Detect, Measure, Analyze.
Thank You for Attending Today’s Webinar Your Host John Greivell VP Operations RAECO-LIC LLC
[email protected]
Our Featured Speaker Ray Follis Industrial Fire Products Specialist Honeywell Security and Fire
[email protected]
Honeywell Industrial Fire Protection for Safety Related Applications
Learning Objectives • Key differences between process safety system and life safety systems • The basic advantages of a fully integrated life safety / process safety system • A brief introduction to the Honeywell HS-81 Fire & Gas system architecture and similarities to that of a Safety PLC. • The significance of listings and certifications, including SIL 2 / SIL 3, GOST, UL 864, EN-54, ABS and other certifications. • An introduction to the HS-81 configuration (software) and ease of use. • Q&A with the presenter. 2
HONEYWELL - CONFIDENTIAL
File Number
Our Facility Model for Process F&G
Production ProductionArea Area MCCs & RIEs Process Buildings
Admin Building
3
Control Room
HONEYWELL - CONFIDENTIAL
File Number
How Is Industrial Different Than Commercial? Commercial Fire Detection
Office spaces Detection and evacuation Building code Smoke and heat detection Redundant controls not required Little interaction with building controls EN54 or UL approvals
4
Industrial Fire
Processing areas Reduce risks of hazard Performance based Flame, gas, smoke and heat detection with explosion proof or intrinsically safe devices Redundancy and high availability required with sub-second response time Interaction with plant process control to initiate safety response/shutdown ATEX, IEC – 61508, UL, FM EN-54 approvals
One site, but different requirements HONEYWELL - CONFIDENTIAL
File Number
Conventional F&G Philosophy
Gas detectors Flame detectors ESD High power beacons Remote singalling interface with other systems
Point type Smoke/heat detector Manual call point Addressable beacon and sounder
Actuation of discharge Control of delays Dedicated fire detection
Main HMI
5
IEC61508 for safety PLCs continous mode HONEYWELL - CONFIDENTIAL
File Number
Issues
INTERFACING COMMUNICATION ISSUES
Main interface
Designed for Process Safety
Designed for building fire alarm
Actuation only
1. The full function relies on all three systems 2. Maintenance (power supplies and batteries) 3. Total Cost of Ownership
6
HONEYWELL - CONFIDENTIAL
File Number
PLC versus Integrated Life and Process Safety Systems
Integrated Fire & Gas and Life Safety System
Safety PLC • SIL 2 / SIL3 • Inputs, processing and outputs • Open protocol communications • Hardware is generic and designed for various input and output functionality • All logic and functionality is programmed for a project. • Not designed or certified for fire service 7
• SIL 2 / SIL 3 • Inputs, processing and outputs • Open protocol communications • Hardware is purpose built for fire and gas detection service. • The program’s logic and functionality are preengineered for fire and gas detection applications. • Certified to multiple standards for fire service
HONEYWELL - CONFIDENTIAL
File Number
Integrated Fire, Gas and Life Safety
8
HONEYWELL - CONFIDENTIAL
File Number
Panel Architecture
9
HONEYWELL - CONFIDENTIAL
File Number
Hot Swap Capability
• Front plug-in & removal of cards • Automatic monitoring of cards and CPU fault • Automatic and safe disabling of malfunctioning cards • Cards can be hot swapped • CPU auto-configures and checks new card • Power & CPU can be duplicated for automatic fall-over configuration
10
HONEYWELL - CONFIDENTIAL
File Number
Multicard Racks and Scalability E2001-1 Rack
11
Each HS81 rack can contain up to 13 cards. The racks fit in standard, 19” enclosures
The 14th slot of the rack is for the E2002-1 card, which manages the communication bus
The HS81 panel can manage up to 10 racks, for a total of 130 cards
HONEYWELL - CONFIDENTIAL
File Number
Main Capacities
HS-81-HS System Capacities
UL
EN-54
6
10
Racks HW
13 per rack
Cards Single point devices
9906
Addressable devices
29,700 + 29,700 300
Safety zone capacity SW
Devices per zone
99 inputs, 99 outputs, 99 logic gates
Panels per TCP/IP network
12
16510
HONEYWELL - CONFIDENTIAL
99
File Number
F4000 Series Analog Input Module
1, 2 or 8 4-20 mA inputs Direct reading on display (1 or 2 input module) Connection of toxic/flammable gas, and oxygen deficiency sensors 2 alarm thresholds per input SIL 2 certified sensors available
13
HONEYWELL - CONFIDENTIAL
File Number
F7000 Addressable SLC Module
SLC Style 4 or 7 Inputs & Outputs function on the same loop Modules with different manufacturer protocols in the same panel SIL 2 certified detectors available
14
HONEYWELL - CONFIDENTIAL
File Number
Conventional Input Module
Multiple brands & types of detectors accepted 30+ detectors per line including MCPs Short and open circuit monitoring Pre-alarm, alarm, and alarm verification on each line 15
HONEYWELL - CONFIDENTIAL
File Number
F5000 Series Output Modules Discrete command for each output Line monitoring per UL864 Card and circuit level diagnostics Audible, Visual, Relay, Extinguishing and other control functions. Releasing logic using F6000 64 Releasing Zones One main, 3 reserve 16
HONEYWELL - CONFIDENTIAL
File Number
Extinguishing and Releasing Functionality Releasing zone according to EN and NFPA standards one F6001 module per Releasing zone Detection is made with any other input card Module 6001 does not have any physical I/O’s Directional and control valves, manual call points, sounders and other Releasing devices are connected to separate I/O modules or Cards. Releasing control system can be SIL2 or up to SIL3.
17
HONEYWELL - CONFIDENTIAL
File Number
Integration with PC Systems
18
HONEYWELL - CONFIDENTIAL
File Number
Part of a Total Facility Solution Experion Server
FDM
IMS (PHD+PCC+AM)
Operator station
Enterprise Software
Critical Action Panel
DVM
PGM
C300
Hardwired
Safety PLC (ESD)
Safety Builder
Modbus SAFENET
Controllers & Industrial Networks
Hardwired
HS-81 F&G System
VSD /MCC
RS485
IOM
2
2
Sounders & Beacons KNUS GLASSET TRYKK HER PRESS HERE BREAK GLASS
KNUS GLASSET TRYKK HER PRESS HERE BREAK GLASS
SM RUSIO TRYKK HER
BN- 300 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr.
BN- 500 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr.
No.
No.
Gas & flame detectors SIL2/3 Addressable System BREAK GLASS PRESS HERE
Edge Devices
Smoke detectors
19
HONEYWELL - CONFIDENTIAL
File Number
Examples of Safety Equipment Standards and Certifications
• TUV Certification – Verifies equipment meets Safety Integrity Levels (SIL) on a scale of 1 to 4. Reliability is mathematically measured with four being the highest • GOST R – This certificate assures imported products comply with Russian standards, quality and safety requirements. The GOST R certificate is mandatory for customs clearance in Russia • UL 864 – The UL Standard for Control Units and Accessories for Fire Alarm Systems. The focus is compliance with NFPA 72 standards. • ABS – The American Bureau of Shipping establishes standards for maritime fire safety in the United States. • EN-54 – The European Union standard that specifies requirements and laboratory test for fire alarm equipment.
• CE – A conformity marking for products sold in the European Union. 20
HONEYWELL - CONFIDENTIAL
File Number
System Configurator Helps Assemble a Proper System Functionality and Self Checks for Conflicts
21
HONEYWELL - CONFIDENTIAL
File Number
ProS81 Application Program
ProS81
1) Definition of inputs 2) Definition of outputs 3) Definition of rules 4) Check of data validity Runs on any Windows operating system Communication with panel via RS232 or TCP/IP Configuration is protected through password and USB dongle key
22
HONEYWELL - CONFIDENTIAL
File Number
Check of Data Validity
23
HONEYWELL - CONFIDENTIAL
File Number
Review • The differences between safety PLCs and an engineered life safety / process safety systems • Hardware and software on an integrated system are pre-engineered for Fire & Gas and Life Safety applications • The basis advantages of a fully integrated life safety / process safety system • Certified to Process and Life Safety Standards • Multiple platforms combined, including fire alarm, gas & flame, and extinguishing functions. • Process safety functionality integrated into the fire and gas system to eliminate a potential point of failure.
24
HONEYWELL - CONFIDENTIAL
File Number
Questions?
Detect, Measure, Analyze.
Get Social with RAECO • Our Website •
www.raeco.com
• Our Blog •
Blog.raeco.com
• Follow us on LinkedIn •
www.linkedin.com/company/raeco-lic-llc
• Follow us on Twitter •
@RAECOLIC
• Check Out our YouTube Channel •
www.youtube.com/user/RaecoVideos