YORK BACnet Solution: YK Chiller with Variable Speed Drive

Point Map April 18, 2005 Systems Integration YORK BACnet Solution: YK Chiller with Variable Speed Drive Table 1. YK Chiller with Variable Speed Dri...
1 downloads 1 Views 112KB Size
Point Map April 18, 2005

Systems Integration

YORK BACnet Solution: YK Chiller with Variable Speed Drive Table 1.

YK Chiller with Variable Speed Drive APOGEE Points, Application Number: 4058. Range/Unitsa

Point

Type

Description

1

LAO

Device Address



2

LAO

Device Application



3

LAO

Leaving Chilled Liquid Setpoint Selected

°F °C

4

LAO

Motor Current Limit Setpoint Selected

% FLA

7

LDO

Remote Start Stop

Stop/Start

9

LDO

Variable Or Fixed Speed

No/Yes

11

LAI

Leaving Chilled Liquid Temperature

°F °C

12

LAI

Return Chilled Liquid Temperature

°F °C

13

LAI

Evaporator Pressure

psi kPa

14

LAI

Condenser Pressure

psi kPa

15

LAI

Oil Pressure Differential

psi kPa

16

LAI

Return Condenser Liquid Temperature

°F °C

17

LAI

Leaving Condenser Liquid Temperature

°F °C

18

LAI

Motor Current Percent Fla

% FLA

19

LAI

Phase A Current

A

20

LAI

Phase B Current

A

21

LAI

Phase C Current

A

25

LAI

Leaving Chilled Liquid Setpoint Selected

°F °C

26

LAI

Motor Current Limit Setpoint Selected

% FLA

b c

continued on next page...

Siemens Building Technologies, Inc. Document No. 127-1259

Page 1 of 8

Table 1.

YK Chiller with Variable Speed Drive APOGEE Points, Application Number: 4058.

(continued)

Range/Unitsa

Point

Type

Description

27

LAI

Evaporator Saturation Temperature

°F °C

28

LAI

Condenser Saturation Temperature

°F °C

29

LAI

Discharge Temperature

°F °C

30

LAI

Oil Sump Temperature

°F °C

31

LAI

Purge Pressure

psi kPa

32

LAI

Unit Operating Hours

hrs

33

LAI

Unit System Starts

starts

34

LAI

Oil Sump Pressure

psi kPa

35

LAI

Oil Pump Pressure

psi kPa

36

LDI

Motor Run Contacts

Off/On

37

LDI

Liquid Line Solenoid

Off/On

38

LDI

Chilled Liquid Pump

Off/On

39

LDI

Panel Start Switch

Off/On

40

LDI

Chilled Liquid Flow Switch

Off/On

48

LDI

Acc Valid Surge Map

False/True

49

LDI

Acc New Surge Point

False/True

50

LDI

Vsd Water Pump Relay

Stop/Run

51

LDI

Harmonic Filter Installed

False/True

52

LDI

Acc Surge Type

Off/On

56

LAI

Antirecycle Time Remaining

sec

57

LAI

Warning Code

See Table 2

58

LAI

Operation Code

See Table 3

59

LAI

Safety Shutdown Code

See Table 4

60

LAI

Cycling Shutdown Code

See Table 5

61

LAI

Vsd Internal Ambient Temperature

°F °C

62

LAI

Vsd Converter Heatsink Temperature

°F °C

63

LAI

Pre Rotation Vanes Position

%

64

LAI

Acc Map Output Frequency

Hz

65

LAI

Refrigerant Level Setpoint



b c

continued on next page...

Page 2 of 8

Siemens Building Technologies, Inc. Document No. 127-1259

Table 1.

YK Chiller with Variable Speed Drive APOGEE Points, Application Number: 4058.

(continued)

Range/Unitsa

Point

Type

Description

66

LAI

Thrust Bearing Proximity Position



67

LAI

Thrust Bearing Proximity Reference



69

LAI

Acc Map Prv Position

%

70

LAI

Vsd Outputvoltage

V

71

LAI

Vsd Input Power

kW

72

LAI

Vsd Killowatt Hours

kWh

73

LAI

Vsd Dc Bus Voltage

V

74

LAI

Vsd Inverter Link Current

A

75

LAI

Acc Surge Count



76

LAI

Vsd Output Frequency

Hz

77

LAI

Harmonic Filter Maximum Voltage Thd

V

78

LAI

Harmonic Filter Maximum Current Tdd

A

79

LAI

Harmonic Filter Total Supply Kva

kVA

b c

a Values noted for LDIs and LDOs are in the following format: OFF text/ON text. b This column indicates the value/range or engineering units or both if known. c The default English value is not italicized. An italicized entry indicates an SI value.

Table 2.

Warning Codes.

Value

Description

1

No Abnormal Condition

2

Real-Time Clock Failure

3

Default Setpoints Loaded

4

Evaporator Or Condenser Transducer Error

5

Evaporator - Low Pressure Limit

6

Condenser - High Pressure Limit

9

Refrigerant Level Out Of Range

10

Standby Lube - Low Oil Pressure

15

Motor - High Current Limit

16

Vanes Uncalibrated

17

Vanes Uncalibrated - Fixed Speed Operation

18

Harmonic Filter - Operation Inhibited

19

Harmonic Filter - Data Loss continued on next page...

Siemens Building Technologies, Inc. Document No. 127-1259

Page 3 of 8

Table 2.

Warning Codes.

Value

(continued)

Description

20

Harmonic Filter - Input Frequency Out Of Range

26

Seal Lubrication In Process

27

External I/O Board Serial Communications Table 3.

Operational Codes.

Value

Description

1

Unit Stopped - Ready to Start

2

Unit Stopped - Local Shutdown

3

Unit Stopped - Remote Shutdown

4

Unit Stopped - Warning Active

5

Unit Stopped - Cycling Shutdown

6

Unit Stopped - Safety Shutdown

7

Unit Start Inhibit

8

Unit Starting

9

Unit Running - No Abnormal Condition

10

Unit Running - Warning Active

11

Unit Running - Chiller Unload Before Shutdown

12

Unit Coastdown Table 4.

Safety Codes.

Value

Description

1

No Abnormal Condition

2

Evaporator - Low Pressure

3

Evaporator - Transducer Or Leaving Liquid Probe

4

Evaporator - Temperature Transducer

5

Condenser - High Pressure Contacts Open

6

Condenser - High Pressure

7

Condenser - Pressure Transducer Out Of Range

8

Auxiliary Safety - Contacts Closed

9

Discharge - Low Temperature

10

Discharge - High Temperature

11

Oil - High Temperature

12

Oil - Low Differential Pressure

13

Oil - High Differential Pressure

14

Oil - Pump Pressure Transducer Out Of Range

15

Oil - Sump Pressure Transducer Out Of Range

19

Oil - Differential Pressure Calibration continued on next page...

Page 4 of 8

Siemens Building Technologies, Inc. Document No. 127-1259

Table 4.

Safety Codes.

(continued)

Value

Description

21

Oil - Variable Speed Pump - Pressure Setpoint

22

Control Panel - Power Failure

24

Motor Or Starter - Current Imbalance

25

Thrust Bearing - Proximity Probe Clearance

26

Thrust Bearing - Proximity Probe Uncalibrated

27

Thrust Bearing - Proximity Probe Out Of Range

30

VSD - High Heatsink Temperature

31

VSD - 105% Motor Current Overload

32

VSD - High Phase A Inverter Heatsink Temperature

33

VSD - High Phase B Inverter Heatsink Temperature

34

VSD - High Phase C Inverter Heatsink Temperature

35

VSD - High Converter Heatsink Temperature

36

VSD - Precharge Lockout

37

Harmonic Filter - High Heatsink Temperature

38

Harmonic Filter - High Total Demand Distortion

50

Starter - Invalid Motor Selection

52

Evaporator - Low Pressure

53

Evaporator - Low Pressure - Smart Freeze Table 5.

Cycling Codes.

Value

Description

1

No Abnormal Condition

2

Multi-Unit Cycling - Contacts Open

3

System Cycling - Contacts Open

5

Oil - Low Temperature

6

Control Panel - Power Failure

7

Leaving Chilled Liquid - Low Temperature

8

Leaving Chilled Liquid - Flow Switch Open

9

Condenser - Flow Switch Open

10

Motor Controller - Contacts Open

11

Motor Controller - Loss Of Current

12

Power Fault

13

Control Panel - Schedule

14

Starter - Low Supply Line Voltage

15

Starter - High Supply Line Voltage

16

Proximity Probe - Low Supply Voltage continued on next page...

Siemens Building Technologies, Inc. Document No. 127-1259

Page 5 of 8

Table 5.

Cycling Codes.

Value

(continued)

Description

17

Oil - Variable Speed Pump - Drive Contacts Open

18

VSD Initialization Failure

19

VSD Shutdown - Requesting Fault Data

20

VSD - High Phase A Instantaneous Current

21

VSD - High Phase B Instantaneous Current

22

VSD - High Phase C Instantaneous Current

23

VSD - Phase A Gate Driver

24

VSD - Phase B Gate Driver

25

VSD - Phase C Gate Driver

26

VSD - Single Phase Input Power

27

VSD - High DC Bus Voltage

28

VSD - Logic Board Power Supply

29

VSD - Low DC Bus Voltage

30

VSD - DC Bus Voltage Imbalance

31

VSD - High Internal Ambient Temperature

32

VSD - Invalid Current Scale Selection

33

VSD - Low Phase A Inverter Heatsink Temperature

34

VSD - Low Phase B Inverter Heatsink Temperature

35

VSD - Low Phase C Inverter Heatsink Temperature

36

VSD - Low Converter Heatsink Temperature

37

VSD - Precharge - DC Bus Voltage Imbalance

38

VSD - Precharge - Low DC Bus Voltage

39

VSD - Logic Board Processor

40

VSD - Run Signal

41

VSD - Serial Communications

42

VSD - Stop Contacts Open

43

Harmonic Filter - Logic Board Or Communications

44

Harmonic Filter - High DC Bus Voltage

45

Harmonic Filter - High Phase A Instantaneous Current

46

Harmonic Filter - High Phase B Instantaneous Current

47

Harmonic Filter - High Phase C Instantaneous Current

48

Harmonic Filter - Phase Locked Loop

49

Harmonic Filter - Precharge - Low DC Bus Voltage

50

Harmonic Filter - Low DC Bus Voltage

51

Harmonic Filter - DC Bus Voltage Imbalance continued on next page...

Page 6 of 8

Siemens Building Technologies, Inc. Document No. 127-1259

Table 5. Value

Siemens Building Technologies, Inc. Document No. 127-1259

Cycling Codes.

(continued)

Description

52

Harmonic Filter - 110% Input Current Overload

53

Harmonic Filter - Logic Board Power Supply

54

Harmonic Filter - Run Signal

55

Harmonic Filter - DC Current Transformer 1

56

Harmonic Filter - DC Current Transformer 2

74

VSD - Serial Communications

Page 7 of 8

Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2005 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 U.S.A.

Document No. 127-1259 Country of Origin: US Page 8 of 8