Advanced Power Quality and Revenue Metering

SEL-734 Advanced Metering System Advanced Power Quality and Revenue Metering Accurate, comprehensive, and reliable metering for new installations an...
Author: Mariah Knight
19 downloads 2 Views 2MB Size
SEL-734 Advanced Metering System

Advanced Power Quality and Revenue Metering

Accurate, comprehensive, and reliable metering for new installations and retrofits.

Features and Benefits ■ Power Quality Monitoring







■ Use high-resolution waveform capture to analyze interruptions, sags, swells, harmonics, and unbalance.







ACSELERATOR

Record voltage sag/swell/interruption (VSSI) disturbances, monitor harmonics to the 50th order, capture waveforms, measure flicker, and record sequential events. Accurate, Bidirectional Metering Exceeds ANSI C12.20 0.2 and IEC 62053-22 0,2 S accuracy class with bidirectional, full four-quadrant energy metering for generation, interchange, transmission, distribution, or industrial applications. Standard Software Tools Easily configure, test, monitor, and retrieve data using ACSELERATOR QuickSet® SEL-5030 Software. ACSELERATOR QuickSet quickly programs, retrieves, plots, and exports billing data to .HHF or .CSV formats. Time-of-Use (TOU) Metering Provides flexible, time-differentiated energy and demand registers, with multiple day types, rates, seasons, and a 20-year programmable calendar. Automation functions include programmable self-reads and peak demand resets. High-Speed Load Profile Data (LDP) Records Multiple LDP recorders store billing data and power quality data in separate records with a maximum update rate of once every three seconds. ACSELERATOR QuickSet quickly retrieves, plots, and stores load profile data to a laptop computer or remotely over any communications port. Transformer and Line-Loss Compensation Enter transformer nameplate and line impedance information directly into the meter to automatically compensate for transformer or line losses and move the billing point. Complete Automation Customize alarms and automate control based on measured load information using advanced SELOGIC® control equations. Integrate with communications processors for single-point station access. Industry Standard Compliance Fully comply with ANSI and IEC standards with voltage and current ranges of: 57–132 V, 132–277 V; CL2, CL10, CL20, IEC 1 A, 5 A INOM.

QuickSet LDP and .HHF export tool

Schweitzer Engineering Laboratories, Inc.

SEL-734 Data Sheet

2

Power Quality and Recording Options: SEL-734 and SEL-734P The SEL-734 is available with two different power quality and recording feature set levels: standard and advanced. With the advanced power quality and recording option, the SEL-734P

can replace a high-end power quality instrument costing thousands of dollars more. This allows economical power quality monitoring at more locations.

Power Quality and Recording Option

Standard: SEL-734

Advanced: SEL-734P

Available Memory Load Profile Recorder Channels Recorders Acquisition rates Storage at 5-minute intervals in days 12 Channels 96 Channels Flicker Measurement Highest Harmonic Order Waveform Event Reports Storage capacity in events Event duration Sample rate Sequential Events Recorder Number of events Voltage Sag/Swell/Interruption Recorder Typical number of summary events Number of detailed rows Time-of-Use Number of self-reads

32 MB

128 MB

16 1 1, 5, 10, 15, 30, 60 minutes

192 12 3–59 s, 1, 5, 10, 15, 30, 60 minutes

770 N/A

N 15th

2400 280 Y 50th

64 0.25 s 1 kHz

16–3155 0.25, 0.5, 1, 2, 5, or 10 s 1 kHz or 8 kHz

>21,000

>21,000

60 >11,000

60 >11,000

15

15

Simplified Setup and Troubleshooting

Feature Overview

• Use ACSELERATOR QuickSet to customize your metering. Set and edit meter configuration, settings, and logic. • View the HMI screens in ACSELERATOR QuickSet to check wiring connections, phase rotation, and power flow direction. • Voltage and current sequence elements allow fast troubleshooting of miswired installations.

• Form 5, 3-Wire Delta and Form 9, 4-Wire Wye metering connections • ANSI C12.20 0.2 and IEC 62053-22 0,2 S accuracy class • Rack-mount, panel-mount, easily extractable meter (EXM), wall-mount, and NEMA enclosure options available • Simultaneous Ethernet, EIA-485, EIA-232, telephone modem, and optical probe communications • Synchrophasor data (IEEE C37.118) • Enhanced SELOGIC control equations • Communication protocols – SEL ASCII – Modbus® RTU/TCP – SEL Fast Operate/Fast Meter – MIRRORED BITS® communications – SEL Distributed Port Switch (LMD) – DNP3 Serial and LAN/WAN • Inputs/outputs – 2 digital inputs, 3 electromechanical outputs – 4 digital inputs, 4 KY outputs with programmable Ke – 4 digital inputs, 4 electromechanical outputs – 4 analog outputs, 4 KY outputs with programmable Ke – 6 solid-state high-break capacity outputs for dc load – 4 digital inputs, 2 electromechanical 30 A outputs – Battery monitor inputs See model option table for available configurations and options.

SEL-734 Data Sheet

Schweitzer Engineering Laboratories, Inc.

3

Product Overview Advanced Display and Controls Display up to 16 normal points and 16 alternate points with one or three values per screen. Select from Unity, Kilo, or Mega scaling and up to 11 digits.

SEL provides a worldwide, ten-year product warranty—no questions asked.

Navigate alternate displays and settings. Customize the label insert. Record multiplier, CTR, VTR, and primary Kh. Program LEDs.

Easily change meter forms in the field. Read, test, and program with ANSI Type II optical port. Customize nameplate, serial number, and bar code.

Power Supply Board 2 Inputs 3 Outputs

Main Board Ethernet EIA-232 IRIG-B EIA-232/485

Communications Board Expansion Slot #1 EIA-485 Telephone Modem EIA-232

Sealing Provision

I/O Board PT Board Va, Vb, Vc, Vn

CT Board

Expansion Slot #2 4 Inputs 4 Outputs (solid-state or electromechanical) or 4 Analog Outputs 4 Solid-State Outputs

Ia, Ib, Ic, In

Schweitzer Engineering Laboratories, Inc.

SEL-734 Data Sheet

4

Functional Overview SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

SEL-2032

SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

SEL-734

Apply SEL-734 Meters throughout the power system.

SEL-734 Capabilities Accurate Revenue Metering The SEL-734 exceeds ANSI C12.20 0.2 and IEC 62053-22 0,2 S accuracy class requirements. Transformer/line-loss compensation adds to meter accuracy when the meter location and billing points differ. ACSELERATOR QuickSet Software provides a simple test mode interface to easily verify meter accuracy. Communications and I/O Select from seven communications ports and eight communications protocols, including 10/100BASE-T or 100BASE-FX Ethernet. Advanced communications and protocols, such as DNP3, reduce the need for analog and digital outputs. When installations must communicate with legacy equipment, SEL offers digital and analog output options for the SEL-734. The SEL-2800 Fiber-Optic Transceivers provide electrically isolated communications paths between EIA-232 ports. Load Profile Recorder Twelve independent load profile recorders in the SEL-734P allow simultaneous meter and power quality logging of up to 192 data channels. Select up to 16 channels per recorder and sample rate

SEL-734 Data Sheet

intervals from 3 seconds to 60 minutes. Trend averages, minimum, maximum, changes, and snapshots at a rate of once every three seconds. ACSELERATOR QuickSet offers a fast and simple method to retrieve, plot, and export load profile data to .HHF or .CSV formats. Itron MV-90 meter reading software communicates to any SEL-734 communications port and automates meter reads for large-scale metering installations.

Save LDP data in .HHF or .CSV formats.

Schweitzer Engineering Laboratories, Inc.

5

SEL-734 Capabilities (Continued) Measure and Record the Following: • Harmonic current, voltage, and power to the 50th order with accuracy per IEC 61000-4-7* • Harmonic angles for voltage and current • IEC 61000-4-15 flicker* • High-resolution, 8 kHz waveform capture* • Total harmonic distortion (THD), crest factor, and K-factor metering with up to 50th harmonic content • High-speed load profile recording with three-second resolution* • VSSI • Symmetrical components (unbalance)

View event records and waveform captures of system anomalies.

VSSI reports detail system interruptions with 1 ms resolution.

* SEL-734P benefits

VSSI Recorder Correlate system disturbances with the voltage sag/swell/interruptions (VSSI) recorder. Enabled from the factory, the VSSI recorder time-stamps voltage excursions with up to 1ms resolution and records indefinitely using an adaptive sampling rate. The SEL-734 stores and reports residual voltage, duration, affected phases, CBEMA/ITIC reports, and time stamp of occurrence. The VSSI settings include trigger thresholds from ±1% to ±95% of the actual value and automatic recording duration dependent on the length of the voltage excursion. ACSELERATOR QuickSet automatically graphs and analyzes VSSI data, and includes an export feature. Applications with SCADA systems can also retrieve these data using the DNP3 protocol.

SWELL SAG Upper Voltage Limit Lower Voltage Limit Voltage Profile

TOU Metering Record demand and energy consumption with a user-defined calendar; use TOU metering to bill consumption at different rates based on season, day type, and time of day. The program automatically self-reads and resets demand; there is no need to manually reset meters.

Harmonic Metering Monitor, record, and control using individual harmonic values, THD, and K-factor with resolution up to the 50th harmonic.

Interharmonic Metering Measure, record, and control using Group THD. Measure interharmonics from 20 Hz to 3285 Hz in 5 Hz bins.

Schweitzer Engineering Laboratories, Inc.

TOU stores and resets peak demand data.

SEL-734 Data Sheet

6

SEL-734 Capabilities (Continued) IN (Delivered)

Transformer/Line-Loss Compensation When the contractual billing point differs from the meter location, use transformer and line-loss compensation (TLLC) to optimize the metering location and reduce the instrument transformer costs.

BP2

Power Substation

High Voltage Transmission Lines

OUT (Received)

BP3

BP1 Transmission Substation

Substation With Distribution Bus

Power Poles

BP4 IN (Delivered)

Choose from four billing and metering points with TLLC.

59.996 Hz

60.003 Hz

59.996 Hz

Pullman, WA

Chicago, IL

Philadelphia, PA

Chic ago

Tampa

Pullman ia lph

ade

Phil

60.015 Hz Monterrey, Mexico

60.0 Hz

60.007 Hz

San Antonio, TX

Tampa, FL

Mon

terr ey

io ton An San

Synchronized Phasor Measurement Combine the SEL-734 with an SEL IRIG-B time source to measure the system angle in real time with a timing accuracy of ±10 µs. Measure instantaneous voltage and current phase angles in real time to improve system operation with synchrophasor information. Replace state measurement, study validation, or track system stability. Synchronized phasor measurements use the SEL Fast Message synchrophasor protocol and exceed the Level 0 accuracy requirements defined by IEEE C37.118–2005. Use SEL-5077 SYNCHROWAVE® Server Software* or SEL-5078 SYNCHROWAVE Console Software* to view system angle at multiple locations for precise system analysis and system-state measurement, shown to the right.

View system angle at multiple locations.

*Additional cost software.

Predictive Demand The predictive demand function monitors accumulated demand and alarms when the demand exceeds a user-defined limit. The SEL-734 can then shut down loads or peak-shave with generation to avoid demand charges as shown to the right. The predictive demand alarm is available through Modbus, DNP, MIRRORED BITS communications, or the front-panel LEDs.

Frequency Recording Measure frequency for local and remote indication or use in control and data acquisition. Use a load profile recorder for a “strip chart” record of the frequency as often as every three seconds.

Avoided Demand Charge Load

New Peak Predicted

Daily Load Profile

Reduce peak demand charges with the predictive demand alarm.

Minimum/Maximum Metering The SEL-734 automatically records the date and time of minimum and maximum voltage, current, and power measurements. Use this capability for equipment selection, troubleshooting, and diagnosis of any installation. Capture minimum/maximum quantities with 25 ms resolution.

SEL-734 Data Sheet

Schweitzer Engineering Laboratories, Inc.

7

SEL-734 Capabilities (Continued) Logging and Recording Store a minimum of 16,000 sequential events records capturing any power quality disturbance. Retrieve data using ACSELERATOR QuickSet software, Modbus, DNP3, or ASCII. Store and analyze waveform capture data using ACSELERATOR QuickSet. Automatic Event Reporting After recording an event report, the SEL-734 can automatically report event data through SEL or DNP3 protocols to a communications master. SEL-5040 software can automatically collect SEL-734 waveform data without the need for manual retrieval. Password Protection Three password levels ensure protection of critical meter configuration and billing data. Password levels include read only, limited read/write, and full read/write capabilities.

Monitor device and power system events with the Sequential Events Recorder (SER).

Programmable Logic (SELOGIC Control Equations) The meter provides user-programmable logic to combine meter calculations, contact inputs, remote command inputs, and timers to control internal logic and contact outputs. The logic allows the following operations: • Logic (OR, AND, NOT) • Math (+, —, x, /) • Analog compare (>,