Number of Inspected USTs: 4 Financial Responsibility:
Compliance Inspection (TCI) ü Compliance Re-Inspection (TCR) Compliance Inspection DRF Received (TCDI) Discharge Evaluation - Short Form (TDI) Closure Inspection (TXI) Closure Inspection - All Tanks Closed (TXIF) Paperwork Only
ASTs: 0
Mineral Acid Tanks: 0
Mechanism Insurance
Effective Date
10/06/2005
Carrier
Expiration Date
10/06/2006
Commerce&Industry
Inspection Results Based on the inspection results and information provided by the owner/operator, this facility APPEARS TO MEET the requirements of Chapter 27 Articles X (Storage Tanks), XII (Hazardous Material), and XIII (Wellfield Protection) of the Broward County Natural Resource Protection Code and Florida Administrative Code 62-761 and 62-762 (Under and Above Ground Storage Tank Systems), as applicable. (see following pages for details)
NOTICE: By 12/31/09, all underground storage tank systems shall have secondary containment. Name of On-site Representative Receiving Inspection Results and Debriefing: Linda Aflalo - Partner
On-site Representative Signature: Name/Phone Number of Inspector Completing Inspection:
Jose Martinez (954-818-7541) Date Inspection Completed: 3/14/2006
Broward County Board of County Commissioners Josephus Eggelletion, Jr. • Ben Graber • Sue Gunzburger • Kristin D. Jacobs • Ilene Lieberman • Lori Nance Parrish • John E. Rodstrom, Jr. • Jim Scott • Diana Wasserman-Rubin
www.broward.org
Facility Name: Ocello's Woodmont Chevron
Inspection Date: Mar/14/2006
Page 2 of 2
Operation Description at Time of Inspection: Gas station and convenience store.
Inspector Comments: (Refer to page 4 of 4 for violations cited, if any) 1)The piping sumps properly maintained. Water was removed from the sumps. 2)Veeder-Root TLS-350 is working properly. All lights were replaced. 3)Sensors at the sumps and dispensers properly installed. 4)CSLD test done by Veeder - Root TLS 350 and pass. 5)The in line leak detectors test are done electronic by the Veeder - Root TLS 350. 6)The RDRL is developed and available for inspection. 7)The monthly visual inspections are done and they are kept in a log book. The inspections cover all of the items that have secondary containment and the automatic release detection equipment records kept. 8)The registration for the current year has been paid for and is on file. 9)The third party petroleum liability insurance is on file and is up to date. 10)Historical photos taken and current site map develop. 11)The Broward County Hazardous Materials License is kept at the office.
Disbributed Informational Brochures, if Any:
FDEP Storage Tank Inspection Cover Page for: 8625875
Page 1 of 3
Florida Department of Environmental Protection Bureau of Petroleum Storage Systems Facility Inspection Cover Page Facility Information District: SED County: Broward Facility ID#: 8625875 Name: Chevron-Woodmont 8351 Nw 88th Ave Tamarac, FL 33321-1539 Contact: Peter Ocello Phone: 954-722-0111 Account Owner Information Name: Ocello Enterprises 8351 Nw 88th Ave
Type: Retail Station Status: Open Latitude: 26:13:42.2272 Longitude: 80:16:12.3647 LL Method: DPHO LL Status: REVIEWED Status Date: 12//29/2003
FDEP Storage Tank Inspection Cover Page for: 8625875
Page 2 of 3
G 4
10000 Vehicular Diesel
02/01/1983
UNDER
U
5
1000
09/01/1985
UNDER
B
Waste Oil
E O A M
C F K J
8 G L N K
***Note: Construction, Piping, and Monitoring Info not shown for CLOSED tanks (Status of A or B). Most Recent Insurance Document FR Type Insurance
Effective Date
Expiration Date
Company Name
10/06/2005
10/06/2006
Commerce & Industry
Compliance Activity Information Activity Code
Date Done
Results
Inspector
AST/UST Count
Project Description
TCI
03/04/2005 In-Compliance
Martinez_J
0/4
Compliance Assurance
TCI
03/06/2006 Minor Out-Of-Compliance
Martinez_J
0/4
Compliance Assurance
Open Violations Viol Sig Violation Text # Level 03/06/2006 1025 N Not Installed According To Manufacturer'S Instructions Spill Containment, Dispenser Liners And Piping Sumps Accessible; Water And 03/06/2006 1115 N Regulated Substances Not Removed Insp Date
Discharge Information Discharge Cleanup Score Eligibility Info Date Status 11/18/1988 Completed 02/20/1989 Combined 09/07/1995 Inactive Petroleum Liability And Restoration Insurance 09/08/1998 Inactive 10 Program-Eligible