TACO ZONE CONTROLS WIRING GUIDE Pages Switching Relays – Single Zone Wiring
2 – 12
Switching Relays – NON EXP Connected Together with Priority
3 – 19
Switching Relays – EXP Connected Together with Priority
10 – 11
Switching Relays – Multiple Indirect Hot Water Heaters
12 – 13
Switching Relays – EXP Connected To Reset Controls (PC700, 702 & 705)
14 – 21
Zone Valve Controls – NON EXP Connected Together with Priority
22 – 27
Zone Valve Controls – EXP Connected Together with Priority
28 – 31
Zone Valve Controls – Connected To Reset Controls (PC700, 702 & 705)
32 – 39
Hydro Air Fan Controls (HAFC 101 & 201)
40 – 44
Specialty Thermostat and Zone Valve Wiring
45 – 50
Instruction Sheets
51 – 60
Low Water Cutoff and Industrial Flow Switch
61 – 69
Aquastat Wiring
70 – 74
Standard Terms and Definitions Cross Reference
– 75 76 – 77
Do it once. Do it right. © Taco Catalog No. 100-9.0
Effective Date: May 1, 2003 Supersedes Date: August 1, 2001
TACO Product Information Switching Relays Product No. SR501 SR501-845RP SR502 SR503 SR504 SR506
Description 1 Zone Switching Relay 1 Zone Switching Relay Replacement PC Board for Honeywell R845, RA89A, RA832 or Comparable Relay 2 Zone Switching Relay with Priority 3 Zone Switching Relay with Priority 4 Zone Switching Relay with Priority 6 Zone Switching Relay with Priority
Switching Relays with PowerPort Options and Expandable to 20 Zones Product No. Description SR503-EXP 3 Zone Switching Relay with Priority and 3 PowerPorts SR504-EXP 4 Zone Switching Relay with Priority and 3 PowerPorts SR506-EXP 6 Zone Switching Relay with Priority and 3 PowerPorts Zone Valve Controls Product No. ZVC403 ZVC404 ZVC405 ZVC406
Description 3 Zone Valve 4 Zone Valve 5 Zone Valve 6 Zone Valve
Control Control with Priority Control Control with Priority
Zone Valve Controls with PowerPort Options and Expandable to 20 Zones Product No. Description ZVC404-EXP 4 Zone Valve Control with Priority and 2 PowerPorts ZVC406-EXP 6 Zone Valve Control with Priority and 2 PowerPorts Plug-In PowerPort Cards (For use with all -EXP controls) Product No. Description PC600 Post Purge Timer Plug-In Card PC605 Priority Protection Plug-In Card PC610 Universal Timer/Pump Exercise Plug-In Card Add-On Power Controls (For use with all -EXP controls) Product No. Description PC700 Boiler Reset Control PC702 2-Stage Boiler Reset Control PC705 Variable Speed Pump Injection Mixing Control Fan Controls Product No. HAFC101 HAFC201
Description Hydro Air Fan Control Hydro Air Fan Control with Optional Time Delays
Do it once. Do it right.
2
SR501 Switching Relay Wiring
TYPICAL WIRING (COLD START)
SR501 1 ZONE SWITCHING RELAY
ALTERNATIVE WIRING (TANKLESS COIL)
ALTERNATIVE WIRING (24 VAC POWERED INPUT SIGNAL)
THERMOSTAT
THERMOSTAT
T
T
SR501 1 ZONE SWITCHING RELAY
R W T T COM 24 VAC
24 VAC SIGNAL
SR501 1 ZONE SWITCHING RELAY
24 R W VAC T T COM
24 R W VAC T T COM
POWER
POWER
POWER *
T STAT
T STAT
T STAT *
120 VAC INPUT
120 VAC INPUT
4 4 6 6 5 N H 3 N/O N/C N/C N/O
4 4 6 6 5 N H 3 N/O N/C N/C N/O
JUMPER
4 4 6 6 5 N H 3 N/O N/C N/C N/O
JUMPER
TO: TT ON BOILER
TO: ZC
TO: TT ON BOILER
H
TO: ZR
TO: 120 VAC POWER
N CIRCULATOR TO: 120 VAC POWER
CIRCULATOR
CIRCULATOR TO: 120 VAC POWER
REMOVE JUMPER. DO NOT CONNECT POWER TO N AND H TERMINALS.
* T STAT LIGHT WILL GO ON AND OFF WITH 24 VAC SIGNAL. POWER LIGHT WILL ALWAYS BE OFF.
SR502/503 Switching Relay Controlling Another SR502/503 Switching Relay AQUASTAT ON DHW HEATER
A
T
T
ZONE1
ZONE2
ZONE3
MASTER 24 VAC POWER
PRIORITY ON VIA JUMPER PLACEMENT
SR 503
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
POWER ZONE 1 ZONE 2 ZONE 3
N P ZC H
X2 X1 ZR ZONE1 ZONE2
ZONE3
JUMPER
120 VOLT CIRCULATORS
N 120 VAC POWER
H
DHW HEATER CIRCULATOR
T
T
T
ZONE1
ZONE2
ZONE3
PRIORITY OFF VIA JUMPER PLACEMENT
SLAVE 24 VAC POWER
SR 503
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
N P ZC H
POWER ZONE 1 ZONE 2 ZONE 3
X2 X1 ZR ZONE1 ZONE2
ZONE3
JUMPER
BOILER 120 VOLT CIRCULATORS TO: "TT" ON AQUASTAT CONTROL
3
SR502/503 Switching Relay Controlling Another SR504/506 Switching Relay
AQUASTAT ON DHW HEATER
T
A
T
MASTER PRIORITY ON VIA JUMPER PLACEMENT
24 VAC POWER
SR 503
ZONE1
ZONE2
ZONE3
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
POWER ZONE 1 ZONE 2 ZONE 3
N P ZC H
X2 X1 ZR ZONE1 ZONE2
ZONE3
JUMPERS
120 VOLT CIRCULATORS
THERMOSTATS
T
SLAVE SR 506
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE 6 PRIORITY ON
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
120V RELAY
24 VAC POWER
X
X
END SWITCH
PRIORITY OFF
OFF
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
ZC ZR
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
120 VOLT CIRCULATORS
POWER INPUT
FUSE 1 AMP
REMOVE JUMPER
TO: "TT" ON BOILER
BOILER
4
120 VAC INPUT
H N
Two SR504/506 Switching Relays Connected Together AQUASTAT ON DHW HEATER
A T
T
T ZONE 4 PRIORITY ON OFF
SR 504
PRIORITY ON
ZONE 1 ZONE 2 ZONE 3 ZONE 4
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120V RELAY
24 VAC POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER INPUT
120 VOLT CIRCULATORS
FUSE 1 AMP
120 VAC INPUT
JUMPER
DHW HEATER CIRCULATOR
T
BOILER
SR 504
T
T ZONE 4 PRIORITY ON OFF
PRIORITY ON
ZONE 1 ZONE 2 ZONE 3 ZONE 4
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120V RELAY
24 VAC POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
H 120 VAC INPUT
JUMPER
N
TO: "TT" ON BOILER OUTPUT NOT USED
5
Priority Zoning Circulator Controlling SR504/506 Switching Relay
MASTER PRIORITY ON
PRIORITY ZONING CIRCULATOR PRIORITY OFF THERMOSTAT 2 1
BOILER 4 3
ON
PRIORITY POWER IN PR-IN PR-OUT LIVE NEUT
120 VAC INPUT
A AQUASTAT ON DHW HEATER
THERMOSTATS
T
PRIORITY OFF
SLAVE
SR 506
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE 6 PRIORITY ON
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
120V RELAY
24 VAC POWER
X
X
END SWITCH
OFF
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
ZC ZR
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
120 VOLT CIRCULATORS
POWER INPUT
FUSE 1 AMP
REMOVE JUMPER
TO: "TT" ON BOILER
BOILER
6
120 VAC INPUT
H N
Priority Zoning Circulator Controlling 2 SR504/506 Switching Relays MASTER
PRIORITY ZONING CIRCULATOR PRIORITY OFF
THERMOSTAT 2 1
T
A
T
T
T
T
SLAVE ZONE 4 PRIORITY ON OFF
SR 504
PRIORITY POWER IN PR-IN PR-OUT LIVE NEUT
120 VAC INPUT
AQUASTAT ON DHW HEATER
SLAVE
BOILER 4
3
PRIORITY ON
ON
T
T
T
ZONE 4 PRIORITY ON OFF
PRIORITY OFF
SR 504
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 1 ZONE 2 ZONE 3 ZONE 4
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120V RELAY
120V RELAY
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE4 POWER INPUT
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
FUSE 1 AMP
REMOVE JUMPER
BOILER
ZONE3
120 VOLT CIRCULATORS
24 VAC POWER
24 VAC POWER
X
PRIORITY OFF
REMOVE JUMPER
TO: "TT" ON BOILER
H N 120 VAC INPUT
7
8
SR502/503 Switching Relay Controlling 2 SR504/506 Switching Relays AQUASTAT ON DHW HEATER
A
T
T
MASTER PRIORITY ON
24 VAC POWER
SR 503
ZONE1
ZONE2
ZONE3
TWO ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
POWER ZONE 1 ZONE 2 ZONE 3
N P ZC H
X2 X1 ZR ZONE1 ZONE2
ZONE3
JUMPER
T
SLAVE
T
T
T
ZONE 4 PRIORITY ON OFF
SR 504
T
SLAVE
T
T
T
ZONE 4 PRIORITY ON OFF
PRIORITY OFF
SR 504
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 1 ZONE 2 ZONE 3 ZONE 4
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120V RELAY
120V RELAY
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE4 POWER INPUT
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
FUSE 1 AMP
REMOVE JUMPER
BOILER
ZONE3
120 VOLT CIRCULATORS
24 VAC POWER
24 VAC POWER
X
PRIORITY OFF
REMOVE JUMPER
TO: "TT" ON BOILER
H N 120 VAC INPUT
SR501 Switching Relay Controlling 2 SR504/506 Switching Relays AQUASTAT ON
A
MASTER
DHW HEATER
24 R W VAC COM T T
SR501
1 ZONE SWITCHING RELAY
POWER T STAT
4 4 5 5 6 N H 3 N/O N/C N/C N/O
JUMPER
120 VAC INPUT
DHW CIRCULATOR
T
SLAVE
T
T
T
ZONE 4 PRIORITY ON OFF
SR 504
T
SLAVE
PRIORITY OFF
SR 504
ZONE 1 ZONE 2 ZONE 3 ZONE 4
T
T
T
PRIORITY OFF ZONE 4 PRIORITY ON OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER
120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
X
ZONE4 POWER
120 VOLT CIRCULATORS
X
ZC ZR END SWITCH
INPUT
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
FUSE 1 AMP
REMOVE JUMPER
BOILER
120V RELAY
120 VAC POWER
REMOVE JUMPER
TO: "TT" ON BOILER
H N
9
120 VAC INPUT
2 Expandable Switching Relays Connected Together
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
THERMOSTATS
T
SLAVE SLAVE
PLUG-IN CARDS MASTER
EXPANSION
POWER CONTROL INTERFACE
ZONE 4 PRIORITY ON OFF
1 2 3 4
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SR504-EXP FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET NORMAL
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
120V RELAY
SR 504-EXP
POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
120 VAC INPUT
JUMPER
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On THERMOSTATS
T
MASTER PLUG-IN CARDS
SLAVE
POWER CONTROL INTERFACE
A
MASTER
1 2 3 4
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
EXPANSION
RESET
24 VAC
NORMAL
AQUASTAT ON DHW HEATER
ZONE 6 PRIORITY ON OFF
SR 506-EXP SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
120V RELAY
POWER
X
X
END SWITCH
ZC ZR
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
120 VOLT CIRCULATORS
POWER INPUT
FUSE 1 AMP
H JUMPER
N
TO: "TT" ON BOILER
BOILER
10
120 VAC INPUT
DHW CIRCULATOR
3 Expandable Switching Relays Connected Together SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On SLAVE
PLUG-IN CARDS 1 2 3 4
MASTER POWER CONTROL INTERFACE
AQUASTAT ON DHW HEATER
A
T
EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
MASTER
SR504-EXP RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
120V RELAY
SR 504-EXP
POWER
X
X
END SWITCH
ZC ZR
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
120 VAC INPUT
JUMPER
TO: "TT" ON BOILER
BOILER
DHW CIRCULATOR
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
SWITCH SETTINGS
T
SLAVE SLAVE
PLUG-IN CARDS 1 2 3 4
MASTER POWER CONTROL INTERFACE
EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
T
Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
ZONE 4 PRIORITY ON OFF
PLUG-IN CARDS
SLAVE
POWER CONTROL INTERFACE
MASTER
1 2 3 4
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
EXPANSION
SR504-EXP RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET
NORMAL
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER
120V RELAY
X
24 VAC POWER
SR 504-EXP
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
X
X
END SWITCH
INPUT
FUSE 1 AMP
ZC ZR
ZONE 6 PRIORITY ON OFF
SR 506-EXP SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
120V RELAY
ZONE4 POWER
120 VOLT CIRCULATORS
SLAVE
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
120 VOLT CIRCULATORS
POWER INPUT
FUSE 1 AMP
H
JUMPER
JUMPER 120 VAC INPUT
11
120 VAC INPUT
N
12
2 Indirect Water Heaters with Priority Connected to Standard Switching Relays AQUASTATS ON DHW HEATERS
MASTER
A
A PRIORITY OFF
24 VAC POWER
SR 502
ZONE1
ZONE2
ZONE3
TWO ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
POWER ZONE 1 ZONE 2
N P ZC H
X2 X1 ZR ZONE1 ZONE2
ZONE3
JUMPERS
T
SLAVE
SR 504
T
T
T
SLAVE ZONE 4 PRIORITY ON OFF
T
T ZONE 4 PRIORITY ON OFF
PRIORITY ON
SR 504
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 1 ZONE 2 ZONE 3 ZONE 4
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
PRIORITY ON
24 V AC
120V RELAY
120V RELAY
POWER
POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
X
ZC ZR END SWITCH
INPUT
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
FUSE 1 AMP
JUMPER
BOILER
X
ZONE4 POWER
120 VOLT CIRCULATORS
ZONE NOT USED
JUMPER ZONE NOT USED
TO: "TT" ON BOILER
H N 120 VAC INPUT
2 Indirect Water Heaters with Priority Connected to EXP Switching Relays A
AQUASTATS ON DHW HEATERS
A
PRIORITY OFF
24 VAC POWER
SR 502
ZONE1
ZONE2
ZONE3
TWO ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
POWER ZONE 1 ZONE 2
N P ZC H
X2 X1 ZR ZONE1 ZONE2
JUMPERS
ZONE3
DHW CIRCULATORS
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On
T
T
MASTER SLAVE
PLUG-IN CARDS 1 2 3 4
MASTER POWER CONTROL INTERFACE
EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SLAVE SLAVE
ZONE 4 PRIORITY ON OFF
MASTER POWER CONTROL INTERFACE
SR504-EXP RESET NORMAL
PLUG-IN CARDS
1 2 3 4
ZONE 1 ZONE 2 ZONE 3 ZONE 4
EXPANSION
ZONE 4 PRIORITY ON OFF
SR504-EXP
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER
120V RELAY
X
X
END SWITCH
SR 504-EXP ZC ZR
ZONE1 ZONE2
ZONE3
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
120V RELAY
120 VOLT CIRCULATORS
FUSE 1 AMP
SR 504-EXP
POWER
X
ZONE4 POWER
X
END SWITCH
INPUT
ZC ZR
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
JUMPER
JUMPER
TO: "TT" ON BOILER
BOILER
13
ZONE NOT USED
H 120 VAC INPUT
N
14
PC700 Boiler Reset Control Connected to EXP Switching Relay
OUTDOOR SENSOR
SWITCH SETTINGS
THERMOSTATS
Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
PC700 SLAVE BOIL OUT SEN SEN
ZONE CONTROL
1234
PLUG-IN CARDS
MASTER POWER CONTROL INTERFACE
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP
BOILER SENSOR
RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER
120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP H
JUMPER TO: "TT" ON BOILER
BOILER
120 VAC INPUT N
PC702 2–Stage Boiler Reset Control Connected to EXP Switching Relay OUTDOOR SENSOR
DHW DEMAND
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
PC702
THERMOSTATS
T
STAGE STAGE BOIL OUT ZONE 1 2 SEN SEN CONTROL
SLAVE
1234
BOILER SENSOR
PLUG-IN CARDS
MASTER POWER CONTROL INTERFACE
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER
120V RELAY
X
BOILER #1
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP H
JUMPER
120 VAC INPUT N
BOILER #2
15
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
SYSTEM CIRCULATOR (OPTIONAL)
16
PC705 Variable Speed Pump Injection Control Connected to EXP Switching Relay
SWITCH SETTINGS OUTDOOR SENSOR
(SEE NOTE B) RED
BLUE
SYSTEM CIRCULATOR AND/OR BOILER
SLAVE
ZONE CONTROL
BLACK
1234
T PLUG-IN CARDS
MASTER
PC705-2 BOIL SUP OUT SEN SEN SEN
THERMOSTATS
Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
GREEN/GROUND
ZONE 1 ZONE 2 ZONE 3 ZONE 4
INJECTION CIRCULATOR
ZONE 4 PRIORITY ON OFF
SR 504-EXP RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
SUPPLY SENSOR BOILER SENSOR
24 VAC POWER
120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
JUMPER TO: "TT" ON BOILER
BOILER
SYSTEM CIRCULATOR AND/OR BOILER (SEE NOTE A)
N
120 VAC INPUT NOTE A: WHEN SYSTEM CIRCULATOR IS CONNECTED TO ZR TERMINAL ON SWITCHING RELAY, THE MODE SWITCH MUST BE SET TO NORMAL. THE PC705-2 WILL NOT RESET THE BOILER WHEN IN THE NORMAL MODE. NOTE B: WHEN SYSTEM CIRCULATOR IS CONNECTED TO RED WIRE ON PC705-2, THE CIRCULATOR WILL OPERATE ONLY WHEN THERMOSTAT CALLS FOR HEAT AND THE OUTDOOR TEMPERATURE IS BELOW THE WARM WEATHER SHUT DOWN (WWSD) TEMPERATURE. THE WWSD CAN BE ADJUSTED OR TURNED OFF SO THAT THE CIRCULATOR IS NOT AFFECTED BY OUTDOOR TEMPERATURE.
H
PC700 Boiler Reset Control Connected to 2 EXP Switching Relays
OUTDOOR SENSOR
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
PC700
T
SLAVE
MASTER
PLUG-IN CARDS
ZONE 4 PRIORITY ON OFF
1 2 3 4
MASTER
ZONE CONTROL
BOIL OUT SEN SEN
THERMOSTATS
EXPANSION
POWER CONTROL INTERFACE
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SR 504-EXP
BOILER SENSOR
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET NORMAL
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
120V RELAY
POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
TO: "TT" ON BOILER
JUMPER 120 VAC INPUT
BOILER
SWITCH SETTINGS THERMOSTATS
Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
T SLAVE
SLAVE
PLUG-IN CARDS MASTER
POWER CONTROL INTERFACE
1 2 3 4 EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
120V RELAY
24 VAC POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
H
JUMPER
N 120 VAC INPUT
SYSTEM CIRCULATOR (OPTIONAL)
17
PC702 2–Stage Boiler Reset Control Connected to 2 EXP Switching Relays
OUTDOOR SENSOR
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
DHW DEMAND
THERMOSTATS
T MASTER
PC702
SLAVE
STAGE STAGE BOIL OUT ZONE 1 2 SEN SEN CONTROL
PLUG-IN CARDS
ZONE 4 PRIORITY ON OFF
1 2 3 4
MASTER
EXPANSION
POWER CONTROL INTERFACE
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SR 504-EXP
BOILER SENSOR
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET NORMAL
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
120V RELAY
POWER
X
BOILER #1
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
120 VAC INPUT
JUMPER
BOILER #2
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
THERMOSTATS
T
SLAVE MASTER POWER CONTROL INTERFACE
SLAVE
PLUG-IN CARDS 1 2 3 4 EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER
120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
H JUMPER
N 120 VAC INPUT
SYSTEM CIRCULATOR (OPTIONAL)
18
PC705 Variable Speed Pump Injection Control Connected to 2 EXP Switching Relays
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off OUTDOOR SENSOR
THERMOSTATS
T MASTER
GREEN/GROUND (SEE NOTE B ON PAGE 16)
SLAVE
PLUG-IN CARDS 1 2 3 4
MASTER
RED
EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SYSTEM CIRCULATOR
BLUE
SR 504-EXP
PC705-2
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET NORMAL BOIL SUP OUT SEN SEN SEN
ZONE CONTROL
BLACK
ZONE 4 PRIORITY ON OFF
INJECTION CIRCULATOR
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
SUPPLY SENSOR
24 VAC BOILER SENSOR
120V RELAY
POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER INPUT
120 VOLT CIRCULATORS
FUSE 1 AMP
JUMPER TO: "TT" ON BOILER
120 VAC INPUT
BOILER
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
THERMOSTATS
T SLAVE
SLAVE
PLUG-IN CARDS MASTER
POWER CONTROL INTERFACE
1 2 3 4 EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER
120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
H JUMPER
N 120 VAC INPUT
SYSTEM CIRCULATOR (OPTIONAL) (SEE NOTE A ON PAGE 16)
19
PC700 and PC705 Controls Connected to 2 EXP Switching Relays OUTDOOR SENSOR
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
THERMOSTATS
T MASTER
SLAVE
PC700
1 2 3 4
MASTER
ZONE CONTROL
BOIL OUT SEN SEN
PLUG-IN CARDS
EXPANSION
POWER CONTROL INTERFACE
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP
BOILER SENSOR
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET NORMAL
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
120V RELAY
POWER
X
X
ZONE1 ZONE2
ZC ZR END SWITCH
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
120 V AC INPUT
JUMPER
TO: "TT" ON BOILER
BOILER
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority OUTDOOR SENSOR
THERMOSTATS
GREEN/GROUND
T
(SEE NOTE B ON PAGE 16)
SLAVE
RED
BLUE
SYSTEM CIRCULATOR
PC705-2 BOIL SUP OUT SEN SEN SEN
ZONE CONTROL
BLACK
SLAVE
PLUG-IN CARDS MASTER
1 2 3 4 EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP
INJECTION CIRCULATOR
RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
SUPPLY SENSOR BOILER SENSOR
24 VAC POWER
120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP JUMPER
SYSTEM CIRCULATOR (OPTIONAL LOCATION) (SEE NOTE A ON PAGE 16)
H N 120 VAC INPUT
20
PC702 and PC705 Controls Connected to 2 EXP Switching Relays SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
OUTDOOR SENSOR
THERMOSTATS
T MASTER
DHW DEMAND
SLAVE
PC702
PLUG-IN CARDS 1 2 3 4
MASTER
EXPANSION
POWER CONTROL INTERFACE
STAGE STAGE BOIL OUT ZONE 1 2 SEN SEN CONTROL
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 PRIORITY ON OFF
SR 504-EXP FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
RESET NORMAL BOILER SENSOR
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC
120V RELAY
POWER
X
X
ZONE1 ZONE2
ZC ZR END SWITCH
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
BOILER #1
FUSE 1 AMP
120 VAC INPUT
JUMPER
BOILER #2 WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority OUTDOOR SENSOR
THERMOSTATS
T
GREEN/GROUND (SEE NOTE B ON PAGE 16)
SLAVE SLAVE
PLUG-IN CARDS
RED
BLUE
SYSTEM CIRCULATOR
MASTER
1 2 3 4 EXPANSION
ZONE 1 ZONE 2 ZONE 3 ZONE 4
PC705-2 BOIL SUP OUT SEN SEN SEN
ZONE CONTROL
BLACK
ZONE 4 PRIORITY ON OFF
SR 504-EXP
INJECTION CIRCULATOR
RESET NORMAL
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
SUPPLY SENSOR BOILER SENSOR
24 VAC POWER
120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP JUMPER
SYSTEM CIRCULATOR (OPTIONAL LOCATION) (SEE NOTE A ON PAGE 16)
H N 120 VAC INPUT
21
N
120 VAC INPUT BLACK
THERMOSTAT
THERMOSTAT
THERMOSTAT
T
T
T
24 VAC
24 VAC
WHITE
T T ZONE 1 FUSE (5 AMP MAX)
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
POWER IN
H
WHITE
FACTORY INSTALLED TRANSFORMER
22
ZVC403/405 with System Pump
24 VAC
END SWITCH
N/O COM N/C
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
ZVC 405 FIVE ZONE ZONE VALVE CONTROL
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
JUMPER 3&4 TO BOILER AQUASTAT RELAY 1 2 3
BOILER SYSTEM PUMP
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 POWER
N
THERMOSTAT
THERMOSTAT
T
T
T
AQUASTAT ON DHW HEATER
A
24 VAC
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF ON
T T ZONE 1 FUSE (7 AMP MAX)
FACTORY INSTALLED TRANSFORMER
WHITE 120 VAC INPUT BLACK
THERMOSTAT
24 VAC
POWER IN
H
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
ZVC404/406 with System Pump
24 VAC
EXTRA MAIN END END SWITCH SWITCH
N/O COM N/C ZONE 6 RELAY
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 TO BOILER AQUASTAT RELAY DRY CONTACTS
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SEE NOTE
PRIORITY ZONE 1 2 3
BOILER SYSTEM PUMP
VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4
ZVC 406
ZONE 1 1 2 3 4
T STAT 1
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
23
N
THERMOSTAT
THERMOSTAT
T
T
T
AQUASTAT ON DHW HEATER
A
24 VAC
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF ON
T T ZONE 1 FUSE (7 AMP MAX)
FACTORY INSTALLED TRANSFORMER
WHITE 120 VAC INPUT BLACK
THERMOSTAT
24 VAC
POWER IN
H
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
24
ZVC404/406 with Domestic Hot Water (DHW) Pump
24 VAC
EXTRA MAIN END END SWITCH SWITCH
N/O COM N/C ZONE 6 RELAY
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 TO BOILER AQUASTAT RELAY
VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4
ZVC 406
ZONE 1 1 2 3 4
T STAT 1
VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SEE NOTE
PRIORITY ZONE 1 2 3
BOILER DHW PUMP
BOILER TURNS ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
N
THERMOSTAT
THERMOSTAT
T
T
T
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF ON
T T ZONE 1
24 VAC
EXTRA MAIN END END SWITCH SWITCH
N/O COM N/C ZONE 6 RELAY
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4
ZVC 406
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 TO BOILER AQUASTAT RELAY
BOILER
AQUASTAT ON DHW HEATER
A
24 VAC
FUSE (7 AMP MAX)
FACTORY INSTALLED TRANSFORMER
WHITE 120 VAC INPUT BLACK
THERMOSTAT
24 VAC
POWER IN
H
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
ZVC404/406 with System and DHW Pumps
VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SEE NOTE
PRIORITY ZONE 1 2 3
SYSTEM PUMP DHW PUMP
2 WIRE ZONE VALVE (NO END SWITCH)
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
25
N
THERMOSTAT
THERMOSTAT
T
T
T
AQUASTAT ON DHW HEATER
A
24 VAC
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF ON
T T ZONE 1
T T ZONE 2
FUSE (7 AMP MAX)
FACTORY INSTALLED TRANSFORMER
WHITE 120 VAC INPUT BLACK
THERMOSTAT
24 VAC
POWER IN
H
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
26
ZVC404/406 with System, DHW and Secondary Pumps
24 VAC
EXTRA MAIN END END SWITCH SWITCH
N/O COM N/C ZONE 6 RELAY
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
TO BOILER AQUASTAT RELAY
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4
ZVC 406
ZONE 1 1 2 3 4
T STAT 1
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4
VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SEE NOTE
PRIORITY ZONE
BOILER
1 2 3
SYSTEM PUMP DHW PUMP
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
SECONDARY PUMP
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS. SECONDARY PUMP COMES ON WHEN ANY ZONE CALLS EXCEPT PRIORITY ZONE.
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
2 ZVC404/406 Connected Together with Priority
THERMOSTAT
THERMOSTAT
THERMOSTAT
T
T
T
Note: When a circulator is used on the priority o z ne instead of a o z ne valve, jumper 3 and 4 of the priority o z ne.
H
WHITE 120 VAC INPUT BLACK
ZONE 4 PRIORITY
MODE
NORMAL RESET
24 VAC
OFF
PRIORITY ON
ON
T T ZONE 1
POWER IN
T T ZONE 2
FUSE (3 AMP MAX)
EXTRA MAIN END END SWITCH SWITCH
T T ZONE 3
T T ZONE 4
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3
ZVC 404 FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
ZONE 1 1 2 3 4
N/O COM N/C ZONE 4 RELAY
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
VALVE 3 T STAT 4 VALVE 4 POWER ZONE 4 1 2 3 4
TO BOILER AQUASTAT RELAY JUMPER 3&4
JUMPER 3&4
SEE NOTE
PRIORITY ZONE 1 2 3
DRY CONTACTS
MOTOR
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
THERMOSTAT
THERMOSTAT
THERMOSTAT
T
T
T
AQUASTAT ON DHW HEATER
A
24 VAC
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
N
FACTORY INSTALLED TRANSFORMER
24 VAC
ZONE 4 PRIORITY
MODE
NORMAL RESET
24 VAC
OFF ON
T T ZONE 1
POWER IN
FUSE (3 AMP MAX)
EXTRA MAIN END END SWITCH SWITCH
N/O COM N/C ZONE 4 RELAY
T T ZONE 2
T T ZONE 3
T T ZONE 4
ZVC 404
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
VALVE 3 T STAT 4 VALVE 4 POWER ZONE 4 1 2 3 4
JUMPER 3&4
JUMPER 3&4
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3
FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
TO BOILER AQUASTAT RELAY
BOILER
PRIORITY ON
SEE NOTE
PRIORITY ZONE 1 2 3
DRY CONTACTS
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
27
2 EXP Zone Valve Controls Connected Together with System Pump
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On
T
T 24 VAC
SLAVE POWER CONTROLS
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
MASTER 120 VAC INPUT BLACK
AQUASTAT ON DHW HEATER
A
T
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
ZONE 1 1 2 3 4
END SWITCH A BOILER
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
POWER ON
JUMPER 3&4
JUMPER 3&4 TO BOILER AQUASTAT RELAY
MOTOR
1 2 3
BOILER
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
SYSTEM PUMP
VALVE 6
END SWITCH
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
N H
120 VAC INPUT
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
T
T
T
SLAVE POWER CONTROLS
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
28
T T ZONE 4
ZVC 406-EXP FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
SLAVE
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
VALVE 6 POWER ON
SEE NOTE
2 EXP Zone Valve Controls Connected Together with DHW Pump
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On
T
T 24 VAC
SLAVE POWER CONTROLS
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
MASTER 120 VAC INPUT BLACK
AQUASTAT ON DHW HEATER
A
T
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
ZONE 1 1 2 3 4
END SWITCH A BOILER
TO BOILER AQUASTAT RELAY
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
POWER ON
JUMPER 3&4
JUMPER 3&4 MOTOR
1 2 3
BOILER
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
DHW PUMP
VALVE 6
END SWITCH
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
N H
120 VAC INPUT
BOILER TURNS ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
T
T
T
SLAVE POWER CONTROLS
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
SLAVE
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
29
2 EXP Zone Valve Controls Connected Together with System and DHW Pumps
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On
T
T 24 VAC
SLAVE POWER CONTROLS
1 2 3 4
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
ZONE 1 1 2 3 4
END SWITCH A BOILER
TO BOILER AQUASTAT RELAY
BOILER
T T ZONE 2
ZVC 406-EXP FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
MASTER 120 VAC INPUT BLACK
AQUASTAT ON DHW HEATER
A
T
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
POWER ON
JUMPER 3&4
JUMPER 3&4 MOTOR
1 2 3
SYSTEM PUMP
DHW PUMP
VALVE 6
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
END SWITCH
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
N H
120 VAC INPUT
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
T
T
T
SLAVE POWER CONTROLS
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
30
T T ZONE 4
ZVC 406-EXP FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
SLAVE
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
VALVE 6 POWER ON
SEE NOTE
2 EXP Zone Valve Controls Connected Together with System, DHW and Secondary Pumps
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On
T
T 24 VAC
SLAVE POWER CONTROLS
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
24 VAC
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
DHW PUMP
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
ZONE 1 1 2 3 4
END SWITCH A BOILER
TO BOILER AQUASTAT RELAY
BOILER
T T ZONE 2
ZVC 406-EXP FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
MASTER 120 VAC INPUT BLACK
AQUASTAT ON DHW HEATER
A
T
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
MOTOR
1 2 3
SECONDARY PUMP
POWER ON
JUMPER 3&4
JUMPER 3&4
SYSTEM PUMP
VALVE 6
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
END SWITCH
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
N H
120 VAC INPUT
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS. SECONDARY PUMP TURNS ON WHEN ANY ZONE CALLS, EXCEPT PRIORITY ZONE.
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
T
T
T
SLAVE POWER CONTROLS
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
24 VAC
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
SLAVE
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
31
32
PC700 Boiler Reset Control Connected To EXP Zone Valve Control OUTDOOR SENSOR
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
PC700
THERMOSTAT
THERMOSTAT
THERMOSTAT
T
T
T
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
ZONE CONTROL
BOIL OUT SEN SEN
BOILER SENSOR
24 VAC
SLAVE POWER CONTROLS
120 VAC INPUT BLACK
24 VAC
TO BOILER AQUASTAT RELAY
TACO, INC ZVC406-EXP
WHITE
FACTORY INSTALLED TRANSFORMER
MODE RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
END SWITCH A BOILER
DRY CONTACTS
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
SYSTEM CIRCULATOR
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
2 WIRE ZONE VALVE (NO END SWITCH)
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
BOILER
T T ZONE 4
ZVC 406-EXP FUSE 7 AMP MAX
120 VAC INPUT BLACK
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
24 VAC
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H N SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
PC702 2–Stage Boiler Reset Control Connected To EXP Zone Valve Control OUTDOOR SENSOR
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
DHW DEMAND
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
PC702
THERMOSTAT
THERMOSTAT
THERMOSTAT
T
T
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
STAGE STAGE BOIL OUT ZONE 1 2 SEN SEN CONTROL
T
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW BOILER SENSOR
BLACK
24 VAC
SLAVE POWER CONTROLS
BLACK
BOILER #1
TACO, INC ZVC406-EXP
120 VAC INPUT
24 VAC
WHITE
FACTORY INSTALLED TRANSFORMER
MODE RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
1 2 3
SYSTEM CIRCULATOR
DHW CIRCULATOR
2 WIRE ZONE VALVE (NO END SWITCH)
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4
BOILER #2
OFF
ZVC 406-EXP FUSE 7 AMP MAX
120 VAC INPUT
ZONE 6 PRIORITY ON
PLUG-IN CARDS POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
24 VAC
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H N SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
33
34
PC705 Variable Speed Pump Injection Control Connected To EXP Zone Valve Control
OUTDOOR SENSOR
GREEN/GROUND
SYSTEM CIRCULATOR
RED
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
(SEE NOTE B ON PAGE 16) BLUE
PC705-2 BOIL SUP OUT SEN SEN SEN
Note: When a circulator is used on the priority o z ne instead of a o z ne valve, jumper 3 and 4 of the priority o z ne.
INJECTION CIRCULATOR
THERMOSTAT
THERMOSTAT
THERMOSTAT
T
T
T
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
BLACK
ZONE CONTROL
SUPPLY SENSOR
24 VAC
24 VAC
SLAVE POWER CONTROLS
24 VAC
TO BOILER AQUASTAT RELAY
TACO, INC ZVC406-EXP
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
MODE
WHITE
ZONE 6 PRIORITY ON
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
120 VAC INPUT BLACK
PLUG-IN CARDS POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
BOILER SENSOR
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
END SWITCH A BOILER
DRY CONTACTS
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
SYSTEM CIRCULATOR (OPTIONAL LOCATION)
ZONE 5 1 2 3 4
2 WIRE ZONE VALVE (NO END SWITCH)
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
BOILER
ZONE 4 1 2 3 4
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H N SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
PC700 Boiler Reset Control Connected To 2 EXP Zone Valve Controls
OUTDOOR SENSOR
Note: When a circulator is used on the priority o z ne instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
PC700 ZONE CONTROL
T
BOILER SENSOR
T
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
ZONE 6 PRIORITY ON
PLUG-IN CARDS
24 VAC
SLAVE POWER CONTROLS
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
MODE
WHITE
T
24 VAC
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
T STAT 1
OFF
VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
MASTER POWER IN
BOIL OUT SEN SEN
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
ZONE 1 1 2 3 4
END SWITCH A BOILER
N/O COM N/C ZONE 6 RELAY
TO BOILER AQUASTAT RELAY
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
MOTOR
1 2 3
BOILER
DHW CIRCULATOR
POWER ON
JUMPER 3&4
JUMPER 3&4
SYSTEM CIRCULATOR
VALVE 6
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
SEE NOTE
PRIORITY ZONE
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H N
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
T
120 VAC INPUT BLACK
T ZONE 6 PRIORITY ON
SLAVE POWER CONTROLS
MODE
24 VAC
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
WHITE
FACTORY INSTALLED TRANSFORMER
BLACK
POWER IN
120 VAC INPUT
T 24 VAC
PLUG-IN CARDS
24 VAC
TACO, INC ZVC406-EXP
WHITE
FACTORY INSTALLED TRANSFORMER
SLAVE
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
ZONE 6 1 2 3 4
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
35
PC702 2–Stage Boiler Reset Control Connected To 2 EXP Zone Valve Controls
OUTDOOR SENSOR
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
DHW DEMAND
PC702
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
STAGE STAGE BOIL OUT ZONE 1 2 SEN SEN CONTROL
T
BOILER SENSOR
T
SLAVE POWER CONTROLS
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
RESET
1 2 3 4
ZONE 6 PRIORITY ON
T T ZONE 1
EXPANSION MASTER NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
24 VAC
MODE
WHITE
T
24 VAC PLUG-IN CARDS
POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
MASTER
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
ZONE 1 1 2 3 4
END SWITCH A BOILER
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
MOTOR
1 2 3
SYSTEM CIRCULATOR
DHW CIRCULATOR
POWER ON
JUMPER 3&4
JUMPER 3&4
BOILER #1
VALVE 6
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
END SWITCH
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H N
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS. BOILER #2
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
T
T
SLAVE
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
ZONE 6 PRIORITY ON
POWER CONTROLS
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
2 WIRE ZONE VALVE (NO END SWITCH)
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
36
T T ZONE 4
ZVC 406-EXP FUSE 7 AMP MAX
24 VAC
MODE
WHITE
T
24 VAC PLUG-IN CARDS
POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
SLAVE
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
VALVE 6 POWER ON
SEE NOTE
PC705 Variable Speed Pump Injection Control Connected To 2 EXP Zone Valve Controls
OUTDOOR SENSOR
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
GREEN/GROUND
(SEE NOTE B ON PAGE 16)
RED
SYSTEM CIRCULATOR
Note: When a circulator is used on the priority o z ne instead of a o z ne valve, jumper 3 and 4 of the priority o z ne.
BLUE
PC705-2
INJECTION CIRCULATOR
BLACK BOIL SUP OUT SEN SEN SEN
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
ZONE CONTROL
T
SUPPLY SENSOR
T
BLACK
24 VAC
SLAVE POWER CONTROLS
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
BLACK
24 VAC
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
MODE
WHITE
ZONE 6 PRIORITY ON
PLUG-IN CARDS
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
WHITE 120 VAC INPUT
POWER IN
FACTORY INSTALLED TRANSFORMER
BOILER SENSOR
T
24 VAC
MASTER
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
ZONE 1 1 2 3 4
END SWITCH A BOILER
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
MOTOR
1 2 3
BOILER
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
SYSTEM CIRCULATOR (OPTIONAL LOCATION)
VALVE 6 POWER ON
JUMPER 3&4
JUMPER 3&4
DRY CONTACTS
TO BOILER AQUASTAT RELAY
ZONE 2 1 2 3 4
END SWITCH
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H N
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
T
T
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
BLACK
ZONE 6 PRIORITY ON
PLUG-IN CARDS
24 VAC
SLAVE POWER CONTROLS
MODE
WHITE
T
24 VAC
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
120 VAC INPUT BLACK
POWER IN
WHITE
FACTORY INSTALLED TRANSFORMER
SLAVE
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
ZONE 6 1 2 3 4
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
37
PC700 and PC705 Connected To 2 EXP Zone Valve Controls OUTDOOR SENSOR
Note: When a circulator is used on the priority o z ne instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
PC700 ZONE CONTROL
T
BOILER SENSOR
T
24 VAC
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
ZONE 6 PRIORITY ON
PLUG-IN CARDS
SLAVE POWER CONTROLS
MODE
WHITE
T
24 VAC
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
T STAT 1
OFF
VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
MASTER POWER IN
BOIL OUT SEN SEN
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
ZONE 1 1 2 3 4
END SWITCH A BOILER
N/O COM N/C ZONE 6 RELAY
TO BOILER AQUASTAT RELAY
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
POWER ON
JUMPER 3&4
JUMPER 3&4 MOTOR
1 2 3
BOILER
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH) SYSTEM CIRCULATOR
VALVE 6
SEE NOTE
PRIORITY ZONE
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
DHW CIRCULATOR
H N OUTDOOR SENSOR
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
GREEN/GROUND
(SEE NOTE B ON PAGE 16) SYSTEM CIRCULATOR
RED
BLUE
PC705-2 BOIL SUP OUT SEN SEN SEN
INJECTION CIRCULATOR
ZONE CONTROL
BLACK
SUPPLY SENSOR BOILER SENSOR
T
120 VAC INPUT BLACK
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
POWER IN
SLAVE POWER CONTROLS
24 VAC
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
38
T ZONE 6 PRIORITY ON
T T ZONE 1
EXPANSION MASTER
MODE RESET
1 2 3 4
FUSE 7 AMP MAX
WHITE
FACTORY INSTALLED TRANSFORMER
BLACK
T 24 VAC
PLUG-IN CARDS
24 VAC
TACO, INC ZVC406-EXP
WHITE 120 VAC INPUT
FACTORY INSTALLED TRANSFORMER
SLAVE
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
VALVE 6 POWER ON
SEE NOTE
PC702 and PC705 Connected To 2 EXP Zone Valve Controls SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
OUTDOOR SENSOR
DHW DEMAND
PC702
Note: When a circulator is used on the priority zone instead of a o z ne valve, jumper 3 and 4 of the priority o z ne.
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
STAGE STAGE BOIL OUT ZONE 1 2 SEN SEN CONTROL
T
BOILER SENSOR
T
SLAVE POWER CONTROLS
RESET
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
24 VAC
BOILER #1 120 VAC INPUT BLACK
ZONE 6 PRIORITY ON
1 2 3 4
T T ZONE 1
EXPANSION MASTER
NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
T STAT 1
OFF
VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
24 VAC
MODE
WHITE
T
24 VAC PLUG-IN CARDS
POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
MASTER
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
ZONE 1 1 2 3 4
END SWITCH A BOILER
N/O COM N/C ZONE 6 RELAY
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
MOTOR
1 2 3
SYSTEM CIRCULATOR
DHW CIRCULATOR
POWER ON
JUMPER 3&4
JUMPER 3&4
BOILER #2
VALVE 6
TACO 3 WIRE ZONE VALVE
2 WIRE ZONE VALVE (NO END SWITCH)
END SWITCH
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H N OUTDOOR SENSOR
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
GREEN/GROUND
(SEE NOTE B ON PAGE 16)
RED
SYSTEM CIRCULATOR
BLUE
PC705-2
INJECTION CIRCULATOR
BLACK BOIL SUP OUT SEN SEN SEN
ZONE CONTROL
SUPPLY SENSOR BOILER SENSOR
T
T
SLAVE
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
24 VAC
TACO, INC ZVC406-EXP
FACTORY INSTALLED TRANSFORMER
120 VAC INPUT BLACK
ZONE 6 PRIORITY ON
POWER CONTROLS
RESET
1 2 3 4
T T ZONE 1
EXPANSION MASTER NORMAL
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2
ZVC 406-EXP
VALVE 2
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
FUSE 7 AMP MAX
24 VAC
MODE
WHITE
T
24 VAC PLUG-IN CARDS
POWER IN
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
SLAVE
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
DRY CONTACTS
END SWITCH A BOILER
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
JUMPER 3&4
JUMPER 3&4 1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
ZONE 6 1 2 3 4
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
39
HAFC101 with 1 Speed Air Handler
THERMOSTAT
T
Optional Power Wire to Thermostat that Requires 24VAC
To: Aquastat on Return Line of Hydro Coil
C R W Y G T T THERMOSTAT
AQUASTAT
Power On Call for Heat Fan, Cooling Fan, Heating
HAFC101 HYDRO AIR FAN CONTROL
BOILER
AIR HANDLER
X X C R Y G G
LOW HIGH
Dry Contacts To: “T T” on Boiler or Switching Relay
24 VAC
Jumper
Line
Fan Relay
Outdoor Condenser Unit
M
HAFC 101 WITH 1 SPEED AIR HANDLER (Both HFC 101 and HAFC 201 are capable of 1 and 2 speed applications.)
40
HAFC101 with 2 Speed Air Handler
THERMOSTAT
T To: Aquastat on Return Line of Hydro Coil
Optional Power Wire to Thermostat that Requires 24VAC
C R W Y G T T THERMOSTAT
AQUASTAT
Power On Call for Heat Fan, Cooling Fan, Heating
HAFC101 HYDRO AIR FAN CONTROL
BOILER
AIR HANDLER
X X C R Y G G
Line
Fan Relays
High
Low
Dry Contacts To: “T T” on Boiler or Switching Relay
24 VAC
LOW HIGH
Outdoor Condenser Unit
M
HAFC 101 WITH 2 SPEED AIR HANDLER (Both HFC 101 and HAFC 201 are capable of 1 and 2 speed applications.)
41
HAFC201 with 1 Speed Air Handler
To: Optional Aquastat on Return Line of Hydro Coil
THERMOSTAT
T Optional Power Wire to Thermostat that Requires 24VAC
To: Optional Aquastat or Thermostat to sense low ambient temperature
C R W Y G T T T T THERMOSTAT
WATER COIL FREEZE PR AQUASTATS
Power On Call for Heat Fan, Cooling Fan, Heating
HAFC201 HYDRO AIR FAN CONTROL OFF
DRY CONTACTS 1 MIN ON DELAY - FAN 3 MIN ON DELAY - FAN 2 MIN @ 24 HR - PUMP 30 SEC @ 2 WK - PUMP
ON
NOTE: For 4 minute on delay of Heating Fan, switch 1 and 3 MIN ON DELAY to ON position.
5 AMP 1/6 HP RATED
PUMP
BOILER
AIR HANDLER
XX X X C R Y G G
LOW HIGH Jumper
Hot Neutral 24 VAC
(or to “T T” on switching relay)
Fan Relay
Dry Contacts To: “T T” on Boiler or Switching Relay
Line
Circulator
Outdoor Condenser Unit
M
HAFC 201 WITH 1 SPEED AIR HANDLER (Both HFC 101 and HAFC 201 are capable of 1 and 2 speed applications.)
42
HAFC201 with 2 Speed Air Handler
To: Optional Aquastat on Return Line of Hydro Coil
THERMOSTAT
T Optional Power Wire to Thermostat that Requires 24VAC
To: Optional Aquastat or Thermostat to sense low ambient temperature
C R W Y G T T T T THERMOSTAT
WATER COIL FREEZE PR AQUASTATS
Power On Call for Heat Fan, Cooling Fan, Heating
HAFC201 HYDRO AIR FAN CONTROL OFF
DRY CONTACTS 1 MIN ON DELAY - FAN 3 MIN ON DELAY - FAN 2 MIN @ 24 HR - PUMP 30 SEC @ 2 WK - PUMP
ON
NOTE: For 4 minute on delay of Heating Fan, switch 1 and 3 MIN ON DELAY to ON position.
5 AMP 1/6 HP RATED
PUMP
BOILER
AIR HANDLER
XX X X C R Y G G
LOW HIGH
Hot
Line
“T T” on Boiler or Switching Relay
Low
Circulator
High
24 VAC
(or to “T T” on switching relay)
Fan Relays
Neutral
Outdoor Condenser Unit
M
HAFC 201 WITH 2 SPEED AIR HANDLER (Both HFC 101 and HAFC 201 are capable of 1 and 2 speed applications.)
43
T
THERMOSTAT
POWER PM CALL FOR HEAT FAN, COOLING FAN, HEATING
AIR HANDLER
BOILER
POWER PM CALL FOR HEAT FAN, COOLING FAN, HEATING
AIR HANDLER
Fan Relays
Low
OUTDOOR CONDENSER UNIT
Line
2 SPEED AIR HANDLER
2 SPEED AIR HANDLER
SR 504
ZONE 1 ZONE 2 ZONE 3 ZONE 4
HIGH
M
2 SPEED AIR HANDLER
ZONE 4 PRIORITY ON OFF
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
DHW HEATER AQUASTAT
120V RELAY
24 VAC POWER
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
JUMPER TO: "TT" ON BOILER
BOILER
POWER PM CALL FOR HEAT FAN, COOLING FAN, HEATING
AIR HANDLER LOW
M
Line
M
HAFC101 HYDRO AIR FAN CONTROL BOILER
High
24 VAC
OUTDOOR CONDENSER UNIT
AQUASTAT
X X C R Y G G
HIGH
LOW
Fan Relays
Low
THERMOSTAT
X X C R Y G G
HIGH
High
24 VAC
LOW
C R W Y G T T
AQUASTAT
HAFC101 HYDRO AIR FAN CONTROL
X X C R Y G G
TO: AQUASTAT ON RETURN LINE OF HYDRO COIL
OPTIONAL POWER WIRE TO THERMOSTAT THAT REQUIRES 24VAC
C R W Y G T T
AQUASTAT
HAFC101 HYDRO AIR FAN CONTROL BOILER
T
TO: AQUASTAT ON RETURN LINE OF HYDRO COIL
OPTIONAL POWER WIRE TO THERMOSTAT THAT REQUIRES 24VAC
High
TO: AQUASTAT ON RETURN LINE OF HYDRO COIL
C R W Y G T T THERMOSTAT
THERMOSTAT
Fan Relays
T
Line
OPTIONAL POWER WIRE TO THERMOSTAT THAT REQUIRES 24VAC
THERMOSTAT
Low
THERMOSTAT
24 VAC
44
Multiple HAFC’s and Switching Relay
120 VAC INPUT
H N
OUTDOOR CONDENSER UNIT
3 Wire Thermostat Connected to TACO Switching Relay
3 WIRE THERMOSTAT
T
COM
T W
SR 504
T
T
R
ZONE 4 PRIORITY ON OFF ZONE 1 ZONE 2 ZONE 3 ZONE 4
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VAC POWER 120V RELAY
X
X
ZC ZR END SWITCH
ZONE1 ZONE2
ZONE3
ZONE4 POWER
120 VOLT CIRCULATORS
INPUT
FUSE 1 AMP
H JUMPER
120 VAC INPUT
N
TO: "TT" ON BOILER
BOILER
45
THERMOSTAT
T
T
T
R RED
W
T T ZONE 1
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
24 VAC
ZVC 405 FIVE ZONE ZONE VALVE CONTROL
T T
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
JUMPER 3&4
RED RED
END SWITCH
BLACK BLACK
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
WHITE
THERMOSTAT
WH
24 VAC
POWER IN
120 VAC INPUT BLACK
THERMOSTAT
C
COMMON
WHITE
FACTORY INSTALLED TRANSFORMER
46
3 Wire Thermostat Connected to TACO Zone Valve Control
TO T&T ON BOILER OR PUMP RELAY 1 2 3 2 WIRE ZONE VALVE (NO END SWITCH)
3 WIRE ZONE VALVE (TACO TYPE)
MOTOR
END SWITCH
4 WIRE ZONE VALVE (HONEYWELL TYPE)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 POWER
White-Rogers 1361 Hydronic Zone Valve with TACO Zone Valve Control
WHITE
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
WHITE
THERMOSTAT
THERMOSTAT
THERMOSTAT
T
T
T
RIGHT TT SCREW (SEE NOTE)
24 VAC
POWER IN
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
NOTE: WHEN USING ZVC 404 OR ZVC 406, CONNECT WIRE #2 OF ZONE VALVE TO PRIORITY ZONE RIGHT TT SCREW
TERMINAL ASSIGNMENT CONTROL ZONE VALVE 1 1 2 TT (Rt) 3 3 4 2
T T ZONE 1
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
24 VAC
ZVC 405 FIVE ZONE ZONE VALVE CONTROL
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
T T
RED RED
ZONE 1 1 2 3 4
BLACK BLACK
END SWITCH
TO T&T ON BOILER OR PUMP RELAY 2 1 4 3
WHITE-ROGERS 1361 HYDRONIC ZONE VALVE
1 2 3 3 WIRE ZONE VALVE (TACO TYPE)
MOTOR
END SWITCH
4 WIRE ZONE VALVE (HONEYWELL TYPE)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 POWER
47
48
Honeywell VC 40 & 80 (spdt) Hydronic Zone Valve with TACO Zone Valve Control
THERMOSTAT
THERMOSTAT
T
T
T
RIGHT TT SCREW (SEE NOTE)
24 VAC
POWER IN
T T ZONE 1
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
24 VAC
ZVC 405 FIVE ZONE ZONE VALVE CONTROL
END SWITCH
ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
BLACK BLACK
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
WHITE
THERMOSTAT
T T
RED RED
WHITE 120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
NOTE: WHEN USING ZVC 404 OR ZVC 406, CONNECT WIRE #3 OF ZONE VALVE TO PRIORITY ZONE RIGHT TT SCREW
TERMINAL ASSIGNMENT ZONE VALVE CONTROL ORANGE 1 3 BLUE 2 1 BROWN 3 TT (Rt) GRAY 4 4 BLACK 6 2
TO T&T ON BOILER OR PUMP RELAY 3 2
6 4 1
HONEYWELL VC (SPST) HYDRONIC ZONE VALVE SERIES 40 & 80
1 2 3 3 WIRE ZONE VALVE (TACO TYPE)
MOTOR
END SWITCH
4 WIRE ZONE VALVE (HONEYWELL TYPE)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 POWER
570 Zone Valve to Switching Relay
T
THERMOSTAT
24 VAC TRANSFORMER 1 2 3
24 VAC POWER
SR 503
ZONE1
ZONE2
ZONE3
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
N P ZC H
POWER ZONE 1 ZONE 2 ZONE 3
X2 X1 ZR ZONE1 ZONE2
ZONE3
JUMPERS
120 VOLT CIRCULATORS TO: 120 VAC POWER (NEUTRAL) TO: 120 VAC POWER (HOT) TO: "TT" ON AQUASTAT CONTROL TO: "TT" ON AQUASTAT CONTROL
49
WHITE
N
120 VAC INPUT BLACK
THERMOSTAT
THERMOSTAT
T
T
T
AQUASTAT ON DHW HEATER
A
24 VAC
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF
T T ZONE 1
24 VAC
EXTRA MAIN END END SWITCH SWITCH
N/O COM N/C ZONE 6 RELAY
T T ZONE 2
T T ZONE 3
T T ZONE 4
T T ZONE 5
VALVE 2 T STAT 3 VALVE 3 T STAT 4
ZVC 406 SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
ZONE 6 1 2 3 4
JUMPER 3&4
TO BOILER AQUASTAT RELAY DRY CONTACTS
VALVE 1 T STAT 2
T T ZONE 6
JUMPER 3&4
SEE NOTE
PRIORITY ZONE MOTOR
END SWITCH
BOILER SYSTEM PUMP
T STAT 1
ON
FUSE (7 AMP MAX)
FACTORY INSTALLED TRANSFORMER
WHITE 120 VAC INPUT BLACK
THERMOSTAT
24 VAC
POWER IN
H
FACTORY INSTALLED TRANSFORMER
50
Zone Valve Control with 1 Low Temperature Zone Using Priority Zoning Circulator
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
1 2 3
MOTOR
END SWITCH
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
TACO 3 WIRE ZONE VALVE
PRIORITY ON
PRIORITY ZONING CIRCULATOR SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
PRIORITY THERMOSTAT 2 1
BOILER 4 3
PRIORITY POWER IN PR-IN PR-OUT LIVE NEUT
120 VAC INPUT
OFF
ON
Instruction Sheet SR501 Switching Relay
Features: External Indicator Lights Universal Replaceability Snap-in PC Board Simplified Wiring Fully Enclosed Snap-Out Relays 100% Factory Tested Contractor Friendly PC Board Layout Universal Thermostat Compatibility UL Approved Extended 3 Year Warranty Made in the USA
Typical Wiring
SR501 1 ZONE SWITCHING RELAY
Operation: Connect a thermostat to the “T T” terminals on the switching relay. When the thermostat calls for heat, the relay is energized and power is given to the circulator.
Alternative THERMOSTAT Wiring
THERMOSTAT
SR501 1 ZONE SWITCHING RELAY
24 R W VAC T T COM
POWER
POWER
T STAT
T STAT
120 VAC INPUT
120 VAC INPUT
4 4 6 6 5 N H 3 N/O N/C N/C N/O
4 4 6 6 5 N H 3 N/O N/C N/C N/O
JUMPER
JUMPER
Power Input: Connect 120 volt ac power to terminals N and H.
TO: ZC TO: TT ON BOILER
TO: 120 VAC POWER
External Diagnostics: The External lights show full functionality of the switching relay. The green light should always be on, indicating that power is connected. When the thermostat calls for heat, both the appropriate circulator and red indicating light is energized.
TACO SR501 REPLACEMNENT CROSS-REFERENCE
Specifications: PRODUCT NUMBER
NUMBER TRANSFORMER OF ZONES VOLTAGE
MAXIMUM COMBINED LOAD
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH
SR501
1 Zone
7.2 amps
4 1/4"
2 3/4"
All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a single phase motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.
MANUFACTURER
MODEL
CONNECTIONS
Taco
SR501
H
N
3
4 NO 4 NC 5
6 NO
Argo
AR821
1
2
3
4
6
5
6 NC
R/T
W/T C
T
AR822
L1 L2 3
4 NO 4 NC 5
6 NO
6 NC
R/T
G/T
Colombus
MR10
L1 L2 3
4 NO 4 NC 5
6 NO
6 NC
R/T
G/T
C
Erie
SR100
L1 L2 3
4 NO 4 NC 5
6 NO
6 NC
R/T
G/T
C
Honeywell
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.
CIRCULATOR
Terminal Description: T&T Thermostat Connection COM Common side of transformer, to power some setback thermostats N Neutral wire of power input H Hot wire of power input 3 Common terminal for 4 n/o and 4 n/c 4 n/o Normally open terminal 4 n/c Normally closed terminal 6 n/c Normally closed terminal 6 n/o Normally open terminal 5 Common terminal for 6 n/o and 6 n/c
The Taco Connection: Combine the reliability of the Taco Zone Valves, Priority Zoning Circulators, Thermostats, and the “00” family of circulators with the advanced features of the Taco Zone Controls to achieve total system integration. No matter the application, Taco now provides the products to maximize system performance while simplifying both installation and service.
5 1/4"
TO: ZR
TO: 120 VAC POWER
CIRCULATOR
Jumper Placement: The jumper is factory installed between terminals H and 3 to switch power on terminals 4 n/o and 4 n/c.
120 VAC Input
24 R W VAC T T COM
White-Rogers
RA89A
1
2
3
4
T
T
RA832A
1
2
3
4
X
X
T
T
R845A
1
2
3
4
5
6
T
T
889-189
1
2
3
4
T
T
829-845
1
2
3
4
T
T
5
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
6
C
Printed in USA Copyright 2000 TACO, Inc.
Visit our web site at: http://www.taco-hvac.com
51
Instruction Sheet SR501-845RP Universal Replacement Relay
THERMOSTAT
THERMOSTAT
Alternative Wiring
REPLACES HONEYWELL R845, RA89A & RA832 OR COMPARABLE RELAY
Typical Wiring
REPLACES HONEYWELL R845, RA89A & RA832 OR COMPARABLE RELAY
Features: Universal Replaceability Indicator Lights Snap-in PC Board to Existing Enclosure Simplified Wiring Fully Enclosed Snap-Out Relay 100% Factory Tested Universal Thermostat Compatibility UL Approved Extended 3 Year Warranty Made in the USA
R W T T
R W T T POWER
POWER
UNIVERSAL REPLACEMENT RELAY MODEL: SR501-845RP
Operation: Connect a thermostat to the “T T” terminals on the switching relay. When the thermostat calls for heat, the relay is energized and power is given to the circulator.
UNIVERSAL REPLACEMENT RELAY MODEL: SR501-845RP
T STAT
T STAT
120 VAC INPUT
120 VAC INPUT
L2 L1 3 4 5 6
L2 L1 3 4 5 6 TO: TT ON BOILER
Power Input: Connect 120 volt ac power to terminals L1 and L2.
TO: ZC
CIRCULATOR
TO: ZR
JUMPER
Jumper Placement: The jumper is factory installed between terminals L1 and 3 to switch power on terminal 4. Diagnostics: The Indicator lights show full functionality of the switching relay. The green light should always be on, indicating that power is connected. When the thermostat calls for heat, both the appropriate circulator and red indicating light is energized. The Taco Connection: Combine the reliability of the Taco Zone Valves, Priority Zoning Circulators, Thermostats, and the “00” family of circulators with the advanced features of the Taco Zone Controls to achieve total system integration. No matter the application, Taco now provides the products to maximize system performance while simplifying both installation and service.
TO: 120 VAC POWER
Specifications: PRODUCT NUMBER
NUMBER OF ZONES
SR501-845RP
1 Zone
Thermostat Connection Neutral wire of power input Hot wire of power input Common terminal for 4 Normally open terminal Normally open terminal Common terminal for 6
TRANSFORMER MAXIMUM VOLTAGE COMBINED LOAD
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH
120 VAC Input
4 1/4"
7.2 amps
CONNECTIONS
Taco
SR501-845RP
L1
L2
3
4
5
6
R/T
Argo
AR821
1
2
3
4
5
6
T
W/T
AR822
L1
L2
3
4 NO
5
6 NO
R/T
G/T
Colombus
MR10
L1
L2
3
4 NO
5
6 NO
R/T
G/T
Erie
SR100
L1
L2
3
4 NO
5
6 NO
R/T
G/T
Honeywell
RA89A
1
2
3
4
T
T
White-Rogers
RA832A
1
2
3
4
X
X
T
T
R845A
1
2
3
4
5
6
T
T
T
T
5
6
T
T
889-189
1
2
3
4
829-845
1
2
3
4
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
52
2 3/4"
TACO SR501-845RP REPLACEMENT CROSS-REFERENCE MANUFACTURER MODEL
Do it Once. Do it Right. Visit our web site at: http://www.taco-hvac.com
5 1/4"
All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a single phase motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.
Terminal Description: T&T L2 L1 3 4 6 5
CIRCULATOR JUMPER
TO: 120 VAC POWER
Printed in USA Copyright 1999 TACO, Inc.
Instruction Sheet SR502 & SR503 Switching Relay THERMOSTATS
THERMOSTATS
Cold Start Boiler Application
Tankless Coil Boiler Application
24 VAC POWER
24 VAC POWER
SR 503
ZONE1
ZONE2
SR 503
ZONE3
ZONE1
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
N P ZC H
ZONE3
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP
POWER ZONE 1 ZONE 2 ZONE 3
X2 X1 ZR ZONE1 ZONE2
ZONE2
N P ZC H
ZONE3
POWER ZONE 1 ZONE 2 ZONE 3
X2 X1 ZR ZONE1 ZONE2
ZONE3
JUMPERS
JUMPERS
TO: 120 VAC POWER (NEUTRAL)
TO: 120 VAC POWER (NEUTRAL)
TO: 120 VAC POWER (HOT)
TO: 120 VAC POWER (HOT) 120 VOLT CIRCULATORS
TO: "TT" ON AQUASTAT CONTROL
TO: "ZC" ON AQUASTAT CONTROL
120 VOLT CIRCULATORS
TO: "ZR" ON AQUASTAT CONTROL
TO: "TT" ON AQUASTAT CONTROL
Operation: When the thermostat calls for heat, the appropriate circulator is energized and the isolated end switch (X1 and X2) will start the boiler.
Operation: When any thermostat calls for heat, the boiler is given a signal to start. The appropriate circulator is energized only when the boiler temperature is above the set low limit.
Jumper Placement: The jumper should be placed between terminals ZC and H. Connect the isolated end switch, X1 and X2 to the boiler aquastat control. For zone 1 priority, remove jumper between terminals P and ZC.
Jumper Placement: The jumper should be placed between terminals H and X1. Connect terminal ZC to ZC terminal on the aquastat control. Connect terminal ZR to ZR terminal on the aquastat control. Confirm polarity is consistent between boiler aquastat and switching relay. For zone 1 priority, remove jumper between terminals P and ZC.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral wire to terminal N. Hot wire to terminal H.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral wire to terminal N. Hot wire to terminal H.
The Taco Connection: Combine the reliability of the Taco Zone Valves, Priority Zoning Circulators, Thermostats, and the “00” family of circulators with the advanced features of the Taco Zone Controls to achieve total system integration. No matter the application, Taco now provides the products to maximize system performance while simplifying both installation and service.
Features:
External Diagnostics: Externally visible lights show full functionality of the switching relay. The green light should always be on, indicating that power is connected. When the thermostat calls for heat, both the appropriate circulator and red indicating light is energized. Specifications: PRODUCT NUMBER
NUMBER OF ZONES
TRANSFORMER VOLTAGE
MAXIMUM COMBINED LOAD
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH
SR502 SR503
2 with Priority 3 with Priority
120 VAC Input 120 VAC Input
15 amps 15 amps
10 1/4" 10 1/4"
6 3/4" 6 3/4"
2 3/4" 2 3/4"
All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.
External Indicator Lights Priority Simplified Wiring Fully Enclosed Snap-Out Relays Compact Design Fuse Protected 100% Factory Tested Isolated End Switch Contractor Friendly PC Board Layout Universal Thermostat Compatibility UL Approved 24 volt Power Input or Output Terminal Extended 3 Year Warranty Made in the USA
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
Printed in USA Copyright 1999 TACO, Inc.
Visit our web site at: http://www.taco-hvac.com
53
Instruction Sheet SR504 & SR506 Switching Relay THERMOSTATS
THERMOSTATS
Tankless Coil Boiler Application
Cold Start Boiler Application
SR 506
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE 6 PRIORITY ON
X
X
END SWITCH
ZC ZR
120 VOLT CIRCULATORS
FUSE 1 AMP
POWER ZONE 1 ZONE 2 ZONE 3
120V RELAY
24 VAC POWER
POWER INPUT
OFF
ZONE 4
ZONE 5 ZONE 6 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE 6 PRIORITY ON
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4
120V RELAY
24 VAC POWER
SR 506
OFF
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
X
X
END SWITCH
ZONE 5 ZONE 6
ZC ZR
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
120 VOLT CIRCULATORS
POWER INPUT
FUSE 1 AMP
JUMPER TO: "ZC" ON AQUASTAT
TO: "TT" ON BOILER
120 VAC INPUT
120 VAC INPUT TO: "ZR" ON AQUASTAT
Operation: When any thermostat calls for heat, the appropriate circulator is energized and the isolated end switch (X and X) will start the boiler.
Operation: When any thermostat calls for heat, the boiler is given a signal to start. The appropriate circulator is energized only when the boiler temperature is above the set low limit.
Priority Operation: When zone 6 is switched to the priority setting and is actuated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is not switched to priority, all zones will operate independently.
Priority Operation: When zone 6 is switched to the priority setting and is actuated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is not switched to priority, all zones will operate independently.
Jumper Placement: The jumper should be placed between terminals ZC and ZR. Connect the isolated end switch to the aquastat control on the boiler.
Jumper Placement: REMOVE the jumper between terminals ZC and ZR. Connect terminal ZC to ZC terminal on the aqua-stat control. Connect terminal ZR to ZR terminal on the aqua-stat control. Confirm polarity is consistent between boiler aquastat and switching relay.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral wire to terminal N. Hot wire to terminal H.
The Taco Connection: Combine the reliability of the Taco Zone Valves, Priority Zoning Circulators, Thermostats, and the “00” family of circulators with the advanced features of the Taco Zone Controls to achieve total system integration. No matter the application, Taco now provides the products to maximize system performance while simplifying both installation and service. External Diagnostics: Externally visible lights show full functionality of the switching relay. The green light should always be on, indicating that power is connected. When the thermostat calls for heat, both the appropriate circulator and red indicating light is energized.
Specifications: PRODUCT NUMBER
NUMBER OF ZONES
TRANSFORMER VOLTAGE
MAXIMUM COMBINED LOAD
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH
SR504 SR506
4 with Priority 6 with Priority
120 VAC Input 120 VAC Input
20 amps 20 amps
10 1/4" 11 3/4"
6 3/4" 7 1/2"
2 3/4" 3"
All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral wire to terminal N. Hot wire to terminal H. Features:
External Indicator Lights Switchable Priority Simplified Wiring Fully Enclosed Snap-Out Relays Compact Design Fuse Protected 100% Factory Tested Isolated End Switch Contractor Friendly PC Board Layout Universal Thermostat Compatibility UL Approved 24 volt Power Input or Output Terminal Extended 3 Year Warranty Made in the USA
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. Visit our web site at: http://www.taco-hvac.com
54
Printed in USA Copyright 1999 TACO, Inc.
Instruction Sheet SR503-EXP, SR504-EXP & SR506-EXP Switching Relay Cold Start Boiler Application
Tankless Coil Boiler Application
THERMOSTATS
EXPANSION CONNECTIONS 1234
SLAVE
POWER CONTROL INTERFACE
EXPANSION CONNECTIONS PLUG-IN CARDS
MASTER
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
RESET
24 VAC POWER
NORMAL
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
120V RELAY
X
THERMOSTATS
X
END SWITCH
ZONE 6 PRIORITY ON OFF
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
SR 506-EXP ZC ZR
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
120 VOLT CIRCULATORS
1234
SLAVE
POWER CONTROL INTERFACE
PLUG-IN CARDS
MASTER
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
RESET
24 VAC POWER
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
120V RELAY
X
POWER INPUT
POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
SR 506-EXP
X
ZC ZR
END SWITCH
FUSE 1 AMP
NORMAL
ZONE 6 PRIORITY ON OFF
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
120 VOLT CIRCULATORS
POWER INPUT
FUSE 1 AMP
JUMPER TO: "TT" ON BOILER
TO: "ZC" ON AQUASTAT
120 VAC INPUT
120 VAC INPUT
TO: "ZR" ON AQUASTAT
Operation: When any thermostat calls for heat, the appropriate circulator is energized and the isolated end switch (X and X) will start the boiler.
Operation: When any thermostat calls for heat, the boiler is given a signal to start. The appropriate circulator is energized only when the boiler temperature is above the set low limit.
Priority Operation: When zone 6 is switched to the priority setting and is actuated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is not switched to priority, all zones will operate independently.
Priority Operation: When zone 6 is switched to the priority setting and is actuated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is not switched to priority, all zones will operate independently.
Mode Operation: When the mode switch is set to NORMAL, the end switch relay will be energized if any zone is in operation. When the switch is set to RESET, the end switch relay will only be energized if priority zone is in operation, or through the operation of a plug-in reset control.
Mode Operation: When the mode switch is set to NORMAL, the end switch relay will be energized if any zone is in operation. When the switch is set to RESET, the end switch relay will only be energized if priority zone is in operation, or through the operation of a plug-in reset control.
Jumper Placement: The jumper should be placed between terminals ZC and ZR. Connect the isolated end switch to the aquastat control on the boiler.
Jumper Placement: REMOVE the jumper between terminals ZC and ZR. Connect terminal ZC to ZC terminal on the aqua-stat control. Connect terminal ZR to ZR terminal on the aqua-stat control. Confirm polarity is consistent between boiler aquastat and switching relay.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral wire to terminal N. Hot wire to terminal H.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral wire to terminal N. Hot wire to terminal H.
Expansion Connections: Set the expansion switch to MASTER on the switching relay that has the designated priority zone or is utilizing the PowerPort options. Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22 gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding 1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones using any combination of -EXP controls.
Expansion Connections: Set the expansion switch to MASTER on the switching relay that has the designated priority zone or is utilizing the PowerPort options. Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22 gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding 1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones using any combination of -EXP controls.
Features: External Indicator Lights Plug-In PowerPort Cards Switchable Priority Simplified Wiring Add-On Power Controls Fully Enclosed Snap-Out Relays Compact Design Fuse Protected 100% Factory Tested
External Diagnostics: Externally visible lights show full functionality of the switching relay. The green light should always be on, indicating that power is connected. When the thermostat calls for heat, both the appropriate circulator and red indicating light is energized.
Isolated End Switch Expandable to 20 Zones Contractor Friendly PC Board Layout Universal Thermostat Compatibility UL Approved 24 volt Power Input or Output Terminal Extended 3 Year Warranty Made in the USA
Specifications: PRODUCT NUMBER
NUMBER OF ZONES
POWER PORTS
TRANSFORMER VOLTAGE
MAXIMUM COMBINED LOAD
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH
SR503-EXP SR504-EXP SR506-EXP
3 with Priority 4 with Priority 6 with Priority
3 3 3
120 VAC Input 120 VAC Input 120 VAC Input
20 amps 20 amps 20 amps
10 1/4" 10 1/4" 11 3/4"
6 3/4" 6 3/4" 7 1/2"
2 3/4" 2 3/4" 3"
All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
Printed in USA Copyright 1999 TACO, Inc.
Visit our web site at: http://www.taco-hvac.com
55
Instruction Sheet ZVC403 & ZVC405 Zone Valve Control THERMOSTAT
THERMOSTAT
WHITE
24 VAC
T T ZONE 1 FUSE (5 AMP MAX)
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
WHITE
THERMOSTAT
24 VAC
POWER IN
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
Wiring Diagram
24 VAC
END SWITCH
T T ZONE 2
T T ZONE 4
T STAT 1
T T ZONE 5
VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4
ZVC 405 FIVE ZONE ZONE VALVE CONTROL
ZONE 1 1 2 3 4
N/O COM N/C
T T ZONE 3
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
VALVE 4 T STAT 5 VALVE 5 POWER
ZONE 5 1 2 3 4
Installation of Optional System T T
JUMPER 3&4 TO CIRCULATOR OR BOILER AQUASTAT RELAY
END SWITCH
1 2 3
DRY CONTACTS
N/O COM N/C
2 WIRE ZONE VALVE (NO END SWITCH)
MOTOR
TACO 3 WIRE ZONE VALVE
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
HOT
T T
BOILER
120 VAC NEUTRAL
Operation/External Diagnostics: When any thermostat calls for heat, the appropriate zone valve is energized and the yellow light goes on. When the zone valve is fully open, the red light goes on and energizes the end switch relay. The green light should always be on, indicating that power is connected. The Taco Connection: Combine the reliability of the Taco Zone Valves, Priority Zoning Circulators, Thermostats, and the “00” family of circulators with the advanced features of the Taco Zone Controls to achieve total system integration. No matter the application, Taco now provides the products to maximize system performance while simplifying both installation and service. Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.
Specifications: PRODUCT NUMBER
NUMBER OF ZONES
TRANSFORMER VOLTAGE
MAX OUTPUT AT 24 VAC
ZVC403 ZVC405
3 Zone 5 Zone
120 VAC Input 120 VAC Input
40 VA 80 VA
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH 2 3⁄4" 3"
All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of hp (5A) @ 120 VAC.
Features: External Indicator Lights Simplified Wiring Works with 2, 3, or 4Wire Zone Valves Compact Design Fuse Protected 100% Factory Tested Isolated End Switch
Extra Set of Dry Contacts Contractor Friendly PC Board Layout Universal Thermostat Compatibility UL Approved Sturdy Screw Connections Extended 3 Year Warranty Made in the USA
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
56
6 3⁄4" 71⁄2"
1⁄ 6
Do it Once. Do it Right. Visit our web site at: http://www.taco-hvac.com
10 1⁄4" 113⁄4"
Printed in USA Copyright 2000 TACO, Inc.
Instruction Sheet ZVC404 & ZVC406 Zone Valve Control Wiring Diagram
24 VAC
24 VAC
T T ZONE 1
24 VAC
Installation of Optional System and/or DHW Circulator
EXTRA MAIN END END SWITCH SWITCH
N/O COM N/C ZONE 6 RELAY
T T
T T ZONE 2
SYSTEM CIRCULATOR DHW CIRCULATOR
T T ZONE 4
T T ZONE 5
T T ZONE 6
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY ZONE 1 1 2 3 4
ZONE 2 1 2 3 4
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4
ZVC 406
VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
ZONE 6 1 2 3 4
JUMPER 3&4
SEE NOTE
PRIORITY ZONE
DRY CONTACTS
BOILER
T T ZONE 3
JUMPER 3&4
TO CIRCULATOR OR BOILER AQUASTAT RELAY
N/O COM N/C
OFF ON
FUSE (7 AMP MAX)
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
WHITE
ZONE 6 PRIORITY
MODE
NORMAL RESET
POWER IN
FACTORY INSTALLED TRANSFORMER
WHITE
T T
THERMOSTAT INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
120 VAC INPUT BLACK
EXTRA MAIN END END SWITCH SWITCH
THERMOSTAT
THERMOSTAT
1 2 3 2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
MOTOR
END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
(See Note)
NEUTRAL 120 VAC HOT
Operation/External Diagnostics: When any thermostat calls for heat, the appropriate zone valve is energized and the yellow light goes on. When the zone valve is fully open, the red light goes on and energizes the end switch relay. The green light should always be on, indicating that power is connected. Priority Operation: When zone 6 is switched to the priority setting and is actuated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is not switched to priority, all zones will operate independently. Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone. Mode Operation: When the mode switch is set to NORMAL, the end switch relay will be energized if any zone is in operation. When the switch is set to RESET, the end switch relay will only be energized if priority zone is in operation. The Taco Connection: Combine the reliability of the Taco Zone Valves, Priority Zoning Circulators, Thermostats, and the “00” family of circulators with the advanced features of the Taco Zone Controls to achieve total system integration. No matter the application, Taco now provides the products to maximize system performance while simplifying both installation and service.
Specifications: PRODUCT NUMBER
NUMBER OF ZONES
TRANSFORMER VOLTAGE
MAX OUTPUT AT 24 VAC
ZVC404 ZVC406
4 with Priority 6 with Priority
120 VAC Input 120 VAC Input
40 VA 80 VA
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH 101⁄4" 113⁄4"
63⁄4" 71⁄2"
23⁄4" 3"
All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of 1⁄ hp (5A) @ 120 VAC. 6
Features: External Indicator Lights Switchable Priority Simplified Wiring Works with 2, 3, or 4-Wire Zone Valves Compact Design Fuse Protected 100% Factory Tested Isolated End Switch Extra Set of Dry Contacts Contractor Friendly PC Board Layout Universal Thermostat Compatibility UL Approved Sturdy Screw Connections Extended 3 Year Warranty Made in the USA Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs.
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
Printed in USA Copyright 2000 TACO, Inc.
Visit our web site at: http://www.taco-hvac.com
57
Instruction Sheet ZVC404-EXP & ZVC406-EXP Zone Valve Control THERMOSTAT
THERMOSTAT
WHITE
POWER CONTROLS
N/O COM N/C
SLAVE
1 2 3 4
T T ZONE 1
EXPANSION MASTER
T T ZONE 3
T T ZONE 4
T T ZONE 5
T T ZONE 6
OFF
T STAT 1 VALVE 1 T STAT 2 VALVE 2
SIX ZONE ZONE VALVE CONTOL WITH OPTIONAL PRIORITY
T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6
END SWITCH B PUMP
N/O COM N/C ZONE 6 RELAY
ZONE 1 1 2 3 4
END SWITCH A BOILER
TO CIRCULATOR OR BOILER AQUASTAT RELAY
TO CIRCULATOR OR BOILER AQUASTAT RELAY
ZONE 3 1 2 3 4
ZONE 4 1 2 3 4
ZONE 5 1 2 3 4
ZONE 6 1 2 3 4
JUMPER 3&4
MOTOR
1 2 3
2 WIRE ZONE VALVE (NO END SWITCH)
SYSTEM CIRCULATOR
ZONE 2 1 2 3 4
JUMPER 3&4
DRY CONTACTS
END SWITCH A BOILER
T T ZONE 2
ZVC 406-EXP
NORMAL FUSE 7 AMP MAX
24 VAC
RESET
ZONE 6 PRIORITY ON
PLUG-IN CARDS
MODE
Installation of Optional System and/or DHW Circulator END SWITCH B PUMP
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
24 VAC
TACO, INC ZVC406-EXP
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
WHITE
THERMOSTAT
24 VAC
POWER IN
120 VAC INPUT BLACK
FACTORY INSTALLED TRANSFORMER
Wiring Diagram
TACO 3 WIRE ZONE VALVE
END SWITCH
VALVE 6 POWER ON
SEE NOTE
PRIORITY ZONE
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
T T BOILER DHW CIRCULATOR (See Note)
120 VAC
NEUTRAL
HOT
Operation/External Diagnostics: When any thermostat calls for heat, the appropriate zone valve is energized and the yellow light goes on. When the zone valve is fully open, the red light goes on and energizes the end switch relays. The green light should always be on, indicating that power is connected. Priority Operation: When zone 6 is switched to the priority setting and is actuated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is not switched to priority, all zones will operate independently. Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone. Mode Operation: When the mode switch is set to NORMAL, both end switch relays will be energized if any zone is in operation. When the mode switch is set to RESET, the end switch relay “A” will only be energized when the priority zone is in operation. The end switch relay “B” will be energized when any zone is in operation Power Input: Connect 120 volt ac power input to leads on transformer. Neutral to white wire. Hot to black wire. Expansion Connections: Set the expansion switch to MASTER on the zone valve control that has the designated priority zone or is utilizing the PowerPort options. Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22 gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding 1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones using any combination of Switching Relay -EXP or Zone Valve -EXP controls.
The Taco Connection: Combine the reliability of the Taco Zone Valves, Priority Zoning Circulators, Thermostats, and the “00” family of circulators with the advanced features of the Taco Zone Controls to achieve total system integration. No matter the application, Taco now provides the products to maximize system performance while simplifying both installation and service.
Specifications: PRODUCT NUMBER
NUMBER OF ZONES
ZVC404-EXP 4 with Priority ZVC406-EXP 6 with Priority
TRANSFORMER VOLTAGE
MAX OUTPUT AT 24 VAC
120 VAC Input 120 VAC Input
80 VA 80 VA
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH 113⁄4" 113⁄4"
71⁄2" 71⁄2"
3" 3"
All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of 1⁄6 hp (5A) @ 120 VAC.
Features: External Indicator Lights Plug-In PowerPort Cards Switchable Priority Simplified Wiring Add-On Power Controls Works with 2, 3, or 4-Wire Zone Valves UL Approved Fuse Protected 100% Factory Tested
Isolated End Switch Expandable to 20 Zones Extra Set of Dry Contacts Contractor Friendly PC Board Layout Universal Thermostat Compatibility Sturdy Screw Connections Extended 3 Year Warranty Made in the USA
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. Visit our web site at: http://www.taco-hvac.com
58
Printed in USA Copyright 2000 TACO, Inc.
Instruction Sheet Hydro Air Fan Controls To: Optional Aquastat on Return Line of Hydro Coil
THERMOSTAT
Optional Power Wire to Thermostat that Requires 24VAC
4
1 minute on fan delay, in heating mode 3 minute on fan delay, in heating mode 4 minute on fan delay, in heating mode Pump dry contact activated for 2 minutes every 24 hours (boiler contacts not activated) Pump dry contacts activated for 30 seconds every two weeks (boiler contacts not activated)
External Diagnostics: The external lights show full functionality of the Hydro Air Fan Control. The green light should always be on, indicating that power is connected. Red lights indicate fan operation for heating and cooling modes. Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.
Specifications:
Power On Call for Heat Fan, Cooling Fan, Heating
AQUASTAT
Power On Call for Heat Fan, Cooling Fan, Heating
HAFC101 HYDRO AIR FAN CONTROL
DRY CONTACTS 5 AMP 1/6 HP RATED 1 MIN ON DELAY - FAN 3 MIN ON DELAY - FAN 2 MIN @ 24 HR - PUMP 30 SEC @ 2 WK - PUMP
1 2 1&2 3
THERMOSTAT
AQUASTATS
HAFC201 HYDRO AIR FAN CONTROL
ON
Switch Settings (HAFC201):
WATER COIL FREEZE PR
THERMOSTAT
To: Aquastat on Return Line of Hydro Coil
Optional Power Wire to Thermostat that Requires 24VAC
C R W Y G T T
C R W Y G T T T T
Additional HAFC201 Operations:
PUMP
BOILER
BOILER
AIR HANDLER
AIR HANDLER
X X C R Y G G
XX X X C R Y G G Jumper
Hot
Dry Contacts To: “T T” on Boiler or Switching Relay
M
1 Speed Air Handler*
Fan Relays
High
Dry Contacts To: “T T” on Boiler or Switching Relay
Low
Fan Relay
Circulator
Outdoor Condenser Unit
Line
(or to “T T” on switching relay)
24 VAC
Neutral 24 VAC
Selectable one, three or four minute delay on fan operation in heating mode. Selectable pump exercise activates circulator but does not enable boiler contacts. Two minutes every 24 hours minimizes the chance of bacteria build-up in an open loop system. Thirty seconds every two weeks minimizes seasonal start-up problems generally associated with harsh water conditions. Optional aquastat or thermostat can be connected to Freeze Protection TT terminals to reduce the chance of pipes freezing by energizing the pump dry contacts (boiler contacts not activated.)
To: Optional Aquastat or Thermostat to sense low ambient temperature
OFF
The Hydro Air Fan Control is an interface between the thermostat and air handler. It also has an isolated end switch to start the boiler and/or pump. When the thermostat calls for heat, the Fan Control energizes the end switch relay and allows the fan to operate at low speed when the water is above the optional aquastat setting. When the thermostat calls for cooling, the Fan Control energizes the condenser and operates on high speed.
Line
Operation HAFC101 and 201:
THERMOSTAT
Outdoor Condenser Unit
M
2 Speed Air Handler*
* Both HAFC101 and 201 capable of 1 and 2 speed applications
Terminal Description: Thermostat: C Optional: Common side of transformer W White - Heating signal to power some styles of thermostats Y Yellow - Condenser signal R Red - Hot side of transformer used to G Green - Fan signal switch all functions Water Coil Aquastat: TT Connect to aquastat at air handler to control operation of the fan when in the heating mode. Install a jumper if the aquastat is not used Freeze Protection Aquastat: TT Connect to aquastat or thermostat to sense low ambient temperature. Reduces the chance of pipes freezing by energizing the pump dry contacts. Pump Dry Contacts: XX May switch pump directly by bringing in external line voltage or connect to “T T” on a switching relay. Boiler Dry Contacts: XX Connect to the boiler or “T T” terminals on a switching relay. Air Handler: C Common side of transformer to power the Fan Control R Red - Hot side of transformer used to switch all functions Y Yellow - Condenser signal One Speed Motor: Glow Connect the fan to the relay. Keep the jumper installed between Ghigh and Glow. Two Speed Motor: Ghigh Remove jumper and connect Ghigh to the high speed fan relay and connect Glow to the low speed fan relay.
** Model number changed from SR501-F
PRODUCT NUMBER POWER INPUT MAXIMUM RELAY THERMOSTAT SINGLE PHAZE MOTOR NUMBER OF ZONES VOLTAGE COMBINED LOAD TYPE CURRENT RATING (RELAY) HAFC101** 1 Zone 24 VAC Input 5 amps DPDT .18 1/6 HP(5A) @120VAC HAFC201•• 1 Zone 24 VAC Input 5 amps DPDT .18 1/6 HP(5A) @120VAC The Hydro Air Fan Controls are relay type DPDT, have a thermostat current of .18 and a single phase motor rating per zone of 1/6
DIMENSIONS OF ENCLOSURE WIDTH HEIGHT DEPTH 4 1/4" 5 1/4" 2 3/4" 4 1/4" 5 1/4" 2 3/4" HP (5A) @ 120 VAC.
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
Printed in USA Copyright 1999 TACO, Inc.
Visit our web site at: http://www.taco-hvac.com
59
Instruction Sheet
102-094
PC600 Post Purge Timer Plug-In PowerPort Card SUPERSEDES: August 1, 1997 Plant ID No. 9300-867
EFFECTIVE: May 1, 2000
Operation: Once the priority zone is satisfied, the PC600 maintains power to the circulator, but does not fire the boiler. The circulator purges excess heat into the priority zone, minimizing standby loss during warm weather months and optimizing boiler operation when used with a boiler reset control. Power can be maintained to the circulator from a minimum of 10 seconds to a maximum of 420 seconds. The power LED light is energized when the priority zone or the post purge card is in operation. Installation: The PC600 can be installed in any one of the PowerPort terminals located on the Taco Expandable (-EXP) Control(s). Remove the shunt/jumper between pins 9 & 10 on the PowerPort terminal before installing the PC600. Align the connector on the base of the post purge card with the PowerPort terminal on the Expandable Control and push until the two mate. XX Terminals (Optional): The XX terminals on the post purge card can be wired to TT on the boiler to fire only when the priority zone is calling for heat. If using a boiler with an internal reset control, wire the XX terminals in parallel with the TT connections of the internal reset control.
Do it Once. Do it Right.
Printed in USA
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
Instruction Sheet
Copyright 2000 TACO, Inc.
102-095
PC605 Priority Protection Plug-In PowerPort Card SUPERSEDES: MAY 1, 1998 PLANT ID NO. 9300-1012
EFFECTIVE: MAY 1, 2000
Operation: The PC605 Priority Protection Plug-In Card is a solid state control that helps prevent freeze-ups in the event of a priority zone failure. If the priority zone calls for heat continuously for more than one hour, power is returned to the space heating (non-priority) zones, allowing all zones to function independently. Once the priority zone is satisfied, the PC605’s auto-reset is activated and the priority zone is again allowed to have priority for up to one hour the next time it calls. The one hour time frame is not adjustable. The red LED light is energized only when the Priority Protection Card is operating in priority override mode. Installation: The PC605 can be installed in any unoccupied PowerPort terminal located on the Taco Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 & 10 on the Expandable Control unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the Expandable Control and push until the two mate. The PC605 can be used in conjunction with any other Taco PC style PowerPort Cards or Add-on Controls.
Do it Once. Do it Right.
Printed in USA
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
Instruction Sheet
Copyright 2000 TACO, Inc.
102-096
PC610 Pump Exercise and Timer Plug-In PowerPort Card SUPERSEDES: May 31, 1998 Plant ID No. 9300-1025
EFFECTIVE: May 1, 2000
Operation: The PC610 Pump Exercise and Timer Plug-In Card is a solid state universal timer designed to cycle all the pumps that are attached to the Expandable Control(s) at selected time intervals. This minimizes seasonal start-up problems generally associated with harsh water conditions. The control can be configured to reduce the chance of freeze-ups by cycling the pumps more often during cold weather months. Bacteria can be minimized in heating systems that utilize domestic hot water heaters as their heat source by systematically circulating the water. Installation: The PC610 can be installed in any unoccupied PowerPort terminal located on the Taco Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 & 10 on the Expandable Switching Relay unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the Expandable Switching Relay and push until the two mate. The PC610 can be used in conjunction with any other Taco PC style PowerPort Cards or Add-on Controls. Typical Settings: Application On Time Off Time Pump Exercise Bacteria Minimization Freeze Protection
30 sec. 4 min. 4 min.
2 weeks 12 hours 1 hour
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.
60
Printed in USA Copyright 2000 TACO, Inc.
Taco Low Water Cutoff Replacement Guide
Taco
LTA1203N-1
LTM1203N-1
LTA0243N-1
LTM0243N-1 LTA1203R-1 LTM1203R-1 LTA1202R-1 LTM1202R-1 LTA0242R-1 LNA0243S-1 LNA1203S-1 P3R-1 LTA1203S-1 LTM1203S-1 LTA0243S-1 LTM0243S-1
McDonnell & Miller 900 900C PS-800-120 PS-801-120 PS-850-120 PS-851-120 900M 901M 902M PS-801-M-120 PS-850-M-120 PS-851-M-120 PS-800-24 PS-802-24 PS-850-24 PS-852-24 PS-850-M-24 PS-802-M-24 PS-852-M-24 750-120 750-T-120 750-M-120 750-MT-120 PS-851-RX2-120 PS-851-M-RX2-120 PS-802-RX2-24 RB-24 901 RB-120 RB-120II RB-122 RS-1-LP PS-851-SP-120 PS-851-SP-M-120 PS-852-SP-24 PS-852-SP-M-24
Hydrolevel
Honeywell
450 650
RW700A1031 RW700A1056 RW700A1080
550 750
RW700B1054 RW700B1039 RW700B1021
400 600
RW700A1098
500 700 650R 550R 650R 550R 400R 24SV 170SV
RW700A1007 RW700A1106
650SV 550SV 600SV 500SV
Bold / Italics Indicates Discontinued Part Number
61
Taco LT Series 120 Volt LWCO Competitive Wiring Cross Reference 120 VAC Models with 120 VAC Burner Circuits PS-801/851-120 w/Red & Amber LEDs Series 750
LTx120x NC COM NO
H
N
GND
1
P HOT
BURNER CIRCUIT
2
NEUTRAL
P1
P2
5
HOT BURNER CIRCUIT
NEUTRAL
PS-801/851-120 w/Red & Green LEDs
450, 550, 650 & 750 1
4
120 VAC CIRCUIT
120 VAC CIRCUIT
2
3
A
N
HOT
H
C
W
B
HOT BURNER CIRCUIT
120 VAC CIRCUIT
BURNER CIRCUIT
120 VAC CIRCUIT
NEUTRAL
NEUTRAL
120 VAC Models with 24 VAC Burner Circuits PS-801/851-120 w/Red & Amber LEDs Series 750
LTx120x NC COM NO
H
N
GND
P
1 HOT
BURNER CIRCUIT
120 VAC CIRCUIT
2
HOT
NEUTRAL
24 VAC TRANSFORMER
HOT 120 VAC CIRCUIT NEUTRAL
62
P1
P2
24 VAC TRANSFORMER
PS-801/851-120 w/Red & Green LEDs A
BURNER CIRCUIT
24 VAC TRANSFORMER
5 BURNER CIRCUIT
450, 550, 650 & 750 1
4
120 VAC CIRCUIT NEUTRAL
2
3
N
H
C
W
HOT
BURNER CIRCUIT
120 VAC CIRCUIT NEUTRAL
B
24 VAC TRANSFORMER
Taco LT Series 24 Volt LWCO Competitive Wiring Cross Reference 24 VAC Models with 24 VAC Burner Circuits
LTx024x NC COM NO
H
N
GND
P HOT
BURNER CIRCUIT
24 VAC CIRCUIT NEUTRAL
PS-802/852-24
400, 500, 600 & 700 2
1
P1
P2
A
N
HOT
H
C
W
B
HOT BURNER CIRCUIT
24 VAC CIRCUIT
BURNER CIRCUIT
24 VAC CIRCUIT
NEUTRAL
NEUTRAL
24 VAC Models with 120 VAC Burner Circuits
LTx024x NC COM NO
H
N
GND
P
HOT BURNER CIRCUIT
120 VAC CIRCUIT
24 VAC TRANSFORMER
NEUTRAL
PS-802/852-24
400, 500, 600 & 700 2
1
P1
P2
HOT
A
N
C
W
B
HOT BURNER CIRCUIT
120 VAC CIRCUIT
BURNER CIRCUIT
120 VAC CIRCUIT
24 VAC TRANSFORMER NEUTRAL
H
24 VAC TRANSFORMER NEUTRAL
63
Taco LN Series 120 Volt LWCO Competitive Wiring Cross Reference 120 VAC Models with 120 VAC Burner Circuits
RB-120
LNA120S N
H
COM NC
NO
HOT
1
2
3
4
5
HOT BURNER CIRCUIT
120 VAC CIRCUIT
BURNER CIRCUIT
120 VAC CIRCUIT
NEUTRAL
NEUTRAL
170
RB-122 N
H
B
C
GN
HOT
H
P1
P2
A
HOT BURNER CIRCUIT
120 VAC CIRCUIT
BURNER CIRCUIT
120 VAC CIRCUIT
NEUTRAL
NEUTRAL
120 VAC Models with 24 VAC Burner Circuits
RB-120
LNA120S N
H
COM NC
HOT
BURNER CIRCUIT
120 VAC CIRCUIT NEUTRAL
NO
1
H
B
HOT
NEUTRAL
64
24 VAC TRANSFORMER
5
120 VAC CIRCUIT
24 VAC TRANSFORMER
170 C
GN
BURNER CIRCUIT
120 VAC CIRCUIT
4
BURNER CIRCUIT
RB-122 N
3
HOT
NEUTRAL
24 VAC TRANSFORMER
2
HOT 120 VAC CIRCUIT NEUTRAL
H
P1
P2
A
BURNER CIRCUIT
24 VAC TRANSFORMER
Taco LN Series 24 Volt LWCO Competitive Wiring Cross Reference 24 VAC Models with 24 VAC Burner Circuits
RB-24
LNA024S N
H
COM NC
Red White Yellow Yellow Wire Wire Wire Wire
NO
HOT 24 VAC CIRCUIT
HOT BURNER CIRCUIT
BURNER CIRCUIT
24 VAC CIRCUIT
NEUTRAL
NEUTRAL
24 Black White Orange Brown Wire Wire Wire Wire
HOT BURNER CIRCUIT
24 VAC CIRCUIT NEUTRAL
24 VAC Models with 120 VAC Burner Circuits
LNA024S N
H
COM NC
NO
HOT 120 VAC CIRCUIT
BURNER CIRCUIT
NEUTRAL 24 VAC TRANSFORMER
65
Wiring TACO LN or LT Series 24VAC Low Water Cutoff to McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder SWITCH POSITION #2 1
UNI-MATCH WATER FEEDER MODEL WF2-U-24
2
3
0R
W
N
M&M 2 3
H
Set the TACO LT Model’s DOM to 30 seconds and DOB to 15 seconds.*
24VAC SUPPLY 50/60 Hz
N * Note on switch position:
H BURNER
N
H
COM
Switch setting 1 (M&M), the feed cycle repeats indefinitely. Position 2 and 3 gives one feed cycle. If using the LN series, choose whichever position best matches the application:
NC NO
AC POWER OUTPUT CONTACTS
24 VAC LWCO Using Burner Circuit Power Source Remove jumper between H and COM if using power source other than burner circuit or when using mixed voltages.
WF-2 switch to position 1 - 60 sec. delay, 90 sec. feed, repeats WF-2 switch to position 2 - 90 sec. delay, 90 sec. feed WF-2 switch to position 3 - 100 sec. delay, 90 sec. feed
Do not connect feeder to a manual reset LWCO.
Wiring TACO LN or LT Series 120VAC Low Water Cutoff to McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder SWITCH POSITION #2 1
UNI-MATCH WATER FEEDER MODEL WF2-U-120
2
3
0R
W
N
M&M 2 3
H
Set the TACO LT Model’s DOM to 30 seconds and DOB to 15 seconds.*
120VAC SUPPLY 50/60 Hz
N * Note on switch position:
H BURNER
N
H
COM
NC NO
AC POWER OUTPUT CONTACTS
120 VAC LWCO Using Burner Circuit Power Source Remove jumper between H and COM if using power source other than burner circuit or when using mixed voltages. Do not connect feeder to a manual reset LWCO. 66
Switch setting 1 (M&M), the feed cycle repeats indefinitely. Position 2 and 3 gives one feed cycle. If using the LN series, choose whichever position best matches the application: WF-2 switch to position 1 - 60 sec. delay, 90 sec. feed, repeats WF-2 switch to position 2 - 90 sec. delay, 90 sec. feed WF-2 switch to position 3 - 100 sec. delay, 90 sec. feed
Wiring TACO LN or LT Series 24VAC Low Water Cutoff to Hydrolevel VXT-24 Water Feeder (Non-Display Model)
SAFGARD VXT-24 WATER FEEDER WHITE
BLACK
Set the TACO LT Model’s DOB to 30 seconds and DOM to 15 seconds. Set Safgard as desired.
24VAC SUPPLY 50/60 Hz
N H
BURNER
N
H
COM
NC NO
AC POWER OUTPUT CONTACTS
24 VAC LWCO Using Burner Circuit Power Source Remove jumper between H and COM if using power source other than burner circuit or when using mixed voltages. Do not connect feeder to a manual reset LWCO.
Wiring TACO LN or LT Series 120VAC Low Water Cutoff to Hydrolevel VXT-120 Water Feeder (Non-Display Model)
SAFGARD VXT-120 WATER FEEDER WHITE
BLACK
Set the TACO LT Model’s DOB to 30 seconds and DOM to 15 seconds. Set Safgard as desired.
120VAC SUPPLY 50/60 Hz
N H
BURNER
N
H
COM
NC NO
AC POWER OUTPUT CONTACTS
120 VAC LWCO Using Burner Circuit Power Source Remove jumper between H and COM if using power source other than burner circuit or when using mixed voltages. Do not connect feeder to a manual reset LWCO. 67
Wiring TACO LN or LT Series 24VAC Low Water Cutoff to Hydrolevel VXT-24 Programmable Water Feeder (Model with Display)
SAFGARD VRTX-24 WATER FEEDER WHITE
BLACK
RED
Set the TACO LT Model’s DOB to 30 seconds and DOM to 15 seconds. Set Safgard as desired.
24VAC SUPPLY 50/60 Hz
N H
BURNER
N
H
COM
NC NO
AC POWER OUTPUT CONTACTS
24 VAC LWCO Using Burner Circuit Power Source Remove jumper between H and COM if using power source other than burner circuit or when using mixed voltages. Do not connect feeder to a manual reset LWCO.
Wiring TACO LN or LT Series 120VAC Low Water Cutoff to Hydrolevel VXT-120 Programmable Water Feeder (Model with Display)
SAFGARD VRTX-120 WATER FEEDER WHITE
BLACK
RED
Set the TACO LT Model’s DOB to 30 seconds and DOM to 15 seconds. Set Safgard as desired.
120VAC SUPPLY 50/60 Hz
N H
BURNER
N
H
COM
NC NO
AC POWER OUTPUT CONTACTS
120 VAC LWCO Using Burner Circuit Power Source Remove jumper between H and COM if using power source other than burner circuit or when using mixed voltages. Do not connect feeder to a manual reset LWCO. 68
Taco Industrial Flow Switch Replacement Guide
Taco IFS01BF-1
Potter IFS-1
IFS01BR-1
McDonnell & Miller FS4-3
Hydrolevel 44-100
FS4-3-RP
IFS01SF-1
IFSS-1
FS4-3S FS4-3S-E
IFS02BF-1
IFS-2
FS4-3D FS4-3D-E
IFS02SF-1 IFSH1BF-1 IFSH1SF-1 IFSH2BF-1 IFSH2SF-1 IFSW2BF-1 IFSW2SF-1
IFSS-2 IFS-HC-1 IFSS-HC-1 IFS-HC-2 IFSS-HC-2 IFS-WP-2 IFSS-WP-2
IFSWSBF-1
IFS-WPS IFS-WP-1
IFSWSSF-1
IFSS-WPS IFSS-WP-1
IFSWTBF-1 IFSWTBR-1
Johnson Controls / Penn F61KB-11 F61LB-1
FS4-3DS
FS8-W
F61MB-1 F61MB-5
IFS-WPT FS4-3RP-T
69
Aquastat Wiring L1 (HOT)
L2 (NEUTRAL) 120 VAC INPUT
L1
T
L2
TACO ZONE CONTROL
T END SWITCH
C1
B2
ZC
C2
ZR
B1
CIRCULATOR ON BOILER (IF ATTACHED)
HONEYWELL L8124A & C OR EQUAL LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
MILLI-VOLTAGE GAS VALVE
B1
T
B2
TACO ZONE CONTROL
T END SWITCH
C
L1
L1 (HOT)
T1
L2
CIRCULATOR ON BOILER (IF ATTACHED)
C2
L2 (NEUTRAL)
120 VAC INPUT
HONEYWELL L8124B OR EQUAL
TACO ZONE CONTROL
Z
T2
END SWITCH CIRCULATOR ON BOILER (IF ATTACHED)
B1
C2
L1
L2
B2
LOW VOLTAGE GAS VALVE
70
C1
L1 (HOT)
120 VAC INPUT
L2 (NEUTRAL)
HONEYWELL L8124E OR EQUAL
Aquastat Wiring
TV
TACO ZONE CONTROL
Z
T
END SWITCH
L1
ZC
ZR
B1
L2
B2 C2
C1
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
120 VAC INPUT
L1 (HOT)
CIRCULATOR ON BOILER (IF ATTACHED)
L2 (NEUTRAL)
L1 (HOT)
HONEYWELL L8124G & L OR EQUAL
L2 (NEUTRAL) 120 VAC INPUT
L1
T
L2
TACO ZONE CONTROL
T END SWITCH
B2
C1
ZC
C2
ZR
B1
CIRCULATOR ON BOILER (IF ATTACHED)
L1 (HOT)
HONEYWELL L8124M OR EQUAL LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
L2 (NEUTRAL) 120 VAC INPUT
L1
T
L2
TACO ZONE CONTROL
T END SWITCH
3
C1
C2
B1
CIRCULATOR ON BOILER (IF ATTACHED)
B2
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
HONEYWELL L8148A OR EQUAL
71
Aquastat Wiring
TV
TACO ZONE CONTROL
T
W
END SWITCH CIRCULATOR ON BOILER (IF ATTACHED)
Z
B1
C1
C2
L1
L2
B2
L1 (HOT)
LOW VOLTAGE GAS VALVE
TV
W
TP
Z
120 VAC INPUT
L2 (NEUTRAL)
HONEYWELL L8148E OR EQUAL
TACO ZONE CONTROL
T END SWITCH
MILLIVOLTAGE GAS VALVE
B1
B2
CIRCULATOR ON BOILER (IF ATTACHED)
C2
L1
L2
B3
LOW VOLTAGE GAS VALVE
OR
C1
L1 (HOT)
L1 (HOT)
120 VAC INPUT
L2 (NEUTRAL)
HONEYWELL L8148J OR EQUAL
L2 (NEUTRAL) 120 VAC INPUT
L1
B1
L2
B2 C2
TACO ZONE CONTROL
OIL BURNER AND IGNITION END SWITCH
C1 ZC
CIRCULATOR ON BOILER (IF ATTACHED)
ZR T
T
F
F
CAD CELL
72
HONEYWELL L8182D OR EQUAL
Aquastat Wiring
L1 (HOT)
L2 (NEUTRAL)
120 VAC INPUT
L1
T
L2
TACO SWITCHING RELAY
T
T
ZC
ZR
N
H
THERMOSTAT (IF INDEPENDENT ZONE)
C1
B2
ZC
C2
ZR
B1
CIRCULATOR ON BOILER (IF ATTACHED)
THERMOSTAT (IF INDEPENDENT ZONE)
T
TV
HONEYWELL L8124A & C OR EQUAL LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
TACO SWITCHING RELAY ZC
Z
T
L1
ZC
ZR
B1
L2
B2 C2
C1
120 VAC INPUT
CIRCULATOR ON BOILER (IF ATTACHED)
L2 (NEUTRAL)
L1 (HOT)
ZR
N
H
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
HONEYWELL L8124G & L OR EQUAL
L1 (HOT)
120 VAC INPUT
L1
L2 (NEUTRAL) T
L2
TACO SWITCHING RELAY
T
T
ZC
ZR
N
H
THERMOSTAT (IF INDEPENDENT ZONE)
C1
B2
C2
ZC
ZR
CIRCULATOR ON BOILER (IF ATTACHED)
B1
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
HONEYWELL L8124M OR EQUAL
73
Aquastat Wiring L1 (HOT) 120 VAC
L2 (NEUTRAL)
INPUT
L1
T
L2
R B2
3
W
B
B L6006 LOW LIMIT CONTROLER
TACO SWITCHING RELAY
T
T
ZC
ZR
N
H
THERMOSTAT (IF INDEPENDENT ZONE)
R C2
C1
B1
B2
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
CIRCULATOR ON BOILER (IF ATTACHED)
L1 (HOT)
L2 (NEUTRAL)
120 VAC INPUT
L1
HONEYWELL L8148A OR EQUAL
B1
L2
B2 C2
OIL BURNER AND IGNITION
C1 ZC
TACO SWITCHING RELAY ZC
ZR
N
H
CIRCULATOR ON BOILER (IF ATTACHED)
ZR T
T
T
74
F THERMOSTAT (IF INDEPENDENT ZONE)
F
CAD CELL
HONEYWELL L8182D OR EQUAL
Standard Terms and Definitions Switching Relay: Transformer and relay in one box, which allows a low voltage thermostat to control a line voltage load (circulator), with an isolated end switch that can energize the boiler.
Zone Valve Control: Transformer and relay in one box, which allows a low voltage thermostat to control a low voltage zone valve, with an isolated end switch that can energize the boiler and/or circulators.
Dry Contacts: Set of relay contacts that make and beak, where no voltage is present. Usually can switch 24 or 120 VAC. Isolated End Set Switch: Set of dry contacts that make when a zone calls for heat. Usually connected to a boiler’s aquastat TT. Mode Switch: Switch set to NORMAL – When any zone calls for heat, the end switch will make and fire the boiler. Switch set to RESET – When any zone calls for heat, a heat demand signal is given to external add-on reset control and it controls boiler operation.Also when the priority zone calls for heat and is switched to priority, the end switch will override reset control and fire boiler to high limit.
TT: Where thermostat or aquastat connects on a heating control. XX: Denotes Isolated End Switch. Low Voltage: 24 VAC for most HVAC systems. Line Voltage: Normally 120 VAC relative to ground. H or L1: Hot side of line voltage. N or L2: Neutral side of line voltage. ZR: 120 VAC (Hot) signal from switching relay to boiler’s operating aquastat to fire the burner to high limit when any zone calls for heat. Also ideal for controlling primary circulator.
ZC: 120 VAC (Hot) signal from boiler’s operating aquastat to switching relay allowing circulator(s) to run when aquastat is above the set low limit. Cold Start: A boiler that fires only when there is a call for heat. Tankless Coil: A method of heating domestic water utilizing a heat exchanger inside a boiler.The boiler also maintains heat year round to deliver hot water on demand.
DHW Heater: A method of heating domestic water utilizing a heat exchanger and storage tank. Transformer: A component for increasing or reducing AC voltage. Rated in VA (volts x amps). OHMS Law:
Example: A 24 volt, 40 VA transformer can produce how much current? Current = VA / Voltage
I = E/R R = E/I E=IxR W=ExI I = W(VA)/E
where
40 / 24 = 1.6 Amps
I = Current in Amps R = Resistance in Ohms E = Volts W = Watts or VA
RELAY CONTACTS: N/C: Normally closed connection of a relay, when not energized. N/O: Normally open connection of a relay, when not energized. Com: The common terminal for normally open and normally closed. Pole: The number of independent circuits of a switch or relay. Throw: The number of settings which a switch or relay can have.
3 4 4 6 6 5
COM N/O N/C N/C N/O COM
DPDT = Double Pole Double Throw 75
76
TACO Zone Controls Cross-Reference TACO
ARGO
ERIE
HONEYWELL
WHITE-ROGERS
SR501 SR501-845RP SR502 SR503 SR504 SR506
AR821 (1), AR822
SR100
RA89A (2), RA845A (1), RA832A (1)
889-189 (2), 829-845 (1)
SR503-EXP SR504-EXP SR506-EXP
ARM-861-DP (5,6), ARM-3P ARM-842-DP (5,6), ARM-4P ARM-866-DP (5,6), ARM-6P
SWITCHING RELAYS 1 1 2 3 4 6
Zone Zone Zone Zone Zone Zone
Switching Switching Switching Switching Switching Switching
Relay Relay Relay Relay Relay Relay
(DPDT) Replacement PC Board (DTSP) with Priority with Priority with Priority with Priority
AR-861-2 (3) AR-861-3 (3) AR-842 AR-866
SR201 SR301 SR601 SR601 (4)
R8888A1007 R8888B1005
SWITCHING RELAYS WITH POWERPORT OPTIONS 3 Zone Switching Relay with Priority and 3 Power Ports 4 Zone Switching Relay with Priority and 3 Power Ports 6 Zone Switching Relay with Priority and 3 Power Ports
ZONE VALVE CONTROLS 3 4 5 6
Zone Valve Zone Valve Zone Valve Zone Valve
Control Control with Priority Control Control with Priority
ZVC403 ZVC404 ZVC405 ZVC406
(7) (7) (7) (7)
AZ-3 AZ-4P AZ-5 AZ-6P
ZONE VALVE CONTROLS WITH POWERPORT OPTIONS 4 Zone Valve Control with Priority and 2 Power Ports 6 Zone Valve Control with Priority and 2 Power Ports
ZVC404-EXP ZVC406-EXP
PLUG IN POWERPORT CARDS Post Purge Timer Plug-In Card Priority Protection Plug-In Card Universal Timer/Pump Exercize Plug-In Card
PC600 PC605 PC610
DPM-1
R8889A1014 R8889B1012 VL500 (8) VL500 (8)
TACO Zone Controls Cross-Reference (Continued) TACO
ARGO
ERIE
PC700 PC702 PC705
DPM-2
BB1200
HAFC101 HAFC201
ARH-1, ARH-2, ARH-3
WA300
SR024-001RP SR120-001RP
R-35 R-49
EXP10
ADD-ON POWER CONTROLS Boiler Reset Control 2-Stage Boiler Reset Control Variable Speed Pump Injection Mixing Control
BB3000
FAN CONTROLS 1 Zone Hydro Air Fan Control (1 or 2 Speed) 1 Zone Hydro Air Fan Control with Time Delays (1 or 2 Speed)
REPLACEMENT PARTS 24 Volt Replacement Relay 120 Volt Replacement Relay
NOTES: 1. Does not have both normally open and normally closed contacts. 2. Has only one set of normally open contacts (SPST). 3. Does not have optional priority. 4. Can be expanded to five and six zones with the addition of EXP10 relays. 5. Argo ARM units are expandable to 10 zones using special controls (ARM-1, ARM-4) with a phone jack. TACO switching relays can be expanded up to 20 zones using any combination of -EXP models with no special connections. 6. Includes only one data port for adding data port modules. 7. All TACO zone valve controls include an extra set of dry contacts (N/O, Common, N/C). 8. VL500 is only 5 zones, 4 normal and 1 priority.
HONEYWELL
WHITE-ROGERS
77
Do it Once. Do it Right. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. Visit our web site at: http://www.taco-hvac.com
Printed in USA Copyright 2003 TACO, Inc.