Learning Objectives • Key differences between process safety system and life safety systems • The basic advantages of a fully integrated life safety / process safety system • A brief introduction to the Honeywell HS-81 Fire & Gas system architecture and similarities to that of a Safety PLC. • The significance of listings and certifications, including SIL 2 / SIL 3, GOST, UL 864, EN-54, ABS and other certifications. • An introduction to the HS-81 configuration (software) and ease of use. • Q&A with the presenter. 2

HONEYWELL - CONFIDENTIAL

File Number

Our Facility Model for Process F&G

Production ProductionArea Area MCCs & RIEs Process Buildings

Admin Building

3

Control Room

HONEYWELL - CONFIDENTIAL

File Number

How Is Industrial Different Than Commercial? Commercial Fire Detection

Office spaces Detection and evacuation Building code Smoke and heat detection Redundant controls not required Little interaction with building controls EN54 or UL approvals

4

Industrial Fire

Processing areas Reduce risks of hazard Performance based Flame, gas, smoke and heat detection with explosion proof or intrinsically safe devices Redundancy and high availability required with sub-second response time Interaction with plant process control to initiate safety response/shutdown ATEX, IEC – 61508, UL, FM EN-54 approvals

One site, but different requirements HONEYWELL - CONFIDENTIAL

File Number

Conventional F&G Philosophy

Gas detectors Flame detectors ESD High power beacons Remote singalling interface with other systems

Point type Smoke/heat detector Manual call point Addressable beacon and sounder

Actuation of discharge Control of delays Dedicated fire detection

Main HMI

5

IEC61508 for safety PLCs continous mode HONEYWELL - CONFIDENTIAL

File Number

Issues

INTERFACING COMMUNICATION ISSUES

Main interface

Designed for Process Safety

Designed for building fire alarm

Actuation only

1. The full function relies on all three systems 2. Maintenance (power supplies and batteries) 3. Total Cost of Ownership

6

HONEYWELL - CONFIDENTIAL

File Number

PLC versus Integrated Life and Process Safety Systems

Integrated Fire & Gas and Life Safety System

Safety PLC • SIL 2 / SIL3 • Inputs, processing and outputs • Open protocol communications • Hardware is generic and designed for various input and output functionality • All logic and functionality is programmed for a project. • Not designed or certified for fire service 7

• SIL 2 / SIL 3 • Inputs, processing and outputs • Open protocol communications • Hardware is purpose built for fire and gas detection service. • The program’s logic and functionality are preengineered for fire and gas detection applications. • Certified to multiple standards for fire service

HONEYWELL - CONFIDENTIAL

File Number

Integrated Fire, Gas and Life Safety

8

HONEYWELL - CONFIDENTIAL

File Number

Panel Architecture

9

HONEYWELL - CONFIDENTIAL

File Number

Hot Swap Capability

• Front plug-in & removal of cards • Automatic monitoring of cards and CPU fault • Automatic and safe disabling of malfunctioning cards • Cards can be hot swapped • CPU auto-configures and checks new card • Power & CPU can be duplicated for automatic fall-over configuration

10

HONEYWELL - CONFIDENTIAL

File Number

Multicard Racks and Scalability E2001-1 Rack

11



Each HS81 rack can contain up to 13 cards. The racks fit in standard, 19” enclosures



The 14th slot of the rack is for the E2002-1 card, which manages the communication bus



The HS81 panel can manage up to 10 racks, for a total of 130 cards

HONEYWELL - CONFIDENTIAL

File Number

Main Capacities

HS-81-HS System Capacities

UL

EN-54

6

10

Racks HW

13 per rack

Cards Single point devices

9906

Addressable devices

29,700 + 29,700 300

Safety zone capacity SW

Devices per zone

99 inputs, 99 outputs, 99 logic gates

Panels per TCP/IP network

12

16510

HONEYWELL - CONFIDENTIAL

99

File Number

F4000 Series Analog Input Module

1, 2 or 8 4-20 mA inputs Direct reading on display (1 or 2 input module) Connection of toxic/flammable gas, and oxygen deficiency sensors 2 alarm thresholds per input SIL 2 certified sensors available

13

HONEYWELL - CONFIDENTIAL

File Number

F7000 Addressable SLC Module

SLC Style 4 or 7 Inputs & Outputs function on the same loop Modules with different manufacturer protocols in the same panel SIL 2 certified detectors available

14

HONEYWELL - CONFIDENTIAL

File Number

Conventional Input Module

Multiple brands & types of detectors accepted 30+ detectors per line including MCPs Short and open circuit monitoring Pre-alarm, alarm, and alarm verification on each line 15

HONEYWELL - CONFIDENTIAL

File Number

F5000 Series Output Modules Discrete command for each output Line monitoring per UL864 Card and circuit level diagnostics Audible, Visual, Relay, Extinguishing and other control functions. Releasing logic using F6000 64 Releasing Zones One main, 3 reserve 16

HONEYWELL - CONFIDENTIAL

File Number

Extinguishing and Releasing Functionality Releasing zone according to EN and NFPA standards one F6001 module per Releasing zone Detection is made with any other input card Module 6001 does not have any physical I/O’s Directional and control valves, manual call points, sounders and other Releasing devices are connected to separate I/O modules or Cards. Releasing control system can be SIL2 or up to SIL3.

17

HONEYWELL - CONFIDENTIAL

File Number

Integration with PC Systems

18

HONEYWELL - CONFIDENTIAL

File Number

Part of a Total Facility Solution Experion Server

FDM

IMS (PHD+PCC+AM)

Operator station

Enterprise Software

Critical Action Panel

DVM

PGM

C300

Hardwired

Safety PLC (ESD)

Safety Builder

Modbus SAFENET

Controllers & Industrial Networks

Hardwired

HS-81 F&G System

VSD /MCC

RS485

IOM

2

2

Sounders & Beacons KNUS GLASSET TRYKK HER PRESS HERE BREAK GLASS

KNUS GLASSET TRYKK HER PRESS HERE BREAK GLASS

SM RUSIO TRYKK HER

BN- 300 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr.

BN- 500 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr.

No.

No.

Gas & flame detectors SIL2/3 Addressable System BREAK GLASS PRESS HERE

Edge Devices

Smoke detectors

19

HONEYWELL - CONFIDENTIAL

File Number

Examples of Safety Equipment Standards and Certifications

• TUV Certification – Verifies equipment meets Safety Integrity Levels (SIL) on a scale of 1 to 4. Reliability is mathematically measured with four being the highest • GOST R – This certificate assures imported products comply with Russian standards, quality and safety requirements. The GOST R certificate is mandatory for customs clearance in Russia • UL 864 – The UL Standard for Control Units and Accessories for Fire Alarm Systems. The focus is compliance with NFPA 72 standards. • ABS – The American Bureau of Shipping establishes standards for maritime fire safety in the United States. • EN-54 – The European Union standard that specifies requirements and laboratory test for fire alarm equipment.

• CE – A conformity marking for products sold in the European Union. 20

HONEYWELL - CONFIDENTIAL

File Number

System Configurator Helps Assemble a Proper System Functionality and Self Checks for Conflicts

21

HONEYWELL - CONFIDENTIAL

File Number

ProS81 Application Program

ProS81

1) Definition of inputs 2) Definition of outputs 3) Definition of rules 4) Check of data validity  Runs on any Windows operating system  Communication with panel via RS232 or TCP/IP  Configuration is protected through password and USB dongle key

22

HONEYWELL - CONFIDENTIAL

File Number

Check of Data Validity

23

HONEYWELL - CONFIDENTIAL

File Number

Review • The differences between safety PLCs and an engineered life safety / process safety systems • Hardware and software on an integrated system are pre-engineered for Fire & Gas and Life Safety applications • The basis advantages of a fully integrated life safety / process safety system • Certified to Process and Life Safety Standards • Multiple platforms combined, including fire alarm, gas & flame, and extinguishing functions. • Process safety functionality integrated into the fire and gas system to eliminate a potential point of failure.

24

HONEYWELL - CONFIDENTIAL

File Number

Questions?

Detect, Measure, Analyze.

Get Social with RAECO • Our Website •

www.raeco.com

• Our Blog •

Blog.raeco.com

• Follow us on LinkedIn •

www.linkedin.com/company/raeco-lic-llc

• Follow us on Twitter •

@RAECOLIC

• Check Out our YouTube Channel •

www.youtube.com/user/RaecoVideos

Suggest Documents