Chapter-17 Chilled Water System Configurations

႔ Chapter-17 Chilled Water System Configurations Chapter-17 Chilled Water System Configurations ၁၇.၁ Chilled Water Plant Basics Chilled water plant ...
Author: Sybil Hudson
3 downloads 0 Views 2MB Size


Chapter-17 Chilled Water System Configurations

Chapter-17 Chilled Water System Configurations ၁၇.၁ Chilled Water Plant Basics Chilled water plant

(functional parts)

(၁) Chilled water



chiller

(၂) Air Handling Units(AHU) ၊ Fan Coil Units(FCU) ၊ CRAC units (၃) Chilled water distribution pumps and pipes (၄) Condenser water pumps, pipes, and cooling towers (၅) Controls (operation of the mechanical components together as a system)



၁၇.၁.၁ Chilled Water Temperatures Comfort cooling system

chilled water supply temperature

6.7°C (44°F)



3.3°C (38°F)

chilled water temperature

ၾ (၁) Chilled water temperature



(၂) Chilled water temperature

chilled water

(flow)



(lower supply air temperature)

(air flow rate) (၃) Chilled water temperature

Air side ၾ

chilled water coil ၌



(dehumidification) (၄) Chilled water temperature (၅)

system efficiency



chilled water distribution system ၏ capacity

chilled water temperature Chilled water temperature

consumption)

Chilled water flow rate

(energy

system

(၆) Chilled water temperature

ၾ ၾ

chiller ၏

chiller



(energy



၏ system

၌ condensation (sweating) 17-1

Chillers and Chilled Water Systems



insulation

Chilled water

34°F(1.1°C)

chiller

(sophisticated) evaporator

chiller control

(method)

၁၇.၁.၂ Effect of Chilled Water Temperature Chiller

leaving chilled water temperature

temperature

refrigerant

pressure

႔ refrigerant temperature

leaving chilled water

leaving chilled water

pressure

႔ ၾ

compressor work



(energy consumption)

Chiller

system



Leaving chilled water temperature



chiller

pump



temperature

(flow rate)

chilled water



၁၇.၁.၃ Effect of Chilled Water Flow Rate Evaporator

heat exchanger



Chilled water (erosion)၊ (flow rate)

chilled water

(flow rate)

(vibration) ၊

ၾ (noise)

heat transfer efficiency

(flow rate)

(water velocity)





႔ chiller performance

႔ ၾ

(minimum flow)

၁၇.၁.၄ Condenser Water Temperature chiller

enteri Design temperature

(lowest allowable temperature)

chiller condenser water temperature



၁၇.၁.၅ Effect of Condenser Water Temperature Chiller pressure

entering

refrigerant temperature



Entering condenser water temperature

(temperature)

(pressure)

consumption)

compressor



Entering

(power consumption) (energy



(power ၾ

Chiller

system

consumption) ၾ

refrigerant



Entering

chiller efficiency

၁၇.၁.၇ Effect of Condenser Water Flow Rate Condenser

heat exchanger

(flow) (vibration) ၊ heat transfer efficiency (startup conditions) (specific range of limits) 17-2





(water flow rate)

(water velocity)

(noise)

႔ Chiller performance

condenser water flow

(erosion)၊ (flow rate) Chiller

ၾ ႔



Chapter-17 Chilled Water System Configurations



water velocity

(water hardness) tube

condenser tube

F





(water hardness)

velocity

3.51 ft/s (1.07 m/s)

၁၇.၁.၈ Chilled Water and Condenser Water Flow Rates Chilled water system

condenser water

(installation)

(flow rate)



chilled water

(operation)

AHRI 550/590

flow rate •

2.4 gpm/ton [0.043 liter per second/kW] for evaporator water flow rate



3.0 gpm/ton [0.054 lps/kW] for condenser water flow rate flow rate

(temperature difference) 10°F(5.5°C)

Compressor efficiency 9.1°F(5.1°C)

condenser

(temperature difference)

10°F(5.6°C)

၁၇.၂ Single Chiller System Chiller configuration

single chiller system Chiller plant

chiller



၁၇-၁ Chiller (

) Chiller

၏ condenser water loop ၾ

chiller ၏

system

chilled water

႔ ၾ ႔ single chiller system

system





(break down)



Multiple chillers standby chiller



h



Standby chiller

chiller

(break down) ၾ

( ) Chiller

၊ data center

multiple chillers system

system Standby chiller

(break down)

computer center ႔

(application)

chilled water loop

ၾ Centrifugal compressor

load

chiller

႔ ၾ

chiller full load capacity ၏ 30% 17-3

Chillers and Chilled Water Systems



Chilled water plant

chiller

“installed capacity”



Peak load

“running capacity”

capacity

chiller

Running capacity

capacity





“capacity to load ratio” - chiller plant (500RT x 4)

500RT chiller (၄)

Peak load

1,500RT (500RT x 3)

install capacity

500RT chiller (၃) ႔ ၾ

2,000RT

running capacity

capacity to load ratio

0.75(1,500RT/2,000RT)

၁၇.၂.၁ Single Chiller System Advantages and Disadvantages Table 17-1 advantages and disadvantages of single chiller system (Advantages)

(Disadvantages)

– Lower first cost

– Inefficient at low load conditions

– Simple system for installation and control

– Lack of back-up and redundancy

၁၇.၃ Multiple Chiller System

၁၇-၂ Chiller configuration chiller



chiller



water cooled plant

system reliability

efficiency



chiller

Multiple chiller system configuration configuration ၏ 95%

parallel configuration ၊ chiller

chiller 2011



parallel

Chilled water

ၾ ၊ consultant

AHRI Standard 550/590-2011

AHRI

(contractor) ၾ

Reference AHRI 550/590-

“performance rating of water chilling packages using the vapor compression cycle” AHRI 550/590-2011 chiller

17-4

series configuration

Parallel configuration

Chiller ၾ

Chiller

chillers ၊ cooling towers ၊ chilled water pumps ၊ condenser water pumps ၊

piping ၊ accessories controls

plant



(comply)

chiller





Chapter-17 Chilled Water System Configurations

Chiller ၏ parameter ၾ

chiller

(standard) ၏ efficiency (k

Load Value (IPLV)



Non-standard Part Load Value (NPLV)

AHRI 550/590-2011 Chiller

performance

Integrated Part ႔

(standard)

S

(construction) E

15 “S R22



(installation)

M h

R134a

psig

” chiller

၏ condenser

(pressure)



Part load

chiller manufacturer

Chiller

(comply)

maximum capacity )

15

pressure vessel

(comply)

Underwriter Laboratory (UL) standard 465 Chiller



ASME(American Society of Mechanical Engineering)

၏ boiler and pressure vessel code

(

evaporator



Pressure vessel



(

)

႔ ၾ

part load operating performance

Intergrated Part Load Value (IPLV)

Non-standard Part Load Value (NPLV)

(၂)

၁၇.၄ Parallel Chillers System Table 17-2 advantages and disadvantages of parallel chillers system (Advantages) – More efficient at low load conditions

(Disadvantages) – Increased first cost

– Provides back-up and/or redundancy – More difficult to control effectively, especially with different size chillers (should have computerized system) – More equipment to maintain h (၁) Primary only system (၂) Primary - Secondary system (၃)

၁၇.၅ P

O P



S h

“primary only system”

P h

h

ၾ h



h

S ႔

h ႔

“ h ႔

h

h ႔

h secondary chill

17-5

Chillers and Chilled Water Systems



၁၇-၄

၁၇-၅

chiller ၁၇-၆

h

h



h h

၁၇-၆







h

ch Dedicated

pump

h

႔ chiller

၁၇-၃ Primary only circuit

၁၇-၄ Common header system

၁၇-၅ One to one



dedicated system

၁၇-၆ Primary only system with common header

၁၇.၅.၁ Primary Only System with Common Header ၁၇-၆)

primary only system

Primary

h

h

water ၆)

seconadry chilled

h production loop(primary ch

၁၇-

႔ 17-6

h

c ႔

h h



Chapter-17 Chilled Water System Configurations

h

h

h

primary chilled water pump ႔

pump h

h



h

h







h

h

h

၊ ႔

h





evaporator

h



h

h

co

(amount chilled water flow rate)

pressure drop)





h

ၾ h

chiller





႔ ၾ

h

h

႔ h ႔ (a

constant f

h

၊ h

h





h

h

၁၇-၇(



) Schematic of the constant-flow rate primary system.

Primary chilled water pump ႔

h

h

S





h

h

h



h

႔ P

h h

chille

h ၊



(size ၊ 17-7

Chillers and Chilled Water Systems



complexity)



chiller

႔ ၾ



႔ ႔

h







h

common h



h

h

h





h

const

၁၇-၇( ) Primary only system with one to one configuration with two way valve h h





႔ ၂

h ႔

flow rate)

၂ ႔



၏ h

(chilled water

h ၾ

speed)

၁၇-၈ Primary only system with dedicated pump 17-8





Chapter-17 Chilled Water System Configurations



h

chilled water flow rate) h

h





leaving chilled water temperature setpoint h

h h







h

h

s

instability)

၁၇.၅.၂ Primary Only System with Dedicated Pump (၁၇-၈)



(office 200RT AHU

၏ design load �

600 TR (100 tons of refrigeration each floor)

AHU

AHU 600RT

capacity



Δ

1

Chiller

ၾ Chiller



total installed capacity

� 200 tons capacity chiller (၃) � Chiller

၏ capacity

chilled water supply (CHWS) temperature 44°F

12°F)

(flow rate) 400 GPM ( 4 Δ

AHU ၏ cooling coil

Δ

x

h

12°F)

)

(flow rate) 200

GPM ( 4 Δ x 1 � Dedicated pump

၁၇.၅.၃ Primary-Only System ၏ (disadvantage) (၂) control

chiller staging

bypass



(၁) Chiller

plant plant ၾ

(၂)

၊ chiller

plant

base load

chiller staging

bypass control system

plant

primary-secondary system

Fail-safe

operation

primary-secondary

system

Table 17-2 advantages and disadvantages of primary-only systems Secondary pump P





h ၏ ႔ 17-9

Chillers and Chilled Water Systems



၁၇.၆ Primary - Secondary System ၁၇-၇) P

h

h

h



“production pump”

Primary chilled water

“production circuit/loop” S

h

“distrubution pump”

Secondary chilled water

“distrubution circuit/loop” Primary- secondary pumping system loop

chilled water system

circuit



loop

circuit







neutral bridge (de-coupler) (၁) Primary circuit

chilled water

Primary pump

constant volume ၊ low head pump Chiller

primary pump

(၂) Secondary circuit

ၾ one to one configuration



common header

chilled water distribution

Secondary circuit ၏

pumps ၊ Fan Coil Units (FCU)၊ Air Handling Units (AHU) terminal unit



speed pump

Secondary pump



(၃) De-coupler secondary

secondary loop

primary loop

secondary loop







variable

(pressure drop)



primary loop pumping

control valves

constant speed

Secondary circuit pump

(၂)

common pipe hydraulic





Primary-

(primary

secondary)

၁၇.၆.၁ Dedicated Pump and Manifold Pump (Common Header) ၁၇-၁

-

Primary-secondary

h

seconadry chilled water circuit

(distribution loop) c

h

Primary chilled wa

dedicated pump

h





၁၇-၉-

primary chilled water

circuit/

production loop (primary chilled water Dedicated pump





M

h

h ႔

17-10

h

secondary chilled water pump ႔

h



dedicated pump



h



၁၇-၉(

Chapter-17 Chilled Water System Configurations

) Primary secondary with manifolded pumps (၁၇-၉)

( )Primary secondary with dedicated pumps

primary - secondary





common h ၾ



၁၇-၉( ၁၇-၉- )

“D



variable secondary flow) system

chilled



secondary circuit

h h

priamry chilled water

flow

secondary chilled water P

secondary circuit h

ၾ ၏

flow rate)

chilled water

႔ ၾ chilled water flow rate)





၊ 17-11

Chillers and Chilled Water Systems



၁၇.၆.၂ Dedicated Pumps at Production Loop or Primary Chilled Water Circuit/Loop Pro h

h



၌ “









h





evaporator pre

chiller



dedicated pump

h

P

h

(constant flow of

water

- 5



(standard chilled water flow rate)

h

၏ stand

h

1,200 GPM (500R x .4 PM

႔ two-way modulating valve

h

႔ ၾ

h

h S

D

SD



Variable Frequency Dirve (VFD)

Primary chilled water pump (production pump ႔

h

႔ pressure

႔ ၾ

loss)





h



h



h Primary chilled wa -

h P

side)

၁၇-၁ Production loop

၁၇-၁၁ Dedicated pumps at production loop (primary chilled water circuit/loop) 17-12

-

production loop (load

x

loa

distribution loop

၁၇-၁၂ M



Common header at production loop



Chapter-17 Chilled Water System Configurations

H

production

(chiller) loop

distribution (AHU/FCU) loop

control Primary secondary pumping arrangement pump

(၂)

distribution

Production



AHU/FCU

pump (၂) (၂)

႔ Pump



ၾ Production pump

chiller



primary pump

production side

(pressure drop) Distribution

distribution system

AHU/FCU

pump ႔၏

(pressure drop) ၁၇-၁၃ Decoupled arrangement Chiller

(minimum flow rate)

bypass

bypass valve

၁၇.၆.၃ Bypass Line



Decouple Line sizing

Primary–secondary

variable-primary-flow system (decoupled system) Bypass line

10%

15%

chiller ၏ VPF system

bypass line (flow rate)

bypass line

chiller

၏ (pressure loss) line

bypass

water velocity x

bypass line

bypass line (၁ )



Bypass

valve

၁၇-၁၄ Decoupled system supply tee 

Bypass Valve 

Maintain a minimum chilled water flow rate through the chillers 

Differential pressure measurement across each chiller evaporator



Flow meter preferred



Modulates open to maintain the minimum flow through operating chiller(s).



Bypass valve is normally open, but closed unless Min flow breeched



Pipe and valve sized for Min flow of operating chillers



High Rangeability (100:1 preferred)



PSID Ratings for Static, Dynamic, And Close Off = Shut Off Head of Pumps 17-13

Chillers and Chilled Water Systems





Linear Proportion (Flow to Valve Position) Characteristic preferred



Fast Acting Actuator



Locate in Plant around chillers/pumps (preferrred) Energy saving



၁၇.၆.၄ Bypass Control Problems Bypass control ၾ

(complex



Chiller

flow

Magnetic

flow meter

Magnetic flow meter flow meter

(

)

(accuracy)

Elbow

Signal transmitter ( )

Valve

flow meter

ၾ ႔



valve calibration

(differential pressure across the valve) b

control loop tuning



Pump chiller

(minimum flow rate)

၏ design flow rate

(half)

၌ differential pressure

System ၾ

chiller

low load

bypass valve

chiller Control loop

tune chiller ႔

plant

control loop

tuning

pressure independent control valve

Pressure independent control valve (constant differential pressure) ( )

(flow)



system ႔

bypass control

control

control

- AHU

၊ AHU

bypass control

control (ဃ)

(complex) control system ႔

Bypass system

(nuisance) chiller trip

Manual reset ၾ



reset (out of service)

(operator)

ၾ hydraulically decouple

production

distribution



(flow rate) ၾ

(

) Bypass piping

( ) No-flow static head (from the building water column) ( ) Water 17-14



ၾ Pumping system



Chapter-17 Chilled Water System Configurations

D

h

chillers

႔ ၾ

chiller

(flow)

D

(number of operating



bypass pipe

restriction

Bypass piping ၌

(zero pressure loss) bypass piping





(restrictions)

- check valve

၁၇.၆.၅ Production Loop/Circuit



Primary Loop/Circuit Production loop

distribution loop

(independent chilled

water

Conventional

temperature

controller





၊ chiller (simplest)

႔ ၾ

chiller

leaving chilled water system temperature rise

၁၇-၁၅ Production loop Decoupled system

chiller



chilled water temperature

chiller

Distribution pump



distribution piping

secondary pump AHU/FCU

chiller water header

supply header water





terminal unit



Distribution system

(၁၇-၁၆)

distribution system flow control

Cooling coil

configuration

flow control valve



ၾ Load

cooling coil valve

three way valve Two-way modulating valve



Chiller

f

႔ system

-

pump

(energy consumption) variable speed drive distribution pump

Decoupled system ၾ 17-15

Chillers and Chilled Water Systems



AHU ၊ FCU ၊ CRAC unit

terminal equipment

(simultaneously) peak load load

load

(sum of the peaks load)





Variable flow system

႔ chiller ၊ pump

pump

pipe

(sizes)

load



႔ ၾ





over pumping

(pumping energy) AHU ၊ FCU ၾ

peak

Return water temperature



(return water temperature)

chilled water

cooling coil



ၾ ႔





chilled

water return system

part load condition ၌ return water

Counter flow cooling coil

design temperature

coil

chilled water

Return water chiller



၏ efficiency

Return water

system

configuration

၁၇.၆.၆ Secondary Loop Flow Control ၏

P configuration

ၾ Variable

terminal equipment

two-way automati

Variable Frequency Drive (VFD)



farthest point or last control valve and terminal ၌ Primary/secondary system P

P

primary variable flow design



two way

h

-

႔၏



S set point

SD

h

P V D

17-16



-h



Chapter-17 Chilled Water System Configurations

h



Pressure D

HVAC Controls and Building Automation Systems

S ၌

h

(minimum pressure

h



S

pressure differential sensor

D ၏

signal

System demand





open

control valve

system pressure difference) ၾ

pump speed

Part Distribution syste ၾ

distribution flow

Δ Consta -

flow constant ႔

valve

h

bypass port





terminal heat transfer device

Constan



Three way FCU

terminal heat exchange device (AHU/FCU)





ၾ ၏

supply temperature set point

S ၾ



temperature difference

flow installation cost ႔

heat



x h



(temperature difference h



pump System

efficienc

17-17

Chillers and Chilled Water Systems



၁၇-၁၆ Constant flow primary/secondary chilled water system Variable flow distrib P

Δ

-

modulating two-way S

E ES

S

.1–1

S

. .4.1

-

SD

(၁၇-၁၆)

constant primary and constant variable system

Constant speed primary pumps

၁၇-၁၈ VSD control

Seconadry chilled water p

supply tee

load terminal









chilled water c water p



၏ friction

၏h

seconadry chilled water c

h

AHU/



seconadry chilled water pump ၾ

pump curve

AHU/FCU/CRAC u

h

Primary chilled water p h



constant speed secondary pumps

၁၇-၁၇ Distribution loop and bypass pipe FCU/CRAC unit

D

႔၏

primary chilled water p s

၏h

primary

seconadry chilled

၏ friction

(

ၾ Primary chilled water pump ၏ Seconadry chilled water pump ၏ ၏ 17-18

h

၏ ၏



Chapter-17 Chilled Water System Configurations

S

h



chilled water flow rat

၏ cooling

၏ cooling ႔ ၾ

h



h Seconadry

h

Variable S

Frequency Drive (VFD)

D

SD

speed (chilled w

S



Variable







h



SD

part l

energy saving)

-

S

(pressure difference between the supply and return water piping)

va

variable sp ႔

differenti

Variable

Speed Drive SD

၁၇-၁၉(

)



h

၁၇-၁၉( )



high



raise) ၏ cooling

႔၏

Cooling

-way control

h

way control valve

two႔



differential pressure) seconadry chilled water pump (distribution pump ၏

speed)

distribution

႔ ႔

- ၁၇-၁၉- ) ႔



multiple distribution pump configuration) East building (A) ၊ ၊ B

B



17-19

Chillers and Chilled Water Systems







x



primary circuit (supply f

secondary circuit (demand f



P ႔

h

ၾ ၾ

၁၇-၂ Secondary flow (1200 GPM

၁၇.၆.၇ Secondary (Demand) Flow Secondary flow (1200 GPM

primary flow (800 GPM)

Primary (Supply) Flow





primary flow (1200 GPM



၁၇-

၂ (၁၇-၂ )

building cooling

water flow rate)

1

PM

Primary circuit (productio

1

h ႔ ၾ

1

PM





PM ႔

၌ chilled water

၁၇.၆.၈ Secondary (Supply) Flow Secondary flow (1200 GPM

17-20

4

p ၾ

၂၁)

(chilled

Primary (Demand) Flow primary flow (800 GPM

၁၇-



Chapter-17 Chilled Water System Configurations

၁၇-၂၁ Secondary circuit (demand) 1200 GPM > Primary circuit (supply) 800 GPM

၁၇-၂၂ Secondary circuit (demand) 600 GPM < Primary circuit (supply) 800 GPM Secondary 1,

b

chilled water flow rate)

PM

P

1 ၾ

h

PM

pump (၂)

PM

႔ ၾ (1200GPM - 800GPM)

400

4

GPM

႔ ၾ 17-21

Chillers and Chilled Water Systems



400 GPM



S

chilled water flow(1200)

chilled water flow

PM



h



႔ h

h



h

h

၁၇.၆.၉ Secondary (Supply) Flow

Primary (Demand) Flow

Secondary flow (600 GPM

primary flow (800 GPM

၁၇-၂၂ P



Secondary circuit (de

h

PM



(chilled water flow rate)

PM

႔ ၾ

GPM

(800-600)

႔ ၾ

GPM

secondary circuit (demand)



S

chilled water flow chilled water flow (800 GPM)

PM ၾ

h





h h

h





h

h D

h

၁၇.၆.၁ Primary-secondary system ၏ Primary-secondary system ၏ (၁)

Evaporator



(constant flow through evaporator)

Primary-secondary system

s

chiller ၏ evaporator



႔ Chiller evaporator l

Primary-secondary system

႔ primary loop

control

staging sequence

17-22

(freezing)

Load

Primary flow decouple

(၂)



(inadvertent shutdown) system flow

chilled water Chiller controls packages

Chiller

load



(၃)

Chapter-17 Chilled Water System Configurations

Primary-secondary system



႔ ၾ

system၊

system၊

ၾ (၄)

Total dynamic head

independent loop

၁၇.၆.၁၁ Primary/Secondary System







(Disadvantages)

Primary-secondary system ၏ (၁)

Δ s Primary-secondary system

evaporator

႔ ၾ

chiller water flow rate

႔ ႔ ၾ

(actual flow) load

flow rate flow

chilled water return

temperature C

secondary pump VSD ၾ

Primary loop

decouple





bypass

chilled water supply

return water

return water temperature

(၂)

(၃)

pump speed ႔

system efficiency

(Capital investment)

(Higher operating and energy costs) Primary-secondary system Primary loop

constant speed constant flow



Pump

(၄

variable speed pump off-peak load ၾ

(Requires more plant space) Primary pump

secondary pump

၁၇-၂၃ Primary secondary System



၁၇-၂၄ Variable Primary Flow (VFP) system 17-23

Chillers and Chilled Water Systems



Table 17-4 primary-secondary chilled water system ၏ Chiller flow

load flow



႔ (temperature differential)

equipment

system Thermal storage system

(sophisticated) control system

Water side economizer

၁၇-၂၅ Variable primary chilled water plant

၁၇.၇ Variable Flow Primary (၁)



chiller

(၂)

(Simplifies system design)

(၃)

(minimum flow)

variable flow modulating control valve

Bypass (၄)

(parallel)



parallel or series design) 17-24

(series)

(System can be



Chapter-17 Chilled Water System Configurations

Summary on Variable Primary Flow (VPF) Chillers

Pumps



Size equally with same WPDs (best)



Respect Min/Max Flows through chillers



Set Pump VSD Ramp function to about 10%/min (600 sec 0 to Max Speed)



Use Modulating Valves (preferred) on chiller evaporator headered pumping



Use 2 Position Valves (1 min stroke) on chiller evaporator dedicated pumping



VSD Controllers



Headered Pumping Arrangement (preferred)



Dedicated Pumping OK (over-size pumps)

2 Way Valves 

Select for Static, Dynamic, Close-off ratings (PSID) equal to pump SOH (plus fill pressure)



Range-ability 100 to 200:1



If Bypass – fast acting, linear proportion



If Coils –

“O -O ”

1 -15 min

intervals) Controls



Set-point far out in index circuit (lower the value, the better the pump energy)



Set Ramp function in VSD Controller (10%/min average)



Run 1 more pump than chillers (when headered)



Chillers On by common Supply Temp, Load, Amps, Adj Flow (Adj for Low Delta T)



Chillers Off by Amps, Load, Adj Flow (Adj for Low Delta T)



Over-pump Chillers to combat Low Delta T and get Max Cap out of chillers



Bypass controlled by Min flow (preferred) or Min WPD of largest chiller (locate in plant for best energy, but can go anywhere in system)

၁၇.၇.၁ Variable Primary Flow Only (VPF) Advantages (၁)

Lower Capital Cost Installed (vs Primary/Secondary)

(၂)

No secondary pumps/piping/valves/electrical to buy and install

(၃)

Fewer piping and electrical connections – less field labor

(၄)

No large Common pipe, but smaller Bypass pipe/valve/flow meter/controls

(၅)

Lower CHW Pumping Energy

(၆)

Potential Savings, may reduce pump horsepower and initial cost.

(၇)

Reference ARTI (Air Conditioning & Refrigeration Technology Institute)

(၈)

Estimated energy savings of 3 to 8 percent

(၉)

Estimating initial cost saving of 4 to 8 percent

(၁ ) Estimating life cycling saving cost 3 to 5 percent (၁၁) Smaller Footprint (vs Primary/Secondary) (၁၂) More space available or better access to the other equipment (၁၃) Higher Reliability (၁၄) Fewer mechanical components (၁၅) Any pump can serve any chiller 17-25

Chillers and Chilled Water Systems



(၁၆) Lower Capital Cost Installed (vs Primary/Secondary) (၁၇) No secondary pumps/piping/valves/electrical to buy and install (၁၈) Fewer piping and electrical connections – less field labor

၁၇.၇.၂ Variable Primary Flow Only (VPF) Disadvantages (၁) Potentially higher PSID rated 2-Way valves in system (၂) Requires more robust (complex and calibrated) control system (၃) Requires coordinated control of chillers, isolation valves, and pumps in sequencing (၄) Potentially longer commissioning time and start-up (ref ASHRAE Taylor article) (၅) Requires greater operator sophistication (၆) Sudden flow variation through the chiller (၇) More of an issue when additional machines are staged on (၈) More complexity with bypass control

၁၇.၈ Condenser Water Circuit h ႔ ၾ

h

၁၇-၂၆ Condenser water pump piping options ႔

condenser water piping arrangement

Option A Dedicate a pump for each condenser (၁၇-၂၆-A) Option B Provide a common header at the pump discharge and two-way automatic isolation valves for each condenser (၁၇-၂၆-B) Option C Provide a common header with normally closed (NC) manual isolation valves in the header between pumps (၁၇-၂၆-C) 17-26





Chapter-17 Chilled Water System Configurations

Option A -

(Advantages)

(၁) Chiller

condenser

Option A

head

(pressure drop)

pump



option B drop

Option B

pump

chiller



condenser pressure

၏ head

Pressure drop

balancing valve

(၂)

control Chiller



Chiller

pump

pump

refrigerant





pump down

(၃) Pump



ၾ chiller

pump

trip

chiller



chiller

Pump

Option B

pump

chiller

chiller ၊

Option B -

(Advantages)

(၁) Redundancy

Option A Option B

(၂) Option B

pump

h

chiller



႔(standby pump)

Option A

(standby pump)



႔(standby pump)

Option B (၃) Isolation valve

condenser pump

chiller

(၄) Water side economizer

Water side economizer

(cold weather) (၅) Option C

headered pump

manual isolation valve

Option A

Capacity Option A

Chiller

chiller

standby pump

pump

(၆) Option A

Chiller ၾ

pump

manual isolation valve

(one to one)

Option C

Head pressure control

Option B

standby pump

Option B

၁၇.၈.၁ Refrigerant Head Pressure Control Chiller Screw chiller

၌ minimum refrigerant head (lift) evaporator

condenser



minimum refrigerant head

Hermetic centrifugal chiller ၊ magnetic bearing chiller minimum refrigerant head



(၂)

ၾ ၾ

refrigerant head pressure

17-27

Chillers and Chilled Water Systems



Chiller

cooling tower basin chiller



head pressure safeties

start-up head



chiller

Low

Head pressure control

(manufacturer)

Water side economizer

minimum refrigerant head

Head pressure control temperature

၁၇.၈.၂

cold starts

cooling tower water



head pressure

h



Minimum Flow Rates Cooling tower



distribute)

fill



(uniformly

Fill (minimum flow rate) (minimum flow rate) ႔



fill (dry surface)









(heat reject fill

၁၇-၂၇ Cooling tower cell isolation options Option A (left)

No isolation valve

Option B (center)

Auto-isolation valves on supply only

Option C (right)

Auto-isolation valves on supply and suction

Option A Option A

efficient

Cell Fan ၏

SD

(speed)

cooling tower

ၾ 25%

ၾ Option B Option B

automatic isolation valve

basin level

supply line

equalizer

- tower cell (၃) cell (၂)

17-28



Duty (peak heat rejection)

equilizer isolation valve

Cell

Suction ၾ

cell

automatic



Chapter-17 Chilled Water System Configurations

equalizer equalizer

cell



(undersized) supply cell ) cell Overflow pipe ႔ ၾ

(overflow)

make up water valve

make up water





equalizer

Option C Option C ၌ automatic isolation valve

supply

suction line

Automatic valve equalizer

Valve ၊





Cooling tower

Option C equalizer

၁၇.၉ Low Delta – T Syndrome Chiller and leaving)

၏ capacity

flow rate

chilled water temperature difference (entering

႔၏

Constant-flow system

peak design condition

(flow rate)

∆T (difference between the chiller supply and return) Air-conditioning 1%

(applications)



(operational hours) Three-way valve



၏ 99%

Δ low Δ



Bypass

operating temperature

(phenomenon)

HVAC industry

part load

chilled water bypass

chilled water return temperature differential

system

load (BTU/hr)







chiller

(rated)

capacity Chiller

chilled water leaving temperature

control

Cooling load

chilled water supply temperature ၊ chilled water return temperature ၾ

၁၇.၉.၁ Low Delta-

chilled water return temperature

Δ

- chiller 52°F





chiller ၏ loading

Syndrome ၏

Constant flow system temperature

chilled water flow

low Δ



design return water temperature 55°F h

loading

႔ return water percentage (%

17-29

Chillers and Chilled Water Systems



[ Where:

]

CHL (%): Percent chiller loading CWRTR: Real chilled water return temperature CWSTD: Design chilled water supply temperature CWRTD: Design chilled water return temperature

h

Δ

Design

= 55- 45

1 °

Δ

Actual

[ chiller

= 52 – 45 = 7°F: ]

rated capacity ၏ 70%

chiller



Chiller

tower

pump

cooling



၁၇.၉.၂ Chiller Performance centrifugal chiller



performance (၁) h Evaporator

l

chilled water leaving temperature (relative humidity )

reset

65%

(၂) Condenser water entering temperature Chiller manufacturer (၃) Fouling factor 0.00025 h ft2 °F/Btu (0.000044 m2 °C/W)

Condensing surface fouling factor fouling factor

၊ tube cleaning

၊ outdoor air

brush cleaning system (၄) Evaporator ၏ surface area

condenser ၏ surface area

၊ condenser

chiller efficiency evaporator

contamination

႔ evaporator

(manufacturers) centrifugal chiller condenser

evaporator





condenser

compressor

minimum performance

႔ ၾ evaporator ၊ condenser

compressor



၁၇.၁ Series Chiller System Chiller

(series)

Chiller

၏ flow rate

၏ evaporator chiller

17-30

single pass

mixing problem system flow

႔ flow rate (၂) ႔





chiller



double pass

(series) ၾ

Chiller efficiency



Chapter-17 Chilled Water System Configurations

၁၇-၂၈ Series chillers ၾ

upstream chiller

water

(warmer temperatures) return

ၾ ၾ

(pipe in series)

chiller

(pressure drop)

pressure loss

Low flow system ၾ

[9°C]

႔ ၾ

chiller

System

total system

(series) (temperature difference)

16°F

(pressure loss)

၁၇.၁ .၁ Advantages and Disadvantages of Series Chillers Table 17-5 advantages and disadvantages of series chillers Advantages

Disadvantages

– Easier to control with simple control systems



Increased pumping requirements for chilled

water – Effective with different size chillers

– Chillers may not be interchangeable

– Utilize one stand-by pump – Good for large temperature differential systems (၁၇-၂၈)

(၁၇-၂၉) ႔

multiple chiller

chiller (၂)

(၁) Chilled water coil

(series)

(series) (higher temperature rise)

(lower water flow

rate) (၂)

(series)

chiller



(pressure drop)

pump head (၃) Part-load operation

control

(၄) Multiple-chiller plant

parallel

၁၇.၁ .၂ Series Counter Flow Series counter flow Downstream machine

energy

40°F [4.4°C] chilled water

Upstream machine

50°F 17-31

Chillers and Chilled Water Systems



[10°C] chilled water

Downstream machine

Upstream machine

႔ 85°F [29.4°C] condenser water

႔ condenser water



Condenser water ၾ



Single large chiller condenser water circuit compressor

(pumping costs)

chiller

condenser water flow direction



၌ lift

Chilled water





series-counter flow

duplex machine

Evaporator

duplex ၏

Efficiency

refrigerant circuit



ၾ System reliability

၁၇-၂၉ Series counter flow chillers

၁၇.၁၁ Chiller Staging Multiple chiller plant

chiller





(staging the chillers, on

or off) (၁) Primary loop

chilled water flow rate

(၂) System load (၃) Chiller

chiller(s) staging chilled water pump

Chilled water system

17-32

secondary loop

၊ condenser water pump cooling load

cooling tower



chilled water flow rate



Chapter-17 Chilled Water System Configurations

Where: •

:

B

•D

h ……

h

:

. 4

•S :

1

•S :

h

h

•Δ : h

1B

-°F)

. .

- T supply water] in °F

fluid (water flow rate) density

specific gravity

HVAC OR (1 ton of refrigeration = Heat extraction rate of 12000 BTU/hr) - chilled water system Chilled water supply temperature capacity

၏ chilled water flow rate 42°F

return temperature

6,000 GPM 54°F

cooling

refrigeration ton

GPM = 6,000

Δ

Supply water temperature = 42°F

LF

12 °F (54°F – 42°F) 4 Δ

41

PM

Return water temperature = 54°F

( design load Chilled water pump

)

(

)

chiller ၏ flow rate

chiller

Chiller ၏ output capacity Cooling load demand

temperature range (Δ ) ၏ flow rate return water temperature

return water temperature

17-33

Chillers and Chilled Water Systems



၁၇-၃ Chilled water plant

၁၇-၃၁ Chilled water plant with common header

၁၇-၃၂ Chilled water plant with common header (header pumps)

၁၇-၃၃ Chilled water plant (dedicated pumps) -End17-34