CALIFORNIA ECONOMIZER

CONTROLS Page # A Actuators   Damper...........................................................61-66   Direct Coupled................................
Author: Meredith Small
21 downloads 0 Views 6MB Size
CONTROLS

Page #

A

Actuators   Damper...........................................................61-66   Direct Coupled................................................65-66   Valve....................................................................66 Adapters   Burner Modernization...........................116, 118-119   Junction Block......................................................25   Thermocouple......................................................25 Air Pressure Switch...................................10, 111, 131 Aluminum Pilot Tubing.............................................69 Amplifiers, Flame Safeguard................75-76, 115, 117 Aquastat Controls.....................................................54 ASCO Valves..................................................123-124 AUBURN......................................................127-128 B BALABAN Ignitors.................................................93 Burner Nozzles......................................................129 Burners, Pilot.....................................................68, 111 C CALIFORNIA ECONOMIZER...........................95-102 CAM-STAT......................................................112-113 Carbon Dioxide Controller........................................50 Contactors, Furnas.........................................130-131 Controls   Aquastat...............................................................54   Burner.....................................................78, 116-118   Condenser Fan Speed....................................16-17   Electronic Modulating...........................................43   Enthalpy...............................................................53   Fan and Limit.............................55-56, 109, 112-113   Freeze Protection.................................................30   Heat Pump Defrost Control...................................32   Humidity..........................................................51-53   Ignition.......................................................24-25, 81   Liquid Level.............................................................7   Packaged Terminal...............................................33   Pressure    Encapsulated.................................................8-9    JOHNSON CONTROLS...............8, 10, 12-15, 20    RANCO......................................................27-28   Temperature.........1-7, 26, 28-31, 33, 41-47, 106-107 D Damper Motors...................................................61-66 Damper Linkage.................................................66-67 Defrost Clocks................................................131-137 Defrost Thermostats...............................................132 Defrost Timers, Domestic......................................131 Detectors, Flame...............................................71, 111 Draft Controls.........................................................113 E Economizer Logic Modules.................................48-49 Electric Heat Sequencers......................................109 Enthalpy Controls.....................................................53

Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

SUBJECT INDEX

Page # F Fan and Limit Controls...................55-56, 109, 112-113 Fan Relays..........................................................58-59 Fan Timers, Electronic..............................................82 Fan Speed Control..............................................16-17 FIELD CONTROLS INC........................................113 Filter, Fuel Oil.........................................................125 FIREYE...........................................................114-121 Flame Detectors   Cadmium Cell................................................71, 111   Ultra-Violet...........................................................71 Flame Rods............................................................127 Flame Safeguard..................................71-80, 114-121   Amplifiers...........................................75-76, 115, 117   Controls..................................72-74, 76-79, 114-118   Display Module...............................................80, 117   Programmers.....................................77, 79, 114-117   Testers..........................................................73, 121 Float Valve, HONEYWELL.......................................90 Fluid Power Gas Valve Actuators........................85-86 FURNAS........................................................130-131 G Gas Pressure Regulators......................................122 Gas Valves...................................85-92, 110, 123-124 Guards, Thermostat..................................................34 H Heat Pump Defrost Control......................................32 HONEYWELL   Actuators/Damper Motors...............................61-66   Aquastat Controls.................................................54   Damper Linkages............................................66-67   Enthalpy Control...................................................53   Fan & Limit Controls.......................................55-56   Fan Centers.....................................................58-59   Flame Safeguard Controls.............................71-80   FocusPRO......................................................37-38   Gas Valves......................................................85-90   Humidity Controls............................................51-53   Line Voltage Thermostats................................36,40   Motorized Valves.............................................83-84   Pilot Ignition Modules..........................................81   Potentiometers................................................67-68   Pressuretrol® Controllers......................................60   Relays.............................................................58-59   Temperature Controls......................................41-47   Thermostats....................................................35-40   Thermostat Guards..............................................34   Ventilation Controls.........................................48-50   VisionPRO............................................................38   Zone...........................................................67, 83-84 Hoses - Pressure Controls.......................................15 HSI Ignitors..............................................................93 I Ignitor Adjusting Tool..............................................128 Ignitors.........................................................70, 93, 127 Ignition   Controls..................................24-25, 81, 94, 107-108   Terminals............................................................128   Transformers.................................................70, 113   Wire............................................................128-129 Immersion Wells.......................................................42 Infinity Control Switch...............................................91 Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

SUBJECT INDEX

Page # J JARD MAGNETICS Transformers...........................57 JOHNSON CONTROLS.......................................1-26   Defrost and Fan Delay Controls.............................4   Electronic Temperature Controls.....................4, 6-7   Fan Speed Controls.........................................16-17   Flow Switches........................................................7   Hoses - Pressure Control....................................15   Oil Pressure Controls.........................................9-11   Pilot Ignition Control........................................24-25   Pressure Controls............................8, 10, 12-15, 20   System 350.....................................................17-20   Temperature Controls..........................................1-7   Variable Frequency Drives..............................16-17   Water Regulating Valves.................................21-23   Water Valve Flange Kits........................................23 M MAXITROL............................................................122 MONARCH MANUFACTURING WORKS INC......129 N NORTON Ignitors...................................................93 Nozzles, Oil Burner................................................129 O Oil Pressure Controls............................................9-11 P PARAGON ELECTRIC...................................132-136 Pilot Burners......................................................68, 111 Pilot Relight Kit.........................................................94 Pilot Tubing, Aluminum............................................69 Potentiometers..................................................67-68 PRECISION Time Clocks......................................137 Pressure Controls   Encapsulated......................................................8-9   JOHNSON CONTROLS..................8, 10, 12-15, 20   RANCO...........................................................27-28 R RANCO..............................................................26-33   Defrost Control.....................................................32   Pressure Controls...........................................27-28   Reversing Valves..................................................32   Temperature Controls..........................26, 28-31, 33 Relays   Electric Heat.........................................................74   Fan.................................................................58-59   HONEYWELL.................................................58-59 ROBERTSHAW   Gas Valves......................................................91-92   Ignition Modules...................................................94   Thermostats.........................................................91 RW BECKETT................................................125-127 S Sequencers, Electric Heat.....................................109 Snap Disc Controls................................................109 Switches   Air Pressure.....................................10, 60, 111, 131   Flow........................................................................7   Pressure.............................................................131 Synchronous Time Controls...................................131 System 350.........................................................17-20

Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Page # T Temperature Controls...1-7, 26, 28-31, 33, 41-47, 106-107 Testers   Flame Safeguard..........................................73, 121   Flame Simulator...................................................72 Thermocouples........................................................69 Thermopile Generators.....................................68, 111 Thermostat Guards..................................................34 Thermostats   HONEYWELL.................................................35-40   JOHNSON CONTROLS.....................................1-7   ROBERTSHAW....................................................91   WHITE-RODGERS.....................................103-106 Time Clocks   PARAGON..................................................132-136   PRECISION.......................................................137 Time Controls..................................................131-132 Time Switches, Electronic...............................131-132 Timers   Defrost........................................................131-137   Delay..................................................................113   Fan.......................................................................82 Transformers......................................................56-57 Tubing, Aluminum....................................................69 U Ultra Violet Flame Detectors....................................71 Universal Ignition Module.........................................81 V Valves   3-Way Mixing and Diverting.................................84   Butterfly................................................................87   Gas............................................85-92, 110, 123-124   Industrial Gas.......................................................87   Oil Burner Control.........................................83, 129   Reversing.............................................................32   Temperature Actuated Water................................22   Thermostatic Radiator..........................................82   Water Regulating............................................21-23   Zone....................................................67, 83-84, 109 W Water Regulating Valves.....................................21-23 WESTWOOD.........................................................127 WHITE-RODGERS   Air Switch............................................................111   Fan Centers..........................................................59   Flame Sensors...................................................108   Gas Valves..........................................................110   Ignition Controls..........................................107-108   Temperature Controls..................................106-107   Thermostats................................................103-106 Winter Watchman....................................................35 Wires, Ignition.................................................128-129 Z Zoning Systems................................................95-102

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

JOHNSON TEMPERATURE CONTROLS

A11 SERIES LOW TEMPERATURE CUTOUT TEMPERATURE MAKE UP AIR HEATER COIL Order Number Switch Action Range (°F)

Differential

Bulb and Capillary

A11A-1C

spst open low

35 - 45

Manual reset

A11B-1C

spst open low

35 - 45

8°F fixed

20’ of 1/8” OD tubing 4’ cap 20’ of 1/8” OD tubing 4’ cap

Note: Bulb not supplied.

Max. Bulb 120 Vac (amps) Temp. (°F) 250 16.0 250

16.0

A19 SERIES REMOTE BULB CONTROLS WIDE RANGE ADJUSTABLE DIFFERENTIAL Order Number A19ABA-40C A19ABC-24C A19ABC-36 A19ABC-37C

Switch Bulb Well Number Max. Bulb Range (°F) Differential (°F) Bulb and Capillary Action (not supplied) Temp. (°F) spst -30 - 100 3 - 12 3/8” x 4” WEL14A-602R 140 spdt -30 - 100 3 - 12 3/8” x 4” WEL14A-602R 140 spdt -30 - 100 3 - 12 3/8” x 4” WEL14A-602R 140 spdt -30 - 100 3 - 12 3/8” x 4” WEL14A-602R 140

120 Vac (amps) 16.0 16.0 16.0 16.0

FIXED DIFFERENTIAL Switch Action spdt

Order Number A19AAF-12C

Range (°F) Differential (°F) 25 - 225

Bulb Well Number (not supplied) WEL14A-602R

Bulb and Capillary

3 1/2

3/8” x 3”

Max. Bulb Temp. (°F) 275

120 Vac (amps) 6.0

CASE COMPENSATED FIXED DIFFERENTIAL Order Number

Switch Action

Range (°F)

Differential (°F)

Bulb and Capillary

A19AAD-12C

spst open low

-30 - 50

3 1/2

3/8” x 4”

Bulb Well Number (not supplied) WEL14A-602R

Max. Bulb 120 Vac (amps) Temp. (°F) 6.0

CLOSE DIFFERENTIAL Order Number

Switch Action

Range (°F)

A19AAD-5C A19AAF-20C A19AAF-21C

spst open low 30 - 50 milk cooler spdt -30 - 100 spdt 40 - 90

Differential (°F) Bulb and Capillary 2 2 1/2 1 1/2

3/8” x 2 5/8” 3/8” x 4” 3/8” x 5 3/4”

Bulb Well Number (not supplied) WEL16A-601R WEL14A-602R WEL14A-603R

Max. Bulb 120 Vac (amps) Temp. (°F) 190 6.0 140 6.0 140 6.0

Bulb Well Number (not supplied) WEL14A-602R WEL14A-602R WEL14A-602R

Max. Bulb Temp. (°F) 140 140 290

MANUAL RESET Order Number

Switch Action

A19ACA-14C A19ACA-15C A19ADB-1C

spst open low spst open low spst open high

Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

Range (°F) Differential (°F) -30 - 100 -30 - 100 100 - 240

604.202.4853 905.988.1724

Bulb and Capillary

Manual reset Manual reset Manual reset

Vancouver Island Windsor

604.282.0118 519.251.9925

3/8” x 4” 3/8” x 4” 3/8” x 3 1/2”

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

120 Vac (amps) 16.0 16.0 10.0

306.373.9227

1

JOHNSON TEMPERATURE CONTROLS

A19 SERIES HIGH RANGE TEMPERATURE CONTROLS HIGH RANGE Order Number A19AAB-10C A19AAC-9C A19AAB-38C A19ADB-31C A19ADC-31C

Application

Range (°F)

Differential

Bulb and Capillary

10 °F

spst, open high 200 - 550 oven thermostat spdt 100 - 240 spst, NEMA 1 Manual reset, spst, NEMA 1 Manual reset, spdt, NEMA 1

90 - 325 90 - 325

1 15’ -

3/16” x 6” copper, 8’ cap 3/8” x 3 7/8” copper, 6’ cap* 1/4” x 5”, 15’ cap 10’ cap

100 - 240

-

10’ cap

5 °F

Bulb Well Number 120 Vac Max. Bulb (not supplied) (amps) Temp. (°F ) 16.0 620 WEL14A-602R

16.0

290

-

-

-

-

-

-

1. With 3″ bulb support.

A19 SERIES THERMOSTATS FOR CROP DRYING Order Number

Switch Action

Range (°F)

Differential (°F)

Bulb and Capillary

A19AAE-3C A19ABB-2C

spst open high spst open high

50 - 180 50 - 200

2 fixed 6 - 24

1/8” x 1 1/4” 10’ capillary .290” x 2 1/2” 10’ capillary

Max. Bulb Temp. (°F) 200 240

Electrical Rating 120 Vac 6.0A 10.0A

A19 SERIES SPECIAL PURPOSE THERMOSTATS RUBBER COATED BULB AND CAPILLARY Order Number A19AAF-4C

Switch Action spdt

Range (°F) 40 - 90

Differential (°F) Bulb and Capillary 120 Vac Max. Bulb Temp. (°F) 1 1/2 3/8” x 5 3/4” rubber 6.0A 140 coated 6’ capillary

A19 SERIES HOT WATER TEMPERATURE CONTROLS SPDT WELL IMMERSION Order Number A19ABC-11C A19ABC-12C

Application

Switch Action

Range (°F)

Differential (°F)

Open high, open low, (operating and circulator) Remote mfg. (operating and circulator)

spdt

100 - 240

6 - 24

spdt

100 - 240

6 - 24

Well Connection Size Max. Bulb Temp. - NPT (°F) 1/2 290 1/2” 8’ capillary

290

A19 SERIES HOT WATER STRAP-ON TEMPERATURE CONTROLS UNIVERSAL REPLACEMENT Order Number A19DAC-1C

Burnaby Kitchener

2

Switch Action spdt

604.298.4472 519.748.0961

Interior BC St.Catharines

Range (°F) 100 - 240

604.202.4853 905.988.1724

Differential (°F) Range Adjuster 10 fixed Convertible

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

120 Vac 10A

Edmonton Ottawa

Mounting Clamp-on strap

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

JOHNSON TEMPERATURE CONTROLS

A19 SERIES RAINPROOF ENCLOSURE INDUSTRIAL THERMOSTAT Order Number A19ANC-1C

Switch Max. Bulb Range (°F) Differential (°F) Bulb and Capillary Bulb Well Number Action Temp. (°F) spdt 0 - 150 6 .290” x 2 1/2” 10’ capillary WEL11A-601R 190

120 Vac 16.0A

WEL SERIES BULB WELLS FOR REMOTE BULB THERMOSTATS AND WATER VALVES Inches Pipe Thread (inches) Order Number WEL11A-601R WEL14A-602R WEL17A-600R

A

B

2 3/8 2 5/16 4 15/16 1 13/16 10 7/16 3/4

C

Material

Inside D Outside E Connector

.299 .430 .763

1/2

1/2 1/2 3/4

Brass Brass Malleable

Tube Copper Copper Copper

Max. Temp. Max. Pressure Solder Joint Plating (°F) (psig) 250 300 Soft 250 300 Silver Brite-Dip 250 250 Silver Tin

A19 SERIES COILED BULB THERMOSTATS VENTILATING, HEATING Order Number A19BAC-1C

Switch Action spdt

Range (°F) 30 - 110

Differential (°F) 3 1/2 fixed

Bulb and Capillary 1 3/8” x 2 1/4” coiled

Max. Bulb Temp. (°F) 140

120 Vac 16.0A

COOLING Order Number A19BBC-2C

Switch Action Range (°F) spdt -30 - 100

Differential (°F) Bulb and Capillary 3 - 12 1 3/8” x 2 1/4” coiled

Max. Bulb Temp. (°F) 140

120 Vac 16.0A

FLANGE MOUNTED DUCT THERMOSTATS FOR ROOF TOP UNITS, MAKE-UP HEATERS, DUCT HEATERS, AND AIR HANDLING SYSTEMS Flat flange mounting with special coil element permits proper positioning of the sensing bulb in the air stream. Order Number A19EAF-2C

Stages 1

Switch Action spdt

Range (°F) 30 - 110

Differential (°F) Electrical Rating Max. Bulb Temp. 2 6A @ 120V 140

AGRICULTURAL/INDUSTRIAL THERMOSTAT WITH NEMA 4X ENCLOSURE

The A19PRC is a rain tight single stage electromechanical thermostat designed for heating and ventilation applications. Order Number A19PRC-1C

Switch Action Spdt

Range (°F) 30 - 110

Differential (°F) 3 - 12

Bulb and Capillary 1 3/8” x 2 1/4” coiled

Range Adjuster Knob

A19 SERIES WATER CHILLERS WITH LOCKED CUTOUT ADJUSTABLE CUT-IN Order Number

Switch Action

A19ZBA-1C

spst close high, open low

Range (°F) Differential (°F) 38 - 80

8 - 40

Includes: FTG13A-600R packing nut.

Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

Bulb and Capillary 3/8 x 3 7/16” 6’ capillary

604.282.0118 519.251.9925

Calgary North Bay

Bulb Well Number (not supplied) WEL14A-602R

403.214.2134 780.476.0800

Edmonton Ottawa

Max. Bulb Temp. (°F) 140

780.451.4744 613.742.0083

Range Adjuster Knob

Saskatchewan www.isc.tv

120 Vac 16.0A

306.373.9227

3

JOHNSON TEMPERATURE CONTROLS A19 SERIES DEFROST DURATION AND FAN DELAY Order Number Switch Action Range (°F) A19ZBC-2C

spdt

45 - 85

Fan delay temperature is factory set at 25°F.

Bulb and Electrical Rating Max. Bulb Temp. (°F) Range Adjuster Capillary @ 120 Vac 1 9/54” x 3 1/8” 140 Knob 16.0A table 6 6’ capillary

A319 ELECTRONIC TEMPERATURE CONTROLS

Line voltage single-stage electronic temperature control with single-pole, double-throw relay output and LED indication. Designed with heating or cooling modes of operation, adjustable differential, and an interchangeable temperature sensor. Couples electronic accuracy with remote sensing capability in a NEMA 1 high-impact plastic enclosure suitable for surface or DIN rail mounting. Order Number A319ABC-24-01

Description A319 temperature control with sensor (120 or 240 Vac) set point range -20°F to 100°F, differential range 1°F - 30°F

ACCESSORIES Order Number WEL11A-601R BKT287-1R BKT287-2R PLT344-1R

Description Immersion well for use with TE-6300-608, use with thermal compound 12” long DIN rail for use with A319 36” long DIN rail for use with A319 End clamps, (2) for DIN rail mounting of A319 controls

A419 ELECTRONIC TEMPERATURE CONTROL WITH DISPLAY AND SENSOR

A419 electronic temperature control with display and sensor. Features: lockable front-panel touchpad for setup and adjustment, liquid crystal display for viewing the temperature and status of other functions; LED indicates the controls output relay (On/Off) status; available in 24 VAC or 120/240 VAC models. Order Number A419ABC-1C A419AEC-1C A419GBF-1C A419GEF-1C

Enclosure NEMA 1 NEMA 4X NEMA 1 NEMA 4X

Voltage 120 or 240 Vac, 60 Hz 120 or 240 Vac, 60 Hz 24 Vac, 50/60 Hz, Class 2 24 Vac, 50/60 Hz, Class 2

Set Point Range -30°F - 212°F (-34°C - 100°C) -30°F - 212°F (-34°C - 100°C) -30°F - 212°F (-34°C - 100°C) -30°F - 212°F (-34°C - 100°C)

Differential Range 1° - 30° 1° - 30° 1° - 30° 1° - 30°

PARTS & ACCESSORIES Order Number A99BB-200C A99BA-200C A99BB-25C BKT287-1R BKT287-2R PLT344-1R CLK350-2C WEL11A-601R

Burnaby Kitchener

4

604.298.4472 519.748.0961

Description PTC sensor with 6.5’ (1.98 m) leads PTC sensor with 6.5’ (1.98 m) shielded leads PTC sensor with 9” (0.25 m) leads 35 x 7.5 mm, 0.305 m (12”) long DIN rail 35 x 7.5 mm, 0.914 m (36”) long DIN rail Two end clamps, for DIN rail mounting 7-day programmable digital clock; electronic switch output Immersion well (used with thermal compound)

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

JOHNSON TEMPERATURE CONTROLS

A28 TWO STAGE TEMPERATURE CONTROLS ADJUSTABLE INTERSTAGE DIFFERENTIAL WIDE RANGE Order Number A28AA-28C A28AA-29C A28AA-36C A28AA-37C A28AJ-4C

Switch Differential / Bulb and Bulb Well Number Range (°F) (spdt) Adjusted Stages Capillary (not supplied) 2 30 - 110 3.5 / 2 - 7 12’ averaging bulb, 6’ capillary 2 -30 - 100 5/2-7 3/8” x 4 1/16”, WEL14A-602R 8’ capillary 2 40 - 90 3/2-7 3/8” x 6”, 6’ capillary 2 60 - 140 5/2-7 3/8” x 4”, 6’ capillary WEL14A-602R 2 20 - 80 2/2-7 3/16” x 22”, 6’ capillary

Bulb Range 120 Vac Temp. Adjuster (amps) 140 Screwdriver 16.0 slot 140 Convertible 16.0 140 230 140

Knob Knob Knob

16.0 16.0 6.0

A28 TWO STAGE AGRICULTURAL THERMOSTAT WITH NEMA 4X ENCLOSURE

Designed for use in agricultural and industrial applications that require compliance with Article 547 of the National Electrical Code. Differential Fixed (°F) Order Number Switch Action Range (°F) Each Stage Between Stage Bulb and Capillary Range Adjuster A28PJ-1C 2 30 - 110 2 2 adjusted 1 3/8” x 2 1/4” coiled Knob

A28 TWO STAGE FLANGE MOUNTED DUCT THERMOSTATS

These duct thermostats are used on roof top units, make-up heaters and air handling systems of all types. They have spdt snap-acting contact units and are unaffected by barometric pressure or cross ambient temperatures. Differential Fixed (°F) Order Number Stages Switch Action Range (°F) Each Stage Between Stage Max. Temp. @ Bulb (°F) A28AK-1C 2 2 30 - 110 2 3 140 Electrical ratings: 6.0A @ 120 Vac

A36 SERIES 4-STAGE REMOTE BULB THERMOSTATS

Open construction for use in panel mounting. Order Number Switch Action Range (°F) A36AHA-50C

4 spdt switches

55 - 95

A36AHB-33C

4 spdt switches

0 - 70

A36AHA-52C

4 spdt switches

55 - 95

A36AHA-58C

4 spdt switches

0 - 70

Differential Fixed

Bulb and Capillary

2°F each stage 1 1/2°F between stages 2°F each stage 2 1/2°F between stages 2°F each stage 1 1/2°F between stages* 3°F each stage 2 1/2°F between stages^

3/8” x 5” 18” capillary w/12” nylon armour 3/8” x 4 3/4” 15’ braid armour capillary 3/8” x 5 1/4” 6’ capillary w/12” nylon armour 3/8” x 4” 15’ braid armour capillary

Calibrated at mid-switching point – computer room or comfort control Calibrated at low-switching point – special close control chiller applications Calibrated at low-switching point – standard chiller applications Maximum bulb temperature: 120 °F in operation; 140 °F when shipping

Bulb Well Number (not supplied) WEL14A-603R WEL14A-602R WEL14A-603R WEL14A-602R

ELECTRICAL MOTOR RATINGS: FULL LOAD Order Number A36AHA A36AHB

Burnaby Kitchener

604.298.4472 519.748.0961

120 Vac 10.0A 6.0A

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

208 Vac 6.9A 3.4A

604.282.0118 519.251.9925

Calgary North Bay

240 Vac 5.0A 3.0A

403.214.2134 780.476.0800

Edmonton Ottawa

277 Vac -

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

5

JOHNSON TEMPERATURE CONTROLS

A72 SERIES TWO POLE HEAVY DUTY TEMPERATURE CONTROLS ADJUSTABLE DIFFERENTIAL Order Number Switch Action Range (°F) Differential (°F) A72AA-1

dpst close high open low dpst close high open low

A72AA-2C

-30 - 30

4 - 40

15 - 55

3 - 30

Bulb and Electrical Rating Maximum Bulb Range Adjuster Capillary @ 120 Vac Temp (°F) 3/8” x 3” Screwdriver slot 24.0A 200 6’ capillary 3/8” x 3” Screwdriver slot 24.0A 200 6’ capillary

ELECTRONIC TEMPERATURE/DEFROST CONTROL WITH RELAY PACK

The MR series temperature controls are designed for use with hot gas or electric heat defrost in both refrigeration and freezer units. Either time or temperature based defrost termination may be selected. The MR series incorporates control functions such as compressor control, defrost, fan and alarm management. Features: Single package provides the functionality of multiple components at a cost-effective price. Mounting flexibility allows the control and relay pack to be mounted together or separately, facilitating multiple configurations. Accurate, interchangeable temperature sensor provides reliable control performance with up to 300 ft. of wiring. Easily readable temperature display can show either evaporator or process temperature at the touch of a button. Heavy duty relays allow direct control of compressors, fans, defrost heaters and alarms. Alarm management functions provide both local alarm codes and a relay closure that can be used to trigger a remote alarm or a dial-out modem. Applications: These relay pack mounted controls provide direct control of compressors up to 2 hp, electric heater loads of up to 20 amperes, and evaporator fan loads of up to 3/4 hp. The need for separate relays is eliminated in these applications. In addition, the MR4PMUHV controls combine the functionality of an electromechanical thermostat, mechanical clock, defrost termination device and temperature readout device with the accuracy of electronic technology. Order Number MR4PMUHV-12C

Description

Voltage

Relay pack defrost control with two A99 sensors

120/240 Vac

Power Consumption 10VA @ 240 Vac 5VA @ 120 Vac

Ambient Operating Conditions (°F) ± 1.8°F/± 1°C 14 - 111°F Accuracy

H x W x D (in) 7.94 x 3.6 x 2.4

MR TEMPERATURE STAGE CONTROL MODULES

The MR series controls are versatile, microprocessor-based, multifunction, programmable temperature controls. Depending on the model chosen, the MR series controls can also manage alarm, defrost cycle (active or passive defrost) and evaporator fan functions. The MR series controls have large red LED displays. These compact controls are available in panel mount and DIN rail mount varieties. The MR series controls use the A99B temperature sensors, which allow remote mounting of the display unit. Features: Allows adjustment of control settings to meet application needs. Provides alarm codes and an alarm output relay that can be used to trigger a remote alarm or dial-out modem. Displays temperature and other functions quickly and clearly. Allows user to disable programming buttons and deter accidental or unauthorized changes. Provides accurate control performance with up to 300 feet of wiring (adjustable temperature offset is provided for longer wiring). Checks control operation by cycling all outputs and testing all LEDs. Order Number Description MR2PM24-11C MR2 Panel Mount Control, A99BB-200C sensor included MR2DR24-11C MR2 DIN Rail Control, A99bb-200C sensor included MR4PM24-12C MS4 Panel Mount Control, A99BB-200C sensor included MR4DR24-12C MS4 DIN Rail Control, A99bb-200C sensor included

Ship Weight (lbs) 0.53 0.79 0.90 1.17

ACCESSORIES Order Number A99BA-200C A99BB-200C A99BB-300C A99BB-500C A99BB-600C Burnaby Kitchener

6

604.298.4472 519.748.0961

Description Temperature sensor range: -40 - 212°F. Cable length and type: 6 1/2’ shielded Temperature sensor range: -40 - 212°F. Cable length and type: 6 1/2’ PVC Temperature sensor range: -40 - 212°F. Cable length and type: 9 3/4’ PVC Temperature sensor range: -40 - 212°F. Cable length and type: 16 3/8’ PVC Temperature sensor range: -40 - 212°F. Cable length and type: 19 1/2’ PVC Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

JOHNSON TEMPERATURE CONTROLS

MS TEMPERATURE STAGE CONTROL MODULES

The MS series temperature controls are versatile, microprocessor-based, multifunction, programmable temperature controls. They are designed for single and multiple stage temperature control applications. Depending on the model selected, the MS series controls can operate in direct mode, reverse mode, deadband mode and independent mode. The MS series controls have large, easy-to-read, red LED displays. Features: programmable functions allow adjustment of control settings to meet application needs; alarm management function provide visible alarm codes on the display; easily readable LED display shows temperature and functions quickly and clearly; programming button lockout allows user to disable programming buttons to deter accidental or unauthorized changes; accurate temperature with up to 300’ of wiring (an adjustable offset is provided for longer wiring); self-test procedure checks control operation by cycling all outputs and testing all LEDs. Order Number Description MS1DR24T-11C MS1 single stage, DIN rail mount temperature control, A99BB-200C sensors included, 24V MS2DR24T-11C MS2 two-stage, DIN rail mount temperature control, A99BB-200C sensors included, 24V MS2PM24T-11C MS2 two-stage, panel mount temperature control, A99BB-200C sensors included, 24V MS4DR24T-11C MS4 four-stage, DIN rail mount temperature control, (2) A99BB-200C sensors included, 24V MS4PM24T-11C MS4 four-stage, panel temperature control, (2) A99BB-200C sensors included, 24V

Ship Weight (lbs) 0.75 0.79 0.53 1.17 0.9

FLOW SWITCHES

F61 SERIES FLOW SWITCHES LOW FLOW RATE SPDT

For liquids not injurious to the brass and phosphor bronze parts. SPECIFICATIONS: Minimum Liquid temperature: 32°F Ambient temperature: 32 – 180°F Order Number F61KD-4C

Inlet / Outlet Size Female NPTF (in) 3/4 x 3/4

Enclosure NEMA Type 1

Adjustment Range - GPM R to Y Closes R to Y Opens Max. Liquid Flow Increase Flow Decrease Temp. (°F) Min. 0.6 Max. 1.1 Min. 0.3 Max. 0.9 250

Max. Liquid Pres. (psig) 150

Electrical Motor Ratings: Full Load: 16.0A @ 120 Vac; 8.8A @ 208 Vac; 8.0A @ 240 Vac.

F61 SERIES FLOW SWITCH STANDARD FLOW RATE SPDT For liquids not injurious to the brass and phosphor bronze parts. Liquid Temperature °F Order Number

Pipe Connection (in)

Enclosure

1 MNPT 1 MNPT

NEMA 1 NEMA 4

F61KB-11C F61MB-1C

Maximum Liquid Pressure (psig) 150 150

Minimum

Maximum

32 -20

250 250

Ambient Temperature Range °F 32 - 180 32 - 180

Electrical Motor Ratings: 1 HP @ 120 Vac, 208 Vac, or 240 Vac Full Load: 16.0A @ 120 Vac; 8.8A @ 208 Vac; 8.0A @ 240 Vac. Includes: 3″ and 6″ paddles (may be trimmed).

REPLACEMENT PADDLES FOR F61KB, F61MB AND F62 SERIES Order Number KIT21A-601

Description 6” paddle kit for Series F61

F63 SERIES LIQUID LEVEL FLOAT SWITCHES FOR CLOSED TANKS Minimum tank diameter: 9 inches Order Number F63BF-1C

Switch Type of Action Enclosure spdt Vapour tight

Pipe connection: 1” NPT brass Liquid Temp. (°F) Max.

Min.

250

-20

Note: Not for use with hazardous fluids or in hazardous atmosphere. Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

Max. Ambient Temperature (°F) 180 604.282.0118 519.251.9925

Calgary North Bay

Max. Liquid 120 Vac Pressure (psig) 100 16A 403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

7

JOHNSON PRESSURE CONTROLS AND SWITCHES P10 SERIES LOW PRESSURE CONTROLS SINGLE- OR TWO-STAGE Maximum allowable pressure: 150 psig Order Number

Stages

Contact Action

Range (psig)

1 1

spdt spdt

3 - 20 2 - 20

P10BC-7C P10BG-3C

Factory Setting Switch PSIG Differential 12 (R to Y cut-in) 2 12 (R to Y cut-in) 0.2

Pressure Connector FNPTF (in) Barbed Fitting Female NPSF

1. Rated for 24A. Non-inductive, spst only. 2. Max. connected load shall not exceed 2,000 VA. Includes: Universal mounting bracket No. BKT16A-600. Barb fitting. P10FC-4 also has a jumper installed on the common terminals. Electrical Ratings: 16A @ 120 Vac

P20 SERIES AIR CONDITIONING LIMIT PRESSURE SWITCHES UNIVERSAL FIELD REPLACEMENT CONTROLS FOR NON-CORROSIVE REFRIGERANTS 36” capillary with 1/4” sweat section. Includes mounting bracket. Setting (psig) Switch Max. Bellows Order Number Range of Cutout (psig) Differential Opens Closes Action Pressure (psig) P20BB-1C Open on fall 7 - 150 Manual reset 40 Lockout manual reset 250 P20DB-1C Open on rise 100 - 425 Manual reset 400 Lockout manual reset 450 P20EB-1C spdt 7 - 150 25 psi fixed 40 65 psig 250 P20EB-2C spdt 100 - 425 70 psi fixed 400 330 psig 450

ELECTRICAL MOTOR RATINGS: 1 PHASE Motor Duty Full Load Locked Rotor Maximum 300 Vac

120 Vac 16.0 96.0 -

208 Vac 9.2 55.2 Suitable for 20 - 24 Vac

Amps

240 Vac 8.0 48.0 Suitable for 20 - 24 Vac

277 Vac 7.0 42.0 -

P100 SERIES ENCAPSULATED PRESSURE SWITCHES DIRECT MOUNT DESIGN NONADJUSTABLE SPST For use with non-corrosive refrigerants. Automatic reset in both open low and open high configurations and manual reset with open high action. Includes 1/4” SAE female flare fitting with internal depressor. Setting (psig) Order Number Switch Action Application Opens Closes Gemline P100AP-201C Open on fall Low cutout 10 40 P100AP-2C Open on fall Low cutout 35 60 P100AP-3C Open on fall Fan cycling 150 225 P100AP-4C Open on fall Fan cycling 170 250 P100DA-1C Open on rise High Limit 410 Lockout manual reset PC103 P100DA-2C Open on rise High Limit 475 Lockout manual reset P100DA-35C Open on rise High Limit 350 Lockout manual reset P100DC-3C Open on rise High Limit 375 Lockout manual reset P100CP-1C Open on rise High cutout 400 300 PC151 P100CP-2C Open on rise High cutout 425 325 PC100

Burnaby Kitchener

8

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

Replaces Ranco MPF-7004 MPF-7008 MPH-7107 MPH-7108

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

Robertshaw 3100-004 3100-103 3100-151 3100-100

306.373.9227

PRESSURE SWITCHES AND CONTROLS

ALLTEMP MINIATURE PRESSURE CONTROLS Operating temperature: -20°F - 150°F Refrigerant temperature: -35°F - 275°F LOW PRESSURE CUT OUT Setting (psig) Order Number 25-RML-520 25-RML-1025 25-RML-1535 25-RML-2045 25-RML-2580 25-RML-3560 25-RML-4080 25-RML-4560

Cut Out 5 10 15 20 25 35 40 45

HIGH PRESSURE CUT OUT Setting (psig) Order Number Cut Out Cut In 25-RMH-250180 250 180 25-RMH-300200 300 200 25-RMH-325225 325 225 25-RMH-350250 350 250 25-RMH-375275 375 275 25-RMH-400300 400 300 25-RMH-425325 425 325

Cut In 20 25 35 45 80 60 80 60

CONDENSER FAN CYCLING Setting (psig) Order Number Cut Out Cut In 25-RMF-75120 75 120 25-RMF-110170 110 170 25-RMF-150225 150 225 25-RMF-190275 190 275 25-RMF-300400 300 400

MARS CONDENSOR FAN CYLCING PRESSURE CONTROLS FIXED SETTINGS Order Number 33341

Opening 210

Pressure

Reset 275

Switch Action Open on fall

Mounting (in) 1/4 Female SAE

Application Cycling Switch

Contact Ratings: 24–240V, 6A steady-state max. FLA

JOHNSON PRESSURE CONTROLS

P28 SERIES LUBE OIL PROTECTION CONTROLS (WITH TIME DELAY)

The P28 series provides dependable shutdown on pressure of lubricated refrigeration compressors by sending low lube oil pressure. A built-in time delay switch, accurately compensated for ambient temperature, allows for pressure pick up on start and avoids nuisance shutdowns on pressure drops of short duration during the running cycle. Maximum bellows pressure: 325 psig Range1: 8 - 70 psig Order Number P28AA-1C P28AA-2C P28AA-17C P28AA-18C P28AN-15C P28AN-1C P28DA-1C P28GA-2C P28NA-5C

Time Delay (sec) 90 60 120 45 30 90 90 90 120

Heater Circuit 120/240 Vac 120/240 Vac 120/240 Vac 120/240 Vac 120/240 Vac 120/240 Vac 120/240 Vac 120/240 Vac 24 Vac or Vdc

Type of Reset Manual Manual Manual Manual Manual Manual Manual Automatic Manual

1. Switch differential approximately 5 psi. Factory set @ 9# cut-out. 2. UNIVERSAL REPLACEMENT: Replaces Ranco P30-3701. 3. UNIVERSAL REPLACEMENT: Replaces Ranco P30-3801. 4. With Safelite and Alarm Circuit. Includes: Mounting brackets.

Refrigerant

Pressure Connection (in)

Non-Corrosive all-range Non-Corrosive all-range Non-Corrosive all-range Non-Corrosive all-range Ammonia Ammonia Non-Corrosive all-range Non-Corrosive all-range Non-Corrosive all-range

36 capillary with 1/4 flare nut 36 capillary with 1/4 flare nut 36 capillary with 1/4 flare nut 36 capillary with 1/4 flare nut 1/4 female NPT 1/4 female NPT 36 capillary with 1/4 flare nut 36 capillary with 1/4 flare nut 36 capillary with 1/4 flare nut

ELECTRICAL RATINGS PILOT DUTY Time Delay Heater Circuit 120/240 Vac 12 Vac or Vdc 24 Vac or Vdc

* Must be same voltage as pilot circuit.

Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

Pilot Circuit 750 VA. 120/240 Vac 125 VA. 24 Vac 57.5 VA. 24 Vdc 125 VA. 24 Vac 57.5 VA. 24 Vdc

Alarm Circuit* 125 VA. 120/240 Vac 125 VA. 24 Vac 57.5 VA. 24 Vdc 125 VA. 24 Vac 57.5 VA. 24 Vdc

^ Must be same voltage as time delay circuit.

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

Contact Rating 2to1:2to3^ 10A @ 120 Vac 5A @ 240 Vac 10A @ 24 Vac 10A @ 24 Vdc 10A @ 24 Vac 10A @ 24 Vdc

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

9

JOHNSON PRESSURE CONTROLS

P29 SERIES LOW PRESSURE PROTECTION CONTROL (WITH TIME DELAY) P29NC is a low pressure control with time delay and lockout, which requires manual reset. A drop in pressure energizes the time delay relay and opens a contact after 60 seconds, shutting down the equipment. The time delay prevents nuisance shutdowns due to momentary fluctuations in system pressures. Includes mounting brackets.

P29NC-3C

Time-Delay Setting (sec)* 60 (factory set)

Switch Action spst

P29NC-2C

60 (factory set)

spst

Order Number

Pressure to Open Pressure Drop to Contacts (psig) Close Contacts (psi) 20” - 100 1-3 20” - 100

Max. Bellows Pressure (psig) 325

1-3

*. Contact Customer Service for time delay other than 60 seconds. Electrical Ratings: Pilot duty rating: 750 VA, 120/240 Vac or 57.5 VA, 24 Vdc.

325

Pressure Connection (in) 36 copper capillary tube with 1/4 flare nut 1/4 male flare fitting

P32 SERIES SENSITIVE PRESSURE SWITCHES SENSES AIR FLOW IN DUCTS This differential pressure switch is used to sense pressure/air flow in ducts. Easy-to-read setpoint scale. Versatile mounting options. Pressure/air flow proving with electric duct heaters, humidifiers and other equipment. Maximum pressure/air flow control for variable volume systems. Reheat duct powered systems. Clogged filter detection. Detection of icing of air conditioning coils and initiation of defrost cycle. Sensitive pressure settings and dust-tight snap switch. Electrical Ratings (Full Load) Contact Sensitivity At Scale Order Number Range Set Point Bracket 120 Vac 208 Vac 240 Vac Action Min. Set Point Plate P32AC-1C spdt 0.15 - 12” WC 0.07” WC Adjustable Yes L 9.8A 5.65A 4.9A P32AC-2C spdt 0.05 - 5” WC 0.04” WC Adjustable Yes U 9.8A 5.65A 4.9A P32AF-1C spdt 0.05 - 5” WC 0.025” WC Adjustable Yes L 5.8A 3.35A 2.9A P32AF-2C spdt 0.05 - 5” WC 0.025” WC Adjustable Yes U 5.8A 3.35A 2.9A 1. Supplied with 1/4″ compression fitting, 4″ extension tube, 2 mounting screws, “O” gasket, angle barb fitting installed.

P45 SERIES LUBE OIL PROTECTION CONTROL (WITH TIME DELAY)

The P45 control provides dependable, low lube oil pressure protection for refrigeration compressors. The factory set pressure setting provides operation to the compressor manufacturer’s specification. A built-in time delay relay, compensated for ambient temperature, allows for pressure pick-up on start and avoids nuisance shutdowns on short duration pressure losses during the running cycle. Time delay heater circuit: 120/240 Vac Pilot duty: 750 VA. 120/240 Vac Maximum bellows pressure: 425 psig Range: 7 – 60 psig Order Number P45NCA-12C P45NCA-82C

Time Delay (sec) 120 45

Heater Circuit 120/240 Vac 120/240 Vac

Type of Reset Manual Manual

Factory (psig) 9* 6.5^

Refrigerant

Pressure Connection (in)

Non-corrosive Non-corrosive

36 capillary with 1/4 flare nut 36 capillary with 1/4 flare nut

1. UNIVERSAL REPLACEMENT: Replaces Ranco P30-5826. *. Switch differential approximate 5 psi. Time delay energizes at 9 psi pressure difference, de-energized at 14 psi difference. ^. Switch differential approximate 4.5 psi. Time delay relay energizes at 6.5 psi pressure difference, de-energized at 11 psi difference. Note: Time Delay Relay is not field replaceable.

SUPER HOSE LUBE OIL PRESSURE CONTROLS The P128 series control provides dependable low pressure lube oil cut-out for pressure lubricated refrigeration compressors. Order Number P128AA-1C P128AA-2C

Burnaby Kitchener

10

604.298.4472 519.748.0961

Time Delay (sec) 90 60

Interior BC St.Catharines

Heater Circuit (Vac)

Type of Reset

120/240 120/240

Manual Manual

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

Adjustment Range (psi) 8 - 70 8 - 70

403.214.2134 780.476.0800

Edmonton Ottawa

Refrigerant Non-corrosive Non-corrosive

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

JOHNSON PRESSURE CONTROLS

P145 SERIES SUPERHOSE LUBE OIL FAILURE CUTOUT CONTROLS Order Number P145NCA-12C P145NCA-82C P145NCB-12C

Time Delay Heater (sec) Circuit (Vac) 120 120/240 45 120/240 120 120/240

Range (psi)

Type of Reset Pressure Connection

9 - factory set 6.5 - factory set 9 - factory set

Manual Manual Manual

1/4” male flared 1/4” male flared 1/4” male flared

Refrigerant Non-corrosive Non-corrosive Non-corrosive

P545 SERIES ELECTRONIC LUBE OIL CONTROLS

The P545 series Electronic Lube Oil Control is designed for use on refrigeration compressors equipped with an oil pump that accepts a single-point differential pressure switch. The P400 switch continuously monitors net lube oil pressure and the P545 control locks out the compressor if lube oil pressure falls below the manufacturer’s recommended net pressure for longer than the recommended lube oil time delay. Front-mount LED’s indicate the status of the lubrication system and a user-selectable, minimum-off time delay can be set to minimize compressor short cycling. A Johnson Controls/PENN® R310AD Current Sensing Switch, sold separately may be used to disable the P545 control lockout circuit during abnormal compressor shutdowns. Single-Pole Double-Throw (SPDT) relay contacts for liquid line solenoid and alarm applications - allows liquid line solenoid to be closed if the P545 control shots off the compressor due to low oil pressure; provides alarm indication, including circuits that use neon lights. Relay contact output for compressor - provides reliable, long-lasting operation. Built-in test circuit - verifies proper control operation quickly, without additional tools or equipment. Improved noise immunity - exceeds immunity requirements of UL 991 for transient overvoltage: IEC 61000-4-3 for radiated Radio Frequency (RF) and IEC 61000-4-6 for RF-induced conducted disturbances. Selection of anti-short cycle strategy for a wide range of equipment requirements: possible elimination of external short-cycle timer. Order Number P545NCB-22C1 P545NCB-25C1 P545NCB-82C1

Lube Oil Delay (sec) 120 90 120

P400 Switch P400AD-2 P400BD-1 P400AD-1

1. Switch and wiring harness included

Wiring Harness WHA-P400-100 WHA-P400-125 WHA-P400-100

Control and Sensor/Switch Compatibility P345 or P445 Control with P345 or P445 Control with Test P300 Sensor P400 Switch WHA-P300-xxx only WHA-P300-xxx or Wiring Harness1 WHA-P400-xxx 6-8 second delay Does not function 2 Test Switch

Fits Compressors by Copeland Bitzer Carlyle

P545 Control and P300 Sensor WHA-P300-xxx only Immediate

P545 Control and P400 Switch WHA-P300-xxx or WHA-P400-xxx Immediate

Accessories P400 Single-Point Differential Lube Oil Pressure Switch Order Number P400AD-1C P400AD-2C P400BD-1C

Open Point (Differential Pressure) 7.0 ± 1.0 psid 12.75 ± 0.75 psid 10.0 ± 1.5 psid

Close Point (Differential Above Open Point) Less than or equal to 2.0 psid Less than or equal to 1.5 psid Less than or equal to 3.0 psid

Threads

Wiring Harness

3/4-16 UNF

WHA-P400-100

M20 x 1.5

WHA-P400-125

Wiring Harnesses and Other Accessories Order Number Description KITP545-82C1 CST29A-600C sensor block; P545NCB-82 control; P400AD-1C switch; WHA-P400-100C wiring harness WHA-P400-100C 3 1/3 ft (1 m) length wiring harness WHA-P400-125C 4 ft (1 1/4 m) length wiring harness WHA-P400-250C 8 ft (2 1/2 m) length wiring harness WHA-P400-430C 14 ft (4 1/3 m) length wiring harness R310AD-1C Low-voltage Current Sensing Switch 271-51 Universal Mounting Bracket 1. Contact Carlyle Compressor Co. to order Sensor Block Gasket 06DA680063

Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

11

JOHNSON PRESSURE CONTROLS

P70 SERIES HIGH PRESSURE CUTOUTS WITH ALARM CIRCUITS ALL RANGE FOR R12, R22, R134, R500, R502 This control has two sets of contacts. The main set of contact controls the main load and the auxiliary contact simultaneously actuates a signal or auxiliary circuit. The main contacts (Line-M2) are open-high / close-low. The electrical contacts operate from a pressure sensing element. Order Number P70KA-1C

Switch Action

Range (psig)

L-M1 close high, L-M2 pen high, 4-wire 2-circuit

50 - 450

Pressure Max. Bellows Connector (in) Pressure (psig) Lockout (requires 36 capillary 475 manual reset after cutout) 1/4 flare nut Differential

Electrical Ratings: On main contacts: 16.0A at 120 Vac.

P70 SERIES SINGLE POLE HIGH PRESSURE CONTROLS

Employs a set of switch contacts that are opened and closed by the movement of pressure actuated bellows. The load-carrying contact provide direct control of AC motors within the control rating. Includes a universal mounting bracket. Air conditioning and refrigeration applications. HEAD PRESSURE FAN CYCLING Order Number P70AA-118C P70AA-2C

Switch Action

Range (psig) Differential

close high, open low close high, open low

100 - 400 0 - 150

35 - 200 12 - 40

Limited Knob Max. Bellows Adjustment Pressure (psig) 36” capillary - 1/4” flare nut None 500 36” capillary - 1/4” flare nut None 500 Pressure Connector

120 Vac 20A 20A

ALL RANGE FOR R12, R22, R134, R500, R502 Order Number

Switch Action

Range (psig)

Differential

P70CA-2C

open high, close low

50 - 450

60 - 150

P70CA-3C

open high, close low

50 - 450

60 - 150

P70DA-1C

open high, close low

50 - 450

Lockout (requires manual reset)

Switch Action

Range (psig)

Differential

close high, open low open high, close low open high, close low

50 - 450 50 - 450 50 - 450

20 - 100 50 - 150 Lockout (requires manual reset)

Pressure Connector (in) 1/4 male flared connection 36 capillary 1/4 flare nut 36 capillary 1/4 flare nut

Limited Knob Adjustment None

Pressure Connector (in) 1/4 female NPT 1/4 female NPT 1/4 female NPT

Limited Knob Adjustment None None None

Max. Bellows 120 Vac Pressure (psig) 475 20A

None

475

20A

None

475

20A

FOR AMMONIA Order Number P70AA-119C P70CA-5C P70DA-2C

Max. Bellows Pressure 400 475 475

120 Vac 20A 20A 20A

1. UNIVERSAL REPLACEMENT: Replaces Ranco O10-2054. Includes: Mounting bracket

P70 SERIES SINGLE POLE LOW PRESSURE CONTROLS CONTROL OF AIR, WATER, AND OIL PRESSURE MICRO-SET FOR R12, R22, R134A, R500, R502

Order Number P70AB-12C

Burnaby Kitchener

12

Switch Action

Range (psig) Differential (psi)

close high, open low

604.298.4472 519.748.0961

Interior BC St.Catharines

12 - 80

604.202.4853 905.988.1724

5 - 35

Vancouver Island Windsor

604.282.0118 519.251.9925

Pressure Connector (in) 36 capillary 1/4 flare nut Calgary North Bay

Limited Knob Max. Bellows Adjustment Pressure (psig) Cut-off 500

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

120 Vac FLA

LRA

20

120

Saskatchewan www.isc.tv

306.373.9227

JOHNSON PRESSURE CONTROLS

P70 SERIES SINGLE POLE LOW PRESSURE CONTROLS ALL RANGE FOR R12, R22, R134A, R500, R502 Order Number

Switch Action

Pressure Connector (in) 1/4 male flared 36 capillary 1/4 flare nut 36 capillary 1/4 flare nut

Range (psig) Differential (psi)

P70AB-1C P70AB-2C

close high, open low close high, open low

20 - 100 20 - 100

6 - 70 6 - 70

P70CA-1C

close high, open low

20 - 100

6 - 70

Limited Knob Max. Bellows Adjustment Pressure (psig) Cut-off 325 Cut-off 325 None

120 Vac FLA

LRA

20 20

120 120

20

120

325

FOR AMMONIA Pressure Limited Knob Max. Bellows Order Number Switch Action Range (psig) Differential (psi) Connector (in) Adjustment Pressure (psig) P70AA-5C close high, open low 20 - 100 6 - 70 1/4 female NPT None 325 P70CA-4C close high, open low 20 - 100 6 - 70 1/4 female NPT None 325

120 Vac FLA

LRA

20 20

120 120

P170 SERIES SUPERHOSE SINGLE POLE PRESSURE CONTROLS SINGLE POLE, LOW PRESSURE Pressure connector is a 1/4” male flared connector. Order Number P170AB-2C P170AB-12C P170CA-1C

Switch Action

Limited Knob Adjustment Cutout Cutout None

Range (psig) Differential (psi)

close high, open low close high, open low open high, close low

20 - 100 12 - 80 20 - 100

6 - 50 5 - 35 6 - 50

Max. Bellows Pressure (psig) 325 500 325

SINGLE POLE, HIGH PRESSURE Order Number

Switch Action

Range (psig)

Differential (psi)

P170AA-118C P170CA-3C P170DA-1C

close high, open low open high, close low open high, close low

100 - 400 50 - 450 50 - 450

35 - 200 60 - 150 Lockout (requires manual reset)

Limited Knob Adjustment None None None

Max. Bellows Pressure (psig) 500 475 475

HIGH PRESSURE CUTOUT W/ALARM CIRCUIT Order Number P170KA-1C

Switch Action

Range (psig)

Differential (psi)

L-M1 close high, L-M2 open high, 4-wire 2-Circuit

50 - 450

Lockout (requires manual reset)

Limited Knob Adjustment None

Max. Bellows Pressure (psig) 475

P170 SERIES SUPERHOSE SINGLE POLE, DUAL PRESSURE CONTROLS Order Number P170LB-1C P170LB-6C P170MA-1C P170MA-18C P170NA-1C

Switch Action

Range (psig)

spst^ spst^ spst** spst** spst^^

Low: 20 to 100, High: 100 to 425 Low: 12 to 80, High: 100 to 425 Low: 20 to 100, High: 100 to 425 Low: 12 to 80, High: 100 to 425 Low: 20 to 100, High: 100 to 425

Limited Knob Adjustment Cutout* Cutout* None None None

Max. Bellows Pressure (psig) 325 low, 450 high 500 low, 475 high 325 low, 450 high 500 low, 475 high 325 low, 450 high

^. Automatic reset High and Low pressure. *. Adjusting knob supplied on Differential (Low side cutout setting) to limit adjustment 5 psi above or below setting. **. Automatic reset Low, manual reset High pressure. ^^. Manual reset High and Low pressure. Burnaby Kitchener

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

13

JOHNSON PRESSURE CONTROLS

P70 SERIES SINGLE POLE DUAL PRESSURE CONTROLS MICRO-SET FOR R12, R22, R500, R502 Low (psig) High (psig) Switch Pressure Limited Knob Max. Bellows Order Number Range Diff. Range Diff. (non-adjustable) Action Connector (in) Adjustment Pressure (psig) P70LB-6C SPST 12 - 80 5 - 35 100 Under 300 psig, 55 psi; 36 capillary Cutout* 500 Low, - 425 over 300 psig, 65 psi 1/4 flare nut 475 High P70MA-18C SPST 12 - 80 5 - 35 100 Lockout (requires 36 capillary None 500 Low, - 425 manual reset) 1/4 flare nut 475 High

ALL RANGE FOR R12, R22, R500, R502 Low (psig) Switch Order Number Range Differential Action P70LB-1C SPST 20 - 100 6 - 50

100 - 425

P70MA-1C

SPST

20 - 100

100 - 425

P70NA-1C

SPST

20 - 100 Lockout (requires 100 - 425 manual reset)

6 - 50

Range

High (psig) Differential (non-adjustable) Under 300 psig, 55 psi; over 300 psig, 65 psi Lockout (requires manual reset) Lockout (requires manual reset)

Pressure Connector (in) 36 capillary 1/4 flare nut 36 capillary 1/4 flare nut 36 capillary 1/4 flare nut

Limited Knob Max. Bellows Adjustment Pressure (psig) Cutout* 325 Low, 450 High None

325 Low, 450 High

None

325 Low, 450 High

P70 SERIES SINGLE POLE DUAL PRESSURE CONTROLS FOR AMMONIA Low (psig)

P70LA-2C

Switch Action SPST

P70MA-2C

SPST

Order Number

High (psig) Differential Range Differential Range (non-adjustable) 20 - 100 6 - 50 100 - 425 Under 300 psig, 55 psi; over 300 psig, 65 psi 20 - 100 6 - 50 100 - 425 Lockout (requires manual reset)

Pressure Connector (in) 1/4 female NPT

Limited Knob Adjustment None

1/4 female NPT

None

*. Adjusting knob supplied on differential (low side cutout setting) to limit adjustment 5 psi above or below setting.^. High pressure cutout stops available.

Max. Bellows Pressure (psig) 325 Low, 450 High 325 Low, 450 High

P72 SERIES TWO POLE LOW PRESSURE CONTROLS ALL RANGE FOR R12, R22, R134, R500, R502 Order Number P72AA-1C P72AB-1C

Switch Action DPST close high open low DPST close high open low

Range (psig) 20 - 100

Differential (psi) 6 - 50

20 - 100

6 - 50

Pressure Connector (in) 36 capillary 1/4 flare nut 36 capillary 1/4 flare nut

Limited Knob Adjustment None

Max. Bellows Pressure (psig) 325

Cutout adjustment limited to 7 psi

325

Note: Adjusting knob supplied on differential (cutout setting) to limit adjustments to 5 psi above or below normal setting. Electrical Ratings: 24.0A @ 120 Vac.

Burnaby Kitchener

14

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

JOHNSON PRESSURE CONTROLS

P72 SERIES TWO POLE HIGH PRESSURE CONTROLS HEAD PRESSURE FAN CYCLING Order Number

Switch Action

Range (psig)

P72AA-27C

dpst close high, open low

100 - 400

Differential (psi)

Pressure Connector (in)

Min. 35 - max. 200 36 capillary - 1/4 flare nut

Max. Bellows Pressure (psig) 500

ALL RANGE FOR R12, R22, R134, R500, R502 Order Number P72CA-2C P72DA-1C

Switch Action dpst open high, close low dpst open high, close low

Range (psig) 50 - 450

Differential (psi) Min. 60 - max. 150

Pressure Connector (in) 36 capillary - 1/4 flare nut

Max. Bellows Pressure 475

50 - 450

Lockout (requires manual reset)

36 capillary - 1/4 flare nut

475

P72 SERIES TWO POLE DUAL PRESSURE CONTROLS ALL RANGE FOR R12, R22, R134, R500, R502 Low Pressure (psig)

P72LA-1C

Switch Action dpst

20 - 100

P72LB-1C

dpst

20 - 100

P72MA-1C

dpst

20 - 100

P72NA-1C

dpst

20 - 100

Order Number

Range

High Pressure (psig) Differential Pressure Knob Max. Bellows Differential Range (non-adjustable) Connector (in) Adjustment Pressure (psig) Min. 6 - max. 50 100 - 425 Under 300 psig, 55 psi; 36 capillary None 325 Low over 300 psig, 65 psi 1/4 flare nut 475 High Min. 6 - max. 50 100 - 425 Under 300 psig, 55 psi; 36 capillary Low side cutout 325 Low over 300 psig, 65 psi 1/4 flare nut adjustment 475 High limited to 7 psi Min. 6 - max. 50 100 - 425 Lockout (requires 36 capillary None 325 Low manual reset) 1/4 flare nut 475 High Lockout (requires 100 - 425 Lockout (requires 36 capillary None 325 Low manual reset) manual reset) 1/4 flare nut 475 High

P74 SERIES DIFFERENTIAL PRESSURE CONTROLS

Measures the pressure difference between two sources (supply and return lines). A change in differential pressure will reposition the switching mechanism to cause corrective action of supplementary control equipment. Applications: differential pressure sensing on chillers or water cooled condensers; lube oil failure cutout for refrigeration compressors (same as the P28, but does not incorporate time delay); positioning M100 Series motor actuated valves (P74JA-2); prove pump operation. FOR ALL REFRIGERANTS EXCEPT AMMONIA Order Number P74AA-1C P74BA-1C P74FA-1C P74EA-8C

Differential Range (psig) spst closes on decrease 8 - 70 adjustable in pressure differential spst opens on decrease 8 - 70 adjustable in pressure differential spdt (snap-acting) 8 - 60 spdt (floating) 2 - 26 Switch Action

Includes: Universal mounting bracket.

Pressure Connections (in) 36 capillary 1/4 flare nut 36 capillary 1/4 flare nut 1/4 male flare 36 capillary 1/4 flare nut

Electrical Ratings Max. Bellows (50/60Hz) (momentary - psig) 20A @ 120 Vac 325

Bellows Material Stainless steel

20A @ 120 Vac

325

Stainless steel

6A @ 120 Vac 16A @ 120 Vac

180 180

Brass Bellows; brass

PRESSURE CONTROL HOSES Order Number HHCC1S HHC18S HHC2S HHC3S HHC4S HHC5S Burnaby Kitchener

604.298.4472 519.748.0961

Description CPS 12” CAP Tube Control Hose STR x 90 Degree CPS 18” CAP Tube Control Hose STR x 90 Degree CPS 24” CAP Tube Control Hose STR x 90 Degree CPS 36” CAP Tube Control Hose STR x 90 Degree CPS 48” CAP Tube Control Hose STR x 90 Degree CPS 60” CAP Tube Control Hose STR x 90 Degree Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

15

JOHNSON ELECTRONIC FAN SPEED CONTROL

P66 SERIES REPLACEMENT ELECTRONIC FAN SPEED CONTROLS

Pressure actuated electronic motor speed controller. This control can be used with single phase permanent split capacitor and shaded pole motors which are approved by the motor and equipment manufacturer for speed control applications. By directly sensing pressure, this device electronically varies the speed of a fan motor. Controlling head pressure in the condensing section of a refrigeration system is a common application. Typical applications include: computer room air conditioning, commercial air conditioning, and commercial refrigeration. This control is designed to replace On/Off fan cycling controls, multiple speed motors, condenser flood-back systems, temperature fan speed control, and modulating louver systems. Low pressure range: 80 – 200 psig Effective throttling range (ETR): 30 psi High pressure range: 140 – 350 psig Effective throttling range (ETR): 60 psi Maximum over pressure: 450 psig Control voltage: 24 Vac, 1 VA SINGLE PRESSURE INPUT Order Number

Operating Range (psig)

P66AAB-1C P66AAB-4C P66AAB-6C P66AAB-9C P66AAB-10C P66AAB-14C P66AAB-15C P66ABB-24C

190/250 135/165 170/230 170/230 190/250 220/280 190/250 190/250

Effective Throttling Range 60 60 60 60 60 60 60 60

Pressure Range

Start Voltage % of line

Capillary Length (in)

140 - 350 140 - 350 140 - 350 140 - 350 140 - 350 140 - 350 140 - 350 140 - 350

10 10 16 40 16 40 40 16

60 60 60 60 120 120 60 60

DUAL PRESSURE INPUT Order Number P66BAB-1C P66BAB-3C P66BAB-5C

Operating Range (psig) 190/250 170/230 190/250

Effective Throttling Range 60 60 60

Pressure Range

Start Voltage % of line

Capillary Length (in)

140 - 350 140 - 350 140 - 350

10 16 16

60 60 120

*. When two P15’s are used in parallel with one motor, replace both P15’s with one P66BAB. Select the P66BAB with an operating range similar to that of the P15’s being replaced. **. Start voltage for P15 models 40% 3. 50 Hz. Electrical Ratings: Full load: 8A @ 208 Vac; 8A @ 240 Vac; 6.9A @ 277 Vac; 4A @ 480 Vac. Caution: It is recommended that the P66 be used only with low heat rise ball bearing motors which are approved by the motor manufacturer for fan speed control operation.

VFD66 SERIES CONDENSER FAN SPEED CONTROLS

Designed for speed control of 3-phase motors, especially for condenser fan motors in refrigeration and HVAC systems. Condenser fan speed is controlled by varying the frequency and voltage of the power supplied to the motor. Uses input(s) from various devices to stabilize condenser head pressure. This is especially desirable during low ambient conditions by varying fan speed to meet changing load conditions. Condenser fan speed control may be based on pressure, temperature or both. Accepts input signals from the P35 pressure transducer. System 350 or any other 0 – 5 or 0 – 10 VDC analog input. Has a simple interface, which makes it easy to understand and use. End-user setup is minimized because of the application-specific design. NEMA 1 Enclosure without Alarm Output Kit = VFD66 Model VFD66 Model Packaged with P35AG-9200 VFD66AAA-1C VFD66AAA-100C VFD66BAA-1C VFD66BAA-100C VFD66CAA-1C VFD66CAA-100C VFD66DAA-1C VFD66DAA-100C VFD66EBA-1C VFD66EBA-100C VFD66FBA-1C VFD66FBA-100C

Burnaby Kitchener

16

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

NEMA 1 Enclosure with Alarm Output VFD66AAE-1C VFD66CAE-1C VFD66DAE-1C VFD66EBE-1C VFD66FBE-1C

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Voltage

Max. Amp

230 VAC 50 Hz, 208/230 VAC 60 Hz 400 VAC 50 Hz, 460 VAC 60 Hz 230 VAC 50 Hz, 208/230 VAC 60 Hz 400 VAC 50 Hz, 460 VAC 60 Hz 230 VAC 50 Hz, 208/230 VAC 60 HZ 400 VAC 50 Hz, 460 VAC 60 Hz

4.0 1.8 7.5 3.6 10.6 5.5

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

JOHNSON FAN SPEED CONTROL

VFD66 SERIES CONDENSER FAN SPEED CONTROLS ACCESSORIES Order Number P35AG-9200R VFD66-CVR-1C A350PS-1C P352PN-3C P399AAA-1-200C P399AAC-1-200C P399BAA-1-200C P399BAC-1-200C P399CAA-1-200C P399CAC-1-200C P399AAA-1C P399AAC-1C P399BAA-1C P399BAC-1C P399CAA-1C P399CAC-1C WHA-P399-200C WHA-P399-400C WHA-P399-600C

Description Pressure Transducer, 0-350 psi range External Potentiometer Replacement Cover Proportional Plus Integral Temperature Control Proportional Plus Integral Pressure Control Pressure Transducer, 0-100 psis, 1/8 inch NPTM pressure connection, with 6 1/2 ft (2 m) wire harness with pigtails Pressure Transducer, 0-100 psis, 1/4 inch SAE female flare pressure connection with valve depressor, with 6 1/2 ft (2 m) wire harness with pigtails Pressure Transducer, 0-500 psis, 1/8 inch NPTM pressure connection, with 6 1/2 ft (2 m) wire harness with pigtails Pressure Transducer, 0-500 psis, 1/4 inch SAE female flare pressure connection with valve depressor, with 6 1/2 ft (2 m) wire harness with pigtails Pressure Transducer, 0-750 psis, 1/8 inch MPTM pressure connection, with 6 1/2 ft (2 m) wire harness with pigtails Pressure Transducer, 0-750 psis, 1/4 inch SAE female flare pressure connection with valve depressor, with 6 1/2 ft (2 m) wire harness with pigtails Electronic Pressure Transducer, 0-100 psi range; 1/8 inch NPT male connector Electronic Pressure Transducer, 0-100 psi range; 1/4 inch NPT female connector Electronic Pressure Transducer, 0-500 psi range; 1/8 inch NPT male connector Electronic Pressure Transducer, 0-500 psi range; 1/4 inch NPT female connector Electronic Pressure Transducer, 0-750 psi range; 1/8 inch NPT male connector Electronic Pressure Transducer, 0-750 psi range; 1/4 inch NPT female connector Wire Harness 6 1/2 ft (2 m) length with pigtails Wire Harness 13 ft (4 m) length with pigtails Wire Harness 19 5/8 ft (6 m) length with pigtails

JOHNSON SYSTEM 350 MODULAR CONTROLS

A350A/B SERIES ELECTRONIC ON / OFF TEMPERATURE CONTROLS

System 350™ is a modular electronic control series consisting of a wide variety of on/off temperature, humidity and pressure applications as well as proportional temperature and temperature reset. The basic system consists of a control module, which accept add-on stage, LCD display and transformer modules. A variety of temperature, pressure and humidity sensors are also available. Hundreds of different control systems can be configured using combination. Of the controls and their add-on accessories. Five-pin connectors eliminate wiring errors. The modules can be DIN rail or surface mounted. Features: field selectable heat/cool mode; adjustable setpoint and differential; surface or DIN rail mounting; LED indication of relay status; 5-pin connectors eliminate wiring between modules. Order Number A350AA-1C A350AA-2C A350BA-1C A350BA-2C

Includes: A99BC-25C sensor

Output Spdt relay Spdt relay Spdt relay Spdt relay

Range -30 - 130°F 90 - 250°F -35 - 55°C 30 - 121°C

Differential/Offset Adjustment 1 - 30°F 1 - 30°F 0.5 - 17°C 0.5 - 17°C

A350E SERIES ELECTRONIC ON / OFF COOLING CONTROL With SPDT relay output; LED indication and both Fahrenheit and Celsius temperature scales. Besides being a cooling only control, the A350E has two features that differentiate it from the A350 Electronic temperature control; adjustable minimum setpoint and sensor short/open circuit protection. Sensor included. Order Number A350EA-4C

Burnaby Kitchener

604.298.4472 519.748.0961

Output Spdt

Interior BC St.Catharines

Range 10 - 65°F (-12 - 18°C)

604.202.4853 905.988.1724

Vancouver Island Windsor

Adjustable Differential 1 - 30°F (0.5 - 17°C)

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Minimum Setpoint Four jumper settings: 20°F, 30°F, 40°F, and off

Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

17

JOHNSON SYSTEM 350 MODULAR CONTROLS

A350P SERIES ELECTRONIC PROPORTIONAL PLUS INTEGRAL TEMPERATURE CONTROLS Have both Fahrenheit and Celsius temperature scales and a unique ten-segment LED that display percentage of output. Adjustments include setpoint (Fahrenheit or Celsius), throttling range, minimum output, and reverse or direct acting mode of operation (for heating or cooling applications). It also has a heat/cool switch allowing for direct or reverse acting output. Application capabilities include mixing valves for chilled or hot water control and modulating dampers for air flow. Sensor included. Proportional Output Signal Voltage Current 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA

Order Number A350PS-2C A350PS-1C

Range 90 - 250°F (30 - 120°C) -30 - 130°F (-35 - 55°C)

Throttling Range 2 - 30°F (1 - 17°C) 2 - 30°F (1 - 17°C)

Sensor Included A99BC-25C A99BC-25C

A350R SERIES ELECTRONIC TEMPERATURE RESET CONTROLS With an SPDT (normally open) relay with LED indication for both relay operation and night setback mode, the A350R raises or lowers (resets) the temperature of the supply water or supply air based on a proportional drop or rise in temperature at the outdoor sensor. Adjustments include reset ratio (1:5 to 3:1) differential (1 to 30°F) and selectable warm weather shutdown temperature settings. Typical applications include On/Off control of single or multi-stage boilers. Temperature sensors included. Order Number A350RS-1C

Output Spst relay

Minimum Supply Temperature (°F) Differential (°F) Reset Ratio - Outdoor/Indoor 50 - 160°F 1 - 30°F 1:5 - 3:1 adjustment

Setback Range (°F) 0-30°F

W351 SERIES ELECTRONIC ON / OFF HUMIDITY CONTROLS An electronic humidity control with LED indication used in conjunction with the HE-63000 or HE-6310 series of humidity transmitters to stage humidification and dehumidification equipment. Order Number W351AA-1C W351AA-2C W351AB-2C

Setpoint Range 10 - 90% RH 10 - 90% RH 10 - 90% RH

Differential 2 - 10% RH 2 - 10% RH 2 - 10% RH

Sensor Includes room sensor HE-6300-3 Includes room sensor HE-6310-3 -

W351P SERIES ELECTRONIC PROPORTIONAL PLUS INTEGRAL HUMIDITY CONTROLS Display percent of output. Adjustments include: setpoint, integration constant, throttling range, minimum output, and reverse and direct acting mode of operation. A typical application includes modulating steam valves for humidification. Proportional Output Voltage Current 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA

Order Number W351PP-1C W351PN-1C W351PN-2C

Humidity Range 10 - 90% RH 10 -90% RH 10 - 90% RH

Throttling Range 2 - 10% RH 2 - 10% RH 2 - 10% RH

Sensor None Includes HE-6310-3 Includes HE-6310-3

HUMIDITY TRANSMITTERS A high precision humidity transmitter with an integral temperature sensor combined in one enclosure. The All Polymer humidity element has an operating range of 0 to 100% RH (non-condensing). The silicon temperature element has an operating range of 32°F to 140°F. Order Number HE67530N0BT HE67530N00P

Mounting Wall Duct

P352 SERIES ELECTRONIC ON / OFF PRESSURE CONTROLS Display percent of output. Adjustments include: setpoint, integration constant, throttling range, minimum output, and reverse and direct acting mode of operation. Applications include duct static pressure control and building pressurization. Order Number P352AB-2C P352AB-3C P352AB-4C

Output SPDT relay* SPDT relay* SPDT relay*

Pressure Range (psig) 0 - 100 90 - 250 240 - 600

Adjustable Differential (psi) 2 - 50 10 - 100 10 - 100

*. Contacts rated @ 10A non-inductive, 1/2 HP 120/240 Vac, 125 VA pilot duty 24/240 Vac. Burnaby Kitchener

18

604.298.4472 519.748.0961

Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Sensor P399AAA-1C or P399AAC-1C P399BAA-1C or P399BAC-1C P399CAA-1C or P399CAC-1C Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

Display D352AA-2C D352AA-2C D352AA-2C 306.373.9227

JOHNSON SYSTEM 350 MODULAR CONTROLS

P352P SERIES ELECTRONIC PROPORTIONAL PLUS INTEGRAL STATIC PRESSURE CONTROLS

Display percent of output. Adjustments include: setpoint, integration constant, throttling range, minimum output, and reverse and direct acting mode of operation. Application includes duct static pressure control and building pressurization. Order Number P352PQ-1C P352PQ-2C P352PN-2C P352PN-3C P352PN-4C

*. Order separately.

Proportional Output Voltage Current 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA

Setpoint and Throttling Range 0.5 - 5 WC 0.0255 - 0.25 WC 0 - 100 / 5 - 50 psi 90 - 250 / 10 - 100 psi 240 - 600 / 10 - 100 psi

Sensor* DPT-2640-7 DPT-2640-3 P399 P399 P399

Sensor Input Range 0 - 10 WC corresponds to 0 - 5 Vdc 0 - 0.5 WC corresponds to 0 - 5 Vdc 0 - 100 psi 0 - 500 psi 0 - 750 psi

S350 / S351 / S352 SERIES TEMPERATURE, HUMIDITY AND PRESSURE STAGE MODULES Have three adjustments: reverse or direct-acting operation, differential and offset. Applications include any job requiring multiple staging when used in conjunction with any respective System 350 control. Order Number R353AA-1C S353AA-1C

Description Electronic sequencer signal input module Electronic sequencer stage module

P353 / S353 SERIES ELECTRONIC SEQUENCERS Display percent of output, adjustments include: setpoint, integration constant, throttling range, minimum output, and reverse and direct acting mode of operation. Applications include duct static pressure control and building pressurization. Order Number P352PQ-1C P352PQ-2C

Proportional Output Voltage Current 0 - 10 Vdc 0 - 20 mA 0 - 10 Vdc 0 - 20 mA

Setpoint and Throttling Range 0.5 - 5” WC 0.0255 - 0.25” WC

Sensor* DPT-2640-7 DPT-2640-3

Sensor Input Range 0 - 10” WC corresponds to 0 - 5 Vdc 0 - 0.5” WC corresponds to 0 - 5 Vdc

*. Order separately.

D350 / D351 / D352 SERIES TEMPERATURE, HUMIDITY AND PRESSURE DISPLAY MODULES Has a 3-digit LCD display that provides continuous sensor output information (read-only) for use with A350, W351 and P352 controls. Display modules feature a setpoint button located on front of the module to obtain actual space conditions or setpoint readings. Display modules can be helpful when making accurate setpoint adjustments to System 350 controls. Order Number D350AA-1 D351AA-1C D352AA-1C D352AA-2C D352CA-1C D352CA-2C

Display Range -30 - 250 °F 10 - 90% RH 0 - 435 psi 0 - 750 psi 0 - 9.99” WC 0 - 0.999” WC

*. Provided by the P352 pressure control.

In\put Voltage 12 Vdc 14 Vdc 5 Vdc* 14 Vdc 14 Vdc

Display Characters (lcd) 0.35 3 - digit 0.35” 3 - digit 0.35” 3 - digit 0.35” 3 - digit 0.35” 3 - digit 0.35”

Mounting Wall or DIN rail Surface or DIN rail Surface or DIN rail Surface or DIN rail Surface or DIN rail

CLK350 SERIES TIME CLOCKS A high precision humidity transmitter with an integral temperature sensor combined in one enclosure. The All Polymer humidity element has an operating range of 0 to 100% RH (non-condensing). The silicon temperature element has an operating range of 32°F to 140°F. Order Number CLK350-2

Output Electronic switch (open collector transistor)

Programs 7 day programmable, up to 294 On and Off events per week

S350C SERIES TEMPERATURE SLAVE STAGE MODULES A high precision humidity transmitter with an integral temperature sensor combined in one enclosure. The All Polymer humidity element has an operating range of 0 to 100% RH (non-condensing). The silicon temperature element has an operating range of 32°F to 140°F. Order Number S350CC-1C Burnaby Kitchener

604.298.4472 519.748.0961

Setpoint Adjustment Range (°C) -34 - 55 Interior BC St.Catharines

604.202.4853 905.988.1724

Vancouver Island Windsor

604.282.0118 519.251.9925

Calgary North Bay

403.214.2134 780.476.0800

Differential Adjustment Range (°C) 0.5 - 17 Edmonton Ottawa

780.451.4744 613.742.0083

Saskatchewan www.isc.tv

306.373.9227

19

JOHNSON SYSTEM 350 MODULAR CONTROLS Y350R - POWER MODULE

The Y350R Power Module provides a convenient means of powering System 350 modules in situations where Class 2 power is not available. Input voltage is 120/240 VAC. Output voltage is 24 VDC unfiltered. 5-pin, plug together connector, surface or DIN rail mounting. Order Number Y350R-1C

Description Power Module is used to supply Class 2 unfiltered 24 VDC power to system 350 controls.

Input Voltage 120/240 VAC 50/60 Hz

Output Voltage Class 2, 24 VDC unfiltered, 10 VA max

DIGITAL ELECTRONIC PRESSURE CONTROLS

The P470 electronic pressure control with display is a single-stage, On/Off, electronic pressure control with an spdt output delay. The control may be field set to operate in one of three pressure ranges (0 – 100 psi, 0 – 500 psi, or 50 – 750 psi), as either an open-high or open-low control. The P470 control features large LCD that displays the sensed pressure and other system-status indicators, as well as the adjustable setpoints in the programming mode. The P470 control has a lockable, 3-front panel LED that indicates the output relay status. The P470 controls uses a P399 electronic pressure transducer to generate a pressure signal and WHAP399 wiring harness, which eliminates many of the constraints of capillary-tube control applications. Operating pressure ranges: 0 – 100 psi, 0 – 500 psi, 50 – 750 psi Minimum differential pressure: 5 psi, 20 psi, 20 psi Displayed resolution: 1 psi, 3 psi, 5 psi Control accuracy: ± 1.5% of selected operating pressure range plus transducer accuracy Transducer type: P399 electronic pressure transducer Enclosure, case and cover: NEMA 1 high-impact thermoplastic Order Number Description P470EB-1C Line voltage with display supply voltage: 120 or 208/240 Vac P470FB-1C Low voltage (