The Pig Machine Heat Carbon Dioxide, CO2
SWINE VENTILATION Mark Oberreuter , P.E. Ventilation Engineer Automated Production Systems
Oxygen, O2
Negative Pressure Ventilation
Measuring the Environment • • • • • •
Temperature Static Pressure Air Velocity @ Inlet Air Velocity @ Pig Level Relative Humidity Gases (Ammonia, Carbon Dioxide, etc.)
Measuring the Environment
Temperature
• Temperature Static Pressure Air Velocity @ Inlet Air Velocity @ Pig Level Relative Humidity Gases (Ammonia, Carbon Dioxide, etc.)
100 90
TEMPERATURE, OF
• • • • •
Water, H2O
Ammonia, NH3
80 70 60 50 40 0
5
10
15
20
25
AGE IN WEEKS
1
Temperature
Temperature • Indoor Probes – At least two - in case one goes bad – Multiple in larger rooms – Close to pig level but out of reach – Not in front of heaters or inlets
• Outdoor Probes – Locate on north wall under eave Probe
Temperature
Measuring the Environment • Temperature
• Static Pressure • • • •
Air Velocity @ Inlet Air Velocity @ Pig Level Relative Humidity Gases (Ammonia, Carbon Dioxide, etc.)
Static Pressure
Static Pressure - Fans Normal Range
8000
FAN AIRFLOW, CFM
7000 6000 5000 4000 3000 2000 1000 0 0
0.05
0.1
0.15
0.2
0.25
0.3
STATIC PRESSURE, IN. WATER
2
Static Pressure - Inlets
Static Pressure
Normal Range 2500
INLET AIRFLOW, CFM
2000
1500
1000
500
0 0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
**Warning – Wind will influence reading**
STATIC PRESSURE, IN. WATER
Measuring the Environment
Air Velocity @ Pig Level
• Temperature • Static Pressure
800 ft/min
• Air Velocity @ Inlet • Air Velocity @ Pig Level • Relative Humidity • Gases (Ammonia, Carbon Dioxide, etc.)
200 ft/min
Air Velocity @ Inlet
Air Velocity @ Inlet 1000
Airflow 4000 x Cd x
SP x Area
900
Cd 0.60
700
SP x Area
Airflow Velocity x Area
Velocity 2400 x
SP
Velocity, ft/min
Airflow 2400 x
800
600 500 400 300
Airflow (cfm)
Cd = discharge coefficient (0.0 – 1.0)
200
Velocity (ft/min)
SP = static pressure (in. water)(0.00 – 0.10)
100
Area (ft2)
0
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
0.12
0.13
0.14
0.15
Static Pressure, in. water
3
Air Velocity @ Inlet Airflow Velocity x Area Feet 2 CFM Minute x Feet
Area
OPENING TYPE
Air Velocity @ Inlet Airflow Velocity
VELOCITY
PIT WALL OPENING FOR PIT FAN
1000
COLD WEATHER ACTUATED INLETS
800
MILD WEATHER ACTUATED INLETS
700
TUNNEL CURTAIN
600
OPENING INTO THE ATTIC FOR INLETS
500
EVAPORATIVE COOLING ON ROOM
400
EVAPORATIVE COOLING ON HALLWAY
350
Measuring the Environment • Temperature • Static Pressure • Air Velocity @ Inlet
**Warning – Position at inlet will influence reading**
Air Velocity @ Pig Level 800 ft/min
• Air Velocity @ Pig Level • Relative Humidity • Gases (Ammonia, Carbon Dioxide, etc.)
Air Velocity @ Pig Level
200 ft/min
Air Velocity @ Pig Level
Author: Steven J. Hoff Iowa State University
4
Air Velocity @ Pig Level
Air Velocity @ Pig Level
10
WIND CHILL, DEGREE F
9 8 7 6 5 4 3 2 1 0 0
50
100
150
200
250
300
350
400
AIR VELOCITY, FT/MIN
Measuring the Environment • • • •
Relative Humidity
Temperature Static Pressure Air Velocity @ Inlet Air Velocity @ Pig Level
• Relative Humidity • Gases (Ammonia, Carbon Dioxide, etc.)
Relative Humidity
**Warning – Requires regular maintenance to be remain accurate**
Relative Humidity
**Warning – Accuracy may diminish over time**
5
Measuring the Environment • • • • •
Gases
Temperature Static Pressure Air Velocity @ Inlet Air Velocity @ Pig Level Relative Humidity
• Gases (Ammonia, Carbon Dioxide, etc.)
Gases
Single Wide Finisher Cold Weather Ventilation
Single Wide Finisher Natural Ventilation w/Stir Fans
Double Wide Finisher Cold Weather Ventilation
6
Gestation Cold Weather Ventilation
Gestation Tunnel Ventilation w/Evap Cooling
Farrowing Cold & Hot Ventilation
Management
Controller Set Point
Controls Backup Systems Ceiling Inlets Airflow Reducers Maintenance
100 90
TEMPERATURE, OF
• • • • •
Double Wide Finisher Tunnel Ventilation
80 70 60 50 40 0
5
10
15
20
25
AGE IN WEEKS
7
Controller Set Point
Controller Set Point
• Reference temperature • Necessary to lower as pigs grow • Most settings move with set point
Controller Set Point
Controller Set Point
Controller Set Point
Controller Set Point • Set Point Curve
Set Point
8
Minimum Ventilation
Minimum Ventilation
• When room temp is below set point • Minimum ventilation required to remove humidity, gases and supply oxygen • Typical signs: – To little -> high humidity – To much -> wasting heat
Minimum Ventilation WEIGHTS (lbs)
COLD MILD (cfm/hd) (cfm/hd)
Minimum Ventilation
HOT NO TUNNEL TUNNEL Air Change Velocity Air Change (cfm/hd) (seconds) (ft/min) (seconds)
400
20
80
650
40A
****
****
NURSERY
10 to 60
2 to 5
15
40
40
****
****
FINISHER
60 to 240
5 to 10
35-50
120
40
300-400
30-45
WEAN-TO-FINISH
10 to 240
2 to 10
35-50
120
40
300-400
30-45
FARROWING
FAN TYPE APP-12 APP-14 APP-18 APP-24 APP-36 APPB-36 APPB-50 CS54C1-P
WITH CONE N.A.A 2710 4890 7120 11310 11280 23200 30044
WITHOUT CONE 1447 2385 4205 6002 10297 9920 20151 N.A.
MINIMUM AIRFLOWC 150 450 700 1200 6000 N.P.B N.P. N.P.
A
N.A. stand for not available N.P. stands for not possible Minimum airflow rating when fan is at the lowest variable speed setting * Maximum airflow rating is at 0.05 in. w.g. * Deduct 15% airflow when using a wind diverter cone B C
GESTATION A
325
12
60
150
35
300-600
30-45
USE 45 SECONDS IF EVAPORATIVE COOLING IS USED
Adjusting Minimum Ventilation • Manually adjust % on control • Humidity sensor compensation • Minimum vent curves
Manually Adjust % on Control • Minimum speed can be adjusted between 40% and 100% • Minimum speed curve must be turned off
Minimum Speed Setting
9
Humidity Sensor Compensation • Connect optional humidity sensor to control
Minimum Vent Curve • Multiple points for day and speed
Humidity settings Red light will appear when it is time to clean the filter. (approx. 6 months)
Staging Fans
Staging Fans - Bandwidths
• Bandwidths – Number of degrees to go from minimum speed to maximum speed • 2 degrees in winter • 1 degree in summer
– Higher end controls automatically adjust bandwidths with outside temperature
• Don’t more than double the existing airflow with the next stage
Motor Type
1800
1600 1
1400
2 3
1200
4
FAN RPM
• Choose correct motor type for the motor that is being used (#1 thru #10) • All fans on the same stage must have the same exact motor
APP-18F Motor Curve 2000
5
1000
6 7
800
8 9
600
10
400
200
0 %
40
45
50
55
60
65
70
75
80
85
90
95
100
Percentage Setting on the Controller
10
Motor Curves
Heater Set Points
Offset = 2 deg F Differential = 1 to 2 deg F
Zoned Heaters • Probe and heater assignments
Back Up Systems • Thermostats – Heater 5 deg less than set point – Cooling 5 deg more than its on temperature – Adjust as set point is adjusted
• Curtain drops – Make sure they are hooked up – Test 4 times a year
• Generators – Test generator and transfer switch monthly
• Alarm systems
Inlet INLETPerformance PERFORMANCE
Managing Ceiling Inlets 2500
Inlet type Inlet spacing Controlling the opening of the inlet Avoiding obstacles in the room
Actuated 2000
AIRFLOW, CFM
• • • •
Counter-Weighted 1500
Fixed Opening 1000
500
4-Way 0 0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0.11
STATIC PRESSURE, IN W.G.
11
Automatic – Non Weighted (C-2000)
Automatic – Non Weighted • Maximum spacing – 20 ft. x 20 ft.
• Adjustments – Close one or two sides – Manually close all sides in the summer
Automatic – Weighted (CAI-1000CW & CAI-2700CW)
Automatic - Weighted • Maximum spacing – 20 ft. x 20 ft.
• Adjustments – Move the weights • Harder to open in the winter • Easier to open in the spring and fall
– Manually close all sides in the summer
Actuated Ceiling Inlet (ACI-2-4000 & ACI-4000P2)
Actuated Ceiling Inlet • Maximum spacing – 28 ft. down the length of the building – 40 ft. across the width of the building
• Adjustments – Control automatically adjusts the opening as needed – Control automatically closes the inlet in the summer
12
Actuated Ceiling Inlet
Managing Actuated Ceiling Inlets • Pulley configurations
• Controlling the opening
– 2 in. travel of actuator = 1 in. of travel of the inlets
– Static pressure – Potentiometer feedback – Timed
• Slows movement of the inlet for better accuracy • Lighter load on the actuator
– Use a winch for each row of inlets • Easier future adjustments • **Warning** Only adjust inlets when actuator is closed
Pulley Configuration One row - End location
Pulley Configuration One row – Middle location
Pulley Configuration
Pulley Configuration
Two rows - End location
Two rows Middle location
13
Actuated Ceiling Inlets • Adjustments will be necessary – especially in the first 6 months of use • **Warning** Don’t over tighten the inlets in the closed position
Ceiling Inlets • Avoid obstacles in the room
Ceiling Inlets • Avoid obstacles in the room
Ceiling Inlets • Avoid obstacles in the room
– Walls – Other inlets – Feed lines
– Walls – Other inlets – Feed lines
Airflow Reducers
Maintenance
• Incorrect open to attic – Insulation stops, no ridge vents
• • • • • •
Pit lids not sealed Manure level to high Fans not clean Damaged fans Holes in curtain Install fan covers
> 10 feet
– Walls – Other inlets – Feed lines
Fans • • • • • • •
Do not run variable fans too low. Provide wind protection if required. Cover cooling fans in winter. Clean shutters, props and housings. Replace broken cones, housings, etc. Grease bearings on belt drive fans. Maintain proper belt tension.
14
Maintenance
Maintenance
Inlets • Adjust counter weights to maintain proper air speed. • Adjust actuated inlets to maintain correct opening. • Close some inlets to maintain air speed. • Keep inlets clean and working freely. • Inspect insulation stops to prevent inlet blockage. • Provide adequate air opening into the attic.
Maintenance Heaters • Check heater offset and differential to prevent heater from ramping up ventilation. • Clean heaters before each heating season. • Keep heater parts on hand.
Curtain Machines • • • •
Grease drive screw, block and bearings. Inspect and replace worn cables. Minimize leaks around the curtain. Use caution when adjusting curtains with winch.
Maintenance Controls • Regularly test all back-up systems. – Alarm system – Thermostats – Curtain drops – Generator
Maintenance Evap Cooling • Check for dry streaks (holes are plugged) • Let pad dry completely every 24 hours • Bleed off a portion of the water regularly
THANK YOU
15