Bulletin HY11-5715-577/UK

Installation Manual VS111 Series

Plug-In Amplifier for Proportional Valves

Parker Hannifin GmbH Hydraulic Controls Division Gutenbergstr. 38 41564 Kaarst, Germany Tel.: +49-181 99 44 43 0 Fax: +49-2131-513-230 E-mail: [email protected] Copyright  2002, Parker Hannifin GmbH

Plug-In Amplifier VS111 Series

Installation Manual

Note This document and other information from Parker Hannifin GmbH, its subsidiaries, sales offices and authorized distributors provide product or system options for further investigation by users having technical expertise. Before you select or use any product or system it is important that you analyse all aspects of your application and review the information concerning the product or system in the current product catalogue. Due to the variety of operating conditions and applications for these products or systems, the user, through his own analysis and testing, is solely responsible for making the final selection of the products and systems and assuring that all performance and safety requirements of the application are met. The products are subject to change by Parker Hannifin GmbH at any time without notice.

IA UK VS111.INDD 19.06.06 RH

2

Parker Hannifin GmbH Hydraulic Controls Division

Plug-In Amplifier VS111 Series

Installation Manual The plug-in amplifier VS111 is used to control proportional pressure, directional control, and flow valves. The amplifier is mounted directly on the proportional solenoid and secured by a central screw. It supplies a drive current for one proportional solenoid. This current is proportional to the command signal at the amplifier input. In conjunction with a proportional valve this allows an infinite adjustment of a pressure or flow rate.

Features •

Solenoid drive



Simple mounting direct to the valve



Standard voltage or current signal inputs



Control from PLC also possible



Temperature-independent solenoid current



Solenoid connection acc. EN 175301-803 (2+E)



Installation connection acc. EN 175201-804 (6+E)



Conformity to the European EMC standards (CE)

Block diagram

IA UK VS111.INDD 19.06.06 RH

3

Parker Hannifin GmbH Hydraulic Controls Division

Plug-In Amplifier VS111 Series

Installation Manual Ordering Code

VS

1

1

0

1

0

Valve type

Valve amplifier Code

Valve type

0 1 2 8

without* Proportional flow valve Proportional DC valve Proportional pressure valve

20 Design Series

*The versions acc. codes 1...8 will be shipped factory set. The version Code 0 needs to be set to the connected valve's characteristics.

Attention: Installation connector has to be ordered separately (order no. HR 2150 2072).

EMC EN 50081-2 EN 50082-2

EN 55011 EN 61000-4-2 EN 61000-4-3

EN 61000-4-4 EN 61000-4-5

Characteristics Supply voltage range

[V]

Current consumption

[A]

18...32, ripple < 5% 0.8

Power consumption (at 24V)

[VA]

20

Input signal ranges input voltage input current

[V] [mA]

0...+10 / 0...+15, 100kOhm 0...20 / 4...20, 500Ohm

Diagnostic output

[V]

0.1 = ^ 0.2A

Reference output

[V]

15 ± 5% / max. 5mA

Solenoid output current max.

[A]

0.8

Temperature drift of output current

[%]

< ± 2%

Adjustment ranges Min Max

[%] [%]

0...50 0...100

[s]

0.1...8

Ramp time range Dither amplitude range Dither frequency

[%]

0...90

[Hz]

40 / 80

Protection class Ambient temperature range

IP65 mounted condition [°C]

-20...60

Connection Installation connector Solenoid connector

6 + E, EN 175201-804 2 + E, EN 175301-803

Installation cross sections min. Cable outer dimension

AWG 17 [mm]

max. 11

Cable length

[m]

max. 50

Pre-fuse

[A]

2.0 lag, DIN 41571

IA UK VS111.INDD 19.06.06 RH

4

Parker Hannifin GmbH Hydraulic Controls Division

Installation Manual

Plug-In Amplifier VS111 Series

Connection Examples Command value given by external signal

Command value given by potentiometer

Selection and Adjustment Options Com. signal

B1

B3

B4

B5

0...10V 0...15V 0...20mA 4...20mA

x x x

x x

2-3 2-3 2-3 1-2

x x x -

Dither frequency

B2

40 Hz 80 Hz

x

Connection Arrangement Installation Connector

IA UK VS111.INDD 19.06.06 RH

5

Parker Hannifin GmbH Hydraulic Controls Division

Plug-In Amplifier VS111 Series

Installation Manual Dimensions

Adjustment Instruction Note: For all following adjustments the potentiometer "Dither signal" has to set fully counterclockwise first. The solenoid current measured at the diagnostic output should be observed (plug-in amplifier connected to the solenoid). Please take notice of the adjustment sequence! 3. Ramp time setting

1. MIN current setting

- Adjust the response time by variation of the potentiometers "Ramp up" and "Ramp down", until the required transition behaviour is reached.

-Command signal zero (0V/0mA) -Turn the potentiometer "MIN current" clockwise, until the required valve adjustment is reached. 2. MAX current setting

4. Dither adjustment

-Command signal maximum (10V/15V/20mA) -Turn the potentiometer "MAX current", until the required valve adjustment is reached.

- Select dither frequency aac. solenoid/ valve type, with jumper B2 = 80 Hz without jumper B2 = 40 Hz - Feed in approx. 40% command signal. - Turn the potentiometer "Dither signal" max. clockwise, until an oscillating is audible within the hydraulic system.

Direction to trouble shooting The required max. current can just keep constant until the condition Max current (A) =

Supply voltage (V) 2V actual solenoid spool resistance (Ohms)*

will be keeped. This means for example, that if a solenoid spool of 24V/0.8A will be connected to the amplifier, the supply voltage should reach approx. 30V. *the resistance of the spool increases by warming for up to 40%. IA UK VS111.INDD 19.06.06 RH

6

Parker Hannifin GmbH Hydraulic Controls Division

Plug-In Amplifier VS111 Series

Installation Manual

Installation Guide to Provision of Electromagnetic Compatibility Power Supply The utilized power supply has to comply with the EMC-standards (CE-sign, certificate of conformity). Relays and solenoids operating from the same supply circuit has to be fitted by surge protection elements. Wiring Cable The wiring cable between the control cabinet and the valve has to be shielded. The wiring has to be installed from a 7wire cable that utilizes a common shielding and a cross section of min. AWG17. The capacity should not exceed a value of approx. 130pF/m (wire/wire). The maximum cable length is 50 m. No power current lines may be placed in parallel to the valve's wiring cables. The cable shield has to be connected to the connector pin 2. The earth pin of the connector has to be installed as separate wire within the cable to the cabinet and should there be connected to the Earth Ground potential.

Example

IA UK VS111.INDD 19.06.06 RH

7

Parker Hannifin GmbH Hydraulic Controls Division