PROJECT : L.G. HOSPITAL BY AMC , AHMEDABAD PRINCIPAL CONSULTANT : BHAVESH SHAH AND PRITI SHAH MGPS CONSULTANT : SHETH TECHNO CONSULTANTS PVT. LTD. VOLUME I - MEDICAL GAS PIPELINE SYSTEM BILL OF QUANTITY ESTIMATE SR. NO.
DESCRIPTION
UNIT
QTY
UNIT RATES IN RS.
Total Rs.
NOS. A Note : 1)The below mentioned prices are all inclusive of Design / Supply / Installation / Leak Testing / Comissioning of the Medical Gas Pipe Line System as per tender specification. And the scope coveres the Defact Liability Period of 36 Months , during this period all the routine and break down maintanance shall be carried out by the contractor at his own cost. The prices are inclusive of all taxes / duties / freight / site handling / lifting / shifting etc. 2) For L1 Consideration the weitage on Volume I shall be given 75% and on Volume II 25%.
1.0
SITC of OXYGEN SYSTEM AS PER TENDER SPECIFICATION
1.1
20 + 20 Bulk cylindcer Manifold for Oxygen complete with middle fram , bottom frame , NRV and Tail piece, The cylinder manifold should be as per ISO7396-1:2007certification and EN 737 / NFPA 99 C standard.
SET
1
350000
350000
1.2
1 x 4 Cylinder Emergency Oxygen System Supply through regulator having Non Halogenated polymer in high pressure side , The cylinder manifold should be as per ISO7396-1:2007certification and EN 737 / NFPA 99 C standard.
SET
1
85000
85000
1.3
Fully Automatic Control Panel for Oxygen with automatic change over facility as Per ISO-7396-1/2007 certification and EN 737 / NFPA 99 C standard. , Suitable for 2 Banks of Ox Cylinder and provision for connection to liq oxigen tank supply.
SET
1
450000
450000
2.0
SITC of NITROUS OXIDE SYSTEM
2.1
2 + 2 Bulk cyliner Manifold for Nitrous Oxide complete with middle fram, bottom frame , NRVs, Tail pipes. The cylinder manifold should be as per ISO7396-1:2007certification and EN 737 / NFPA 99 C standard.
SET
1
95000
95000
2.2
Nitrus Cylinder with regulator and trolly for ready to use in case of emergency. ( One for Ground Floor and 2nd for tenth floor )
SET
2
30000
60000
2.3
Fully Automatic Control Panel for N2O with Automatic Change over facility. The control panel should be as per ISO7396-1:2007certification and EN 737 / NFPA 99 C standard.
SET
1
430000
430000
3.0
SITC of VACCUM SYSTEM
3.1
SITC of Triplex Vaccum Pump System complete with High Efficiency Electric motor and starter , silencer , NRV , shut off ball valve , and all other required acessories as specified in the technical specifications. The system should be as per ISO7396-1:2007 certification and EN 737 / NFPA 99 C standard. 2 Working + 1 Stand By ( 100 % Stand by system ) Capacity :: 2500 LPM at 0.1 mbar ( 7.5 HP Apx. ) The system should be supplied with 3000 Ltr Common receiver tank.
SET
1
3500000
3500000
4.0
MEDICAL AIR AT 4 BAR
4.1
SITC Duplex Air Cooled screw compressor system complete with Air Drier , inlet filter , High Efficiency Electrical Motor ( 30 HP - Apx. Rating ) and Motor starter , pully, pressure reducing station for Both 4 Bar and 7 Bar and common 3000 ltrs air Receiver etc. 1 Working + 1 Stand By ( 100 % Stand by system ) Capacity :: 2500 LPM at 8 Bar Pressure
SET
1
7500000
7500000
4.2
3-stage breathing air Filtration System
SET
2
120000
240000
5.0
SITC of Double Locking Outlet Points as per ISO 9170-1/2008 certification and EN 737 / NFPA 99 C standard having CE mark
5.1
Oxygen Outlet Point
Set
168
5500
924000
MGPS TENDER DOCUMENT
BILL OF QUANTITY - VOL I
PROJECT : L.G. HOSPITAL BY AMC , AHMEDABAD PRINCIPAL CONSULTANT : BHAVESH SHAH AND PRITI SHAH MGPS CONSULTANT : SHETH TECHNO CONSULTANTS PVT. LTD. VOLUME I - MEDICAL GAS PIPELINE SYSTEM BILL OF QUANTITY ESTIMATE SR. NO.
DESCRIPTION
UNIT
QTY
UNIT RATES IN RS.
Total Rs.
5.2
Nitrous Outlet Point
Set
14
5500
77000
5.3
C-Air-4 bar Outlet Point
Set
46
5500
253000
5.4
C-Air-7 bar Outlet Point
Set
5
12500
62500
5.5
Vaccum outlet Point
Set
168
5500
924000
6.0
SITC of Distribution Copper Pipe - Lloyd Certified
6.1
76 mm OD - 1.5 mm Thickness
Rmt
123
4050
498150
6.2
54 mm OD - 1.2 mm Thickness
Rmt
5
2050
10250
6.3
42 mm OD - 1.2 mm Thickness
Rmt
369
1700
627300
6.4
35 mm OD - 1.2 mm Thickness
Rmt
820
1550
1271000
6.5
28 mm OD - 0.9 mm Thickness
Rmt
2322
855
1985310
6.6
22 mm OD - 0.9 mm Thickness
Rmt
1428.3
647
924110.1
6.7
15 mm OD - 0.9 mm Thickness
Rmt
2451
500
1225500
6.8
12 mm OD- 0.7 mm Thickness
Rmt
60
330
19800
7.0
SITC of Isolation Valve fully compliant to ISO7396-1:2007 certification and EN 737 / NFPA 99 C standard.
7.1
15 mm
SET
12
2800
33600
7.2
22 mm
SET
4
3200
12800
7.3
28 mm
SET
4
5000
20000
7.4
35 mm
SET
2
7400
14800
7.5
42 mm
SET
2
10000
20000
7.6
76 mm
SET
2
14000
28000
8.0
Area Valve Box with Valves, Pressure gauges & Nist connect fully compliant to ISO7396-1:2007 certification and EN 737 / NFPA 99 C
8.1
5 Gas Line Valve Box
SET
15
55000
825000
8.2
4 Gas Line Valve Box
SET
11
45000
495000
8.3
3 Gas Line Valve Box
SET
1
40000
40000
8.4
2 Gas Line Valve Box
SET
37
27500
1017500
9.0
BPC Flowmeter with Humidifier ( Oxygen Line )
SET
168
1600
268800
10.0
Ward Vaccum Unit with 600 ml Collection Jar
SET
168
4500
756000
11.0
Theatre Suction Unit
SET
14
8150
114100
12.0
Conversion Kit for O2
SET
13
4500
58500
13.0
Conversion Kit for N20
SET
13
4500
58500
14.0
HP AIS Tubing
MGPS TENDER DOCUMENT
BILL OF QUANTITY - VOL I
PROJECT : L.G. HOSPITAL BY AMC , AHMEDABAD PRINCIPAL CONSULTANT : BHAVESH SHAH AND PRITI SHAH MGPS CONSULTANT : SHETH TECHNO CONSULTANTS PVT. LTD. VOLUME I - MEDICAL GAS PIPELINE SYSTEM BILL OF QUANTITY ESTIMATE SR. NO.
DESCRIPTION
UNIT
QTY
UNIT RATES IN RS.
Total Rs.
14.1
White for oxygen
Mtrs
3
625
1875
14.2
Blue for N2O
Mtrs
3
625
1875
14.3
Black for Air
Mtrs
3
625
1875
14.4
Yellow for Vaccum
Mtrs
3
625
1875
15.0
High Quality Refined Rubber L P Tubing ( Vaccum Jar Connection )
Mtr
1050
200
210000
16.0
Area Alarm Panel at OT and ICU Floor having in built isolation valves comply to ISO 7396 - 1 : 2007 certification and EN 737 / NFPA 99 C standard.
16.1.1 5-gas
SET
2
175000
350000
16.2.2 3-gas
SET
4
130000
520000
16.2
Master Alarm Management System - 5 gas line - comply to ISO 7396 - 1 : 2007 certification and EN 737 / NFPA 99 C standard.
SET
1
1050000
1050000
17.1
SITC of Common Electrical Panel and cabling from electrical panel to compressed Air & Vaccum System complete with required foundation
SET
1
280000
280000
17.2
Supply, laying, connection, testing and commissioning of heavy duty medium voltage cables as per Specification and IS 7098 PART I XLPE insulated and outer sheeth of FRLS and inner PVC sheeth stranded AL conductor unless or otherwise specified. The copper cables shall be confirming to IS:1554, PVC insulated and sheathed, stranded copper conductors. The cable shall be laid underground when laid outside the building. It shall be laid in prepared trench / cable tray / wall clamped / duct when laid inside the building. The cable shall be laid with RCC Hume pipe at the entry of the building. The unit rate shall include
350
26250
90000
5220000
Delivery of the cable at site Loading, unloading and delivery of the cable at site store.(If applicable) Shifting of cable from site store to place of installation. Supply & fixing of cable G I clamps(With GI Screw) ,Nylon Tie, brackets, supports, route markers etc. where ever required to fix the cables safely. Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. Excavation, back filling and leveling of ground along with supply & laying of fine sand, protection bricks and other necessary civil material for laying cables outside the building. Testing of insulation and continuity of cable and submission of reports to the client's representative. 17.2.1 3.5 c x 70 sq. mm. Al. XLPE cable 18.0
19 19.1
MTR
Horizontal Bed Head Panels for ICU/ICCU as per specification , the out let shall comply to out let point summary. The Bed Head Panel should comply to ISO 11197-2004 certification and EN 737 / NFPA 99 C standard. CIVIL WORK
Floating Foundation for MGPS equipment
MGPS TENDER DOCUMENT
BILL OF QUANTITY - VOL I
SET
75 58
PROJECT : L.G. HOSPITAL BY AMC , AHMEDABAD PRINCIPAL CONSULTANT : BHAVESH SHAH AND PRITI SHAH MGPS CONSULTANT : SHETH TECHNO CONSULTANTS PVT. LTD. VOLUME I - MEDICAL GAS PIPELINE SYSTEM BILL OF QUANTITY ESTIMATE SR. NO.
DESCRIPTION
UNIT
QTY
UNIT RATES IN RS.
Total Rs.
Lot
1
21500
21500
Lot
1
21500
21500
providing & laying ordinary cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregates 20 mm nominal size) and finishing smooth with curing etc.complete including the cost of form work but excluding the cost of reinforcement for R.C.C. work. The same shall be layed on rubber lining of 50mm thickness 19.1.1 Floundation for Air Compressors ( 2 Compressors ) / Receiver Tank / Air Dryer / Related Piping etc 19.1.2 Floundation for Vaccum Pumps ( 3 Pumps ) / Receiver Tank / Related Piping etc 19.2
Core cutting in RCC members of any dia ( Not more then 3") , Complete with cutting , finishing , sealing and painting
Set
36
1250
45000
19.3
Hole cutting in Brick Wall members of any dia ( Not more then 6 ") Complete with cutting , finishing , sealing and painting
Set
48
450
21600
19.4
Hole cutting in Aluminium/glass partition members of any dia ( Not more then 6 ") Complete with cutting , finishing , sealing
Set
36
1250
45000
19.5
Providing and fixing Polycarbonate roof sheets (double layer or two skin) of approved make, on structural roofing / sky light structures in shapes as per Architect’s drawing. The rate shall include cost of scaffolding, screws, nuts, bolts and all necessary fixtures and fastening etc. complete.
Sqm
50
2650
132500
19.6
Providing and fixing M.S.hollow structural steel section like SHR, RHS, tubes etc. or as suggested in contractors's drawing including of all labours and materials for all levels Profile Cutting,threading,drilling, Nut-Bolting, Welding and applying Rust remover and 1-coats of Zinc Chromate / red lead paint and three or more coats of synthetic enamel paint of approved shade and made (“Asian or Tata or" equi.) as directed and specified as directed by Architect / Clerk-Of-Work. For all levels, lift and leads.
Sqm
50
1050
52500
19.7
Cylinder Manifold Area RCC plat form with suitable foundation design required to handle cylinder loading worst case. The heigh of the plat form should be apx. 1.2 Mtr for easy loading / unloading of the cylinders , the scope includes the rainforcement required for the strength and stability of the plat form.
Sqm
50
2250
112500
19.8
MS Fabrication Job - Mainly for working plat form at each floor level in the service shaft
Kgs
1250
65
81250
GRAND TOTAL FOR MGPS SYSTEM INSTALLATION
33,471,620.10
Rs. Three Cror Thirty Four Lacs Seventy One Thousand Six Hundred Twenty only ( For Vol I) Note : 1)The above prices are all inclusive of Design / Supply / Installation / Leak Testing / Comissioning of the Medical Gas Pipe Line System as per tender specification. And the scope coveres the Defact Liability Period of 36 Months , during this period all the routine and break down maintanance shall be carried out by the contractor at his own cost. 2) For L1 Consideration the weitage on Volume I shall be given 75% and on Volume II 25%.
MGPS TENDER DOCUMENT
BILL OF QUANTITY - VOL I
PROJECT : L.G. HOSPITAL BY AMC , AHMEDABAD PRINCIPAL CONSULTANT : BHAVESH SHAH AND PRITI SHAH MGPS CONSULTANT : SHETH TECHNO CONSULTANTS PVT. LTD. VOLUME I - MEDICAL GAS PIPELINE SYSTEM BILL OF QUANTITY ESTIMATE SR. NO.
DESCRIPTION
UNIT
QTY
UNIT RATES IN RS.
Total Rs.
I / We am/are willing to carry out the work at ___________% above / below ( Should be written in figures and words ) the estimated cost mentioned above for Volume 1. The amount of my/our tender works out as under. Estimated Cost Put to Tender : Rs. 3,34,71,620/- ( For Vol I ) Add/Deduct ________ % : Rs. __________ Net Total : Rs. __________ In Words Rs. ( For Vol I ) ____________________________________________________________________________________ Signature of Tenderer :
Additional City Engineer - Bridge Project Ahmedabad Municipal Corporation
Name Company Seal Date
MGPS TENDER DOCUMENT
Date
BILL OF QUANTITY - VOL I