Tile Steam Room and Steam Shower Technical Design Manual

Corporate Headquarters: LATICRETE International, Inc.

Eastern Europe: +790.9661.1644 India: +91.40.3041.3100 Latin America: +1.203.393.0010 Middle East: +971.7.244.6396 South East Asia: +65.6515.3028

DS–125.0–1109 ©2009 LATICRETE International, Inc. LATICRETE, LATAPOXY, SPECTRALOCK and the

LATICRETE Technical Services Department

Europe: +34.96.649.1908

logo are Registered Trademarks of LATICRETE International, Inc.

Microban is a registered trademark of Microban Products Company. Kevlar is a registered trademark of Dupont Products Company. GREENGUARD Indoor Air Quality Certified® Product.

9

©2009 LATICRETE International, Inc. All rights reserved. No part of this publication (except for previously published articles and industry references) may be reproduced or transmitted in any form or by any means, electronic or mechanical, without the written permission of LATICRETE International, Inc. The information and recommendations contained herein are based on the experience of the author and LATICRETE International, Inc. While we believe the information presented in these documents to be correct, LATICRETE International, Inc. and its employees assume no responsibility for its accuracy or for the opinions expressed herein. The information contained in this publication should not be used or relied upon for any specific application or project without competent examination by qualified professionals and verification of its accuracy, suitability, and applicability. Users of information from this publication assume all liability arising from such use. Tile Steam Room and Steam Shower Technical Design Manual ©2009 LATICRETE International, Inc.

Tiled Steam Room and Steam Shower Technical Design Manual LATICRETE Technical Services

Tiled Steam Room and Steam Shower – Technical Design Manual

1

2

Tiled Steam Room and Steam Shower – Technical Design Manual

Table of Contents Preface..................................................................................................................................................5 Section 1: Introduction 1.1 Steam Room Facts......................................................................................................................9

1.2 Tile Installations in Steam Rooms – Materials and Methods....................................................9



1.3 Summary . ................................................................................................................................13

Section 2: Specification for Steam Room – Full Mortar Bed Method Detail ES-SR613..............................................................................................................................16

General Information.......................................................................................................................17



Products........................................................................................................................................ 24



Execution Statement..................................................................................................................... 27



Health and Safety.......................................................................................................................... 34

Section 3: Specification for Steam Room – Thin Bed Method Detail ES-SR614............................................................................................................................. 36

General Information...................................................................................................................... 37



Products........................................................................................................................................ 43



Execution Statement..................................................................................................................... 46



Health and Safety.......................................................................................................................... 54

Section 4: Steam Room Detail Drawings...................................................................................... 4.1 ES-SR613 – Steam Room – Full Mortar Bed with Waterproofing........................................... 56

4.2 ES-SR614 – Steam Room – Thin Bed Method with Waterproofing........................................ 57



4.3 ES-SR614B – Steam Room – Cement Backer Board – Vapor Barrier Placement................... 58



4.4 ES-P605 – Pool/Fountain/Steam Room Penetration............................................................ 59



4.5 WP-SR302 – Steam Room Drain Detail.................................................................................. 60

Section 5: Maintenance and Protection....................................................................................... 5.1 Quality Assurance.................................................................................................................... 62

5.2 Preventative and Corrective Maintenance............................................................................. 63



5.3 Protection and Sealing............................................................................................................ 64



5.4 Case Study – Full Mortar Bed Steam Room........................................................................... 65

Section 6: Appendix............................................................................................................................. 6.1 Steam Room Frequently Asked Questions............................................................................. 78

6.2 Resource Guide – Trade Organizations and Technical Resources......................................... 80



6.3 Glossary................................................................................................................................... 82

Tiled Steam Room and Steam Shower – Technical Design Manual

3

4

Tiled Steam Room and Steam Shower – Technical Design Manual

Preface

LATICRETE International, Inc., a world leader in the manufacturing of ceramic tile and stone installation systems, has long recognized the need for a technical design manual to provide guidelines and recommendations for the design, specification and installation of tile and stone in steam room/steam shower applications. Improved technology in steam room construction and equipment has made steam rooms and steam showers readily available to anyone. In keeping with our position as an industry leader, LATICRETE International is publishing this Tiled Steam Room and Steam Shower Technical Design Manual to provide information and guidelines to architects, design professionals, construction professionals, tile installation professionals, and the tile and stone distribution industry. It is the goal of this manual to provide the necessary information to help ensure a proper and long-lasting tile installation in a steam room or steam shower environment.

Tiled Steam Room and Steam Shower – Technical Design Manual

5

6

Tiled Steam Room and Steam Shower – Technical Design Manual

Section 1: Introduction

Tiled Steam Room and Steam Shower – Technical Design Manual

7

8

Tiled Steam Room and Steam Shower – Technical Design Manual

Section 1: Introduction 1.1 Steam Room Facts Who wouldn’t like to have a steam bath or steam shower in their own home? Steam provides an invigorating way to maintain or restore physical and mental health. Sitting in a steam room environment can help the body to burn calories, improve circulation, relax muscles, flush toxins from the body, cleanse pores, relieve stress, and help induce more relaxing sleep. All of this in just twenty minutes a day! The fact is; steam rooms and steam showers are becoming more and more common in home environments. They are no longer just for health clubs or the very wealthy; now anybody can own their own steam room. Steam room and steam showers are fairly often included in new home construction, rather than a standard shower. While there are many benefits to owning and using a steam room or steam shower there are also some basic principles that must be kept in mind when designing, installing and using these units: 1. Prevent steam from escaping.

9235 Waterproofing Membrane. Tile is the perfect finish for a steam room application and choosing the right tile is important. For best results, the tile should be impervious (i.e. porcelain) or have a glazed surface to help limit the amount of moisture and moisture vapor that makes its way into the system. An acceptable vapor barrier can be a vital component of any steam room and, when properly installed, can prevent moisture from getting into wall and ceiling cavities. When hot, moist air comes in contact with cooler surfaces (at or below dew point) it condenses and turns back into water. If the dew point temperature is within the wall cavity then the moisture will either build up within the wall or show up in areas where water is not supposed to be found. This can lead to structural damage, mold, water problems, poor indoor air quality, and more. In order to function properly it is critical that this vapor barrier laps into the shower pan (another critical component of a steam room installation).

2. Collect any condensed water and allow it to drain properly.

1.2 Tile Installations in Steam Room and Shower Applications Materials and Methods

3. Keep  water from dripping on the steam room occupants.

Let’s look at two typical steam room constructs:

Steam generation units create a great deal of moisture; this moisture initially takes the form of water vapor (steam). This water vapor is highly penetrative and any room not properly prepared may be exposed to damage caused by excessive moisture. Proper measures must be taken to prevent moisture transgression into or through walls, ceiling and floor.

1. The first design incorporates steel or wood framing and a concrete, slab-on-grade sub-floor. The ceiling should be sloped at least 2" minimum per foot (50 mm per 300 mm) to prevent water from dripping on steam room occupants (per Tile Council of North America recommendations). The floor should be pre-pitched (prior to the installation of the shower pan liner) at the rate of 1/4" per foot (6 mm per 300 mm) to make sure that water flows toward the drain. Keep in mind that a shower pan is required in all steam room/steam shower installations!

These preventive measures include a properly placed, suitable vapor barrier and/or an acceptable waterproofing membrane. LATICRETE International, Inc. always recommends using both a vapor barrier, placed on the framing or on the concrete/concrete masonry units prior to further construction, and LATICRETE® Hydro Ban™ or LATICRETE

Tiled Steam Room and Steam Shower – Technical Design Manual

9

Heading1:Here Section Introduction The installation begins with the proper choice and placement of a two-part clamping-ringstyle drain with weepers as per ASME A112.6.3. Place tile spacers or gravel around weep holes, as detailed by the design professional, to prevent mortar from clogging the weep holes and should be installed by a qualified plumber in accord with International Residential Code (IRC) P2709.4. The pipes and drain should be properly supported to prevent problems in the future. A suitable primary shower pan liner, complying with ASTM D 4068, D 4551 or other International Code Council (ICC) and International Association of Plumbing and Mechanical Officers (IAPMO) approved material, would then be installed to tie into the bottom flange of the drain (without blocking the weep holes). The liner must be turned up the walls to a point at least 3" (75 mm) above the top of the curb or 6" (150 mm) above the floor in steam rooms or steam showers without curbs. The shower pan must be properly formed and fastened to prevent problems. Check with local building code to help determine what shower pan liner is acceptable in your area. This pan will act as your vapor barrier on the floor. Curbs must be sloped to drain back into the steam room for condensation runoff. Perform a flood test to determine integrity of the pan liner and make repairs as necessary before proceeding. After the shower pan liner is in place, install the vapor barrier directly onto the side of the wall and ceiling framing that will be exposed to the steam room. The vapor barrier should be 4 – 6 mil thick polyethylene (cross laminated virgin polyethylene is excellent) and, if possible, should be one piece that can fit into the entire area. Fasten the vapor barrier to the studs with corrosion-resistant fasteners. A spot of LATICRETE® Latasil™ (100% silicone sealant) onto the fasteners will help prevent moisture penetration through the fastener holes. Make sure that the vapor barrier is properly formed and is tight to the studs of the walls and ceiling. Yes – the vapor barrier 10

must be installed onto the ceiling as well as the walls because steam can certainly escape through the ceiling. It is imperative that this vapor barrier be placed so that it laps into the shower pan liner! This way any moisture that comes in contact with the vapor barrier will drain into the shower pan and through the weep holes of the drain. Next, install a 2" (50 mm) thick (minimum) wire-reinforced, mortar bed comprised of LATICRETE 3701 Fortified Mortar Bed; or, LATICRETE 226 Thick Bed Mortar gauged with LATICRETE 3701 Mortar Admix onto the shower floor. The wire-reinforcement should be 2" x 2" (50 mm x 50 mm), 16 gauge, galvanized, welded wire mesh and should be placed at half the depth of the mortar bed. Make sure that the mortar bed maintains the 1/4" per foot (6 mm per 300 mm) slope to drain which was established by the pre-pitch in the sub-floor. After the mortar bed has cured, the installation of the cement backer board on the walls and ceiling can begin. The addition of a suitable insulation material between the wall and ceiling framing should be done before installation of the cement backer board. Insulation will help keep the heat in the steam room, cool air out, and helps to control the dew point (the temperature where condensation takes place) within the wall. The cement backer board used must be acceptable for steam room use and installed per the board manufacturer’s written installation instructions; this includes taping of all board joints. Use LATICRETE 254 Platinum and 2" (50 mm) wide, alkaliresistant fiberglass mesh tape to treat the board joints. Be sure to allow space at the ceiling/wall transition for the insertion of a slip joint to allow for proper expansion/ contraction to take place. Pipes and penetrations through board should be accounted for and space between board and penetration should be kept to a minimum. Allow the mortar used to tape the board joints to harden and then commence with

Tiled Steam Room and Steam Shower – Technical Design Manual

Section 1: Introduction waterproofing the entire inside area of the steam room with LATICRETE Hydro Ban™ or LATICRETE 9235 Waterproofing Membrane. The entire steam room should be waterproofed, including the ceiling, walls, floor, seat, and any other exposed area; this will help improve the functionality of the vapor barrier and inhibit the passage of most of the moisture through the system. Loop the LATICRETE Hydro Ban or LATICRETE 9235 Waterproofing Membrane into the slip joints to allow for movement in these areas. Any vapor transpiring through the LATICRETE 9235 Waterproofing Membrane should easily be handled by the vapor barrier. For more information on the installation of LATICRETE Hydro Ban or LATICRETE 9235 Waterproofing Membrane, please refer to www.laticrete.com. Make sure that ANY and ALL penetrations are properly waterproofed and sealed tightly with LATICRETE Latasil! Tile can be installed directly onto the LATICRETE Hydro Ban or LATICRETE 9235 Waterproofing Membrane as soon as it is dry to the touch. LATICRETE 254 Platinum is the thin-set of choice for steam room/ steam shower installations. Check with the manufacturer of the tile to make sure that it is compatible in steam room applications.

2. The second design involves installation over all other substrates including concrete or masonry walls. Again, the ceiling should be sloped at least 2" minimum per foot (50 mm per 300 mm) to prevent water from dripping on steam room occupants (per Tile Council of North America recommendations). The floor should be pre-pitched (prior to the installation of the shower pan) at the rate of 1/4" per foot (6 mm per 300 mm) to make sure that water flows toward the drain. Also, a shower pan is required in ALL steam room/steam shower installations! The installation begins with the proper choice and placement of a two-part clamping ring style drains with weepers as per ASME A112.6.3. Place tile spacers or gravel around weep holes, as detailed by the design professional, to prevent mortar from clogging the weep holes, they should be installed by a qualified plumber in accord with IRC P2709.4. The pipes and drain should be properly supported to prevent problems in the future. For this type of steam room construction, LATICRETE Hydro Ban or LATICRETE 9235 Waterproofing Membrane can be used as the primary shower pan liner. A suitable primary shower pan liner material, complying with

Once the tiles have set firm, grout the installation with LATICRETE SpectraLOCK®† PRO Grout for best performance. Alternative grouting choices would be LATICRETE PermaColor™ Grout^. Use LATICRETE Latasil, with LATICRETE 9118 Primer, in slip joints, steam jets, movement joints, around the drain, to seal lighting fixtures, access panels (if present), or at any change of plane. The use of LATICRETE SpectraLOCK PRO Grout will add to the performance of the tile installation because it has an absorption rate of 265 psi (1.8 MPa) 5. 7 day Shear Bond Strength (ANSI A118.10) >200 psi (1.4 MPa) 6. 28 Day Shear Bond Strength (ANSI A118.4): >214 psi (1.48 – 2.4 MPa) 7. Service Rating (TCA/ASTM C627): Extra Heavy 8. Total VOC Content: < 0.05 mg/m3 B. Epoxy Waterproofing Membrane to be 3 component epoxy, trowel applied specifically designed to be used under ceramic tile, stone or brick and requires only 24 hours prior to flood testing: 1. Breaking Strength (ANSI A118.10): 450 – 530 psi (3.1-3.6 MPa) 2. Waterproofness (ANSI A118.10): No Water penetration 3. 7 day Shear Bond Strength (ANSI A118.10): 110 – 150 psi (0.8 – 1 MPa) 4. 28 Day Shear Bond Strength (ANSI A118.10): 90 – 120 psi (0.6 – 0.83 MPa) 5. 12 Week Shear Bond Strength (ANSI A118.10): 110 – 130 psi (0.8 – 0.9 MPa) 6. Total VOC Content: 214 – 343 psi (1.48 – 2.4 MPa) 6. S  ervice Rating (TCA/ASTM C627): Extra Heavy 7. Total VOC Content: < 0.05 mg/m3

NOTE TO SPECIFIER: Edit applicable tile installation accessories.

2.6 Performance Specification – Tile Installation Materials A. Sound Abatement and Crack Isolation Mat shall be load bearing, shock and vibration resistant. It shall be certified by independent laboratory testing to meet the specified acoustical performance when installed in a Floor Assembly with a 6" (150 mm) concrete slab, as well as meet the following physical requirements: 1. Service Rating (ASTM C627): Light 2. Point Load (ANSI A118.12-5.2): >1250 psi (8.6 MPa) 3. Installed Weight (ASTM C905 Modified): 2.6 lbs/ft2 (12.8 kg/m2) 4. Delta Impact Insulation Class (ΔIIC; ASTM E2179): 20 B. Sound Abatement and Crack Suppression Adhesive shall comply with ANSI A118.12, provide an Extra Heavy rating and provide a minimum ΔIIC of 15:

D. Wire Reinforcing: 2" x 2" (50 x 50 mm) x 16 ASW gauge or 0.0625" (1.6 mm) diameter galvanized steel welded wire mesh complying with ANSI A108.02 3.7, ASTM A185 and ASTM A82.

1. Service Rating (ASTM C627): Extra Heavy

E. Cleavage membrane: 15 pound asphalt saturated, non-perforated roofing felt complying with ASTM D226, 15 pound coal tar saturated, non-perforated roofing felt complying with ASTM D227 or 4.0 mils (0.1 mm) thick polyethylene plastic film complying with ASTM D4397.

4. Minimum Shear Bond Strength (ANSI A118.12): 100psi (0.7 MPa)

F. C  ementitious backer board units: size and thickness as specified, complying with ANSI A118.9. G. Thresholds: Provide marble saddles complying with ASTM C241 for abrasion resistance and ASTM C503 for exterior use, in color, size, shape and thickness as indicated on drawings.

2. Delta Impact Insulation Class (ΔIIC; ASTM E2179): 15 3. Point Load (ANSI A118.12 5.2): >1000 psi (6.9 MPa)

C. Moisture Vapor Reduction to be epoxy based and GreenGuard compliant as well as meet the following physical requirements: 1. Shear Bond to Concrete (ANSI A118.12 – 5.1.5): >285 psi (2.0 MPa) 2. Alkalinity Resistance (ASTM C267): Pass 3. Permeability (ASTM F1869): 9.7 lbs/1,000 ft2/ 24 hours down to 0.2 lbs/1,000 ft2/24 hours (248 µg/s•m2 down to 11 µg/s•m2)

Tiled Steam Room and Steam Shower – Technical Design Manual

25

Section 2: Part 2 – Products D. Latex Portland Cement Mortar for thick beds, screeds, leveling beds and scratch/ plaster coats to be weather, frost, shock resistant and meet the following physical requirements: 1. C  ompressive Strength (ANSI A118.4 Modified): >4000 psi (27.6 MPa) 2. Water Absorption (ANSI A118.6): ≤ 5% 3. S  ervice Rating (TCA/ASTM C627): Extra Heavy 4. Smoke and Flame Contribution (ASTM E84 Modified): 0 5. Total VOC Content: < 0.05 mg/m3 E. Self-Leveling Underlayment shall be mixed with water to produce a pumpable, fast setting, free flowing cementitious underlayment which can be poured from a feather-edge to 1-1/2" (38 mm) thick in one pour. 1. 4 Hour Compressive Strength (ANSI A118.4 Mod.): >1500 psi (10.3 MPa)

7. Cured Epoxy Adhesive to be chemically and stain resistant to ketchup, mustard, tea, coffee, milk, soda, beer, wine, bleach (5% solution), ammonia, juices, vegetable oil, detergents, brine, sugar, cosmetics and blood, as well as chemically resistant to dilute food acids, dilute alkalis, gasoline, turpentine and mineral spirits. G. L atex Portland Cement Thin Bed Mortar for thin set and slurry bond coats to be weather, frost, shock resistant, non-flammable and meet the following physical requirements: 1. Compressive strength (ANSI A118.4): >2500 psi (17.2 MPa) 2. Bond strength (ANSI A118.4): >450 psi (3.1 MPa) 3. Smoke and Flame Contribution (ASTM E84 Modified): 0 4. Total VOC Content: 2800 psi (19.3 MPa)

H. Organic Adhesive shall be non-flammable, water resistant, latex adhesive and shall meet the following physical requirements:

3. 2  8 Day Compressive Strength (ANSI A118.4 Mod.): >4300 psi (29.7 MPa)

1. Open Time (ANSI A136.1): 70 minutes at 75°F (24°C)

4. Tensile Strength (ANSI A118.7): >500 psi (3.5 MPa)

2. Color: White

5. Time To Foot Traffic: 3 – 4 Hours 6. Total VOC Content: 5000 psi (34.4 MPa) 2. S  hear Bond Strength (ANSI A118.3): >1250 psi (8.6 MPa) 3. Thermal Shock Resistance (ANSI A118.3): >600 psi (4.1 MPa) 4. Tensile Strength (ANSI A118.3): >1400 psi (9.6 MPa) 5. Shrinkage (ANSI A118.3): 0 – 0.1% 26

6. Total VOC Content: 8" x 8"/200 mm x 200 mm) tile/stone, rib/button/lug back tiles, pavers or sheet mounted ceramics/mosaics, spread latex portland cement mortar onto the back of (i.e. ‘back-butter’) each piece/sheet in addition to trowelling latex portland cement mortar over the substrate. Beat each piece/sheet into the latex portland cement mortar with a beating block or rubber mallet to insure full bedding and flatness. Allow installation to set until firm. Clean excess latex portland cement mortar from tile or stone face and joints between pieces. Use the following LATICRETE System Materials LATICRETE 254 Platinum References LATICRETE Data Sheet: 677.0 LATICRETE MSDS: 254 GREENGUARD Certificate: 254 LATICRETE Technical Data Sheets: 105, 118, 199, 209 F. Grouting or Pointing: NOTE TO SPECIFIER: Select one of following and specify color for each type/color of ceramic tile, mosaic, paver, trim unit:

32

Tiled Steam Room and Steam Shower – Technical Design Manual

Section 2: Part 3 – Execution Statement 1. C  hemical Resistant, Water Cleanable TileGrouting Epoxy (ANSI A118.3): Follow manufacturer‘s recommendations for minimum cure time prior to grouting. Store liquid components of LATICRETE SpectraLOCK® PRO Grout† for 24 hours at 70 – 80°F (21 – 27°C) prior to use to facilitate mixing and application. Substrate temperature must be 40 – 95°F (4 – 35°C). Verify joints are free of dirt, debris or grout spacers. Sponge or wipe dust/dirt off tile faces and remove water standing in joints. Apply grout release to face of absorptive, abrasive, non-slip or rough textured ceramic tile, pavers, bricks, stone or trim units that are not hot paraffin coated to facilitate cleaning. Cut open pouch and pour LATICRETE SpectraLOCK PRO Grout Part A Liquid into a clean mixing pail. Then open pouch and pour LATICRETE SpectraLOCK PRO Grout Part B Liquid into the mixing pail. Mix by hand or with a slow speed (200 psi (1.4 MPa)

NOTE TO SPECIFIER: Edit for each tile type.

6. 28 Day Shear Bond Strength (ANSI A118.4): >214 psi (1.48 – 2.4 MPa)

A. Ceramic Tile B. Grade:

7.Service Rating Extra Heavy

C. Size: D. Edge F. Color G. Special shapes H. Location:

2.4 Ceramic Tile Installation Materials Manufacturer A. L ATICRETE International, Inc., 1 Laticrete Park North, Bethany, CT 06524-3423 USA Phone +1.800.243.4788, +1.203.393.0010 [email protected], www.laticrete.com; www.laticrete.com/green NOTE TO SPECIFIER: Use either the following performance specification or the proprietary specification.

2.5 Performance Specification –Tile Installation Accessories

1. Hydrostatic Test (ASTM D4068): Pass at

break

(ASTM

B. Epoxy Waterproofing Membrane to be 3 component epoxy, trowel applied specifically designed to be used under ceramic tile, stone or brick and requires only 24 hours prior to flood testing: 1. B  reaking Strength (ANSI A118.10): 450– 530 psi (3.1–3.6 MPa) 2. Waterproofness (ANSI A118.10): No Water penetration 3. 7 day Shear Bond Strength (ANSI A118.10): 110–150 psi (0.8–1 MPa) 4. 28 Day Shear Bond Strength (ANSI A118.10): 90–120 psi (0.6–0.83 MPa) 5. 12 Week Shear Bond Strength (ANSI A118.10): 110–130 psi (0.8–0.9 MPa) 6. Total VOC Content: 265 psi (1.8 MPa)

46

C627):

8. Total VOC Content: 214 – 343 psi (1.48 – 2.4 MPa) 6. Service Rating Extra Heavy

(TCA/ASTM

C627):

7. Total VOC Content: 1250 psi (8.6 MPa) 3. Installed Weight (ASTM C905 Modified): 2.6 lbs/ft2 (12.8 kg/m2)

4. Delta Impact Insulation Class (ΔIIC; ASTM E2179): 20 B. Sound Abatement and Crack Suppression Adhesive shall comply with ANSI A118.12, provide an Extra Heavy rating and provide a minimum ΔIIC of 15: 1. Service Rating (ASTM C627): Extra Heavy 2. Delta Impact Insulation Class (ΔIIC; ASTM E2179): 15 3. Point Load (ANSI A118.12 5.2): >1000 psi (6.9 MPa) 4. Minimum Shear Bond Strength (ANSI A118.12): 100psi (0.7 MPa) C. Moisture Vapor Reduction to be epoxy based and GreenGuard compliant as well as meet the following physical requirements: 1. Shear Bond to Concrete (ANSI A118.12– 5.1.5): >285 psi (2.0 MPa) 2. Alkalinity Resistance (ASTM C267): Pass 3. Permeability (ASTM F1869): 9.7 lbs/1,000 ft2/24 hours down to 0.2 lbs/1,000 ft2/24 hours (248 µg/s•m2 down to 11 µg/s•m2) D. Latex Portland Cement Mortar for thick beds, screeds, leveling beds and scratch/ plaster coats to be weather, frost, shock resistant and meet the following physical requirements: 1. Compressive Strength (ANSI Modified): >4000 psi (27.6 MPa)

A118.4

2. Water Absorption (ANSI A118.6): ≤ 5% 3. S  ervice Rating (TCA/ASTM C627): Extra Heavy 4. Smoke and Flame Contribution (ASTM E84 Modified): 0 5. Total VOC Content: