Understanding Chilled Beam and VAV Systems John Murphy, LEED® AP BD+C Applications Engineer Trane Ingersoll Rand La Crosse, Wisconsin
Chilled Beams • Brief overview of chilled beams • Assess marketed advantages of chilled beam systems versus VAV • Discuss challenges of applying chilled beam systems • Review some common applications
2
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
1
Passive Chilled Beam
ceiling
water pipes coil
perforated metal casing
3
Active Chilled Beam primary air
nozzles coils
ceiling induced air
induced air + primary air
4
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
2
Active Chilled Beams
5
Source of images: Halton
active chilled beams
Primary Air System
primary air handler
OA RA
EA
PA
RA
PA
RA
active chilled beam
RA
Primary air must be sufficiently drier than space: • to offset space latent load, and • to keep space DP below chilled beam surface temp
6
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
3
window
Induction of Mid-20th Century Active Chilled Beams • Installed on ceiling rather than under windows – More coil surface area – Lower air pressure required induced room air
• Warmer water temperature – No condensation – More coil surface area – Lower air pressure required
nozzles
• Larger ducts floor primary air
condensate drain connection
– Lower air pressure required – Less noise
77
Chilled Beams • Brief overview of chilled beams • Assess marketed advantages of chilled beam systems versus VAV • Discuss challenges of applying chilled beam systems • Review some common applications
8
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
4
active chilled beams
Claimed Advantage #1 • “An ACB system typically allows for smaller ductwork and d smaller ll air-handling i h dli units it than th a VAV system.” t ” – Primary airflow < supply airflow due to induction – Shorter floor-to-floor height required? – Less mechanical room floor space?
9
active chilled beams
Determining Primary Airflow Rate • Primary airflow (PA) is
PA
b based d on llargestt of: f – Minimum outdoor airflow required (ASHRAE 62.1) – Airflow required to offset space latent load (depends on dew point of PA) – Airflow needed to induce sufficient room air (RA) to offset the space sensible cooling load
RA SA
SA
10
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
5
active chilled beams
Determining Primary Airflow Rate Minimum OA per ASHRAE 62.1 (to achieve LEED IEQc2) ACB C system Airflow required to offset space latent load
Airflow needed to induce sufficient room air to offset space sensible ibl cooling li lload d VAV system Airflow needed to offset space sensible cooling load
Example: office space 0.085 cfm/ft2 (0.085 × 1.3 = 0.11 cfm/ft2) 0.085 cfm/ft2 0.11 cfm/ft2 0.36 cfm/ft2
(DPTPA = 47°F) (DPTPA = 49°F) (DPTPA = 53°F)
0.36 cfm/ft2 (55°F primary air) (four, 6-ft long beams)
0.90 cfm/ft2 (55°F supply air)
11
active chilled beams
Determining Primary Airflow Rate Minimum OA per ASHRAE 62.1 (to achieve LEED IEQc2) ACB C system Airflow required to offset space latent load
Airflow needed to induce sufficient room air to offset space sensible ibl cooling li lload d VAV system Airflow needed to offset space sensible cooling load
Example: K-12 classroom 0.47 cfm/ft2 (0.47 × 1.3 = 0.61 cfm/ft2) 0.47 cfm/ft2 0.61 cfm/ft2 1.20 cfm/ft2
(DPTPA = 44°F) (DPTPA = 47°F) (DPTPA = 51°F)
0.47 cfm/ft2 (55°F primary air) (eight, 4-ft long beams)
1.20 cfm/ft2 (55°F supply air)
12
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
6
Minimum Outdoor Airflow Required by ASHRAE 62.1 typical ACB primary airflow (0.30 to 0.70 cfm/ft2) Barracks sleeping area example (0.47 cfm/ft2)
Classroom (age 9 plus) Conference/meeting room Corridor Courtroom Hotel bedroom/living room Laboratory Lecture classroom Library Lobby (hotel, dormitory)
example (0.36 cfm/ft2)
Office space Reception area Retail sales floor 0.10
0.20
0.30
0.40
0.50
0.60
0.70
minimum outdoor airflow required,
0.80
0.90
1.0
cfm/ft2
(based on default occupant densities)
13
active chilled beams
Claimed Advantage #2 • “An ACB system can typically achieve relatively low sound d llevels.” l ” – No fans or compressors in or near occupied spaces – Constant primary airflow = constant sound – Depends on air pressure
14
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
7
active chilled beams
Claimed Advantage #3 • “An ACB system uses significantly less energy than a VAV system, t due d to: t 1. Significant fan energy savings (because of the reduced primary airflow), and 2. Higher chiller efficiency (because of the warmer water temperature delivered to the chilled beams), and 3. Avoiding reheat (because of zone-level cooling coils).”
15
Fan Energy Use: ACB vs. VAV •
A zone served by ACB’s may require 60% to 70% less primary airflow, at design cooling conditions… …but the difference in annual fan energy use will be much closer because the VAV system benefits from: 1. Reduced zone airflow at part load 2. System load diversity 3. U 3 Unloading oad g o of tthe e supp supply y fan a at pa partt load oad
16
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
8
example
Zone Primary Airflow at Part Load zone e primary airflow, cfm m/ft2
1.0
1.0
conventional VAV system
0.8
0.8
0.6
0.6
0.4
0.4
30% minimum i i airflow i fl setting tti
0.2
0
cold-air VAV system
active chilled beam system
design heating load
space load
0.2
design cooling load
0
17
System Load Diversity variable-volume fan 0.72 cfm/ft2
OA
multiple-zone VAV system central VAV fan sized for “block” airflow
RA
EA
PA
PA
fan airflow = diversity × Σ zone primary airflows
RA
RA
RA
0.90 cfm/ft2
0.90 cfm/ft2
0.90 cfm/ft2
constant-volume fan 0.36 cfm/ft2
OA
active chilled beam system central CV fan sized for “sum-of-peaks” sum of peaks airflow
RA
EA
For this example: system load diversity = 80% fan airflow = 80% × 0.90 cfm/ft2 = 0.72 cfm/ft2
PA
RA
0.36 cfm/ft2
PA
RA
0.36 cfm/ft2
RA
0.36 cfm/ft2
fan airflow = Σ zone primary airflows For this example: fan airflow = 0.36 cfm/ft2
18
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
9
typical VAV system supply fan
Part-Load Performance fan input power, % of de esign
100
80
60
40
VAV supply l fan f with VFD
20
0
0
20
40
60
80
100
supply fan airflow, % of design 19
supply fan energy use
ACB vs. Conventional VAV fan in nput power, bhp/100 00 ft2
1.0
0.8
conventional VAV
design cooling conditions
0.6
active chilled beam
0.4
VAV uses more fan energy
ACB uses more fan energy
0.2
68% of VAV supply fan design airflow
0
0
0.2
0.4
0.6
0.8
1.0
supply fan airflow, cfm/ft2 20
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
10
supply fan energy use
ACB vs. Cold-Air VAV fan in nput power, bhp/100 00 ft2
1.0
0.8
0.6
cold-air VAV
active chilled beam
0.4
design cooling conditions VAV uses more fan energy
ACB uses more fan energy
0.2
80% of VAV supply fan design airflow
0
0
0.2
0.4
0.6
0.8
1.0
supply fan airflow, cfm/ft2 21
Chiller Energy Use: ACB vs. VAV •
Chilled water delivered to the chilled beams must be warmer to avoid condensation… …but the chilled water delivered to the primary AHU’s still must be cold to dehumidify the building.
22
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
11
Dedicated Chilled-Water Plants chillers
57°F
42°F
63°F
58°F
variable-flow pumps
bypass for minimum flow primary air handlers
chilled beams
23
Shared Chilled-Water Plant
42°F
57°F
mixing valve primary air handlers
42°F
T
chilled beams
58°F
54°F 63°F
24
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
12
Chiller Energy Use ACB system • Warm water delivered to chilled beams • Still needs cold water delivered to the primary AHU’s for dehumidification • Typically no DCV • No (or minimal) capacity for airside economizing • Waterside economizing (more effective due to warmer water temp)
VAV system Cold water delivered to central VAV air-handling units
•
• • •
Commonly implement DCV 100% capacity for airside economizing Can use waterside economizing, but airside economizing is more efficient
25
Waterside Economizer chillers
57°F
42°F variable-flow pumps
bypass for minimum flow primary air handlers
mixing valve 42°F
T
variable-flow pump
58°F
54°F 63°F from cooling tower
chilled beams
waterside economizer heat exchanger
26
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
13
Pumping Energy: ACB vs. VAV ACB system • Higher pumping energy use • Warm water temperatures (58°F to 60°F) • Small waterside ΔT (5°F to 6°F) • Water pumped to chilled beams in every space
VAV system Lower pumping energy use • Cold water temperatures (40°F to 44°F) • Large waterside ΔT (12°F to 14°F) • Water pumped only to centralized mechanical rooms
•
27
Impact of Reheat Energy VAV terminal with 40% minimum airflow setting primary airflow at design conditions = 0.90 cfm/ft2 primary airflow when reheat is activated: = 40% × 0.90 cfm/ft2 = 0.36 0 36 cfm/ft f /f 2 cooling provided when primary airflow is at minimum: = 0.36 cfm/ft2 of 55°F primary air
PA 0.36 cfm/ft2 55°F
Reheat is needed to avoid overcooling the space when the space sensible cooling load < 40% of design load.
PA 0.36 cfm/ft2 55°F
RA
active chilled beam primary airflow at design conditions = 0.36 cfm/ft2 primary airflow when CHW valve is fully closed = 0.36 cfm/ft2 cooling provided when CHW valve is fully closed: = 0.36 cfm/ft2 of 55°F primary air
Heat is needed to avoid overcooling the space when the space sensible cooling load < 40% of design load. 28
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
14
example office space
Cold vs. Neutral Primary Air “Cold” (55°F) primary-air temperature
PA 0.36 cfm/ft2 55°F
RA
• four ((4)) ACBs,, each 6-ft long g x 2-ft wide • primary airflow at design conditions = 0.36 cfm/ft2 • total water flow = 6.0 gpm
“Neutral” (70°F) primary-air temperature
PA 0.50 0 50 cfm/ft f /ft2 70°F
RA
• six (6) ACBs, each 6-ft long x 2-ft wide • primary i airflow i fl att design d i conditions diti = 0.50 0 50 cfm/ft f /ft2 • total water flow = 9.0 gpm
29
Heating Energy: ACB vs. VAV ACB system • Heat added when CHW valve closes and primary airflow begins to overcool the space • Typically no DCV
VAV system Heat added when damper closes to minimum and primary airflow begins to overcool space • Commonly implement DCV • Parallel fan-powered VAV terminals can draw warm air from ceiling plenum
•
30
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
15
office building
Example Energy Analysis • “Baseline” chilled-water VAV system – ASHRAE 90.1-2007, Appendix G (55°F supply air)
• Active chilled beam system – Four-pipe active chilled beams – Separate primary AHUs for perimeter and interior areas (with SAT reset and economizers) – Separate water-cooled chiller plants (low-flow plant supplying primary AHUs)
• “High-performance” chilled-water VAV system – 48°F supply l air i (d (ductwork t k nott downsized) d i d) – Optimized VAV system controls (ventilation optimization, SAT reset) – Parallel fan-powered VAV terminals – Low-flow, water-cooled chiller plant 31
Example Energy Analysis Annual Building Energy U Use, kBtu/yr
12,000,000
10,000,000
Houston
Los Angeles
Philadelphia
St. Louis
Pumps Fans Heating
8,000,000
Cooling Plug Loads Lighting
6,000,000
4,000,000
2,000,000
32
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
16
Chilled Beams • Brief overview of chilled beams • Assess marketed advantages of chilled beam systems versus VAV • Discuss challenges of applying chilled beam systems • Review some common applications
33
ACB challenges
High Installed Cost • Limited cooling capacity = lots of ceiling space – Warmer water temperature requires more coil surface area – Induction with low static pressures requires more coil surface area to keep airside pressure drop low
eight i h (8) active i chilled hill d beams, b each 4-ft long x 2-ft wide four (4) active chilled beams, each 6-ft long x 2-ft wide
Example: 1000-ft2 office space
Example: 1000-ft2 classroom
34
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
17
System design variable
Impact on installed cost of the chilled beams
Impact on performance of the overall system
2-pipe versus 4-pipe chilled beams
A 2-pipe beam provides more cooling capacity than a 4-pipe beam because more coil surface is available
Using 2-pipe beams requires a separate heating system, otherwise it can result in poorer comfort control because either cold water or warm water is delivered to all zones
Primary airflow rate (cfm)
Increasing the primary airflow rate through the nozzles results in more air being induced from the space space, which increased the capacity of the chilled beam coils
Increasing the primary airflow rate increases primary AHU fan energy use, increases noise in the space space, and requires a larger primary AHU and larger ductwork
Inlet static pressure of the primary air
Increasing the static pressure at the inlet to the nozzles results in more air being induced from the space, which increased the capacity of the chilled beam coils
Increasing the inlet pressure increases primary AHU fan energy use, and increases noise in the space
Dry-bulb temperature of the primary air
Delivering the primary air at a colder temperature means that less of the space sensible cooling load needs to be offset by the chilled beams
Using a colder primary-air temperature may cause the space to overcool and low sensible cooling loads, thus requiring the chilled beam (or separate heating system) to add heat to prevent overcooling space
Entering water temperature
Supplying colder water to the chilled beam increases the cooling capacity of the beam
Using a colder water temperature requires the space dew point to be lower to avoid condensation, which means the primary air needs to be dehumidified to a lower dew point
Water flow rate (gpm)
Increasing the water flow rate increases the cooling capacity of the beam
Increasing the water flow rate increases pump energy use and requires larger pipes and pumps 35
ACB challenges
Need to Prevent Condensation • Primary air system used to limit indoor dew point (typically (t i ll below b l 55°F) • Warm chilled-water temperatures delivered to beams (typically between 58°F and 60°F) • Start primary air system (chilled beams off) to reduce indoor humidity following shutdown • Tight g building g envelope and g good building g pressure control to minimize infiltration – Use caution if the building has operable windows or natural ventilation
36
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
18
ACB challenges
Risk of Water Leaks • Lots of water piping, pipe connections, and valves above b every space iin th the b building ildi – Four-pipe systems have twice as much piping and twice as many connections
Example: 1000-ft2 office space
Example: 1000-ft2 classroom
37
ACB challenges
No Filtration of Local Recirc Air • Chilled beams typically not equipped with a filter – Coils intended to operate dry (no condensation), lessening concern about preventing wet coil surfaces from getting dirty – Still concern about removing particles generated indoors or brought indoors
38
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
19
ACB challenges
Limited Heating Capability • Active chilled beams have limited heating capacity • Chilled beam systems often use a separate heating system (baseboard convectors, radiant floor heat)
39
Chilled Beams • Brief overview of chilled beams • Assess marketed advantages of chilled beam systems versus VAV • Discuss challenges of applying chilled beam systems • Review some common applications
40
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
20
Office Buildings Why ACB might be a good fit:
Why ACB might not be a good fit:
• Low sensible cooling loads • Low ventilation rates resultlt in i primary i AHU • Low latent loads using mixed air • Not friendly for re-configuring spaces
41
Schools Why ACB might be a good fit:
Why ACB might not be a good fit:
• High ventilation rates
• High latent loads require
resultlt in i primary i AHU with 100% OA • Low sound levels
llow d dew point i t primary i air i • Lack of economizing capacity
42
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
21
Hospital Patient Rooms Why ACB might be a good fit:
Why ACB might not be a good fit:
• High minimum air change
• No local filtration
rates t (6 ACH) • Low latent loads
( d requirement?) (code i t?)
43
Patient Room: All-Air System VAV terminal with reheat coil
230 cfm supply airflow 200 cfm (6 ACH) minimum 67 cfm (2 ACH) outdoor air
return airflow 200 ft2 with 10-ft ceiling height
Design space sensible cooling load = 5000 Btu/hr Design supply airflow (55°F) = 230 cfm Minimum outdoor airflow (ASHRAE 170) = 67 cfm (2 ACH) Minimum supply airflow (ASHRAE 170) = 200 cfm (6 ACH) Airflow turndown before activating reheat = 12%
44
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
22
Patient Room: ACB System active chilled beam (qty 1, 10 ft long, 4-pipe)
67 cfm (2 ACH) primary airflow 100% outdoor air
268 cfm (>6 ACH) total airflow primary air + induced room air (3:1 induction ratio)
exhaust airflow 200 ft2 with 10-ft ceiling height
Design space sensible cooling load Design primary airflow (55°F) Minimum outdoor airflow (ASHRAE 170) Total room airflow Capacity turndown before activating heat
= 5000 Btu/hr = 67 cfm = 67 cfm (2 ACH) = 268 cfm (8 ACH, 3:1 induction ratio) = 70%
45
active chilled beam systems compared to VAV systems
Summary Potential advantages • Smaller ductwork and smaller air handlers – Primary airflow < supply airflow, but likely > outdoor airflow
• Low sound levels • Impact on overall system energy? – Primary airflow < supply airflow, but constant airflow – Warm water for beams, but cold water primary AHU – Increased pumping energy – No DCV, limited airside economizing
Challenges • High installed cost • Need to prevent condensation • Risk of water leaks • No filtration of local recirculated air • Limited heating capability
46
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
23
Additional Resources •
“Understanding Chilled Beam Systems,” Trane Engineers Newsletter ADM-APN034-EN (2009) www.trane.com/engineersnewsletter
•
Chilled-Water VAV Systems, Trane application manual SYS-APM008-EN (2009)
47
© 2010 Trane, a business of Ingersoll-Rand Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional.
24