GE Energy
3.3kV-27kV Embedded Pole Vacuum Circuit Breaker Leading the future of electrification
3.3kV-27kV Embedded Pole Vacuum Circuit Breaker Leading the future of electrification
GE GE is a diversified organization covering a myriad of market segments, including infrastructure, finance and media. From energy, water, transportation and health to access to money and information, GE serves customers in more than 100 countries and employs more than 300,000 people worldwide. The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the original index in 1896.
Industrial Solutions GE Industrial Solutions, a division of GE Energy, is a global leading provider in power distribution, offering a wide range of services and products which include medium and low voltage power distribution equipment and components, motor & control systems and service products that are safe, reliable and offer high performance.
Honour 2010 World's Most Innovative Companies 2011 World’s Most Admired Companies 2009 World’s Most Respected Companies 2011 Best Global Brand
2008 World’s Most Respected Companies
2007 World’s Best R&D Companies
80
More Than 80 Years of Interrupter Experience GE pioneered experimental vacuum interrupters in the 1920s. Refined it and introduced the world's first 15kV Vacuum circuit breaker in the 1960s, To date, this interrupter design has been the world leader in vacuum technology and has accumulated over 45 years of reliable field service.
A World Class Quality Manufactured, assembled and tested all in the same sophisticated facility, SecoVac is the product of state of the art manufacturing processes assured by ISO 9001:2008 and ISO 14001 certification. Precision tooled parts, computer aided design and advanced production techniques, as well as the protection of the 'E Coat' (cathodic electrocoating) paint process have resulted in a standard of excellence unmatched in the industry.
eco
Universal Applications SecoVac is designed, assembled and tested to meet or exceed applicable IEC, GB and DL standards. It is suitable for applications in all major industries including T&D, Oil & Gas, Automotive, Processing plants, Iron and Steel mills, Mining, Commercial buildings, etc. It provides protection for all types of applications: coble, overhead lines, motors, capacitors, transformers, busbar sections, etc.
Environment Conscious Selecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used for SecoVac series MV embedded pole vacuum circuit breaker instead of SF6 gas.
Contents General Introduction GE GE Industrial Solutions
Description Brief Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02 Vacuum Interrupter (VI) . . . . . . . . . . . . . . . . . . . . . . . 04 Application Condition . . . . . . . . . . . . . . . . . . . . . . . . . 05 Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06 Advanced Technology . . . . . . . . . . . . . . . . . . . . . . . . 08 Standards and Quality Control . . . . . . . . . . . . . . . . 08 Environmental Protection . . . . . . . . . . . . . . . . . . . . . 10
Selection Guide Introduction and Type Description . . . . . . . . . . . . 12 Product Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Primary disconnect . . . . . . . . . . . . . . . . . . . . . . . . 12 Breaker mechanism . . . . . . . . . . . . . . . . . . . . . . . 12 Interlock system . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Typical layout for vacuum circuit breaker . . . 13 Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Electric parameter . . . . . . . . . . . . . . . . . . . . . . . . . 14 Overall dimension . . . . . . . . . . . . . . . . . . . . . . . . . 14 SecoVac VB2 Plus L-frame . . . . . . . . . . . . . . . . . 19
Measurement, Protection and Control Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Operation Internal Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . 28 Working Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Vacuum interrupter . . . . . . . . . . . . . . . . . . . . . . . . 30 Working principle of operating mechanism . . . . 30 Spring motor spring charging . . . . . . . . . . . . . . 30 Closing operation . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Anti-Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Tripping operation . . . . . . . . . . . . . . . . . . . . . . . . . 31 Reclosing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Check
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Preparation Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Description
Introduction
02
SecoVac series 3.3kV-27kV vacuum circuit breaker designed by GE is a three-phase AC indoor breaker with 3.3kV-27kV rated voltage and can be applied in controlling and protecting electrical equipment in industrial and mineral enterprises, power plants and substations. The product conforms to the IEC 62271 standard. It is especially suitable for conditions which require frequent operation. The breaker can be installed in the switchgear both in fixed type and withdrawable type. It is the optimum choice for the control and protection of MV power distribution systems.
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Reliability, safety and performance in a compact package
Leading vacuum and insulation technology
Built to highest quality standards
Reliability and safety
GE has developed environmentally
SecoVac circuit breakers are designed
SecoVac circuit breakers have a number
friendly vacuum circuit breakers which
and fully third-party type tested to the
of inbuilt safety capabilities which can be
are capable of reliably switching high
latest IEC 62271-100 and IEC 62271-1
incorporated into the switchgear design.
stress fault currents. Increased dielectric
standards. All SecoVac circuit breakers
Due to its innovative operating
strength of the SecoVac circuit breaker
meet or exceed the electrical and
mechanism the SecoVac breaker has
is achieved through encapsulation of
mechanical endurance requirements of
industry leading reliability that is rated at
the vacuum interrupter in epoxy resin
E2 and M2 in accordance with IEC 62271-
10,000 operations.
material. SecoVac circuit breaker family
100.
Description
SecoVac 3.3kV-27kV Vacuum Circuit Breakers Provide:
utilizes this solid insulation technology that has been catering to a wide scope of applications for years.
Adaptability and versatility SecoVac circuit breakers can be used in a
Environmentally-friendly design
Storage conditions
wide scope of applications such as the
In order to retain all of the functional
protection of transformers, capacitor
units qualities when stored for prolonged
banks, motors. The breaker can be used
periods, we recommend that the
in a wide range of environments to suit all
equipment is stored in its original
regions of the globe.
GE’s vacuum and solid insulation
packaging in dry conditions sheltered
technology is free of SF6 gas that
from the sun and rain at a temperature
contributes significantly to the greenhouse
of between -15°C and 40°C. For storage:
effect and associated climate change.
-30°C. 03
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Vacuum Interrupter (VI)
Maintenance free GE vacuum interrupters are hermetically sealed and offer extensive vacuum integrity. Dedicated to proven reliability, safety and performance, GE vacuum
Description
interrupting technology offers highest quality products which are sealed for life.
Structural durability At the heart of the 3.3kV-27kV IEC circuit breaker portfolio is GE’s proven vacuum interruption technology and eighty years of expertise in this field.
SecoVac circuit breaker is an embedded pole type, which is extremely durable. It can protect the vacuum interrupter from mechanical and climatic influence such as humidity, moisture and dust.
The vacuum interrupter is where current making and
The interrupter is immune to shock and
breaking occurs. Copper chromium contacts provide
vibration.
superior performance characteristics. The vacuum in the arc chamber protects the copper chromium contacts from adverse effects such as contamination and corrosion.
High performance SecoVac circuit breakers provide you with: ●● High dielectric strength ●● High creepage distance ●● High mechanical strength ●● Low moisture absorption ●● Optimum thermal conductivity
Compact size Combined with GE's embedded pole technology, SecoVac circuit breaker has a very compact design. It offers high current and interruption ratings in a small, cost effective package.
04
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Special application condition
●● The ambient air temperature does not
If the actual application conditions differ
exceed 40°C and its average value,
from the normal application conditions,
measured over a period of 24 hours,
circuit breaker and associated devices
does not exceed 35°C. The minimum
and auxiliary equipment shall be designed
ambient air temperature is –15°C
and manufactured to comply with any
(storage and transportation is allowed
special application conditions. For special
at -30°C)
application conditions please consult with
●● For applications above 1,000m please
GE in advance, normally the following
refer to chapter 4.2.2 of IEC 60071-2
special service conditions maybe
(see following table for reference)
encountered:
●● The conditions of humidity are as
●● The installation location is more than
follows:
1,000m above sea level ●● The ambient temperature is between
- The average value of the relative humidity, measured over a period of
-15°C and 40°C, for other conditions
24 hours, does not exceed 95%
please contact GE sales for further detail
- The average value of water vapor
●● The circuit breaker current and
pressure, measured over a period of
dielectric ratings must be lowered for
24 hours, does not exceed 2.2kPa
high altitude and elevated temperature
- The average value of the relative
applications
humidity, measured over a period of one month, does not exceed 90% - The average value of water vapor pressure, measured over a period of one month, does not exceed 1.8kPa ●● Seismic intensity to UBC zone 4 or GB
intensity 9 ●● No adverse operating environment
such as dust, humidity, vermin, polluted ambient and high altitude operating site
m 1,000 1,500 2,000 2,500 3,000 3,500 4,000
Altitude Derating MV K (m=1) V 1 1 1.062 0.94 1.132 0.88 1.2 0.83 1.28 0.78 1.36 0.74 1.44 0.69
K (m=0.9) 1 1.056 0.12 1.18 1.246 1.32 1.39
In 1 0.95 0.89 0.85 0.80 0.76 0.72
IEC 60071-2, 4.2.2 the altitude correction factor can be calculated using the following equation, which modified to reflect that no correction is required up to 1000m.
Kа=e Where H Is the altitude, in metres m Is taken as a fixed value in each case for simplification as follows m = 1 for power frequency, lightning impulse and phase-to-phase switching impulse voltages m = 0.9 for longitudinal switching impulse voltages m(H-1000)/8150
Description
High performance
Environment
Application Condition
05
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Applications
Utilities and power plants Power generation stations Transformer stations Switching stations
Description
Main and auxiliary switchgear
Industry Oil and Gas Mining Marine Pulp and Paper Cement Textiles Chemicals Automotive Petrochemical Data Center Metallurgy
Transport Airports Ports Railways Underground transport
Services Supermarkets Shopping malls Hospitals Large infrastructures and civil works
06
Description
Applications
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
07
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Advanced Technology
Standard and Quality Control
High adaptability ●● Compare to traditional design,
enhanced reliability ●● Less resistance ●● Less mechanical parts ●● Various applications for different
Description
climates
Quality
Type test
SecoVac circuit breakers provide you with:
●● Dielectric test
●● IEC standard, 3rd party KEMA
●● Temperature rise test
certification ●● Advanced manufactoring process
ensured quality ●● Advanced testing equipment
Mechanical structure
●● Withstand current test ●● Mechanical operation test ●● ES-Mechanical operation test ●● Capacitive current switching test
●● Integrated routing test
●● Single modular design ●● Integrate closing/opening module ●● Compact size, less than 86 parts ●● Enhanced reliability ●● Low maintenance
Standard 3.3kV-27kV Embedded Pole Vacuum Breaker complies with the standards and specifications and has been type tested
earth switches ●● IEC 62271-1:2007 the common
in accordance with the following IEC
specification for high voltages
publications:
switchgear and control gear standards
●● IEC 62271-100:2008 high-voltage
alternating current circuit breaks ●● IEC 62271-200:2003 AC metal enclosed
switchgear and control gear for rated voltages above 1kV and up to 52kV 08
●● Alternating current disconnector and
●● IEC 60529:2001 degrees of protection
as provided by enclosures (IP code)
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Gelation) technology and advanced vacuum mixing and degassing technology. The Vogel clamping machine is an essential piece of equipment to ensure the mechanical and insulating strength of the embedded pole of 3.3kV-27kV series MV embedded pole vacuum circuit breaker. As well as the processing facilities, the testing facilities are also very important to the quality control of the breaker. In the manufacturing process of SecoVac, from incoming material quality control to the final inspection and testing, every step is strictly calibrated and tested. Every embedded pole goes through the following inspection and testing before it is allowed into the breaker assembly line: ●● X-ray inspection ●● Power frequency withstand voltage test ●● Partial discharge measurement ●● Thermal cycling test
g
GE Energy Industrial Solutions 1) Each position for withdrawable units shall be clearly indicated. The operation 3.4 shall be flexible and reliable. 2) Functional units with same type and same size should be interchangeable
Routine tests Report(MV switchgear) Project Name
Contract No.
Type
Serial No. Rated Normal Current
Rated Voltage Breaker No. Applicable Standards:
___________kV
IEC62271-200: 2003
Item No. Description 1 1.1
Result
4
□Pass □Fail
5
Insulation resistance between main circuit and earth after Power-frequency withstand voltage test:__________Ω .
□Pass □Fail
6
Power-frequency withstand voltage test of auxiliary circuit. __________kV, 1s, without breakdown
□Pass □Fail
7
Actual electrical connection, including auxiliary switches and meters, should comply with diagrams. Operation test should be correct. (sample check of polarity, ratio)
□Pass □Fail
8
Resistance measurement of main circuit Phase A(L1)______________μΩ Phase B(L2)______________μΩ Phase C(L3)______________μΩ
□Pass □Fail
9
Inspection of protection degree(IP_______).
10
Cleanliness check (dust & impurities are not allowed)
Remark
Structure inspection Check overall dimensions, Coating, electroplating.
□Pass □Fail
Right installation of components. Mark, 1.2 size, amount and nameplates, etc. should comply with requirement of drawings.
□Pass □Fail
Arrangement and main circuit connection should comply with single-line diagrams 1.3 provided by customer and technical specification.
□Pass □Fail
2
Checking of torque for main busbar joint shall meet the requirement.
3
Mechanical characteristics and mechanical operation test
Close and open breaker 5 times repeatedly without malfunction; 3.1 Repeat inserting and drawing out truck unit 5 times without malfunction. 3.2
□Pass □Fail
Insulation resistance between main circuit and earth before Power-frequency withstand voltage test :________Ω Power-frequency withstand voltage test of main circuit. Ambient temperature__________℃ Relative humidity ____________% 1) Phase to phase, phase to earth __________kV, 1min, without breakdown. 2) Across the isolating distance __________kV, 1min, without breakdown.
__________ A
Conclusion Inspector/ Date
Inspect anti-pumping function of breaker 3 times repeatedly.
1) Mechanical characteristic of main C.B. should meet the technical specification. Repeat charging the breaker 3 times, under 85% and 110% rated voltage respectively without malfunction. 2) The breaker should not be tripped below 30% rated voltage, 3 times 3.3 repeatedly. the range of control voltage for circuit breakers are as follows:85%~110% rated voltage, circuit breaker should be reliably closed; 70%(DC) / 85%(AC)~110% rated voltage, circuit breaker should be reliably opened; 3 times repeatedly.
□Pass □Fail
□Pass □Fail □Pass □Fail
11 Accompanying documents all ready. 12 Spare parts all ready.
□Pass □Fail
□Pass □Fail
Operate mechanical interlock device 5 times, without failure.
3.5
13 Accessories all ready.
□Pass □Fail □Pass □Fail □Pass □Fail □Pass □Fail □Pass □Fail
Remarks
Before delivery, the following tests and inspections will be done for 3.3kV-27kV embedded pole vacuum circuit breakers in factory by means of advanced testing equipment: ●● Dynamic characteristics measurement (Closing/opening speed, contact bounce, wipe
etc.) ●● Power frequency withstand voltage testing ●● Inspection of interlocking system between breaker and withdrawable unit ●● Secondary wiring inspection ●● Circuit resistance measurement
Description
The high quality of the embedded pole is achieved by using the latest APG (Auto Pressure
Quality Control
The state-of-the-art processing and advanced quality control
09
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Environmental Protection Selecting low environmental impact technologies has become increasingly important when choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used for 3.3kV-27kV series MV embedded pole vacuum circuit breaker instead of SF6 gas. Manufactured, assembled and tested all in the same sophisticated facility, SecoVac is the product of state-of-the-art manufacturing
Description
processes assured by ISO 9001:2000 and ISO 14001 certification.
10
Using precision tools, computer-aided design and advanced production techniques.
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Selection Guide Introduction and Type Description . . . . . . . . . . . . 12 Product Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Typical layout for vacuum circuit breaker . . . 13 Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Electric parameter . . . . . . . . . . . . . . . . . . . . . . . . . 14 Overall dimension . . . . . . . . . . . . . . . . . . . . . . . . . 14 SecoVac VB2 Plus L-frame . . . . . . . . . . . . . . . . . 19
Selection Guide
Primary disconnect . . . . . . . . . . . . . . . . . . . . . . . . 12 Breaker mechanism . . . . . . . . . . . . . . . . . . . . . . . 12 Interlock system . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
11
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Selection Guide Introduction and Type Description Up to 17.5kV SecoVac
-ŕ
SecoVac Series Rated voltage: VB2 Plus vacuum 7.2kV, 12kV, circuit breaker 15kV, 17.5kV
/T
Spring operating mechanism
24kV, 27kV SecoVac
-ŕ
SecoVac Series Rated voltage: VB2 Plus vacuum 24kV, 27kV circuit breaker
/T
Spring operating mechanism
ŕ-
Rated current (A): 630, 1250, 1600, 2000, 2500, 3150, 4000* (*force cooling)
ŕ-
Rated current (A): 630, 1250, 2000, 2500
ŕ
Rated short-circuit breaking current (kA): 25, 31.5, 40
ŕ
W: Withdrawable; F: Fixed
ŕ
Rated short-circuit breaking current (kA): 25, 31.5
ŕ
W: Withdrawable; F: Fixed
Selection Guide
Product Structure
12
SecoVac 3.3kV-27kV Breaker Features
Front panel
Primary disconnect
Breaker mechanism
Front panel fits into a collar frame in the
The primary disconnect cycloid (tulip)
All the mechanical parts of the mechanism
equipment when the breaker is in the
contact set is rugged and easy-to-inspect.
are integrated into individual opening
connect position. It provides a metal
Designed for optimum contact area,
and closing modules. The modules are
barrier between the breaker compartment
it is manufactured from silver-plated
universal to SecoVac embedded pole
and the secondary device compartment.
copper and tested for continuous and
vacuum circuit breaker series, regardless
Clearly marked and easy-to-read
short-circuit current ratings. The tulip
of rating. The module design assures no
operating controls and indicators include
cluster design expands easily, providing
mechanical adjustment is required after
trip button, close button, open/close
better finger contact area than flat type
replacement. This offers the user shorter
indicator, charge/discharge indicator,
contact designs, and delivering proper
lead-times and reduces operational and
operations counter and provision for
contact integrity throughout the life of the
maintenance costs.
manually charging the breaker.
equipment.
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Interlock system
Undercart
For personnel safety, SecoVac 3.3kV-27kV
SecoGear offers manual operation
is designed with a number of mechanical
undercart system which can be operated
and electrical interlocks. For example,
for racking in and out. The undercart has
breaker contacts must be open before
an interlock with earthing switch, which
the breaker can be moved from test to
prevents misoperation. And it also allows
connected position. A positive mechanical
earthing function of circuit breaker by
stop is provided when the breaker
means of metallic structure.
reaches the connect or test/disconnect positions. Mechanical rejection interlocks are provided to permit only the insertion of properly rated breakers into specific compartments. These and other necessary interlocks provide a comprehensive safety system. Furthermore, springs automatically discharge when the breaker is withdrawn from the connect position and breakers
Typical layout for vacuum circuit breaker
1
Tripping button
2
Status indicator for charging
3
Closing button
4
Counter
5
Indicator for open or close
6
Charging handle
1 3 2
4 5
Selection Guide
cannot be inserted in the closed position.
6
Figure 1. Front facial of the circuit breaker
1 1
Upper contact arm
2
Embedded poles
3
Lower contact arm
4
Tulip cluster
2 3 4
Figure 2. Primary circuit
13
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Spare parts The following spare parts are available to be ordered. If required please contact GE. Description Auxiliary switch F10-18 Auxiliary switch GDF-5 Trip coil Position coil Micro Position switch Energy charge motor
Remarks 1 part per breaker 2 parts per breaker 1 part per breaker 1 part per breaker 3 parts per breaker 1 part per breaker
Description Counter Oil buffer Control wiring board Electromagnet for locking Electromagnet for locking truck
Remarks 1 piece per set 1 piece per set 1 piece per set 1 piece per set 1 piece per set
Selection Guide
Electrical parameter Rated Voltage
kV
Rated Current
A
Frequency Rated Power Frequency Withstand Voltage (1min) Rated Lightning Impulse Withstand Voltage (Peak Values) Rated Short Circuit Breaking Current Rated Short Time Withstand Current (3s) Rated Peak Withstand Current Rated Peak Making Current Capacitor Bank Switching Current Electrical Endurance Mechanical Endurance Rated Auxiliary Control Voltage Opening Time Closing Time
3.3~12
15
17.5
24
630/1250/1600/2000/ 2500/3150/4000*
Hz kV kV kA kA kA kA A No. of times No. of times V ms ms
50/60 36 95 25/31.5/40 25/31.5/40 65/82/104 65/82/104
28 75
27
630/1250/1600/2000/2500 38 95
488
50/60 65 125 25/31.5 201.5 25/31.5 65/82 65/82
400 (C2) E2 10,000 (M2) 36/48/60/110/220/240 V DC 110/220 V AC 20~50 30~70 e
户内高压真空断路器
Vacuum circuit breaker GE Consumer & Industrial Systems 产 品 型 号 Type designation 出 厂 编 号 Serial number 额 定 电 压 kV Rated voltage(Ur) 额 定 电 流 A Rated normal current(Ir) 额 定 频 率 Hz Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) kV Rated lightning impulse withstand voltage(Up) 额 定 短 路 开 断 电 流 kA Rated short-circuit breaking current(Isc) 额 定 短 时 耐 受 电 流 kA Rated short time withstand current (4s) 额 定 电 缆 充 电 开 断 电 流 A Rated cable-charging breaking current 电 机 电 压 V motor voltage 分 闸 合 闸 装 置 电 压 V Rated supply voltage of closing and opening devices 执 行 标 准 Relevant standarder 额 定 操 作 顺 序 O-0.3s-CO-180s-CO Rated operating sequence 重 量 kg Weight 出 厂 日 期 Manufacture date
Overall dimension
注意!
高压危险!请严格遵守操作规程。 Warning! High voltage dangerous! Always observe the instruction manual and follow the rules.
上 海 通 用 电 气 开 关 有 限 公 司 Shanghai GE Breakers Co.,Ltd.
SecoVac 3.3kV-17.5kV/630~1250A-25~31.5kA (Phase to phase distance: 150mm) 502 516 531
Withdrawable type 488
488 201.5
201.5
637
637
275±1
275±1
ØD
ØD
150±1
e
78
280±1
注意!
高压危险!请严格遵守操作规程。 Warning! High voltage dangerous! Always observe
户内高压真空断路器
95.5
the instruction manual and follow the rules.
上 海 通 用 电 气 开 关 有 限 公 司 Shanghai GE Breakers Co.,Ltd.
kV kA kA A V
注意!
V
高压危险!请严格遵守操作规程。 Warning!
O-0.3s-CO-180s-CO
436±1
High voltage dangerous! Always observe
kg
the instruction manual and follow the rules.
上 海 通 用 电 气 开 关 有 限 公 司
32
Shanghai GE Breakers Co.,Ltd.
502 150±1
492±1 456
516 531
150±1
14
492±1 456
76
502 516 531
599±1
436±1 150±1
150±1
599±1
95.5
A
78
kV
Hz
76
产 品 型 号 Type designation 出 厂 编 号 Serial number 额 定 电 压 Rated voltage(Ur) 额 定 电 流 Rated normal current(Ir) 额 定 频 率 Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) Rated lightning impulse withstand voltage(Up) 额 定 短 路 开 断 电 流 Rated short-circuit breaking current(Isc) 额 定 短 时 耐 受 电 流 Rated short time withstand current (4s) 额 定 电 缆 充 电 开 断 电 流 Rated cable-charging breaking current 电 机 电 压 motor voltage 分 闸 合 闸 装 置 电 压 Rated supply voltage of closing and opening devices 执 行 标 准 Relevant standarder 额 定 操 作 顺 序 Rated operating sequence 重 量 Weight 出 厂 日 期 Manufacture date
280±1
e
户内高压真空断路器
Vacuum circuit breaker GE Consumer & Industrial Systems 产 品 型 号 Type designation 出 厂 编 号 Serial number 额 定 电 压 kV Rated voltage(Ur) 额 定 电 流 A Rated normal current(Ir) 额 定 频 率 Hz Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) kV Rated lightning impulse withstand voltage(Up) 额 定 短 路 开 断 电 流 kA Rated short-circuit breaking current(Isc) 额 定 短 时 耐 受 电 流 kA Rated short time withstand current (4s) 额 定 电 缆 充 电 开 断 电 流 A Rated cable-charging breaking current 电 机 电 压 V motor voltage 分 闸 合 闸 装 置 电 压 V Rated supply voltage of closing and opening devices 执 行 标 准 Relevant standarder 额 定 操 作 顺 序 O-0.3s-CO-180s-CO Rated operating sequence 重 量 kg Weight 出 厂 日 期 Vacuum circuit breaker GE Consumer & Industrial Systems Manufacture date
32
492±1 456
150±1
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Fixed type ∅62
Terminal section 150
150
275
M16 Depth 22mm
838
451.5 GE Engery
Industrial Solutions 产 品 型 号 Type designation 出 厂 编 号 Serial number 额 定 电 压 Rated voltage(Ur) 额 定 电 流 Rated normal current(Ir) 额 定 频 率 Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) Rated lightning impulse withstand voltage(Up) 额 定 短 路 开 断 电 流 Rated short-circuit breaking current(Isc) 额 定 短 时 耐 受 电 流 Rated short time withstand current (3s) 额 定 电 缆 充 电 开 断 电 流 Rated cable-charging breaking current 电 机 电 压 motor voltage 分 闸 合 闸 装 置 电 压 Rated supply voltage of closing and opening devices 执 行 标 准 Relevant standarder 额 定 操 作 顺 序 Rated operating sequence 重 量 Weight 出 厂 日 期 Manufacture date
376.5
户内高压真空断路器
Vacuum circuit breaker
kV
4-M12
A Hz kV kA
237
e
kA A V V
注意!
高压危险!请严格遵守操作规程。 Warning!
2V&2V&2 2V&2V&2 kg
High voltage dangerous! Always observe the instruction manual and follow the rules.
上 海 通 用 电 气 开 关 有 限 公 司 Shanghai GE Breakers Co.,Ltd.
370 450
275
45
118
443
e
户内高压真空断路器
GE Consumer & Industrial Systems 产品型号 Type designation 出厂编号 Serial number 额定电压 Rated voltage(Ur) 额定电流 Rated normal current(Ir) 额定频率 Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) Rated lightning impulse withstand voltage(Up) 额定短路开断电流 Rated short-circuit breaking current(Isc) 额定短时耐受电流 Rated short time withstand current (4s) 额定电缆充电开断电流 Rated cable-charging breaking current 电机电压 motor voltage 分闸合闸装置电压 Rated supply voltage of closing and opening devices 执行标准 Relevant standarder 额定操作顺序 Rated operating sequence 重量 Weight 出厂日期 Manufacture date
Vacuum circuit breaker
kV A Hz kV kA kA A V
注意!
V
高压危险!请严格遵守操作规程。 Warning!
O-0.3s-CO-180s-CO
High voltage dangerous! Always observe
kg
the instruction manual and follow the rules.
上海通用电气开关有限公司 Shanghai GE Breakers Co.,Ltd.
SecoVac 3.3kV-17.5kV/T1250~4000A-40kA (Phase to phase distance: 275mm) 852 864 881
Withdrawable type 838
838
376.5
310 ±1 295 ±1
e
户内高压真空断路器
A Hz kV kA kA A V
Vacuum circuit breaker
注意!
V
高压危险!请严格遵守操作规程。 Warning!
O-0.3s-CO-180s-CO
kV A Hz kV kA kA A V
注意!
V
高压危险!请严格遵守操作规程。 Warning!
O-0.3s-CO-180s-CO
High voltage dangerous! Always observe
kg
86
kV
86
GE Consumer & Industrial Systems 产品型号 Type designation 出厂编号 Serial number 额定电压 Rated voltage(Ur) 额定电流 Rated normal current(Ir) 额定频率 Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) Rated lightning impulse withstand voltage(Up) 额定短路开断电流 Rated short-circuit breaking current(Isc) 额定短时耐受电流 Rated short time withstand current (4s) 额定电缆充电开断电流 Rated cable-charging breaking current 电机电压 motor voltage 分闸合闸装置电压 Rated supply voltage of closing and opening devices 执行标准 Relevant standarder 额定操作顺序 Rated operating sequence 重量 Weight 出厂日期 Manufacture date
户内高压真空断路器
Vacuum circuit breaker
735
735
310 ±1 295 ±1
e
GE Consumer & Industrial Systems 产品型号 Type designation 出厂编号 Serial number 额定电压 Rated voltage(Ur) 额定电流 Rated normal current(Ir) 额定频率 Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) Rated lightning impulse withstand voltage(Up) 额定短路开断电流 Rated short-circuit breaking current(Isc) 额定短时耐受电流 Rated short time withstand current (4s) 额定电缆充电开断电流 Rated cable-charging breaking current 电机电压 motor voltage 分闸合闸装置电压 Rated supply voltage of closing and opening devices 执行标准 Relevant standarder 额定操作顺序 Rated operating sequence 重量 Weight 出厂日期 Manufacture date
the instruction manual and follow the rules.
High voltage dangerous! Always observe
kg
上海通用电气开关有限公司
the instruction manual and follow the rules.
Shanghai GE Breakers Co.,Ltd.
上海通用电气开关有限公司
852 864 881
836±1 Fixed type (794) 275±1
586±1
836±1 (794)
275±1
76
76
Shanghai GE Breakers Co.,Ltd.
852 864 881
836±1 (794)
275±1
Ø109
Ø109
275±1
Selection Guide
376.5
95.5
95.5 361±1586±1
39
361±1
39
275±1
275±1
30 110
275
Terminal section
275
27
100
∅80 4-M10
451.5
310
(20mm in depth)
GE Engery
户内高压真空断路器
Vacuum circuit breaker
4-M12
kV A Hz kV
252
e
Industrial Solutions 产 品 型 号 Type designation 出 厂 编 号 Serial number 额 定 电 压 Rated voltage(Ur) 额 定 电 流 Rated normal current(Ir) 额 定 频 率 Rated frequency 额 定 雷 电 冲 击 耐 压 (峰值) Rated lightning impulse withstand voltage(Up) 额 定 短 路 开 断 电 流 Rated short-circuit breaking current(Isc) 额 定 短 时 耐 受 电 流 Rated short time withstand current (3s) 额 定 电 缆 充 电 开 断 电 流 Rated cable-charging breaking current 电 机 电 压 motor voltage 分 闸 合 闸 装 置 电 压 Rated supply voltage of closing and opening devices 执 行 标 准 Relevant standarder 额 定 操 作 顺 序 Rated operating sequence 重 量 Weight 出 厂 日 期 Manufacture date
kA kA A V V
注意!
2V&2V&2 2V&2V&2
高压危险!请严格遵守操作规程。 Warning!
kg
High voltage dangerous! Always observe the instruction manual and follow the rules.
上 海 通 用 电 气 开 关 有 限 公 司 Shanghai GE Breakers Co.,Ltd.
720 34.5
275
118
788
15
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Overall dimension SecoVac 3.3kV-17.5kV/T1250A/2000A-40kA (Phase to phase distance: 210mm) Withdrawable type
Fixed type 210
210
110 100
2XM10-Depth 15mm
45°
78
70
252
310
Selection Guide
M18 Depth 25mm
520 588
16
33.5 586
118
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
SecoVac 24kV-27kV/T630~1250A-31.5kA (Phase to phase distance: 210mm) Withdrawable type
Fixed type 210
210
Terminal section
70
302
665
Selection Guide
310
M18 depth 25mm
45,0°
52,0 520
4-M12
275
118
588
17
ø109
310±1
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
345±1
Overall dimension e
SecoVac 24kV-27kV/1250~2500A-31.5kA (Phase to phase distance: 275mm) Withdrawable type
881
ø109
838
ø109
838
852
112,5
64
74 74
112,5
64
345±1
e e
345±1
852 881
852
320 651±1 651±1
881
320
Fixed type 275±1,5 275±1,5
275±1,5 275±1,5
30 27
Terminal section 275
4-M10 depth 20mm
15 30
310
45
452
730
5
4-M12 720 788
18
ø82
145 100
305
Selection Guide
275
25
275
118
762
762
310±1
310±1
275±1,5
275±1,5
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
SecoVac VB2 Plus L-frame
B
A View 1250A spout
A
N
ØE
690
7
G
3150A Spout
453
∅1
M10 25mm depth M12 35mm depth H F F+9
65
9 16-∅
50
∅60
110
2
255
380 255
D±1
260
L
J
M10 23mm depth
C±1
270
M8 20mm depth
M R-∅
A View
31.5
SecoVac 3.3kV-17.5kV
200
200
216
I
59
P±1
P±1
59
1250A 25X84 3150A 42X126
725
B 794
C 275
D 453
E 49
F 632
G 1031
H 310
I 934
800mm 1250/2000A
915
781
310
468
90
782
1039
460
977
1000mm 3150A
915
779
310
468
109
982
1039
660
969
J 78 124/1250A 114/2000A 101
L 556
M 75
N 150
R 2
NA 584
P 150
NA
NA
NA
210
0
137.5
5
275
N 170 223
P 210 275
SecoVac 24kV-27kV A B
Selection Guide
A 914
650mm 1250A
25
C±1
73
N
m
0m
0X3
2500A Spout 60
G
M1
91 245.5
L
K
D±1
12
M J
E
E
120
197.5
mm
45
6X
M1
197.5 H F
I 896
P± 1 P± 1
800mm 1250A 1000mm 2500A
A 1142 1142
B 896 896
C 310 310
D 617.5 617.5
E 157.5 150
F 792 992
G 1121.5 1121.5
H 460 660
I 1142 1264
J 26 41
K 185 150
L 145 150
M 40 69.5
19
Measurement, Protection and Control
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
20
Measurement, Protection and Control Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Measurement, Protection and Control For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/F650.htm
Multilin 650 Family Advanced protection, control and monitoring system
Key benefits plus programmable logic ●● Flexible and cost effective control for complex systems -
Use IEC compatible programmable logic to customize the functionality of your protection & control system to address unique, site specific applications ●● Human machine interface (HMI) - Standard backlit LCD display
with 4 x 20, optional 16 x 40 (240 x 128 pixels) graphical LCD, programmable buttons and directional keys for selecting setting menus and submenus ●● Minimize replacement time - Modular with card draw-out
construction ●● Reduce troubleshooting time and maintenance costs - IRIG-B
●● Cost Effective Access information - Via multiple protocols,
through standard RS232 & RS485 Ethernet Ports ●● Optimal integration flexibility via open standard protocols -
Modbus RTU, DNP 3.0 Level 2, IEC 60870-5-104, IEC 61850, IEC 870-5-103 ●● Minimize communication down time - Reliable redundant
Ethernet Communication ports with 10/100BaseTX, 100BaseFX with ST connectors and optional double 100BaseFX, with ST connectors ●● Complete asset monitoring - Full metering including demand
& energy ●● Follow technology evolution - Flash memory for product field
upgrade
time synchronization, event reports, waveform capture, data logger
Measurement, Protection and Control
●● Unique built-in control features - Comprehensive protection
Applications ●● F650: Management and primary protection of distribution
feeders and bus couplers ●● F650: Backup protection of busses, transformers and power
lines ●● G650: Packaged generator mains failure detection
●● G650: Distributed generation management device ●● G650: Reliable Distributed Generation interconnection
protection system ●● W650: Wind turbine protection, control and monitoring ●● W650: Distributed generation grid interconnection device 21
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Features Protection and control
User interface
●● Up to 32 Programmable digital inputs
●● Large graphic (16 x 40) or regular (4 x 20) character display
●● Up to 16 digital outputs
●● Easy-to-use control via Shuttle key
●● Trip Circuit Supervision
●● Front USB port or standard RS232
●● Redundant power supply option
●● Rear wire 10/100BaseTX Ethernet for LAN connection
●● Configurable PLC logic according to IEC 61131-3
●● Rear wire CAN bus port (OPEN CAN protocol - W650)
●● Fully configurable graphic display HMI interface
●● Optional fibre optic 100BaseFX Ethernet, single or redundant
●● Alarms panel
●● Optional rear RS485 port ●● 1 ready LED and 15 programmable LED indicators
Monitoring and metering ●● Energy metering
●● Data logger
●● Demand metering
●● Sequence of event
●● Trip circuit monitoring
●● Self diagnostic
●● EnerVistaTM Integrator providing easy integration of data in the
650 relay into new or existing monitoring and control systems
●● Oscillography
Metering
Measurement, Protection and Control
Overview The Multilin 650 family has been designed
screens.
The Multilin 650 provides the following
as a comprehensive protection, control,
The metering capability allows 0.5%
metering values.
metering and monitoring package. The
accuracy for current and 1% from 10V to
●● Current: Ia, Ib, Ic, In, Ig, Isg
microprocessor based architecture
208V for voltage in metering range.
●● Phase-to-phase and phase-to-ground
is a complete solution for different
Monitoring functions include a 479
voltage values for bus and line: Van,
applications that complies with the most
event recorder, and a programmable
Vbn, Vcn, Vab, Vbc, Vca, Vx
relevant international standards.
oscillography recorder.
All the elements required for each
The Multilin 650’s communications
application have been integrated into a
capability and option make the product
single package for a cost-effective, reliable
very unique. These units include
and simple utilization. The low number of
a maximum of three independent
●● Power factor (per phase and total)
components, thanks to the use of state-
communication ports: COM1, COM2
●● Frequency
of-the-art but mature technology, deliver
and COM3, with many physical choices
●● These signals are available for local
a very high reliability.
through the use of two removable plug-
display and accessible remotely using
Hardware inputs and outputs have been
and-play boards.
communications
designed in a modular way that allow
The brain of the Multilin 650 units includes
easy migration from simple to more
a powerful built-in virtual PLC. This PLC
Recording functions
complex applications.
can be programmed according to the IEC
The recording functions within the Multilin
The control functions include a full-
61131-3 language by functional block
650 include:
scheme virtual PLC with an optional
diagrams.
●● Event recorder capable of storing 479
graphical display. The combination of
650 units come with 8 to 32 digital inputs
time-tagged events (1 true millisecond
both elements provide total control for
and with 8 to 16 outputs depending on
accurate tagging)
a bay. This means real-time monitoring
options. All digital inputs may be filtered
of breakers and selector switches, open
with a separate debounce time to tailor
can be stored in memory. The capacity
and close commands supervised by the
customer requirements.
of each record will depend on the type of
programmable interlockings and metering 22
●● Active power (per phase and total) : Wa,
Wb, Wc, W ●● Reactive power (per phase and total) :
VARa, VARb, VARc, VAR
●● Up to 20 separate oscillography records
oscillo selected (1 Mbyte/Max. No. Osc)
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
These records are stored in non volatile
Communications
memory. Therefore, there is no need
Multilin 650 units incorporate up to
for internal battery monitoring or
three ports that operate independently.
maintenance.
Redundant ports are available for high
TCP/IP and IEC 60870-5-104.
reliability applications: Trip circuit monitoring
Available protocols for rear port 1 and 2
Multilin 650 units offer as an option two
are ModBus RTU, IEC 103 and serial DNP
complete supervision circuits for breaker
3.0.
trip and closing coils and circuits. These
The third port is located in a removable
supervision inputs monitor both the
communications card. This plug-and-
battery voltage level and the continuity of
play card can be easily changed in the
the trip and/or closing circuits, applying
future as new standards arrive to the
current through those circuits and
market, thus providing a migration path
checking that it flows properly. In order
to the customer.
to apply this feature it is necessary to
The protocol available for the third port
choose I/O board 1 option 2.
is DNP 3.0 over TCP/IP, UDP/IP, ModBus
User Interface
●● Graphic 16 x 40 or text 4 x 20 LCD display ●● Fluorescent backlight to improve visibility
●● Local/Remote/Off pushbutton with LEDs ●● Key control for easy navigation ●● Ergonomic programmable keys
●● Electrically isolated front USB communication port ANSI Device Numbers & Functions
Functional Block Diagram
1
52 79 1
CLOSE Monitoring
27X
TRIP
3
3
50BF 1
49 3
50PH 50PL 3
3
46
48
3
3
32FP 3
32
32N
3
3
BROKEN CONDUCTOR
3
59X
51PH/V 51PL/V 67P R
R
3
3
3
50N 3
51N 3
3
67N 3
25 1
1
2
50G 3
1
2
51G
67G 3
3
50SG 51SG 3
3
27
59
50IG 3
67SG
METERING
3
3V_0
3
47 3
3
3
VTFF 1
81U 3
81O 3
81R 3
59NH 3
F650 Digital Bay Controller
59NL 3
EN F650 BLOCK F.CDR
Device Number
Function
N/A 81R VTFF
Bus/Line Overvoltage Neutral Overvoltage - High/Low Phase Directional Overcurrent Neutral Directional Overcurrent Ground Directional Overcurrent Sensitive Ground Directional Overcurrent Autorecloser Under/Over Frequency Broken Conductor Detection Load Encroachment Frequency Rate of Change VT Fuse Failure Detection
25 27/27X 32 32FP 32N 46 47 48 49 50 BF 50PH/PL 50N 50G 50SG 50IG 51N 51G 51SG 51PH/V 51PL/V 59/59X 59NH/NL 67P 67N 67G 67SG 79 81 U/O
Synchrocheck Bus/Line Undervoltage Sensitive Directional Power Forward Power Wattmetric zero-sequence directional Negative Sequence Time Overcurrent Negative Sequence Voltage Blocked Rotor Thermal Image - overload protection Breaker Failure Phase Instantaneous Overcurrent (High/Low) Neutral Instantaneous Overcurrent Ground Instantaneous Overcurrent Sensitive Ground Instantaneous Overcurrent Isolated Ground Instantaneous Overcurrent Neutral Time Overcurrent Ground Time Overcurrent Sensitive Ground Time Overcurrent Voltage Restraint Phase Time Overcurrent
Measurement, Protection and Control
●● Multicolor programmable LEDs with label panel
23
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Measurement, Protection and Control For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/3Series.htm
Multilin 3 Series Intuitive industrial and utility protective relay systems for feeders, motors and transformers
Key benefits ●● Easy-to-use and cost effective protection and control for
Measurement, Protection and Control
feeders, motors and transformers ●● Effortless draw-out construction eliminates requirements for
test switches and reduces downtime ●● Environmental monitoring system to alarm on destructive
operating conditions to enable preventative maintenance ●● Easy-to-use interface and set up in one simple step ●● Accelerated Life Cycle Tested to ensure reliability of relay
operation under abnormal conditions ●● Advanced power system diagnostics to increase reliability
through fault and disturbance recording capabilities ●● Arc Flash mitigation via zone inter-tripping, flex curves and
multiple setting groups
●● Application flexibility with the use of programmable logic
elements ●● Large backlit display with 40 characters for easy viewing of
relay information and settings ●● Flexible communications with multiple ports & protocols to
allow seamless integration into new and existing infrastructure ●● Easy access to information via multiple communication
network options including USB, Serial, Fiber & Copper Ethernet ●● Reduced wiring with support for remote I/O ●● Reduce setup and configuration time with the Simplified Motor
Setup screen ●● Powerful Security Audit Trail tool to increase security and
minimize system risks by tracking setting changes
Applications ●● Advanced protection, monitoring & control relays for feeders
(Multilin 350), motors (Multilin 339) and transformers (Multilin 345) ●● Industrial feeders with enhanced breaker monitoring and
diagnostics
24
●● Distribution utility down stream breaker protection ●● Medium voltage utility feeders with advanced control features
including, cold load pickup, auto reclose and multiple setting groups
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Features
Easy-to-use
Protection & control
Drawout construction
(for Multilin 350 Feeder Protection System)
The Multilin 3 Series offers a complete
●● Phase, neutral and ground TOC and IOC
drawout feature eliminating the need for
●● Undervoltage, overvoltage, frequency
rewiring after testing has been concluded.
●● Neutral/ground directional
The withdrawable feature also eradicates
●● Negative sequence overcurrent
the need to disconnect communication
●● ANSI, IAC, IEC, flex curves ●● Cable Thermal Model protection
Overview
cables, e.g. fiber, copper, RJ45, etc and helps retain communication status even
●● Breaker failure
The Multilin 3 Series of protection relays
after a relay has been withdrawn from its
●● Cold load pick-up
are highly functional, economical
case.
●● Four-shot auto reclose
protection relays for feeders, motors and
●● 8 digital inputs, 7 contact outputs
transformers. By providing an economical
●● Two setting groups
system for protection, control, monitoring and metering, and both local and
●● Event Recorder: 256 events with 1ms
time stamping ●● Oscillography with 32 samples per
cycle and digital states ●● IRIG-B clock synchronization ●● Relay & Asset Health Diagnostics ●● Security audit trail
User interface and programming
remote user interfaces in one assembly, the Multilin 3 Series relays effectively eliminate the need for expensive discrete components. The Multilin 3 Series provides detailed diagnostic information allowing users to troubleshoot and minimize downtime. Detailed diagnostics is provided via the 256 1ms time stamped event recorder
Advanced communications
and the 192 cycle Oscillography report
Easy integration into new or existing
sampled at 32 samples per cycle.
infrastructure
The robust Multilin 3 Series streamlines
With several Ethernet and serial port
user work flow processes and simplifies
options, and a variety of communication
engineering tasks such as configuration,
protocols, the Multilin 3 Series provides
wiring, testing, commissioning, and
advanced and flexible communication
maintenance. This cost-effective relay
selections enabling seamless integration
also offers enhanced features such as
into new or existing applications.
diagnostics, preventative maintenance,
The Multilin 3 Series supports various
EnerVista™ software
device health reports and advance
industry standard protocols such as, IEC
●● An industry-leading suite of software
security features.
61850 & IEC 61850 GOOSE, Modbus RTU,
●● 4x20 character LCD display ●● Control panel with 12 LED indicators ●● Front USB and rear serial, Ethernet and
Fiber ports ●● Multiple protocols - IEC 61850 & 61850
GOOSE, ModBus™ RTU, ModBus™ TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
tools that simplifies every aspect of
Modbus TCP/IP, DNP3.0, IEC 60870-5-104
working with Multilin devices
and IEC 60870-5-103.
Measurement, Protection and Control
Metering & monitoring
●● Document and software archiving
toolset to ensure reference material and device utilities are up-to-date
25
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Enhanced diagnostics
EnerVistaTM Launchpad
Security
Preventative maintenance
EnerVista™ Launchpad is a complete set of
Security audit trail
The Multilin 3 Series allows users to track
powerful device setup and configuration tools
The Multilin 3 Series monitors security
relay exposure to extreme environmental
that is included at no extra charge with the SR
and reliability of asset protection. The
conditions by monitoring and alarming
Relays.
Multilin 3 Series protection devices
at high temperatures. This data allows
●● Set up the Multilin 3 Series Relays - and any
offer complete traceability of any
user to proactively schedule regular
other Multilin device - in minutes. Retrieve
relay setting and command changes,
maintenance work and upgrade activities.
and view oscillography and event data at
allowing the user to quickly identify
the click of a button
changes made to the relay.
All relays utilize EnerVista setup TM
●● Build an instant archive on any of the
software for communication, monitoring and metering. Actual values, setpoints,
latest Multilin manuals, service advisories,
status, trending, and waveform capture
application notes, specifications or firmware for your SR Relay
information may all be viewed via
●● Automatic document and software version
the software, and can be used for
updates via the internet and detailed e-mail
troubleshooting.
notification of new releases
User Interface ●● SETPOINT GROUP 1, 2:
Measurement, Protection and Control
These indicators are continuously on if corresponding group provides settings for protection elements. TRIP: Indicator turns on when relay detects a trip condition. Operates the trip relay to open the breaker. ALARM: While relay detects an alarm condition, indicator flashes. PICKUP: Indicator lights steady when any protection feature pickup threshold exceeded.
●● DISPLAY:
4 line text for easy viewing of key data.
●● LEDs:
10 LED indicators for quick diagnostics.
●● KEYPAD:
Ten button keypad for access to device interrogation and change of settings.
●● FRONT PORT:
Electrically isolated front USB communication port.
Protection Features
ANSI Device Numbers & Functions
BUS BUS VT 52 79 TRIP 3
CLOSE
1
50N 2
51P 2
51N 1
CLP 1
50_2 1
50BF
49
1
1
59X
59_2 1
1
59N
81U
1
81O
2
2
METERING 1
79
50G/ 51G 51G
50G
TRANSIENT RECORDER EVENT RECORDER
1
350 RELAY
26
27X 1
MONITORING 50P
LOAD
59P
27P 1
2
Device Number 27P 27X 49 50P 50N 50G 50BF 50_2 51P 51G 51N 59P 59X 59N 59_2 67G 67N 79 81U 81O CLP
Function Phase Undervoltage Auxiliary Undervoltage Thermal Model Phase Instantaneous Overcurrent Neutral Instantaneous Overcurrent Ground/Sensitive Ground Instantaneous Overcurrent Breaker Failure Negative Sequence Overcurrent Phase Timed Overcurrent Ground Timed Overcurrent Neutral Timed Overcurrent Phase Overvoltage Auxiliary Overvoltage Neutral Overvoltage Negative Sequence Overvoltage Ground Directional Overcurrent Neutral Directional Overcurrent Autoreclose Underfrequency Overfrequency Cold Load Pickup
Latched Lockout available as a standard feature
Operation
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Operation Internal Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . 28 Working Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Vacuum interrupter . . . . . . . . . . . . . . . . . . . . . . . . 30 Working principle of operating mechanism . . . . 30 Spring motor spring charging . . . . . . . . . . . . . . 30 Closing operation . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Anti-Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Tripping operation . . . . . . . . . . . . . . . . . . . . . . . . . 31 Reclosing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Preparation Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
27
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Internal Wiring Diagram Withdrawable Type Spring Charge Motor 26
24
Closing Circuit
Breaker Interlock Circuit
10
25
V2
36
(22) S1
34
35
11
4
Operation
S9
14
21
43
22
S5 44
S9
34
13
33 34
S8
14
24
23 24
S8
13 S5
57
V5 A~ C+ B-
K0
(11)
(74)
S5
S5
(12)
91
31
41
71
61
63
23
33
83
93
92
32
42
72
62
64
24
34
84
94
S5
(2)
S8
53
43 44
S9
54
31
32
16 13 15 17 19 33 37 38
39 18
40
55
S9
S9
54
53 S8
54
S8
81 S5
21 22 51 50
82
12
S5
14
48
49 58
56
S9: Limit switch (service position)
CC: Closing coil
KO: Anti-pumping relay (optional)
S8: Limit switch (testing position)
TC: Trip coil
BC: Electromagnet for locking (optional)
S4: Electromagnet for locking's auxiliary switch
M: Spring Charge Motor
ZC: Electromagnet for locking truck (optional)
S5: Auxiliary switch
V1~V4: Rectifier
S1~S3: Energy storing limit switch Note: 1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state. 2. The polarity in dashed frame should be connected to common DC voltage terminal. 3. Rectifier will be removed if DC supply voltage is being used.
28
D~
2
53
23
33
13 14
47
1
V3
(73)
(54) S5
20
2
8
29
ZC
43 44
S3
9 23 27 28
BC
(21)
(14)
7
Y4 1
(53) S5
(3)
S3
5
TC
S4
(5)
(22)
3
S2
M (51) (52)
Truck Interlock Circuit 6
CC
K0 (13) (14)
(13)
30
V4
V1
(21)
Opening Circuit
52
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Fixed Type Spring Charge Motor
Breaker Interlock Circuit Opening Circuit 30
52
10
25
24
26
Closing Circuit
V2
M
S4
S5
(73)
(54) S5
(74)
(3)
(14)
36
35
2
43 S5 44 S5
21 22
(12)
S5
91
31
41
71
61
63
23
33
83
93
92
32
42
72
62
64
24
34
84
94
S5
(22) S1
11
22
(11) S5
(2) K0
(21) S3
34
21
8
51
31
32
16 13 15 17 19 33 37 38
39 18
4
13
81
14 S5
82
12
50
20
Operation
(13)
9 23 27 28 29
BC
(53)
(5)
(22) S3
7
TC
(13) (14) S2
(21)
5
CC
K0
(51) (52)
3
V3
V4
V1
6
S5
14
S4: Electromagnet for locking's auxiliary switch
CC: Closing coil
KO: Anti-pumping relay (optional)
S5: Auxiliary switch
TC: Trip coil
BC: Over current release coil (optional)
S1~S3: Energy storing travel switch
M: Energy storing motor
ZC: Electromagnet for locking (optional)
V1~V4: Rectifier
C: Control
Note: 1. This wiring diagram describes that a breaker is uncharged and is in an open state. 2. The polarity in dashed frame should be consistent when the operation voltage is DC.
29
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Working Principle Vacuum interrupter The vacuum gas pressure inside vacuum interrupter is less than 1.33×10-3Pa. Under normal circuit conditions the interrupter is closed. Arcing is established within the interrupter by withdrawing the moving contact from stationary contact. This arc burns in the metal vapor evaporated from local hot spots on the contact surfaces. The metal vapor continually leaves the inter-contact region and recondenses on the contact surfaces and surrounding metal vapor condensation shield. The latter is usually isolated from both contacts and serves to protect the glass or ceramic envelope from vapor deposition. At current zero, vapor production ceases and the original vacuum condition is rapidly approached. The dielectric strength of the interrupter also increases, and the circuit is interrupted. Within the contacts in the open position, the circuit voltage is withstood internally by the inter-contact gap
Operation
and externally by the insulating envelope.
Working Principle of Operating Mechanism Spring motor spring charging 1
The energy that is necessary for closing the circuit breaker is provided by the closing spring. The energy storage can be done by the motor or by the manual charging handle. Motor spring charging The energy charging mechanism consists of energy storing motor, gear wheel, cam, holder and closing spring. When the energy-storing motor (11) is charged, the pinion of output shaft (12) that is connected to motor will rotateand drive the gear wheel. The holder fixed on the gear wheel will make the cam fixed on the shaft move, which then drive the shaft to rotate, so that draws out the closing spring (17) for storing energy. When the block on the gear wheel is pushed away, the clutch is separated and the holder (4) will hold the roller on the cam (5) to keep the mechanism in charged position, thus completing the charging operation succeeds.
30
6 2
5 4 3 Figure 3. 1 Embedded pole 2 Insulating rod 3 Opening spring
4 Holder 5 Cam 6 Position switch
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
When energy is charged manually, the operator charges the spring by operating the energy-charging handle on the mechanism up and down repeatedly. When the charging operation is completed, you can hear a 'click', and the energy charging indicator (13) is switched over, as well as the status of position switch (6), cutting the secondary charging circuit. The operating mechanism now is ready for the next operation. (Figure 3)
Closing operation
Anti-Pump
When the closing circuit is powered, the closing coil is energized
Anti-pumping function is fitted with SecoVac to prevent repeated
and the holder (4) will rotate counter clockwise to break away
sequences of opening and closing operations. Once the circuit
from the roller on the cam (5). The cam, under the action of the
breaker is in closed position, the closing operation will be
force from closing spring (17), will rotate clockwise,
prohibited.
to push the roller on the main shaft, which will move the main connecting rod down through arm, so that the insulating rod (2) moves upright, pushing the movable contact to the fixed contact at the required speed, and compressing the contact spring and making it a necessary contact travel (overtravel) to ensure the pressure is generated between movable and fixed contacts.
Reclosing When the circuit breaker is closed, the mechanism can be charged for close, so that the circuit breaker can reclose immediately after tripping.
After the closed operation is finished, the closed/opening indicator (9) will indicate 'closed'. The power to the closing circuit will be cut. If the external power supply is energized, the charging
7
Operation
shaft (10) in counter clockwise rotation. The main shaft moves the
circuit motor will operate and the charging operation will be finished automatically. Note: Once the circuit breaker is in closed position, the closing operation will be prohibited.
Tripping operation When the breaker receives an opening command (the opening push button is pressed or the tripping coil (16) is energized), the tripping shaft will rotate clockwise. Under the action of opening spring (3) and contact-compressing spring, main shaft will move clockwise, and the insulating rod (2) will make the movable contact to separate from the fixed contact at a suitable speed. The buffer will absorb the residual energy and tripping operation is completed. After the tripping operation is finished, the closing/opening indicator (9) will indicate 'open'. Meanwhile, the counter will record the operation.
17
8
16
9 10
15
11
14 13 12 Figure 4. 7 Closing coil 8 Holder 9 Open/close indicator 10 Main shaft 11 Motor 12 Output shaft
13 Charging indicator 14 Latch coil 15 Over-current release 16 Tripping coil 17 Closing spring
31
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Interlocks
Installation
The follow interlocking facilities are
Correct installation is of primary
incorporated to ensure the safe operation
importance, the manufacturer’s
of the breaker. when the breaker is closed,
instructions must be carefully studied
the withdrawable circuit breaker cannot
and followed. It is good practice to use
be racked between the service position
gloves for handling the breaker during the
and test position.
installation.
●● When the earthing switch is in the
closed position, the withdrawable
Please carry out installation and wiring
circuit breaker cannot be racked into
of breaker according to manual. Do not
the service position
place any foreign objects in the breaker or
●● When the withdrawable circuit breaker
●● The careful and professional
modify it in anyway.
is in service position, the earthing
installation is a fundamental condition
switch cannot be closed
for the failure free operation of the
Check before installation
circuit breaker ●● The circuit breaker should be
After the breaker is unpacked, check
installed so that there are no external
the poles for any signs of mechanical
forces applied to it from busbars or
damage. The product nameplate and
mechanical supports
quality certificate shall conform to the
Operation
Installation for fixed circuit breakers
●● The busbar connection should not
order. Check goods according with the
cause any deformation to the breaker
packing list.
terminals ●● Take note of supplied drawings for bolt
Clean the insulating parts with a clean dry cloth. Make sure the upper and lower
sizing and lengths ●● Use the standard bolts with strength
contact arms are clean and free of any
of class 8.8 and the disc springs to
deformation caused by mishandling
tighten the bus bar (Table 1)
during transport or storage. Check the vacuum degree in the vacuum interrupter through power frequency withstand voltage test. If it fails, please contact or your local GE office.
Table 1 Tightening torque of bolt Basic dimensions of bolts (mm) M8 M10 M12 M16
32
Tightening torque without lubricant applied (N•m) 25 45 85 170
Tightening torgue with lubricant applied (N•m) 10 25 45 80
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Commissioning
Preparation Work
All commissioning and operation work
●● Check the circuit breaker for any
shall be carried out by persons who have
damage or any other dangerous
received professional training and are
environmental influence
familiar with operation of the breaker.
●● Wipe down the breaker, especially dirt
Necessary protective and preventive
that may have accumulated on the
measures shall be taken during work.
surface of the insulator. Especially the
●● Use the product under normal working
dirt on the surface of insulation
conditions and within the range of technical data according to the specifications of IEC 62271-1:2007
●● The lifting hook of the circuit breaker
must be removed prior to operation ●● Check the primary and secondary
circuits as well as the earthing ●● Implement energy charged, opening
and closing operations. Manually
Considerations
ensure the breaker is operating correctly
Operation for withdrawable circuit breaker ●● Put the circuit breaker into test position ●● Connect the secondary wiring plug and
times to ensure correct operation by local and remote control ●● Insert the handle and rotate the racking
handle clockwise about 20 revolutions.
Operation
open and close the breaker several
Upon the 'click', the withdrawable circuit breaker will be in the service position (Don't apply excessive force, to avoid any damage)
33
Check List
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Check List
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
34
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Check list for SecoVac 3.3kV-17.5kV IEC SecoVac VB2 Plus Check list COUNTRY:
PROJECT NAME:
PO NO.:
BASIC Type Code:
Qty:
Type
□ Withdrawable
□ Fixed
Rated Voltage
□ 12kV
□ 17.5kV
Rated Current
□ 630A
□ 1250A
□ 1600A
Rated Short-Circuit Breaking Current
□ 25kA
□ 31.5kA
□ 40kA
Pole Center Distance (P)
□ 150mm 630A, 1250A; 25kA, 31.5kA
□ 275mm 1600A, 2000A, 3150A, 4000A; 25kA, 31.5kA, 40kA
□ DC24V
□ DC30V
□ DC36V
□ DC48V
□ DC60V
Tripping/Closing Release (Y2, Y3)
□ 2000A
□ 2500A
□ 3150A
□ DC110V
□ DC125V
□ DC220V
□ AC110V
□ AC220V
□ Other
Charging Motor (M)
□ DC110V
□ DC125V
□ DC220V
□ AC110V
□ AC220V
□ Other
Secondary Wiring
□ Standard
Withdrawable Type SecoVac
Earthing
□ Earthing at the bottom of SecoVac VB2 Plus withdrawable unit □ Earthing on both sides of SecoVac VB2 Plus withdrawable unit □ Other
Fixed Type SecoVac
Mechanical □ Mechanical Interlock (VCB-DS & VCB-ES) Interlock Earthing
Ground Type
□ Nonstandard (Refer to drawing with number:
□ Earthing at the bottom of SecoVac withdrawable unit
Dimension □ Standard
□ 4000A
)
□ Other
□ Nonstandard (Refer to drawing with number:
)
OPTION 1: Blocking magnet of closing circuit loop (Y1)
□ DC220V
□ DC110V
Anti-Pump Relay (K0)
□ Required
□ Not required
□ AC220V
□ AC110V
□ Other
□ Not required
OPTION 2: (Extra expense is required.) Secondary Tripping Release (Y10) Blocking Magnet of SecoVac withdrawable unit (Y0)
□ DC24V
□ DC30V
□ DC36V
□ DC48V
□ DC60V
□ DC110V
□ DC125V
□ DC220V
□ AC110V
□ AC220V
□ DC220V
□ DC110V
□ AC220V
□ AC110V
□ Other
□ Other
Other Special Requirement (Please list other special requirement if any, and attach drawings or attachment)
By:
□ Required (Extra price needed)
(Signature & Stamp)
Remark: 1 Please tick √ in □ and send this checking list with official purchase order.
Check List
□ Not required
L-Frame
2 One secondary socket with jacks is offered for each SecoVac. One operation lever and one charging lever is offered for each five SecoVac of each project. Additional quantity required beyond above will be charged. 3 'Standard' herein means the solutions listed in SecoVac brochure. Should you have any question, please feel free to contact us. 4 If Option 1 or 2 is not ticked, SecoVac will not be equipped with related function. If Option 2 or other nonstandard solution is required, it will be charged additionally, and the delivery time will be longer. 35
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Check list for SecoVac 24kV, 27kV IEC SecoVac VB2 Plus Check list COUNTRY:
PROJECT NAME:
PO NO.:
BASIC Type Code:
Qty:
Type
□ Withdrawable
□ Fixed
Rated Voltage
□ 24kV
□ 27kV
Rated Current
□ 1250A
□ 1600A
Rated Short-Circuit Breaking Current
□ 31.5kA
□ 25kA
Pole Center Distance (P)
□ 210mm 630A, 1250A; 25kA, 31.5kA
□ 275mm 2000A, 2500A; 25kA, 31.5kA
□ DC24V
□ DC36V
Tripping/Closing Release (Y2, Y3)
□ DC30V
□ 2000A
□ 2500A
□ DC48V
□ DC60V
□ DC110V
□ DC125V
□ DC220V
□ AC110V
□ AC220V
□ Other
Charging Motor (M)
□ DC110V
□ DC125V
□ DC220V
□ AC110V
□ AC220V
□ Other
Secondary Wiring
□ Standard
Withdrawable Type SecoVac
Earthing
□ Earthing at the bottom of SecoVac VB2 Plus withdrawable unit □ Earthing on both sides of SecoVac VB2 Plus withdrawable unit □ Other
Fixed Type SecoVac
Mechanical □ Mechanical Interlock (VCB-DS & VCB-ES) Interlock Earthing
Ground Type
□ Nonstandard (Refer to drawing with number:
□ Earthing at the bottom of SecoVac withdrawable unit
Dimension □ Standard
)
□ Other
□ Nonstandard (Refer to drawing with number:
)
OPTION 1: Blocking magnet of closing circuit loop (Y1)
□ DC220V
□ DC110V
Anti-Pump Relay (K0)
□ Required
□ Not required
□ AC220V
□ AC110V
□ Other
□ Not required
OPTION 2: (Extra expense is required.) Secondary Tripping Release (Y10) Blocking Magnet of SecoVac withdrawable unit (Y0)
□ DC24V
□ DC30V
□ DC36V
□ DC48V
□ DC60V
□ DC110V
□ DC125V
□ DC220V
□ AC110V
□ AC220V
□ DC220V
□ DC110V
□ AC220V
□ AC110V
□ Other
□ Other
Other Special Requirement (Please list other special requirement if any, and attach drawings or attachment) □ Not required
Check List
L-Frame
By:
□ Required (Extra price needed)
(Signature & Stamp)
Remark: 1 Please tick √ in □ and send this checking list with official purchase order. 2 One secondary socket with jacks is offered for each SecoVac. One operation lever and one charging lever is offered for each five SecoVac of each project. Additional quantity required beyond above will be charged. 3 'Standard' herein means the solutions listed in SecoVac brochure. Should you have any question, please feel free to contact us. 4 If Option 1 or 2 is not ticked, SecoVac will not be equipped with related function. If Option 2 or other nonstandard solution is required, it will be charged additionally, and the delivery time will be longer.
36
You may be interested in other MV Seco-family products For more information, please visit www.geindustrial.com
GE Energy
Greater China Shanghai
Taiwan
4F, Building 2, CTP, No.1 Hua Tuo Rd.
6F, No. 8, Min Sheng E. Rd., Sec. 3,
Zhang Jiang Hi-Tech Park
Taipei 10480
Shanghai, China 201203
T : +886 2 2183 7000
T : +86 21 3877 7888
F : +886 2 2516 6829
F : +86 21 3877 7600
South East Aisa Malaysia
Philippines
Indonesia
Level 6, 1 Sentral,
8F Net Cube Building, 30th Street
BRI II Tower, 27th floor
Jalan Travers, Kuala Lumpur Sentral
Corner 3rd Avenue, Crescent West Park
Jl. Jend. Sudirman No. 44-46
Kuala Lumpur, Malaysia 50470
Global City Taguig 1634
Jakarta 10210
T : +603 2273 9788
T : +63 2 877 7000
T: +62 21 573 0430
F : +603 2273 7988
F : +63 2 846 0629
F: +62 21 574 7089
Thailand
Vietnam
Singapore
25th floor, CRC Tower, All Seasons Place
Saigon Centre, Unit 1, Floor 7
240 Tanjong Pagar Road
87/2 Wireless Road, Lumpini
Le Loi Boulevard, District 1
#06-00 GE Tower
Pathumwan, Bangkok 10330
HoChiMinh City
Singapore 088540
T : +66 2 648 0202
T : +84 8 3914 6700
T : +65 6220 7022
F : +66 2 648 0200
F : +84 8 3827 8229
F : +65 6326 3015
ANZ
Australia
New Zealand
125-127 Long Street
Level 1, 8 Tangihua Street
Smithfield, Sydney, NSW 2164
Auckland, North Island
T : +61 2 8788 6911
T : +64 9 353 6706
F : +61 2 8788 7224
F : +64 9 353 6707
North Asia Japan
Korea
11F, Akasaka Park Bldg.,5-2-20
3rd Floor, GE Tower, 71-3,
Akasaka, Minato-ku
Cheongdam-dong, Gangnam-gu
Tokyo 107-6111
Seoul, Korea 135-100
T : +81 3 3588 5288
T : +82 2 6201 4501
F : +81 3 3585 3010
F : +82 2 6201 4344
For more information, please visit www.geindustrial.com Printing Code: IN201202B30EN © Copyright GE Industrial Solutions 2012