Using PI Batch View All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 1

1.1

Using PI Batch View

1.1.1

Objectives

Given a PI Server configured with batch records, use the PI BatchView add-in in PI ProcessBook and PI DataLink to: • • • • 1.1.2

Search for PI UnitBatches and PI SubBatches (Part A); Build displays showing the current and historical batches; Display and compare process values; Create a Microsoft Excel Report (Part B). Problem description

Part A

Using PI BatchView add-in in PI ProcessBook, build a display that allows the user to interactively run the following query: •

On Digester 1 or 2, find PI UnitBatches that were completed in the last 12 hours and that lasted between 50 and 60 minutes. Display only the Sulfate Cooking phase information by aligning all the start times;

Part B Using PI BatchView add-in in PI DataLink, build a Microsoft Excel Report for the last PI UnitBatches ran on the digester units along with the information on the temperature and pressure. 1.1.3

Approach

Part A Using PI ProcessBook and PI BatchView, build a batch display by:

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 2

1. 2. 3. 4. 5. 6.

Adding the search, result, Gantt chart and batch trend to the display; Defaulting the search for the units to “Digest*”; Adding a batch trend for the temperature; Adding a batch trend for the pressure; Configuring the search component to include the duration and filter parameter; Using the display in run mode and perform the query.

Part B

Using PI DataLink and PI BatchView, build a batch report by: 7. Open the UC-BatchViewTemplate.xlsx file;

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 3

8. Configure the Batch Search tool from the PI add-in menu; 9. Explore the report.

Try to do this exercise on your own before proceeding to the Step-by-Step Instructions.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 4

1.1.4

Step-by-Step Solution (Part A)

Create a New Display 1. Start the PI ProcessBook application. 2. Open a new display from the File > New menu. 3. Name your display Digesters and press on OK. 4. Maximize the display and switch to the build mode Tools > Build. 5. From the tool bar, select the PI BatchView toolbar button.

6. Define the object area from the top left corner to the bottom right of the display. 7. In the Batch Definition configuration window, select the Main tab and set the following parameters: o

Search for PIUnitBatches (default);

o

Set the PI Server to your PI Server name unless stated otherwise;

o

Under the Unit Name option, enter the string Digest*. At this point click on the Search button.

o

From the Available Aliases, move the Temperature and Pressure aliases to the Tag/Aliases window.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 5

Note: If the Temperature and Pressure Aliases do not show, it is more likely that they were not defined for every unit which returned PI UnitBatches in the results table.

8. Switch to the layout tab.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 6

9. Add the Search and Results options from the Visible Symbols section to the display using the check box. 10. Configure the Search symbol to display the Duration and Filter options by clicking on the Configure… button or by double-clicking on the Search symbol preview… 11. and then select the Duration and Filter options then click on OK.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 7

12. Split the batch trend in two trends by selecting Batch Trend (Pressure, Temperature) from the Trends section and use the split button.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 8

13. Use the Configuration… button and set the trend title to Pressure and Temperature then click on OK.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 9

14. The final configuration window should look like this:

15. Click on OK to complete the batch trend. 16. Reorganize the display to fit on one column the Search and Results symbols and on the second column the Gantt chart and both batch trend. In order to resize and move a symbol, click once on one of the components of the batch group. You will notice that the entire group is selected. Click a second time one symbol to select it specifically. Now, with the selected symbol, you can drag and resize it using its resizing handles. Moving the trends, you will experience the synchronization mechanism when the vertical access of a trend is aligned with the vertical access of the Gantt chart. There will be arrows appearing on the trends. 17. Switch to run mode.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 10

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 11

Query: ۫ on On Digester 1, find, on the last 24 hours, the batches for which the temperature exceeded 185 ◌C more than 5% of the PI UnitBatches during less than 75 minutes. 18. In run mode, use the Search symbol to specify the query parameters: o

Unit Name = Digest*1;

o

Active Range = Active between *-1 day and *;

o

Duration = Shorter than 75m;

o

Filter = ‘Temperature’ > 185 (or choose another value by inspecting the trend of Temperature) for Period: Greater than 5%.

19. Click on Search.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 12

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 13

1.1.5

Step-by-Step Solution (Part B)

For the DataLink part of this lab, Part B, you can start by opening up a template file in C:\Labs\Analytics\Using PI BatchView\Template. The file name is BatchViewTemplate.xlsx. The template is not the full solution, but it does have the objects and formatting required for the lab to save you time.

This lab also includes the full solution in C:\Labs\Analytics\Using PI BatchView\Solution\, the file BatchViewDemo.xlsx. We recommend this if you are in "executive overview" mode and want to test the features described in the lab.

1. Start Microsft Excel 2007. (Start > Programs > Microsoft Office > Microsoft Office Excel.) 2. Open the file C:\Labs\Analytics\Using PI BatchView\Template\BatchViewTemplate.xlsx using the Office Button.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 14

3. The template already contains the selection parameters and the formatting of your report. Set your cursor in Cell A12. Invoke the PI BatchView search panel by selecting Add-Ins > PI > Batch Search.

4. Fill the PI BatchView for Excel Search page with the cells as shown in the following picture. (Use cell references as described in #5 below.) Click on Search to make sure that you are retrieving data.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 15

5. Note that you could enter the information directly in the dialog window, but using references to the spreadsheet will allow you to dynamically update the report.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 16

6. Moving to the settings tab, select Two PISubBatchLevels with Show Levels Using Indentation with separate columns.

7. Click on OK when the configuration is completed.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577

Page 17

From that point, you can change you search criteria, parameter and analysis and observ the impact of the changes on the report.

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. © Copyright 1995-2009 OSIsoft, LLC, 777 Davis St., Suite 250, San Leandro, CA 94577