0.70 / 2.5
0.73 / 2.6
0.29 / 1.0
0.32 / 1.2
0.38 / 1.4
0.56 / 2.0
0.70 / 2.5
0.73 / 2.6
7.3
9.9
8.9
9.2
6.8
7.0
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT PUMP
PIPING
TANK
MAX. WATER OPER. PRESSURE
kPa/psi
WATER FLOW RATE
l/s/m3/hr
INSTALLATION PIPE CONNECITON HEAD
1000 / 145
mm/in m
25.4 / 1
MATERIAL
CAST IRON / STAINLESS STEEL
CAPACITY/VOLUME
22 / 0.78
L/ft3
40 / 1.41
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 100%
M4AC020CR - M4AC060CR (Heatpump, R407C) M4AC020CR
M4AC025CR
M4AC030CR
M4AC040CR
M4AC050CR
M4AC060CR
Btu/h
17000
22000
25000
40000
46000
51000
W
4982
6448
7327
11723
13481
14947
Btu/h
20000
25500
32500
45000
51000
60000
W
5861
7474
9525
13188
14947
17584
COOLING
W
2597
3076
3804
4820
5446
6507
HEATING
W
2685
2745
4004
4994
5647
6268
MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE
V/Ph/Hz
220-240 / 1 / 50
380-415 / 3 / 50
REFRIGERANT TYPE
R407C
CONTROL UNIT DIMENSION
CAPILLARY TUBE HEIGHT
mm/in
800 / 31.5
1410 / 55.5
WIDTH
mm/in
1160 / 45.7
1160 / 45.7
DEPTH
mm/in
128 / 282
195 / 430
460 / 18.1 196 / 432
203 / 448
UNIT WEIGHT
kg/lb
116 / 256
460 / 18.1 123 / 271
SOUND PRESSURE LEVEL
dBA
57
57
58
60
60
61
COOLING
l/s/m3/hr
0.24 / 0.9
0.31 / 1.1
0.35 / 1.3
0.56 / 2.0
0.64 / 2.3
0.71 / 2.6
HEATING
l/s/m3/hr
0.28 / 1.0
0.36 / 1.3
0.46 / 1.7
0.63 / 2.3
0.71 / 2.6
0.84 / 3.0
l/s/m3/hr l/s/m3/hr mm/in
0.25 / 0.9
0.32 / 1.2
0.35 / 1.3
0.56 / 2.0
0.64 / 2.3
0.71 / 2.6
0.31 / 1.1
0.35 / 1.3
0.46 / 1.7
0.63 / 2.3
0.71 / 2.6
0.84 / 3.0
COOLING
m
8.7
10.1
9.4
9.2
8.2
7.5
HEATING
m
7.7
9.3
7.6
7.5
6.4
3.5
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT MAX. WATER OPER. PRESSURE PUMP
WATER FLOW RATE
COOLING HEATING
INSTALLATION PIPE CONNECITON PIPING
TANK
HEAD MATERIAL CAPACITY/VOLUME
kPa / psi
1000 / 145
25.4 / 1
CAST IRON / STAINLESS STEEL L/ft3
CAST IRON / STAINLESS STEEL
22 / 0.78
CAST IRON / STAINLESS STEEL 40 / 1.41
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 100%
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE. b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
S2
Mini Chiller Specifications MAC080C - MAC150C (Cooling Only, R22) MAC080C
MAC100C
MAC120C
MAC150C
Btu/h
78000
93000
116000
138000
W
22860
27257
33998
40445
W
8667
10175
11005
13779
MODEL NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE
V/Ph/Hz
380-415 / 3 / 50
REFRIGERANT TYPE
R22
CONTROL
TXV
UNIT DIMENSION
HEIGHT
mm/in
WIDTH
mm/in
1500 / 59.1
DEPTH
mm/in
900 / 35.4
1245 / 49.0 1800 / 70.9 1150 / 45.3
UNIT WEIGHT
kg/lb
340 / 750
350 / 772
460 / 1014
540 / 1190
SOUND PRESSURE LEVEL
dBA
65
66
67
69
l/s/m3/hr
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
26.0
23.5
25.0
23.0
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT PUMP
PIPING
TANK
MAX. WATER OPER. PRESSURE
kPa/psi
WATER FLOW RATE
l/s/m3/hr
INSTALLATION PIPE CONNECITON HEAD
1000 / 145
mm/in m
42 / 1 1/4"
MATERIAL
NA
CAPACITY/VOLUME
NA
L/ft3
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 50 - 100%
MAC080CR - MAC150CR (Heatpump, R22) MAC080CR
MAC100CR
MAC120CR
MAC150CR
Btu/h
77000
94000
113000
138000
W
22567
27549
33118
40445
Btu/h
90000
110000
120000
132000
MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER
W
26376
32239
35169
38686
COOLING
W
9577
11255
11714
13881
HEATING
W
9329
10759
11948
14572
POWER SOURCE
V/Ph/Hz
380-415 / 3 / 50
REFRIGERANT TYPE
R22
CONTROL
CAPILLARY TUBE
UNIT DIMENSION
HEIGHT
mm/in
WIDTH
mm/in
1500 / 59.1
1245 / 49.0
DEPTH
mm/in
900 / 35.4
1800 / 70.9 1150 / 45.3
UNIT WEIGHT
kg/lb
350 / 772
360 / 794
480 / 1058
560 / 1235
SOUND PRESSURE LEVEL
dBA
65
66
67
69
COOLING
l/s/m
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
HEATING
l/s/m
1.14 / 4.1
1.37 / 4.9
1.79 / 6.4
2.10 / 7.6
COOLING
l/s/m3/hr
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
HEATING
l/s/m3/hr
1.14 / 4.1
1.37 / 4.9
1.79 / 6.4
2.10 / 7.6
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT MAX. WATER OPER. PRESSURE PUMP
WATER FLOW RATE
kPa/psi
INSTALLATION PIPE CONNECITON PIPING
TANK
HEAD
1000 / 145
mm/in
42 / 1 1/4"
COOLING
m
26.0
23.5
25.0
23.0
HEATING
m
25.0
22.5
24.5
22.5
MATERIAL CAPACITY/VOLUME
NA NA
L/ft3
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 50 - 100%
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE. b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
S3
Mini Chiller Specifications M4AC080C - M4AC150C (Cooling Only, R407C) M4AC080C
M4AC100C
M4AC120C
M4AC150C
Btu/h
74000
88000
115000
13700
W
21688
25791
33705
40152
W
9463
10771
11805
14531
MODEL NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE
V/Ph/Hz
380-415 / 3 / 50
REFRIGERANT TYPE
R407C
CONTROL
TXV
UNIT DIMENSION
1245 / 49.0
HEIGHT
mm/in
WIDTH
mm/in
1500 / 59.1
DEPTH
mm/in
900 / 35.4
1800 / 70.9 1150 / 45.3
UNIT WEIGHT
kg/lb
340 / 750
350 / 772
460 / 1014
540 / 1190
SOUND PRESSURE LEVEL
dBA
65
66
67
69
l/s/m3/hr
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
26.0
23.5
25.0
23.0
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT PUMP
PIPING
TANK
MAX. WATER OPER. PRESSURE
kPa/psi
WATER FLOW RATE
l/s/m3/hr
INSTALLATION PIPE CONNECITON HEAD
1000 / 145
mm/in m
42 / 1 1/4"
MATERIAL
NA
CAPACITY/VOLUME
NA
L/ft3
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 50 - 100%
M4AC080CR - M4AC150CR (Heatpump, R407C) M4AC080CR
M4AC100CR
M4AC120CR
M4AC150CR
Btu/h
74000
88000
110000
130000
W
21688
25791
32239
38101
Btu/h
90000
98000
118000
144000
MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER
W
26377
28722
34583
42204
COOLING
W
9946
11028
12273
15151
HEATING
W
9975
11134
12386
15824
POWER SOURCE
V/Ph/Hz
380-415 / 3 / 50
REFRIGERANT TYPE
R407C
CONTROL
TXV
UNIT DIMENSION
HEIGHT
mm/in
WIDTH
mm/in
1500 / 59.1
DEPTH
mm/in
900 / 35.4
1245 / 49.0 1800 / 70.9 1150 / 45.3
UNIT WEIGHT
kg/lb
340 / 750
350 / 772
460 / 1014
540 / 1190
SOUND PRESSURE LEVEL
dBA
65
66
67
69
COOLING
l/s/m3/hr
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
HEATING
l/s/m3/hr
1.14 / 4.1
1.37 / 4.9
1.79 / 6.4
2.10 / 7.6
COOLING
l/s/m3/hr
1.08 / 3.9
1.31 / 4.7
1.67 / 6.0
2.00 / 7.2
HEATING
l/s/m3/hr
1.14 / 4.1
1.37 / 4.9
1.79 / 6.4
2.10 / 7.6
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT MAX. WATER OPER. PRESSURE PUMP
WATER FLOW RATE
kPa/psi
INSTALLATION PIPE CONNECITON PIPING
TANK
HEAD
1000 / 145
mm/in
42 / 1 1/4"
COOLING
m
26.0
23.5
25.0
23.0
HEATING
m
25.0
22.5
24.5
22.5
MATERIAL CAPACITY/VOLUME
NA NA
L/ft3
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 50 - 100%
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE. b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
S4
Mini Chiller Specifications M5AC020CR - M5AC055CR (Heatpump, R410A) M5AC020CR
M5AC025CR
M5AC030CR
M5AC040CR
M5AC050CR
M5AC055CR
Btu/h
17000
21000
26800
37500
47000
50000
W
4980
6150
7848
10981
13763
14641
Btu/h
21500
25000
32500
40800
51000
55000
W
6300
7330
9517
11947
14934
16105
COOLING
W
2550
2760
3720
4330
5090
5890
HEATING
W
2590
2790
3630
4490
5130
5990
MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE
V/Ph/Hz
220-240 / 1 / 50
220-240 / 1 / 50 or 380-415 / 3 / 50
REFRIGERANT TYPE
R410A
CONTROL UNIT DIMENSION
CAPILLARY TUBE
CAPILLARY TUBE & TXV
HEIGHT
mm/in
800 / 31.5
790 / 31.1
1410 / 55.5
1410 / 55.5
WIDTH
mm/in
1160 / 45.7
1010 / 39.8
1010 / 39.8
1010 / 39.8
DEPTH
mm/in
460 / 18.1
460 / 18.1
460 / 18.1
460 / 18.1
UNIT WEIGHT
kg/lb
125 / 276
165 / 364
125 / 276
165 / 364
167 / 368
173 / 381
SOUND PRESSURE LEVEL
dBA
57
57
58
60
60
60
COOLING
l/s/m3/hr
0.23 / 0.84
0.28 / 1.00
0.42 / 1.5
0.53 / 1.9
0.64 / 2.3
0.72 / 2.6
HEATING
l/s/m3/hr
0.32 / 1.16
0.35 / 1.25
0.42 / 1.5
0.53 / 1.9
0.64 / 2.3
0.72 / 2.6
0.42 / 1.5
0.53 / 1.9
0.64 / 2.3
0.72 / 2.6
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT MAX. WATER OPER. PRESSURE PUMP
WATER FLOW RATE
TANK
HEAD
1000 / 145
l/s/m3/hr
0.23 / 0.84
0.28 / 1.00
HEATING
l/s/m3/hr
0.32 / 1.16
0.35 / 1.25
INSTALLATION PIPE CONNECITON PIPING
kPa/psi
COOLING
mm/in
25.4 / 1
COOLING
m
8.7
10.1
9.0
10.0
7.9
7.9
HEATING
m
7.7
9.3
7.7
8.9
6.4
5.7
MATERIAL CAPACITY/VOLUME
CAST IRON / STAINLESS STEEL
NA
22 / 0.78
NA
L/ft3
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 100%
0 - 50 - 100%
0 - 40 - 60 - 100%
0 - 50 - 100%
M5ACV030CR - M5ACV135CR (Inverter Heatpump, R410A) MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER
M5ACV030CR
M5ACV055CR
M5ACV075CR
M5ACV100CR
M5ACV135CR
M5ACV210CR
Btu/h
27000
50000
70000
95000
131500
200000
W
7913
14654
20515
27800
38540
58617
Btu/h
33000
55000
75000
100000
141500
210000
W
9663
16119
21980
29300
41470
61548
COOLING
W
5279
7600
9050
12000
15750
22300
HEATING
W
4418
6100
7900
11400
16250
21800
V/Ph/Hz
220-240 / 1 / 50
POWER SOURCE
380-415 / 3 / 50
REFRIGERANT TYPE
R410A
CONTROL UNIT DIMENSION
ELECTRONIC EXPANSION VALVE (EXV)
EXV / CAPILLARY TUBE
HEIGHT
mm/in
790 / 31.1
1410 / 55.5
1460 / 57.5
1260 / 49.6
1260 / 49.6
1786 / 70.31
WIDTH
mm/in
1010 / 39.8
1010 / 39.8
1150 / 45.3
1500 / 59.1
1800 / 70.9
2093 / 82.4
DEPTH
mm/in
460 / 18.1
550 / 21.7
1150 / 45.3
1192 / 46.9
195 / 430
200 / 440
900 / 35.4 360 / 794
560 / 1235
682 85
UNIT WEIGHT
kg/lb
460 / 18.1 128 / 282
SOUND PRESSURE LEVEL
dBA
59
62
65
63
67
COOLING
l/s/m3/hr
0.3 ( 1.3 )
0.7 ( 2.5 )
0.9 ( 3.4 )
1.3 ( 4.8 )
1.8 ( 6.6 )
2.67 (9.8)
HEATING
l/s/m3/hr
0.4 ( 1.5 )
0.8 ( 2.7 )
1.0 ( 3.7 )
1.4 ( 5.0 )
2.0 ( 7.1 )
2.86 (10.5)
EVAPORATOR NOMINAL WATER FLOW HYDRAULIC KIT MAX. WATER OPER. PRESSURE WATER FLOW RATE
TANK
HEAD
1000 / 145
l/s/m3/hr
0.3 ( 1.3 )
0.7 ( 2.5 )
0.9 ( 3.4 )
1.3 ( 4.8 )
1.8 ( 6.6 )
2.7 (9.6)
HEATING
l/s/m3/hr
0.4 ( 1.5 )
0.8 ( 2.7 )
1.0 ( 3.7 )
1.4 ( 5.0 )
2.0 ( 7.1 )
2.9 (10.3)
INSTALLATION PIPE CONNECITON PIPING
kPa/psi
COOLING
mm/in
25.4 / 1
38.0 / 1.5
COOLING
m
7.7
12.7
22.3
17.3
16.5
25
HEATING
m
7.0
11.5
21.3
15.7
14.5
25
0 - 122000
0 - 149000
0 - 210000
MATERIAL CAPACITY/VOLUME
NA NA
L/ft3
COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)
0 - 28700
0 - 55000
0 - 75000
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE. b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
S5
Chilled Water Fan Coil Unit Specifications MCK020AW - MCK050AW (Ceilling Cassette A Series) MODEL Btu/h
MCK020AW
MCK025AW
MCK030AW
MCK040AW
MCK050AW
22500
25500
30000
33500
36500
NOMINAL TOTAL COOLING CAPACITY W
6620
7500
8800
9950
10800
Btu/h
16700
18400
21800
24200
26300
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50°C) NOMINAL AIR FLOW
UNIT DIMENSION - ( ) WITH PANEL
HIGH
W
4900
5400
6400
7100
7700
Btu/h
28500
32000
37500
40500
44000
W
8400
9500
11000
12000
12900
l/s / CFM
364 / 771
383 / 812
433 / 918
483 / 1024
511 / 1083
HEIGHT
mm/in
335 / 13.2 ( 363 / 14.3 )
WIDTH
mm/in
820 / 32.3 ( 930 / 36.6 )
DEPTH
mm/in
821 / 32.3 ( 930 / 36.6 )
UNIT WEIGHT ( UNIT + PANEL )
kg/lb
( 31+4 ) / ( 68.2+8.8 )
( 32+4 ) / ( 70.4+0.44 )
( 35+4 ) / ( 77+8.8 )
( 38+4 ) / (83.6+8.8 )
( 40+4 ) / ( 88+8.8 )
SOUND PRESSURE LEVEL ( H/M/L )
dBA
42 / 39 / 37
45 / 42 / 40
49 / 45 / 43
51 / 48 / 46
53 / 52 / 50
USGPM
5.00
5.70
6.70
7.50
8.20
LITRES/M
18.90
21.55
25.33
28.35
31.00
HEAD LOSS (COOLING)
kPa / psi
24.8 / 3.6
30.8 / 4.47
41.6 / 6.03
52.2 / 7.57
69.3 / 10.05
HEAD LOSS (HEATING) : 50°C
kPa / psi
21.4 / 3.1
26.8 / 3.89
35.3 / 5.12
45.2 / 6.55
64.1 / 9.29
NOMINAL WATER FLOW RATE
CONNECTION
3/4" BSP FEMALE UNION
MCK020AWH - MCK050AWH (4 Pipies Ceilling Cassette) MCK020AWH
MCK025AWH
MCK030AWH
MCK040AWH
MCK050AWH
Btu/h
13000
13500
15800
17100
17600
W
3810
3960
4630
5010
5160
Btu/h
11600
12000
13900
15000
15500
W
3400
3520
4070
4400
4540
Btu/h
36000
37500
42700
46000
47000
W
10550
10990
12510
13480
13770
HIGH
l/s / CFM
349 / 740
368 / 780
415 / 880
467 / 990
491 / 1040
MEDIUM
l/s / CFM
297 / 630
312 / 660
349 / 740
406 / 860
448 / 950
LOW
l/s / CFM
283 / 600
283 / 600
321 / 680
359 / 760
411 / 870
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50°C)
NOMINAL AIR FLOW
UNIT DIMENSION - ( ) WITH PANEL
HEIGHT
mm/in
335 / 13.2 ( 363 / 14.3 )
WIDTH
mm/in
820 / 32.3 ( 930 / 36.6 )
DEPTH
mm/in
821 / 32.3 ( 930 / 36.6 )
UNIT WEIGHT ( UNIT + PANEL )
kg/lb
( 31+4 ) / ( 68.2+8.8 )
( 32+4 ) / ( 70.4+0.44 )
( 35+4 ) / ( 77+8.8 )
( 38+4 ) / (83.6+8.8 )
( 40+4 ) / ( 88+8.8 )
SOUND PRESSURE LEVEL ( H/M/L )
dBA
42 / 39 / 37
45 / 42 / 40
49 / 45 / 43
51 / 48 / 46
53 / 52 / 50
USGPM
2.90
3.00
3.50
3.80
3.90
LITRES/M
10.96
11.34
13.23
14.36
14.74
Add.Heat
USGPM
4.00
4.19
4.76
5.11
5.20
Exch
LITRES/M
15.1
15.83
18
19.3
19.67
HEAD LOSS (COOLING)
kPa / psi
3.56 / 0.52
3.78 / 0.55
4.94 / 0.72
5.7 / 0.83
5.96 / 0.86
HEAD LOSS (HEATING) : 50°C
kPa / psi
4.8 / 0.7
5.5 / 0.8
7.2 / 1.04
8.6 / 1.23
8.8 / 1.28
Cooling NOMINAL WATER FLOW RATE
CONNECTION
3/4" BSP FEMALE UNION
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F) b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F) 4) SOUND PRESSURE LEVEL IS MEASURE IN ANECHOIC CHAMBER, AND ACCORDING TO JIS C 9612 STANDARD. MCK020/025AW/AWH : POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA. MCK030/040/050AW/AWH : 1.5m BELOW THE FACIA (JIS B 8615).
S6
Chilled Water Fan Coil Unit Specifications MCK015BW - MCK025BW (Ceilling Cassette B Series) MODEL
MCK015BW
MCK020BW
MCK025BW
Btu/h
12500
17000
18000
W
3660
4980
5270
Btu/h
9250
11330
13300
W
2710
3320
3900
Btu/h
16000
18000
21000
W
4690
5270
6150
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50°C) NOMINAL AIR FLOW
UNIT DIMENSION - ( ) WITH PANEL
HIGH
l/s / CFM
194 / 410
226 / 480
HEIGHT
mm/in
293 / 11.5 ( 345 / 13.6 )
WIDTH
mm/in
650 / 25.6 ( 727 / 28.6 )
DEPTH
mm/in
UNIT WEIGHT ( UNIT + PANEL )
650 / 25.6 ( 727 / 28.6 )
kg/lb
SOUND PRESSURE LEVEL ( H/M/L )
( 30+3 ) / ( 66+6.6)
( 31+3 ) / (68.2+6.6 )
dBA
36 / 33 / 29
40 / 36 / 30
43 / 41 / 37
USGPM
2.78
3.79
4.00
NOMINAL WATER FLOW RATE LITRES/M
10.50
14.30
15.20
HEAD LOSS (COOLING)
kPa / psi
39.3 / 5.70
9.70 / 1.41
10.3 / 1.50
HEAD LOSS (HEATING) : 50°C
kPa / psi
33 / 4.78
7.6 / 1.10
15.9 / 2.30
CONNECTION
3/4" BSP FEMALE UNION
MCK010CW - MCK020CW (Ceilling Cassette C Series) MCK010CW
MCK015CW
MCK020CW
Btu/h
8000
14000
14500
MODEL
NOMINAL TOTAL COOLING CAPACITY W
2340
4100
4250
Btu/h
6700
10400
11100
W
1970
3060
3240
Btu/h
10900
17500
18500
W
3200
5120
5420
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50°C) NOMINAL AIR FLOW
UNIT DIMENSION - ( ) WITH PANEL
HIGH
l/s / CFM
184 / 390
203 / 430
HEIGHT
mm/in
250 / 9.8 ( 295 / 11.6 )
WIDTH
mm/in
570 / 22.4 ( 640 / 25.2 )
DEPTH
mm/in
570 / 22.4 ( 640 / 25.2 )
UNIT WEIGHT ( UNIT + PANEL )
kg/lb
( 22+2 ) / (48.5+4.4)
SOUND PRESSURE LEVEL ( H/M/L )
dBA
44 / 43 / 42
( 23+2 ) / ( 50.6+4.4 ) 44 / 42 / 41
47 / 46 / 44
USGPM
1.76
3.10
3.22
NOMINAL WATER FLOW RATE LITRES/M
6.67
11.83
12.17
HEAD LOSS (COOLING)
kPa / psi
67.3 / 9.76
68.6 / 9.95
68.8 / 9.98
HEAD LOSS (HEATING) : 50°C
kPa / psi
61.9 / 8.98
70.5 / 10.22
71.2 / 10.32
CONNECTION
3/4" BSP FEMALE UNION
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F) b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F) 4) SOUND PRESSURE LEVEL ARE MEASURED IN ANECHOIC TEST ROOM & ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.
S7
Chilled Water Fan Coil Unit Specifications MCM007CBW - MCM020DW (Ceilling Convertible) MCM007CBW
MCM010CBW
MCM015CBW
MCM020DW
Btu/h
6500
8600
10500
17700
W
1910
2500
3080
5190
Btu/h
5000
6660
8570
13650
W
1460
1950
2510
4000
Btu/h
7800
10600
14300
22000
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 70ºC) NOMINAL AIR FLOW
UNIT DIMENSION
HIGH
W
2280
3100
4190
6450
l/s/CFM
95 / 200
142/ 300
190 / 400
264 / 660
HEIGHT
mm/in
235 / 9.3
214 / 8.4
WIDTH
mm/in
666 / 26.2
1214 / 47.8
DEPTH
mm/in
824 / 32.4
174 1 / 46.2
670 / 26.4
UNIT WEIGHT
kg/lb
33 / 72.8
35 / 77.2
43 / 94.8
SOUND PRESSURE LEVEL ( H/M/L )
dBA
45 / 42 / 37
46 / 43 / 38
47 / 44 / 39
50 / 47 / 40
USGPM
1.45
1.89
2.33
3.92
LITRES/M
5.50
7.17
8.83
14.83
HEAD LOSS (COOLING)
kPa/psi
9.30 / 1.35
15.4 / 2.23
4.5 / 0.65
45.6 / 6.61
HEAD LOSS (HEATING) : 70ºC
kPa/psi
7.0 / 1.01
12.7 / 1.84
3.6 / 0.52
39.2 / 5.68
NOMINAL WATER FLOW RATE
CONNECTION
3/4" BSP FEMALE ADAPTOR
MCM025DW - MCM050DW (Ceilling Convertible) MODEL Btu/h
MCM025DW
MCM030DW
MCM040DW
MCM050DW
20800
24600
31200
45000
NOMINAL TOTAL COOLING CAPACITY W
6100
4210
9140
13190
Btu/h
15000
17700
25600
31400
W
4400
5190
7500
9200
Btu/h
25900
28000
42300
51500
W
7590
8210
12400
15100
329 / 697
449 / 949
500 / 1058
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60ºC) NOMINAL AIR FLOW
UNIT DIMENSION
HIGH
l/s/CFM
297 / 630
HEIGHT
mm/in
214 / 8.4
WIDTH
mm/in
DEPTH
mm/in
249 / 9.8 1214 / 47.8
1714 / 67.5 670 / 26.4
UNIT WEIGHT
kg/lb
43 / 94.8
45 / 99.2
SOUND PRESSURE LEVEL ( H/M/L )
dBA
54 / 53 / 50
51 / 50 / 48
54 / 53 / 52
70 / 154.3 54 / 53 / 52
USGPM
4.63
5.46
6.91
10.00
NOMINAL WATER FLOW RATE LITRES/M
17.50
20.67
26.17
37.83
HEAD LOSS (COOLING)
kPa/psi
55.7 / 8.07
49.4 / 7.16
124.0 / 3.48
37.7 / 5.46
HEAD LOSS (HEATING) : 60ºC
kPa/psi
48.1 / 6.97
43.0 / 6.23
21.5 / 3.11
31.6 / 4.58
CONNECTION
3/4" BSP FEMALE ADAPTOR
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19ºC (66.2ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF) b) HEATING - ENTERING AIR TEMP.: 20ºC (68ºF) DB, ENTERING WATER TEMP. : 70ºC (158ºF), LEAVING WATER TEMP. : 65ºC (149ºF) c) MCM025DW-MCM050DW: HEATING - ENTERING AIR TEMP.: 20ºC (68ºF) DB, ENTERING WATER TEMP. : 60ºC (140ºF), LEAVING WATER TEMP. : 55ºC (131ºF) 4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS C 9612 STANDARD. MCM020/025DW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE UNIT. MCM030/040/050DW : 1 m IN FRONT OF THE UNIT AND 1m BELOW THE AIR DISCHARGE OPENING. (JIS B 8615) MCE007-015CBW: 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.
S8
Chilled Water Fan Coil Unit Specifications MCC010CW - MCC028CW (Ceiling Concealed) MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60ºC)
NOMINAL AIR FLOW
MCC015CW
MCC020CW
MCC025CW
MCC028CW
Btu/h
9900
15000
18000
22500
26000
W
2902
4396
5275
6594
7620
Btu/h
7000
10000
13600
17900
19500
W
2052
2931
3986
5246
5715
Btu/h
19000
25500
38000
48000
55000
W
5569
7474
11137
14068
16120
SUPER HIGH
l/s/CFM
NA
NA
NA
NA
401 / 850
HIGH
l/s/CFM
142 / 300
241 / 510
330 / 700
345 / 730
382 / 810
MEDIUM
l/s/CFM
123 / 260
208 / 440
321 / 680
340 / 720
363 / 770
LOW
l/s/CFM
104 / 220
170 / 360
293 / 620
274 / 580
335 / 710
EXTERNAL STATIC ( H/M/L )
UNIT DIMENSION
MCC010CW
mmAq
5/4/3
5/4/3
5/4/3
5/4/3
10 / 8 / 7 / 6
HEIGHT
mm/in
261 / 10.3
262 / 10.3
263 / 10.3
261 / 10.3
290 / 11.4
WIDTH
mm/in
765 / 30.1
905 / 35.6
1065 / 41.9
1200 / 47.2
942 / 37.1
DEPTH
mm/in
411 / 16.2
412 / 16.2
413 / 16.2
411 / 16.2
600 / 23.6
UNIT WEIGHT
kg/lb
17 / 37.5
21 / 46.3
22 / 48.5
25 / 55.1
38 / 83.8
SOUND PRESSURE LEVEL ( H/M/L )
dBA
33 / 30 / 26
37 / 34 / 29
38 / 36 / 34
40 / 39 / 36
44 / 41 / 38 / 34
USGPM
2.00
2.58
4.20
4.70
5.70
LITRES/M
7.57
9.77
15.90
17.79
21.58
HEAD LOSS (COOLING)
kPa/psi
8.83 / 1.28
13.97 / 2.03
18.28 / 2.65
24.12 / 3.50
14.69 / 2.13
HEAD LOSS (HEATING) : 60ºC
kPa/psi
6.69 / 0.97
10.76 / 1.56
14.20 / 2.06
18.96 / 2.75
11.38 / 1.65
NOMINAL WATER FLOW RATE
CONNECTION
3/4" BSP FEMALE ADAPTOR
MCC030CW - MCC060CW (Ceiling Concealed) MODEL
MCC030CW
MCC038CW
MCC040CW
MCC050CW
MCC060CW
Btu/h
28000
35000
38000
47000
54000
W
8206
10258
11137
13775
15826
Btu/h
21800
27600
34000
34700
39900
W
6389
8089
9965
10170
11694
Btu/h
60000
65000
75000
95000
110000
W
17585
19050
21981
27843
32239
SUPER HIGH
l/s/CFM
425 / 900
727 / 1540
519 / 1100
750 / 1590
779 / 1650
HIGH
l/s/CFM
392 / 830
694 / 1470
500 / 1060
651 / 1380
722 / 1530
MEDIUM
l/s/CFM
359 / 760
670 / 1420
467 / 990
604 / 1280
675 / 1430
LOW
l/s/CFM
335 / 710
637 / 1350
425 / 900
571 / 1210
609 / 1290
mmAq
21 / 17 / 13 / 9
14 / 12 / 11 / 9
21/ 18 / 13 / 9
18 / 16 / 14 / 11
18 / 16 / 14 / 10
HEIGHT
mm/in
378 / 14.9
310 / 12.2
378 / 14.9
378 / 14.9
379 / 14.9
WIDTH
mm/in
929 / 36.6
1247 / 49.1
1045 / 41.1
1299 / 51.1
1499 / 59.0
DEPTH
mm/in
541 / 21.3
638 / 25.1
541 / 21.3
541 / 21.3
542 / 21.3
UNIT WEIGHT
kg/lb
39 / 86.0
41 / 90.4
42 / 92.6
54 / 119.0
62 / 136.7
SOUND PRESSURE LEVEL ( SH/H/M/L )
dBA
49 / 46 / 42 / 38
55 / 51 / 48 / 45
51 / 49 / 45 / 41
53 / 52 / 50 / 47
55 / 53 / 50 / 47 10.80
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60ºC)
NOMINAL AIR FLOW
EXTERNAL STATIC ( SH/H/M/L )
UNIT DIMENSION
USGPM
6.20
9.60
7.40
10.00
LITRES/M
23.47
36.34
28.01
37.85
40.88
HEAD LOSS (COOLING)
kPa/psi
12.82 / 1.89
44.24 / 6.42
18.86 / 2.74
37.08 / 5.38
7.01 / 1.02
HEAD LOSS (HEATING) : 60ºC
kPa/psi
9.86 / 1.43
35.78 / 5.19
14.69 / 2.13
29.65 / 4.30
5.38 / 0.78
NOMINAL WATER FLOW RATE
CONNECTION
3/4" BSP FEMALE ADAPTOR
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19ºC (66.2ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF) b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 60°C (140°F), LEAVING WATER TEMP. : 55°C (131°F) 4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB STD - GB/D17758. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT. TESTED WITH 2m LENGTH DUCT AT THE AIR DISCHARGE OUTLET ANS AIR RETURN INLET.
S9
7/8" BSP FEMALE ADAPTOR
Chilled Water Fan Coil Unit Specifications MCW200C - MCW1200C (Ceilling Concealed) MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60ºC)
MCW200C
MCW300C
MCW400C
MCW600C
MCW800C
MCW1000C
MCW1200C
Btu/h
7710
11460
14450
22260
27880
31360
40650
W
2260
3359
4235
6524
8171
9191
11914
Btu/h
5120
7850
9740
15020
18470
21290
27340
W
1501
2301
2855
4402
5413
6240
8013
Btu/h
13440
19510
25740
38640
48510
53970
69810
W
3939
5718
7544
11325
14217
15818
20460
SUPER HIGH l/s/CFM NOMINAL AIR FLOW
NA
NA
NA
NA
NA
NA
NA
HIGH
l/s/CFM
114 / 241
153 / 324
214 / 453
295 / 624
403 / 853
455 / 965
575 / 1218
MEDIUM
l/s/CFM
94 / 200
129 / 274
144 / 306
236 / 500
328 / 695
378 / 800
489 / 1036
LOW
l/s/CFM
64 / 135
97 / 206
109 / 230
197 / 418
256 / 542
305 / 647
419 / 888
EXTERNAL STATIC ( H/M/L )
UNIT DIMENSION
mmAq
Up to 8.13 mmAq
HEIGHT
mm/in
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
WIDTH
mm/in
714 / 28.1
884 / 34.8
1014 / 39.9
1214 / 47.8
1464 / 57.6
1564 / 61.6
1824 / 71.8
DEPTH
mm/in
490 / 19.3
490 / 19.3
490 / 19.3
490 / 19.3
490 / 19.3
490 / 19.3
490 / 19.3
UNIT WEIGHT
kg/lb
19
22
26
30
41
44
46
SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa
dBA
40.1 / 37.2 / 34.9
48.3 / 44.7 / 37.8
48.7 / 46.3 / 46.4
49.0 / 47.2 / 43.3
53.1 / 51.5 / 49.7
53.1 / 52.0 / 51.1
52.4 / 50.6 / 47.4
USGPM
1.85
2.64
3.43
4.76
6.34
7.66
10.04
LITRES/M
7.00
10.00
13.00
18.00
24.00
29.00
38.00
HEAD LOSS (COOLING)
kPa/psi
14.6 / 2.12
12 / 1.74
21.6 / 3.13
38.2 / 5.54
18.4 / 2.67
21 / 3.05
32.7 / 4.74
HEAD LOSS (HEATING) : 60ºC
kPa/psi
14.6 / 2.12
12 / 1.74
21.6 / 3.13
38.2 / 5.54
18.4 / 2.67
21 / 3.05
32.7 / 4.74
NOMINAL WATER FLOW RATE
CONNECTION
3/4" BSP FEMALE ADAPTOR
MCW200H - MCW1200H (Ceilling Concealed) MCW200H
MCW300H
MCW400H
MCW600H
MCW800H
MCW1000H
MCW1200H
Btu/h
7710
10240
14330
20810
26100
28320
34800
W
2260
3000
4200
6100
7650
8300
10200
Btu/h
5220
6960
9900
14330
18080
20130
26410
W
1530
2040
2900
4200
5300
5900
7740
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60ºC) - 3 ROWS
Btu/h
12180
17200
24670
33300
43670
49300
64110
W
3570
5040
7230
9760
12800
14450
18790
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60ºC) - 1 ROW
Btu/h
4810
7850
11430
15120
17740
23920
29240
W
1410
2300
3350
4430
5200
7010
8570
NA
NA
NA
NA
NA
NA
NA
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY
SUPER HIGH l/s/CFM NOMINAL AIR FLOW
HIGH
l/s/CFM
113 / 240
165 / 350
212 / 450
316 / 670
396 / 840
472 / 1000
604 / 1280
MEDIUM
l/s/CFM
94 / 200
142 / 300
189 / 400
307 / 650
345 / 730
415 / 880
519 / 1100
LOW
l/s/CFM
76 / 160
94 / 200
165 / 350
212 / 450
288 / 610
302 / 640
425 / 900
EXTERNAL STATIC ( SH/H/M/L ) UNIT DIMENSION
mmAq
Up to 8.13 mmAq
HEIGHT
mm/in
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
251 / 9.9
WIDTH
mm/in
714 / 28.1
884 / 34.8
1014 / 39.9
1214 / 47.8
1464 / 57.6
1564 / 61.6
1824 / 71.8
DEPTH
490 / 19.3
mm/in
490 / 19.3
490 / 19.3
490 / 19.3
490 / 19.3
490 / 19.3
490 / 19.3
UNIT WEIGHT
kg/lb
20
24
28
32
44
47
49
SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa
dBA
40.1 / 37.2 / 34.9
48.3 / 44.7 / 37.8
48.7 / 46.3 / 46.4
49.0 / 47.2 / 43.3
53.1 / 51.5 / 49.7
53.1 / 52.0 / 51.1
52.4 / 50.6 / 47.4
NOMINAL WATER FLOW RATE - 3 ROWS
USGPM
1.80
2.51
3.43
4.76
6.13
6.87
8.45
LITRES/M
6.80
9.50
13.00
18.00
23.20
26.00
32.00
USGPM
0.87
1.22
1.74
2.11
2.38
3.20
3.72
LITRES/M
3.30
4.60
6.60
8.00
9.00
12.10
14.10
HEAD LOSS (COOLING) - 3 ROWS
kPa/psi
16 / 2.32
13 / 1.89
22 / 3.19
47 / 6.82
33 / 4.79
26 / 3.77
45 / 6.53
HEAD LOSS (HEATING) : 60ºC - 3 ROWs
kPa/psi
16 / 2.32
13 / 1.89
22 / 3.19
47 / 6.82
33 / 4.79
26 / 3.77
45 / 6.53
HEAD LOSS (COOLING) - 1 ROW
kPa/psi
8 / 1.16
8 / 1.16
15 / 2.18
17 / 2.47
21 / 3.05
18 / 2.61
20 / 2.9
HEAD LOSS (HEATING) : 60ºC - 1 ROW
kPa/psi
8 / 1.16
8 / 1.16
15 / 2.18
17 / 2.47
21 / 3.05
18 / 2.61
20 / 2.9
NOMINAL WATER FLOW RATE - 1 ROW
CONNECTION
3/4" BSP FEMALE ADAPTOR
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19.5ºC (67.1ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF) b) HEATING - ENTERING AIR TEMP.: 21ºC (69.8ºF) DB, ENTERING WATER TEMP. : 60ºC (140ºF), LEAVING WATER TEMP. : 55ºC (131ºF) 3) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.
S10
Chilled Water Fan Coil Unit Specifications MWM007GW - MWM025GW (Wall Mount) MWM007GW
MWM010GW
MWM015GW
MWM020GW
MWM025GW
Btu/h
8000
9500
11000
15500
18000
W
2340
2780
3220
4540
5280
Btu/h
5900
6900
8000
12500
14800
MODEL NOMINAL TOTAL COOLING CAPACITY - 1 NOMINAL SENSIBLE COOLING CAPACITY
50Hz
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50°C) NOMINAL TOTAL COOLING CAPACITY - 1Ø NOMINAL SENSIBLE COOLING CAPACITY
60Hz
UNIT DIMENSION
HIGH
1740
2030
2350
3650
4330
10300
12800
14000
20500
23000
W
3020
3750
4100
6010
6740
Btu/h
9500
11000
15500
18000
W
2784
3224
4543
5275
Btu/h
7220
8360
11780
13680
W
NA
Btu/h
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50°C) NOMINAL AIR FLOW
W Btu/h
W
2116
2450
3453
4009
12800
14000
20500
23000
3751
4103
6008
6741
142 / 300
163 / 345
297 / 630
312 / 660
l/s / CFM
130 / 275
HEIGHT
mm/in
260 / 10.2
260 / 10.2
304 / 12.0
WIDTH
mm/in
799 / 31.5
899 / 35.4
1062 / 41.8
DEPTH
mm/in
198 / 7.8
198 / 7.8
UNIT WEIGHT
kg/lb
10 / 22.1
12 / 26.5
SOUND PRESSURE LEVEL ( H/M/L )
dBA
40 / 35 / 29
39 / 34 / 28
42 / 36 / 29
USGPM
1.80
2.10
2.40
3.40
4.00
LITRES/M
6.80
7.94
9.07
12.85
15.12
kPa / psi
48.3 / 7
64.7 / 9.38
69.3 / 10.05
50.3 / 7.29
69.3 / 10.05
kPa / psi
42 / 6.09
58.6 / 8.5 2.16
60.6 / 8.79 2.42
50.6 / 7.34 3.43
70.6 / 10.24 3.65
NOMINAL WATER FLOW RATE 50Hz
HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50°C
USGPM
NOMINAL WATER FLOW RATE 60Hz
HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50°C
LITRES/M kPa / psi
NA
kPa / psi
222 / 8.7 16 / 35.3
16 / 35.3
49 / 43 / 40
50 / 48 / 44
8.18
9.16
12.98
13.82
54.9 / 7.95
67.8 / 9.83
50.4 / 7.31
41.7 / 6.04
61.8 / 8.95
50.9 / 7.38
35.8 / 5.19
47.0 / 6.81
CONNECTION
1/2" BSP FEMALE ADAPTOR
MDB075BW - MDB0150BW (Ducted Blower) MDB075BW
MDB0100BW
MDB0125BW
MDB0150BW
Btu/h
73000
95000
122500
157800
W
21395
27843
35903
46249
Btu/h
57200
71400
94500
118000
W
16764
20926
27696
34584
Btu/h
160000
200000
265000
329000
W
46893
58617
77667
96424
l/s / CFM
1128 / 2390
1444 / 3060
1897 / 4020
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 70°C) NOMINAL AIR FLOW EXTERNAL STATIC
mmAq
10
2077 / 4400 15
HEIGHT
mm/in
572 / 22.5
572 / 22.5
885 / 34.8
885 / 34.8
WIDTH
mm/in
1502 / 59.1
1502 / 59.1
1640 / 64.6
1640 / 64.6
DEPTH
mm/in
761 / 30.0
761 / 30.0
1040 / 40.9
1040 / 40.9
UNIT WEIGHT
kg/lb
96 / 211.6
100 / 220.5
140 / 308.6
145 / 319.7
SOUND PRESSURE LEVEL
dBA
56
57
58
59
UNIT DIMENSION
USGPM
16.30
20.00
27.10
35.00
LITRES/M
61.70
75.71
102.58
132.50
HEAD LOSS (COOLING)
kPa / psi
20.13 / 2.92
16.27 / 2.36
22.75 / 3.30
18.96 / 2.75
HEAD LOSS (HEATING) : 70°C
kPa / psi
15.89 / 2.30
12.69 / 1.84
17.93 / 2.60
14.89 / 2.16
NOMINAL WATER FLOW RATE
CONNECTION
1 1/8" BRAZING
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F) b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F) 4) a) MDB: SOUND PRESSURE LEVEL ARE TESTED IN ANECHOIC CHAMBER AT 1.4m BELOW THE UNIT (FREE RETURN AND THE DISCHARGE AIR WAS DUCTED TO ADJACENT ROOM) b) MWM:SOUND PRESSURE LEVEL ARE TESTED IN ANECHOIC CHAMBER AND ACCORDING TO JIS C 9612 STANDARD. MWMFW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE UNIT. MWM301W : 1m IN FRONT AND 1 m BELOW THE DISCHARGE OPENING OF THE UNIT (JIS B 8615)
S11
Chilled Water Fan Coil Unit Specifications MCE015EW - MCE025EW (Ceiling Convertible) MCE015EW
MCE020EW
MCE025EW
Btu/h
15500
20300
21000
W
4540
5950
6160
Btu/h
12700
15400
16200
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 70ºC)
NOMINAL AIR FLOW
UNIT DIMENSION
W
3720
4520
4740
Btu/h
19500
25000
28000
W
5720
7330
8210
HIGH
l/s/CFM
245 / 519
273 / 579
293 / 619
MEDIUM
l/s/CFM
217 / 460
250 / 530
269 / 570
LOW
l/s/CFM
192 / 406
231 / 490
245 / 520
HEIGHT
mm/in
212.5 / 8.4
WIDTH
mm/in
1090 / 42.9
DEPTH
mm/in
630 / 24.8
UNIT WEIGHT
kg/lb
27 / 59.7
27 / 59.7
28 / 61.9
SOUND PRESSURE LEVEL ( H/M/L )
dBA
48 / 46 / 43
50 / 47 / 46
51 / 48 / 47
USGPM
3.43
4.49
4.67
LITRES/M
13.00
17.00
17.67
HEAD LOSS (COOLING)
kPa/psi
28 / 4.0
48 / 7.0
57 / 8.3
HEAD LOSS (HEATING) : 50ºC
kPa/psi
24 / 3.5
42 / 6.1
50 / 7.3
NOMINAL WATER FLOW RATE
CONNECTION
1/2" BSP FEMALE ADAPTOR
Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19ºC (66.2ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF) b) HEATING - ENTERING AIR TEMP.: 20ºC (68ºF) DB, ENTERING WATER TEMP. : 70ºC (158ºF), LEAVING WATER TEMP. : 65ºC (149ºF) 4) SOUND PRESSURE LEVEL ARE TESTED IN ANECHOIC CHAMBER AND ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT
S12
Products manufactured in an ISO certified facility. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
© 2008 McQuay International
+1 (800) 432-1342
www.mcquay.com
A Global Leader in System Solutions for Air Conditioning, Heating, Ventilating and Refrigeration.