Standard Features

  

 Input: PT 100 OR thermocouples

 Configurable Co Ranges Using Solder Pads

 Output: 4 …20 mA, 2 wire design

RTD or Thermocouple Programmable Ranges Economical

 Fault Signal: For sensor burnout and sensor short circuiting

 Temperature Range: Large ambient temperature range  Size: Compact

 Guarantee: 5 years

Type T19.10 Analog Temperature Transmitter

Datasheet: T19.01

Ready-To-Ship Temperature Transmitters





Description Part #

Type

Pt100 Small Range 3656471 Pt100 Large Range 3656609

Price $120.00

Type T19.30 Analog Temperature Transmitter

Standard Features

 Input: PT 100 OR thermocouples  Configurable Co Ranges

 Output: 4 …20 mA, 2 wire design

 RTD or Thermocouple  Programmable Ranges  DIN Rail Mount

 Fault Signal: For sensor burnout and sensor short circuiting  Temperature Range: Large ambient temperature range  Size: Compact

 Guarantee: 5 years Datasheet T19.30



Type T19.30 Analog Temperature Transmitter

Ready-To-Ship Temperature Transmitters



Type

Description Part #

Pt100 Small Range 7827912 Pt100 Large Range 7889178

Price $148.00

For pricing info, call 1-888-WIKA-USA or visit www.wika.com

Type T24.10 Temperature Transmitter Standard Features

 Configurable with Windows PC without sensor simulation, remote configuration also possible from the control room via the current loop

  

 Analog signal processing, ideal for multiplex-systems

RTD Only Programmable Potted Electronics

 For Pt 100 and resistance-sensors, 3 wire  Analog output 4 … 20 mA, 2 wire design

 EMC Conformity per EN 61 326 and NAMUR NE 21

 Sensor burnout monitoring in accordance with NAMUR NE 43

 Compact design suitable for any DIN connection head of form B



Ready-To-Ship Temperature Transmitters Type

Standard

Description Part #

Price

4363048

$210.00

Type T24.10 Temperature Transmitters

Datasheet: T24.10

Type T53.10 Fieldbus Temperature Transmitter Standard Features  Field bus protocol PROFIBUS PA & Foundation Fiedbus  Configurable for connection to RTDs, Thermocouples, Resistance - sensor, mV - sensor

 Foundation Fieldbus  PROFIBUS® Transmitter  Programmable  Digital Temperature Transmitter

 Dual sensor capable  Class protection, intrinsically safe per FISCO-Model II 1 G EEx ia ll B / II C T4 / T5 / T6 II 2 G EEx ib ll B / II C T4 / T5 / T6  EMC Directive 89/336/EWG, DIN EN 61 326:2002, NAMUR NE 21  Isolation voltage AC 1500 V between sensor and bus

Type T53.10 Fieldbus Temperature Transmitter

 95% Rh protection  Terminal connections with captive screws

Data sheet: T-53.10



Ready-To-Ship Temperature Transmitters Type

Standard

Description Part # 42512236

For pricing info, call 1-888-WIKA-USA or visit www.wika.com

Price

$690.00

Type T12.10 Digital Temperature Transmitter Standard Features

 Inputs: Refer to table  Accuracy: RTD: (Per DIN IEC 770, 23°C ±5°C) ±0.2 °C or 0.1°C + 0.05% of valve; Thermocouple: (Per DIN IEC 770, 23°C ±5°C) 0.5°C or 10uV or 0.05% of value

 Digital Temperature Transmitter  Programmable  CE Certified

 Thermocouple Break Protection: Program- mable, Upscale (23 mA) or Downscale (3.8 mA)  Cold Junction Compensation: Programmable internal or external (Pt 100), Accuracy ±1.0°C  RTD Wiring Configuration: 2, 3, or 4 wire  Response Time: Programmable 1 to 60 seconds. Measurement Update Time 2/second

Type T12.10

 Maximum Lead Wire Resistance: Thermocouple: 500 Ohm; RTD: 10 Ohm per lead  Output: 4-20 mA  Maximum Output Load: RMAX < (VS - 9v) / 0.021 A  Load Effect: < 0.01% of span/100 Ohm  Power Supply: 9 to 36 Vdc  Power Supply Effect: < 0.005% of span/V  Isolation: 1500 Vac, 60 s  Environmental: Operating Temperature: -40 to 185°F (-40 to 85°C ); Optional Operating Temperature: -40 to 220°F (-40 to 105°C), -58 to 185°F(-50 to 85°C); Humidity: 100% non- condensing Vibration: 10 Hz to 2 KHz, 5 g per DIN IEC 68 2-6; Warm-up time: 5 minutes  Construction: Case Material: Plastic; Dimensions: 1.95" dia. (49.5 mm ), 1.12" ht. (28.5 mm); Weight: 2.47 oz (0.07 kg.)  Warranty: 5 years



T-12 Programmable Inputs and Ranges Input Sensor Standard Range °C Range °F Min. Span J IEC 584 -100 to 1200 -148 to 2192 50 K K IEC 584 -180 to 1372 -292 to 2500 50 K N IEC 584 -180 to 1300 -292 to 2372 100 K T IEC 584 -200 to 400 -328 to 752 50 K E IEC 584 -100 to 1000 -148 to 1832 50 K Thermocouple L DIN 43710 -100 to 900 -148 to 1652 50 K U DIN 43710 -180 to 600 -292 to 1112 75 K R IEC 584 -50 to 1760 -58 to 3200 200 K S IEC 584 -50 to 1760 -58 to 3200 200 K B IEC 584 400 to 1820 752 to 3308 200 K W3 ASTM E988 0 to 2300 32 to 4172 200 K W5 ASTM E988 0 to 2300 32 to 4172 200 K RTD Pt 100 Pt 100 -200 to 850 -328 to 1562 25 K Ni 100 Ni 100 -60 to 250 -76 to 482 25 K Linear 0 to 5K Ohm 30 Ohm Resistance DC Voltage -10 to 800 mV 5 mV (Unipolar)

Ready-To-Ship Temperature Transmitters Type

Standard Rail Adapter Configuration Set

Description Part #

3616933 3593789 11606304

Price

$290.00 $21.35 $264.30

Datasheet: T12.10 For pricing info, call 1-888-WIKA-USA or visit www.wika.com

Type T12.30 Digital Temperature Transmitter  Digital Temperature Transmitter  Programmable  DIN Rail

Standard Features

 Inputs: Refer to table  Accuracy: RTD: (Per DIN IEC 770, 23°C ±5°C) ±0.2 °C or 0.025%FS + 0.1;Thermocouple: (Per DIN IEC 770, 23°C ±5°C) ±0.5 or 0.05%FS or ± 10µv Thermocouple Break Protection: Programmable, Upscale (23 mA) or Downscale (3.8 mA)  Cold Junction Compensation: Programmable internal or external (Pt 100), Accuracy ±1.0°C  RTD Wiring Configuration: 2, 3, or 4 wire  Response Time: Programmable 1 to 60 seconds  Measurement Update Time: 2/second  Maximum Lead Wire Resistance: Thermocouple: 500 Ohm; RTD: 10 Ohm per lead

Type T12.30

 Output: 4-20 mA  Maximum Output Load: RMAX < (VS - 9v) / 0.021 A  Load Effect: < 0.01% of span/100 Ohm  Power Supply: 9 to 36 Vdc  Power Supply Effect: < 0.005% of span/V  Isolation: 1500 Vac, 60 s  Environmental: T12.30 Operating Temperature: -14 to 158°F (-25 to 70ºC); Humidity: 100% non- condensing; Vibration: 10 Hz to 2 KHz, 5 g per DIN IEC 68 2-6; Warm-up time: 5 minutes  Construction: Case Material: Plastic; Weight: T12.10: 2.4oz (0.07kg); T12.30: 7oz (0.2kg)  Warranty: 5 years



T-12 Programmable Inputs and Ranges Input Sensor Standard Range °C Range °F Min. Span J IEC 584 -100 to 1200 -148 to 2192 50 K K IEC 584 -180 to 1372 -292 to 2500 50 K N IEC 584 -180 to 1300 -292 to 2372 100 K T IEC 584 -200 to 400 -328 to 752 50 K E IEC 584 -100 to 1000 -148 to 1832 50 K Thermocouple L DIN 43710 -100 to 900 -148 to 1652 50 K U DIN 43710 -180 to 600 -292 to 1112 75 K R IEC 584 -50 to 1760 -58 to 3200 200 K S IEC 584 -50 to 1760 -58 to 3200 200 K B IEC 584 400 to 1820 752 to 3308 200 K W3 ASTM E988 0 to 2300 32 to 4172 200 K W5 ASTM E988 0 to 2300 32 to 4172 200 K RTD Pt 100 Pt 100 -200 to 850 -328 to 1562 25 K Ni 100 Ni 100 -60 to 250 -76 to 482 25 K Linear 0 to 5K Ohm 30 Ohm Resistance DC Voltage -10 to 800 mV 5 mV (Unipolar)

Ready-To-Ship Temperature Transmitters Type

Standard Configuration Set

Description Part #

3625321 11606304

Datasheet: T12.30 For pricing info, call 1-888-WIKA-USA or visit www.wika.com

Price

$392.00 $264.30

Type T32.1S/T32.3S

Digital Temperature Transmitter with Hart® protocol

 Digital Temperature Transmitter  Programmable  HART® Communicator Standard Features

 Output: 4-20 mA  Inputs: Refer to table  TÜV certified SIL version for protective equipment

Type T32.1S

 Universal connection for one or two sensors  Sensor drift detection allows an error signal to be sent if deviation between sensor 1 and sensor 2 exceeds user selectable value

Type T32.3S

 Sensor break detection in accordance to NAMUR NE89  Isolation: voltage AC 12--V between server and current loop  Warranty: 5 years



Ready-To-Ship Temperature Transmitters Type

T32.1S - Standard T32.3S - Standard

Description Part # 12655423 12655458

Datasheet: T32.1S & T32.3S For pricing info, call 1-888-WIKA-USA or visit www.wika.com

Price

$440.00 $555.00

Type T32.1S/T32.3S

Digital Temperature Transmitter with Hart® protocol

Temperature transmitter input Resistance sensor Pt100 Pt(x)

4)

JPt100

10 ... 1000

Ni100

Resistance sensor

max. configurable measuring range 1)

-200 ... +850 °C

Standard

α values

IEC 60751: 2008 α = 0.00385

-200 ... +850 °C

IEC 60751: 2008

-60 ... +250 °C

DIN 43760: 1987 α = 0.00618

-200 ... +500 °C 0 ... 8,370 Ω



JIS C1606: 1989

Minimum measuring span 14) 10 K or 3.8 Ω whichever is greater

α = 0.00385

α = 0.003916

4Ω

0 ... 100 % Sensor current at the measurement

max. 0.3 mA (Pt100)

Max. wire resistance

50 Ω each wire, 3-/4-wire

Potentiometer

9)



10 %

Type J (Fe-CuNi) Type K (NiCr-Ni)

Type L (Fe-CuNi)

Type E (NiCr-Cu)

max. configurable measuring range 1)

Standard

-270 ... +1,372 °C

IEC 60584-1: 1995

-210 ... +1,200 °C

IEC 60584-1: 1995

-200 ... +900 °C

DIN 43760: 1987

-270 ... +1,000 °C

Type N (NiCrSi-NiSi) -270 ... +1,300 °C Type T (Cu-CuNi)

-270 ... +400 °C

Type R (PtRh-Pt)

-50 ... +1,768 °C

Type U (Cu-CuNi) Type S (PtRh-Pt)

Type B (PtRh-Pt) mV sensor

Connection type

-200 ... +600 °C



Minimum measuring span 14)

50 K or 2 mV whichever is greater

IEC 60584-1: 1995 IEC 60584-1: 1995 IEC 60584-1: 1995 DIN 43710: 1985

0 ... +1,820 °C 15) IEC 60584-1: 1995

200 K

IEC 60584-1: 1995

- 500 ... +1,800 mV

Cold junction compensation, configurable 1) 2)

≤ ±0.12 °C

≤ ±0.0094 °C 6) 7)

≤ ±0.12 °C

≤ ±0.12 °C

5)

≤ ±1.68 Ω ≤ 0.50 %

5)

8)

10)

≤ ±0.0094 °C 6) 7) ≤ ±0.0094 °C 6) 7) ≤ ±0.1584 Ω 8)

≤ ±0.0100 % 10)

Typical measuring Temperature coefficient deviation 2) per °C typical 3) ≤ ±0.91 °C 11)

≤ ±0.0217 °C 7) 11)

≤ ±0.91 °C 11)

≤ ±0.0203 °C 7) 11)

≤ ±0.91 °C 11) ≤ ±1.02 °C 11) ≤ ±0.92 °C 11)

150 K

Max. wire resistance

≤ ±0.0094 °C 6) 7)

5)

≤ ±0.98 °C 11)

IEC 60584-1: 1995

-50 ... +1,768 °C

≤ ±0.12 °C 5)

1 sensor 2- /4- /3-wire or 2 sensors 2-wire (for further information, please refer to designation of terminal connections)

Connection type

Thermocouple

Typical measuring Temperature coefficient deviation 2) per °C typical 3)

150 K

4 mV

≤ ±0.92 °C 11) ≤ ±1.66 °C 11) ≤ ±1.66 °C 11)

≤ ±1.73 °C 12)

≤ ±0.33 mV 13)

≤ ±0.0238 °C 7) 11) ≤ ±0.0224 °C 7) 11) ≤ ±0.0238 °C 7) 11) ≤ ±0.0191 °C 7) 11) ≤ ±0.0191 °C 7) 11) ≤ ±0.0338 °C 7) 11) ≤ ±0.0338 °C 7) 11) ≤ ±0.0500 °C 7) 12)

≤ ±0.0311 mV 7) 13)

1 sensor or 2 sensors (for further information, please refer to "designation of terminal connections") 5 kΩ each wire

internal compensation or external with Pt100, with thermostat or off

Other units e. g. °F and K possible Measuring deviation (input + output) at ambient temperature 23 °C ±3 K, without influence of lead resistance; example calculation see page 4 3) Temperature coefficient (input + output) per °C 4) x configurable between 10 … 1,000 5) Based on 3-wire Pt100, Ni100, 150 °C MV 6) Based on 150 °C MV 7) In ambient temperature range -40 … +85 °C 8) Based on a sensor with max. 5 kΩ 9) Rtotal: 10 ... 100 kΩ 10) Based on a potentiometer value of 50 %

11) 12) 13) 14)

Based on 400 °C MV with cold junction compensation error Based on 1000 °C MV with cold junction compensation error Based on measuring range 0 ... 1 V, 400 mV MV The transmitter can be configured below these limits but not recommended due to loss of accuracy. 15) Specification valid only for measuring range between 450 ... 1,820 °C bold: basic configuration italic: This sensors are not allowed at option SIL (T32.xS.xxx-S)

MV = Measuring value (temperature measuring values in °C)

Datasheet: T32.1S & T32.3S For pricing info, call 1-888-WIKA-USA or visit www.wika.com

Suggest Documents