Synchronous Machines in Power Systems and Drives
Most of the electrical power generators are threephase synchronous generators Synchronous motors are competitive in higher power ranges because of efficiency and lower costs Reluctance and permanent motors are popular at lower power ranges Synchronous generator in power systems
transient stability study: maintain synchronism from large oscillations caused by a transient disturbance dynamic stability study: small signal behavior and stability about some operating point long-term dynamic energy balance study: dynamics of slower acting components
Stability Studies
Sub-transient time constant of machine is between 0.03 to 0.04 second, shorter than electromechanical oscillation Electromechanical oscillation frequency between synchronous generators in a power system lies between 0.5 to 3 Hz (0.33 to 2 second) Transient time constant of machine is between 0.5 to 10 second which is longer than the period of electromechanical oscillation Slower acting component with longer time constants such as boilers and AGC response may need more time between 10sec to 2 min Different model shall fit into the different analysis
Basic Dynamics of Synchronous Generators
Basic dynamic behavior of synchronous generator in transient situations:
voltage behind the transient reactance of a generator and network E’=Eth+ j Xt I, Xt = X’d + Xth jX’d
AC Network
One-line diagram
jX’th
E’
E’th
Circuit Equivalent
take Thevenin’s voltage as reference phasor Eth= Eth ∠0, and E’=E ∠δ
Basic Dynamics of Synchronous Generators
electrical output power of the generator E ' Eth Pgen= R(E’I*) = pu sin δ Xt from the above equation, we can see that power transfer characteristic for the system is a sine wave with max value E’Eth/Xt the rotor motion without damping Pmech-Pgen= 2 H dω pu ωb dt replace the dω/dt with d2δ/dt2, we obtain swing equation
Pmech − Pgen
2 H d 2δ = ωb dt 2
ω dδ pu or = b 2H dt 2
∫ (P
mech
− Pgen )dδ
If machine was to maintain synchronism, excursion of δ would be bounded and (dδ/dt) would have return to zero
Transient Power Angle Characteristics δ max
∫δ
min
Pmech1
transient power angle characteristics ( Pmech − Pgen )dδ = ∫
δ ss
δ min
A2
( Pmech − Pgen )dδ + ∫
δ max
δ ss
( Pmech − Pgen )dδ
A2max
A1
Pmech1
δmax δSS
Pmech0
δ0 δ0 δSS δmax
π-δSS
Equal Criteria: A1 = A2 A1 < A2max A1 = A2max A1 > A2max
Stable Critically Stable Unstable
t0
t
Transient Power Curve And Dynamics
Without damping loss, rotor oscillates about δSS. Otherwise, δ eventually settles to δSS. The gain in rotor momentum could carry δ beyond critical angle π- δSS which Pmech1>Pgen and rotor accelerates to lose synchronism For purpose of determining the synchronism of the machine, area of A2max should be larger than area of A1 (area of A2max is from δSS to π- δSS) Transient power angle curve may be raised by increasing the excitation control of E’ As a need to give a high speed control of E’ would introduce a negative damping and adversely affect the dynamic stability, see [103] The power system stabilizer (PSS) is introduced to obtain a better transient performance over the control of excitation system adverse impact of PSS: interaction of PSS and torsional mode of turbine shaft gives rise to sub-synchronous oscillations Transient stability study is mainly concerned in the synchronous generator, to switch from motor notation to generator notation, it is required to invert the sign of all stator currents in the voltage equation, flux linkage equation, and torque equations.
Transient Model with d,q Field Windings
In this chapter, there are two more models to express the synchronous machine dynamics: transient model and sub-transient model The model difference between transient model in this chapter and that in chapter 7 is that transient model in this chapter uses more machine parameters directly obtained from standard tests, such as reactances and time constants For derivation of transient model equations, please see pp. 468-474 Transient model (without damper winding): state variable λd, λq
stator winding equations
dλq rs − Ed' − λq + vq = − ' + ωr λd Lq ω dt
rotor winding equations ' dE Ld − L'd Ld ' q ' Tdo + ' Eq = E f + ' dt Ld Ld Torque
ωr λd
r vd = − s' Ld
dλd Eq' ω − λd + dt − ωr λq
' ' − L L L dE q q q ' ' d ωr λq + ' Ed = − E g − Tqo ' dt Lq Lq
' 3 P λd Ed' λq Eq 1 1 + − ' − ' λd λq Tem = ' ' 2 2 ωr Lq ωr Ld Ld Lq
Transient Model with d,q Field Windings
Simplification of transient model
in the transient analysis, damper windings are no longer active in transient stability prediction, rotor winding transient are dominant. first swing of the rotor would be the interval of interest, and the rotor transients vary at the rate of Tdo’ and Tqo’ the rotor transient would impact speed voltage term, ωrλd, ωrλq, and greater than that of dλq/dt, dλd/dt. Therefore, the effect of dλq/dt, dλd/dt could be neglected the transient model can be further simplified by neglecting dλq/dt, dλd/dt
Transient Model Equations
Simplified transient model equations (ωr=ωe except for rotor mechanical dynamics)
Stator winding equations (see pp.473 )
inputs : vq , Eq' , vd , Ed'
vd = − rsid + xq' iq + Ed'
outputs : iq , id
Rotor winding equations
vq = − rsiq − xd' id + Eq'
Tdo'
dEq'
+ Eq' = E f − ( xd − xd' )id
dt ' ' dEd Tqo + Ed' = − E g + ( xq − xq' )iq dt Torque Equation:
Tem = −
inputs : E f , E g , id , iq outputs : Ed' , Eq'
3 P { Eq' iq + Ed' id + ( xq' − xd' )id iq } 2 2ωe
N.m
Transient Model Equations
Rotor equations
dωrm J = Tem + Tmech − Tdamp (N.m) dt inputs : Tem + Tmech − Tdamp
d {(ωr − ωe ) / ωb } = Tem ( pu ) + Tmech ( pu ) − Tdamp ( pu ) (pu) 2H dt output : ωr dδ e = ωr − ωe , dt
P ωr = ωrm 2
Transient Model Block Diagram
Stator Block
Transient Model Block Diagram
Rotor Block
Transient Model Block Diagram
Field voltage equation
d axis
q axis
Transient Model Block Diagram
Overall block diagram
from excitation system
Synchronous machine model in Chap 7
Overall block diagram
Project 10-1 Fault tests of Synchronous Machine
(Homework): You are given a synchronous machine model with the machine parameters given in Table 10.7 Set 1 to construct the transient synchronous machine model. The machine is connected to the following source: v1=1√2sin(120πt+0) pu v2=1√2sin(120πt-2π/3) pu v3=1√2sin(120πt+2π/3) pu
1.
With excitation reference voltage Ef= 1pu, Tmech = 1 pu (mechanical torque), apply three-phase bolted fault to ground at t=10 sec, fault clear at t=10.25 sec, observe and plot a. b. c. d. e. f.
vq, vd, iq, id, in one figure ia, ib, ic in one figure Pgen, Tem, δ, ω in one figure Qgen, If’, in one figure Show the critical fault clearing time and plot δ vs. time with stable and unstable conditions discuss what you see on the plots (ex. observe transient in field current and qd, abc current)
Project 10-1 Fault tests of Synchronous Machine 2.
With excitation reference voltage Ef = 1pu, Tmech = 1 pu (mechanical torque), apply single phase to ground fault on phase c at t=10 sec, fault clear at t=10.25 sec, observe and plot 1) 2) 3) 4) 5)
vq, vd, iq, id, in one figure ia, ib, ic in one figure Pgen, Tem, δ, ω in one figure Qgen, If’, in one figure discuss what you see on the plots (ex. observe transient in field current and qd, abc current)
Suggestion: the figure time scale can be shown starting from t=9 sec through the time when system becomes stable after the fault cleared
EXCITATION SYSTEMS
Scheme of Excitation systems contains
pilot exciter main exciter to provide field winding voltage/current of synchronous machine slip rings (optional) automatic voltage regulator
Classification of excitation systems
dc excitation
primary excitation power is from dc generator whose field winding is on the same shaft as rotor of synchronous generator
rotating part
EXCITATION SYSTEMS
Classification of excitation systems
ac excitation (static)
field winding of alternator is on the same shaft as the rotor of the synchronous machine alternator’s stator and rectifier are stationary
EXCITATION SYSTEMS
Classification of excitation systems
ac excitation (rotary)
armature of alternator and rectifier are on the same shaft as the rotor of the synchronous machine alternator’s rotor field winding is stationary
EXCITATION SYSTEMS
Classification of excitation systems
ac excitation (from ac bus)
pilot exciter function is replaced by ac bus voltage use controllable rectifier to adjust dc excitation
EXCITATION SYSTEMS
Overall scheme of excitation systems
detector, regulator, exciter, stabilizer, diode bridge, power system stabilizer components
exciter
detector
diode bridge
regulator
COMPONENTS OF EXCITATION SYSTEMS
voltage transducer and load compensation circuit
voltage transducer and rectifier are modeled by a single time constant with unity gain compensation of excitation voltage due to internal load is represented by RC+jXC compensator
transducer
COMPONENTS OF EXCITATION SYSTEMS
voltage regulator
consists of an error amplifier with limiter transient gain reduction can be achieved by adding a zero-pole compensator
stabilizer signal
stabilizer feedback signal
error amplifier with limiter transient gain reduction Tc (vref-vfb), (1/s) and feedback loop.
Case 2: Multi-machines System
Inside generator model :
exciter
Case 2: Multi-machines System
Inside generator model :
rotor block
ωr
Case 2: Multi-machines System
Inside generator model :
generator model Ef
1
Exc_sw(1) Exc_sw
in_Vref |Vt|
vqt
Sw
1 vdt 1 s
1/Tpdo(1)
sum
exciter
1/Tpdo xd(1)-xpd(1)
out_|Vt|
Eqp_ 3
2 out_|I|
Eqp out_Pgen id_
4 out_Qgen
VIPQ stator_wdg
Gain2
delta
2
5 out_delta
in_iqe iq
6
3 id
out_puslip
in_ide
7
qde2qdr
4
iq_
out_Tem in_Tmech
xq(1)-xpd(1)
Rotor
Gain 8 1/Tpqo(1) Sum
Gain1
1 s
out_Eqpe 9
Edp qdr2qde
out_Edpe
Case 2: Multi-machines System Overall model diagram
ide1 U(E) Scope
U
y1
Selector1
Sbratio(1) Sys/Gen1VA_
T o Workspace Mux
Mux
vref(1)
Initialize and plot
Vref1
m2
Clock
T Eqpe1 Edpe1
T mech1
tmodel
Sys/Gen1VA iqe1 -K-
Sys/Gen2VA iqe2
-K-
U(E) Scope1
U
y2
Selector
Eqpe2
T o Workspace1 Mux
Mux_ 1.
vref(2)
T3
iqe4
Vref2
Edpe2
0
T1
T4
vde3
T mech(2) T mech2
T2
vqe3
Clock1
tmodel1
T5
ide4 ide2
network Sbratio(2) Sys/Gen2VA_
Project 10-3 Multi-synchronous machines Project
Read carefully on project 2 in 10.9.2: multi-machines system Use the simulation model (machine parameters are in Set 1 of TABLE 10.7) to run the simulation as follow:
run the simulation to create plots as figure 10.24 (a), (b), and (c). In this case, step changes in torque is applied at generator 2. As you can see in the figure, machine originally operate in Tmech = 0.8pu, a step change in torque to 0.9pu at t=7 sec, then a step change to 0.7pu at t=15 sec, finally a step change to 0.8 pu at t=22 sec. Use the line impedances (in pu) as follow: z14 = 0.004+j0.1, z24 = 0.004+j0.1, z34 = 0.008+j0.3, y40=1.2-j0.6, report and comment on the figures.
run the similar simulation as above but increase the line impedance of z14 = 0.016+j0.4, z24 = 0.016+j0.4 (decrease the electrical strength), plot results similar to figure 10.24(a,b,c) and observe the interaction of generator 1 and 2 due to the change of electrical strength z14 and z24, report on the difference due to the change of electrical strength
Tmech2 = 0.8pu and Tmech1 = 0pu, a fault current of iq4e-jid4e = -(2-j2) pu is to be introduced at t=5 sec. the fault duration is 0.15 seconds. Use the line impedances (in pu) as follow: z14 = 0.004+j0.1, z24 = 0.004+j0.1, z34 = 0.008+j0.3, plot results similar to figure 10.25(a,b,c) , plot all the bus voltages vs. time, and report the interaction of generator 1 and 2 due to the fault Observe how long the duration of the fault is so that the generator 2 will be out of synchronism?