Split System Cooling Units

Split System Cooling Units Split System Cooling Units TTA075A-TTA200B Air Handlers TWE050A-TWE200B 50 Hz December 2000 SS-PRC003-EN Introduction ...
Author: Kimberly Kelly
22 downloads 2 Views 4MB Size
Split System Cooling Units Split System Cooling Units TTA075A-TTA200B Air Handlers TWE050A-TWE200B 50 Hz

December 2000

SS-PRC003-EN

Introduction

Split System Heat Pump Units… Designed With Your Needs In Mind. The Trane reputation for quality and reliability in air conditioning continues with the Odyssey™ family of light commercial split systems. Trane paid attention to your needs to make sure you get a system that will meet your job requirements every time...and at a competitive price.

©American Standard Inc. 2000

CoupleTrane’s reputation for quality and reliability in split system air conditioners with efficiency, flexibility, and installation ease...and you have systems that will give you “Simply the Best Value.”

SS-PRC003-EN

Contents Introduction Features and Benefits

2

Application Considerations

7

Selection Procedure

8

4

Model Number Description

General Data

9 10

Performance Data

13

Cooling Performance Fan Performance

SS-PRC003-EN

Electric Power

13 39 46

Connection and Wiring

48

Dimension and Weights

54

Mechanical Specifications

75

3

Features and Benefits

Condensing Units

• Trane 3-D® scroll compressor (TTA075-100A) • (2)Trane Climatuff compressors ™

(TTA100-125B) with independent refrigerant circuits • (2)Trane 3-D scroll compressors (TTA155-200B) with independent refrigerant circuits • 2) Manifolded scroll compressors with unloading capability (TTA100-155C) • Compressor motor overload protection • Control transformer • High and low pressure cutout switches • Internal pressure relief valve (TTA100B125B) • Liquid line filter drier, factory installed • Holding charge of nitrogen • Copper tube, aluminum plate fin coils • Low ambient cooling to 35°F (1.7°C) as manufactured • Weather resistant baked enamel finish • Heavy gauge steel cabinet • Mounting/lifting rails under base All condensing units offer these optional accessories: • Head Pressure Control — Low Ambient CoolingTo 0°F (-17.8°C) • Coil Guards Kits • Isolators both Rubber-in-Shear and SpringType • Anti-Short-Cycle Kit • Time Delay Relay • Black Epoxy Coated Condenser Coils

4

Air Handlers

• Low voltage terminal board • Expansion valve(s) • Convertible • PVC drain pan • Fan relay • Efficient evaporator coil • Baked enamel finish • Filter access panel • 1” (25.4 mm) throwaway filters standard with provisions for field supplied 2” (50.8 mm) filters • Adjustable belt drive motor • Single point power entry to electric heaters • Refrigerant piping and/or electrical connections provided from either side

Odyssey™ air handler versatility is further increased by a complete line of optional accessories designed to match and easy to install: • Discharge Plenum and Grille • Return Grille • Subbase • Electric Heaters • High Static Evaporator Motor • Isolators both Rubber-in-Shear and SpringType

SS-PRC003-EN

Features and Benefits Condensing Units Options The Odyssey™ split system product line includes condensing units in both single unloading and dual compressor options. TTA075A andTTA100A-ton single compressor models feature single refrigeration circuitry lowering job installation costs by requiring only one set of refrigerant lines.These units are ideal for their low cost, new construction jobs, as well as renovation and replacement buildings. Equally important, Odyssey offers a single refrigerant circuit/capacity unloading option inTTA100C and TTA155C condensing units. These unloading units feature dual manifolded scroll compressors. They offer an excellent opportunity for both new construction and replacement jobs with two stages of capacity modulation and a single refrigeration circuit.

In addition, Odyssey modelsTTA100B, TTA125B,TTA155B andTTA200B are dual compressor units to give true standby protection; if one compressor fails, the second will automatically start-up. Also, the first compressor can be serviced without shutting down the unit since refrigerant circuits are independent. Dual compressors are not just for protection; they also save energy costs. Most buildings are designed for the peak load requirements, yet the building usually operates at less than peak load. During light load conditions only one compressor functions to maintain the space comfort thus reducing the need for energy. Trane split systems have been specified in thousands of applications.You will find Odyssey will win even more jobs with its smaller, more manageable cabinet. Low Ambient Cooling Operation Each condensing unit can operate to 35°F (1.7°C) as standard. An accessory Head Pressure Control gives you the capability to operate to 0°F (-17.8°C).

SS-PRC003-EN

5

Features and Benefits Air Handlers Offer More Flexibility Flexibility is a key to meeting changing market requirements. Odyssey split systems offer not only various compressor options but also convertible air handlers.The air handlers can be installed either vertically in a mechanical room or horizontally above a ceiling. They do not require any removal of panels or reconfiguration of the drain pan to make either airflow application work. These air handlers have a double sloped condensate drain pan that allows for either airflow configuration and can easily be removed for cleaning. All the air handlers feature factory installed belt drive and ball bearing evaporator fans with adjustable sheaves for maximum airflow performance. The standard motor on theTWE100A air handler will deliver 3325 cfm (5650 m3/h) at 1.0” (250 Pa) ESP. Additionally, oversized motors are available for higher static applications. Odyssey air handler versatility is further increased by a complete line of accessories designed to match and install smoothly: • Discharge Plenum and Grille • Return Grille • Subbase • Electric Heaters • High Static Evaporator Motor • Isolators both Rubber-in-Shear and SpringType • A Full Line ofThermostats Odyssey™ — A Complete Split System Odyssey delivers the flexibility to select a complete system that meets your particular job requirements. Air Handlers are designed, tested, and rated with condensing units to let you select the proper match between capacity and load. Condensing units can also be matched with Trane built-up air handlers.These matched systems can be quickly engineered for specific applications using Trane’s computerized selection programs.

6

SS-PRC003-EN

Application Considerations Application of this product should be within the catalogued airflow and performance considerations. Clearance Requirements The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances that appear inadequate should be reviewed with your localTrane Representative.

Low Ambient Cooling As manufactured, these units can operate to 35°F (1.7°C) in the cooling mode of operation. An accessory head pressure control will allow operation to 0°F (-17.8°C) outdoor ambient. When using these units with control systems such as bypass changeover Variable Air Volume, consider the requirement for a head pressure control to allow low ambient cooling.

Typical Horizontal Air Handler Application

Typical Split System Application Typical Vertical Air Handler Application

SS-PRC003-EN

7

Selection Procedure Cooling Capacity Step 1 — Calculate the building’s total and sensible cooling loads at design conditions. Use theTrane calculation form or any other standard accepted method.

Note:The formula below the table can be used to calculate Fan Motor Heat, 3.5 x Bhp = MBh 3.5 x 1.17 = 4.10 MBh

Step 2 — Size the equipment usingTable 13-1. Match the cooling loads at design conditions.

NetTotal Cooling Capacity = 77.7 MBh – 4.10 = 73.6 MBh 16.8 - 1.2 = 15.6 kW Net Sensible Cooling Capacity = 57.3 MBh – 4.10 = 53.2 MBh 22.8 - 1.2 = 21.6 kW

Example:The following are the building cooling requirements a Electrical Characteristics: 380-415/50/3 b Summer Design Conditions: Entering Evaporator Coil: 80 DB/67 WB (27 DB/19 WB C) Outdoor Ambient: 95° F (35° C) c Total Cooling Load: 75 MBh (22 kW) d Sensible Cooling Load: 53 MBh (15.5 kW) e Airflow: 3000 cfm (5097 m3/h) External Static Pressure: 0.77 in. (192.5 Pa) Table 13-1 shows that aTTA075A matched with aTWE075A has a gross cooling capacity of 77.7 MBh (22.8 kW) and 57.3 MBh (16.8 kW) sensible capacity at 95 DB (35° C) ambient and 3000 cfm (5097 m3/h) and 80 DB/67 WB (27 DB/19 WB) air entering the evaporator. To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit static pressure: External Static Standard Filter Supplementary Electric Heat Total Static Pressure

In. Pa 0.77 193 0.10 25 0.23 57 1.10 275

1.375 x (kW) = kW 1.375 x 0.8 = 1.1 kW

Heating Capacity Step 1 — Calculate the building heating load. Step 2 — Size the system heating capacity to match the calculated building heating load.The following are building heating requirements: a Total Heating Load at 97.0 MBh (28.4 kW) b 3000 cfm (5097 m3/h) c Electric Supplementary Heaters Table 45-1, the 34.88 kW heater has a capacity of 119,045 btu. FromTable 47-1, the 34.88 kW indicates the heater model number is BAYHTRL435A.This heater will adequately cover the building’s heating requirement. Air Delivery Selection External static pressure drop through the air distribution system has been calculated to be 0.77 inches (192.5 Pa) of water gauge. FromTable 44-2 static pressure drop through the electric heater is 0.23 inches (57.5 Pa) of water (0.77 + 0.23 = 1.00 in.) (192.5 + 57.5 = 250 Pa). EnterTable 39-1 forTWE075AD at 3000 cfm (5097 m3/h) and 1.00 static pressure (250 Pa).The standard motor at 821 rpm will give the desired airflow.

Note: The Evaporator Fan Performance Table has included the effect of a 1 in. (250 Pa) filter already.Therefore, the actualTotal Static Pressure is 1.10 - 0.10 = 1.00 in. (275 - 25 = 250 Pa). With 3000 cfm (5097 m3/h) and 1.00 inches (250 Pa), Table 39-1 shows a 1.17 bhp (0.8 kW).

8

SS-PRC003-EN

Model Number Description CONDENSING UNIT MODEL NOMENCLATURE T T A 0 7 5 A D 0 0 B 0 Service Digit TTA = Cooling Only Nominal Gross Cooling Capacity (MBh) 075 = 75 100 = 100 155 = 155 200 = 200

Minor Design Sequence Factory Installed Options 00 = No Options 0S = Black Epoxy Coated Condenser Coil Electrical Characteristics D = 380-415/3/50

Compressor A = Single Compressor B = Dual Compressor C = Scroll

AIR HANDLER MODEL NOMENCLATURE T W E 0 5 0 A D 0 0 B 0 Service Digit TWE = Cooling Convertible Minor Design Sequence Nominal Gross Cooling Capacity (MBh) 050 = 50 075 = 75 100 = 100 155 = 155 200 = 200

Factory Installed Options 00 = No Options Electrical Characteristics D = 380-415/3/50

Refrigerant Circuit A = Single B = Dual

SS-PRC003-EN

9

General Data

Condensing Unit

Table GD-1 — General Data Cooling Performance1 Gross Cooling Capacity, btu (kW) Matched Air Handler (kW) Condensing Unit Only2 (kW) ARI Net Cooling Capacity3 (kW) System Power kW Condensing Unit Power kW Compressor Number Type No. Speeds No. Motors Motor HP (kW) Motor RPM ARI Sound Rating (Bels)4 System Data5 No. Refrigerant Circuits Suction Line in. (mm) OD Liquid Line in. (mm) OD Outdoor Coil — Type Tube Size in. (mm) OD Face Area, sq. ft (m2) Rows Fins Per Inch Outdoor Fan Type No. Used Diameter in. (mm) DriveType No. Speeds CFM6 (m3/h) No. Motors Motor HP (kW) Motor RPM R-22 Refrigerant Charge, lb7 (kg)

TTA075A

TTA085A

TTA100A

TTA100B

82,000(24.01) 80,000(23.36) 79,000(23.06) 7.92 7.32

91,000(26.64) 91,000(26.64) 87,000(25.47) 8.7 7.8

111,000(32.59) 107,000(31.36) 107,000(31.36) 10.66 9.76

102,000(30.0) 102,000(30.0) 100,000(29.3) 11.3 10.3

1 Trane 3-D® Scroll 1 1 6.25 (4.7) 2875 8.8

1 Trane 3-D® Scroll 1 1 6.91(5.16) 2875 8.8

1 Trane 3-D® Scroll 1 1 8.33(6.21) 2875 8.8

2 Trane Climatuff™ 2

1 1.375(34.9) 0.500(12.7) Plate Fin 0.375(9.5) 15.33(1.42) 2 20(508) Propeller 1 26.00(660.4) Direct 1 4700(7985) 1 0.33(.24) 925 13.0(5.90)

1 1.375(34.9) 0.500(12.7) Plate Fin 0.375(9.5) 18.43(1.71) 2 20(508) Propeller 1 28.00(711.2) Direct 1 6500(11042) 1 0.75(.56) 925 16.0(7.26)

1 1.375(34.9) 0.500(12.7) Plate Fin 0.375(9.5) 18.4(1.71) 2 20(508) Propeller 1 28.00(711.2) Direct 1 6500(11042) 1 0.75(.56) 975 16.0(7.26)

2 1.120(28.5) 0.375(9.5) Plate Fin 0.375(9.5) 18.43(5.6) 2 20(508) Propeller 1 28.00(711.2) Direct 1 6500(11042) 1 0.75(.55) 925 18.8(8.5)

4.15(3.1) 2875 9.0

Notes: 1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F (35°C) ambient. 3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry bulb, and 67°F (19.4°C) entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270. 5. System Data based on maximum linear length 80 ft (26.7 m) Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications manual. 6. Outdoor Fan cfm is rated with standard air-dry coil outdoor. 7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.

10

SS-PRC003-EN

General Data

Condensing Unit

Table GD-2— General Data Cooling Performance1 Gross Cooling Capacity, btu (kW) Matched Air Handler Condensing Unit Only2 ARI Net Cooling Capacity3 System Power kW Condensing Unit Power kW Compressor Number Type No. Speeds No. Motors Motor HP (kW) Motor RPM ARI Sound Rating (Bels)4 System Data5 No. Refrigerant Circuits Suction Line in. (mm) OD Liquid Line in. (mm) OD Outdoor Coil — Type Tube Size in. (mm) OD Face Area, sq. ft (m2) Rows Fins Per Inch Outdoor Fan Type No. Used Diameter in. (mm) Drive Type No. Speeds CFM6 (m3/h) No. Motors Motor HP (kW) Motor RPM R-22 Refrigerant Charge, lb7 (kg)

TTA100C

TTA125B

TTA155B

TTA155C

TTA200B

108,000(31.62) 108,000(31.62) 106,000(31.05) 9.61 9.01

127,000(37.2) 127,000(37.2) 123,000(36.0) 13.1 12.1

166,000(48.60) 163,000(47.73) 161,000(47.14) 16.01 14.58

160,000(46.85) 155,000(45.39) 153,000(44.80) 15.4 14.6

216,000(63.24) 209,000(61.18) 209,000(61.18) 21.40 19.39

2 Scroll Tandem 2 4.16(3.10) 2875 8.8

2 Trane Climatuff™ 1 2 5.20(3.9) 2875 8.8

2 Trane 3-D® Scroll 1 2 6.25(4.7) 2875 8.8

2 Trane 3-D® ScrollTandem 1 1 6.25(4.7) 2875 8.8

2 Trane 3-D® Scroll 1 2 8.33(6.21) 2875 8.8

1 1.375(34.9) 0.500(12.7) Plate Fin 0.375(9.5) 18.4(1.71) 2 20 (508) Propeller 1 28.00(711.2) Direct 1 6500(11042) 1 0.75(.56) 925 15.5(7.03)

2 1.375(34.9) 0.500(12.7) Plate Fin 0.375(9.5) 23.97(7.3) 2 18(457.2) Propeller 1 28.00(711.2) Direct 1 6760(11484) 1 0.75(.55) 925 25.2(11.4)

2 1.375(34.9) 0.500(12.7) Plate Fin 0.375(9.5) 30.66(2.84) 2 20(508) Propeller 2 26.00(660.4) Direct 1 9400(15969) 1 0.33(.24) 925 26.0(11.8)

1 1.625(41.3) 0.625(15.9) Plate Fin 0.375(9.5) 30.66(2.84) 2 20 (508) Propeller 2 26.00(660.4) Direct 1 9400(15969) 1 0.33(.24) 925 27.0(12.34)

2 1.375(34.9) 0.500(12.7) Plate Fin 0.375(9.5) 43.9(4.08) 2 15(381) Propeller 2 28.00(711.2) Direct 1 13400(22764) 2 0.75(.56) 925 36.0(16.33)

Notes: 1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction temperature and at 95°F (35°C) ambient. 3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.2 m) of 1.375, 0.500 OD interconnecting tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) ambient, 80°F (26.7°C) entering dry bulb, and 67°F (19.4°C) entering wet bulb at ARI rated cfm. 4. Sound Rating shown is tested in accordance with ARI Standard 270. 5. System Data based on maximum linear length 80 ft (26.7 m) Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications manual. 6. Outdoor Fan cfm is rated with standard air-dry coil outdoor. 7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.

SS-PRC003-EN

11

General Data

Air Handler

Table GD-3 — General Data TWE050A System Data1 No. Refrigerant Circuits 1 Suction Line in. (mm) OD 1.120(28.4) Liquid Line in. (mm) OD 0.38(9.7) Indoor Coil — Type Plate Fin Tube Size in. (mm) OD 0.375(9.5) 5.00(.47) Face Area sq. ft (m2) Rows 3 Fins Per Inch 12 Refrigerant Control Expansion Valve Drain Connection No. 4 Drain Connection Size in. (mm) 0.75(19.0) Drain Connection Type PVC Indoor Fan Type FC Centrifugal No. Used 1 Diameter in. (mm) 12.0(304.8) Width in. (mm) 12.0(304.8) Drive Type Belt No. Speeds 1 3 1670(2837) CFM (m /h) No. Motors 1 Motor HP (kW) - Standard/Oversized 0.75/1.0(.55/.74) Motor RPM (Standard) 1425 Motor Frame Size (Standard) 56 Filters — Type Throwaway Furnished Yes No. 1/1 Recommended Size, in. (mm) 16x20x1/20x20x1 (406.4x508x25.4/ 508x508x25.4)

TWE075A

TWE100A

TWE100B

1 1.380(35.0) 0.50(12.7) Plate Fin 0.375(9.5) 8.07(.75) 3 12 Expansion Valve 4 0.75(19.0) PVC FC Centrifugal 1 15.0(381) 15.0(381) Belt 1 2500(4247) 1

1 1.380(35.0) 0.50(12.7) Plate Fin 0.375(9.5) 11.18(1.0) 3 12 Expansion Valve 4 0.75(19.0) PVC FC Centrifugal 1 15.0(381) 15.0(381) Belt 1 3325(5649) 1

2 1.380(35.0) 0.50(12.7) Plate Fin 0.375(9.5) 11.18(1.0) 3 12 Expansion Valve 4 0.75(19.0) PVC FC Centrifugal 1 15.0(381) 15.0(381) Belt 1 3325(5649) 1

1.0/1.5(.74/1.11) 1425 56 Throwaway Yes 3 16x25x1 (406.4x635x25.4)

1.5/2.0(1.11/1.49) 1425 56 Throwaway Yes 4 16x25x1 (406.4x635x25.4)

1.5/2.0(1.11/1.49) 1425 56 Throwaway Yes 4 16x25x1 (406.4x635x25.4)

Notes: 1. ARI certified with various condensing units per ARI Standard 210/240 or 340/360-93. Refer to Performance Data section in this catalog.

Table GD-4 — General Data System Data No. Refrigerant Circuits Suction Line in. (mm) OD Liquid Line in. (mm) OD Indoor Coil — Type Tube Size in. (mm) OD Face Area sq. ft (m2) Rows Fins Per Inch Refrigerant Control Drain Connection No. Drain Connection Size in. (mm) Drain Connection Type Indoor Fan Type No. Used Diameter in. (mm) Width in. (mm) Drive Type No. Speeds CFM (m3/h) No. Motors Motor HP — Standard/Oversized Motor RPM (Standard) Motor Frame Size (Standard) Filters — Type Furnished No. Recommended Size, in. (mm)

12

TWE155B

TWE200B

2 1.38(35.0) 0.500(12.7) Plate Fin 0.375(9.5) 16.33(1.52) 3 12 Expansion Valve 4 1.000(25.4) PVC FC Centrifugal 2 15.0(381) 15.0(381) Belt 1 5000(8494) 1 2.0/3.0(1.49/2.24) 1425 145T Throwaway Yes 8 15x20x2 (381x508x50.8)

2 1.38(35.0) 0.500(12.7) Plate Fin 0.375(9.5) 21.63(2.01) 3 12 Expansion Valve 4 1.000(25.4) PVC FC Centrifugal 2 15.0(381) 15.0(381) Belt 1 6650(11297) 1 3.0/5.0(2.24/3.72) 1425 184T Throwaway Yes 4/4 16x20x2/16x25x2 (406.4x508x50.8/ 406.4x635x50.8)

Notes: 1. ARI certified with various condensing units per ARI Standard 210/240 or 340/360-93. Refer to Performance Data section in this catalog.

SS-PRC003-EN

Performance Data

System

Table PD-1 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit with TWE075A Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 2250

2500

2750

3000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 75.7 76.2 77.8 81.8 77.3 77.9 80.4 84.6 78.6 79.4 82.7 86.9 79.7 80.8 84.6 89.0

SHC 59.6 69.5 77.8 81.8 62.3 73.2 80.4 84.6 64.9 76.7 82.7 86.9 67.3 80.1 84.6 89.0

67 TGC 83.5 83.7 84.1 84.6 85.1 85.3 85.7 86.4 86.3 86.6 87.0 88.0 87.4 87.7 88.2 89.1

SHC 50.1 57.4 67.3 77.2 49.2 59.9 70.6 81.6 50.8 62.2 73.9 85.8 52.3 64.5 77.0 89.1

95

73 TGC 91.7 92.0 92.4 92.5 93.1 93.6 94.0 94.2 94.2 94.8 95.3 95.5 95.2 95.9 96.1 96.7

SHC 34.0 44.6 54.9 64.8 34.5 46.1 57.4 67.9 35.2 47.5 59.7 70.9 35.7 48.8 61.3 73.7

61 TGC 73.1 73.6 75.6 79.4 74.5 75.2 78.0 82.0 75.7 76.6 80.1 84.3 76.7 77.7 82.0 86.3

105 Entering Wet Bulb (°F) 73 61

67 SHC 58.2 68.1 75.6 79.4 60.9 71.8 78.0 82.0 63.4 75.3 80.1 84.3 65.9 77.7 82.0 86.3

TGC 80.5 80.6 81.1 81.6 81.9 82.1 82.6 83.4 83.0 83.3 83.8 85.0 84.0 84.4 84.9 86.4

SHC 48.8 56.0 65.9 75.8 47.8 58.5 69.2 80.2 49.4 60.8 72.4 84.4 51.0 63.0 75.5 86.4

TGC 88.2 88.6 89.0 89.2 89.4 90.0 90.4 90.7 90.4 91.1 91.4 91.9 91.3 92.1 92.4 93.0

SHC 32.7 43.3 53.6 63.4 33.3 44.8 56.0 66.5 33.9 46.2 57.8 69.4 34.3 47.5 59.8 72.3

TGC 69.9 70.5 72.9 76.7 71.2 72.0 75.2 79.1 72.3 73.1 77.2 81.2 73.2 74.8 78.9 83.1

SHC 56.6 66.6 72.9 76.7 59.2 70.2 75.2 79.1 61.7 73.1 77.2 81.2 64.1 74.8 78.9 83.1

67 TGC 76.9 77.1 77.6 78.3 78.2 78.5 78.9 79.9 79.3 79.6 80.1 81.3 79.8 80.6 81.2 83.2

SHC 47.4 54.4 64.2 74.3 46.3 56.8 67.6 78.6 47.9 59.1 70.7 81.3 48.9 61.3 73.8 83.2

115

73 TGC 84.1 84.7 85.1 85.3 85.2 85.9 86.2 86.7 86.1 87.0 87.3 87.9 86.9 87.9 88.3 88.8

SHC 31.3 41.8 52.2 61.8 31.8 43.3 54.1 64.9 32.4 44.7 56.2 67.8 32.8 46.0 58.2 70.6

61 TGC 66.3 67.0 69.9 73.5 67.5 68.5 72.0 75.8 68.5 69.9 73.8 77.8 69.4 71.4 75.5 79.6

SHC 54.8 64.8 69.9 73.5 57.4 68.4 72.0 75.8 59.8 69.9 73.8 77.8 62.2 71.4 75.5 79.6

67 TGC 72.9 73.2 73.7 74.5 74.1 74.4 74.9 75.9 74.7 75.5 76.1 77.9 75.6 76.4 77.1 79.6

73

SHC TGC SHC 45.8 79.5 29.8 52.6 80.3 40.3 62.5 80.8 50.6 72.5 81.1 60.1 44.6 80.6 30.3 55.0 81.5 41.7 65.7 81.8 52.4 75.9 82.4 63.1 45.7 81.4 30.8 57.2 82.5 43.1 68.9 82.9 54.4 77.9 83.4 66.0 47.0 82.1 31.2 59.4 83.3 44.4 72.0 83.8 56.3 79.6 84.3 68.8

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-1 — Gross Cooling Capacities (kW) TTA075A Condensing Unit with TWE075A Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 3823

4248

4673

5098

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 22.2 22.3 22.8 24.0 22.6 22.8 23.5 24.8 23.0 23.2 24.2 25.5 23.3 23.7 24.8 26.1

SHC 17.5 20.4 22.8 24.0 18.2 21.4 23.5 24.8 19.0 22.5 24.2 25.5 19.7 23.5 24.8 26.1

19.4 TGC 24.5 24.5 24.6 24.8 24.9 25.0 25.1 25.3 25.3 25.4 25.5 25.8 25.6 25.7 25.8 26.1

SHC 14.7 16.8 19.7 22.6 14.4 17.5 20.7 23.9 14.9 18.2 21.6 25.1 15.3 18.9 22.5 26.1

35.0

22.8 TGC 26.9 26.9 27.1 27.1 27.3 27.4 27.5 27.6 27.6 27.8 27.9 28.0 27.9 28.1 28.1 28.3

SHC 9.9 13.1 16.1 19.0 10.1 13.5 16.8 19.9 10.3 13.9 17.5 20.8 10.4 14.3 18.0 21.6

16.1 TGC 21.4 21.5 22.1 23.3 21.8 22.0 22.8 24.0 22.2 22.4 23.5 24.7 22.4 22.8 24.0 25.3

19.4 SHC 17.0 20.0 22.1 23.3 17.8 21.0 22.8 24.0 18.6 22.1 23.5 24.7 19.3 22.8 24.0 25.3

TGC 23.6 23.6 23.7 23.9 24.0 24.0 24.2 24.4 24.3 24.4 24.5 24.9 24.6 24.7 24.9 25.3

SHC 14.3 16.4 19.3 22.2 14.0 17.1 20.3 23.5 14.5 17.8 21.2 24.7 14.9 18.4 22.1 25.3

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 25.8 25.9 26.1 26.1 26.2 26.3 26.5 26.5 26.5 26.7 26.8 26.9 26.7 27.0 27.1 27.2

SHC 9.6 12.7 15.7 18.6 9.7 13.1 16.4 19.5 9.9 13.5 16.9 20.3 10.0 13.9 17.5 21.2

TGC 20.5 20.6 21.3 22.5 20.8 21.1 22.0 23.2 21.2 21.4 22.6 23.8 21.4 21.9 23.1 24.3

SHC 16.6 19.5 21.3 22.5 17.3 20.6 22.0 23.2 18.1 21.4 22.6 23.8 18.8 21.9 23.1 24.3

19.4 TGC 22.5 22.6 22.7 22.9 22.9 23.0 23.1 23.4 23.2 23.3 23.5 23.8 23.4 23.6 23.8 24.4

SHC 13.9 15.9 18.8 21.7 13.6 16.6 19.8 23.0 14.0 17.3 20.7 23.8 14.3 17.9 21.6 24.4

46.1

22.8 TGC 24.6 24.8 24.9 25.0 24.9 25.2 25.2 25.4 25.2 25.5 25.6 25.7 25.4 25.7 25.8 26.0

SHC 9.2 12.3 15.3 18.1 9.3 12.7 15.9 19.0 9.5 13.1 16.5 19.8 9.6 13.5 17.0 20.7

16.1 TGC 19.4 19.6 20.5 21.5 19.8 20.1 21.1 22.2 20.0 20.5 21.6 22.8 20.3 20.9 22.1 23.3

SHC 16.0 19.0 20.5 21.5 16.8 20.0 21.1 22.2 17.5 20.5 21.6 22.8 18.2 20.9 22.1 23.3

19.4 TGC 21.4 21.4 21.6 21.8 21.7 21.8 21.9 22.2 21.9 22.1 22.3 22.8 22.1 22.4 22.6 23.3

22.8

SHC TGC SHC 13.4 23.3 8.7 15.4 23.5 11.8 18.3 23.7 14.8 21.2 23.7 17.6 13.1 23.6 8.9 16.1 23.9 12.2 19.3 24.0 15.3 22.2 24.1 18.5 13.4 23.8 9.0 16.8 24.2 12.6 20.2 24.3 15.9 22.8 24.4 19.3 13.8 24.0 9.1 17.4 24.4 13.0 21.1 24.5 16.5 23.3 24.7 20.2

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

13

Performance Data

System

Table PD-2 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit with TWE100A Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow

2550

2875

3200

3525

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 79.9 80.7 83.7 88.0 81.5 82.8 86.7 91.2 82.9 84.6 89.2 93.9 84.2 86.6 91.4 96.2

SHC 65.5 77.2 83.7 88.0 69.1 82.3 86.7 91.2 72.6 84.6 89.2 93.9 75.9 86.6 91.4 96.2

67 TGC 87.9 88.1 88.5 89.5 89.5 89.8 90.3 91.2 90.8 91.2 91.9 93.9 91.6 92.3 93.2 96.2

SHC 54.1 62.8 74.4 86.2 53.5 66.1 79.0 91.2 55.7 69.3 83.4 93.9 57.1 72.3 87.7 96.2

95

73 TGC 95.9 96.6 97.0 97.2 97.3 98.2 98.6 98.8 98.5 99.4 99.7 100.2 99.4 100.5 100.9 101.4

SHC 35.7 48.0 60.0 71.4 36.4 49.9 63.3 75.6 37.0 51.8 65.7 79.7 37.6 53.5 68.4 83.6

61 TGC 76.9 77.9 81.1 85.3 78.4 79.6 83.9 88.3 79.8 81.8 86.3 90.9 80.9 83.7 88.4 93.0

105 Entering Wet Bulb (°F) 73 61

67 SHC 64.0 75.8 81.1 85.3 67.6 79.6 83.9 88.3 71.0 81.8 86.3 90.9 74.3 83.7 88.4 93.0

TGC 84.5 84.8 85.2 86.3 86.0 86.3 86.9 88.4 86.9 87.6 88.4 90.9 87.9 88.7 89.7 93.1

SHC 52.7 61.3 72.9 84.8 52.1 64.6 77.5 88.4 53.7 67.7 81.9 90.9 55.5 70.7 86.1 93.1

TGC 92.0 92.8 93.3 93.5 93.3 94.3 94.5 95.1 94.3 95.5 95.8 96.3 95.1 96.5 96.9 97.5

SHC 34.4 46.6 58.7 69.9 35.1 48.5 61.3 74.1 35.6 50.4 64.1 78.2 36.2 52.1 66.8 82.1

TGC 73.5 74.6 78.1 82.2 74.9 76.5 80.8 85.1 76.1 78.6 83.0 87.4 77.2 80.4 84.9 89.5

SHC 62.2 74.1 78.1 82.2 65.8 76.5 80.8 85.1 69.2 78.6 83.0 87.4 72.5 80.4 84.9 89.5

67 TGC 80.7 81.0 81.5 82.3 82.0 82.4 83.1 85.2 82.8 83.6 84.5 87.5 83.7 84.5 85.8 89.6

SHC 51.2 59.6 71.2 82.3 50.5 62.8 75.8 85.2 51.9 65.9 80.1 87.5 53.6 68.9 84.4 89.6

115

73 TGC 87.7 88.6 89.2 89.4 88.8 90.0 90.3 90.8 89.7 91.1 91.5 92.1 90.4 92.0 92.5 93.1

SHC 32.9 45.1 57.2 68.3 33.5 47.0 59.6 72.5 34.1 48.9 62.4 76.5 34.6 50.6 65.1 80.4

61 TGC 69.6 70.8 74.8 78.8 70.9 73.1 77.2 81.4 72.1 75.0 79.3 83.7 73.1 76.7 81.1 85.6

SHC 60.3 70.8 74.8 78.8 63.8 73.1 77.2 81.4 67.2 75.0 79.3 83.7 70.4 76.7 81.1 85.6

67 TGC 76.4 76.8 77.3 78.9 77.2 78.1 78.9 81.5 78.3 79.1 80.2 83.8 79.1 80.0 81.2 85.7

SHC 49.5 57.7 69.4 78.9 48.1 60.9 73.9 81.5 49.9 63.9 78.2 83.8 51.6 66.9 81.2 85.7

73 TGC 82.9 84.0 84.3 84.9 83.9 85.3 85.7 86.2 84.6 86.3 86.8 87.4 85.1 87.1 87.7 88.5

SHC 31.3 43.5 54.9 66.5 31.8 45.4 57.8 70.7 32.4 47.2 60.5 74.7 32.9 49.0 63.1 78.6

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-2 — Gross Cooling Capacities (kW) TTA075A Condensing Unit with TWE100A Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 4331

4885

5436

5990

Enter. Dry Bulb (°C) 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2

16.1 TGC 23.4 23.6 24.5 25.8 23.9 24.2 25.4 26.7 24.3 24.8 26.1 27.5 24.6 25.4 26.8 28.2

SHC 19.2 22.6 24.5 25.8 20.2 24.1 25.4 26.7 21.2 24.8 26.1 27.5 22.2 25.4 26.8 28.2

19.4 TGC 25.7 25.8 25.9 26.2 26.2 26.3 26.4 26.7 26.6 26.7 26.9 27.5 26.8 27.0 27.3 28.2

SHC 15.8 18.4 21.8 25.2 15.7 19.4 23.1 26.7 16.3 20.3 24.4 27.5 16.7 21.2 25.7 28.2

35.0

22.8 TGC 28.1 28.3 28.4 28.4 28.5 28.7 28.9 28.9 28.8 29.1 29.2 29.3 29.1 29.4 29.5 29.7

SHC 10.5 14.0 17.6 20.9 10.7 14.6 18.5 22.1 10.8 15.2 19.2 23.3 11.0 15.7 20.0 24.5

16.1 TGC 22.5 22.8 23.8 25.0 23.0 23.3 24.6 25.9 23.4 24.0 25.3 26.6 23.7 24.5 25.9 27.2

19.4 SHC 18.7 22.2 23.8 25.0 19.8 23.3 24.6 25.9 20.8 24.0 25.3 26.6 21.8 24.5 25.9 27.2

TGC 24.7 24.8 25.0 25.3 25.2 25.3 25.5 25.9 25.4 25.7 25.9 26.6 25.7 26.0 26.3 27.3

SHC 15.4 18.0 21.3 24.8 15.3 18.9 22.7 25.9 15.7 19.8 24.0 26.6 16.3 20.7 25.2 27.3

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 26.9 27.2 27.3 27.4 27.3 27.6 27.7 27.8 27.6 28.0 28.1 28.2 27.9 28.2 28.4 28.5

SHC 10.1 13.6 17.2 20.5 10.3 14.2 18.0 21.7 10.4 14.8 18.8 22.9 10.6 15.3 19.6 24.0

TGC 21.5 21.8 22.9 24.1 21.9 22.4 23.7 24.9 22.3 23.0 24.3 25.6 22.6 23.5 24.9 26.2

SHC 18.2 21.7 22.9 24.1 19.3 22.4 23.7 24.9 20.3 23.0 24.3 25.6 21.2 23.5 24.9 26.2

19.4 TGC 23.6 23.7 23.9 24.1 24.0 24.1 24.3 24.9 24.2 24.5 24.7 25.6 24.5 24.8 25.1 26.2

SHC 15.0 17.5 20.9 24.1 14.8 18.4 22.2 24.9 15.2 19.3 23.5 25.6 15.7 20.2 24.7 26.2

46.1

22.8 TGC 25.7 26.0 26.1 26.2 26.0 26.3 26.4 26.6 26.3 26.7 26.8 27.0 26.5 26.9 27.1 27.3

SHC 9.6 13.2 16.7 20.0 9.8 13.8 17.5 21.2 10.0 14.3 18.3 22.4 10.1 14.8 19.0 23.5

16.1 TGC 20.4 20.7 21.9 23.1 20.8 21.4 22.6 23.8 21.1 22.0 23.2 24.5 21.4 22.4 23.7 25.1

SHC 17.7 20.7 21.9 23.1 18.7 21.4 22.6 23.8 19.7 22.0 23.2 24.5 20.6 22.4 23.7 25.1

19.4 TGC 22.4 22.5 22.6 23.1 22.6 22.9 23.1 23.9 22.9 23.2 23.5 24.5 23.2 23.4 23.8 25.1

SHC 14.5 16.9 20.3 23.1 14.1 17.8 21.6 23.9 14.6 18.7 22.9 24.5 15.1 19.6 23.8 25.1

22.8 TGC 24.3 24.6 24.7 24.9 24.6 25.0 25.1 25.3 24.8 25.3 25.4 25.6 24.9 25.5 25.7 25.9

SHC 9.2 12.7 16.1 19.5 9.3 13.3 16.9 20.7 9.5 13.8 17.7 21.9 9.6 14.3 18.5 23.0

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

14

SS-PRC003-EN

Performance Data

System

Table PD-3 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit with TWE075A Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 2250

2500

2750

3000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 83.0 83.2 83.7 86.2 84.8 85.2 86.1 89.5 86.6 87.0 88.3 92.4 88.1 88.5 90.2 95.0

SHC 61.8 70.5 79.6 86.2 64.2 73.9 84.0 89.5 66.6 77.1 88.1 92.4 68.9 80.2 90.2 95.0

67 TGC 92.0 92.3 92.4 92.8 94.2 94.5 94.6 95.0 96.0 96.3 96.5 96.9 97.5 97.9 98.2 98.6

SHC 53.4 59.7 68.8 77.8 52.1 62.3 72.0 81.7 53.6 64.6 75.0 85.5 55.1 66.9 77.8 89.1

95

73 TGC 102.2 102.2 102.5 102.8 104.4 104.5 104.8 105.1 106.2 106.3 106.7 107.0 107.7 107.9 108.3 108.4

SHC 37.6 48.0 57.4 66.7 38.4 49.4 59.6 69.8 39.2 50.8 61.8 72.8 39.9 52.1 63.8 75.1

61 TGC 80.0 80.4 81.1 84.0 81.9 82.3 83.4 87.1 83.5 84.0 85.3 89.9 85.0 85.5 87.7 92.3

105 Entering Wet Bulb (°F) 73 61

67 SHC 60.1 69.0 78.2 84.0 62.6 72.4 82.5 87.1 65.0 75.5 85.3 89.9 67.3 78.6 87.7 92.3

TGC 88.9 89.2 89.4 89.8 90.9 91.3 91.5 91.9 92.6 93.0 93.2 93.6 94.0 94.2 94.8 95.3

SHC 52.1 58.3 67.3 76.3 50.6 60.8 70.4 80.2 52.2 63.2 73.4 83.9 53.6 65.0 76.2 87.6

TGC 98.7 98.8 99.1 99.4 100.8 100.9 101.2 101.6 102.4 102.6 103.0 103.1 103.8 104.1 104.5 104.7

SHC 36.4 46.6 56.0 65.3 37.1 48.0 58.2 68.4 37.9 49.3 60.4 71.0 38.6 50.6 62.4 73.6

TGC 76.9 77.4 78.2 81.5 78.8 79.2 80.2 84.5 80.3 80.8 82.7 87.2 81.6 82.2 84.9 89.5

SHC 58.5 67.4 76.6 81.5 61.0 70.7 80.2 84.5 63.3 73.9 82.7 87.2 65.6 76.9 84.9 89.5

67 TGC 85.6 86.0 86.1 86.5 87.5 87.9 88.1 88.5 89.0 89.2 89.8 90.2 90.4 90.6 91.2 91.8

SHC 50.7 56.8 65.7 74.7 49.1 59.3 68.8 78.6 50.6 61.3 71.8 82.3 52.1 63.4 74.6 85.9

115

73 TGC 95.0 95.2 95.5 95.8 96.9 97.1 97.5 97.9 98.4 98.7 99.2 99.3 99.7 100.1 100.6 100.8

SHC 35.1 45.1 54.5 63.9 35.8 46.5 56.8 67.0 36.5 47.8 58.9 69.4 37.2 49.1 60.9 72.0

61 TGC 73.7 74.2 75.3 78.9 75.4 75.9 77.6 81.8 76.9 77.5 79.9 84.3 78.1 78.9 82.1 86.6

SHC 56.8 65.7 75.0 78.9 59.2 69.0 77.6 81.8 61.6 72.1 79.9 84.3 63.8 75.2 82.1 86.6

67 TGC 82.1 82.5 82.7 83.1 83.9 84.3 84.6 85.0 85.3 85.6 86.1 86.7 86.6 86.9 87.5 88.3

SHC 49.3 55.3 64.1 73.1 47.5 57.7 67.2 76.9 49.0 59.6 70.1 80.7 50.5 61.6 72.8 84.3

73 TGC 91.2 91.3 91.8 92.1 92.9 93.2 93.6 93.8 94.2 94.7 95.2 95.4 95.4 96.0 96.5 96.8

SHC 33.8 43.6 53.0 62.4 34.4 45.0 55.3 65.0 35.1 46.3 57.4 67.7 35.7 47.6 59.4 70.3

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-3 — Gross Cooling Capacities (kW) TTA085A Condensing Unit with TWE075A Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 3823

4248

4673

5098

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 24.3 24.3 24.5 25.3 24.8 25.0 25.2 26.2 25.3 25.5 25.8 27.1 25.8 25.9 26.4 27.8

SHC 18.1 20.6 23.3 25.3 18.8 21.6 24.6 26.2 19.5 22.6 25.8 27.1 20.2 23.5 26.4 27.8

19.4 TGC 26.9 27.0 27.1 27.2 27.6 27.7 27.7 27.8 28.1 28.2 28.3 28.4 28.6 28.7 28.7 28.9

SHC 15.6 17.5 20.1 22.8 15.2 18.2 21.1 23.9 15.7 18.9 22.0 25.0 16.1 19.6 22.8 26.1

35.0

22.8 TGC 29.9 29.9 30.0 30.1 30.6 30.6 30.7 30.8 31.1 31.1 31.2 31.3 31.5 31.6 31.7 31.7

SHC 11.0 14.0 16.8 19.5 11.3 14.5 17.5 20.4 11.5 14.9 18.1 21.3 11.7 15.2 18.7 22.0

16.1 TGC 23.4 23.5 23.7 24.6 24.0 24.1 24.4 25.5 24.5 24.6 25.0 26.3 24.9 25.0 25.7 27.0

19.4 SHC 17.6 20.2 22.9 24.6 18.3 21.2 24.1 25.5 19.0 22.1 25.0 26.3 19.7 23.0 25.7 27.0

TGC 26.0 26.1 26.2 26.3 26.6 26.7 26.8 26.9 27.1 27.2 27.3 27.4 27.5 27.6 27.8 27.9

SHC 15.3 17.1 19.7 22.3 14.8 17.8 20.6 23.5 15.3 18.5 21.5 24.6 15.7 19.0 22.3 25.6

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 28.9 28.9 29.0 29.1 29.5 29.5 29.6 29.7 30.0 30.0 30.2 30.2 30.4 30.5 30.6 30.7

SHC 10.7 13.6 16.4 19.1 10.9 14.1 17.0 20.0 11.1 14.4 17.7 20.8 11.3 14.8 18.3 21.5

TGC 22.5 22.7 22.9 23.9 23.1 23.2 23.5 24.7 23.5 23.7 24.2 25.5 23.9 24.1 24.9 26.2

SHC 17.1 19.7 22.4 23.9 17.9 20.7 23.5 24.7 18.5 21.6 24.2 25.5 19.2 22.5 24.9 26.2

19.4 TGC 25.1 25.2 25.2 25.3 25.6 25.7 25.8 25.9 26.1 26.1 26.3 26.4 26.5 26.5 26.7 26.9

SHC 14.9 16.6 19.2 21.9 14.4 17.4 20.2 23.0 14.8 17.9 21.0 24.1 15.2 18.6 21.8 25.2

46.1

22.8 TGC 27.8 27.9 28.0 28.1 28.4 28.4 28.6 28.7 28.8 28.9 29.0 29.1 29.2 29.3 29.5 29.5

SHC 10.3 13.2 16.0 18.7 10.5 13.6 16.6 19.6 10.7 14.0 17.2 20.3 10.9 14.4 17.8 21.1

16.1 TGC 21.6 21.7 22.0 23.1 22.1 22.2 22.7 24.0 22.5 22.7 23.4 24.7 22.9 23.1 24.0 25.4

19.4

22.8

SHC TGC SHC TGC SHC 16.6 24.0 14.4 26.7 9.9 19.2 24.2 16.2 26.7 12.8 22.0 24.2 18.8 26.9 15.5 23.1 24.3 21.4 27.0 18.3 17.3 24.6 13.9 27.2 10.1 20.2 24.7 16.9 27.3 13.2 22.7 24.8 19.7 27.4 16.2 24.0 24.9 22.5 27.5 19.0 18.0 25.0 14.4 27.6 10.3 21.1 25.1 17.5 27.7 13.6 23.4 25.2 20.5 27.9 16.8 24.7 25.4 23.6 27.9 19.8 18.7 25.4 14.8 27.9 10.5 22.0 25.4 18.0 28.1 13.9 24.0 25.6 21.3 28.3 17.4 25.4 25.8 24.7 28.3 20.6

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

15

Performance Data

System

Table PD-4 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit with TWE100A Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 2500

2800

3100

3400

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61

67

95

73

TGC SHC TGC SHC TGC SHC 87.9 67.0 97.4 57.4 107.7 39.8 88.3 77.4 97.8 65.0 107.9 51.3 89.3 88.1 98.0 75.3 108.3 62.2 93.2 93.2 98.3 85.7 108.7 73.0 90.0 70.2 99.6 56.2 109.9 40.6 90.5 81.6 100.1 68.1 110.2 53.1 92.0 92.0 100.3 79.2 110.7 65.0 96.8 96.8 100.7 90.7 110.8 76.5 91.8 73.2 101.5 58.1 111.6 41.4 92.4 85.7 101.7 70.6 112.1 54.7 95.0 95.0 102.2 82.9 112.7 67.7 100.0 100.0 102.8 95.4 112.9 80.0 93.4 76.1 103.0 59.9 113.0 42.2 94.1 89.6 103.3 73.2 113.7 56.3 97.7 97.7 103.9 86.5 114.3 70.3 102.9 102.9 104.7 100.1 114.6 83.3

61 TGC 84.8 85.2 86.1 90.6 86.8 87.3 89.4 94.1 88.5 89.2 92.2 97.2 89.9 90.8 94.8 99.9

105 Entering Wet Bulb (°F) 73 61

67 SHC 65.4 75.8 86.1 90.6 68.5 80.0 89.4 94.1 71.5 84.0 92.2 97.2 74.3 87.9 94.8 99.9

TGC 93.9 94.4 94.6 95.0 96.0 96.5 96.7 97.2 97.7 98.0 98.6 99.3 99.2 99.5 100.1 101.1

SHC 56.0 63.4 73.7 84.1 54.6 66.5 77.5 89.0 56.5 68.9 81.3 93.8 58.3 71.4 84.8 98.4

TGC 103.9 104.1 104.6 104.9 105.8 106.3 106.8 106.9 107.3 108.0 108.6 108.9 108.6 109.5 110.2 110.5

SHC 38.3 49.8 60.7 71.5 39.2 51.6 63.5 74.9 40.0 53.2 66.2 78.3 40.7 54.8 68.7 81.6

TGC 81.5 81.9 83.4 87.9 83.4 83.9 86.6 91.2 85.0 85.7 89.3 94.1 86.3 87.4 91.7 96.7

SHC 63.7 74.1 83.4 87.9 66.8 78.2 86.6 91.2 69.7 82.2 89.3 94.1 72.5 86.1 91.7 96.7

67 TGC 90.3 90.8 91.0 91.4 92.3 92.5 93.0 93.6 93.9 94.2 94.7 95.6 95.2 95.6 96.2 97.5

SHC 54.5 61.9 72.0 82.4 53.0 64.5 75.8 87.4 54.9 67.1 79.5 92.1 56.7 69.7 83.0 96.7

115

73 TGC 99.8 100.2 100.7 100.8 101.5 102.2 102.7 102.9 102.9 103.8 104.4 104.7 104.1 105.2 105.5 106.2

SHC 36.8 48.3 59.2 69.6 37.7 50.0 62.0 73.2 38.5 51.6 64.6 76.6 39.1 53.2 66.6 79.9

61 TGC 78.0 78.5 80.6 85.0 79.8 80.5 83.6 88.2 81.3 82.2 86.2 91.0 82.5 83.6 88.5 93.4

SHC 61.9 72.3 80.6 85.0 64.9 76.4 83.6 88.2 67.8 80.4 86.2 91.0 70.6 83.6 88.5 93.4

67 TGC 86.5 86.7 87.3 87.8 88.3 88.6 89.2 89.9 89.8 90.2 90.8 91.9 91.1 91.5 92.1 93.5

SHC 53.0 59.9 70.2 80.7 51.4 62.7 74.1 85.6 53.2 65.3 77.7 90.4 55.0 67.8 81.2 93.5

73 TGC 95.4 96.0 96.6 96.8 97.0 97.9 98.5 98.7 98.3 99.4 99.7 100.4 99.4 100.7 101.1 101.8

SHC 35.5 46.7 57.6 67.9 36.1 48.4 60.4 71.5 36.9 50.0 62.5 74.9 37.4 51.6 64.8 78.1

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-4 — Gross Cooling Capacities (kW) TTA085A Condensing Unit with TWE100A Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 4248

4756

5267

5778

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 25.7 25.9 26.1 27.3 26.4 26.5 26.9 28.4 26.9 27.1 27.8 29.3 27.3 27.6 28.6 30.1

SHC 19.6 22.7 25.8 27.3 20.6 23.9 26.9 28.4 21.4 25.1 27.8 29.3 22.3 26.2 28.6 30.1

19.4 TGC 28.5 28.6 28.7 28.8 29.2 29.3 29.4 29.5 29.7 29.8 29.9 30.1 30.2 30.2 30.4 30.7

SHC 16.8 19.0 22.0 25.1 16.4 19.9 23.2 26.5 17.0 20.7 24.3 27.9 17.5 21.4 25.3 29.3

35.0

22.8 TGC 31.5 31.6 31.7 31.8 32.2 32.3 32.4 32.4 32.7 32.8 33.0 33.0 33.1 33.3 33.5 33.6

SHC 11.6 15.0 18.2 21.4 11.9 15.5 19.0 22.4 12.1 16.0 19.8 23.4 12.4 16.5 20.6 24.4

16.1 TGC 24.8 24.9 25.2 26.5 25.4 25.6 26.2 27.6 25.9 26.1 27.0 28.4 26.3 26.6 27.8 29.2

19.4 SHC 19.1 22.2 25.2 26.5 20.1 23.4 26.2 27.6 20.9 24.6 27.0 28.4 21.8 25.7 27.8 29.2

TGC 27.5 27.6 27.7 27.8 28.1 28.3 28.3 28.5 28.6 28.7 28.9 29.1 29.0 29.1 29.3 29.6

SHC 16.4 18.6 21.6 24.6 16.0 19.5 22.7 26.1 16.6 20.2 23.8 27.5 17.1 20.9 24.8 28.8

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 30.4 30.5 30.6 30.7 31.0 31.1 31.3 31.3 31.4 31.6 31.8 31.9 31.8 32.1 32.3 32.3

SHC 11.2 14.6 17.8 20.9 11.5 15.1 18.6 21.9 11.7 15.6 19.4 22.9 11.9 16.0 20.1 23.9

TGC 23.9 24.0 24.4 25.7 24.4 24.6 25.3 26.7 24.9 25.1 26.1 27.6 25.3 25.6 26.9 28.3

SHC 18.6 21.7 24.4 25.7 19.5 22.9 25.3 26.7 20.4 24.1 26.1 27.6 21.2 25.2 26.9 28.3

19.4 TGC 26.4 26.6 26.6 26.8 27.0 27.1 27.2 27.4 27.5 27.6 27.7 28.0 27.9 28.0 28.2 28.5

SHC 16.0 18.1 21.1 24.1 15.5 18.9 22.2 25.6 16.1 19.7 23.3 27.0 16.6 20.4 24.3 28.3

46.1

22.8 TGC 29.2 29.3 29.5 29.5 29.7 29.9 30.1 30.1 30.1 30.4 30.6 30.7 30.5 30.8 30.9 31.1

SHC 10.8 14.1 17.3 20.4 11.0 14.6 18.1 21.4 11.3 15.1 18.9 22.4 11.4 15.6 19.5 23.4

16.1 TGC 22.8 23.0 23.6 24.9 23.4 23.6 24.5 25.8 23.8 24.1 25.2 26.6 24.2 24.5 25.9 27.4

19.4

22.8

SHC TGC SHC TGC SHC 18.1 25.3 15.5 27.9 10.4 21.2 25.4 17.5 28.1 13.7 23.6 25.6 20.6 28.3 16.9 24.9 25.7 23.6 28.3 19.9 19.0 25.9 15.0 28.4 10.6 22.4 25.9 18.3 28.7 14.2 24.5 26.1 21.7 28.8 17.7 25.8 26.3 25.1 28.9 20.9 19.9 26.3 15.6 28.8 10.8 23.6 26.4 19.1 29.1 14.7 25.2 26.6 22.8 29.2 18.3 26.6 26.9 26.5 29.4 21.9 20.7 26.7 16.1 29.1 11.0 24.5 26.8 19.9 29.5 15.1 25.9 27.0 23.8 29.6 19.0 27.4 27.4 27.4 29.8 22.9

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

16

SS-PRC003-EN

Performance Data

System

Table PD-5 — Gross Cooling Capacities (MBh) TTA100A Condensing Unit with TWE100A Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow

3025

3350

3675

4000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 102.0 102.4 103.6 107.8 104.1 104.6 106.1 111.5 106.0 106.6 109.1 114.7 107.6 108.4 111.8 117.6

SHC 77.6 89.6 101.9 107.8 80.8 93.8 106.1 111.5 83.8 97.8 109.1 114.7 86.7 101.7 111.8 117.6

67 TGC 112.8 113.2 113.4 113.8 115.1 115.5 115.7 116.2 116.9 117.4 117.6 118.3 118.5 118.7 119.3 120.2

SHC 67.2 75.1 87.0 98.9 64.6 78.2 90.9 103.9 66.6 81.1 94.7 108.7 68.4 83.4 98.2 113.3

95

73 TGC 124.5 124.6 125.0 125.4 126.7 126.9 127.3 127.7 128.5 128.8 129.3 129.4 130.0 130.4 130.9 131.2

SHC 46.0 59.2 71.7 84.1 46.8 60.9 74.5 88.0 47.7 62.6 77.2 91.1 48.6 64.1 79.7 94.5

61 TGC 98.2 98.7 100.2 104.7 100.3 100.8 102.9 108.3 102.0 102.7 105.8 111.3 103.5 104.5 108.4 114.1

105 Entering Wet Bulb (°F) 73 61

67 SHC 75.7 87.6 100.1 104.7 78.8 91.8 102.9 108.3 81.8 95.8 105.8 111.3 84.6 99.7 108.4 114.1

TGC 108.7 109.2 109.3 109.8 110.8 111.3 111.5 112.1 112.5 112.7 113.3 114.1 114.0 114.3 114.9 116.0

SHC 65.5 73.2 85.1 97.0 62.8 76.3 89.0 102.0 64.7 78.8 92.7 106.8 66.5 81.4 96.2 111.4

TGC 119.9 120.1 120.5 120.9 121.9 122.2 122.7 122.8 123.5 124.0 124.5 124.7 124.9 125.5 126.1 126.4

SHC 44.4 57.4 69.9 82.4 45.2 59.1 72.7 85.8 46.0 60.8 75.4 89.2 46.7 62.3 77.9 92.5

TGC 94.3 94.8 96.5 101.5 96.2 96.9 99.6 104.9 97.8 98.7 102.4 107.8 99.3 100.4 104.8 110.4

SHC 73.6 85.5 96.5 101.5 76.7 89.7 99.6 104.9 79.7 93.8 102.4 107.8 82.5 97.6 104.8 110.4

67 TGC 104.4 104.9 105.1 105.6 106.3 106.5 107.1 107.8 107.9 108.2 108.8 109.8 109.3 109.7 110.3 111.6

SHC 63.8 71.4 83.1 95.0 60.9 74.0 86.9 100.0 62.8 76.7 90.6 104.8 64.5 79.3 94.1 109.4

115

73 TGC 115.1 115.4 115.9 116.3 116.9 117.4 117.9 118.1 118.4 119.0 119.6 119.9 119.6 120.4 121.1 121.4

SHC 42.7 55.6 68.1 80.6 43.5 57.3 70.9 83.8 44.3 58.9 73.5 87.2 44.8 60.5 76.1 90.5

61 TGC 90.2 90.8 93.1 98.1 92.0 92.8 96.1 101.3 93.5 94.5 98.7 104.0 94.8 96.2 101.1 106.5

SHC 71.5 83.4 93.1 98.1 74.5 87.6 96.1 101.3 77.5 91.6 98.7 104.0 80.2 95.5 101.1 106.5

67 TGC 99.9 100.5 100.7 101.3 101.7 102.0 102.6 103.4 103.2 103.6 104.2 105.4 104.5 104.9 105.6 106.6

SHC 62.0 69.4 81.0 93.0 58.9 71.9 84.8 98.0 60.8 74.6 88.5 102.7 62.6 77.1 92.0 106.6

73 TGC 110.1 110.5 111.1 111.3 111.7 112.4 113.0 113.2 113.0 113.9 114.5 114.8 114.2 115.2 115.5 116.3

SHC 41.0 53.7 66.3 78.2 41.7 55.4 69.0 81.8 42.4 57.0 71.6 85.2 42.9 58.6 73.6 88.4

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-5 — Gross Cooling Capacities (kW) TTA100A Condensing Unit with TWE100A Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 5141

5692

6242

6797

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 29.9 30.0 30.3 31.6 30.5 30.6 31.1 32.6 31.0 31.2 31.9 33.6 31.5 31.7 32.7 34.4

SHC 22.7 26.2 29.8 31.6 23.7 27.5 31.1 32.6 24.5 28.6 31.9 33.6 25.4 29.8 32.7 34.4

19.4 TGC 33.0 33.2 33.2 33.3 33.7 33.8 33.9 34.0 34.2 34.4 34.4 34.6 34.7 34.8 34.9 35.2

SHC 19.7 22.0 25.5 29.0 18.9 22.9 26.6 30.4 19.5 23.7 27.7 31.8 20.0 24.4 28.8 33.2

35.0

22.8 TGC 36.4 36.5 36.6 36.7 37.1 37.2 37.3 37.4 37.6 37.7 37.9 37.9 38.1 38.2 38.3 38.4

SHC 13.5 17.3 21.0 24.6 13.7 17.8 21.8 25.8 14.0 18.3 22.6 26.7 14.2 18.8 23.3 27.7

16.1 TGC 28.8 28.9 29.3 30.7 29.4 29.5 30.1 31.7 29.9 30.1 31.0 32.6 30.3 30.6 31.7 33.4

19.4 SHC 22.2 25.6 29.3 30.7 23.1 26.9 30.1 31.7 24.0 28.1 31.0 32.6 24.8 29.2 31.7 33.4

TGC 31.8 32.0 32.0 32.1 32.4 32.6 32.7 32.8 32.9 33.0 33.2 33.4 33.4 33.5 33.6 34.0

SHC 19.2 21.4 24.9 28.4 18.4 22.3 26.0 29.9 18.9 23.1 27.1 31.3 19.5 23.8 28.2 32.6

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 35.1 35.2 35.3 35.4 35.7 35.8 35.9 36.0 36.2 36.3 36.5 36.5 36.6 36.8 36.9 37.0

SHC 13.0 16.8 20.5 24.1 13.2 17.3 21.3 25.1 13.5 17.8 22.1 26.1 13.7 18.3 22.8 27.1

TGC 27.6 27.8 28.2 29.7 28.2 28.4 29.2 30.7 28.6 28.9 30.0 31.6 29.1 29.4 30.7 32.3

SHC 21.6 25.0 28.2 29.7 22.5 26.3 29.2 30.7 23.3 27.5 30.0 31.6 24.2 28.6 30.7 32.3

19.4 TGC 30.6 30.7 30.8 30.9 31.1 31.2 31.4 31.6 31.6 31.7 31.9 32.1 32.0 32.1 32.3 32.7

SHC 18.7 20.9 24.3 27.8 17.8 21.7 25.5 29.3 18.4 22.5 26.5 30.7 18.9 23.2 27.6 32.0

46.1

22.8 TGC 33.7 33.8 33.9 34.1 34.2 34.4 34.5 34.6 34.7 34.9 35.0 35.1 35.0 35.3 35.4 35.5

SHC 12.5 16.3 19.9 23.6 12.7 16.8 20.8 24.5 13.0 17.3 21.5 25.5 13.1 17.7 22.3 26.5

16.1 TGC 26.4 26.6 27.3 28.7 26.9 27.2 28.1 29.7 27.4 27.7 28.9 30.5 27.8 28.2 29.6 31.2

19.4

22.8

SHC TGC SHC TGC SHC 20.9 29.2 18.1 32.2 12.0 24.4 29.4 20.3 32.4 15.7 27.3 29.5 23.7 32.5 19.4 28.7 29.7 27.2 32.6 22.9 21.8 29.8 17.3 32.7 12.2 25.7 29.9 21.1 32.9 16.2 28.1 30.0 24.8 33.1 20.2 29.7 30.3 28.7 33.1 23.9 22.7 30.2 17.8 33.1 12.4 26.8 30.3 21.8 33.4 16.7 28.9 30.5 25.9 33.5 21.0 30.5 30.9 30.1 33.6 24.9 23.5 30.6 18.3 33.4 12.5 28.0 30.7 22.6 33.7 17.1 29.6 30.9 26.9 33.8 21.5 31.2 31.2 31.2 34.0 25.9

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

17

Performance Data

System

Table PD-6 — Gross Cooling Capacities (MBh) TTA100B Condensing Unit with TWE100B Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 3000

3325

3675

4000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 94.9 95.1 97.0 102.0 96.7 97.3 100.1 105.4 98.5 99.3 103.1 108.5 99.9 101.1 105.6 111.2

SHC 74.4 86.5 97.0 102.0 77.6 90.9 100.1 105.4 81.0 95.4 103.1 108.5 83.9 99.4 105.6 111.2

67 TGC 105.3 105.5 105.6 105.9 107.3 107.5 107.6 108.2 109.0 109.3 109.5 110.4 110.5 110.6 110.9 112.3

SHC 63.8 71.4 83.4 95.4 61.1 74.4 87.4 100.4 70.3 77.5 91.4 105.6 64.9 80.1 95.0 110.3

95

73 TGC 116.4 116.4 116.6 116.8 118.3 118.4 118.6 118.8 120.0 120.2 120.4 120.6 121.4 121.6 121.9 122.1

SHC 42.9 55.6 67.8 80.0 43.7 57.3 70.6 83.8 44.8 59.0 73.4 87.3 45.2 60.5 75.9 90.6

61 TGC 90.0 90.4 93.0 97.9 91.7 92.4 96.0 101.1 93.3 94.4 98.8 104.1 94.6 95.7 101.2 106.6

105 Entering Wet Bulb (°F) 73 61

67 SHC 72.0 84.2 93.0 97.9 75.2 88.6 96.0 101.1 78.5 93.1 98.8 104.1 81.4 95.7 101.2 106.6

67

115

73

TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 100.1 61.7 110.7 40.9 84.9 69.5 94.6 59.5 104.8 38.8 100.3 69.0 110.7 53.4 85.5 81.9 94.8 66.6 104.8 51.1 100.3 81.1 110.9 65.6 88.8 88.8 94.8 78.7 104.9 63.3 100.8 93.1 111.1 77.7 93.6 93.6 95.5 90.8 105.1 75.4 101.9 58.7 112.5 41.7 86.5 72.7 96.3 56.3 106.4 39.4 102.1 72.1 112.6 55.0 87.5 86.3 96.4 69.6 106.5 52.7 102.2 85.0 112.8 68.3 91.7 91.7 96.5 82.6 106.6 65.9 103.0 98.2 112.9 81.4 96.6 96.6 97.6 95.9 106.7 78.9 103.5 68.1 114.0 42.5 87.9 76.0 97.7 65.8 107.8 40.2 103.7 75.1 114.2 56.7 89.1 89.1 97.8 72.6 107.9 54.4 103.9 89.0 114.4 71.1 94.3 94.3 98.1 86.6 108.1 68.7 105.1 103.4 114.5 85.0 99.4 99.4 99.3 99.3 108.2 82.6 104.8 62.5 115.3 42.9 89.1 78.9 98.9 60.0 109.0 40.5 104.9 77.7 115.5 58.2 91.2 91.2 99.0 75.2 109.1 55.9 105.3 92.6 115.7 73.5 96.5 96.5 99.4 90.2 109.3 71.1 106.5 106.5 115.9 88.2 101.7 101.7 101.6 101.6 109.4 85.8

61 TGC 79.6 80.5 84.5 89.1 81.0 82.2 87.1 91.9 82.4 84.5 89.5 94.5 83.5 86.4 91.5 96.6

SHC 67.0 79.5 84.5 89.1 70.2 82.2 87.1 91.9 73.5 84.5 89.5 94.5 76.4 86.4 91.5 96.6

67 TGC 88.9 89.0 89.1 90.1 90.4 90.5 90.6 91.9 91.7 91.8 92.2 94.4 92.8 92.8 93.4 96.6

SHC 57.3 64.2 76.2 88.5 53.8 67.1 80.1 91.91 63.1 70.0 84.2 94.4 57.5 72.7 87.8 96.6

73 TGC 98.6 98.6 98.7 98.8 100.1 100.1 100.2 100.3 101.3 101.4 101.6 101.7 102.4 102.5 102.6 102.7

SHC 36.6 48.7 60.9 73.0 37.1 50.3 63.5 76.4 38.4 52.0 66.3 80.1 38.2 53.5 68.7 83.4

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-6 — Gross Cooling Capacities (kW) TTA100B Condensing Unit with TWE100B Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 5098

5648

6246

6797

Enter. Dry Bulb (°C) 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2

16.1 TGC 27.8 27.9 28.4 29.9 28.4 28.5 29.4 30.9 28.9 29.1 30.2 31.8 29.3 29.6 31.0 32.6

SHC 21.8 25.4 28.4 29.9 22.8 26.6 29.4 30.9 23.7 28.0 30.2 31.8 24.6 29.1 31.0 32.6

19.4 TGC 30.9 30.9 31.0 31.1 31.5 31.5 31.5 31.7 32.0 32.0 32.1 32.4 32.4 32.4 32.5 32.9

SHC 18.7 20.9 24.5 28.0 17.9 21.8 25.6 29.4 20.6 22.7 26.8 31.0 19.0 23.5 27.8 32.3

35.0

22.8 TGC 34.1 34.1 34.2 34.2 34.7 34.7 34.8 34.8 35.2 35.2 35.3 35.3 35.6 35.6 35.7 35.8

SHC 12.6 16.3 19.9 23.4 12.8 16.8 20.7 24.5 13.1 17.3 21.5 25.6 13.2 17.7 22.2 26.5

16.1 TGC 26.4 26.5 27.3 28.7 26.9 27.1 28.1 29.6 27.4 27.7 29.0 30.5 27.7 28.1 29.7 31.2

19.4 SHC 21.1 24.7 27.3 28.7 22.0 26.0 28.1 29.6 23.0 27.3 29.0 30.5 23.9 28.1 29.7 31.2

TGC 29.3 29.4 29.4 29.5 29.9 29.9 30.0 30.2 30.3 30.4 30.4 30.8 30.7 30.8 30.9 31.2

SHC 18.1 20.2 23.8 27.3 17.2 21.1 24.9 28.8 20.0 22.0 26.1 30.3 18.3 22.8 27.1 31.2

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 32.4 32.5 32.5 32.6 33.0 33.0 33.0 33.1 33.4 33.5 33.5 33.6 33.8 33.8 33.9 34.0

SHC 12.0 15.6 19.2 22.8 12.2 16.1 20.0 23.9 12.5 16.6 20.8 24.9 12.6 17.1 21.6 25.9

TGC 24.9 25.1 26.0 27.4 25.4 25.6 26.9 28.3 25.8 26.1 27.6 29.1 26.1 26.7 28.3 29.8

SHC 20.4 24.0 26.0 27.4 21.3 25.3 26.9 28.3 22.3 26.1 27.6 29.1 23.1 26.7 28.3 29.8

19.4 TGC 27.7 27.8 27.8 28.0 28.2 28.3 28.3 28.6 28.6 28.7 28.8 29.1 29.0 29.0 29.1 29.8

SHC 17.4 19.5 23.1 26.6 16.5 20.4 24.2 28.1 19.3 21.3 25.4 29.1 17.6 22.0 26.4 29.8

46.1

22.8 TGC 30.7 30.7 30.8 30.8 31.2 31.2 31.2 31.3 31.6 31.6 31.7 31.7 31.9 32.0 32.0 32.1

SHC 11.4 15.0 18.5 22.1 11.6 15.5 19.3 23.1 11.8 15.9 20.1 24.2 11.9 16.4 20.9 25.2

16.1 TGC 23.3 23.6 24.8 26.1 23.7 24.1 25.5 26.9 24.1 24.8 26.2 27.7 24.5 25.3 26.8 28.3

SHC 19.6 23.3 24.8 26.1 20.6 24.1 25.5 26.9 21.5 24.8 26.2 27.7 22.4 25.3 26.8 28.3

19.4 TGC 26.1 26.1 26.1 26.4 26.5 26.5 26.6 26.9 26.9 26.9 27.0 27.7 27.2 27.2 27.4 28.3

SHC 16.8 18.8 22.3 25.9 15.8 19.7 23.5 26.9 18.5 20.5 24.7 27.7 16.9 21.3 25.7 28.3

22.8 TGC 28.9 28.9 28.9 29.0 29.3 29.3 29.4 29.4 29.7 29.7 29.8 29.8 30.0 30.0 30.1 30.1

SHC 10.7 14.3 17.8 21.4 10.9 14.8 18.6 22.4 11.3 15.2 19.4 23.5 11.2 15.7 20.1 24.4

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

18

SS-PRC003-EN

Performance Data

System

Table PD-7 — Gross Cooling Capacities (MBh) - Both Compressors - TTA100C Condensing Unit with TWE100A Air Handler (I-P) Ambient Temperature (°F) 85

CFM Airflow 3000

3325

3650

4000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 99.7 100.2 102.1 107.3 101.7 102.4 105.4 110.9 103.6 104.5 108.6 114.2 105.0 106.3 111.2 116.9

SHC 78.1 90.9 102.1 107.3 81.6 95.6 105.4 110.9 85.1 100.4 108.6 114.2 88.3 104.8 111.2 116.9

67 TGC 110.4 110.7 110.9 111.4 112.5 112.8 113.0 113.7 114.2 114.5 114.8 116.0 115.7 115.9 116.3 117.9

SHC 66.8 75.3 88.1 100.9 64.3 78.7 92.4 106.4 73.6 81.8 96.8 112.2 68.4 84.6 100.7 117.3

95

73 TGC 121.8 121.9 122.2 122.4 123.9 124.0 124.3 124.5 125.6 125.8 126.1 126.3 127.1 127.3 127.6 127.8

SHC 45.0 58.6 71.8 85.0 45.8 60.4 74.8 89.1 46.8 62.3 77.9 93.0 47.3 64.0 80.6 96.6

61 TGC 95.7 96.3 98.8 104.0 97.6 98.4 102.0 107.4 99.3 100.5 105.0 110.5 100.6 101.8 107.5 113.2

105 Entering Wet Bulb (°F) 73 61

67 SHC 76.1 88.9 98.8 104.0 79.5 93.6 102.0 107.4 83.0 98.4 105.0 110.5 86.2 101.8 107.5 113.2

TGC 106.1 106.4 106.6 107.2 108.1 108.4 108.6 109.5 109.6 109.9 110.3 111.7 111.1 111.3 111.8 113.3

SHC 65.1 73.5 86.1 99.0 62.4 76.8 90.4 104.5 71.2 79.8 94.8 110.2 66.5 82.6 98.7 113.3

TGC 117.1 117.2 117.5 117.7 119.0 119.1 119.4 119.5 120.6 120.8 121.1 121.3 121.9 122.1 122.5 122.7

SHC 43.3 56.8 70.0 83.2 44.1 58.6 73.0 86.9 45.0 60.4 76.0 91.0 45.4 62.1 78.8 94.7

TGC 91.5 92.2 95.3 100.4 93.2 94.2 98.4 103.7 94.8 95.7 101.2 106.7 96.0 97.9 103.6 109.2

SHC 74.0 86.8 95.3 100.4 77.3 91.5 98.4 103.7 80.8 95.7 101.2 106.7 83.9 97.9 103.6 109.2

67 TGC 101.4 101.8 102.0 102.8 103.3 103.4 103.9 105.0 104.8 105.1 105.6 106.8 106.1 106.4 107.0 109.2

SHC 63.3 71.5 84.1 97.0 60.4 74.4 88.3 102.5 69.3 77.6 92.7 106.8 64.5 80.5 96.6 109.2

115

73 TGC 112.1 112.3 112.6 112.7 113.8 114.0 114.3 114.5 115.3 115.6 115.9 116.1 116.5 116.8 117.2 117.4

SHC 41.6 54.9 68.1 81.0 42.3 56.7 71.1 84.9 43.1 58.5 74.1 89.0 43.4 60.2 76.8 92.6

61 TGC 87.0 87.9 91.6 96.6 88.6 89.9 94.5 99.7 90.0 91.8 97.2 102.6 91.3 93.8 99.4 104.9

SHC 71.7 84.7 91.6 96.6 75.1 89.3 94.5 99.7 78.5 91.8 97.2 102.6 81.6 93.8 99.4 104.9

67 TGC 96.5 97.0 97.2 98.2 98.2 98.5 98.9 99.8 99.6 100.0 100.6 102.7 100.8 101.2 101.9 105.0

SHC 61.4 69.4 81.9 94.9 58.3 72.3 86.1 99.8 67.3 75.4 90.5 102.7 62.4 78.2 94.4 105.0

73 TGC 106.8 107.0 107.4 107.5 108.4 108.6 109.0 109.2 109.7 110.1 110.4 110.7 110.8 111.2 111.4 111.9

SHC 39.8 52.9 66.1 79.0 40.3 54.7 69.1 82.9 41.6 56.5 72.1 86.9 41.5 58.2 74.4 90.5

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-7 — Gross Cooling Capacities (kW) - Both Compressors - TTA100C Condensing Unit with TWE100A Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 5098

5648

6203

6797

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 29.2 29.3 29.9 31.4 29.8 30.0 30.9 32.5 30.3 30.6 31.8 33.4 30.7 31.1 32.6 34.2

SHC 22.9 26.6 29.9 31.4 23.9 28.0 30.9 32.5 24.9 29.4 31.8 33.4 25.8 30.7 32.6 34.2

19.4 TGC 32.3 32.4 32.5 32.6 32.9 33.0 33.1 33.3 33.4 33.5 33.6 34.0 33.9 33.9 34.1 34.5

SHC 19.6 22.1 25.8 29.6 18.8 23.0 27.0 31.2 21.6 23.9 28.3 32.8 20.0 24.8 29.5 34.3

35.0

22.8 TGC 35.7 35.7 35.8 35.8 36.3 36.3 36.4 36.5 36.8 36.8 36.9 37.0 37.2 37.3 37.4 37.4

SHC 13.2 17.1 21.0 24.9 13.4 17.7 21.9 26.1 13.7 18.2 22.8 27.2 13.8 18.7 23.6 28.3

16.1 TGC 28.0 28.2 28.9 30.5 28.6 28.8 29.9 31.4 29.1 29.4 30.7 32.4 29.5 29.8 31.5 33.1

19.4 SHC 22.3 26.0 28.9 30.5 23.3 27.4 29.9 31.4 24.3 28.8 30.7 32.4 25.2 29.8 31.5 33.1

TGC 31.1 31.2 31.2 31.4 31.6 31.7 31.8 32.1 32.1 32.2 32.3 32.7 32.5 32.6 32.7 33.2

SHC 19.1 21.5 25.2 29.0 18.3 22.5 26.5 30.6 20.8 23.4 27.7 32.3 19.5 24.2 28.9 33.2

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 34.3 34.3 34.4 34.5 34.8 34.9 35.0 35.0 35.3 35.4 35.5 35.5 35.7 35.8 35.9 35.9

SHC 12.7 16.6 20.5 24.4 12.9 17.2 21.4 25.5 13.2 17.7 22.3 26.7 13.3 18.2 23.1 27.7

TGC 26.8 27.0 27.9 29.4 27.3 27.6 28.8 30.4 27.8 28.0 29.6 31.2 28.1 28.7 30.3 32.0

SHC 21.7 25.4 27.9 29.4 22.6 26.8 28.8 30.4 23.7 28.0 29.6 31.2 24.6 28.7 30.3 32.0

19.4 TGC 29.7 29.8 29.9 30.1 30.2 30.3 30.4 30.8 30.7 30.8 30.9 31.3 31.1 31.1 31.3 32.0

SHC 18.5 20.9 24.6 28.4 17.7 21.8 25.9 30.0 20.3 22.7 27.1 31.3 18.9 23.6 28.3 32.0

46.1

22.8 TGC 32.8 32.9 33.0 33.0 33.3 33.4 33.5 33.5 33.7 33.8 33.9 34.0 34.1 34.2 34.3 34.4

SHC 12.2 16.1 19.9 23.7 12.4 16.6 20.8 24.9 12.6 17.1 21.7 26.1 12.7 17.6 22.5 27.1

16.1 TGC 25.5 25.7 26.8 28.3 25.9 26.3 27.7 29.2 26.4 26.9 28.4 30.0 26.7 27.5 29.1 30.7

19.4

22.8

SHC TGC SHC TGC SHC 21.0 28.3 18.0 31.3 11.6 24.8 28.4 20.3 31.3 15.5 26.8 28.5 24.0 31.4 19.4 28.3 28.8 27.8 31.5 23.1 22.0 28.8 17.1 31.7 11.8 26.2 28.8 21.2 31.8 16.0 27.7 29.0 25.2 31.9 20.2 29.2 29.2 29.2 32.0 24.3 23.0 29.2 19.7 32.1 12.2 26.9 29.3 22.1 32.2 16.6 28.4 29.4 26.5 32.3 21.1 30.0 30.1 30.1 32.4 25.4 23.9 29.5 18.3 32.4 12.1 27.5 29.6 22.9 32.6 17.0 29.1 29.8 27.6 32.6 21.8 30.7 30.7 30.7 32.8 26.5

Dry coil conditions. Total Gross Cooling Capacity (kW) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

19

Performance Data

System

Table PD-8 — Gross Cooling Capacities (MBh) - Single Compressor - TTA100C Condensing Unit with TWE100A Air Handler (I-P) Ambient Temperature (°F) 85

CFM Airflow 3000

3325

3650

4000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 62.7 65.8 69.8 73.7 63.7 67.4 71.5 75.6 64.8 68.9 73.0 77.2 65.8 70.1 74.3 78.6

SHC 60.3 65.8 69.8 73.7 63.5 67.4 71.5 75.6 64.8 68.9 73.0 77.2 65.8 70.1 74.3 78.6

67 TGC 68.8 69.1 69.8 73.8 69.6 69.9 71.5 75.6 70.3 70.7 73.1 77.3 70.8 71.4 74.4 78.7

SHC 49.8 57.4 69.8 73.8 46.4 60.3 71.5 75.6 55.6 63.3 73.1 77.3 49.8 66.0 74.4 78.7

95

73 TGC 75.3 75.9 76.2 76.5 76.1 76.6 77.0 77.5 76.7 77.3 77.7 78.4 77.2 77.9 78.3 79.2

SHC 29.4 41.9 54.4 67.3 29.2 43.2 57.0 71.1 31.0 44.7 59.8 75.1 30.2 46.1 62.2 78.7

61 TGC 60.1 63.5 67.3 71.2 61.0 65.0 69.0 73.0 62.3 66.3 70.4 74.5 63.3 67.5 71.6 75.8

105 Entering Wet Bulb (°F) 73 61

67 SHC 59.0 63.5 67.3 71.2 61.0 65.0 69.0 73.0 62.3 66.3 70.4 74.5 63.3 67.5 71.6 75.8

TGC 65.9 66.2 67.4 71.3 66.6 67.0 69.0 73.0 67.3 67.8 70.5 74.6 67.8 68.4 71.7 75.9

SHC 48.6 56.2 67.4 71.3 45.1 59.1 69.0 73.0 54.3 62.1 70.5 74.6 48.5 64.8 71.7 75.9

TGC 72.1 72.6 73.1 73.4 72.8 73.4 73.8 74.4 73.3 74.1 74.5 75.3 73.7 74.7 75.0 75.9

SHC 28.4 40.5 53.2 66.1 28.1 42.0 55.8 69.9 30.0 43.5 58.6 73.9 29.1 45.9 61.0 75.9

TGC 57.3 61.0 64.8 68.6 58.6 62.4 66.3 70.3 59.8 63.7 67.7 71.7 60.7 64.7 68.8 72.9

SHC 57.3 61.0 64.8 68.6 58.6 62.4 66.3 70.3 59.8 63.7 67.7 71.7 60.7 64.7 68.8 72.9

67 TGC 62.8 63.2 64.9 68.7 63.5 64.0 66.4 70.3 64.1 64.7 67.8 71.8 64.6 65.3 68.9 73.0

SHC 47.4 54.9 64.9 68.7 43.8 57.8 66.4 70.3 45.6 60.8 67.8 71.8 47.2 63.5 68.9 73.0

115

73 TGC 68.7 69.4 69.8 70.3 69.3 70.1 70.5 71.2 69.8 70.7 71.1 71.8 70.1 71.2 71.6 73.1

SHC 27.3 39.3 52.0 64.9 26.9 40.7 54.6 68.7 28.9 42.2 57.3 71.8 27.9 43.5 59.8 73.1

61 TGC 54.8 58.5 62.1 65.9 56.0 59.8 63.5 67.4 57.1 61.0 64.8 68.8 58.0 61.9 65.9 69.9

SHC 54.8 58.5 62.1 65.9 56.0 59.8 63.5 67.4 57.1 61.0 64.8 68.8 58.0 61.9 65.9 69.9

67 TGC 59.7 60.2 62.2 65.9 60.3 60.9 63.6 67.5 60.9 61.6 64.9 68.8 61.3 62.2 66.0 70.0

73

SHC TGC SHC 46.1 65.2 26.2 53.6 66.0 37.9 62.2 66.5 50.7 65.9 67.0 63.7 42.5 65.7 25.8 56.5 66.6 39.4 63.6 67.1 53.4 67.5 67.9 67.5 44.2 66.1 27.8 59.5 67.2 40.8 64.9 67.7 56.1 68.8 68.9 68.9 45.7 66.4 26.7 62.2 67.6 42.1 66.0 68.2 58.5 70.0 70.0 70.0

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-8 — Gross Cooling Capacities (kW) - Single Compressor - TTA100C Condensing Unit with TWE100A Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 5098

5648

6203

6797

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 18.4 19.3 20.4 21.6 18.7 19.7 20.9 22.1 19.0 20.2 21.4 22.6 19.3 20.5 21.8 23.0

SHC 17.6 19.3 20.4 21.6 18.6 19.7 20.9 22.1 19.0 20.2 21.4 22.6 19.3 20.5 21.8 23.0

19.4 TGC 20.1 20.2 20.4 21.6 20.4 20.5 20.9 22.1 20.6 20.7 21.4 22.6 20.7 20.9 21.8 23.0

SHC 14.6 16.8 20.4 21.6 13.6 17.7 20.9 22.1 16.3 18.5 21.4 22.6 14.6 19.3 21.8 23.0

35.0

22.8 TGC 22.1 22.2 22.3 22.4 22.3 22.4 22.6 22.7 22.4 22.6 22.8 23.0 22.6 22.8 22.9 23.2

SHC 8.6 12.3 15.9 19.7 8.5 12.6 16.7 20.8 9.1 13.1 17.5 22.0 8.8 13.5 18.2 23.0

16.1 TGC 17.6 18.6 19.7 20.9 17.9 19.0 20.2 21.4 18.2 19.4 20.6 21.8 18.5 19.8 21.0 22.2

19.4 SHC 17.3 18.6 19.7 20.9 17.9 19.0 20.2 21.4 18.2 19.4 20.6 21.8 18.5 19.8 21.0 22.2

TGC 19.3 19.4 19.7 20.9 19.5 19.6 20.2 21.4 19.7 19.8 20.6 21.8 19.9 20.0 21.0 22.2

SHC 14.2 16.4 19.7 20.9 13.2 17.3 20.2 21.4 15.9 18.2 20.6 21.8 14.2 19.0 21.0 22.2

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 21.1 21.3 21.4 21.5 21.3 21.5 21.6 21.8 21.5 21.7 21.8 22.0 21.6 21.9 22.0 22.2

SHC 8.3 11.9 15.6 19.4 8.2 12.3 16.4 20.5 8.8 12.7 17.1 21.6 8.5 13.4 17.9 22.2

TGC 16.8 17.9 19.0 20.1 17.2 18.3 19.4 20.6 17.5 18.6 19.8 21.0 17.8 19.0 20.2 21.4

SHC 16.8 17.9 19.0 20.1 17.2 18.3 19.4 20.6 17.5 18.6 19.8 21.0 17.8 19.0 20.2 21.4

19.4 TGC 18.4 18.5 19.0 20.1 18.6 18.7 19.4 20.6 18.8 18.9 19.8 21.0 18.9 19.1 20.2 21.4

SHC 13.9 16.1 19.0 20.1 12.8 16.9 19.4 20.6 13.4 17.8 19.8 21.0 13.8 18.6 20.2 21.4

46.1

22.8 TGC 20.1 20.3 20.4 20.6 20.3 20.5 20.7 20.8 20.4 20.7 20.8 21.0 20.5 20.8 21.0 21.4

SHC 8.0 11.5 15.2 19.0 7.9 11.9 16.0 20.1 8.5 12.4 16.8 21.0 8.2 12.7 17.5 21.4

16.1 TGC 16.0 17.1 18.2 19.3 16.4 17.5 18.6 19.7 16.7 17.8 19.0 20.1 17.0 18.1 19.3 20.5

SHC 16.0 17.1 18.2 19.3 16.4 17.5 18.6 19.7 16.7 17.8 19.0 20.1 17.0 18.1 19.3 20.5

19.4 TGC 17.5 17.6 18.2 19.3 17.7 17.8 18.6 19.8 17.8 18.0 19.0 20.2 18.0 18.2 19.3 20.5

22.8

SHC TGC SHC 13.5 19.1 7.7 15.7 19.3 11.1 18.2 19.5 14.9 19.3 19.6 18.7 12.4 19.2 7.5 16.5 19.5 11.5 18.6 19.7 15.6 19.8 19.9 19.8 12.9 19.3 8.1 17.4 19.7 12.0 19.0 19.8 16.4 20.2 20.2 20.2 13.4 19.4 7.8 18.2 19.8 12.3 19.3 20.0 17.1 20.5 20.5 20.5

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

20

SS-PRC003-EN

Performance Data

System

Table PD-9 — Gross Cooling Capacities (MBh) TTA125B Condensing Unit with TWE100B Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 3000

3325

3675

4000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 108.2 108.2 108.2 110.2 110.0 110.0 110.1 115.3 111.8 111.8 115.4 120.8 113.5 113.5 120.2 123.1

SHC 79.4 93.1 105.3 110.2 83.1 97.4 110.1 115.3 87.0 102.0 115.4 120.8 90.7 106.2 120.2 123.1

67 TGC 117.8 117.8 117.8 117.8 119.6 119.6 119.6 119.6 121.7 121.7 121.7 121.7 123.5 123.5 123.5 123.5

SHC 61.3 75.0 88.6 102.2 64.1 78.4 92.7 106.9 67.1 82.1 97.1 112.0 69.9 85.6 101.2 116.7

95

73 TGC 124.3 124.3 124.3 124.3 126.3 126.3 126.3 126.3 128.4 128.4 128.4 128.4 130.4 130.4 130.4 130.4

SHC 42.2 55.9 69.5 83.2 44.1 58.5 72.7 87.0 46.2 61.3 76.2 91.1 48.2 63.8 79.4 94.9

61 TGC 100.3 100.3 100.3 103.9 101.8 101.8 104.0 108.7 103.6 103.6 108.9 111.6 105.2 105.2 113.5 113.5

105 Entering Wet Bulb (°F) 73 61

67 SHC 76.1 89.8 99.4 103.9 79.6 93.9 104.0 108.7 83.3 98.3 108.9 111.6 86.8 102.5 113.5 113.5

TGC 109.3 109.3 109.3 109.3 111.0 111.0 111.0 111.0 112.9 112.9 112.9 112.9 114.6 114.6 114.6 114.6

SHC 58.1 71.8 85.4 99.0 60.7 75.1 89.3 103.6 63.6 78.6 93.5 108.5 66.3 81.9 97.5 113.0

TGC 115.4 115.4 115.4 115.4 117.2 117.2 117.2 117.2 119.2 119.2 119.2 119.2 121.0 121.0 121.0 121.0

SHC 39.2 52.8 66.5 80.2 41.0 55.2 69.6 83.9 43.0 57.9 72.9 87.8 44.8 60.3 75.9 91.5

TGC 92.3 92.3 93.1 97.4 93.8 93.8 97.4 101.9 95.4 95.4 102.0 103.2 96.9 98.7 104.8 107.6

SHC 72.8 86.5 93.1 97.4 76.1 90.4 97.4 101.9 79.7 94.7 102.0 103.2 83.1 98.7 104.8 107.6

67 TGC 100.8 100.8 100.8 100.8 102.4 102.4 102.4 102.4 104.1 104.1 104.1 105.1 105.7 105.7 105.7 109.5

SHC 54.9 68.5 82.2 96.0 57.4 71.7 85.9 100.4 60.2 75.1 90.0 105.1 62.7 78.2 93.8 109.5

115

73 TGC 106.5 106.5 106.5 106.5 108.2 108.2 108.2 108.2 110.1 110.1 110.1 110.1 111.8 111.8 111.8 111.8

61

67

SHC TGC SHC TGC 36.1 84.4 69.5 92.3 49.7 84.4 82.7 92.3 63.5 86.9 86.9 92.3 77.0 90.8 90.8 92.7 37.7 85.8 72.6 93.7 52.0 86.5 86.5 93.7 66.4 90.9 90.9 93.7 80.6 95.0 95.0 96.9 39.5 87.2 76.1 95.3 54.5 90.6 90.6 95.3 69.5 95.2 95.2 95.3 84.4 99.0 99.0 99.2 41.2 88.6 79.3 96.8 56.8 94.4 94.4 96.8 72.4 96.1 96.1 96.8 87.9 99.8 99.8 101.5

SHC 51.7 65.3 79.0 92.7 54.1 68.3 82.7 96.9 56.6 71.6 86.6 99.2 59.0 74.6 90.2 101.5

73 TGC 97.6 97.6 97.6 97.6 99.2 99.2 99.2 99.2 100.8 100.8 100.8 100.8 102.4 102.4 102.4 102.4

SHC 33.0 46.7 60.3 74.0 34.5 48.9 63.1 77.4 36.1 51.2 66.1 81.0 37.7 53.4 68.9 84.4

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-9 — Gross Cooling Capacities (kW) TTA125B Condensing Unit with TWE100B Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 5098

5648

6246

6797

Enter. Dry Bulb (°C) 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2

16.1 TGC 31.7 31.7 31.7 32.3 32.2 32.2 32.3 33.8 32.8 32.8 33.8 35.4 33.3 33.3 35.2 36.1

SHC 23.3 27.3 30.9 32.3 24.3 28.5 32.3 33.8 25.5 29.9 33.8 35.4 26.6 31.1 35.2 36.1

19.4 TGC 34.5 34.5 34.5 34.5 35.0 35.0 35.0 35.0 35.7 35.7 35.7 35.7 36.2 36.2 36.2 36.2

SHC 18.0 22.0 26.0 29.9 18.8 23.0 27.2 31.3 19.7 24.1 28.5 32.8 20.5 25.1 29.7 34.2

35.0

22.8 TGC 36.4 36.4 36.4 36.4 37.0 37.0 37.0 37.0 37.6 37.6 37.6 37.6 38.2 38.2 38.2 38.2

SHC 12.4 16.4 20.4 24.4 12.9 17.1 21.3 25.5 13.5 18.0 22.3 26.7 14.1 18.7 23.3 27.8

16.1 TGC 29.4 29.4 29.4 30.4 29.8 29.8 30.5 31.8 30.4 30.4 31.9 32.7 30.8 30.8 33.3 33.3

19.4 SHC 22.3 26.3 29.1 30.4 23.3 27.5 30.5 31.8 24.4 28.8 31.9 32.7 25.4 30.0 33.3 33.3

TGC 32.0 32.0 32.0 32.0 32.5 32.5 32.5 32.5 33.1 33.1 33.1 33.1 33.6 33.6 33.6 33.6

SHC 17.0 21.0 25.0 29.0 17.8 22.0 26.2 30.4 18.6 23.0 27.4 31.8 19.4 24.0 28.6 33.1

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 33.8 33.8 33.8 33.8 34.3 34.3 34.3 34.3 34.9 34.9 34.9 34.9 35.5 35.5 35.5 35.5

SHC 11.5 15.5 19.5 23.5 12.0 16.2 20.4 24.6 12.6 17.0 21.4 25.7 13.1 17.7 22.2 26.8

TGC 27.0 27.0 27.3 28.5 27.5 27.5 28.5 29.9 28.0 28.0 29.9 30.2 28.4 28.9 30.7 31.5

SHC 21.3 25.3 27.3 28.5 22.3 26.5 28.5 29.9 23.4 27.7 29.9 30.2 24.3 28.9 30.7 31.5

19.4 TGC 29.5 29.5 29.5 29.5 30.0 30.0 30.0 30.0 30.5 30.5 30.5 30.8 31.0 31.0 31.0 32.1

SHC 16.1 20.1 24.1 28.1 16.8 21.0 25.2 29.4 17.6 22.0 26.4 30.81 18.4 22.9 27.5 32.1

46.1

22.8 TGC 31.2 31.2 31.2 31.2 31.7 31.7 31.7 31.7 32.3 32.3 32.3 32.3 32.8 32.8 32.8 32.8

SHC 10.6 14.6 18.6 22.6 11.0 15.2 19.5 23.6 11.6 16.0 20.4 24.7 12.1 16.6 21.2 25.8

16.1 TGC 24.7 24.7 25.5 26.6 25.1 25.3 26.6 27.8 25.5 26.5 27.9 29.0 26.0 27.7 28.2 29.2

SHC 20.4 24.2 25.5 26.6 21.3 25.3 26.6 27.8 22.3 26.5 27.9 29.0 23.2 27.7 28.2 29.2

19.4 TGC 27.0 27.0 27.0 27.2 27.5 27.5 27.5 28.4 27.9 27.9 27.9 29.1 28.4 28.4 28.4 29.7

SHC 15.1 19.1 23.1 27.2 15.9 20.0 24.2 28.4 16.6 21.0 25.4 29.1 17.3 21.9 26.4 29.7

22.8 TGC 28.6 28.6 28.6 28.6 29.1 29.1 29.1 29.1 29.5 29.5 29.5 29.5 30.0 30.0 30.0 30.0

SHC 9.7 13.7 17.7 21.7 10.1 14.3 18.5 22.7 10.6 15.0 19.4 23.7 11.0 15.6 20.2 24.7

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

21

Performance Data

System

Table PD-10 — Gross Cooling Capacities (MBh) TTA125B Condensing Unit with TWE155B Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM

Enter. Dry Bulb

61

67

95

73

61

67

105 Entering Wet Bulb (°F) 73 61

67

115

73

61

67

Airflow

(°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 75 120.8 96.6 132.7 73.8 141.1 49.7 113.8 93.7 124.9 70.8 132.7 46.7 106.3 90.5 116.6 67.6 123.9 43.6 98.8 87.4 108.3 64.6 80 120.8 114.3 132.7 91.4 141.1 67.4 113.8 111.4 124.9 88.5 132.7 64.5 108.3 108.3 116.6 85.4 123.9 61.3 104.9 104.9 108.3 82.2 3750 85 126.8 126.8 132.7 109.2 141.1 85.1 119.6 119.6 124.9 106.2 132.7 82.1 112.4 112.4 116.6 103.0 123.9 79.1 105.0 105.0 108.3 100.0 90 127.4 127.4 132.7 126.9 141.1 102.8 123.1 123.1 124.9 123.9 132.7 100.0 118.9 118.9 119.7 119.7 123.9 96.7 110.0 110.0 111.2 111.2 75 122.7 101.2 134.9 77.3 143.4 52.0 115.6 98.1 127.0 74.1 134.9 49.0 108.0 94.8 118.5 70.8 125.9 45.7 100.4 91.5 110.1 67.6 80 122.7 119.7 134.9 95.7 143.4 70.6 116.6 116.6 127.0 92.7 134.9 67.5 113.4 113.4 118.5 89.4 125.9 64.2 109.9 109.9 110.1 86.1 4200 85 132.8 132.8 134.9 114.3 143.4 89.1 125.3 125.3 127.0 111.2 134.9 86.0 117.7 117.7 118.5 107.9 125.9 82.9 110.0 110.0 110.1 104.7 90 133.4 133.4 134.9 132.8 143.4 107.7 128.9 128.9 129.8 129.8 134.9 104.7 124.5 124.5 125.3 125.3 125.9 101.3 115.2 115.2 116.4 116.4 75 124.7 105.7 137.1 80.8 145.6 54.3 117.5 102.5 129.0 77.4 137.1 51.2 109.7 99.1 120.4 74.0 127.9 47.7 102.0 95.7 111.8 70.7 80 125.1 125.1 137.1 100.1 145.6 73.8 121.9 121.9 129.0 96.8 137.1 70.5 118.5 118.5 120.4 93.4 127.9 67.1 111.1 111.1 111.8 90.0 4600 85 136.9 136.9 137.1 119.5 145.6 93.1 128.7 128.7 129.0 116.2 137.1 89.9 119.9 119.9 120.4 112.7 127.9 86.6 111.5 111.5 111.8 109.4 90 137.9 137.9 138.8 138.8 145.6 112.5 134.7 134.7 135.6 135.6 137.1 109.5 127.4 127.4 127.8 127.8 127.9 105.8 117.0 117.0 117.7 117.7 75 126.7 110.3 139.2 84.2 147.9 56.7 119.3 106.9 131.0 80.8 139.2 53.4 111.4 103.3 122.3 77.2 129.9 49.8 103.6 99.8 113.6 73.7 80 130.5 130.5 139.2 104.4 147.9 76.9 127.1 127.1 131.0 101.0 139.2 73.6 121.9 121.9 122.3 97.4 129.9 70.0 112.7 112.7 113.6 93.8 5000 85 138.6 138.6 139.2 124.6 147.9 97.1 130.3 130.3 131.0 121.2 139.2 93.7 122.2 122.2 122.3 117.6 129.9 90.3 113.9 113.9 114.1 114.1 90 144.1 144.1 144.8 144.8 147.9 117.4 138.6 138.6 138.7 138.7 139.2 114.2 128.8 128.8 129.4 129.4 129.9 110.4 119.6 119.6 120.2 120.2 Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

73 TGC 115.0 115.0 115.0 115.0 116.9 116.9 116.9 116.9 118.7 118.7 118.7 118.7 120.6 120.6 120.6 120.6

SHC 40.6 58.3 76.0 93.6 42.5 61.1 79.5 98.0 44.4 63.8 83.1 102.5 46.3 66.6 86.7 106.9

All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-10 — Gross Cooling Capacities (kW) TTA125B Condensing Unit with TWE155B Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h

Enter. Dry Bulb

16.1

19.4

35.0

22.8

16.1

Airflow

19.4

40.6 Entering Wet Bulb (°C) 22.8 16.1

19.4

46.1

22.8

16.1

19.4

(°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23.9 35.4 28.3 38.9 21.6 41.3 14.6 33.3 27.5 36.6 20.7 38.9 13.7 31.1 26.5 34.2 19.8 36.3 12.8 28.9 25.6 31.7 18.9 26.7 35.4 33.5 38.9 26.8 41.3 19.7 33.3 32.6 36.6 25.9 38.9 18.9 31.7 31.7 34.2 25.0 36.3 18.0 30.7 30.7 31.7 24.1 6372 29.4 37.2 37.2 38.9 32.0 41.3 24.9 35.0 35.0 36.6 31.1 38.9 24.1 32.9 32.9 34.2 30.2 36.3 23.2 30.8 30.8 31.7 29.3 32.2 37.3 37.3 38.9 37.2 41.3 30.1 36.1 36.1 36.6 36.3 38.9 29.3 34.8 34.8 35.1 35.1 36.3 28.3 32.2 32.2 32.6 32.6 23.9 36.0 29.7 39.5 22.6 42.0 15.2 33.9 28.7 37.2 21.7 39.5 14.4 31.6 27.8 34.7 20.7 36.9 13.4 29.4 26.8 32.3 19.8 26.7 36.0 35.1 39.5 28.0 42.0 20.7 34.2 34.2 37.2 27.2 39.5 19.8 33.2 33.2 34.7 26.2 36.9 18.8 32.2 32.2 32.3 25.2 7135 29.4 38.9 38.9 39.5 33.5 42.0 26.1 36.7 36.7 37.2 32.6 39.5 25.2 34.5 34.5 34.7 31.6 36.9 24.3 32.2 32.2 32.3 30.7 32.2 39.1 39.1 39.5 38.9 42.0 31.6 37.8 37.8 38.0 38.0 39.5 30.7 36.5 36.5 36.7 36.7 36.9 29.7 33.8 33.8 34.1 34.1 23.9 36.5 31.0 40.2 23.7 42.7 15.9 34.4 30.0 37.8 22.7 40.2 15.0 32.1 29.0 35.3 21.7 37.5 14.0 29.9 28.0 32.8 20.7 26.7 36.7 36.7 40.2 29.3 42.7 21.6 35.7 35.7 37.8 28.4 40.2 20.7 34.7 34.7 35.3 27.4 37.5 19.7 32.6 32.6 32.8 26.4 7816 29.4 40.1 40.1 40.2 35.0 42.7 27.3 37.7 37.7 37.8 34.0 40.2 26.3 35.1 35.1 35.3 33.0 37.5 25.4 32.7 32.7 32.8 32.1 32.2 40.4 40.4 40.7 40.7 42.7 33.0 39.5 39.5 39.7 39.7 40.2 32.1 37.3 37.3 37.4 37.4 37.5 31.0 34.3 34.3 34.5 34.5 23.9 37.1 32.3 40.8 24.7 43.3 16.6 35.0 31.3 38.4 23.7 40.8 15.6 32.6 30.3 35.8 22.6 38.1 14.6 30.4 29.2 33.3 21.6 26.7 38.2 38.2 40.8 30.6 43.3 22.5 37.2 37.2 38.4 29.6 40.8 21.6 35.7 35.7 35.8 28.5 38.1 20.5 33.0 33.0 33.3 27.5 8496 29.4 40.6 40.6 40.8 36.5 43.3 28.5 38.2 38.2 38.4 35.5 40.8 27.5 35.8 35.8 35.8 34.5 38.1 26.5 33.4 33.4 33.4 33.4 32.2 42.2 42.2 42.4 42.4 43.3 34.4 40.6 40.6 40.6 40.6 40.8 33.5 37.7 37.7 37.9 37.9 38.1 32.3 35.0 35.0 35.2 35.21 Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

22.8 TGC 33.7 33.7 33.7 33.7 34.3 34.3 34.3 34.3 34.8 34.8 34.8 34.8 35.3 35.3 35.3 35.3

SHC 11.9 17.1 22.3 27.4 12.5 17.9 23.3 28.7 13.0 18.7 24.3 30.0 13.6 19.5 25.4 31.3

All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

22

SS-PRC003-EN

Performance Data

System

Table PD-11 — Gross Cooling Capacities (MBh) TTA155B Condensing Unit with TWE155B Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 4500

5000

5500

6000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 153.6 154.5 157.8 165.9 156.7 158.0 163.0 171.5 159.4 161.0 167.6 176.3 161.6 163.8 171.7 180.7

SHC 120.6 140.6 157.8 165.9 126.1 148.1 163.0 171.5 131.3 155.3 167.6 176.3 136.3 162.2 171.7 180.7

67 TGC 169.3 169.7 170.7 171.6 172.4 172.9 173.9 175.3 174.9 175.7 176.6 178.6 177.1 178.0 179.1 180.9

SHC 101.0 116.3 136.1 156.3 99.7 121.2 143.0 165.1 103.1 125.9 149.5 173.6 106.2 130.4 155.8 180.9

95

73 TGC 185.5 186.6 187.6 188.0 188.2 189.8 190.9 191.5 190.6 192.5 193.0 194.4 192.5 194.7 195.5 196.8

SHC 68.8 90.6 111.5 131.2 69.9 93.6 116.5 137.6 71.2 96.5 120.1 143.6 72.4 99.2 124.2 149.5

61 TGC 148.1 149.2 153.2 161.1 151.0 152.4 158.2 166.4 153.5 155.4 162.5 170.9 155.5 157.6 166.3 175.0

105 Entering Wet Bulb (°F) 73 61

67 SHC 117.8 137.8 153.2 161.1 123.2 145.2 158.2 166.4 128.3 152.3 162.5 170.9 133.2 157.6 166.3 175.0

TGC 163.0 163.5 164.5 165.6 165.9 166.5 167.5 169.1 168.2 169.0 170.0 172.3 169.5 171.2 172.3 175.1

SHC 98.5 113.4 133.3 153.4 97.0 118.3 140.0 162.2 100.3 122.9 146.5 170.7 102.4 127.4 152.7 175.1

TGC 178.1 179.4 180.4 180.8 180.6 182.3 182.7 184.0 182.7 184.6 185.3 186.7 184.4 186.6 187.6 189.0

SHC 66.3 87.8 108.8 128.2 67.3 90.8 112.8 134.5 68.5 93.7 117.0 140.5 69.6 96.4 121.0 146.3

TGC 141.7 142.9 147.8 155.4 144.4 146.0 152.4 160.4 146.6 148.2 156.5 164.7 148.5 151.6 160.0 168.5

SHC 114.5 134.6 147.8 155.4 119.8 141.9 152.4 160.4 124.8 148.2 156.5 164.7 129.7 151.6 160.0 168.5

67 TGC 155.8 156.4 157.4 158.7 158.4 159.1 160.1 162.1 159.8 161.5 162.5 164.9 161.7 163.4 164.7 168.7

SHC 95.6 110.1 130.0 150.2 93.9 114.9 136.6 159.0 96.2 119.4 143.1 164.9 98.8 123.8 149.3 168.7

115

73 TGC 169.8 171.4 172.5 173.0 172.1 174.1 174.6 175.9 173.9 176.2 177.0 178.3 175.4 178.0 179.0 180.3

SHC 63.4 84.9 105.8 125.0 64.4 87.8 109.5 131.2 65.5 90.6 113.6 137.1 66.5 93.3 117.5 142.8

61 TGC 134.4 135.9 141.6 149.1 136.8 138.9 145.9 153.7 138.9 141.7 149.7 157.8 140.6 144.8 153.0 161.3

SHC 110.7 131.0 141.6 149.1 116.0 138.2 145.9 153.7 120.9 141.7 149.7 157.8 125.7 144.8 153.0 161.3

67 TGC 147.7 148.4 149.4 151.1 149.3 151.0 152.0 153.9 151.3 153.1 154.3 157.9 153.6 154.9 156.3 161.5

SHC 92.3 106.4 126.3 146.7 89.6 111.1 132.9 153.9 92.3 115.6 139.3 157.9 96.9 119.9 145.5 161.5

73 TGC 160.6 162.6 163.2 164.5 162.7 165.0 165.8 167.1 164.3 167.0 168.0 169.3 165.6 168.6 169.9 171.2

SHC 60.3 81.6 101.6 121.4 61.2 84.6 105.8 127.6 62.3 87.4 109.9 133.5 63.1 90.1 113.8 139.2

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-11 — Gross Cooling Capacities (kW) TTA155B Condensing Unit with TWE155B Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 7646

8496

9346

10195

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 45.0 45.2 46.2 48.6 45.9 46.3 47.7 50.2 46.7 47.1 49.1 51.6 47.3 48.0 50.3 52.9

SHC 35.3 41.2 46.2 48.6 36.9 43.4 47.7 50.2 38.4 45.5 49.1 51.6 39.9 47.5 50.3 52.9

19.4 TGC 49.6 49.7 50.0 50.2 50.5 50.6 50.9 51.3 51.2 51.4 51.7 52.3 51.9 52.1 52.4 53.0

SHC 29.6 34.0 39.9 45.8 29.2 35.5 41.9 48.3 30.2 36.9 43.8 50.8 31.1 38.2 45.6 53.0

35.0

22.8 TGC 54.3 54.6 54.9 55.0 55.1 55.6 55.9 56.1 55.8 56.3 56.5 56.9 56.4 57.0 57.2 57.6

SHC 20.1 26.5 32.7 38.4 20.5 27.4 34.1 40.3 20.8 28.3 35.2 42.1 21.2 29.1 36.4 43.8

16.1 TGC 43.4 43.7 44.9 47.2 44.2 44.6 46.3 48.7 44.9 45.5 47.6 50.0 45.5 46.1 48.7 51.2

19.4 SHC 34.5 40.4 44.9 47.2 36.1 42.5 46.3 48.7 37.6 44.6 47.6 50.0 39.0 46.1 48.7 51.2

TGC 47.7 47.9 48.2 48.5 48.6 48.8 49.0 49.5 49.3 49.5 49.8 50.4 49.6 50.1 50.4 51.3

SHC 28.8 33.2 39.0 44.9 28.4 34.6 41.0 47.5 29.4 36.0 42.9 50.0 30.0 37.3 44.7 51.3

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 52.1 52.5 52.8 52.9 52.9 53.4 53.5 53.9 53.5 54.1 54.3 54.7 54.0 54.6 54.9 55.3

SHC 19.4 25.7 31.9 37.5 19.7 26.6 33.0 39.4 20.1 27.4 34.3 41.1 20.4 28.2 35.4 42.8

TGC 41.5 41.8 43.3 45.5 42.3 42.8 44.6 47.0 42.9 43.4 45.8 48.2 43.5 44.4 46.9 49.3

SHC 33.5 39.4 43.3 45.5 35.1 41.6 44.6 47.0 36.5 43.4 45.8 48.2 38.0 44.4 46.9 49.3

19.4 TGC 45.6 45.8 46.1 46.5 46.4 46.6 46.9 47.5 46.8 47.3 47.6 48.3 47.3 47.9 48.2 49.4

SHC 28.0 32.2 38.1 44.0 27.5 33.6 40.0 46.5 28.2 35.0 41.9 48.3 28.9 36.3 43.7 49.4

46.1

22.8 TGC 49.7 50.2 50.5 50.7 50.4 51.0 51.1 51.5 50.9 51.6 51.8 52.2 51.4 52.1 52.4 52.8

SHC 18.6 24.8 31.0 36.6 18.9 25.7 32.1 38.4 19.2 26.5 33.3 40.1 19.5 27.3 34.4 41.8

16.1 TGC 39.4 39.8 41.5 43.7 40.1 40.7 42.7 45.0 40.7 41.5 43.8 46.2 41.2 42.4 44.8 47.2

19.4

22.8

SHC TGC SHC TGC SHC 32.4 43.2 27.0 47.0 17.7 38.3 43.5 31.1 47.6 23.9 41.5 43.8 37.0 47.8 29.7 43.7 44.2 42.9 48.2 35.6 34.0 43.7 26.2 47.6 17.9 40.5 44.2 32.5 48.3 24.8 42.7 44.5 38.9 48.6 31.0 45.0 45.1 45.1 48.9 37.4 35.4 44.3 27.0 48.1 18.3 41.5 44.8 33.9 48.9 25.6 43.8 45.2 40.8 49.2 32.2 46.2 46.2 46.2 49.6 39.1 36.8 45.0 28.4 48.5 18.5 42.4 45.3 35.1 49.4 26.4 44.8 45.8 42.6 49.7 33.3 47.2 47.3 47.3 50.1 40.7

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

23

Performance Data

System

Table PD-12— Gross Cooling Capacities (MBh) TTA155B Condensing Unit with TWE200B Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 4500

5000

5500

6000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 158.1 159.2 163.2 171.5 161.4 162.8 168.7 177.4 164.1 166.0 173.5 182.5 166.3 168.5 177.7 187.1

SHC 125.3 146.5 163.2 171.5 131.2 154.7 168.7 177.4 136.9 162.5 173.5 182.5 142.4 168.5 177.7 187.1

67 TGC 174.1 174.5 175.5 176.6 177.3 177.8 178.8 180.4 179.9 180.6 181.6 184.0 181.3 183.0 184.2 187.3

SHC 103.2 120.6 141.6 162.9 103.3 125.9 149.0 172.6 107.0 131.1 156.2 182.0 109.2 136.0 163.2 187.3

95

73 TGC 189.9 191.6 192.7 193.1 192.7 194.8 196.1 196.7 195.0 197.5 198.2 199.6 196.8 199.7 200.7 202.1

SHC 70.5 93.5 115.6 136.3 71.7 96.8 121.1 143.2 72.9 99.9 124.8 149.9 74.1 103.0 129.2 156.4

61 TGC 152.4 153.6 158.3 166.4 155.4 157.0 163.6 172.0 157.9 160.1 168.1 176.8 160.0 163.1 172.0 181.0

105 Entering Wet Bulb (°F) 73 61

67 SHC 122.3 143.6 158.3 166.4 128.2 151.7 163.6 172.0 133.8 159.5 168.1 176.8 139.2 163.1 172.0 181.0

TGC 167.6 168.1 169.0 170.3 170.5 171.1 172.1 174.0 172.0 173.7 174.8 177.0 174.1 175.9 177.2 181.2

SHC 100.6 117.6 138.6 160.0 100.5 122.9 146.0 169.6 103.1 127.9 153.1 177.0 106.0 132.8 160.1 181.2

TGC 182.4 184.2 185.2 185.7 184.9 187.1 187.6 188.8 186.9 189.5 190.2 191.5 188.5 191.4 192.4 193.9

SHC 67.9 90.7 112.8 133.2 69.0 94.0 117.0 140.0 70.2 97.1 121.5 146.6 71.3 100.0 125.9 153.1

TGC 145.7 147.0 152.6 160.5 148.4 150.3 157.5 165.8 150.7 153.2 161.7 170.3 152.7 156.7 165.4 174.2

SHC 118.9 140.2 152.6 160.5 124.6 148.2 157.5 165.8 130.2 153.2 161.7 170.3 135.5 156.7 165.4 174.2

67 TGC 160.0 160.7 161.6 163.2 162.7 163.5 164.5 166.8 164.0 165.8 167.0 170.4 165.9 167.8 169.3 174.4

SHC 97.5 114.1 135.2 156.7 97.3 119.3 142.5 166.3 99.4 124.3 149.6 170.4 102.2 129.1 156.5 174.4

115

73 TGC 173.8 175.9 176.4 177.6 176.0 178.6 179.2 180.5 177.8 180.7 181.7 182.9 179.1 182.5 183.7 185.0

SHC 64.9 87.7 108.9 129.9 66.0 90.9 113.5 136.6 67.1 94.0 118.0 143.2 68.2 97.0 122.3 149.5

61 TGC 138.1 139.7 146.2 153.9 140.5 142.7 150.7 158.8 142.7 146.4 154.7 163.0 144.5 149.6 158.1 166.8

SHC 115.0 136.5 146.2 153.9 120.7 142.7 150.7 158.8 126.1 146.4 154.7 163.0 131.4 149.6 158.1 166.8

67 TGC 151.6 152.4 153.4 155.3 153.1 155.0 156.1 159.0 155.2 157.1 158.5 163.2 156.9 159.0 160.7 167.0

SHC 94.1 110.3 131.4 153.1 92.5 115.4 138.7 159.0 95.3 120.4 145.8 163.2 98.0 125.1 152.6 167.0

73 TGC 164.3 166.9 167.5 168.8 166.2 169.3 170.2 171.5 167.7 171.2 172.4 173.7 168.8 172.8 174.3 175.6

SHC 61.7 84.4 105.2 126.2 62.7 87.6 109.8 133.0 63.8 90.7 114.2 139.5 64.8 93.6 118.4 145.8

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-12 — Gross Cooling Capacities (kW) TTA155B Condensing Unit with TWE200B Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 7646

8496

9346

10195

Enter. Dry Bulb (°C) 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2 23.9 26.7 29.4 32.2

16.1 TGC 46.3 46.6 47.8 50.2 47.2 47.7 49.4 51.9 48.0 48.6 50.8 53.4 48.7 49.3 52.0 54.8

SHC 36.7 42.9 47.8 50.2 38.4 45.3 49.4 51.9 40.1 47.6 50.8 53.4 41.7 49.3 52.0 54.8

19.4 TGC 51.0 51.1 51.4 51.7 51.9 52.1 52.4 52.8 52.7 52.9 53.2 53.9 53.1 53.6 53.9 54.8

SHC 30.2 35.3 41.5 47.7 30.3 36.9 43.6 50.5 31.3 38.4 45.7 53.3 32.0 39.8 47.8 54.8

35.0

22.8 TGC 55.6 56.1 56.4 56.5 56.4 57.0 57.4 57.6 57.1 57.8 58.0 58.4 57.6 58.5 58.8 59.2

SHC 20.7 27.4 33.9 39.9 21.0 28.3 35.4 41.9 21.3 29.3 36.5 43.9 21.7 30.1 37.8 45.8

16.1 TGC 44.6 45.0 46.4 48.7 45.5 46.0 47.9 50.4 46.2 46.9 49.2 51.8 46.8 47.7 50.4 53.0

19.4 SHC 35.8 42.0 46.4 48.7 37.5 44.4 47.9 50.4 39.2 46.7 49.2 51.8 40.8 47.7 50.4 53.0

TGC 49.1 49.2 49.5 49.9 49.9 50.1 50.4 50.9 50.4 50.9 51.2 51.8 51.0 51.5 51.9 53.1

SHC 29.4 34.4 40.6 46.8 29.4 36.0 42.7 49.7 30.2 37.5 44.8 51.8 31.0 38.9 46.9 53.1

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 53.4 53.9 54.2 54.4 54.1 54.8 54.9 55.3 54.7 55.5 55.7 56.1 55.2 56.1 56.3 56.8

SHC 19.9 26.6 33.0 39.0 20.2 27.5 34.2 41.0 20.5 28.4 35.6 42.9 20.9 29.3 36.9 44.8

TGC 42.7 43.1 44.7 47.0 43.4 44.0 46.1 48.5 44.1 44.9 47.4 49.9 44.7 45.9 48.4 51.0

SHC 34.8 41.1 44.7 47.0 36.5 43.4 46.1 48.5 38.1 44.9 47.4 49.9 39.7 45.9 48.4 51.0

19.4 TGC 46.9 47.0 47.3 47.8 47.6 47.9 48.2 48.8 48.0 48.6 48.9 49.9 48.6 49.1 49.6 51.1

SHC 28.5 33.4 39.6 45.9 28.5 34.9 41.7 48.7 29.1 36.4 43.8 49.9 29.9 37.8 45.8 51.1

46.1

22.8 TGC 50.9 51.5 51.6 52.0 51.5 52.3 52.5 52.9 52.0 52.9 53.2 53.6 52.4 53.4 53.8 54.2

SHC 19.0 25.7 31.9 38.0 19.3 26.6 33.2 40.0 19.6 27.5 34.6 41.9 20.0 28.4 35.8 43.8

16.1 TGC 40.4 40.9 42.8 45.1 41.1 41.8 44.1 46.5 41.8 42.9 45.3 47.7 42.3 43.8 46.3 48.8

SHC 33.7 40.0 42.8 45.1 35.3 41.8 44.1 46.5 36.9 42.9 45.3 47.7 38.5 43.8 46.3 48.8

19.4 TGC 44.4 44.6 44.9 45.5 44.8 45.4 45.7 46.6 45.4 46.0 46.4 47.8 45.9 46.5 47.0 48.9

SHC 27.6 32.3 38.5 44.8 27.1 33.8 40.6 46.6 27.9 35.2 42.7 47.8 28.7 36.6 44.7 48.9

22.8 TGC 48.1 48.9 49.0 49.4 48.7 49.6 49.8 50.2 49.1 50.1 50.5 50.9 49.4 50.6 51.0 51.4

SHC 18.1 24.7 30.8 37.0 18.4 25.7 32.1 38.9 18.7 26.5 33.4 40.8 19.0 27.4 34.7 42.7

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

24

SS-PRC003-EN

Performance Data

System

Table PD-13 — Gross Cooling Capacities (MBh) - Both Compressors - TTA155C Condensing Unit With TWE155B Air Handler (I-P) Ambient Temperature (°F) 85

CFM Airflow 4500

5000

5500

6000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 147.1 147.9 152.6 160.5 150.0 151.2 157.6 165.9 152.4 154.3 162.0 170.7 154.4 157.1 165.9 174.9

SHC 118.2 138.6 152.6 160.5 123.9 146.4 157.6 165.9 129.4 153.9 162.0 170.7 134.6 157.1 165.9 174.9

67 TGC 163.0 163.3 163.5 164.5 165.9 166.1 166.5 168.1 168.4 168.6 169.1 170.9 170.5 170.8 171.5 175.1

SHC 98.8 113.9 134.0 154.5 96.6 119.0 141.1 163.7 100.0 124.0 147.9 170.9 103.1 128.8 154.6 175.1

95

73 TGC 180.4 180.5 180.8 180.9 183.5 183.6 183.8 184.0 185.9 186.1 186.4 186.6 188.0 188.2 188.6 188.9

SHC 66.6 87.8 108.6 129.2 68.0 90.8 113.6 135.8 69.1 93.7 118.3 142.1 70.0 96.4 122.9 148.3

61 TGC 141.7 142.7 148.0 155.8 144.4 145.9 152.8 160.9 146.6 148.6 156.9 165.3 148.5 152.1 160.6 169.2

105 Entering Wet Bulb (°F) 73 61

67 SHC 115.6 136.0 148.0 155.8 121.2 143.8 152.8 160.9 126.6 148.6 156.9 165.3 131.8 152.1 160.6 169.2

TGC 156.9 157.2 157.4 158.6 159.6 159.8 160.2 162.1 161.8 162.0 162.6 165.4 163.7 164.0 164.8 169.4

SHC 96.3 111.3 131.3 151.9 94.0 116.3 138.4 161.1 97.3 121.2 145.1 165.4 100.4 126.0 151.7 169.4

TGC 173.3 173.4 173.6 173.8 176.1 176.2 176.5 176.7 178.3 178.5 178.8 179.1 180.3 180.4 180.6 181.1

SHC 64.1 85.1 106.0 126.4 65.3 88.1 110.9 133.0 66.3 91.0 115.6 139.3 67.2 93.7 119.8 145.4

TGC 135.4 136.7 142.7 150.3 137.8 139.4 147.2 155.1 139.9 143.0 151.1 159.2 141.7 146.2 154.5 162.8

SHC 112.5 133.1 142.7 150.3 118.1 139.4 147.2 155.1 123.4 143.0 151.1 159.2 128.6 146.2 154.5 162.8

67 TGC 149.9 150.1 150.5 152.0 152.4 152.6 153.1 155.2 154.4 154.7 155.4 159.4 156.1 156.4 157.5 163.0

SHC 93.6 108.1 128.3 149.0 91.0 113.2 135.3 155.2 94.3 118.1 142.1 159.4 97.4 122.8 148.6 163.0

115

73 TGC 165.4 165.5 165.8 166.0 167.8 168.0 168.3 168.6 169.9 170.0 170.2 170.7 171.6 171.8 172.1 172.6

SHC 61.4 82.2 103.0 123.3 62.4 85.1 107.9 129.9 63.3 87.9 112.3 136.1 64.2 90.6 116.6 142.2

61 TGC 128.3 130.0 136.7 144.1 130.5 133.2 140.9 148.6 132.5 136.6 144.5 152.5 134.2 139.6 147.7 155.9

SHC 109.1 129.8 136.7 144.1 114.6 133.2 140.9 148.6 120.0 136.6 144.5 152.5 125.1 139.6 147.7 155.9

67 TGC 142.1 142.3 142.8 144.3 144.3 144.6 145.2 148.7 146.2 146.5 147.4 152.7 147.7 148.1 149.5 156.1

SHC 90.5 104.8 125.0 144.3 87.8 109.8 132.0 148.7 91.0 114.7 138.7 152.7 94.1 119.3 145.3 156.1

73 TGC 156.9 157.1 157.3 157.6 159.1 159.3 159.7 159.9 161.0 161.2 161.4 161.9 162.5 162.8 163.1 163.5

SHC 58.5 79.1 99.9 120.1 59.2 82.0 104.8 126.6 60.2 84.8 109.0 132.8 61.0 87.5 113.2 138.9

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-13 — Gross Cooling Capacities (kW) - Both Compressors - TTA155C Condensing Unit With TWE155B Air Handler (SI) Ambient Temperature (°C) 29.4

m3/h Airflow 7646

8496

9346

10195

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 43.1 43.3 44.7 47.0 43.9 44.3 46.2 48.6 44.6 45.2 47.4 50.0 45.2 46.0 48.6 51.2

SHC 34.6 40.6 44.7 47.0 36.3 42.9 46.2 48.6 37.9 45.1 47.4 50.0 39.4 46.0 48.6 51.2

19.4 TGC 47.7 47.8 47.9 48.2 48.6 48.6 48.8 49.2 49.3 49.4 49.5 50.0 49.9 50.0 50.2 51.3

SHC 28.9 33.4 39.2 45.2 28.3 34.9 41.3 47.9 29.3 36.3 43.3 50.0 30.2 37.7 45.3 51.3

35.0

22.8 TGC 52.8 52.8 52.9 53.0 53.7 53.7 53.8 53.9 54.4 54.5 54.6 54.6 55.1 55.1 55.2 55.3

SHC 19.5 25.7 31.8 37.8 19.9 26.6 33.3 39.8 20.2 27.4 34.6 41.6 20.5 28.2 36.0 43.4

16.1 TGC 41.5 41.8 43.3 45.6 42.3 42.7 44.7 47.1 42.9 43.5 46.0 48.4 43.5 44.5 47.0 49.6

19.4 SHC 33.8 39.8 43.3 45.6 35.5 42.1 44.7 47.1 37.1 43.5 46.0 48.4 38.6 44.5 47.0 49.6

TGC 45.9 46.0 46.1 46.4 46.7 46.8 46.9 47.5 47.4 47.4 47.6 48.4 47.9 48.0 48.3 49.6

SHC 28.2 32.6 38.5 44.5 27.5 34.1 40.5 47.2 28.5 35.5 42.5 48.4 29.4 36.9 44.4 49.6

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 50.7 50.8 50.8 50.9 51.6 51.6 51.7 51.7 52.2 52.3 52.4 52.4 52.8 52.8 52.9 53.0

SHC 18.8 24.9 31.0 37.0 19.1 25.8 32.5 38.9 19.4 26.6 33.8 40.8 19.7 27.4 35.1 42.6

TGC 39.7 40.0 41.8 44.0 40.4 40.8 43.1 45.4 41.0 41.9 44.2 46.6 41.5 42.8 45.2 47.7

SHC 32.9 39.0 41.8 44.0 34.6 40.8 43.1 45.4 36.1 41.9 44.2 46.6 37.7 42.8 45.2 47.7

19.4 TGC 43.9 43.9 44.1 44.5 44.6 44.7 44.8 45.4 45.2 45.3 45.5 46.7 45.7 45.8 46.1 47.7

SHC 27.4 31.7 37.6 43.6 26.7 33.2 39.6 45.4 27.6 34.6 41.6 46.7 28.5 36.0 43.5 47.7

46.1

22.8 TGC 48.4 48.5 48.5 48.6 49.1 49.2 49.3 49.4 49.7 49.8 49.8 50.0 50.2 50.3 50.4 50.5

SHC 18.0 24.1 30.2 36.1 18.3 24.9 31.6 38.0 18.5 25.7 32.9 39.9 18.8 26.5 34.1 41.6

16.1 TGC 37.6 38.1 40.0 42.2 38.2 39.0 41.3 43.5 38.8 40.0 42.3 44.6 39.3 40.9 43.2 45.6

19.4

22.8

SHC TGC SHC TGC SHC 31.9 41.6 26.5 45.9 17.1 38.0 41.7 30.7 46.0 23.2 40.0 41.8 36.6 46.1 29.3 42.2 42.3 42.3 46.1 35.2 33.6 42.3 25.7 46.6 17.3 39.0 42.3 32.2 46.7 24.0 41.3 42.5 38.6 46.7 30.7 43.5 43.6 43.6 46.8 37.1 35.1 42.8 26.6 47.1 17.6 40.0 42.9 33.6 47.2 24.8 42.3 43.2 40.6 47.3 31.9 44.6 44.7 44.7 47.4 38.9 36.6 43.3 27.5 47.6 17.9 40.9 43.4 34.9 47.7 25.6 43.2 43.8 42.5 47.7 33.2 45.6 45.7 45.7 47.9 40.7

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

25

Performance Data

System

Table PD-14 — Gross Cooling Capacities (MBh) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (I-P) Ambient Temperature (°F) 85

CFM Airflow 4500

5000

5500

6000

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 90.4 96.3 102.2 108.3 92.5 98.6 104.7 111.0 94.4 100.6 106.9 113.2 96.0 102.3 108.7 115.1

SHC 90.4 96.3 102.2 108.3 92.5 98.6 104.7 111.0 94.4 100.6 106.9 113.2 96.0 102.3 108.7 115.1

67 TGC 99.1 99.6 102.3 108.4 100.2 100.8 104.8 111.1 101.1 102.0 107.0 113.4 101.9 103.0 108.8 115.2

SHC 67.0 87.3 102.3 108.4 70.1 92.2 104.8 111.1 72.9 97.0 107.0 113.4 75.7 101.7 108.8 115.2

95

73 TGC 109.4 109.8 109.9 110.7 110.4 110.6 111.1 112.2 111.3 111.5 112.0 113.4 112.0 112.4 112.8 115.3

SHC 42.8 62.7 82.7 103.2 42.7 65.1 87.2 109.7 43.5 67.6 91.5 113.4 44.3 70.7 95.7 115.3

61 TGC 87.8 93.4 99.2 105.1 89.7 95.6 101.6 107.6 91.5 97.5 103.6 109.8 92.9 99.1 105.3 111.7

105 Entering Wet Bulb (°F) 73 61

67 SHC 87.8 93.4 99.2 105.1 89.7 95.6 101.6 107.6 91.5 97.5 103.6 109.8 92.9 99.1 105.3 111.7

TGC 95.6 96.1 99.3 105.2 96.6 97.3 101.7 107.7 97.5 98.4 103.7 109.9 98.2 99.1 105.4 111.8

SHC 65.6 85.9 99.3 105.2 68.6 90.8 101.7 107.7 71.5 95.6 103.7 109.9 74.3 99.1 105.4 111.8

TGC 105.2 105.5 106.0 106.9 106.2 106.6 107.0 108.4 107.0 107.4 107.9 110.0 107.6 108.2 108.7 111.9

SHC 41.5 61.1 81.3 101.8 41.3 63.6 85.7 108.3 42.1 66.1 90.1 110.0 42.9 68.5 94.3 111.9

TGC 84.6 90.1 95.7 101.4 86.4 92.1 97.9 103.8 88.0 93.8 99.8 105.9 89.4 95.3 101.4 107.6

SHC 84.6 90.1 95.7 101.4 86.4 92.1 97.9 103.8 88.0 93.8 99.8 105.9 89.4 95.3 101.4 107.6

67 TGC 91.5 92.1 95.8 101.5 92.4 93.3 98.0 103.9 93.2 94.4 99.9 106.0 93.9 95.4 101.5 107.7

SHC 64.0 84.3 95.8 101.5 67.0 89.2 98.0 103.9 69.8 94.0 99.9 106.0 72.6 95.4 101.5 107.7

115

73 TGC 100.7 101.1 101.5 102.6 101.5 102.0 102.5 104.0 102.3 102.8 103.3 106.0 102.9 103.5 104.1 107.8

SHC 40.0 59.5 79.7 100.3 39.8 62.0 84.1 104.0 40.6 64.5 88.5 106.0 41.3 66.8 92.6 107.8

61 TGC 80.9 86.2 91.7 97.3 82.6 88.1 93.8 99.6 84.1 89.7 95.6 101.5 85.4 91.1 97.1 103.2

SHC 80.9 86.2 91.7 97.3 82.6 88.1 93.8 99.6 84.1 89.7 95.6 101.5 85.4 91.1 97.1 103.2

67 TGC 87.0 87.6 91.8 97.4 87.8 88.8 93.9 99.7 88.5 89.8 95.6 101.6 89.1 91.2 97.2 103.3

SHC 62.2 82.5 91.8 97.4 65.1 87.4 93.9 99.7 68.0 89.8 95.6 101.6 70.7 91.2 97.2 103.3

73 TGC 95.7 96.1 96.5 97.5 96.5 97.0 97.5 99.8 97.1 97.8 98.3 101.7 97.6 98.4 99.1 103.4

SHC 38.3 57.7 77.9 97.5 38.1 60.3 82.4 99.8 38.9 62.7 86.7 101.7 39.7 65.1 90.9 103.4

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-14 — Gross Cooling Capacities (kW) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (SI) Ambient Temperature (°C) 29.4

m3/h Airflow 7646

8496

9346

10195

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 26.5 28.2 29.9 31.7 27.1 28.9 30.7 32.5 27.6 29.4 31.3 33.2 28.1 30.0 31.8 33.7

SHC 26.5 28.2 29.9 31.7 27.1 28.9 30.7 32.5 27.6 29.4 31.3 33.2 28.1 30.0 31.8 33.7

19.4 TGC 29.0 29.2 30.0 31.7 29.3 29.5 30.7 32.5 29.6 29.9 31.3 33.2 29.8 30.2 31.9 33.7

SHC 19.6 25.6 30.0 31.7 20.5 27.0 30.7 32.5 21.4 28.4 31.3 33.2 22.2 29.8 31.9 33.7

35.0

22.8 TGC 32.0 32.1 32.2 32.4 32.3 32.4 32.5 32.9 32.6 32.7 32.8 33.2 32.8 32.9 33.0 33.8

SHC 12.5 18.4 24.2 30.2 12.5 19.1 25.5 32.1 12.7 19.8 26.8 33.2 13.0 20.7 28.0 33.8

16.1 TGC 25.7 27.4 29.1 30.8 26.3 28.0 29.7 31.5 26.8 28.5 30.3 32.1 27.2 29.0 30.8 32.7

19.4 SHC 25.7 27.4 29.1 30.8 26.3 28.0 29.7 31.5 26.8 28.5 30.3 32.1 27.2 29.0 30.8 32.7

TGC 28.0 28.1 29.1 30.8 28.3 28.5 29.8 31.5 28.5 28.8 30.4 32.2 28.7 29.0 30.9 32.7

SHC 19.2 25.2 29.1 30.8 20.1 26.6 29.8 31.5 20.9 28.0 30.4 32.2 21.7 29.0 30.9 32.7

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 30.8 30.9 31.0 31.3 31.1 31.2 31.3 31.7 31.3 31.5 31.6 32.2 31.5 31.7 31.8 32.8

SHC 12.1 17.9 23.8 29.8 12.1 18.6 25.1 31.7 12.3 19.4 26.4 32.2 12.5 20.1 27.6 32.8

TGC 24.8 26.4 28.0 29.7 25.3 27.0 28.7 30.4 25.8 27.5 29.2 31.0 26.2 27.9 29.7 31.5

SHC 24.8 26.4 28.0 29.7 25.3 27.0 28.7 30.4 25.8 27.5 29.2 31.0 26.2 27.9 29.7 31.5

19.4 TGC 26.8 27.0 28.0 29.7 27.1 27.3 28.7 30.4 27.3 27.6 29.2 31.0 27.5 27.9 29.7 31.5

SHC 18.7 24.7 28.0 29.7 19.6 26.1 28.7 30.4 20.4 27.5 29.2 31.0 21.3 27.9 29.7 31.5

46.1

22.8 TGC 29.5 29.6 29.7 30.0 29.7 29.9 30.0 30.5 29.9 30.1 30.3 31.0 30.1 30.3 30.5 31.6

SHC 11.7 17.4 23.3 29.4 11.6 18.2 24.6 30.5 11.9 18.9 25.9 31.0 12.1 19.6 27.1 31.6

16.1 TGC 23.7 25.2 26.9 28.5 24.2 25.8 27.5 29.2 24.6 26.3 28.0 29.7 25.0 26.7 28.4 30.2

19.4

22.8

SHC TGC SHC TGC SHC 23.7 25.5 18.2 28.0 11.2 25.2 25.7 24.2 28.2 16.9 26.9 26.9 26.9 28.3 22.8 28.5 28.5 28.5 28.6 28.6 24.2 25.7 19.1 28.2 11.2 25.8 26.0 25.6 28.4 17.6 27.5 27.5 27.5 28.5 24.1 29.2 29.2 29.2 29.2 29.2 24.6 25.9 19.9 28.4 11.4 26.3 26.3 26.3 28.6 18.4 28.0 28.0 28.0 28.8 25.4 29.7 29.8 29.8 29.8 29.8 25.0 26.1 20.7 28.6 11.6 26.7 26.7 26.7 28.8 19.0 28.4 28.5 28.5 29.0 26.6 30.2 30.2 30.2 30.3 30.3

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

26

SS-PRC003-EN

Performance Data

System

Table PD-15 — Gross Cooling Capacities (MBh) TTA200B Condensing Unit with TWE200B Air Handler

(I-P)

Ambient Temperature (°F) 85

CFM Airflow 6000

6675

7350

8025

Enter. Dry Bulb (°F) 75 80 85 90 75 80 85 90 75 80 85 90 75 80 85 90

61 TGC 201.0 202.2 206.7 217.1 204.9 206.6 213.4 224.4 208.3 210.6 219.4 230.7 211.2 214.3 224.6 236.3

SHC 158.5 184.9 206.7 217.1 165.7 194.8 213.4 224.4 172.6 204.3 219.4 230.7 179.2 213.5 224.6 236.3

67 TGC 221.1 221.6 222.8 224.1 225.2 225.8 227.0 228.9 228.5 229.3 230.5 233.3 231.3 232.3 233.7 236.5

SHC 132.8 152.5 178.8 205.3 130.5 159.1 187.8 217.1 134.9 165.4 196.5 228.5 139.1 171.4 204.9 236.5

95

73 TGC 242.4 243.5 244.6 245.0 246.0 247.6 248.8 249.3 248.9 250.9 251.4 252.9 251.4 253.7 254.5 256.0

SHC 89.9 118.4 146.0 172.1 91.4 122.3 152.5 180.5 93.0 126.1 157.5 188.5 94.4 129.7 162.9 196.3

61 TGC 193.1 194.5 200.1 210.4 196.8 198.8 206.6 217.3 200.0 202.7 212.2 223.3 202.6 205.8 217.2 228.6

105 Entering Wet Bulb (°F) 73 61

67 SHC 154.4 180.9 200.1 210.4 161.6 190.8 206.6 217.3 168.4 200.3 212.2 223.3 174.9 205.8 217.2 228.6

TGC 212.5 213.1 214.3 215.9 216.3 217.0 218.2 220.5 219.3 220.3 221.6 224.9 221.0 223.1 224.6 228.8

SHC 129.3 148.6 174.8 201.5 126.8 155.1 183.8 213.2 131.2 161.3 192.5 224.6 134.2 167.2 200.8 228.8

TGC 232.6 234.1 235.3 235.7 235.8 237.8 239.1 239.7 238.5 240.9 241.6 243.1 240.8 243.4 244.4 245.9

SHC 86.5 114.8 142.4 168.2 87.9 118.8 148.9 176.6 89.5 122.5 153.5 184.5 90.7 126.1 158.8 192.2

TGC 184.9 186.6 193.3 203.4 188.4 190.7 199.4 210.0 191.3 193.9 204.7 215.7 193.8 198.3 209.4 220.7

SHC 150.2 176.8 193.3 203.4 157.3 186.6 199.4 210.0 164.0 193.9 204.7 215.7 170.5 198.3 209.4 220.7

115

67 TGC 203.5 204.3 205.5 207.3 207.0 207.9 209.1 211.9 209.8 210.9 212.3 215.9 211.3 213.5 215.2 220.9

SHC 125.7 144.5 170.7 197.5 123.0 150.9 179.7 209.2 127.3 157.0 188.3 215.9 129.8 162.9 196.6 220.9

73 TGC 222.1 224.2 225.5 226.1 225.4 227.7 228.3 229.8 227.8 230.5 231.4 232.9 229.8 232.8 234.0 235.5

SHC 83.0 111.1 138.8 164.2 84.3 115.1 143.9 172.5 85.8 118.8 149.4 180.4 86.9 122.4 154.6 188.1

61 TGC 176.4 178.4 186.1 196.1 179.6 182.5 191.9 202.3 182.3 186.3 197.0 207.7 184.7 190.4 201.4 212.4

SHC 145.8 172.6 186.1 196.1 152.9 182.4 191.9 202.3 159.5 186.3 197.0 207.7 166.0 190.4 201.4 212.4

67 TGC 194.2 195.1 196.4 198.7 197.4 198.5 199.8 202.5 199.1 201.3 202.9 207.9 201.4 203.7 205.6 212.6

SHC 122.0 140.3 166.6 193.5 119.1 146.6 175.5 202.5 121.9 152.7 184.0 207.9 125.3 158.5 192.3 212.6

73 TGC 211.7 214.1 215.5 216.2 214.5 217.2 218.1 219.6 216.7 219.8 220.9 222.4 218.4 221.9 223.3 224.8

SHC 79.5 107.4 135.1 160.2 80.7 111.3 139.7 168.4 82.0 115.0 145.1 176.2 83.1 118.6 150.3 183.8

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

Table PD-15 — Gross Cooling Capacities (MBh) TTA200B Condensing Unit with TWE200B Air Handler

(SI)

Ambient Temperature (°C) 29.4

m3/h Airflow 10195

11340

12488

13633

Enter. Dry Bulb (°C) 24 27 29 32 24 27 29 32 24 27 29 32 24 27 29 32

16.1 TGC 58.8 59.2 60.5 63.6 60.0 60.5 62.5 65.7 61.0 61.7 64.2 67.5 61.8 62.7 65.8 69.2

SHC 46.4 54.1 60.5 63.6 48.5 57.0 62.5 65.7 50.5 59.8 64.2 67.5 52.5 62.5 65.8 69.2

19.4 TGC 64.7 64.9 65.2 65.6 65.9 66.1 66.5 67.0 66.9 67.1 67.5 68.3 67.7 68.0 68.4 69.2

SHC 38.9 44.7 52.3 60.1 38.2 46.6 55.0 63.6 39.5 48.4 57.5 66.9 40.7 50.2 60.0 69.2

35.0

22.8 TGC 71.0 71.3 71.6 71.7 72.0 72.5 72.8 73.0 72.9 73.5 73.6 74.1 73.6 74.3 74.5 74.9

SHC 26.3 34.7 42.7 50.4 26.8 35.8 44.6 52.8 27.2 36.9 46.1 55.2 27.6 38.0 47.7 57.5

16.1 TGC 56.5 57.0 58.6 61.6 57.6 58.2 60.5 63.6 58.5 59.3 62.1 65.4 59.3 60.3 63.6 66.9

19.4 SHC 45.2 53.0 58.6 61.6 47.3 55.9 60.5 63.6 49.3 58.6 62.1 65.4 51.2 60.3 63.6 66.9

TGC 62.2 62.4 62.7 63.2 63.3 63.5 63.9 64.6 64.2 64.5 64.9 65.8 64.7 65.3 65.8 67.0

SHC 37.9 43.5 51.2 59.0 37.1 45.4 53.8 62.4 38.4 47.2 56.4 65.8 39.3 49.0 58.8 67.0

40.6 Entering Wet Bulb (°C) 22.8 16.1 TGC 68.1 68.5 68.9 69.0 69.0 69.6 70.0 70.2 69.8 70.5 70.7 71.2 70.5 71.3 71.6 72.0

SHC 25.3 33.6 41.7 49.3 25.7 34.8 43.6 51.7 26.2 35.9 44.9 54.0 26.6 36.9 46.5 56.3

TGC 54.1 54.6 56.6 59.6 55.2 55.8 58.4 61.5 56.0 56.8 59.9 63.1 56.7 58.1 61.3 64.6

SHC 44.0 51.8 56.6 59.6 46.1 54.6 58.4 61.5 48.0 56.8 59.9 63.1 49.9 58.1 61.3 64.6

19.4 TGC 59.6 59.8 60.2 60.7 60.6 60.9 61.2 62.0 61.4 61.8 62.2 63.2 61.9 62.5 63.0 64.7

SHC 36.8 42.3 50.0 57.8 36.0 44.2 52.6 61.3 37.3 46.0 55.1 63.2 38.0 47.7 57.6 64.7

46.1

22.8 TGC 65.0 65.7 66.0 66.2 66.0 66.7 66.8 67.3 66.7 67.5 67.8 68.2 67.3 68.2 68.5 69.0

SHC 24.3 32.5 40.6 48.1 24.7 33.7 42.1 50.5 25.1 34.8 43.7 52.8 25.5 35.8 45.3 55.1

16.1 TGC 51.6 52.2 54.5 57.4 52.6 53.4 56.2 59.2 53.4 54.5 57.7 60.8 54.1 55.8 59.0 62.2

19.4

22.8

SHC TGC SHC TGC SHC 42.7 56.9 35.7 62.0 23.3 50.5 57.1 41.1 62.7 31.5 54.5 57.5 48.8 63.1 39.6 57.4 58.2 56.7 63.3 46.9 44.8 57.8 34.9 62.8 23.6 53.4 58.1 42.9 63.6 32.6 56.2 58.5 51.4 63.9 40.9 59.2 59.3 59.3 64.3 49.3 46.7 58.3 35.7 63.4 24.0 54.5 58.9 44.7 64.4 33.7 57.7 59.4 53.9 64.7 42.5 60.8 60.9 60.9 65.1 51.6 48.6 59.0 36.7 63.9 24.3 55.8 59.6 46.4 65.0 34.7 59.0 60.2 56.3 65.4 44.0 62.2 62.2 62.2 65.8 53.8

Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat. TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

SS-PRC003-EN

27

Performance Data

Condensing Unit

Table PD-16 — Cooling Performance (MBh) TTA075A Condensing Unit Only ODTemp

(I-P)

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press psig Cap. Btu/1000 OD Unit kW

175 69.1 5.01

181 76.2 5.13

188 83.6 5.27

195 91.2 5.40

202 99.0 5.55

210 106.9 5.70

75

Head press psig Cap. Btu/1000 OD Unit KW

202 66.9 5.54

209 73.7 5.68

216 80.7 5.82

223 87.9 5.97

231 95.3 6.12

239 102.8 6.28

85

Head press psig Cap. Btu/1000 OD Unit KW

232 64.1 6.16

239 70.6 6.31

247 77.3 6.46

254 84.1 6.61

262 91.1 6.77

270 98.2 6.94

95

Head press psig Cap. Btuh/1000 OD Unit KW

264 60.8 6.86

272 66.9 7.02

280 73.2 7.17

288 79.7 7.33

296 86.3 7.49

304 93.1 7.66

105

Head press psig Cap. Btuh/1000 OD Unit KW

299 57.0 7.65

307 62.7 7.80

315 68.7 7.95

323 74.8 8.11

332 81.1 8.27

341 87.6 8.45

115

Head press psig Cap. Btuh/1000 OD Unit KW

335 52.8 8.51

344 58.2 8.65

352 63.7 8.80

361 69.5 8.95

370 75.5 9.12

380 81.8 9.29

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-16 — Cooling Performance (kW) TTA075A Condensing Unit Only ODTemp

(SI)

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1208 20.2 5.01

1251 22.3 5.13

1297 24.5 5.27

1345 26.7 5.40

1395 29.0 5.55

1446 31.3 5.70

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1396 19.6 5.54

1442 21.6 5.68

1491 23.6 5.82

1541 25.7 5.97

1593 27.9 6.12

1647 30.1 6.28

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1600 18.8 6.16

1650 20.7 6.31

1701 22.6 6.46

1754 24.6 6.61

1808 26.7 6.77

1865 28.7 6.94

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1822 17.8 6.86

1874 19.6 7.02

1927 21.4 7.17

1983 23.3 7.33

2040 25.3 7.49

2099 27.3 7.66

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2059 16.7 7.65

2114 18.4 7.80

2170 20.1 7.95

2227 21.9 8.11

2287 23.7 8.27

2350 25.7 8.45

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2313 15.5 8.51

2369 17.0 8.65

2428 18.7 8.80

2488 20.4 8.95

2551 22.1 9.12

2617 24.0 9.29

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

28

SS-PRC003-EN

Performance Data

Condensing Unit

Table PD-17 — Cooling Performance (MBh) TTA085A Condensing Unit Only OD Temp

(I-P)

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

160 79.8 5.64

164 88.0 5.73

169 96.6 5.83

173 105.7 5.93

178 115.1 6.04

184 124.9 6.15

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

185 76.4 6.14

189 84.1 6.23

194 92.3 6.33

199 100.8 6.44

204 109.8 6.56

209 119.2 6.68

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

212 72.6 6.73

217 80.0 6.83

222 87.7 6.94

227 96.0 7.06

232 104.6 7.18

238 113.6 7.31

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

242 68.6 7.43

247 75.7 7.55

252 83.1 7.67

258 91.0 7.79

264 99.3 7.92

270 107.9 8.05

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

275 64.4 8.24

280 71.2 8.36

286 78.4 8.49

292 86.0 8.62

298 94.0 8.76

304 102.3 8.89

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

311 60.0 9.15

317 66.6 9.28

323 73.6 9.42

329 80.9 9.56

335 88.6 9.70

342 96.5 9.83

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-17 — Cooling Performance (kW) TTA085A Condensing Unit Only ODTemp

(SI)

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1102 23.4 5.64

1132 25.8 5.73

1163 28.3 5.83

1196 30.9 5.93

1230 33.7 6.04

1266 36.6 6.15

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1273 22.4 6.14

1304 24.6 6.23

1337 27.0 6.33

1371 29.5 6.44

1407 32.2 6.56

1444 34.9 6.68

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1462 21.3 6.73

1494 23.4 6.83

1529 25.7 6.94

1565 28.1 7.06

1603 30.6 7.18

1642 33.3 7.31

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1669 20.1 7.43

1704 22.2 7.55

1741 24.3 7.67

1779 26.6 7.79

1819 29.1 7.92

1860 31.6 8.05

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1896 18.9 8.24

1934 20.9 8.36

1973 23.0 8.49

2013 25.2 8.62

2055 27.5 8.76

2099 29.9 8.89

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2142 17.6 9.15

2184 19.5 9.28

2225 21.6 9.42

2269 23.7 9.56

2313 25.9 9.70

2358 28.3 9.83

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

SS-PRC003-EN

29

Performance Data

Condensing Unit

Table PD-18 — Cooling Performance (MBh) TTA100A Condensing Unit Only ODTemp

(I-P)

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

174 95.7 6.69

180 105.0 6.84

186 114.7 7.01

193 124.8 7.19

199 135.3 7.37

207 146.1 7.58

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

200 91.2 7.38

206 99.9 7.54

212 109.1 7.72

219 118.7 7.91

226 128.8 8.12

234 139.2 8.34

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

228 86.4 8.19

234 94.7 8.37

241 103.5 8.57

248 112.7 8.77

256 122.3 8.99

264 132.2 9.22

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

259 81.3 9.13

265 89.3 9.33

273 97.8 9.54

280 106.6 9.76

288 115.8 9.99

297 125.2 10.23

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

292 76.1 10.19

299 83.8 10.41

307 91.9 10.64

315 100.4 10.88

324 109.2 11.12

332 118.3 11.36

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

328 70.7 11.37

336 78.2 11.61

344 86.0 11.86

353 94.2 12.11

362 102.6 12.36

371 111.3 12.60

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-18 — Cooling Performance (kW) TTA100A Condensing Unit Only ODTemp

(SI)

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1200 28.0 6.69

1240 30.7 6.84

1283 33.6 7.01

1327 36.5 7.19

1375 39.6 7.37

1425 42.8 7.58

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1377 26.7 7.38

1418 29.3 7.54

1462 32.0 7.72

1509 34.8 7.91

1559 37.7 8.12

1612 40.7 8.34

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1571 25.3 8.19

1615 27.7 8.37

1662 30.3 8.57

1711 33.0 8.77

1763 35.8 8.99

1819 38.7 9.22

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1783 23.8 9.13

1830 26.2 9.33

1880 28.6 9.54

1932 31.2 9.76

1987 33.9 9.99

2045 36.7 10.23

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2014 22.3 10.19

2064 24.5 10.41

2117 26.9 10.64

2173 29.4 10.88

2231 32.0 11.12

2292 34.6 11.36

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2263 20.7 11.37

2318 22.9 11.61

2375 25.2 11.86

2434 27.6 12.11

2495 30.1 12.36

2559 32.6 12.60

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

30

SS-PRC003-EN

Performance Data

Condensing Unit

Table PD-19 — Cooling Performance (MBh) TTA100B Condensing Unit Only OD Temp

(I-P)

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

172 93.8 7.46

178 103.2 7.69

184 113.0 7.90

191 123.2 8.11

198 133.8 8.32

205 144.7 8.52

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

197 88.4 8.00

203 97.4 8.27

210 106.7 8.54

217 116.4 8.79

224 126.5 9.05

232 136.9 9.31

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

224 82.8 8.50

231 91.3 8.82

238 100.2 9.13

246 109.4 9.44

253 118.9 9.75

261 128.8 10.07

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

254 77.0 8.94

261 85.0 9.31

268 93.4 9.68

276 102.1 10.05

284 111.1 10.43

293 120.4 10.81

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

285 71.0 9.32

293 78.5 9.76

301 86.4 10.19

309 94.6 10.63

317 103.1 11.07

326 111.8 11.52

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

319 64.9 9.66

327 72.0 10.16

335 79.3 10.66

344 87.0 11.17

353 94.9 11.68

362 103.1 12.21

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-19 — Cooling Performance (kW) TTA100B Condensing Unit Only OD Temp

(SI)

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1186 27.5 7.46

1227 30.2 7.69

1270 33.1 7.90

1315 36.1 8.11

1362 39.2 8.32

1412 42.4 8.52

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1359 25.9 8.00

1403 28.5 8.27

1449 31.3 8.54

1497 34.1 8.79

1547 37.0 9.05

1600 40.1 9.31

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1546 24.2 8.50

1593 26.7 8.82

1642 29.3 9.13

1693 32.0 9.44

1746 34.8 9.75

1802 37.7 10.07

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1749 22.5 8.94

1799 24.9 9.31

1850 27.3 9.68

1904 29.9 10.05

1960 32.5 10.43

2019 35.2 10.81

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1967 20.8 9.32

2019 23.0 9.76

2073 25.3 10.19

2130 27.7 10.63

2188 30.2 11.07

2249 32.7 11.52

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2200 19.0 9.66

2255 21.1 10.16

2312 23.2 10.66

2371 25.5 11.17

2431 27.8 11.68

2494 30.2 12.21

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

SS-PRC003-EN

31

Performance Data

Condensing Unit

Table PD-20 — Gross Cooling Capacities (MBh) - Both Compressors - (I-P) TTA100C Condensing Unit Only ODTemp

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

147.0 95.6 5.6

152.8 105.6 5.8

158.9 116.2 5.9

165.3 127.2 6.1

172.1 138.7 6.3

179.4 150.7 6.4

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

169.9 90.8 6.2

175.8 100.4 6.3

182.2 110.4 6.5

188.9 121.0 6.7

196.0 132.1 6.8

203.6 143.6 7.0

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

195.0 85.7 6.8

201.2 94.8 7.0

207.8 104.5 7.2

214.9 114.6 7.3

222.3 125.2 7.5

230.3 136.3 7.7

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

222.5 80.4 7.6

229.0 89.1 7.8

236.0 98.3 7.9

243.4 108.0 8.1

251.2 118.2 8.3

259.5 128.8 8.5

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

252.5 74.8 8.5

259.3 83.1 8.6

266.6 92.0 8.8

274.4 101.3 9.0

282.6 111.1 9.2

291.3 121.3 9.4

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

284.9 69.0 9.4

292.1 77.0 9.6

299.8 85.5 9.8

307.9 94.5 10.0

316.6 103.8 10.2

325.7 113.6 10.4

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-20 — Gross Cooling Capacities (kW) - Both Compressors - (SI) TTA100C Condensing Unit Only ODTemp

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1014 28.0 5.59

1054 30.9 5.76

1095 34.0 5.93

1140 37.2 6.09

1187 40.6 6.27

1237 44.1 6.45

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1171 26.6 6.17

1212 29.4 6.33

1256 32.3 6.50

1302 35.4 6.67

1351 38.7 6.85

1404 42.0 7.04

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1345 25.1 6.85

1388 27.8 7.00

1433 30.6 7.17

1482 33.6 7.35

1533 36.7 7.53

1588 39.9 7.74

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1534 23.5 7.62

1579 26.1 7.78

1627 28.8 7.95

1678 31.6 8.13

1732 34.6 8.32

1789 37.7 8.53

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1741 21.9 8.49

1788 24.3 8.65

1838 26.9 8.82

1892 29.7 9.01

1949 32.5 9.22

2009 35.5 9.43

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1964 20.2 9.44

2014 22.5 9.61

2067 25.0 9.79

2123 27.7 9.99

2183 30.4 10.20

2246 33.3 10.43

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

32

SS-PRC003-EN

Performance Data

Condensing Unit

Table PD-21 — Gross Cooling Capacities (MBh) - Single Compressor - (I-P) TTA100C Condensing Unit Only OD Temp

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

119.4 52.0 2.9

122.4 58.0 3.0

125.5 64.3 3.1

128.8 70.8 3.1

132.2 77.6 3.2

135.8 84.7 3.2

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

140.4 49.6 3.2

143.6 55.3 3.2

146.8 61.3 3.3

150.3 67.6 3.3

153.9 74.1 3.4

157.6 80.9 3.4

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

163.7 47.1 3.4

167.0 52.4 3.5

170.5 58.1 3.5

174.1 64.1 3.6

177.9 70.4 3.6

181.9 77.0 3.7

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

189.5 44.3 3.8

192.9 49.4 3.8

196.5 54.8 3.9

200.4 60.5 3.9

204.4 66.6 4.0

208.7 72.9 4.0

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

217.7 41.4 4.2

221.3 46.2 4.2

225.2 51.4 4.2

229.2 56.8 4.3

233.5 62.6 4.3

238.0 68.7 4.4

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

248.5 38.3 4.6

252.4 42.9 4.6

256.4 47.8 4.7

260.7 53.0 4.7

265.3 58.5 4.8

270.0 64.3 4.8

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-21 — Gross Cooling Capacities (kW) - Single Compressor - (SI) TTA100C Condensing Unit Only OD Temp

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

823 15.2 2.95

844 17.0 3.01

866 18.8 3.06

888 20.7 3.12

912 22.7 3.17

936 24.8 3.21

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

968 14.5 3.17

990 16.2 3.22

1012 18.0 3.27

1036 19.8 3.32

1061 21.7 3.37

1087 23.7 3.42

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1129 13.8 3.45

1151 15.3 3.49

1175 17.0 3.54

1200 18.8 3.59

1227 20.6 3.64

1254 22.5 3.69

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1306 13.0 3.78

1330 14.5 3.82

1355 16.0 3.86

1381 17.7 3.91

1409 19.5 3.96

1439 21.3 4.01

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1501 12.1 4.16

1526 13.5 4.20

1552 15.0 4.24

1580 16.6 4.29

1610 18.3 4.34

1641 20.1 4.39

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1714 11.2 4.60

1740 12.6 4.63

1768 14.0 4.67

1798 15.5 4.72

1829 17.1 4.77

1862 18.8 4.82

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

SS-PRC003-EN

33

Performance Data

Condensing Unit

Table PD-22 — Cooling Performance (MBh) TTA125B Condensing Unit Only ODTemp

(I-P)

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

169 115.6 8.89

174 127.1 9.17

180 139.1 9.43

186 151.6 9.70

193 164.5 9.96

199 177.9 10.23

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

194 109.1 9.43

200 120.1 9.77

206 131.6 10.10

212 143.5 10.43

219 155.9 10.76

227 168.6 11.10

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

221 102.5 9.98

227 112.9 10.37

234 123.9 10.77

241 135.2 11.17

248 146.9 11.58

256 159.0 11.99

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

250 95.7 10.52

257 105.6 10.98

264 115.9 11.45

272 126.6 11.92

280 137.7 12.41

288 149.1 12.90

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

282 88.7 11.06

290 98.1 11.59

297 107.8 12.14

305 117.8 12.69

313 128.2 13.25

321 138.9 13.83

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

317 81.7 11.59

324 90.4 12.21

332 99.5 12.83

340 108.9 13.47

349 118.6 14.11

358 128.6 14.78

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-22 — Cooling Performance (kW) TTA125B Condensing Unit Only ODTemp

(SI)

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1163 33.9 8.89

1201 37.2 9.17

1241 40.7 9.43

1283 44.4 9.70

1327 48.2 9.96

1374 52.1 10.23

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1335 32.0 9.43

1377 35.2 9.77

1420 38.5 10.10

1465 42.0 10.43

1512 45.6 10.76

1562 49.4 11.10

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1523 30.0 9.98

1568 33.1 10.37

1614 36.3 10.77

1662 39.6 11.17

1712 43.0 11.58

1765 46.6 11.99

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1727 28.0 10.52

1774 30.9 10.98

1823 33.9 11.45

1874 37.1 11.92

1928 40.3 12.41

1983 43.7 12.90

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1947 26.0 11.06

1997 28.7 11.59

2049 31.6 12.14

2103 34.5 12.69

2159 37.5 13.25

2217 40.7 13.83

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2185 23.9 11.59

2237 26.5 12.21

2291 29.1 12.83

2347 31.9 13.47

2405 34.7 14.11

2465 37.7 14.78

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

34

SS-PRC003-EN

Performance Data

Condensing Unit

Table PD-23 — Cooling Performance (MBh) TTA155B Condensing Unit Only OD Temp

(I-P)

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

173 140.3 9.95

179 154.9 10.20

186 170.1 10.48

194 185.9 10.78

201 202.2 11.10

209 218.8 11.43

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

200 136.0 11.00

206 150.0 11.28

214 164.4 11.58

221 179.3 11.90

229 194.6 12.23

238 210.3 12.58

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

228 130.4 12.22

236 143.6 12.52

243 157.3 12.84

251 171.4 13.17

259 185.9 13.51

268 200.7 13.87

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

259 123.6 13.60

267 136.1 13.92

275 149.0 14.24

283 162.4 14.58

292 176.1 14.92

301 190.2 15.29

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

293 115.9 15.15

301 127.6 15.46

309 139.8 15.78

317 152.3 16.11

326 165.3 16.46

336 178.8 16.84

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

328 107.4 16.84

336 118.3 17.13

345 129.7 17.44

354 141.5 17.77

363 153.9 18.12

373 166.8 18.50

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-23 — Cooling Performance (kW) TTA155B Condensing Unit Only OD Temp

(SI)

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1192 41.1 9.95

1238 45.4 10.20

1285 49.8 10.48

1336 54.4 10.78

1389 59.2 11.10

1444 64.1 11.43

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1376 39.8 11.00

1424 43.9 11.28

1474 48.1 11.58

1526 52.5 11.90

1581 57.0 12.23

1638 61.6 12.58

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1575 38.2 12.22

1625 42.1 12.52

1677 46.1 12.84

1732 50.2 13.17

1788 54.4 13.51

1848 58.8 13.87

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1789 36.2 13.60

1841 39.9 13.92

1896 43.6 14.24

1952 47.5 14.58

2012 51.6 14.92

2073 55.7 15.29

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2018 33.9 15.15

2073 37.4 15.46

2130 40.9 15.78

2188 44.6 16.11

2250 48.4 16.46

2315 52.4 16.84

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2263 31.4 16.84

2320 34.6 17.13

2379 38.0 17.44

2440 41.4 17.77

2504 45.1 18.12

2571 48.8 18.50

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

SS-PRC003-EN

35

Performance Data

Condensing Unit

Table PD-24 — Gross Cooling Capacities (MBh) - Both Compressors - (I-P) TTA155C Condensing Unit Only OD Temp

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press. PSIG Cap. Btuh/1000 OD Unit KW

164.9 132.3 9.3

170.4 146.2 9.5

176.3 160.9 9.7

182.6 176.2 10.0

189.2 192.1 10.2

196.0 208.5 10.5

75

Head press. PSIG Cap. Btuh/1000 OD Unit KW

191.3 128.5 10.3

197.3 142.0 10.5

203.6 156.0 10.7

210.3 170.6 11.0

217.2 185.6 11.3

224.4 201.0 11.6

85

Head press. PSIG Cap. Btuh/1000 OD Unit KW

220.1 123.5 11.4

226.5 136.4 11.7

233.2 149.7 11.9

240.2 163.5 12.2

247.4 177.7 12.5

255.0 192.3 12.8

95

Head press. PSIG Cap. Btuh/1000 OD Unit KW

251.1 117.4 12.7

257.9 129.6 13.0

265.0 142.2 13.3

272.4 155.3 13.6

280.0 168.7 13.9

287.9 182.6 14.2

105

Head press. PSIG Cap. Btuh/1000 OD Unit KW

284.5 110.4 14.2

291.7 121.9 14.5

299.1 133.8 14.8

306.8 146.1 15.0

314.8 158.8 15.3

323.2 172.0 15.7

115

Head press. PSIG Cap. Btuh/1000 OD Unit KW

320.2 102.7 15.8

327.7 113.4 16.1

335.4 124.5 16.4

343.4 136.1 16.6

351.8 148.1 16.9

360.6 160.7 17.3

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-24 — Gross Cooling Capacities (kW) - Both Compressors - (SI) TTA155C Condensing Unit Only ODTemp

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1137 38.7 9.30

1175 42.8 9.50

1216 47.1 9.72

1259 51.6 9.96

1304 56.2 10.22

1352 61.0 10.49

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1319 37.6 10.27

1361 41.6 10.50

1404 45.7 10.75

1450 49.9 11.01

1497 54.3 11.29

1547 58.9 11.58

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1517 36.2 11.41

1562 39.9 11.67

1608 43.8 11.94

1656 47.9 12.22

1706 52.0 12.51

1758 56.3 12.81

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1731 34.4 12.73

1778 38.0 13.00

1827 41.6 13.28

1878 45.5 13.56

1930 49.4 13.86

1985 53.5 14.17

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1962 32.3 14.21

2011 35.7 14.48

2062 39.2 14.76

2115 42.8 15.04

2170 46.5 15.34

2228 50.4 15.66

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2208 30.1 15.84

2259 33.2 16.10

2313 36.5 16.36

2368 39.8 16.64

2426 43.4 16.94

2487 47.1 17.26

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

36

SS-PRC003-EN

Performance Data

Condensing Unit

Table PD-25 — Cooling Performance (MBh) - Single Compressor - (I-P) TTA155C Condensing Unit Only ODTemp

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press. PSIG Cap. Btuh/1000 OD Unit KW

137.1 67.8 4.8

139.8 75.1 4.8

142.6 82.9 4.8

145.7 91.3 4.9

149.0 100.1 5.0

152.4 109.4 5.0

75

Head press. PSIG Cap. Btuh/1000 OD Unit KW

161.2 66.9 5.1

164.2 74.1 5.2

167.3 81.7 5.3

170.6 89.7 5.3

174.1 98.1 5.4

177.7 106.9 5.5

85

Head press. PSIG Cap. Btuh/1000 OD Unit KW

187.7 65.1 5.6

191.0 72.1 5.7

194.3 79.5 5.7

197.9 87.2 5.8

201.6 95.2 5.9

205.4 103.5 6.0

95

Head press. PSIG Cap. Btuh/1000 OD Unit KW

216.7 62.6 6.2

220.2 69.4 6.3

223.9 76.5 6.3

227.7 83.8 6.4

231.6 91.5 6.5

235.6 99.4 6.6

105

Head press. PSIG Cap. Btuh/1000 OD Unit KW

248.3 59.5 6.9

252.0 65.9 6.9

255.9 72.7 7.0

260.0 79.7 7.1

264.1 87.1 7.1

268.5 94.7 7.2

115

Head press. PSIG Cap. Btuh/1000 OD Unit KW

282.5 55.8 7.6

286.5 61.9 7.7

290.6 68.3 7.7

294.9 75.0 7.8

299.3 82.0 7.9

303.9 89.3 8.0

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-25 — Cooling Performance (kW) - Single Compressor - (SI) TTA155C Condensing Unit Only ODTemp

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

945 19.9 4.76

964 22.0 4.80

983 24.3 4.85

1005 26.7 4.91

1027 29.3 4.97

1051 32.0 5.04

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1112 19.6 5.14

1132 21.7 5.19

1154 23.9 5.25

1176 26.3 5.32

1200 28.7 5.39

1225 31.3 5.47

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1294 19.1 5.62

1317 21.1 5.68

1340 23.3 5.75

1364 25.5 5.82

1390 27.9 5.90

1416 30.3 5.98

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1494 18.3 6.19

1518 20.3 6.26

1544 22.4 6.33

1570 24.5 6.41

1597 26.8 6.48

1625 29.1 6.57

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1712 17.4 6.85

1738 19.3 6.92

1765 21.3 6.99

1792 23.3 7.07

1821 25.5 7.15

1851 27.7 7.23

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1948 16.3 7.61

1975 18.1 7.67

2004 20.0 7.74

2033 22.0 7.81

2064 24.0 7.89

2096 26.2 7.97

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

SS-PRC003-EN

37

Performance Data

Condensing Unit

Table PD-26 — Cooling Capacities (MBh) TTA200B Condensing Unit Only ODTemp

(I-P)

Suction Reference Temperature °F

°F

30

35

40

45

50

55

65

Head press PSIG Cap. Btuh/1000 OD Unit KW

181 188.3 12.97

187 206.3 13.31

194 225.0 13.66

201 244.3 14.04

208 264.3 14.45

216 285.0 14.88

75

Head press PSIG Cap. Btuh/1000 OD Unit KW

207 179.3 14.39

214 196.2 14.76

221 213.9 15.15

229 232.4 15.57

237 251.6 16.02

245 271.4 16.48

85

Head press PSIG Cap. Btuh/1000 OD Unit KW

236 169.7 16.07

244 185.9 16.47

251 202.8 16.90

259 220.4 17.36

267 238.8 17.83

276 257.7 18.32

95

Head press PSIG Cap. Btuh/1000 OD Unit KW

268 159.7 17.98

276 175.2 18.43

284 191.4 18.90

292 208.4 19.39

301 225.9 19.89

310 244.0 20.40

105

Head press PSIG Cap. Btuh/1000 OD Unit KW

302 149.2 20.13

311 164.2 20.63

319 179.9 21.14

328 196.2 21.67

338 213.1 22.19

347 230.3 22.70

115

Head press PSIG Cap. Btuh/1000 OD Unit KW

339 138.4 22.50

348 153.0 23.06

358 168.3 23.62

367 184.0 24.18

377 200.1 24.72

387 216.5 25.23

Performance Data Calculated at 15 deg. subcooling and 15 deg. superheat.

Table PD-26 — Cooling Capacities (MBh) TTA200B Condensing Unit Only ODTemp

(SI)

Suction Reference Temperature °C

°C

-1.1

1.7

4.4

7.2

10.0

12.8

18.3

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1248 55.1 12.97

1292 60.4 13.31

1338 65.9 13.66

1387 71.5 14.04

1437 77.4 14.45

1491 83.4 14.88

23.9

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1430 52.5 14.39

1476 57.4 14.76

1525 62.6 15.15

1577 68.0 15.57

1631 73.7 16.02

1688 79.5 16.48

29.4

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1630 49.7 16.07

1680 54.4 16.47

1732 59.4 16.90

1787 64.5 17.36

1844 69.9 17.83

1904 75.4 18.32

35.0

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

1848 46.7 17.98

1901 51.3 18.43

1957 56.1 18.90

2015 61.0 19.39

2076 66.2 19.89

2139 71.4 20.40

40.6

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2085 43.7 20.13

2142 48.1 20.63

2202 52.7 21.14

2264 57.5 21.67

2329 62.4 22.19

2395 67.4 22.70

46.1

Head pressure (kPA) Capacity (kW) OD Unit Power (kW)

2340 40.5 22.50

2402 44.8 23.06

2467 49.3 23.62

2533 53.9 24.18

2602 58.6 24.72

2671 63.4 25.23

Performance Data Calculated at 8.3 deg. subcooling and 8.3 deg. superheat.

38

SS-PRC003-EN

Performance Data

Air Handler

Table PD-27— Evaporator Fan Performance — TWE050A (I-P) External Static Pressure (Inches of Water Column) CFM

.10" .20" .30" .40" .50" .60" .70" .80" .90" 1.00" 1.10" RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1400 1500 1600 1700 1800 1900 2000 2100

— — — 601 625 642 659 674

— — — 646 0.37 698 — 607 0.36 661 0.40 713 — 625 0.38 676 0.43 727 0.35 648 0.40 696 0.44 744 0.36 671 0.41 716 0.46 762 0.40 687 0.45 731 0.50 776 0.44 703 0.49 745 0.54 790 0.48 722 0.54 770 0.60 817 0.75 HP Standard Motor and Standard Static Drive

0.42 0.45 0.48 0.49 0.51 0.55 0.60 0.65

751 764 778 792 807 820 833 857

0.47 0.50 0.52 0.54 0.56 0.60 0.65 0.70

803 816 828 841 853 865 877 897

0.52 856 0.56 908 0.61 941 0.54 867 0.59 919 0.64 952 0.57 879 0.62 930 0.67 963 0.59 889 0.64 937 0.69 971 0.61 898 0.66 944 0.71 979 0.66 909 0.71 951 0.75 987 0.70 920 0.75 957 0.80 994 0.75 936 0.80 973 0.85 1009 1.0 HP Oversized Motor and High Static Drive

0.65 0.67 0.70 0.73 0.76 0.80 0.84 0.89

973 984 995 1005 — — — —

0.68 1006 0.71 0.71 — — 0.74 — — 0.77 — — — — — — — — — — — — — —

Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-27— Evaporator Fan Performance — TWE050A (SI) External Static Pressure (Pascal) m3/hr

25 50 75 100 125 150 174 199 224 249 274 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

2379 2549 2718 2888 3058 3228 3398 3568

— — — 601 625 642 659 674

— — — 646 0.28 698 — 607 0.27 661 0.30 713 — 625 0.28 676 0.32 727 0.26 648 0.30 696 0.33 744 0.27 671 0.31 716 0.34 762 0.30 687 0.34 731 0.37 776 0.33 703 0.37 745 0.40 790 0.36 722 0.40 770 0.45 817 0.56 kW Standard Motor and Standard Static Drive

0.31 0.34 0.36 0.37 0.38 0.41 0.45 0.48

751 764 778 792 807 820 833 857

0.35 0.37 0.39 0.40 0.42 0.45 0.48 0.52

803 816 828 841 853 865 877 897

0.39 856 0.42 908 0.45 941 0.40 867 0.44 919 0.48 952 0.43 879 0.46 930 0.50 963 0.44 889 0.48 937 0.51 971 0.45 898 0.49 944 0.53 979 0.49 909 0.53 951 0.56 987 0.52 920 0.56 957 0.60 994 0.56 936 0.60 973 0.63 1009 0.75 kW Oversized Motor and High Static Drive

0.48 0.50 0.52 0.54 0.57 0.60 0.63 0.66

973 984 995 1005 — — — —

0.51 1006 0.53 0.53 — — 0.55 — — 0.57 — — — — — — — — — — — — — —

Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-28 — Blower Speeds — TWE050A Drive Standard High Static

SS-PRC003-EN

6

5

N/A N/A

590 713

Motor DriveTurns Open 4 3 2 639 772

688 832

737 891

1

0

786 951

835 1009

39

Performance Data

Air Handler

Table PD-29— Evaporator Fan Performance TWE075A (I-P) External Static Pressure (In. Of Water Column) 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

CFM 2000 2125 2250 2375 2500 2625 2750 2875 3000

— — 443 0.44 489 — — 453 0.46 499 — — 463 0.49 510 — — 473 0.51 520 445 0.47 489 0.54 533 464 0.50 506 0.57 548 484 0.53 523 0.59 562 504 0.56 540 0.62 576 524 0.59 557 0.65 590 1.0 HP Standard Motor and Low Static Drive

0.49 0.52 0.55 0.57 0.60 0.63 0.66 0.68 0.71

535 546 556 567 578 589 601 612 624

0.54 0.57 0.61 0.64 0.67 0.69 0.72 0.74 0.77

581 592 602 613 622 631 640 648 657

0.59 627 0.64 673 0.69 0.63 638 0.68 684 0.74 0.67 649 0.73 695 0.79 0.70 660 0.77 706 0.83 0.73 667 0.80 711 0.86 0.76 672 0.82 714 0.88 0.78 678 0.84 717 0.91 0.81 684 0.87 720 0.93 0.83 690 0.89 723 0.95 1.0 HP Standard Motor and Drive

Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

719 730 742 753 756 757 758 759 760

0.74 0.79 0.85 0.90 0.93 0.95 0.97 0.99 1.01

765 0.79 791 0.83 818 0.89 771 0.85 798 0.90 825 0.96 776 0.91 804 0.97 831 1.03 782 0.97 810 1.03 838 1.10 784 0.99 813 1.07 842 1.14 786 1.01 815 1.09 844 1.17 787 1.03 817 1.12 847 1.21 789 1.05 819 1.15 850 1.24 790 1.07 821 1.17 853 1.27 1.5 HP Oversized Motor and High Static Drive

Table PD-29 — Continued External Static Pressure (In. Of Water Column) CFM 2000 2125 2250 2375 2500 2625 2750 2875 3000

1.20 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 844 0.96 871 1.02 897 1.09 852 1.03 879 1.09 906 1.16 859 1.10 886 1.17 914 1.23 866 1.17 894 1.24 922 1.30 870 1.21 899 1.29 928 1.36 874 1.25 903 1.33 932 1.42 877 1.29 907 1.38 937 1.47 880 1.33 911 1.43 942 1.52 884 1.37 915 1.48 946 1.58 1.5 HP Oversized Motor and High Static Drive

924 933 942 950 — — — — —

1.15 950 1.21 1.22 — — 1.30 — — 1.37 — — — — — — — — — — — — — — — — —

1.0 HP Standard Motor and Drive

Table PD-29 — Evaporator Fan Performance TWE075A (SI) External Static Pressure (Pascal) m3/hr 3338 3547 3755 3964 4173 4381 4590 4798 5007

25 50 75 100 125 150 174 199 224 249 274 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW — — 443 0.33 489 0.37 — — 453 0.34 499 0.39 — — 463 0.37 510 0.41 — — 473 0.38 520 0.43 445 0.35 489 0.4 533 0.45 464 0.37 506 0.43 548 0.47 484 0.4 523 0.44 562 0.49 504 0.42 540 0.46 576 0.51 524 0.44 557 0.48 590 0.53 .75 kW Standard Motor and Low Static Drive

535 546 556 567 578 589 601 612 624

0.4 0.43 0.45 0.48 0.5 0.51 0.54 0.55 0.57

Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-30 — Blower Speeds — TWE075A Motor Drive Turns Open Drive Standard Low Static High Static

6

5

4

3

2

1

0

N/A N/A N/A

600 428 700

650 464 750

700 499 800

750 535 850

800 571 900

850 606 950

581 592 602 613 622 631 640 648 657

0.44 627 0.48 673 0.51 0.47 638 0.51 684 0.55 0.5 649 0.54 695 0.59 0.52 660 0.57 706 0.62 0.54 667 0.6 711 0.64 0.57 672 0.61 714 0.66 0.58 678 0.63 717 0.68 0.6 684 0.65 720 0.69 0.62 690 0.66 723 0.71 .75 kW Standard Motor and Drive

719 730 742 753 756 757 758 759 760

0.55 0.59 0.63 0.67 0.69 0.71 0.72 0.74 0.75

765 0.59 791 0.62 818 0.66 771 0.63 798 0.67 825 0.72 776 0.68 804 0.72 831 0.77 782 0.72 810 0.77 838 0.82 784 0.74 813 0.8 842 0.85 786 0.75 815 0.81 844 0.87 787 0.77 817 0.84 847 0.9 789 0.78 819 0.86 850 0.92 790 0.8 821 0.87 853 0.95 1.12 kW Oversized Motor and High Static Drive

Table PD-29 — Continued External Static Pressure (Pascal) m3/hr

299 324 349 374 398 RPM kW RPM kW RPM kW RPM kW RPM kW

3338 844 0.72 871 0.76 897 0.81 924 0.86 950 3547 852 0.77 879 0.81 906 0.87 933 0.91 — 3755 859 0.82 886 0.87 914 0.92 942 0.97 — 3964 866 0.87 894 0.92 922 0.97 950 1.02 — 4173 870 0.9 899 0.96 928 1.01 — — — 4381 874 0.93 903 0.99 932 1.06 — — — 4590 877 0.96 907 1.03 937 1.1 — — — 4798 880 0.99 911 1.07 942 1.13 — — — 5007 884 1.02 915 1.1 946 1.18 — — — 1.12 kW Oversized Motor and High Static Drive

0.9 — — — — — — — —

.75 kW Standard Motor and Drive

40

SS-PRC003-EN

Performance Data

Air Handler

Table PD-31 — Evaporator Fan Performance TWE100A,TWE100B (I-P) External Static Pressure (In. Of Water Column) CFM

0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.20 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP Standard Motor and Low Static Drive 2600 460 0.32 493 0.39 527 0.47 565 0.55 603 0.63 641 0.71 2775 473 0.37 506 0.45 540 0.53 576 0.61 613 0.69 649 0.77 2950 487 0.43 519 0.50 552 0.58 587 0.67 623 0.75 658 0.83 3125 501 0.49 532 0.56 565 0.64 599 0.72 632 0.81 666 0.89 3300 520 0.58 548 0.65 581 0.73 613 0.81 644 0.89 677 0.98 3475 541 0.69 568 0.76 600 0.84 631 0.93 658 1.00 691 1.08 3650 562 0.82 588 0.88 618 0.97 648 1.05 671 1.11 703 1.19 3825 582 0.96 608 1.03 637 1.11 666 1.20 685 1.26 711 1.31 4000 602 1.11 628 1.17 656 1.26 683 1.35 698 1.40 720 1.43 1.5 HP Standard Motor and

679 0.79 686 0.85 693 0.91 700 0.97 710 1.06 721 1.16 732 1.27 739 1.38 747 1.50 Drive

Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. 4. Low Static Drive must be field supplied.

717 723 728 734 740 746 753 763 773

0.87 0.93 0.99 1.05 1.13 1.21 1.31 1.44 1.58

744 748 751 755 759 764 772 787 801

0.94 772 1.01 826 1.16 1.00 775 1.07 830 1.20 1.06 779 1.12 833 1.25 1.11 783 1.18 737 1.30 1.19 787 1.25 841 1.37 1.28 793 1.34 846 1.48 1.38 801 1.45 853 1.59 1.51 815 1.58 862 1.74 1.64 829 1.71 872 1.89 2.0 HP Oversized Motor and High Static Drive

Table PD-31— Continued External Static Pressure (In. Of Water Column) CFM

1.40 1.60 RPM BHP RPM BHP

2.0 HP Oversized Motor and High Static Drive 2600 881 1.30 936 1.45 2775 884 1.36 938 1.51 2960 886 1.41 939 1.57 3125 889 1.47 941 1.64 3300 892 1.54 945 1.73 3475 897 1.63 950 1.85 3650 902 1.73 955 1.99 3825 912 1.89 960 2.18 4000 922 2.04 965 2.30

Table PD-31— Evaporator Fan Performance TWE0100A,TWE100B (SI) External Static Pressure (Pascal) m3/hr

25 50 75 100 125 150 174 199 224 249 299 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

1.12 kW Standard Motor and Low Static Drive 4417 460 0.24 493 0.29 527 0.35 565 0.41 603 0.47 641 0.53 679 4715 473 0.28 506 0.34 540 0.4 576 0.45 613 0.51 649 0.57 686 5012 487 0.32 519 0.37 552 0.43 587 0.5 623 0.56 658 0.62 693 5309 501 0.37 532 0.42 565 0.48 599 0.54 632 0.6 666 0.66 700 5607 520 0.43 548 0.48 581 0.54 613 0.6 644 0.66 677 0.73 710 5904 541 0.51 568 0.57 600 0.63 631 0.69 658 0.75 691 0.8 721 6201 562 0.61 588 0.66 618 0.72 648 0.78 671 0.83 703 0.89 732 6499 582 0.72 608 0.77 637 0.83 666 0.89 685 0.94 711 0.98 739 6796 602 0.83 628 0.87 656 0.94 683 1.01 698 1.04 720 1.07 747 1.12 kW Standard Motor and Drive Notes: 1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 3.0 turns open. Adjustments are made in 0.5 turn increments. 4. Low Static Drive must be field supplied.

Table PD-32 — Blower Speeds — TWE100A, TWE100B Motor Sheave Turns Open Drive Standard Low Static High Static High Static II

6

5

4

3

2

1

0

N/A N/A N/A N/A

587 453 606 745

629 485 641 789

671 518 677 833

713 550 713 877

755 583 748 920

796 615 784 965

SS-PRC003-EN

0.59 0.63 0.68 0.72 0.79 0.87 0.95 1.03 1.12

717 723 728 734 740 746 753 763 773

0.65 0.69 0.74 0.78 0.84 0.9 0.98 1.07 1.18

744 0.7 772 0.75 826 0.87 748 0.75 775 0.8 830 0.89 751 0.79 779 0.84 833 0.93 755 0.83 783 0.88 737 0.97 759 0.89 787 0.93 841 1.02 764 0.95 793 1 846 1.1 772 1.03 801 1.08 853 1.19 787 1.13 815 1.18 862 1.3 801 1.22 829 1.28 872 1.41 1.49 kW Oversized Motor and High Static Drive

Table PD-31— Continued External Static Pressure (Pascal) m3/hr

349 398 RPM kW RPM kW

1.49 kW Oversized Motor and High Static Drive 881 0.97 936 1.08 884 1.01 938 1.13 886 1.05 939 1.17 889 1.1 941 1.22 892 1.15 945 1.29 897 1.22 950 1.38 902 1.29 955 1.48 912 1.41 960 1.63 922 1.52 965 1.72

4417 4715 5012 5309 5607 5904 6201 6499 6796

41

Performance Data

Air Handler

Table PD-33 — Evaporator Fan Performance — TWE155B (I-P) External Static Pressure (Inches of Water Column) CFM

4000 4250 4500 4750 5000 5260 5500 5750 6000

.10" .20" .30" .40" .50" .60" .70" .80" .90" 1.00" 1.20" 1.40" RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

628 633 637 641 645 650 652 653 655

1.34 1.37 1.40 1.42 1.44 1.46 1.47 1.48 1.49

653 658 662 666 670 675 678 680 681

1.38 1.41 1.44 1.50 1.52 1.53 1.55 1.57 1.59

2.0 678 683 687 691 695 700 703 706 709

HP Standard Motor 1.43 692 1.48 708 1.46 697 1.51 713 1.49 701 1.53 717 1.53 705 1.61 721 1.56 710 1.65 725 1.59 716 1.67 728 1.63 721 1.71 734 1.68 726 1.76 743 1.74 731 1.80 752

and 1.52 1.55 1.58 1.63 1.67 1.70 1.75 1.81 1.87

Drive 723 1.57 728 1.60 732 1.63 736 1.65 739 1.68 741 1.73 747 1.78 761 1.86 774 1.94

738 743 747 751 758 765 775 789 803

1.60 1.62 1.64 1.66 1.70 1.75 1.83 1.94 2.05

749 751 754 765 777 790 804 817 831

1.61 1.63 1.65 1.67 1.74 1.82 1.92 2.04 2.17

759 770 782 793 806 819 832 846 860

1.62 1.64 1.67 1.72 1.81 1.92 2.03 2.16 2.29

3.0 HP Oversized Motor and High Static Drive 795 1.66 851 1.85 907 2.03 806 1.71 862 1.90 918 2.11 817 1.76 873 1.96 929 2.19 828 1.81 884 2.01 940 2.27 839 1.91 896 2.13 — — 849 2.03 907 2.28 — — 861 2.15 920 2.44 — — 875 2.29 935 2.61 — — 889 2.44 950 2.78 — —

Notes: 1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-33 — Evaporator Fan Performance TWE155B (SI) External Static Pressure (Pascal) m3/hr

6796 7221 7646 8070 8495 8937 9345 9769 10194

25 50 75 100 125 150 174 199 224 249 299 349 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

628 633 637 641 645 650 652 653 655

1 1.02 1.04 1.06 1.07 1.09 1.1 1.1 1.11

653 658 662 666 670 675 678 680 681

1.03 1.05 1.07 1.12 1.13 1.14 1.16 1.17 1.19

1.49 kW Standard Motor and Drive 678 1.07 692 1.1 708 1.13 723 1.17 683 1.09 697 1.13 713 1.16 728 1.19 687 1.11 701 1.14 717 1.18 732 1.22 691 1.14 705 1.2 721 1.22 736 1.23 695 1.16 710 1.23 725 1.25 739 1.25 700 1.19 716 1.25 728 1.27 741 1.29 703 1.22 721 1.28 734 1.3 747 1.33 706 1.25 726 1.31 743 1.3 761 1.39 709 1.3 731 1.34 752 1.35 774 1.45

738 743 747 751 758 765 775 789 803

1.19 1.21 1.23 1.24 1.27 1.3 1.36 1.45 1.53

749 751 754 765 777 790 804 817 831

1.2 1.22 1.23 1.25 1.3 1.36 1.43 1.52 1.62

759 770 782 793 806 819 832 846 860

1.21 1.22 1.25 1.28 1.35 1.43 1.51 1.61 1.71

2.24 kW Oversized Motor and High Static Drive 795 1.24 851 1.38 907 1.51 806 1.28 862 1.42 918 1.57 817 1.31 873 1.46 929 1.63 828 1.35 884 1.5 940 1.69 839 1.42 896 1.59 — — 849 1.51 907 1.7 — — 861 1.6 920 1.82 — — 875 1.71 935 1.95 — — 889 1.82 950 2.07 — —

Notes: 1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-34— Blower Speeds — TWE155B Motor Sheave Turns Open Drive Standard High Static

42

6

5

4

3

2

1

0

619 777

648 806

677 835

705 863

734 892

763 921

N/A 950

SS-PRC003-EN

Performance Data

Air Handler

Table PD-35 — Evaporator Fan Performance TWE200B (I-P) External Static Pressure (In. Of Water Column) CFM

0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.20 140 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

5200 — — 5525 — — 5850 — — 6175 473 0.99 6500 492 1.12 6825 510 1.25 7150 528 1.38 7475 550 1.61 7800 572 1.83 3.0 HP Standard Motor and Low Static Drive

461 0.74 503 0.91 545 479 0.88 521 1.04 563 497 1.01 539 1.18 581 515 1.15 557 1.31 599 534 1.28 576 1.45 618 552 1.42 594 1.59 636 570 1.56 612 1.73 654 594 1.77 640 1.92 683 618 1.97 668 2.10 712 3.0 HP Standard Motor and Low Static Drive System II

1.07 1.21 1.34 1.48 1.61 1.75 1.90 2.08 2.27

587 605 623 641 660 678 697 721 746

1.03 1.21 1.39 1.57 1.75 1.91 2.07 2.29 2.52

619 640 661 682 702 723 744 760 776

1.17 685 1.40 723 1.59 1.35 701 1.58 739 1.77 1.53 717 1.76 755 1.95 1.71 732 1.94 769 2.12 1.90 748 2.12 784 2.30 2.10 763 2.30 794 2.47 2.30 779 2.49 804 2.64 2.50 790 2.67 815 2.81 2.69 802 2.84 826 2.99 3.0 HP Standard Motor and Standard Drive System

Notes: 1. Performance based on a wet coil and 2 inch (51mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. 4. Low static drive components referencing this note are field supplied.

750 766 782 796 811 820 830 840 851

1.74 1.92 2.10 2.27 2.45 2.62 2.78 2.96 3.13

777 793 809 823 838 846 855 865 876

1.89 851 2.19 898 2.39 2.07 859 2.37 906 2.60 2.25 868 2.55 915 2.81 2.43 877 2.73 924 3.02 2.60 886 2.91 933 3.22 2.77 894 3.09 941 3.42 2.94 903 3.26 950 3.62 3.11 914 3.47 959 3.85 3.27 926 3.67 969 4.08 5.0 HP Oversized Motor and High Static Drive System

Table PD-35 — Continued External Static Pressure (In. Of Water Column) CFM

1.60 1.80 RPM BHP RPM BHP

5.0 HP Oversized Motor and High Static Drive System 5200 944 2.75 989 3.12 5525 952 2.96 997 3.33 5850 961 3.17 1006 3.54 5175 970 3.38 1015 3.75 8500 978 3.59 1023 3.96 8825 986 3.80 — — 7150 994 4.01 — — 7475 1003 4.25 — — 7800 1012 4.50 — —

Table PD-35 — Evaporator Fan Performance TWE200B (SI) External Static Pressure (Pascal) m3/hr

25 50 75 100 125 150 174 199 224 249 299 349 RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

8835 — — 461 0.55 503 0.68 545 0.8 9387 — — 479 0.66 521 0.78 563 0.9 9939 — — 497 0.75 539 0.88 581 1 10491 473 0.74 515 0.86 557 0.98 599 1.1 11044 492 0.84 534 0.95 576 1.08 618 1.2 11596 510 0.93 552 1.06 594 1.19 636 1.3 12148 528 1.03 570 1.16 612 1.29 654 1.42 12700 550 1.2 594 1.32 640 1.43 683 1.55 13252 572 1.36 618 1.47 668 1.57 712 1.69 2.24 kW Standard 2.24 kW Standard Motor and Low Motor and Low Static Drive System Static Drive System II

587 605 623 641 660 678 697 721 746

0.77 0.9 1.04 1.17 1.3 1.42 1.54 1.71 1.88

619 640 661 682 702 723 744 760 776

0.87 1.01 1.14 1.28 1.42 1.57 1.72 1.87 2.01

685 1.04 723 1.19 750 701 1.18 739 1.32 766 717 1.31 755 1.45 782 732 1.45 769 1.58 796 748 1.58 784 1.72 811 763 1.72 794 1.84 820 779 1.86 804 1.97 830 790 1.99 815 2.1 840 802 2.12 826 2.23 851 2.24 kW Standard Motor and Standard Drive System

Notes: 1. Performance based on a wet coil and 2 inch (51mm) throwaway filters. 2. Tabulated brake horsepower is the motor shaft output required. 3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments. 4. Low static drive components referencing this note are field supplied.

External Static Pressure (Pascal) m3/hr

Motor Sheave Turns Open Standard Low Static I Low Static II High Static SS-PRC003-EN

777 1.41 851 1.63 898 1.78 793 1.54 859 1.77 906 1.94 809 1.68 868 1.9 915 2.1 823 1.81 877 2.04 924 2.52 838 1.94 886 2.17 933 2.4 846 2.07 894 2.3 941 2.55 855 2.19 903 2.43 950 2.7 865 2.32 914 2.59 959 2.87 876 2.44 926 2.74 969 3.04 3.73 kW Oversized Motor and High Static Drive System

Table PD-35 — Continued

Table PD-36— Blower Speeds — TWE200B Drive

1.3 1.43 1.57 1.69 1.83 1.95 2.07 2.21 2.33

6

5

4

3

2

1

0

706 457 574 N/A

732 478 595 821

758 500 617 862

784 521 638 903

811 542 659 945

837 563 680 986

863 585 702 1027

398 448 RPM kW RPM kW

3.73 kW Oversized Motor and High Static Drive System 8835 944 2.05 989 2.33 9387 952 2.21 997 2.48 9939 961 2.36 1006 2.64 10491 970 2.52 1015 2.8 11044 978 2.68 1023 2.95 11596 986 2.83 — — 12148 994 2.99 — — 12700 1003 3.17 — — 13252 1012 3.36 — —

43

Performance Data

Table PD-37— Discharge Plenum And Grille Assembly Throw Distance (ft) — Air Handler Unit Model No.

m3/h 2380 2718 3060 3398 3737 3568 4079 4586 5098 5436 6116 6797 7477 8154 7304 8327 9176 10195 9515 10872 12233 13594

CFM 1400 1600 1800 2000 2200 2100 2400 2700 3000 3200 3600 4000 4400 4800 4300 4900 5400 6000 5600 6400 7200 8000

TWE050

TWE075

TWE100

TWE155

TWE200

Straight 38 (11.6) 42 (12.8) 46 (14.0) 48 (14.6) 51 (15.5) 49 (14.9) 52 (15.9) 55 (16.8) 58 (17.7) 56 (17.1) 62 (18.9) 66 (20.1) 71 (21.6) 76 (23.2) 42 (12.8) 47 (14.3) 52 (15.9) 57 (17.4) 50 (15.2) 56 (17.1) 62 (18.9) 66 (20.1)

Louver Angle Deflection Position 20, ft (m) 40, ft (m) 24 (7.3) 22 (6.7) 31 (9.4) 26 (7.9) 37 (11.3) 29 (8.8) 43 (13.1) 33 (10.1) 50 (15.2) 36 (11.0) 38 (11.6) 31 (9.4) 43 (13.1) 35 (10.7) 48 (14.6) 38 (11.6) 53 (16.2) 42 (12.8) 46 (14.0) 38 (11.6) 51 (15.5) 42 (12.8) 57 (17.4) 47 (14.3) 62 (18.9) 52 (15.9) 67 (20.4) 56 (17.1) 32 (9.8) 29 (8.8) 38 (11.6) 32 (9.8) 44 (13.4) 37 (11.3) 49 (14.9) 41 (12.5) 40 (12.2) 33 (10.1) 46 (14.0) 38 (11.6) 51 (15.5) 42 (12.8) 57 (17.4) 47 (14.3)

55, ft (m) 18 (5.5) 20 (6.1) 22 (6.7) 24 (7.3) 25 (7.6) 27 (8.2) 29 (8.8) 31 (9.4) 32 (9.8) 30 (9.1) 33 (10.1) 35 (10.7) 38 (11.6) 42 (12.8) 21 (6.4) 25 (7.6) 29 (8.8) 32 (9.8) 27 (8.2) 30 (9.1) 33 (10.1) 35 (10.7)

Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s). Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by throw factor: Terminal Velocity Throw Factor 50 fpm (.25 m/s) x 1.50 100 fpm (.51 m/s) x .75 150 fpm (.76 m/s) x .50

Table PD-38— Static Pressure Drop Through Accessories (Inches Of Water Column)1 — Air Handler Unit Model No. TWE050A

TWE075A TWE100A TWE100B TWE155B

TWE200B

CFM 1400 1600 2000 2100 2400 3000 2800 3200 4300 4800 6000 5600 6400 8000

3

m /h 2380 2718 3398 3568 4079 5098 4756 5436 7304 8154 10195 9515 10872 13594

Discharge Return Grille Plenum and Grille2 1 In. wc Pascal In. wc1 Pascal .09 (22.4) .16 (39.8) .12 (29.9) .21 (52.3) .18 (44.8) .33 (82.2) .05 (12.5) .19 (47.3) .08 (19.9) .27 (67.2) .13 (32.4) .40 (99.6) .04 (10.0) .34 (84.7) .07 (17.4) .43 (107.1) .07 (17.4) .18 (44.8) .09 (22.4) .23 (57.3) .15 (37.4) .34 (84.7) .07 (17.4) .32 (79.7) .11 (27.4) .43 (107.1) .17 (42.3) .66 (164.3)

5-10 .06 08 .13 .02 .03 .06 .03 .06 .02 .03 .06 .04 .06 .10

Electric Heaters (kW) 15-20 25-30 35-50 .06 .12 — .08 .14 — .13 .19 — .03 .05 .08 .06 .08 .12 .12 .17 .23 .04 .14 .20 .13 .19 .26 .02 .04 .05 .03 .06 .08 .06 .12 .17 .04 .10 .15 .0-6 .13 .19 .10 .20 .30

1. Return air filter ESP included in Fan Performance Table data. 2. At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installer’s Guide.

44

SS-PRC003-EN

Performance Data

Table PD-39 — Auxiliary Electric Heat Capacity — Air Handler Unit Model No. TWE050/075/100AD TWE100BD TWE075, 100AD TWE100BD TWE155,200B

Total kW 5.00 9.96 14.96 24.92

No. of Stages 1 1 1 2

34.88 10.00 19.92 29.92 49.84

2 1 1 2 2

Stage 1 kW Btu Input Output 5.00 17,065 9.96 33,993 14.96 51,058 14.96 51,058

Stage 2 kW Btu Input Output — — — — — — 9.96 33,993

kW Input 5.00 9.96 14.96 24.92

Btu Output 17,065 33,993 51,058 85,051

19.92 10.00 19.92 19.92 29.92

14.96 — — 10.00 19.92

34.88 10.00 19.92 29.92 49.84

119,045 34,130 67,987 102,117 170,104

*Heaters are rated at 400v. For other than rated voltage, 2 Voltage Capacity = x Rated Capacity and kW = Rated Voltage

(

SS-PRC003-EN

)

67,987 34,130 67,987 67,987 102,117

Voltage ( Rated Voltage )

2

51,058 — — 34,130 67,987

Total

Rated kW.

45

Electrical Data

Table ED-1 — Unit Wiring — Condensing Units Unit Model No.

Unit Operating Voltage

Minimum Circuit Ampacity

Maximum Fuse Size or Maximum Circuit Breaker

TTA075A TTA085A TTA100A TTA100B TTA125B TTA155B TTA155C TTA200B

380/415 380/415 380/415 380/415 380/415 380/415 380/415 380/415

15.5 17.8 21.5 26.3 27.4 28.3 35.1 39.3

25 25 35 35 35 35 45 50

Table ED-2 — Electrical Characteristics — Motors — Condensing Units Compressor Motor

Condenser Fan Motor Amps

Unit Model No. TTA075A TTA085A TTA100A TTA100B TTA125B TTA155B TTA155C TTA200B

No. 1 1 1 2 2 2 1 2

RLA (Ea.) 11.0 11.9 14.9 10.5 11.0 11.0 14.0 14.9

Phase 3 3 3 3 3 3 3 3

Amps LRA (Ea.) 90.0 118.0 118.0 71.0 64.0 90.0 92.5 118.0

No. 1 1 1 1 2 2 2 2

FLA (Ea.) 1.6 2.7 2.7 2.7 2.7 1.6 1.6 2.7

Phase 1 1 1 1 1 1 1 1

LRA (Ea.) 4.0 9.3 9.3 7.0 7.0 4.0 3.8 9.3

NOTE: 1. Electrical characteristics reflect nameplate values and are calculated in accordance with UL and ARI specifications.

Table ED-3 — Electrical Characteristics — Motors — Air Handler Standard Fan Motor Unit Model No. TWE050 TWE075 TWE100 TWE155 TWE200

Amps Volts 380/415 380/415 380/415 380/415 380/415

Phase 3 3 3 3 3

FLA 2.9 3.8 4.0 4.5 7.6

LRA 8.2 19.7 27.5 36.2 45.0

Phase 3 3 3 3 3

Oversized Fan Motor Amps FLA 1.8 4.0 5.3 6.9 9.0

LRA 21.6 27.5 37.5 39.2 65.1

Table ED-4 — Unit Wiring — Air Handler

46

Unit Model No.

Minimum Unit Operating Voltage Range

Maximum Fuse Circuit Ampacity

Size or Maximum Circuit Breaker

TWE050 TWE075 TWE100 TWE155 TWE200

380/415 380/415 380/415 380/415 380/415

4 5 5 6 10

15 15 15 15 15

SS-PRC003-EN

Electric Heat Data

Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — Air Handlers Heater Model No. BAYHTRL405A BAYHTRL410A BAYHTRL415A BAYHTRL425A BAYHTRL405A BAYHTRL410A BAYHTRL415A BAYHTRL425A BAYHTRL435A BAYHTRL405A BAYHTRL410A BAYHTRL415A BAYHTRL425A BAYHTRL435A BAYHTRM410A BAYHTRM420A BAYHTRM430A BAYHTRM450A BAYHTRM410A BAYHTRM420A BAYHTRM430A BAYHTRM450A

Heater kW Rating1 5.00 9.96 14.96 24.92 5.00 9.96 14.96 24.92 34.88 5.00 9.96 14.96 29.92 34.88 10.00 19.92 29.92 49.84 10.00 19.92 29.92 49.84

To Use with Unit

Control Stages 1 1 1 2 1 1 1 2 2 1 1 1 2 2 1 1 2 2 1 1 2 2

TWE050AD

TWE075AD

TWE100AD, TWE100BD

TWE155BD

TWE200BD

Minimum Circuit Ampacity 2 11 17 24 37 12 18 25 38 51 12 19 25 38 52 19 32 46 72 23 36 49 76

Maximum Fuse Breaker Size 2 15 20 25 40 15 20 25 40 60 15 20 25 40 60 20 35 50 80 25 40 50 80

1. kW ratings are at 400v for 3 phase, 400v air handlers 2 2 Voltage Voltage For other than rated voltage, ampacity = x Rated Capacity and kW = Rated kW. Rated Voltage Rated Voltage 2. Any power supply and circuits must be wired and protected in accordance with local codes. MCA and Maximum Fuse Size is based on 400V. 3. Field wire must be rated at least 167°F (75°C). 4. Field wire must be rated at least 194°F (90°C).

(

SS-PRC003-EN

)

(

)

47

Jobsite Connections Wiring shown with dashed lines is to be furnished and installed by the customer. All customer- supplied wiring must be copper only and must conform to local electrical codes. NOTE: 1. When electric heater accessory is used, single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only. TTA050/TWE050A Field Wiring: A — 3 power wires. Line voltage for 3 phase, 2 wires for single phase. B — 3 power wires. Line voltage for 3 phase, 2 wires for single phase. C — Cooling only thermostat: 3 wires, 24 volts. — One-stage electric heat: add 1 additional wire, 24 volts. — Two-stage electric heat: add 2 additional wires, 24 volts. D — 2 wires, 24 volts. (2) TTA050/TWE100B Field Wiring: A — 3 power wires. Line voltage for 3 phase, 2 wires for single phase. B — 3 power wires. Line voltage for 3 phase, 2 wires for single phase. C — Cooling only thermostat: 4 wires, 24 volts. — One-stage electric heat add 1 additional wire, 24 volts. — Two-stage electric heat: add 2 additional wires, 24 volts. D — 2 wires, 24 volts to outdoor section ‘’A’’ — 2 wires, 24 volts to outdoor section ‘’B’’

48

TTA075A/TWE075A; TTA085/TWE075A; TTA085/TWE100A; TTA100A/TWE100A Field Wiring: A — 3 power wires, line voltage. B — 3 power wires, line voltage for 3 phase; 2 wires for single phase. C — Cooling only thermostat: 3 wires, 24 volts. — One-stage electric heat: add 1 additional wire, 24 volts. — Two-stage electric heat: add 2 additional wires; 24 volts. D — 4 wires, 24 volts.

D — 5 wires, 24 volts.

TTA100B/TWE100B Field Wiring: A — 3 power wires, line voltage. B — 3 power wires, line voltage for 3 phase; 2 wires for single phase. C — Cooling only thermostat: 4 wires, 24 volts. — One-stage electric heat: add 1 additional wire, 24 volts. — Two-stage electric heat: add 2 additional wires, 24 volts.

(2)TTA075A/TWE155B; (2) TTA100A/TWE200B Field Wiring: A — 3 power wires, line voltage. B — 3 power wires, line voltage. C — Cooling only thermostat: 4 wires, 24 volts. — One-stage electric heat: add 1 additional wire, 24 volts. — Two-stage electric heat: add 2 additional wires, 24 volts. D — 6 wires, 24 volts.

TTA125B/TWE155B; TTA155B/TWE155B; TTA200B/TWE200B; TTA155C/TWE155B Field Wiring A — 3 power wires, line voltage B — 3 power wires, line voltage C — Cooling only thermostat: 4 wires, 24 volts. — One-stage electric heat: add 1 additional wire, 24 volts. — Two-stage electric heat: add 2 additional wires, 24 volts. D — 5 wires, 24 volts.

SS-PRC003-EN

Typical Wiring

Air Handler

Air Handler Typical wiring diagram. For specific wiring, see individual Service Facts.

SS-PRC003-EN

49

Typical Wiring

Condensing Unit

Condensing Unit — Single Compressor Typical wiring diagram. For specific wiring, see individual Service Facts.

50

SS-PRC003-EN

Typical Wiring

Condensing Unit

Condensing Unit — Single Compressor

SS-PRC003-EN

51

Typical Wiring

Condensing Unit

Condensing Unit — Dual Compressor Typical wiring diagram. For specific wiring, see individual Service Facts.

52

SS-PRC003-EN

Typical Wiring

Condensing Unit

Condensing Unit — Dual Compressor

C757164P01

SS-PRC003-EN

53

Dimensional Data

Figure DD-1 — TTA075 Condensing Units

All dimensions are in inches and millimeters.

Note 1: Minimum Clearance for proper operation is 36 inches (914) from walls, shrubbery, privacy fences, etc. Minimum clearance between adjacent units is 72 inches (1829).

54

SS-PRC003-EN

Dimensional Data

Figure DD-2 — TTA085A and 100A Condensing Units

All dimensions are in inches and millimeters.

Note 1: Minimum Clearance for proper operation is 36 inches (914) from walls, shrubbery, privacy fences, etc. Minimum clearance between adjacent units is 72 inches (1829).

SS-PRC003-EN

55

Dimensional Data

Figure DD-3 — TTA100C Condensing Units

All dimensions are in inches and millimeters.

Note 1: Minimum Clearance for proper operation is 36 inches (914) from walls, shrubbery, privacy fences, etc. Minimum clearance between adjacent units is 72 inches (1829).

56

SS-PRC003-EN

Dimensional Data

Figure DD-4 — TTA100B and TTA125B Condensing Units

All dimensions are in inches and millimeters.

SS-PRC003-EN

57

Dimensional Data

Figure DD- 5— TTA155B Condensing Unit

All dimensions are in inches and millimeters.

Note 1: Minimum Clearance for proper operation is 36 inches (914) from walls, shrubbery, privacy fences, etc. Minimum clearance between adjacent units is 72 inches (1829).

58

SS-PRC003-EN

Dimensional Data

Figure DD-6 — TTA155C Condensing Units

All dimensions are in inches and millimeters.

Note 1: Minimum Clearance for proper operation is 36 inches (914) from walls, shrubbery, privacy fences, etc. Minimum clearance between adjacent units is 72 inches (1829).

SS-PRC003-EN

59

Dimensional Data

Figure DD-7 — TTA200B Condensing Unit

All dimensions are in inches and millimeters.

Note 1: Minimum Clearance for proper operation is 36 inches (914) from walls, shrubbery, privacy fences, etc. Minimum clearance between adjacent units is 72 inches (1829).

60

SS-PRC003-EN

Dimensional Data

Figure DD-8 — TWE050A Air Handlers

All dimensions are in inches and millimeters.

Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit.

SS-PRC003-EN

61

Dimensional Data

Figure DD-9 — TWE075A Air Handlers

All dimensions are in inches and millimeters.

Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit.

62

SS-PRC003-EN

Dimensional Data

Figure DD-10 — TWE100A Air Handlers

All dimensions are in inches and millimeters.

Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit.

SS-PRC003-EN

63

Dimensional Data

Figure DD-11 — TWE100B Air Handlers

All dimensions are in inches and millimeters.

Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit.

64

SS-PRC003-EN

Dimensional Data

Figure DD-12 — TWE050A, 075A, 100A and TWE100B Air Handlers

All dimensions are in inches and millimeters.

Table DD-1 — Air Handler Dimensions — in. (mm) Model No. TWE050A TWE075A TWE100A TWE100B

SS-PRC003-EN

AA 35 5/8 (905) 45 1/8 (1146.2) 61 1/8 (1552.6) 61 1/8 (1552.6)

AB 12 1/16 (306.4) 16 (406.4) 16 (406.4) 16 (406.4)

AC 1 5/8 (41.3) 1 11/16 (42.9) 1 11/16 (42.9) 1 11/16 (42.9)

AD 32 1/4 (819.2) 41 15/16 (1065.2) 57 15/16 (1471.6) 57 15/16 (1471.6)

AE 2 15/16 (74.6) 6 5/8 (168.3) 6 5/8 (168.3) 6 5/8 (168.3)

AF 32 1/4 (819.2) 41 3/4 (1060.5) 57 13/16 (1468.4) 57 13/16 (1468.4)

AJ 7 13/16 (198.4) 7 (177.8) 7 (177.8) 7 (177.8)

AK 12 3/8 (314.3) 16 (406.4) 16 (406.4) 16 (406.4)

AL 34 9/16 (878) 36 7/8 (936.6) 36 7/8 (936.6) 36 7/8 (936.6)

65

Dimensional Data

Figure DD-13 — TWE155B Air Handlers

All dimensions are in inches and millimeters.

Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit.

66

SS-PRC003-EN

Dimensional Data

Figure DD-14 — TWE200B Air Handlers

All dimensions are in inches and millimeters.

Notes: 1. Length, Width, and Height Dimensions do not include 1/2” (12.7mm) access panel depth. 2. Removable drain pan and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration. Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning. Access plate must be reinstalled after sliding drain pan back into unit. 3. If periodic drain pan cleaning is required, allow room for partial removal of pan on drain connection end of unit.

SS-PRC003-EN

67

Dimensional Data

Figure DD-15 — TWE155B and 200B Air Handlers

All dimensions are in inches and millimeters.

Table DD-2 — Air Handler Dimensions — in. (mm) Model No. TWE155B TWE200B

A 77 1/4 (1962.2) 89 1/4 (2267)

B 1 3/16 (30.2) 1 11/16 (42.9)

C 48 (1219.2) 50 13/16 (1290.6)

D 11 7/16 (290.5) 11 1/2 (292.1)

E 18 (457.2) 20 1/8 (511.2)

F 3 3/8 (85.7) 3 1/16 (77.8)

G 35 1/16 (890.6) 39 1/8 (993.8)

H 73 7/8 (1876.4) 82 7/8 (2105)

J 3 3/4 (95.3) 4 9/16 (115.9)

P 2 7/8 (73) 4 /16 (122.2)

Q 35 1/16 (890.6) 1 39 /8 (993.8)

R 3 3/4 (95.3) 9 4 /16 (115.9)

S 35 1/16 (890.6) 1 39 /8 (993.8)

T 73 3/8 (1863.7) 7 82 /8 (2105)

Table DD-2 — Air Handler Dimensions — in. (mm) (Continued) Model No. TWE155B TWE240B

68

K 35 1/16 (890.6) 1 39 /8 (993.8)

L 2 13/16 (71.4) 7 4 /8 (123.8)

M 18 (457.2) 20 (508)

N 3 9/16 (90.5) 3 (76.2)

13

SS-PRC003-EN

Dimensional Data

Figure 16 — Electric Heater for TWE050, 075, 100 Air Handlers

All dimensions are in inches and millimeters.

Figure DD-17 — Electric Heater for TWE155 and 200 Air Handlers

SS-PRC003-EN

69

Dimensional Data

Table DD-3 — Discharge Plenum And Grille Dimensions — in. (mm) Model TWE050

Model No. BAYPLNM015

TWE075

BAYPLNM016

TWE100

BAYPLNM017

Figure DD-18 — Discharge Plenum and Grille

All dimensions are in inches and millimeters.

A B C 3715/16 2115/16 28 (963.6) (557.2) (711.2) 471/2 25 28 (1206.5) (635) (711.2) 1 63 /2 25 28 (1612.9) (635) (711.2)

Table DD-4 — Discharge Plenum And Grille Dimensions — in. (mm) For Use with Electric Heat Model TWE050

Model No. BAYPLNM025

TWE075

BAYPLNM026

TWE100

BAYPLNM027

TWE155

BAYPLNM028

TWE200

BAYPLNM029

A B 3715/16 2115/16 (963.6) (557.2) 471/2 25 (1206.5) (635) 1 63 /2 25 (1612.9) (635) 791/2 2711/16 (2019.3) (703.3) 921/2 307/16 (2349.5) (773.1)

C 29 (736.6) 29 (736.6) 29 (736.6) 35 (889) 35 (889)

Table DD-5 — Subbase Dimensions — in. (mm) Model TWE050

Model No. BAYBASE001

TWE075

BAYBASE002

TWE100

BAYBASE003

TWE155

BAYBASE004

TWE200

BAYBASE005

70

A 38 (965.2) 471/2 (1206.5) 631/2 (1612.9) 791/2 (2019.3) 921/2 (2349.5)

Figure DD-19 — Subbase B 22 (558.8) 25 (635) 25 (635) 275/8 (701.7) 307/16 (773.1)

SS-PRC003-EN

Dimensional Data

Figure DD-20 — Hot Water Coil

All dimensions are in inches and millimeters.

3.00 (76 mm) DIA. HOLE FOR 2” (50.8 mm) NPT SUPPLY

3.00 (76 mm) DIA. HOLE FOR 2” (50.8 mm) NPT RETURN

329/32 99 mm

BAYWATR017

3.00 (76 mm) DIA. HOLE FOR 2” (50.8 mm) NPT SUPPLY

3.00 (76 mm) DIA. HOLE FOR 2” (50.8 mm) NPT RETURN

BAYWATR018 BAYWATR019 BAYWATR020 BAYWATR021

Table DD-6 — Hot Water Coil Dimensions — in. (mm) Model TWE050

Accessory No. BAYWATR017

TWE075

BAYWATR018

TWE100

BAYWATR019

TWE155

BAYWATR020

TWE200

BAYWATR021

SS-PRC003-EN

A 38 (965) 4719/32 (1209) 6319/32 (1615) 7921/32 (2023) 9221/32 (2353)

B 223/32 (561) 255/32 (639) 255/32 (639) 2725/32 (706) 3019/32 (777)

C 135/8 (346) 1519/32 (396) 1519/32 (396) 147/16 (367) 163/8 (416)

D 5 (127) 5 (127) 6 (152) 6 (152) 7 (178)

E 9 (229) 1027/32 (275) 117/8 (302) 153/32 (383) 1423/32 (374)

F 141/32 (356) 171/8 (435) 171/8 (435) 193/4 (502) 229/16 (573)

G 14 (356) 14 (356) 16 (406) 16 (406) 18 (457)

H 26 (660) 30 (762) 36 (914) 51 (1295) 64 (1626)

J 12 (305) 18 (457) 18 (457) 18 (457) 18 (457)

K 6 (152) 27 8 /32 (225) 1327/32 (352) 147/32 (361) 147/32 (361)

L 41/32 (102) 83/32 (206) 83/32 (206) 615/16 (176) 87/8 (225)

N 227/32 (72) 227/32 (72) 227/32 (72) 17/8 (48) 33/4 (95)

M 81/32 (204) 103/8 (264) 103/8 (264) 99/16 (243) 99/16 (243)

MM 109/16 (268) 77/8 (200) 77/8 (200) 71/16 (179) 71/16 (179)

71

Dimensional Data

Figure DD-21 — Steam Coil

All dimensions are in inches and millimeters.

Table DD-7 — Steam Coil Dimensions — in. (mm) Model TWE050

Accessory No. BAYWATR012

TWE075

BAYWATR013

TWE100

BAYWATR014

TWE155

BAYWATR015

TWE200

BAYWATR016

72

A 38 (965.2) 475/8 (1209.7) 635/8 (1616.1) 795/8 (2022.5) 925/8 (2352.7)

B 221/8 (562) 253/16 (639.8) 253/16 (639.8) 2713/16 (706.4) 305/8 (777.9)

C D E F 133/16 5 9 141/16 (335) (127) (228.6) (357.2) 1913/16 5 107/8 171/8 (503.2) (127) (276.2) (435) 1913/16 6 117/8 171/8 (503.2) (152.4) (301.6) (435) 2415/16 6 151/16 193/4 (633.4) (152.4) (382.6) (501.7) 257/8 7 143/4 229/16 (657.2) (177.8) (374.7) (573.1)

G 14 (355.6) 14 (355.6) 16 (406.4) 16 (406.4) 18 (457.2)

H 103/8 (263.5) 133/8 (339.7) 133/8 (339.7) 181/2 (469.9) 191/2 (495.3)

J 113/8 (288.9) 113/8 (288.9) 111/8 (282.6) 111/8 (282.6) 121/6 (309)

K 2 (50.8) 21/2 (63.5) 21/2 (63.5) 21/2 (63.5) 21/2 (63.5)

L M N 11/2 26 12 (38.1) (660.4) (304.8) 2 30 18 (50.8) (762) (457.2) 2 36 18 (50.8) (914.4) (457.2) 2 51 18 (50.8) (1295.4) (457.2) 2 64 18 (50.8) (1625.6) (457.2)

P Q 6 27/8 (152.4) (73) 87/8 27/8 (225.4) (73) 133/8 27/8 (339.7) (73) 143/16 17/8 (360.4) (47.6) 143/16 33/4 (360 .4) (95.3)

R 93/4 (247.7) 93/4 (247.7) 93/4 (247.7) 93/4 (247.7) 107/8 (276.2)

SS-PRC003-EN

Weights

Table W-1 — Unit and Corner Weights — lb (kg) Unit Model No. TTA075A TTA100A TTA100B TTA100C TTA125B TTA155B TTA155C TTA200B

Shipping Maximum — lb (kg) 366 (166.0) 444 (201.4) 514 (233.1) 483 (219.1) 542 (245.9) 744 (337.5) 745 (337.9) 915 (415.0)

Net Maximum — lb (kg) 322 (146.1) 390 (176.9) 460 (208.7) 428 (194.1) 488 (221.4) 668 (303.0) 660 (299.4) 830 (376.5)

1 105 (47.6) 134 (60.8) 153 (69.4) 139 (63.0) 153 (69.4) 192 (87.1) 216 (98.0) 240 (108.9)

Corner Weights 2 3 80 59 (36.3) (26.8) 95.5 66.5 (43.3) (30.2) 145 79 (65.8) (35.8) 125 78 (56.7) (35.4) 156 90 (70.8) (40.8) 192 142 (87.1) (64.4) 211 115 (95.7) (52.2) 232 176 (105.2) (79.8)

4 78 (35.4) 94 (42.6) 83 (37.7) 86 (39.0) 89 (40.4) 142 (64.4) 118 (53.5) 182 (82.6)

Table W-2 — Accessory Weights — Net lb (kg) Unit Model No. TTA075A TTA100A TTA100B TTA125B TTA155D TTA155C TTA200B

RIS Isolators 2 (.9) 2 (.9) 2 (.9) 2 (.9) 2 (.9)

Steel Spring Isolators 12 (5.4) 12 (5.4) 12 (5.4) 12 (5.4) 12 (5.4)

Anti Short Cycle Timer 1 (.5) 1 (.5) 1 (.5) 1 (.5) 1 (.5)

Coil Guard 8 (3.6) 11 (5) 20 (9.1) 22 (10) 34 (15.4)

Thermostats 1 (.5) 1 (.5) 1 (.5) 1 (.5) 1 (.5)

Low Ambient 23 (10.4) 23 (10.4) 23 (10.4) 23 (10.4) 23 (10.4)

TTA155, 200 TTA075, 100, 125

SS-PRC003-EN

73

Weights

Table W-3 — Air Handlers, Coils, And Corner Weights — lb (kg)1 Unit Model No. TWE050 TWE075 TWE100 TWE125 TWE200

Shipping Maximum (lb) 298 (135) 388 (176) 473 (214.6) 754 (342) 886 (401.9)

Net Maximum (lb) 262 (118.9) 346 (157) 419 (190.1) 690 (313) 820 (372)

#1 59 (26.8) 79 (35.9) 107 (48.5) 173 (78.5) 204 (92.5)

Corner Weights — Vertical #2 #3 59 59 (26.8) (26.8) 79 79 (35.9) (35.9) 107 107 (48.5) (48.5) 173 173 (78.5) (78.5) 204 204 (92.5) (92.5)

#4 59 (26.8) 79 (35.9) 107 (48.5) 173 (78.5) 204 (92.5)

A 54 (24.5) 77 (35) 102 (46.3) 174 (79) 185 (84)

Corner Weights — Horizontal B C 64 64 (29) (29.03) 84 81 (38.1) (36.7) 113 113 (51.3) (51.3) 156 190 (70.8) (86.2) 228 221 (103.4) (100.3)

D 54 (24.5) 73 (33.1) 102 (46.3) 170 (77.1) 179 (81.2)

Note: 1. If application requires steam or hot water heating coils, field supplied isolators must be utilized.

Vertical TWE050, 075, 100

Vertical TWE155, 200

Horizontal TWE050, 075, 100

Horizontal TWE155, 200

Table W-4 — Accessory Weights (Net lb)

Unit Model No. TWE050 TWE075 TWE100 TWE155 TWE200

Discharge Plenum And Grille1 58 (26.3) 73 (33.1) 92 (41.7) 124 (56.3) 145 (65.8)

Discharge Plenum And Grille2 93 (42.2) 123 (55.8) 156 (70.8) 230 (104.3) 264 (119.8)

Return Air Grille 3 (1.4) 5 (2.3) 7 (3.2) 10 (4.5) 12 (5.4)

Electric Heat Min. Max. 32/43 (14.5/19.5) 27/45 (12.3/20.4) 27/45 (12.3/20.4) 79/100 (35.8/45.4) 79/100 (35.8/45.4)

Subbase 14 (6.4) 19 (8.6) 23 (10.4) 27 (12.3) 31 (14.06)

Oversized Motor 31 (14.1) 48 (21.8) 50 (22.7) 80 (36.3) 88 (40)

RIS Isolator Floor Mount 2 (.9) 2 (.9) 2 (.9) 2 (.9) 2 (.9)

RIS Isolator Suspended Mount 9 (4) 6 (2.7) 7 (3.2) 7 (3.2) 9 (4)

Steel Spring Isolator Floor Mount 12 (5.4) 12 (5.4) 12 (5.4) 12 (5.4) 12 (5.4)

Steel Spring Isolator Suspended Mount 6 (2.7) 6 (2.7) 6 (2.7) 6 (2.7) 6 (2.7)

Note: 1. For use when no heat is supplied. 2. For use with electric heat.

74

SS-PRC003-EN

Mechanical Specifications General Units shall be assembled on heavy gauge steel mounting/lifting rails and shall be weatherproofed. Units shall include a hermetic scroll or reciprocating compressor(s), plate fin condenser coil, fans and motors, controls, and holding charge of nitrogen. Operating range shall be between 115°F (46.1°C) and 35°F (1.7°C) in cooling as standard from the factory. Units shall be rated in accordance with ARI Standard 210/240, 340/360 or 365. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Units surface shall be tested 500 hours in salt spray test. Units shall have removable end panels which allow access to all major components and controls. Refrigeration System – Single Compressor TTA075A,TTA100A units shall have a single refrigeration circuit. Each refrigeration circuit has an integral subcooling circuit. A refrigeration filter drier shall be provided as standard.The units shall have both a liquid line and suction gas line service valve with gauge port.TTA075A,TTA100A units shall have one direct-drive, hermetic scroll compressor with centrifugal oil pump providing positive lubrication to moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Crankcase heater, discharge line thermostat, and currentsensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low vibration and noise by having no suction and discharge valves. External high and low pressure cutout devices shall be provided. Evaporator defrost control provided in indoor blower coil shall prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered.

SS-PRC003-EN

Refrigeration System – Dual Compressor TTA100B,TTA125B,TTA155B,TTA200B units shall have two separate and independent refrigeration circuits. Each refrigeration circuit shall have an integral subcooling circuit. A refrigeration filter drier shall be provided as standard. Units shall have both a liquid line and suction gas line service valve with gauge port. TTA100B,TTA125B, units shall have two Trane direct-drive, hermetic reciprocating compressors with centrifugal oil pump and provide positive lubrication to all moving parts. Reciprocating compressor shall have internal spring isolation and sound muffling to minimize vibration transmission and noise. TTA155B,TTA200B units shall have two Trane direct-drive, hermetic scroll compressors with centrifugal oil pump and provide positive lubrication to all moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Crankcase heater, discharge line thermostat, and current-sensitive motor overloads shall be included for maximum protection. Scroll compressor shall provide inherently low vibration and noise by having no suction and discharge valves. External high and low pressure cutout devices shall be provided. Evaporator defrost control provided in indoor blower coil shall prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered.

Condensing Units Refrigeration System — Dual Manifolded Compressors TTA 100C andTTA155C units shall have a single refrigeration circuit with an integral subcooling circuit. A refrigeration filter drier shall be provided as standard. Units shall have both a liquid line and suction gas line service valve with gauge port. The units shall have two scroll compressors manifolded together. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Crankcase heater, discharge line thermostat, and current-sensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low vibration and noise by having no suction and discharge valves. External high and low pressure cutout devices shall be provided. Evaporator defrost control provided in the indoor blower coil shall prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered. Condenser Coil Coils shall be internally finned or smooth bore 3/8” (10 mm) copper tubes mechanically bonded to a configured aluminum plate fin as standard. Coil shall be factory pressure and leak tested to 420 psig (2,899 kPa) air pressure. Metal grilles with PVC coating for coil protection is optional. Condenser Fan And Motor(s) Direct-drive, statically and dynamically balanced, 26 or 28-inch (660 or 711 mm) propeller fan(s) with aluminum blades and electro- coated steel hubs shall be used in draw-thru vertical discharge position. Either permanently lubricated totally enclosed or open construction motors shall be provided and shall have built-in current and thermal overload protection. Motor(s) shall have be either ball or sleeve bearing type.

75

Mechanical Specifications Controls Condensing units shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Control wiring shall be 24-volt control circuit which includes fusing and control transformer. Units shall provide external location for mounting a fused disconnect device.Time delay timers to prevent compressors in dual compressor units from simultaneous start-up and anti- recycle timers are available as optional accessories. Low Ambient Operation Standard units shall start and operate to approximately 35°F (1.7°C) when matched withTrane air handlers and coils. Optional head pressure control accessory permits operation to 0°F (17.8°C). Accessories Low Ambient Head Pressure Control —This accessory shall modulate the RPM of unit outdoor fan motor in response to outdoor ambient temperature and unit head pressure. Accessory provides unit cooling operation to outdoor temperatures of 0° F (-17.8° C). Vibration Isolation Packages —This accessory shall reduce transmission of noise and vibration to building structures, equipment, and adjacent spaces. Packages shall be available in either neoprene-in-shear or spring-flex types.

76

Condensing Units Hot Gas Bypass Kit —This accessory shall be available to provide capacity modulation. Time Delay Relay —This accessory shall prevent compressors in dual compressor unit from combine on line simultaneously.Time shall be 24-volt, 60 cycle, with four minute timing period. Anti-Short-Cycle Timer —This accessory shall prevent rapid on-off compressor cycling in light load conditions by not allowing compressor to operate for 5-7 minutes upon shutdown.This accessory shall consist of a 24-volt, solid state timing device with either 5 or 7 minute fixed-off timing period. Condenser Coil Guard — Metal grille with PVC coating shall be provided to alleviate coil damage. Factory Installed Accessories Black Epoxy Coated Condenser Coil — This option is designed to provide corrosion protection of air cooled condenser coils for seacoast application.The black epoxy coil protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock.The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B177.

SS-PRC003-EN

Mechanical Specifications General Air handler units shall be completely factory assembled including coil, condensate drain pan, fan motor(s), filters, and controls in an insulated casing that can be applied in either vertical or horizontal configuration. Units shall be rated and tested in accordance with ARI Standard 210, 240, 360. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Casing is completely insulated with fireretardant, permanent, odorless, glass fiber material. Knockouts shall be provided for unit electrical power and refrigerant piping connections. Captive screws shall be standard on all access panels. Refrigeration System TheTWE050A,TWE075A,TWE100A units shall have a single refrigeration circuit and theTWE050B,TWE100B,TWE155B, TWE200B units shall have dual refrigeration circuits. Each refrigeration circuit is controlled by a factory installed thermal expansion valve. Evaporator Coil Configured aluminum fin surface shall be mechanically bonded to 3/8” (10 mm) internally enhanced copper tubing and factory pressure and leak tested at 375 psig (2,586 kPa). Coil is arranged for draw-thru airflow and shall provide condensate drain pan constructed of PVC plastic and provide external connections on either side of the unit.

SS-PRC003-EN

Evaporator Fan Double inlet, double width, forward curved, centrifugal-type fan(s) with adjustable belt drive shall be standard. Thermal overload protection shall be standard on motor. Fan and motor bearings shall be permanently lubricated. Oversized motors shall be available as an option for high static application. Controls Magnetic evaporator fan contactor, low voltage terminal strip, check valve(s), and single point power entry shall be included. All necessary controls shall be factory-installed and wired. Evaporator defrost control shall be included to prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered. Filters One inch, throwaway filters shall be standard onTWE050A,TWE050B, TWE075A,TWE100A andTWE100B model air handlers. Filters shall be accessible from the side coil access panel. Filter rack can be field converted to two-inch capability.Two-inch throwaway filters shall be standard on TWE155B andTWE200B models. Accessories Electric Heaters — Approved electric heat modules shall be available for installation directly on fan discharge. Electric heaters shall be available in a wide range of capacities with one or two-stage control, single-point electric power connection and terminal strip connections. Electric heater elements shall be constructed on heavy-duty nickel chromium elements internally wye connected on 480 volt, three phase. Each 480 volt heater shall have automatic line break high limit controls.

Air Handlers Discharge Plenums and Grilles — Accessory discharge plenums shall be available for vertical, free discharge applications. Plenums shall be constructed of heavy-gauge, zinc coated, galvanized steel finished with baked enamel to match the air handler unit. Grilles shall be satin finished aluminum and have four-way adjustable louvers. Return Air Grilles — Accessory return air grille shall be provided for vertical front, free return applications. Grilles shall be installed in place of the front lower side panel. Grille shall be satin finished aluminum with non-adjustable louvers. Mounting Subbase —This accessory shall be available for vertical floor mount configurations. Subbase shall be constructed of heavy gauge, zinc coated, galvanized steel with baked enamel finish to match air handler unit. Subbase is required in the vertical air flow application for condensate drain trapping and when isolators are required. Vibration Isolators —This accessory shall reduce transmission of noise and vibration to building structures, equipment, and adjacent spaces. Packages shall be available in either neoprene-in shear or spring-flex types in floor or suspended mountings. Oversized Motors — Field installed oversized motors shall be available for high static pressure applications. Control Options Standard Indoor Thermostats —Two stage heating and cooling operation or one stage heating and cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Setback Thermostat —The option shall provide heating setback and cooling setup with 7-day programming capability.

77

78

79

Literature Order Number

TheTrane Company An American Standard Company www.trane.com For more information contact your local office or e-mail us at [email protected]

SS-PRC003-EN

File No.

PL-UN-SS-PRC003-EN-12-00

Supersedes

SS-PRC003-EN 07-00

Stocking Location

Inland - LaCrosse

SinceTheTrane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.