VFL Series PID Controllers
INSTRUCTION MANUAL ■FRONT PANEL DESCRIPTION:
(1) PV-Process Value (2) SV-Setting Value (3) AT-Auto tuning LED (4) MA-Manual mode LED (5) A1-Alarm 1 LED (6) A2-Alarm 2 LED (7) C1-Control 1 LED (8) C2-Control 2 LED
-SET KEY. Press once to access the next programmable parameter.
(1)
Press and hold this key for 5 seconds to reset alarm timer. (2)
-UP KEY. Press to increase the set point or parameter value.
(3)
-DOWN KEY. Press to decrease the set point or parameter value.
(4)
-SHIFT KEY. Press the shift key for 5 seconds to execute Auto Tune process (Yes. 1 mode) To abort an Auto Tune process, press and hold the shift key for 5 seconds.
(5)
-Press the SET and UP keys once to return the normal operation.
(6)
-LEVEL KEY. Press the SET & SHIFT keys simultaneously for 5 seconds to select programming level, then press the SET key to enter this level. ---Press the UP & DOWN keys simultaneously for 5 seconds to access “LnLo” & “LnHi” parameters.
(7)
■PANEL CUTOUT:
Model
A
B
C
D
E
a
b
c
d
48VFL
48
48
6
100
45
45+0.5
45+0.5
60
48
96VFL
96
96
10
80
91
92+0.5
92+0.5
120
96
(Units: mm)
■ WIRING DIAGRAM
■Wiring Precautions: 1. Before wiring, verify the controller label for correct model number and options. 2. For thermocouple input, use the appropriate compensation wire. And note the polarity of input signal. 3. To avoid noise induction, keep input signal wires away from instrument power lines, load lines and power lines of other electrical equipment.
■ PROGRAMMING LEVEL PARAMETERS ■ lst. Prog. Level
2nd. Prog. Level
3rd. Prog. Level
4th Prog. Level
5th. Prog. Level
+
1. When 2nd Output (Cooling) is not selected, CPb、Cti、 Ctd、HYS2 and db parameters are not available. 2. When Pb≠0.0, HYS1 will be skipped. 3. When CPb≠0.0,HYS2 will be skipped. 4. When Pb=0.0,ti、td will be skipped. 5. When CPb=0.0,Cti、Ctd will be skipped.
■PARAMETER DESCRIPTION: LEVEL Selection Press
keys for at least 5 seconds to access Soft Level. Use key to select programming level. Then press LEVEL
or
key to enter this level.
Description SoFt Level PID Level Option Level
USER LEVEL CODE
DESCRIPTION Set point value of control Alarm 1 set point value/Timer set value while A1FU is set to T.on or T. off, the unit can be HH.MM or MM.SS. It depends on
RANGE LoLt - HiLt
Default 500
-1999 - 9999/ 00.00~99.59
10
-1999 - 9999/ 00.00~99.59
10
the “P.tnE” parameter. Alarm 2 set point value/ Timer set value while A2FU is set to T.on or T. off, the unit can be HH.MM or MM.SS. It depends on the “P.tnE” parameter. :Auto-tuning is disable :Standard type auto-tuning. Autotune PV is compared wit SV during auto tuning. :Low PV type auto-tuning.
no
PV is compared with SV-10%FS during Auto-tuning. :Disable the manual mode Manual control
no
:Enable the manual mode. Output percentage. Adjustable when “Hand” is set to “Yes”
-100.0
-
0.0
100.0
SOFT LEVEL Code
Description Ramp rate for the process value to limit an abrupt Change of process (℃/min) Set point value of soft-start Output percentage of soft-start
Range 0 - 9999 (0.0 – 999.9)
Default 0.0
LoLt - HiLt
0
0.0 - 100.0
100.0
PID LEVEL CODE
DESCRIPTION
RANGE
Default
0.0-300.0%
10.0
0-3600sec
240
0-900sec
60
0-100sec
15
0.0-300.0%
10.0
0-3600sec
240
0-900sec
60
0-100sec
15
Hysteresis for ON/OFF control on output 1
0-2000(0.0-200.0)
1
Hysteresis for ON/OFF control on output 2
0-2000(0.0-200.0)
1
Hysteresis of alarm 1
0-2000
1
Hysteresis of alarm 2
0-2000
1
Proportional band variable. Set to 0.0 for ON/OFF control mode Integral time (Reset). This value is automatically calculated by activating the Autotune function. If desired, the user can later adjust this parameter to better suit the application. When PB=0.0, this parameter will be not available. When set to zero, Pb & td ≠ 0 for PD control Derivative (Rate). This value is automatically calculated by activating the Auto tune function. If desired, the user can later adjust this parameter to better suit the application. When PB=0.0, this parameter will be not available. When set to zero, Pb & td ≠ 0 for PI control Proportional cycle time of output 1 Proportional band variable for secondary control output (cooling). Set 0.0 for ON/OFF Integral time for secondary control output. When PB=0.0, this parameter will be not available. When set to zero, Pb & td ≠ 0 for PD control Derivative time for secondary control output. When Pb=0.0, this parameter will be not available. When set to zero, Pb & ti ≠ 0 for PI control Proportional cycle time of output 2
Dead band value. This defines the area in which output 1 and output 2 are both active (negative value) or the area in which output 1 and output 2 are both inactive (positive value) Set point offset. This value will be added to SV to perform control.
-1000-1000 (-100.0-100.0) -1000-1000
0 0
(-100.0-100.0)
It mainly used to eliminate offset error during Pb control
-1000-2000
Process value offset. Permits the user to offset the PV indication
0
(-100.0-200.0)
from the actual PV Parameter lock. This security feature locks out selected levels or single parameters prohibiting tampering and inadvertent programming changes 0000
All parameters are locked out
0001
Only SP is adjustable
0010
Only USER level is adjustable
0011
USER and PID levels are adjustable
0100
USER,PID,OPTI levels are adjustable
0101
USER, SOFT, PID, OPTI levels are adjustable
0100
0101~0111 All parameters in all levels are unlocked 1000=0000,1001=0001,1010=0010,1011=0011,1100=0100 1000~1111 The only difference is that Output 2 is unlocked
OPTION
LEVEL
CODE
DESCRIPTION
RANGE
Default
Refer to figure.
K
Input type selection.
tYPE J K T E B R S N C D-PT J-PT LINE
RANGE(℃) RANGE(℉) -50 ~ 1000 -58 ~ 1832 -50 ~ 1370 -58 ~ 2498 -270 ~ 400 -454 ~ 752 -50 ~ 750 -58 ~ 1382 0 ~ 1800 32 ~ 3272 0 ~ 1750 32 ~ 3182 0 ~ 1750 32 ~ 3182 -50 ~ 1300 -58 ~ 2372 -50 ~ 1800 -58 ~ 3272 -200 ~ 850 -328 ~ 1652 -200 ~ 650 -328 ~ 1202 -1999 ~ 9999
Unit of process value :Degrees C
℃
:Degrees F : Engineer units for linear input Decimal point selection 0000 0000:No decimal point 000.0 000.0:0.1 resolution
0000 00.00
00.00:0.01 resolution, used for linear input only 0.000 0.000:0.001 resolution, used for linear input only Output 1 control action. : Reverse action for heating : Direct action for cooling
Low limit of span or range. Set the low limit lower than the Full range
0
Full range
1000
0.0-99.9
10.0
00.00~99.59
00.00
lowest expected SV and PV display High limit of span or range. Set the high limit higher than highest expected SV and PV display
Software filter.
Time scale for timer alarm. Hours:Minutes; Minutes:Seconds
None, Hi, Lo, dif.H, dif.L, bd.Hi , bd.Lo If A1FU=None, the alarm function is cancelled t.on, t.oFF none, Stdy, Alarm 1 mode. Refer to alarm mode section for detail.. Lath, St.La Alarm 2 function. Refer to alarm function section for detail none, Hi, Lo, dif.H, dif.L, bd.Hi, bd.Lo If A2FU=None, it means alarm fuction is cancelled. t.on, t.oFF none, Stdy, Alarm 2 mode. Refer to alarm mode section for details Lath, St.La Alarm 1 function. Refer to alarm section for details
Controller address. For use with PC RS-485 interface
0 - 255
0
Baud rate. 2.4k=2400bps, 4.8k=4800 bps, 9.6k=9600 bps,
2.4k, 4.8k
19.2k=19200 bps
9.6k, 19.2k
9.6k
Description
Default
Code
Range Low Scale of Linear Input
-1999~9999(-199.9~999.9)
0.0
High Scale of Linear Input
-1999~9999(-199.9~999.9)
100.0
Scaling for Linear Input 1. Press and hold the UP and DOWN keys simultaneously for 5 seconds to access the “LnLo” parameter. 2. Adjust “LnLo” setting to correspond to the low scale; after adjustment, press
key once to access “LnHi”
3. Adjust “LnHi” setting to correspond to the high scale; after adjustment press
key once to exit
ALARM FUNCTION A1FU/A2FU
ALARM TYPE Alarm function OFF
ALARM OUTPUT OPERATION Output OFF
Process high alarm
▲ SP
PV
Process low alarm
▲ SP
PV
Deviation high alarm
▲ SP+ALSP
PV
Deviation low alarm
▲ SP+ALSP
Band high alarm
▲ SP-ALSP OFF ▲ SP-ALSP
Band low alarm
PV
OFF ▲ ▲ PV SP SP+ALSP OFF ▲ ▲ PV SP SP+ALSP
On-timer
ALSP ▲ ▲ SP
Off-timer
ALSP ▲ ▲ SP
PV
PV
ALARM MODE A1MD/A2MD
DESCRIPTION Normal alarm mode/ When timer function is selected, with the PV 50MΩ
Noise rejection
Common Mode: 120 dB; Normal Mode: 60 dB (typical)
Operating conditions
14 to 122 F (-10 to 50 C); 90% Relative Humidity max.
Storage temperature
-4 to 140 F (-20 to 60 C)
o
Panel cut-out dimensions
o
o
o
1.77 x 1.77" ±0.02" (45.0 x 45.0mm ±0.5mm) for 48VFL 3.62 x 3.62" ±0.02" (92.0 x 92.0mm ±0.5mm) for 96VFL
Thermocouple Input Specifications Thermocouple (TC) types
J, K, T, E, B, R, S, N, and C (user programmable)
TC Break protect
Upscale and Downscale
Lead wire effect
0.015% / ohm
Input impedance
> 10MΩ
Repeatability
0.83 C
Temperature stability
5uV/ C typical
TC Ranges
Type K:
-58 to 2498oF (-50 to 1370oC)
Type J:
-58 to 1830 F (-50 to 1000 C)
Type B:
32 to 3272 F (0 to 1800 C)
Type T:
-454 to 752oF (-270 to 400oC)
Type E:
-58 to 1382oF (-50 to 750oC)
Type R:
32 to 3182 F (0 to 1750 C)
Type S:
32 to 3182 F (0 to 1750 C)
Type N:
-58 to 2372oF (-50 to 1300oC)
Type C:
-58 to 3272 F (-50 to 1800 C)
o
o
o
o
o
o
o
o
o
o
o
o
RTD Input Specifications RTD type
Platinum 100Ω (DIN or JIS)
RTD range
-328 to 1202oF (-200 to 650oC)
Break protection
Up- and down-scale
Lead wire effect
0.015 / Ohm
Repeatability
0.2oC
o
Analog (Linear) Input Specifications Current Input
4 to 20mA DC (2.7Ω input impedance)
Voltage Input
1 to 5V DC (>10MΩ input impedance)
Display range
-1999 to 9999 digits
Repeatability
Within 1 digit
Relay and Pulse DC Output Specifications Relay outputs
SPST (dry contact) relays can switch up to 5 Amps @ 110V AC or 24VDC (for resistive loads only)
Pulsed DC outputs
0 to 24 VDC output (drives resistive loads to 250Ω max.)
Control actions
Indirect or reverse acting (heating) and direct acting (cooling)
Control types
ON/OFF control with Hysteresis (dead band) Time proportioning control (for relay or pulsed DC output) Standard proportional output (analog output)
Automatic tuning
Push-button activation. Automatically tunes the proportional band and integral/derivative times.
Manual Tuning
Proportional Band (Pb): 0.0 to 300.0% of Full Scale Integral time or ‘Reset’ (Ti): 0 to 3000 seconds (includes anti-reset wind-up) Derivative time or ‘Rate’ (Td): 0 to 900 seconds Cycle Time: 0 to 100 seconds (set to ‘0’ for 4-20mA output) Hysteresis: 0.0 to 25.5% of Full Scale
ALARM Output Specifications Alarm relay outputs
SPST, dry contact relay can switch up to 3 Amps @ 110VAC; (for Resistive Loads)
Alarm modes
Deviation, Absolute, and Band Alarms with dead band (Hysteresis) adjustment.
ANALOG Output Specifications Analog output
4-20mA DC
Load limits
600Ω max.
Programming
Set Cycle Time (Ct) to ‘0’ to enable the analog output
Warranty EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment (a six month limited warranty applies to sensors and cables). If it should become necessary to return the instrument for service during or beyond the warranty period, contact the Customer Service Department at (781) 890-7440 ext. 210 for authorization or visit our website www.extech.com for contact information. A Return Authorization (RA) number must be issued before any product is returned to Extech. The sender is responsible for shipping charges, freight, insurance and proper packaging to prevent damage in transit. This warranty does not apply to defects resulting from action of the user such as misuse, improper wiring, operation outside of specification, improper maintenance or repair, or unauthorized modification. Extech specifically disclaims any implied warranties or merchantability or fitness for a specific purpose and will not be liable for any direct, indirect, incidental or consequential damages. Extech's total liability is limited to repair or replacement of the product. The warranty set forth above is inclusive and no other warranty, whether written or oral, is expressed or implied.
Calibration and Repair Services Extech offers repair and calibration services for the products we sell. Extech also provides NIST certification for most products. Call the Customer Service Department for information on calibration services available for this product (refer to the phone, email, and website information in the support box provided below). Extech recommends that annual calibrations be performed to verify meter performance and accuracy.
Technical Support To contact Technical Support, refer to the phone, email, and website information in the support box provided below. Before contacting Extech, please have the following information handy: Detailed description of concern Current settings of all controller programming menu levels Controller wiring diagram or schematic Documentation for the process to which the controller is connected (description, schematic, wiring, block diagrams, etc.) Instruction manual for the controller Error messages from controller’s display (if any)
Support line (781) 890-7440 Technical support: Extension 200; E-mail:
[email protected] Repair & Returns: Extension 210; E-mail:
[email protected] Product specifications subject to change without notice For the latest version of this User’s Guide, Software updates, and other up-to-the-minute product information, visit our website: www.extech.com Extech Instruments Corporation, 285 Bear Hill Rd., Waltham, MA 02451 Copyright © 2007 Extech Instruments Corporation All rights reserved including the right of reproduction in whole or in part in any form.