Solar Panel Expansion Tank Sizing: Getting It Right – Part I The most common type of solar thermal system uses a closed piping loop between the colle...
Author: Vernon Webster
4 downloads 0 Views 951KB Size
Solar Panel

Expansion Tank Sizing: Getting It Right – Part I The most common type of solar thermal system uses a closed piping loop between the collector array and storage tank heat exchanger. BY John Siegenthaler

STAGNATION Under normal operating conditions the collector fluid seldom reaches temperatures in excess of 200F. However, during its service life, almost every solar thermal system will experience stagnation conditions, where bright sunshine strikes the collectors without flow through the absorber plates. This can be caused by several factors including: » loss of electrical power during the day; » failure of a controller or sensor; » the thermal storage tank reaching its maximum allowed temperature; and » during installation before the system is put into operation. Solar collectors rated to the OG-100 standard established by the Solar Rating and Certification Corporation 60

HPAC | APRIL 2009

(SRCC) (solar-rating.org) must undergo 30-day stagnation tests. During this time collectors are subjected to 30 consecutive days where total daily solar radiation is at least 1,500 Btu/ft2/day in the plane of the collector and at least one four-hour period with a minimum solar intensity of 300 Btuh/ft2. The average ambient temperature during this fourhour severe stagnation period must be at least 80F. After this exposure, collectors are visually inspected for any indication of insulation outgassing, pealing or flaking of the absorber coating, or other signs of degradation. Evidence of such degradation would disqualify the collector for the OG-100 certification. The temperature the collector’s absorber plate reaches during stagnation is determined based on: the collector’s

Figure 1 Y-intercept =0.76

1 0.9 collector thermal efficiency (decimal %)

T

his loop is filled with an antifreeze solution such as a 40 per cent solution of propylene glycol. As in any closed hydronic circuit, the fluid expands when heated. To avoid excessively high pressure, an expansion tank must accommodate the increase in volume. The sizing of this tank is similar, yet different, from sizing an expansion tank in a typical hydronic heating system. Determining the size of this tank requires knowledge of how hot the solar collector circuit can become. That subject is analyzed here. Part II of this discussion will appear in an upcoming Solar Panel column and uses this information to size the expansion tank.

0.8 0.7 0.6 slope = (0.76/0.93) = 0.817

0.5 0.4 0.3 0.2 0.1 0 0

0.1

0.2 0.3

0.4 0.5

Inlet fluid parameter

0.6 0.7 0.8 0.9 2  Ti − Ta   º F ⋅ ft ⋅ hr      Btu   I  

1

1.1

hpacmag.com

“This temperature probably surprises some of you. It is high enough to melt 50/50 tin/lead solder.” efficiency graph, assumptions about the solar intensity and ambient air temperature at stagnation conditions. An example of a typical efficiency graph for a flat plate collector is shown in Figure 1. Two numbers describe the straight line on this graph: the Y-intercept and the slope. For the collector represented in Figure 1, the Y-intercept is 0.76. The slope is the change in vertical distance divided by the change in horizontal distance. In Figure 1, this is 0.76 divided by 0.93, which equals 0.817. The Y-intercept and slope numbers are determined by testing and are listed for many specific collectors at SRCC’s web site. During stagnation, there is no fluid flow to extract heat from the collector’s absorber plate. The absorber plate’s temperature will climb until the heat loss from the collector housing matches the rate of incoming solar energy. This temperature can be estimated using Formula 1.

Formula 1:

Tstag=

(Y – intercept) I + Tair (Slope)

Where: (Y – intercept) TTstag = = stagnation temperature=of 0.76 the absorber (F) 317 + 85plate = 380F I + Tair stag 0.817 (Slope) Y – intercept = value where the collector’s efficiency line touches the vertical axis Slope = numerical slope of the efficiency line (Btu/ºF/ft2/hr) I = intensity of solar radiation striking the collector (Btu/hr/ft2) Tair = ambient air temperature around the collector (F) Here is an example: Assume it is a nice bright summer day, and a power outage occurs in the early afternoon. The solar radiation intensity is 1,000 watts per square metre, hpacmag.com

which converts to 317 Btuh/ft2. The outdoor air temperature is 85F. Under these conditions the absorber plate (Y – intercept) in the by Figure 1 (e.g. Y-intercept Tstag = collector represented I+T = 0.76 and(Slope) slope = 0.817)airwould reach a stagnation temperature of:

Tstag=

(Y – intercept) 0.76 317 + 85 = 380F I + Tair = 0.817 (Slope)

This temperature probably surprises some of you. It is high enough to melt 50/50 tin/lead solder. It is also well above the temperature at which the fluid in the collector will remain a liquid. As vapourization of the collector fluid begins, the remaining liquid in the collector gets pushed out into the rest of the piping circuit. A properly-sized expansion tank will accommodate this volume, as well as the expanded volume of the fluid that does not vapourize elsewhere in the loop, so that the pressure relief valve on the circuit does not open. The details of calculating the proper size expansion tank will be discussed in Part II. John Siegenthaler, P.E. is the author of Modern Hydronic Heating. Visit hydronicpros.com for reference information and software to assist in hydronic system design. He can be reached at [email protected].

See John Siegenthaler at the Foothills Conference and Trade Show. Be sure to stop by and visit HPAC at Booth 32

APRIL 2009 | HPAC

61

Solar Panel

Expansion Tank Sizing for Solar Collector Circuits – Part II In Part I (April 2009) we calculated the temperature that the absorber plate in a solar collector could reach under stagnation conditions. BY John Siegenthaler

Figure 1

ABSOLUTE PRESSURE AND BOILING POINT–THE RELATIONSHIP

SELECTING THE PRV Before calculating the volume of the expansion tank it is necessary to know the rated opening pressure of the system’s pressure relief valve. Start by checking local codes to see if they mandate a maximum pressure relief valve setting in solar thermal systems. If this is the case, the code mandated rating is obviously the benchmark. If there are no code restrictions on the rating of the collector circuit pressure relief valve, I suggest it be determined by assuming a cold fill static pressure of 25 psi at the top of the collector array, and calculating the corresponding pressure at the relief valve location. Then, pick a relief valve setting 15 to 20 psi above this pressure. Use Formula 1 to determine the static pressure at the relief valve location. See Figure 2 for the corresponding terms and dimensions.

Formula 1:

P@PRV = P@top +

( (

64.9 H 144

Where: 64.9 64.9 fill = pressure relief valve P@PRV = static cold P@PRV P@top + at pressure H = 25 + 144 144 location (psi)

(

continued on page 24

HPAC | MAY/JUNE 2009

P@top = PPRVrated –

( (

64.9 H 144 hpacmag.com

( (

22

P@top = PPRVrated –

20 = 34 psi

(

64.9 64.9 20 = 41 ps H = 50 – 144 144

(

Figure 1 shows the relationship between absolute pressure and boiling point for a 40 per cent solution of propylene glycol. This is the fluid used in the collector circuit of many closed-loop solar thermal systems. To maintain this solution as a liquid at a stagnation temperature of 350F would require an absolute pressure of about 118 psi (corresponding to a gauge pressure of about 103 psi) in the solar collectors. This is not practical and

(

WHEN BOILING OCCURS

may even violate some mechanical codes that require the pressure in the collector circuit to be no greater than the pressure of the domestic water. We cannot count on pressurization to suppress boiling under maximum stagnation conditions, therefore there will be times when the fluid in the collector will vapourize. Under these conditions the liquid in the piping leading to and from the collector array could also be very hot. To prevent the relief valve from opening under these conditions, the expansion tank must absorb both the fluid displaced by vapourization in the collectors, as well as the expanding volume of the remaining liquid in the circuit.

( (

I

f stagnation occurs on a hot/bright summer afternoon, the temperature that the absorber plate reaches could exceed 350F. We need to deal with the ramifications of such a temperature. Specifically, we need to select a diaphragm-type expansion tank that prevents the system’s pressure relief valve from opening under stagnation conditions.

(

(

(

(

(

(

( ( ( ( ( (

ga

(

64.9 [(6 + 7.95) 0.08 + 6] = 7.83 ga + Vp=) 0.08 Va = 1.1[(V SIZING THEPTANK P ++Vc] = 1.1 c H

( ( (

PRV +14.7 PRV – Pstatic

(

(

64.9 H 144

(

The gauge pressure of 41 psi corresponds to an absolute Va = 1.1[(Vc +PVstatic ) 0.08 + V+c] 64.9 H = 25 + 64.9 20 = 34 psi P@top p ==55.7 pressure of 41+14.7 psi at144 the top of the collectors. 144 According to Figure 1, this pressure would maintain the 40 per 64.9 cent glycol solution the collectors, as 47 a liquid, * + 14.7 PRVin+14.7 = P@top + Pstaticpropylene V = about Va H 297F. 144 = 7.83 = 37.7 to a temperature tof This is definitely higher PRV – Pstatic 47 – 34 than the fluid would see in normal operation, but not high PRV +14.7 enough vapour formation under summer stagnaVt = Vato prevent P – Pstatic RV tion conditions.

(

Vt = Va

(

(

64.9 64.9 = 41 psi P@top = PPRVratedV–= 1.1[(VH = 50) –0.08 + V20 + V 144 144 c] = 1.1 [(6 + 7.95) 0.08 + a c p

(

Figure 2 c + Vp) 0.08 + Vc] Va = 1.1[(V

Pstatic = P@top +

( ( (

P@top = PPRVrated – H 144 PRV +14.7 Vt = V a In our example this wouldPbe: – Pstatic RV

(

(

144

(

(

(

(

20 = 41 psi

(

( (

144

( (

(

(

PRVrated

64.9 H 144

Where: 64.9 64.9 P@top = pressureP at top collector – arrayHas= relief = PofPRVrated 50 – valve @top 64.9 144 144 + reaches pressure (psi) P@PRV =rated P@topopening H 144 PPRVrated = rating of pressure relief valve (psi) Va = 1.1[(V + Vp) 0.08 Vc] to top of H = vertical distance from pressure relief+valve c 64.9 64.9 collectors (feet) + P@PRV = P H = 25 + 20 = 34 psi @top 144 64.9 = density of 40 per cent propylene 64.9144glycol solution at Pstatic = P@top + H 50F 144 144 = units conversion factor 64.9

( (

@top

( (

(

(

( (

Based on this, select a relief valve rated at 50 psi. 64.9 – determine P@topFormula = PPRVrated Use 2 to H the pressure at the top 144 of the collector array just as the selected pressure relief valve is about to open—a condition we want to avoid at 64.9 64.9 20 = 41 psi stagnation. – P =P H = 50 –

P@top = PPRVrated –

(

( (

(

64.9 64.9 H = 25 + 20 = 34 psi 144 144

(

64.9 64.9 H = 25 + 20 = 34 psi 144 144

(

P@PRV = P@top +

( (

Formula 2:

( (

P@top = static cold fill pressure at top of collector array (psi) H = vertical distance from pressure relief valve to top of collectors (feet) 64.9 = density of 40 per cent propylene glycol solution at 50F 144 = units conversion factor For example, assume 25 psi static cold fill pressurization at the top of the array, and 20 feet of vertical distance from 64.9 to the relief valve location. The thePtop of=the array + down H P@top @PRV static pressure at the144 relief valve location would be:

64.9 H 144

(

P@PRV = P@top +

( (

( (

P@PRV = P@top +

(

continued from page 22

( (

Solar Panel

144vapourize during stagnaSince the collector fluid will likely 64.9 64.9 accommodate we=need to 7.83 gallons Va = 1.1[(Vc + Vp) 0.08 + Vc] = 1.1 [(6 + 7.95) 0.08 + 6]tion, + size theHexpansion P P=static = 34 psi = 25 + tank to20 @top 144 64.9 144 64.9 this expansion. P@PRV = P@top + H = 25 + 20 = 34 psi 144 144 must 1: Calculate the volume the expansion tank Step 64.9 64.9 Pstatic = P@top + 20 = 34 psi H = 25 + * + 14.7 PRV +14.7 absorb at stagnation using Formula 47 3. This assumes vapour 144 144 Vt = Va = 7.83 = 37.7 gallons PRVcollector – Pstatic during stagnation 47 – 34 will form in the and that the liquid 64.9 PPRVrated –of the system H will reach 200F temperature P in@top the= remainder PRV +14.7 47* + 14.7 144 Vt = Va = 7.83 = 37.7 gallons above the temperature at which the system was filled. The PRV – Pstatic 47 – 34 latter is a conservatively safe assumption.

(

(

(

Formula 3:

(

(

64.9 64.9 20 = 41 psi H = 50 – 144 144

(

(

P@top = PPRVrated –

( (

(

(

(

(

(

(

(

(

@top

(

(

@PRV

Va = 1.1[(Vc + Vp) 0.08 + Vc] Where: Va = expansion volume to be accommodated (gallons). 64.9 Pstatic = P@top + H Vc = total volume of collector array 144 (gallons) Vp = total volume of collector piping other than PRV +14.7 collectors (gallons) continued on page 26

= 1.1 [(6 + 7.95) 0.08 + 6] Va = 1.1[(Vc + Vp) 0.08 + Vc] hpacmag.com Pstatic = P@top +

(

(

64.9 64.9 20 = 34 psi H = 25 + 144 144

(

HPAC | MAY/JUNE 2009

PRV – Pstatic

(

24

(

(

Vt = Va

(

(

continued from page 24

P@top = PPRVrated –

V = 1.1[(V + V ) 0.08 + V ]

a c p c Step 3: Calculate the minimum required expansion tank volume using Formula 5, which is derived from Boyle’s law.

Vt = Va

(

0.0269 0.0454

( (

1.25" type M copper:

(

3/4" type M copper: 1" type M copper:

(

(

0.068

64.9 P@PRV = P@top + H 1.5" type M copper: 144 0.095

( (

Here is a final example that pulls this all together. Assume a residential solar water heating system has the following 2" type M copper: 0.165 components: 2.5" type M copper: » Four collectors, each having a volume of 1.5 gallons 64.9 0.2543 64.9 P@PRV = P@top + H = 25 + 20 = 34 psiof 120 feet of one-inch copper tubing between » Total 3" type M copper: 0.3630 144 144 heat exchanger and collector array » Heat exchanger volume = 2.5 gallons 64.9 64.9 Step 2: Calculate » Height top array above relief valve = 20 feet theP cold fill at the – static pressure P@top = + of collector P@PRV = of P@top H H PRVrated 144 144 » Pressure relief valve rating = 50 psi location of the pressure relief valve. This is the pressure » Collector circuit caused by the weight of fluid in the collector circuit above 64.9fluid = 40 per 64.9 cent solution of PP@PRV ==PP@top ++ 64.9 HH= 25 + 20 = 34 psi 144 144 64.9 64.9 20propylene @PRV @top glycol the pressure relief valve location, plus the static pressure 144 = 41 psi P@top = PPRVrated – H = 50 – 144 144 Determine the minimum size of a diaphragm-type expansion maintained at the top of the system. It can be calculated 64.9such that 64.9 64.9 tank for==the system using Formula 4. PP@top PP +– HH= 25 + the relief 20 = valve 34 psi does not open PRVrated @PRV @top 144 144 144 under stagnation conditions. The cold fill pressure at the Va = 1.1[(Vc + Vp) 0.08 + Vc] top of the system64.9 is 25 psi. 64.9 Formula 4: 64.9

( ((

(

(

(

(

(

(

(

( 7.95) 0.08 + 6] (= 7.83 gallons 64.9 64.9 ( P = P +( 20 = 34 psi H = 25 + ( 144 144 ( ( Step 2: P +14.7 47 + 14.7 ( ( V=V ( (( = 7.83 ( = 37.7 gallons P –P 47 – 34 V=V

PRV+– Pstatic H Pt static =a1:P@top Step 144

V ) 0.08 + Vc] = 1.1 [(6 + 7.95) 0.08 + 6] = 7.83 gallons Va = 1.1[(VPc + +14.7 RV p Vt = Va PRV – Pstatic 64.9 64.9 Pstatic = P@top + 20 = 34 psi H = 25 + 144 144 Va = 1.1[(Vc + Vp) 0.08 + Vc] = 1.1 [(6 + 7.95) 0.08 + 6] = 7.83 gallons

(

static

(

RV

Vt = Va 26

HPAC | MAY/JUNE 2009

(

(

PRV +14.7 47* + 14.7 PRV – Pstatic = 7.83 47 – 34 = 37.7 gallons

(

(

before the fluid begins to warm.

P +14.7 47* + 14.7 VPt = V=a P RV+ 64.9 = 7.83 64.9 37.7 psigallons PRV – Pstatic H = 25 + 47 – 3420 ==34 static @top 144 144

( ( (

(

RV

circuit. This ensures thet diaphragm is fully expanded against the tank shell a

(

*Note: The air chamber in the diaphragm expansion tank must be pressurized to this calculated static pressure before fluid is added to the collector *

PRV +14.7 64.9

( ( ( ((

@top

(

( (

(

Solution: Va = 1.1[(Vc + Vp) 0.08 + Vc] 64.9array 64.9is20 psi= 6 gallons The collector volume 4 =x 41 1.5 – = PPRVrated P@toptotal H = 50 – 144 144 The total piping plus heat exchanger volume is 120 ft x 64.9 Pstatic = P@top + H 144 Va = 1.1[(V + Vp) 0.08 + Vc= ] 7.95 gallons (0.0454 gallon/ft) + 2.5 c

Where: P +14.7 Vt = Vaat theRVrelief valve location (psi) Pstatic*= static pressure PRV – Pstatic H = height of collector circuit above location of pressure relief valve (feet) Va = 1.1[(Vc + Vp) 0.08 + Vc] = 1.1 [(6 + 64.9 = density of 40 per cent propylene glycol solution at 50F 144 = units conversion factor static

(

20 = 41 psi PP@top ==PPPRVrated –– HH= 50 – @top PRVrated 144 144 144

64.9 Pstatic = P@top + H 144

(

(

(

(

(( (

(

(

(

( (

( (

(

(

( (

(

hpacmag.com

(

(

(

0.0132

PRV +14.7 PRV – Pstatic

(

1/2" type M copper:

64.9 H 144

Where: + Vptank ) 0.08 + Vc](gallons) = 1.1 [(6 + 7.95) 0.08 + Va = 1.1[(V VT = minimum required expansion volume c Va = expansion volume to be accommodated (from Step 1) 64.9 64.9 (gallons) Pstatic = P@top + 20 = 34 psi H = 25 + 144 Pstatic = cold fill static pressure at144 the relief valve location (from Step 2) (psi) PRV +14.7 + 14.7 47*locaPRV = maximumVallowed at the relief valve = Va pressure = 7.83 = 37.7 ga t P – P 47 34 tion (psig). Recommended value relief valve –ratRV is pressure static ing minus three psi. This allows for a slight safety factor against relief valve “dribbling" as the pressure approaches the valve’s rating.

Gallons/foot 0.008272

(

(

(

Formula 5:

FIGURE 3 COPPER COLLECTOR PIPING 3/8" type M copper:

Pstatic = P@top +

(

0.08 = expansion factor for 40 per cent propylene glycol solution for 200F temperature rise 1.1 = 10 per cent added safety factor to allow for system volume estimates Collector fluid volume is usually listed in manufacturer’s specifications, as is the volume of the tank’s internal heat exchanger. The volume of copper collector piping can be estimated using data from Figure 3. If other types of tubing are used for the collector circuit, obtain volume data from the manufacturer.

Tube type/size

(

64.9 64.9 20 = 41 psi H = 50 – 144 144

(

Solar Panel

64.9 H 144

( (

( (

P@top = PPRVrated –

Va = 1.1[(Vc + Vp) 0.08 + Vc]

(

64.9 H 144

PRV +14.7 PRV – Pstatic

(

Vt = Va

(

(

Pstatic = P@top +

Va = 1.1[(Vc + Vp) 0.08 + Vc] = 1.1 [(6 + 7.95) 0.08 + 6] = 7.83 gallons

(

PRV +14.7 47* + 14.7 PRV – Pstatic = 7.83 47 – 34 = 37.7 gallons

(

(

(

(

64.9 64.9 20 = 34 psi H = 25 + 144 144

(

Vt = Va

(

(

+ = P3: Pstatic Step @top

*Note: The PRV value in Step 3 was set to 50-3=47 psi to guard against “dribbling" of the relief valve as it approaches its rated pressure.

As you can see, the expansion tank for the system is significantly larger than a hydronic heating system of similar volume. This is partially the result of very conservative assumptions and partially the result of steam flash in the collectors at stagnation. As in hydronic heating systems, a conservatively sized expansion tank is good insurance against the system requiring servicing following a stagnation condition. The volume of the expansion tank could be reduced by reducing system volume (e.g. smaller tubing, smaller heat exchanger and so on). It could also be reduced by lowering the static pressure at the top of the collector array and/

or increasing the pressure rating of the relief valve. These changes all have consequences, but may be possible in some applications. In cases where the minimum required expansion tank volume exceeds the volume of available tanks, it is acceptable to use multiple tanks connected in parallel. Be sure the air side pressure in each tank is set to the calculated static pressure prior to filling the collector circuit. Finally, be sure to locate the check valve in the collector circuit so that fluid can be pushed out of the bottom and top of the collectors as vapourization occurs (see Figure 2). This is an important detail to avoid “slugging" of the liquid if it can only exit at the top of the collector array. John Siegenthaler, P.E. is the author of Modern Hydronic Heating. Visit hydronicpros.com for reference information and software to assist in hydronic system design. He can be reached at [email protected].

Innovative system technology for modern solar thermal systems

FlowCon Max FA

Solarnetix.indd 1

hpacmag.com

Solex

•Solar stations •Solar heat transfer

PAW GmbH & Co. KG Böcklerstraße 11 D-31789 HAMELN GERMANY +49-5151-9856-0 +49-5151-9856-98 [email protected] www.paw.eu

@

North American Distributor Solarnetix Inc. 777 Warden Ave. Toronto ON CANADA 1- 416-699-6746 [email protected] www.solarnetix.com

@

4/3/08 4:14:00 PM

MAY/JUNE 2009 | HPAC

27