AERCO Modbus Solution: C-MORE Boiler Controller

Point Map September 19, 2006 Systems Integration AERCO Modbus Solution: C-MORE Boiler Controller Table 1. AERCO C-MORE APOGEE Points, Application N...
Author: William Jackson
47 downloads 0 Views 49KB Size
Point Map September 19, 2006

Systems Integration

AERCO Modbus Solution: C-MORE Boiler Controller Table 1.

AERCO C-MORE APOGEE Points, Application Number: 4676. Range/Unitsa

Point

Type

Description

1

LAO

Modbus Slave Address



2

LAI

Application Number



3

LDI

Communication Error

Off/On

4

LAO

IP Address Byte 1



5

LAO

IP Address Byte 2



6

LAO

IP Address Byte 3



7

LAO

IP Address Byte 4



8

LAO

IP Port



9

LAO

Base Offset



10

LAO

Send Initial Values 0=No 1=Yes



11

LAI

Display Code

See Table 2

12

LAI

Unit Status

See Table 3

13

LAI

Outlet Temperature

°F °C

14

LAI

Inlet Temperature

°F °C

15

LAI

Auxiliary Temperature

°F °C

16

LAI

Outdoor Temperature

°F °C

17

LAI

Exhaust Temperature

°F °C

18

LAI

FFWD Temperature

°F °C

19

LAI

Fire Rate Out

%

20

LAI

02 Level

%

21

LAI

C0 Level

ppm

22

LAI

Run Cycle Low (LSB)

cycles

24

LAI

Run Cycle High (MSB)

cycles

b c

continued on next page...

Siemens Building Technologies, Inc. Document No. 127-1518

Page 1 of 8

Table 1.

AERCO C-MORE APOGEE Points, Application Number: 4676.

(continued)

Range/Unitsa

Point

Type

Description

25

LAI

Run Hours Low (LSB)

hrs

26

LAI

Run Hours High (MSB)

hrs

27

LAI

Flame Strenght

%

28

LAI

Active Set Point

°F °C

29

LAI

Fire Rate In

%

30

LAI

Manual Fire Rate

%

31

LAI

Communication Address



32

LAI

Software Version



33

LAI

Fault Log Code



34

LAI

Fault Log Cycle (Low)

cycles

35

LAI

Fault Log Cycle (High)

cycles

37

LAI

Fault Log Day

day

38

LAI

Fault Log Minute

min

39

LAI

Sensor Log Active Set Point

°F °C

40

LAI

Sensor Log Outlet Temperature

°F °C

41

LAI

Sensor Log Inlet Temperature

°F °C

42

LAI

Sensor Log FFWD Temperature

°F °C

43

LAI

Sensor Log Exhaust Temperature

°F °C

44

LAI

Sensor Log Outdoor Temperature

°F °C

45

LAI

Sensor Log Auxiliary Temperature

°F °C

46

LAI

Sensor Log C0 Xmitter

ppm

47

LAI

Sensor Log 02 Xmitter

%

48

LAI

Sensor Log Flow Meter

gpm Lpm

50

LAI

Time Log Status

See Table 4

51

LAI

Time Log Fire Rate

%

52

LAI

Time Log Flame Strengh

%

53

LAI

Time Log Run Length



54

LAI

Time Log Day

day

55

LAI

Time Log Minute

min

b c

continued on next page...

Page 2 of 8

Siemens Building Technologies, Inc. Document No. 127-1518

Table 1.

AERCO C-MORE APOGEE Points, Application Number: 4676.

(continued)

Range/Unitsa

Description

b c

Point

Type

56

LAO

Net Remote Set Point

°F °C

57

LAO

Net Direct Drive

%

58

LAO

Modbus Password



59

LAO

Password



60

LAO

Internal Setpoint

°F °C

61

LAO

Minute of Day

min

62

LAO

Day

day

63

LAO

Unit of Temperature

0 = °Fahrenheit 1 = °Celsius

64

LAO

Baud Rate

bps (See Table 5)

65

LAO

Unit Type

0 = Boiler 1 = Water Heater

66

LAO

Unit Size

See Table 6

67

LAO

Boiler Mode

See Table 7

68

LAO

Remote Signal

See Table 8

69

LAO

Building Reference Temperature

°F °C

70

LAO

Reset Ratio

0.9 – 9.9

71

LDO

Outdoor Sensor Enable

DISABL_ENABLE

72

LAO

System Start Temperature

°F °C

74

LAO

Setpoint Low Limit

°F °C

75

LAO

Setpoint High Limit

°F °C

76

LAO

Temperature High Limit

°F °C

77

LAO

Max Fire Rate

40 – 100%

78

LAO

Pump Delay Timer

0 – 30 min

79

LAO

Auxiliary Start On Delay

0 – 120 sec

80

LAO

Failsafe Mode

0 = Shutdown 1 = Constant Setpoint

81

LAO

Low Fire Timer

2 – 20 sec

82

LAO

Prop Band

°F °C

83

LAO

Integral Gain



84

LAO

Derivative Time

min continued on next page...

Siemens Building Technologies, Inc. Document No. 127-1518

Page 3 of 8

Table 1.

AERCO C-MORE APOGEE Points, Application Number: 4676.

(continued)

Range/Unitsa

Point

Type

Description

86

LAO

Min Load Adjust

°F °C

87

LAO

Max Load Adjust

°F °C

88

LDO

Outlet Feedback

Off/On

89

LDO

Setpoint Limiting

DISABL_ENABLE

90

LAO

Setpoint Limit Band

°F °C

91

LAO

Sensor Log Interval

See Table 9

92

LAO

Fault Log Pointer



93

LAO

Sensor Log Pointer



94

LAO

Time Log Pointer



b c

a Values noted for LDIs and LDOs are in the following format: OFF text/ON text. b This column indicates the value/range or engineering units or both if known. c The default English value is not italicized. An italicized entry indicates an SI value.

Table 2. Code

Status and Fault Messages.

Message

Description

DISABLED HH:MM pm MM/DD/YY

Displayed if ON/OFF switch is set to OFF. The display also shows the time and date that the unit was disabled.

2

STANDBY

Displayed when ON/OFF switch is in the ON position, but there is no demand for heat. The time and date are also displayed.

3

DEMAND DELAY XX sec

Displayed if Demand Delay is active.

PURGING XX sec

Displayed during the purge cycle during startup. The duration of the purge cycle counts up in seconds.

IGNITION TRIAL XX sec

Displayed during ignition trial of startup sequence. The duration of cycle counts up in seconds.

6

FLAME PROVEN

Displayed after flame has been detected for a period of two seconds. Initially, the flame strength is shown in %. After five seconds has elapsed, the time and date are shown in place of flame strength.

7

WARMUP XX sec

Displayed for two minutes during the initial warm-up only.

8

HIGH WATER TEMP SWITCH OPEN

The High Water Temperature Limit Switch is open.

9

LOW WATER LEVEL

The Water Level Control board is indicating low water level.

1

4

5

continued on next page...

Page 4 of 8

Siemens Building Technologies, Inc. Document No. 127-1518

Table 2. Code

Status and Fault Messages.

Message

(continued)

Description

10

LOW GAS PRESSURE

The Low Gas Pressure Limit Switch is open.

11

HIGH GAS PRESSURE

The High Gas Pressure Limit Switch is open.

12

INTERLOCK OPEN

The Remote Interlock is open.

13

DELAYED INTERLOCK OPEN

The Delayed Interlock is open.

14

AIRFLOW FAULT DURING PURGE

The Blower Proof Switch opened during purge.

15

SSOV FAULT DURING PURGE

The SSOV switch opened during purge.

16

PRG SWTCH OPEN DURING PURGE

The Purge Position Limit switch on the Air/Fuel valve opened during purge.

17

IGN SWTCH OPEN DURING IGNITION

The Ignition Position Limit switch on the Air/Fuel valve opened during ignition.

18

AIRFLOW FAULT DURING IGN

The Blower Proof Switch opened during ignition.

19

AIRFLOW FAULT DURING RUN

The Blower Proof Switch opened during run.

20

SSOV FAULT DURING IGN

The SSOV switch closed or failed to open during ignition.

21

SSOV FAULT DURING RUN

The SSOV switch closed for more than 15 seconds during run.

22

FLAME LOSS DURING IGN

The Flame signal was not seen during ignition or lost within five seconds after ignition.

23

FLAME LOSS DURING RUN

The Flame signal was lost during run.

24

HIGH EXHAUST TEMPERATURE

The High Exhaust Temperature Limit Switch is closed.

25

LOSS OF POWER

A power loss occurred. The time and date when power was restored is displayed.

26

LOSS OF SENSOR

Not Currently Used

27

LOSS OF SIGNAL

Not Currently Used

28

HIGH O2 LEVEL

Not Currently Used

29

LOW O2 LEVEL

Not Currently Used

30

HIGH CO LEVEL

Not Currently Used

31

SSOV RELAY FAILURE

A failure has been detected in one of the relays that control the SSOV.

32

RESIDUAL FLAME

The Flame signal was seen for more than 60 seconds during standby.

33

HEAT DEMAND FAILURE

The Heat Demand Relays on the Ignition board failed to activate when commanded.

34

IGN SWTCH CLOSED DURING PURGE

The Ignition Position Limit switch on the Air/Fuel valve closed during purge.

35

PRG SWTCH CLOSED DURING IGNITION

The Purge Position Limit switch on the Air/Fuel valve closed during ignition. continued on next page...

Siemens Building Technologies, Inc. Document No. 127-1518

Page 5 of 8

Table 2. Code

Status and Fault Messages.

(continued)

Message

Description

36

SSOV SWITCH OPEN

The SSOV switch opened during standby.

37

IGNITION BOARD COMM FAULT

Communication fault between the Ignition board and the CPU board.

38

WAIT

Prompts the operator to wait.

39

DIRECT DRIVE SIGNAL FAULT

The direct drive signal is not present or is out of range.

40

REMOTE SETPT SIGNAL FAULT

The remote setpoint signal is not present or is out of range.

41

OUTDOOR TEMP SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out of range.

42

OUTLET TEMP SENSOR FAULT

The temperature measured by the Outlet Sensor is out of range.

43

FFWD TEMP SENSOR FAULT

The temperature measured by the FFWD Sensor is out of range.

44

HIGH WATER TEMPERATURE

The temperature measured by the Outlet Sensor exceeded the Temp Hi Limit setting.

45

LINE VOLTAGE OUT OF PHASE

The High AC voltage is out of phase from the low AC voltage.

46

STEPPER MOTOR FAILURE

The stepper motor failed to move the valve to the desired position.

47

SETPT LIMITING ACTIVE

Setpoint temperature has exceeded the maximum allowable setting.

48

MODBUS COMM FAULT

The RS485 (Modbus) network information is not present or is corrupted.

Table 3. Value

Unit Status. Description

0

Disabled

1

Standby

2

Manual continued on next page...

Page 6 of 8

Siemens Building Technologies, Inc. Document No. 127-1518

Table 3.

Unit Status.

Value

Description

3

Remote

4

Auto

5

Fault Table 4.

Time Log Status.

Value

Description

73

Ignition

74

Off

80

Power Up

82

Run Table 5.

Baud Rate.

Value

Description

0

2.4K

1

4.8K

2

9.6K

3

19.2K Table 6.

Unit Size.

Value

Description

0

0.5 MBTU

1

1 MBTU

2

1.5 MBTU

3

2 MBTU

4

2.5 MBTU

5

3 MBTU Table 7.

Value

(continued)

Boiler Mode. Description

0

Constant Setpoint

1

Remote Setpoint continued on next page...

Siemens Building Technologies, Inc. Document No. 127-1518

Page 7 of 8

Table 7.

Boiler Mode.

Value

(continued)

Description

2

Direct Drive

3

Combo Unit

4

Outdoor Reset Table 8.

Remote Signal.

Value

Description

0

4 – 20mA / 1 – 5v

1

0 – 20mA / 0 – 5v

2

PWM Input

3

Network Table 9.

Sensor Log Interval.

Value

Description

0

Off

1

1 minute

2

5 minutes

3

15 minutes

4

30 minutes

5

1 hour

6

6 hours

7

12 hours

8

24 hours

Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2006 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 U.S.A.