TSLP 1kV(3).doc 15/03/2009 12:15:00 Page 1 of 6
PetroBlock TSLP 0,6/1kV Power cable Flame retardant cable for power, control and lighting. Screened cable for outdoor and underground installation. The PetroBlock barrier provides excellent protection against moisture, hydrocarbons and other chemicals and solvents in the ground.
TSLP 0,6/1kV HFXLPE/LSTPE/CWS/AL/PA/PVC
Operating temperature Operating Voltage
: 90°C : 0,6/1kV
Standards applied Application Fixed installation outdoor and underground for power, control and lighting systems in harsh environments both in EX- and safe areas.
IEC 60502-1 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1
- Design - Conductor - Insulation - Sheath - Flame Retardant
Construction Code Letter Conductor Insulation Lay up / Shielding Inner covering Armour/screen Outer sheath Marking text Outer sheath colour
T
S L P
Annealed stranded copper, IEC 60228 class 2, stranded circular copper SCC (single core cables 1,5 ... 300 mm², multicore cables 1,5 ... 35 mm²), sector shaped copper SSC (3 and 4 core cables above 35 mm²) Crosslinked Polyethylene, IEC 60092-351 (HFXLPE) Cores laid up in concentric layers Extruded halogenfree and flame retardant bedding. Concentric copper wire screen. Sized to be earth conductor. The PetroBlock barrier. Aluminium foil longitudinally wrapped and laminated to a polyamide sheath. A flexible tinned drain wire underneath the aluminium foil. Polyvinyl chloride (PVC), IEC 60092-359(ST2) E.g. "meter" "year" DRAKA NORSK KABEL TSLP 0,6/1KV 3 x 25FR/16 mm2 IEC 60502-1 IEC 60332-1 Black
www.draka.no Subject to change without prior notice
TSLP 1kV(3).doc 15/03/2009 12:15:00 Page 2 of 6
PetroBlock TSLP 0,6/1kV Power cable Core identification power cables Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05
Range and dimensions Cross Cross Thickness Number Conductor Insulation section section Inner of Diameter, Thickness, core, screen, covering, elements mm mm mm² mm² mm
Wire Diameter diameter inner concentric covering, conductor, mm mm
Diameter Moisture Barrier, mm
2
4
4
2.55
0.7
1
10 ± 0.8 0.61
14 ± 0.8 1.8
3
4
4
2.55
0.7
1
4
4
4
2.55
0.7
1
10.5 ± 0.8 11.5 ± 0.8
14.5 ± 0.8 15.5 ± 0.8
2
6
6
3.15
0.7
1
11 ± 0.8 0.61
3
6
6
3.15
0.7
1
12 ± 0.8 0.61
4 2 3
6 10 10
6 10 10
3.15 4.05 4.05
0.7 0.7 0.7
1 1 1
4
10
10
4.05
0.7
1
2
16
16
5.15
0.7
1
3
16
16
5.15
0.7
1
4 3 4
16 25 25
16 16 16
5.15 6.4 6.4
0.7 0.9 0.9
1 1 1
13 ± 0.8 13 ± 0.8 14 ± 0.8 15.5 ± 0.8 15.5 ± 0.8 16.5 ± 0.8 18 ± 0.8 20 ± 1 22 ± 1
3
35
16
7.55
0.9
1
22.5 ± 1 1.02
27 ± 1
1.8
4
35
16
7.55
0.9
1
25 ± 1
29 ± 1
1.9
0.61 0.61
Thickness Outer Sheath, mm
Weight Diameter of outer Cable sheath, Approx. mm (Kg/Km) 17.5 ± 430 0.8
Copper content Approx. (kg/km) 107
1.8
18 ± 0.8 470
143
1.8
19 ± 0.8 530
179
15.5 ± 0.8 17 ± 0.8 17 ± 0.8 18 ± 0.8 19.5 ± 0.8
1.8 1.8 1.8
18.5 ± 0.8 19.5 ± 0.8 20.5 ± 1 21 ± 1 21.5 ± 1
1.8
23 ± 1
940
452
1.02
20 ± 1
1.8
23.5 ± 1 980
439
1.02
21 ± 1
1.8
24.5 ± 1 1130
585
1.02 1.02 1.02
23 ± 1 1.8 24.5 ± 1 1.8 26.5 ± 1 1.8
26.5 ± 1 28 ± 1 30 ± 1.5 30.5 ± 1.5 33 ± 1.5
1320 1530 1830
730 842 1073
1910
1099
2370
1412
0.61 0.81 0.81 0.81
0.68
15 ± 0.8 1.8 1.8
530
167
590
224
680 710 810
281 271 361
Ordering information Part number 851740 851741 851742 851750 851751 851752 851760 851761 851762 851770 851771 851772
Description TSLP 0.6/1kV 2X 4FR/4mm² TSLP 0.6/1kV 3X 4FR/4mm² TSLP 0.6/1kV 4X 4FR/4mm² TSLP 0.6/1kV 2X 6FR/6mm² TSLP 0.6/1kV 3X 6FR/6mm² TSLP 0.6/1kV 4X 6FR/6mm² TSLP 0.6/1kV 2X 10FR/10mm² TSLP 0.6/1kV 3X 10FR/10mm² TSLP 0.6/1kV 4X 10FR/10mm² TSLP 0.6/1kV 2X 16FR/16mm² TSLP 0.6/1kV 3X 16FR/16mm² TSLP 0.6/1kV 4X 16FR/16mm²
Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK
www.draka.no Subject to change without prior notice
EAN No. DNK 7021528517408 7021528517415 7021528517422 7021528517507 7021528517514 7021528517521 7021528517606 7021528517613 7021528517620 7021528517705 7021528517712 7021528517729
EL No. -
TSLP 1kV(3).doc 15/03/2009 12:15:00 Page 3 of 6
PetroBlock TSLP 0,6/1kV Power cable Part number 851781 851782 851791 851792
Description TSLP 0.6/1kV 3X 25FR/16mm² TSLP 0.6/1kV 4X 25FR/16mm² TSLP 0.6/1kV 3X 35FR/16mm² TSLP 0.6/1kV 4X 35FR/16mm²
Sheath Colour BLACK BLACK BLACK BLACK
EAN No. DNK 7021528517811 7021528517828 7021528517910 7021528517927
EL No. -
Electrical values power cables Number of elements
Cross section core, mm²
2 3 4 2 3 4 2 3 4 2 3 4 3 4 3 4
4 4 4 6 6 6 10 10 10 16 16 16 25 25 35 35
Cross section screen, mm² 4 4 4 6 6 6 10 10 10 16 16 16 16 16 16 16
Conductor type 2
SCC SCC SCC SCC SCC SCC SCC SCC SCC SCC SCC SCC SCC SCC SCC SCC
Max. conductor resistance at 20°C, Ohm/km 4.61 4.61 4.61 3.08 3.08 3.08 1.83 1.83 1.83 1.15 1.15 1.15 0.727 0.727 0.524 0.524
Max. conductor resistance at 90°C, Ohm/km 5.88 5.88 5.88 3.93 3.93 3.93 2.33 2.33 2.33 1.47 1.47 1.47 0.927 0.927 0.668 0.668
Reactance at 50Hz, Ohm/km 0.086 0.086 0.086 0.082 0.082 0.082 0.079 0.079 0.079 0.075 0.075 0.075 0.075 0.075 0.073 0.073
Current rating NEN 62.75, Ampere -
Installation recommendations Minimum Bending Radius during Installation 20 x D
Minimum Bending Radius Fixed Installed 12 x D
Maximum Tensile Load During Installation 50 N /mm²
www.draka.no Subject to change without prior notice
Minimum Installation Temperature -10°C
Short circuit rating 1 second, Ampere 560 560 560 840 840 840 1400 1400 1400 2240 2240 2240 3500 3500 4900 4900
TSLP 1kV(3).doc 15/03/2009 12:15:00 Page 4 of 6
PetroBlock TSLP 0,6/1kV Power cable Flame retardant cable for power, control and lighting. Screened cable for outdoor and underground installation. The PetroBlock barrier provides excellent protection against moisture, hydrocarbons and other chemicals and solvents in the ground.
TSLP 0,6/1kV HFXLPE/LSTPE/CWS/AL/PA/PVC
Operating temperature Operating Voltage
: 90°C : 0,6/1kV
Standards applied Application Fixed installation outdoor and underground for power, control and lighting systems in harsh environments both in EX- and safe areas.
IEC 60502-1 IEC 60228 class 2 IEC 60092-351 IEC 60092-359 IEC 60332-1
- Design - Conductor - Insulation - Sheath - Flame Retardant
Construction Code Letter Conductor Insulation Lay up / Shielding Inner covering Armour/screen Outer sheath Marking text Outer sheath colour
T
S L P
Annealed stranded circular copper IEC 60228 class 2 for single core cables or Annealed stranded sectorshaped copper IEC 60228 class 2 for 3- and 4-core cables Crosslinked Polyethylene, IEC 60092-351 (HFXLPE) Three or four sectorshaped cores laid up together. Or only one single core in the cable. Wrapped halogenfree bedding (PP-tape). Concentric copper wire screen. Sized to be earth conductor. The PetroBlock barrier. Aluminium foil longitudinally wrapped and laminated to a polyamide sheath. A flexible tinned drain wire underneath the aluminium foil. Polyvinyl chloride (PVC), IEC 60092-359(ST2) E.g. "meter" "year" DRAKA NORSK KABEL TSLP 0,6/1KV 3 x 95FV/50 mm2 IEC 60502-1 IEC 60332-1 Black
www.draka.no Subject to change without prior notice
TSLP 1kV(3).doc 15/03/2009 12:15:00 Page 5 of 6
PetroBlock TSLP 0,6/1kV Power cable Core identification power cables Single core - Black Two cores - Blue - Brown Three cores - Brown - Black - Grey Four cores - Blue - Brown - Black - Grey Five cores - Blue - Brown - Black - Grey - Black Seven cores and above - White with black numbers Two cores + earth (3G) - Yellow/green - Blue - Brown Three cores + earth (4G) - Yellow/green - Brown - Black - Grey Four cores + earth (5G) - Yellow/green - Blue - Brown - Black - Grey G / X in cable description - G = One of the cores are yellow/green - X = no yellow/green core Core identification - to HD308S2 - and IEC 60446:2007-05
Range and dimensions Cross Number section of core, elements mm²
Cross section screen, mm²
Conductor Diameter, mm
3 4 3 4 3 4 3 4 3 4 3 3 1 1 1
25 25 35 35 50 50 70 70 70 70 95 120 16 50 70
12.6 22.6 26
50 50 70 70 95 95 120 120 150 150 185 240 95 300 400
Wire Insulation diameter Thickness, concentric mm conductor, mm 1.0 0.68 1.0 0.68 1.1 1.37 1.1 1.37 1.1 1.37 1.1 1.37 1.2 1.37 1.2 1.37 1.4 1.37 1.4 1.37 1.6 1.37 1.7 1.745 1.1 1.02 2.0 1.37 2.0 1.37
Diameter Moisture Barrier, mm
Thickness Outer Sheath, mm
Diameter outer sheath, mm
Weight of Cable Approx. (Kg/Km)
Copper content Approx. (kg/km)
25.5 ± 1 28 ± 1 30 ± 1.5 34.5 ± 1.5 34.5 ± 1.5 38 ± 1.5 36.5 ± 1.5 41 ± 2 41 ± 2 45 ± 2 44.5 ± 2 49.5 ± 2 19.5 ± 0.8 33 ± 1.5 36.5 ± 1.5
1.9 2 2.1 2.2 2.2 2.3 2.3 2.4 2.5 2.6 2.6 2.8 1.8 1.9 2.1
29.5 ± 1 32 ± 1.5 34 ± 1.5 39 ± 1.5 39 ± 1.5 42.5 ± 2 41.5 ± 2 46 ± 2 46 ± 2 50.5 ± 2.5 49.5 ± 2 55.5 ± 2.5 23.5 ± 1 36.5 ± 1.5 40.5 ± 2
1980 2480 2760 3500 3720 4660 4620 5800 5610 7020 6940 8840 1350 4100 5000
1468 1883 2118 2715 2942 3770 3801 4834 4582 5874 5756 7472 1009 3418 4182
Ordering information Part number 851801 851802 851811 851812 851821 851822 851831 851832 851841 851842 851851 851861 851888 851893 851894
Description TSLP 0.6/1kV 3X 50FV/25mm² TSLP 0.6/1kV 4X 50FV/25mm² TSLP 0.6/1kV 3X 70FV/35mm² TSLP 0.6/1kV 4X 70FV/35mm² TSLP 0.6/1kV 3X 95FV/50mm² TSLP 0.6/1kV 4X 95FV/50mm² TSLP 0.6/1kV 3X 120FV/70mm² TSLP 0.6/1kV 4X 120FV/70mm² TSLP 0.6/1kV 3X 150FV/70mm² TSLP 0.6/1kV 4X 150FV/70mm² TSLP 0.6/1kV 3X 185FV/95mm² TSLP 0.6/1kV 3X 240FV/120mm² TSLP 0.6/1kV 1X 95FR/16mm² TSLP 0.6/1kV 1X 300FR/50mm² TSLP 0.6/1kV 1X 400FR/70mm²
Sheath Colour BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK
EAN No. DNK 7021528518016 7021528518023 7021528518115 7021528518122 7021528518214 7021528518221 7021528518313 7021528518320 7021528518412 7021528518429 7021528518511 7021528518610 7021528518887 7021528518931 7021528518948
EL No. -
Electrical values power cables Number of elements
Cross section core, mm²
3
50
Cross section screen, mm² 25
Conductor type 2
SSC
Max. conductor resistance at 20°C, Ohm/km 0.387
Max. conductor resistance at 90°C, Ohm/km 0.493
www.draka.no Subject to change without prior notice
Reactance at 50Hz, Ohm/km 0.072
Current rating NEN 62.75, Ampere -
Short circuit rating 1 second, Ampere 7000
TSLP 1kV(3).doc 15/03/2009 12:15:00 Page 6 of 6
PetroBlock TSLP 0,6/1kV Power cable Number of elements
Cross section core, mm²
4 3 4 3 4 3 4 3 4 3 3 1 1 1
50 70 70 95 95 120 120 150 150 185 240 95 300 400
Cross section screen, mm² 25 35 35 50 50 70 70 70 70 95 120 16 50 70
Conductor type 2
SSC SSC SSC SSC SSC SSC SSC SSC SSC SSC SSC SCC SCC SCC
Max. conductor resistance at 20°C, Ohm/km 0.387 0.268 0.268 0.193 0.193 0.153 0.153 0.124 0.124 0.0991 0.0754 0.193 0.0601 0.047
Max. conductor resistance at 90°C, Ohm/km 0.493 0.342 0.342 0.246 0.246 0.195 0.195 0.158 0.158 0.1264 0.0961 0.246 0.0766 0.0599
Reactance at 50Hz, Ohm/km 0.072 0.064 0.064 0.062 0.062 0.063 0.063 0.063 0.063 0.063 0.063 0.091 0.087 0.087
Current rating NEN 62.75, Ampere -
Installation recommendations Minimum Bending Radius during Installation 20 x D
Minimum Bending Radius Fixed Installed 12 x D
Maximum Tensile Load During Installation 50 N /mm²
www.draka.no Subject to change without prior notice
Minimum Installation Temperature -10°C
Short circuit rating 1 second, Ampere 7000 9800 9800 13300 13300 16800 16800 21000 21000 25900 33600 13300 42000 56000